Trane VAV VV550 LonTalk Programming Guide

Installation Operation Programming
VAV VV550 LonTalk Controller
May 2010
VAV-SVP01A-E N
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage-only
accidents.
WARN ING
This equipment is to be serviced/installed by qualified personnel ONLY. Under NO circumstances should an unqualified person service/install it. Servicing/installing this equipment is a job requiring specific knowledge and MUST be left to a professional. It involves working with hazardous components that are potentially life threatening if not handled properly. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
WARN ING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
© 2010 Trane All rights reserved VAV-SVP01A-EN
Warnings, Cautions and Notices
WARN ING
Electrocution and Fire Hazards with Improperly Installed and Grounded Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. All field wiring MUST be performed by qualified personnel. Failure to follow these requirements could result in death or serious injury.
Overview of Manual
Note: One copy of this document ships inside the control panel of each unit and is customer
property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for delivered air systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
VAV-SV P01A-E N 3
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit Control Module VAV VV550 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
VV550 Enhancements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VV550 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Shipping & Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Data Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VAV Start Up/Check Out Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
VV550 Pre-Power Check-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
VV550 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Light Emitting Diode (LED) Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Communication Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wireless Zone Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
VAV VV550 Controller Programming and Operation . . . . . . . . . . . . . . . . . . . . . . 42
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Accessing Rover/Comm5 LonTalk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
VV550 Controller Device Home Tabs: At a Glance . . . . . . . . . . . . . . . . . . . . . 44
Entering and Exiting the Service Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Overriding VAVs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
VAV VV550 Controller Device Home Tabs: Instructions . . . . . . . . . . . . . . . . . . . . 54
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Setpoints Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Unit Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Setup Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Inputs Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Outputs Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Test Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Other Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Overrides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Sequence of Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4 VAV-SVP01A-EN
Occupancy Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Space Temperature Control: Single Duct Units . . . . . . . . . . . . . . . . . . . . . . . . 69
Space Temperature Control: Fan-Powered Units . . . . . . . . . . . . . . . . . . . . . . 72
Ventilation Flow Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Flow Tracking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Air and Water Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Air Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Rover Air and Water Balancing Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Chapter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Diagnosing the Problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Troubleshooting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Trane/Honeywell Proportional Valve Check Out Procedures . . . . . . . . . . . 105
VAV-SV P01A-E N 5

General Information

Chapter Overview

This chapter contains information about the following:
Unit Control Module VAV VV550 Controller
Specifications
VAV VV550 Controller Enhancements
VAV VV550 Controller Features
Shipping & Storage
Data Lists

Unit Control Module VAV VV550 Controller

The VV550 is a microprocessor-based, Direct Digital Controller (DDC) for the (Variable Air Volume) VAV terminal unit. Units have been made with either pneumatic, analog electronic, or microprocessor controls (DDC VAV). This manual discusses only terminal units with Comm 5 VAV VV550 DDC Controller. Factory installed DDC/VAV controls are available with all single duct terminal units, dual duct units, as well as parallel fan-powered and series fan-powered units. Two VAV VV550 Controllers are required for dual duct units (one for the heating duct and one for the cooling duct) and another application requiring to controllers is Flow tracking (one unit controller is programmed from the factory with the Space temperature program and the other is downloaded with the Flow tracking program.
The VAV VV550 Controller can be configured from the factory with three different application programs. The VAV VV550 Controller programmed for space temperature control modulates a VAV's damper blade based on a zone temperature, measured airflow, and set points to continuously control conditioned air delivery to the space. The volume of incoming air is monitored and the damper adjusts to provide accurate control independent of the duct pressure. The damper modulates between operator set points depending on space conditions. Additionally, fan and heat outputs may be energized depending on the application.
The VAV VV550 Controller programmed for ventilation flow control is applied to a VAV terminal and used to temper cold outdoor air (OA) that is brought into a building for ventilation purposes. The tempered air is intended to supply an air-handling unit (AHU), which provides comfort control to the zones it is serving. The VAV terminal supplies the correct amount of ventilation air and, when reheat is added, tempers the ventilation air to reduce the load on the air handler by sensing the discharge air temperature of VAV unit.
The VAV VV550 Controller programmed for Flow Tracking Control (FTC) has two VAV VV550 Controllers working together to provide flow tracking control. One VAV VV550 controller is programmed from the factory with the Space temperature program and the other is downloaded with the Flow tracking program. The space temperature controller airflow output is bound to the flow tracking controller airflow setpoint input. The flow tracking controller adds the configured airflow tracking offset (positive or negative) to the airflow setpoint (communicated airflow setpoint) and controls the airflow to this setpoint.
The VAV VV550 Controller utilizes an FTT-10A Free Topology transceiver, which supports non­polarity sensitive, free topology wiring, which allows the system installer to utilize star, bus, and loop architectures. Available inputs include a twisted/shielded communication link, zone sensor, auxiliary temperature sensor (optional), and Occupy/Unoccupied Sensor (optional), and 24VAC power.
6 VAV-SVP01A-EN

Specifications

General Information
Power Requirements
The UCM VV550 requires 18-32 Vac (24VAC nominal), 50/60 Hz, and up to 50 VA, depending on the number of heat outputs (stages), which consume 10 VA each.
Operating Environments - VAV VV550 Controller
32° to 140°F (0° to 60°C), 5% to 90% relative humidity, non-condensing
Storage Environments - VAV VV550 Controller
-40° to 185°F (-40° to 85°C), 5% to 90% relative humidity, non-condensing
From 5 to 95% non-condensing Relative humidity: From 5 to 95% non-condensing
Analog Inputs
Space temperature; thermistor: 10 kΩ@ 77°F (25°C) From 14 to 122°F (-10 to 50°C) Space setpoint; potentiometer: 1 kΩ From 50 to 90°F (-10 to 32.2°C) Primary/discharge air temperature; thermistor: 10 kΩ@ 77°F (25°C) From -40 to 212°F (-40 to 100°C) Primary air flow; pressure transducer: From 0 to 2 in. water (0 to 498 Pa)
Binary Input
Occupancy or generic (dry contact)
Binary Outputs
Air valve close: maximum output rating: 12 VA Air valve open: maximum output rating: 12 VA Heat stage 1: maximum output rating: 12 VA Heat stage 2: maximum output rating: 12 VA Heat stage 3/Fan on/off: maximum output rating: 12 VA
Agency Listings/Compliance
VAV VV550 Controller: UL 873 and CSA C22.2 No. 24-93: Temperature Indicating and Regulating Equipment VAV VV551 Controller: UL-916-PAZX-energy management CUL-C22.2-signal devices-Canada UL 94-5V (UL flammability rating for plenum use) FCC Part 15, Class A CE marked
Mounting
Typically, the VAV VV550 Controller is factory installed. However, the VAV VV550 Controller is available with retrofit kits, in which case it must be field installed, and it’s named VV551.
Tracer Summit and VV550 Communications Link Wiring
Use 22 AWG Level 4 unshielded communication wire for most Comm5 installations. Limit Comm5 links to 4,500 ft and 60 devices maximum (without a repeater). Use one repeater for an additional 4,500 ft, 60 devices, and 8 communication stubs. Refer to Chapters 2 and 3 for further information about wire selection.
VAV-SV P01A-E N 7
General Information

VV550 Enhancements

Controller Interface Flexibility
VV550 controller allows VAV units to communicate on a Trane Comm5 or LonTalk. This controller works in standalone mode, peer-to-peer with one or more other units, or when connected to a Trane Tracer Summit or a 3rd party building automation system that supports LonTalk.
Manual Test Function
The VV550 controller includes a manual test button that allows the field technician to manually exercise the outputs of the controller. This feature is simple enough for the electrician to use to check valve operation. Though this feature is standard on other Comm5 controllers, the feature is not available on the VAV VV550 Controller.
Flow Tracking
The VV550 controller has been designed with the ability to be applied in flow tracking applications. This allows the controller to pair with one of its peers to mirror the flow if that lead box, with or without an offset (positive or negative static pressure as desired).
Ventilation Flow Control w/ Tempering
The VV550 controller has been designed with the ability to be applied in ventilation flow control applications. These applications pair a fresh air unit with ventilation boxes to provide fresh (tempered) air to a floor/area. This feature also includes a freeze protection sequence to protect the hot water reheat coil from low supply air temperatures.
Auto-commissioning Sequence
The VV550 controller has been designed with an auto-commissioning sequence. With a discharge air temperature sensor, this feature exercises the air valve, fan, and heat in the box and records the temperature before and after the action. This allows the installer to more easily checkout the operation of the box and commission by exception.
Automatic Calibration
The VV550 controller has been designed to automatically calibrate the flow transducer each time the box transitions to unoccupied. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which case Tracer Summit can be used to initiate/ schedule calibration.
Temporary Heat (Construction Mode)
Upon reset (and power-up) if the controller does not detect a valid space temperature the controller will provide temporary heat by driving the air valve to the heating maximum position. Of course, the box will only provide heat if hot air is being provided by the air-handling unit.
Local versus Remote Reheat Flexibility
The controller can be configured to have local and/or remote heat. Plus, configuration flexibility is offered that allows the installer to select whether local or remote heat has priority.
Zone Sensor Air Balancing
When applied with a Trane zone sensor module that includes a setpoint thumbwheel and ON and CANCEL buttons, the controller offers a zone sensor air-balancing feature. This feature allows the balancing contractor to drive the box to either its minimum or maximum flow setting by turning the setpoint thumbwheel on the zone sensor module. Then, the balancing contractor can calibrate the flow reading by pressing the ON (adjusts the reading upwards) or CANCEL (adjusts the reading downwards) buttons on the zone sensor module.
8 VAV-SVP01A-EN
General Information
Flash Download
The VAV controller has been designed with flash memory. This allows us the option of upgrading the controller in the field (features, corrections to defects) without changing out the controller.
Air/Water Balancing Application
An air/water balancing application is available in Rover that simplifies the startup, checkout and balancing of VAV systems. This application is specifically designed for the balancing contractor.
Service Pin from the Trane Zone Sensor
Several Comm5 installation and commissioning scenarios have the technician pressing the "service" button on the controller. By doing so, a service pin message is broadcast and received by either the Rover service tool or by Tracer Summit (depending on the scenario). Because access to the service button on the controller is often difficult, functionality has been included in the controller that allows the technician to press and hold the ON button on the zone sensor to replicate a service button press.
Trane Controller Compatibility
The VV550 is a Comm5 controller. As such, the controller is compatible with the latest generation of Trane controls. This allows the VV550 controller to exist on the same communication wire as the rest of our Comm5 controllers and share data with them as required. Additional inputs and outputs can easily be added to the same communication link (Tracer MP503) for any required auxiliary functions. In the past the cost of adding additional inputs and outputs (Comm4 link by way of a UPCM) was much less cost-effective.
Drive Min and Max from Zone Sensor
When applied with a Trane zone sensor module that includes a thumbwheel setpoint, the VV550 controller can easily be overridden to minimum and maximum flow. By simply turning the thumbwheel to "*" (end of range in one direction) the controller drives the air valve to the minimum cooling flow setpoint. Similarly, turning the thumbwheel to the and "**" (end of range in the other direction) the controller drives the air valve to the maximum cooling flow setpoint.

VV550 Features

Auto-commissioning Report (Tracer Summit)
Tracer Summit v15 and greater includes an auto-commissioning report that extracts and formats the commissioning data for each VAV controller. This commissioning report is valuable both for the installer and for the owner. The feature enables the system to be commissioned by exception -- a benefit for the installer. The feature also can be used as validation -- valuable to the owner.
Simpler VAS
Tracer Summit v15 includes a new VAV Air System (VAS) specifically designed for Comm5 controllers. This new VAS was designed to be much simpler to understand and setup compared to the existing (Comm3/4) VAS.
Static Pressure Optimization
As a part of the standard application, VAS calculates the duct static pressure setpoint based on the most open VAV box. Until Tracer Summit v15, this feature was provided by way of field custom programming.
Ventilation Optimization
As a part of the standard application, the VAV system has the ability to calculate the ventilation setpoint for the air-handling unit. In addition, the VV550 controller has a ventilation ratio limit feature that automatically increases airflow to maintain the required ventilation while operating
VAV-SV P01A-E N 9
General Information
within system limits for outside air percent concentrations in the supply air stream. Until Tracer Summit v15, this feature was provided by way of field custom programming.
CO2 Based Demand Control Ventilation
As a part of the standard application, the VAV system has the ability to calculate the ventilation setpoint for the air-handling unit based on the CO2 in one or more spaces. Until Tracer Summit v15, this feature was provided by way of field custom programming. Plus, functionality was added to the VV550 controller to support this feature (as standard). Providing the equivalent functionality with the current VAV controller would require lots of custom programming.
Ventilation Flexibility
Ventilation can be managed in the following ways:
Fixed occupancy ventilation setpoint
Scheduled (or otherwise calculated) ventilation setpoint
Occupancy sensor to switch between normal and reduced ventilation
•CO
Temperature Statistics
As a part of the standard application, VAS calculates the minimum space temperature (and source), maximum space temperature (and source), and the average space temperature. Until Tracer Summit v15, this feature was provided by way of field custom programming.
sensor for demand-controlled ventilation
2
2
Note: CO
sensor input not available on VV550.
VAV VV550 Controller Compatibility
The VAV VV550 Controller is designed with LonWorks technology and will be LonMark certified. VV550 controller allows VAV units to communicate on a Trane Comm5 or LonTalk link. This controller works in standalone mode, peer-to-peer with one or more other units, or when connected to a Trane Tracer Summit or a 3rd party building automation system that supports LonTalk. The Space Comfort Controller (SCC) is the profile assigned to the VV550 controller.
VAV VV550 Controller Outputs
VAV VV550 Controller Triac outputs for controlling a fan or reheat are rated at 12 VA each.
Wiring Diagram
Figure 2, p. 17 shows a typical wiring diagram for the redesigned VAV VV550 hardware. The new
service part number is BRD2960.
10 VAV-SVP01A-EN
Figure 1. VV550 board layout
General Information
VAV VV550 controller and VAV 4.2 controller comparisons
VAV VV550 VAV 4.2
Supports Comm5 Supports only Comm4 or Comm3 (VariTrac or VariTrane)
No local CO2 sensor input. Uses only a communicated value Local CO2 sensor input is available.
Single star (*) initiates cool minimum airflow override.
Double star (**) initiates cool maximum airflow override.
Does not support VariTrac central control panel (CCP2 and CCP3). Does not support VariTrac CCP2 and CCP3.
Supports ventilation flow control Does not support ventilation flow control.
Supports flow tracking control. Does not support flow tracking control.
Supports enhanced ventilation control sequences. Does not support enhanced ventilation control sequence.
Supports auto-commissioning sequence. Does not support auto-commissioning sequence.
Supports zone sensor air balance sequences. Does not support zone sensor air balance sequence.
Single star (*) initiates maximum flow override after pressing the ON button. Override is held until you move the thumbwheel.
Double star (**) initiates unoccupied override after pressing the ON button. Override is held until you move the thumbwheel.

Shipping & Storage

Each VAV product and its service literature are shipped in the same package. When unpacking, make sure that the literature is not lost or discarded with the packing material. Visually inspect the individual components for obvious defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred during shipment must be filed with the carrier.
When any component of the VAV system and/or field installed accessories must be stored for a period of time prior to being installed, they must be protected from the elements. The storage location temperature should be between -40° to 150°F (-40° to 65.6°C) and the relative humidity should be 10% to 90%, non-condensing. The warranty will not cover damage to the VAV system or controls due to negligence during storage. A controlled indoor environment must be used for storage.
VAV-SV P01A-E N 11
General Information

Data Lists

If you’re going to connect to a generic building automation system, use Table 1, p. 12 and Ta bl e 2 ,
p. 13 for your points list.
Table 1. Input/output listing
Input Description Input SNVT type Output description Output SNVT type
Space temperature nviSpaceTemp SNVT_temp_p Space temperature nvoSpaceTemp SNVT_temp_p
Setpoint nviSetpoint SNVT_temp_p Unit status, mode nvoUnitStatus SNVT_hvac_status
Occupancy, schedule nviOccSchedule SNVT_tod_event Effective setpoint nvoEffectSetpt SNVT_temp_p
Occupancy, manual command
Occupancy sensor nviOccSensor SNVT_occupancy Heat cool mode nvoHeatCool SNVT_hvac_mode
Application mode nviApplicMode SNVT_hvac_mode Setpoint nvoSetpoint SNVT_temp_p
Heat/cool mode input nviHeatCool SNVT_hvac_mode
Fan speed command nviFanSpeedCmd SNVT_switch Terminal load nvoTerminalLoad SNVT_lev_percent
Auxiliary heat enable nviAuxHeatEnable SNVT_switch Space CO
Valve override nviValveOverride SNVT_hvac_overid
Flow override nviFlowOverride SNVT_hvac_overid Air flow nvoAirFlow SNVT_flow
Emergency override nviEmergOverride SNVT_hvac_emerg File table address nvoFileDirectory
Source temperature nviSourceTemp SNVT_temp_p Object status nvoStatus
Space CO
Clear alarms/ diagnostics
Air flow setpoint input nviAirFlowSetpt SNVT_flow
Ventilation ratio limit nviVentRatioLim SNVT_lev_percent
Ventilation for the zone input
(a) Part of the node object.
2
nviOccManCmd SNVT_occupancy Effective occupancy nvoEffectOccup SNVT_occupancy
nviSpaceCO
nviRequest
nviVentSetpt SNVT_flow
2
(a)
SNVT_ppm Alarm message nvoAlarmMessage SNVT_str_asc
SNVT_obj_request
Discharge air temperature
2
Effective air flow setpoint
nvoDischAirTemp SNVT_temp_p
nvoSpaceCO2 SNVT_ppm
nvoEffectFlowSP SNVT_flow
(a)
SNVT_address
(a)
SNVT_obj_status
12 VAV-SV P01A -EN
General Information
Table 2. Configuration properties
Configuration property
description Configuration property SNVT type SCPT reference
Send heartbeat nciSndHrtBt SNVT_time_sec SCPTmaxSendTime (49)
Occ temperature setpoints nciSetpoints SNVT_temp_setpt SCPTsetPnts (60)
Minimum send time nciMinOutTm SNVT_time_sec SCPTminSendTime (52)
Receive heartbeat nciRecHrtBt SNVT_time_sec SCPTmaxRcvTime (48)
Location label nciLocation SNVT_str_asc SCPTlocation (17)
Local bypass time nciBypassTime SNVT_time_min SCPTbypassTime (34)
Manual override time nciManualTime SNVT_time_min SCPTmanOverTime (35)
Space CO
Nominal air flow nciNomFlow SNVT_flow SCPTnomAirFlow (57)
Air flow measurement gain nciFlowGain SNVT_multiplier SCPTsensConstVAV (67)
Minimum air flow nciMinFlow SNVT_flow SCPTminFlow (54)
Maximum air flow nciMaxFlow SNVT_flow SCPTmaxFlow (51)
Minimum air flow for heat nciMinFlowHeat SNVT_flow SCPTminFlowHeat (55)
Maximum air flow for heat nciMaxFlowHeat SNVT_flow SCPTmaxFlowHeat (37)
Minimum flow for standby nciMinFlowStdby SNVT_flow SCPTminFlowStby (56)
Firmware major version nciDevMajVer
Firmware minor version nciDevMinVer
Flow offset for tracking applications nciFlowOffset SNVT_flow_f SCPToffsetFlow (265)
Local heating minimum air flow nciMinFlowUnitHt SNVT_flow SCPTminFlowUnitHeat (270)
(a) Part of the node object
limit nciSpaceCO2Lim SNVT_ppm SCPTlimitCO2 (42)
2
(a)
(a)
n/a SCPTdevMajVer (165)
n/a SCPTdevMinVer (166)
VAV-SV P01A-E N 13

VAV Start Up/Check Out Procedure

Chapter Overview

This chapter contains information about the following:
VV550 Pre-Power Check-Out
Power Wiring Requirements
Light Emitting Diode (LED) Operations
Communication Wiring
Space Temperature Controller Analog Inputs
Zone Sensor Wiring
Auxiliary Sensor Wiring
Binary Input Wiring
Binary Output Wiring
Ventilation Flow Control
Auxiliary Sensor Wiring
Flow Tracking Control
Wireless Zone Sensor

VV550 Pre-Power Check-Out

WARN ING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Check the supply voltage at TB1. Proper polarity must be maintained. TB1-1 is the hot side (+) and TB1-2 is the ground side (-) of the 24VAC input. Refer to Figure 2, p. 17 and Figure 3, p. 18 for the VAV VV550 Controller terminal locations. The VAV VV550 Controller cannot be powered from a common 24VAC transformer that is supplying power to a device containing a full-wave rectifier bridge in its power supply. The acceptable voltage is 18 to 32 VAC (24VAC cataloged). However, voltages at either extreme may result in increased system instability.
Verify that communications wiring has properly been terminated at TB2-1 (+) and TB2-2 (-). Polarity is not important on the communications link.
Verify that the zone sensor connections are correct as detailed in this IOP.
If heat has been added to unit, verify that the proper output connections have been made as detailed in this IOP.
Verify that the tubing is properly connected to the transducer.
14 VAV-SVP01A-EN

VV550 Power Wiring

Power Requirements
WARN ING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARN ING
Electrocution and Fire Hazards with Improperly Installed and Grounded Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in the National Electrical Codes (NEC) and your local/state electrical codes. All field wiring MUST be performed by qualified personnel. Failure to follow these requirements could result in death or serious injury.
Notice:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
VAV Start Up/Check Out Procedure
Use at least 16 AWG for power wiring and connect to terminal TB1-1 (+) and TB1-2 (-). 24VAC is required to power the VAV VV550 Controller and has an acceptable voltage tolerance of 18 to 32 VAC. Refer to Figure 2, p. 17 and Figure 3, p. 18 for the VAV VV550 Controller terminal locations. Replace the VAV VV550 Controller control box cover after field wiring to prevent any electromagnetic interference.
Note: A dedicated 24VAC, 50VA NEC class 2 transformer is recommended to power the VAV VV550
Controller. When powering multiple VAV VV550 Controllers from one transformer, polarity must be maintained. Terminal TB1-1 is designated positive (+) and terminal TB1-2 is negative (-) to the unit casing ground
The power consumption for cooling only Series F Models (VariTrac and VariTrane) is 12 VA (4 VA for the air valve/actuator and 8 VA for the VV550 control board). To determine the total VAV VV550 Controller power requirement, add the power consumption per stage to the circuit board power requirement. For example, a Series F unit containing magnetic contactors with three stages of reheat would consume 42 VA.
Table 3. VA for factory-installed components
Style Volt Amps
F - Style Actuator 4 VA
Air Valve Actuator C through E Style 12 VA
Varitrac Actuator 3 VA
Fan Power Fan Output 6 VA
Hot Water Proportional 4 VA
Hot Water 2 Position 6.5 VA
Electric Heater Magnetic Contactor 10 VA
Electric Heater Mercury Contactor 12 VA
VAV-SV P01A-E N 15
VAV Start Up/Check Out Procedure
Note: VariTrane and VariTrac cooling only Series D and E models consume 20 VA (12 VA for the
actuator and 8 VA for the board). The heating output ratings remain the same.
Refer to Figure 2, p. 17 and Figure 3, p. 18 for VAV VV550 Controller terminal locations and
Figure 59, p. 107 through Figure 66, p. 114 for wiring of output devices.

Light Emitting Diode (LED) Operations

Green Status LED
The green status LED is typically used to indicate whether or not the controller is powered On (24VAC). This is the only LED under direct software control. The green status LED is Off when you press the Test button. The green status LED blinks during manual output testing. Table 4, p. 16 shows and describes the green status LED activity.
Table 4. Green status LED activity
Green status LED activity Description
On Power On, normal operation
Off One of the following: Power Off Controller failure Test button pressed
Blinking for 10 seconds,
0.25 seconds Off; 0.25 seconds On
One blink continuously,
0.25 seconds Off; 2.25 seconds On
Two blinks continuously,
0.25 seconds Off; 0.25 seconds On
0.25 seconds Off; 1.75 seconds On
(a) The wink feature enables you to identify a controller. By sending a request from the Rover service tool, you can request
the controller to wink.
(b) See the diagnostic topic in this guide for a complete list of output override diagnostics.
Wink mode
The controller is in the manual output test mode and no output-override unit diagnostic2 conditions
The controller is in the manual output test mode and one or more output­override unit diagnostic
(a)
(b)
conditions exist
16 VAV-SV P01A -EN
Figure 2. VV550 single duct control diagram
VAV Start Up/Check Out Procedure
VAV-SV P01A-E N 17
VAV Start Up/Check Out Procedure
Figure 3. VV550 fan-powered control diagram
18 VAV-SV P01A -EN

Communication Wiring

WARN ING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARN ING
Electrocution and Fire Hazards with Improperly Installed and Grounded Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in the National Electrical Codes (NEC) and your local/state electrical codes. All field wiring MUST be performed by qualified personnel. Failure to follow these requirements could result in death or serious injury.
Communication Link Wiring
Use 22 AWG Level 4 unshielded communication wire for most Comm5 installations.
Limit Comm5 links to 4,500 ft and 60 devices maximum (without a repeater).
Use the following termination resistors on all links:
•105
Use daisy chain topology.
Limit zone sensor communication stubs to 8 per link, 50 ft each maximum.
Use one repeater for an additional 4,500 ft, 60 devices, and 8 communication stubs.
Ω at each end for Level 4 wire
VAV Start Up/Check Out Procedure
Recommended Wiring Practices
To ensure proper network communication, follow these recommended wiring and planning guidelines when installing communication wire:
All wiring must comply with the National Electrical Code (NEC) and local codes.
Although Comm5 does not require polarity sensitivity, Trane recommends keeping polarity consistent throughout the site.
Make sure that 24VAC power supplies are consistent in how they are grounded. Avoid sharing 24VAC between Comm5 controllers.
Avoid over tightening cable ties and other forms of cable wraps. This can damage the wires inside the cable.
Do not run Comm5 cable alongside or in the same conduit as 24VAC power. This includes the conductors running from triac-type inputs.
In open plenums, avoid running wire near lighting ballasts, especially those using 277 Vac.
Use a daisy chain configuration.
Use termination resistors as described in "Termination resistance placement for Comm5 links"
Insulate termination-resistor leads.
Use only one type of communication wire; do not mix different types
VAV-SV P01A-E N 19
VAV Start Up/Check Out Procedure
Wiring requirements
The recommended Comm5 communication-link wiring is 22 AWG, Level 4, twisted-pair wire. See
Ta ble 5 , p. 2 0 "Specifications for Level 4-compliant cables". The wire can be either shielded or
unshielded. However, unshielded wire is recommended for most installations.
The maximum wire length for Comm5 communication links is 4,500 ft (1,400 m). Comm5 communication-link wiring must be installed in a daisy-chain configuration (Figure 4, p. 21 and
Figure 5, p. 22).
Table 5. Cable specifications
Specification Value
dc resistance (Maximum resistance of a single copper conductor regardless of whether or not it is solid or stranded and regardless of whether or not it is metal coated.)
dc resistance unbalance (maximum) 5%
Mutual capacitance of a pair (maximum) 17 pF/foot
Pair-to-ground unbalance (maximum) 1,000 pF/foot/1,000 ft
Characteristic impedence
Attenuation (maximum dB/1,000 ft at 20°C)
Worst-pair near-end crosstalk (minimum) (Values shown are for information only. The minimum NEXT coupling loss for any pair combination at room temperature is to be greater than the value determined using the formula NEXT (F (0.772)-15 ft.)
dc resistance unbalance (maximum) 5%
log10
(F
/0.72) for all frequencies in the range of 0.772 MHz-20 MHz for a length of 1,000
MHz
MHz
)>NEXT
772 kHz 102 Ω
1.0 MHz 100 Ω
4.0 MHz 100 Ω
8.0 MHz 100 Ω
10.0 MHz 100 Ω
16.0 MHz 100 Ω
20.0 MHz 100 Ω
772 kHz 4.5 dB/1,000 ft at 20°C
1.0 MHz 5.5 dB/1,000 ft at 20°C
4.0 MHz 11.0 dB/1,000 ft at 20°C
8.0 MHz 15.0 dB/1,000 ft at 20°C
10.0 MHz 17.0 dB/1,000 ft at 20°C
772 kHz 58 dB
1.0 MHz 56 dB
4.0 MHz 47 dB
8.0 MHz 42 dB
10.0 MHz 41 dB
16.0 MHz 38 dB
20.0 MHz 36 dB
18.0 Ω/1,000 ft 20°C
± 15% ± 15% ± 15% ± 15% ± 15% ± 15% ± 15%
20 VAV-SVP01A-EN
Figure 4. Daisy chain configuration
Note: Use 105 Ω, 1%, 1/4 W for 22 AWG, Level 4.
Comm5 Link Repeater
A Comm5 link repeater regenerates the signal on a Comm5 link. The configurations on either side of the repeater should be daisy chain. Both link segments require proper termination (Figure 5,
p. 22).
VAV Start Up/Check Out Procedure
Termination Resistor
Ω
Ω
Link repeater requirements.
A link repeater is required when:
The total wire length is greater than the maximum wire run length of 4,500 ft (1,400 m).
More than 60 devices are connected to a link-This total does not include the BCU, the link repeater, and the temporary use of a service tool on the same link.
More than eight zone sensor communication stubs (maximum 50 ft) are required on a Comm5 link
Link repeater connections.
The recommended shield connections are shown in Figure 6, p. 22. Use these connections for instances where shielded communication wire is used. For an example of using a repeater to create an extended daisy chain configuration, see Figure 5, p. 22.
Follow these guidelines when using a repeater:
Read the Comm5 repeater installation (3270 3285) information that comes with the link repeater.
For information about terminating daisy chain configurations, see "Termination resistance placement for Comm5 links" onFigure 4, p. 21.
Connect shield-drain wires entering the repeater to a terminal marked with a capacitor symbol. The entering shield-drain wire must be connected to earth ground at the system panel.
Connect shield-drain wires leaving the repeater to the repeater terminal marked with an earth ground symbol.
VAV-SV P01A-E N 21
VAV Start Up/Check Out Procedure
Ω
Ω
Ω
Ω
Termination Resistors
Termination Resistors
Figure 5. Alternate daisy chain configuration
Notes:
1. Maximum wire length for the entire configuration is 4,500 ft (1,400 m).
2. Comm5 wire length limitations can be extended through the use of a link repeater, see “Comm5 physical link repeater.”
Figure 6. Comm5 shield repeater connection
22 VAV-SVP01A-EN
VAV Start Up/Check Out Procedure
Yellow Comm LED
The yellow Comm5 LED blinks whenever another controller is transmitting. However, the yellow Comm5 LED does not blink when the controller is transmitting data. The yellow Comm5 LED cannot distinguish between messages meant for the controller and messages that the controller ignores.
Ta ble 6 , p. 2 3 shows and describes the yellow Comm LED activity.
Table 6. Yellow comm LED activity
Yellow Comm LED activity Description
LED Off continuously The controller is not detecting communication. (Normal for stand-alone applications.)
LED blinks or flickers The controller detects communication. (Normal for communicating applications, including data sharing.)
LED On continuously Abnormal condition or extremely high traffic on the link.
Table 7. Red service LED activity
Red service LED activity Description
LED is Off continuously after power is applied to the controller. Normal operation
LED is On continuously, even when power is first applied to the controller.
LED flashes about once every two seconds. Uninstalled (normal controller mode). Use the Rover service tool to restore
Someone is pressing the Service push button or the controller failed.
the unit to normal operation. Refer to the Rover product literature for more information.
Service Push Button
Important: If the Service button is held down for more than 15 seconds, the controller will
uninstall itself from the Comm5 network. The red service LED flashing approximately once two every seconds indicates this mode (see Red service LED above). Use the Rover service tool to restore the unit to normal operation. Refer the Rover product literature for more information.
The Service push button can be used, as one of several methods, to install the controller in a communication network. Refer to the Rover service tool product literature EMTX-SVX01*-EN for more information.
Space temperature controller Analog Inputs
Zone Sensor Hardwired Option. Depending on the zone sensor options used, a maximum of
five wires may be required to run from the VAV VV550 Controller to the zone sensor. The zone sensor options are:
Zone sensor only (2 wires) - Part Number X13511528010.
Sensor with night set back- Part Number X13511530010.
Zone sensor with external adjustable - Part Number X13511529010.
Zone sensor with external adjustable night set back, timed override (TOV) on/cancel button ­Part Number X13511527010.
Digital zone sensor - Part Number X13511530010
Communications jack - Part Number X13651467020 (for one box of 12)
Note: All wiring from the zone sensor to the Com link must be twisted shielded pair wiring.
VAV-SV P01A-E N 23
VAV Start Up/Check Out Procedure
Zone Sensor Wireless Option (Wireless Zone Sensor). Receiver is used to receive a signal
from the wireless zone sensor and can be factory installed- Part Number X13790855010. The wiring harness connects the receiver to the VAV VV550 Controller - Part Number X19051672010.
Zone Sensor Wireless Option (Zone Sensor). The wireless zone sensor with night setback
timed override (TOV) on/cancel button. Also can be ordered for Celsius and Fahrenheit setpoint adjustment - Part Number X13790492010 (F), Digital Display wireless zone sensor- Part Number X13790822010
Zone Sensor Wiring
Location and Mounting. A zone sensor in each control zone should be located in the most
critical area of the zone. Sensors should not be mounted in direct sunlight or in the area's supply air stream. Subdivision of the zone may be necessary for adequate control and comfort. Avoid mounting zone sensors in areas subject to the following:
Drafts or "dead spots" behind doors or corners.
Hot or cold air ducts.
Radiant heat from the sun or appliances.
Concealed pipes or chimneys.
Unheated or uncooled surfaces behind the sensor such as outside walls.
Air flows from adjacent zones or other units.
Wiring. Each unit must be controlled by a zone sensor that is designated specifically for use with
the VAV VV550 Controller. Field wiring for the zone sensors must meet the following requirements:
Must be 14 to 18 AWG.
•Refer to Figure 2, p. 17 and Figure 3, p. 18 and the sensor instructions for terminal connections.
If local codes require enclosed conductors, the zone sensor wires should be installed in conduit.
Do not route zone sensor wires in conduit with 24VAC or other high power conducting wires.
Zone sensor comm stubs. For the most reliable communications, limit the number of zone
sensor communication stubs to 8 per Comm5 link unless using a repeater then it is 16 stubs. Each stub should not exceed 50 feet. Exceeding these limits increases the likelihood of communication problems. Connect Communication wire to terminals TB2-5 and TB2-6 on VV550 controller and to comm. Jack in zone sensor
Figure 7. Communication stubs used with a repeater
Notes:
1. Maximum wire length on either side of the repeater is 4,500 ft (1,400 m).
2. The link repeater is limited to 60 devices on either side of the link.
3. Place termination resistors at the end of the link. Use a 105 X resistor at each end of the link for Level 4 wire
24 VAV-SVP01A-EN
Auxiliary Duct Temperature Sensor
The typical mounting position of the auxiliary sensor is upstream of the VAV unit and connected into the DDC controller at TB3-5 and TB3-6. Comm5 could be mounted downstream of the reheat for improved diagnostics (Figure 8, p. 25). Refer to Controller Diagrams Figure 2, p. 17 and
Figure 3, p. 18 for the VAV VV550 Controller terminal locations.
Figure 8. Duct temperature sensors: upstream/downstream
VAV Start Up/Check Out Procedure
Binary Input Wiring
Each VAV VV550 Controller provides one binary input. On the VV550 factory-installed controller, the binary input configuration is set up at the factory. The binary input can be configured with Rover service tool as occupancy or generic or not used. The input associates 0 Vac with open contacts and 24VAC with closed contacts. It is activated by a dry contact switch closure.
Must be 14 to 18 AWG.
•Refer to Figure 2, p. 17 and Figure 3, p. 18 and the sensor instructions for terminal connections.
Occupancy Binary Input. The occupancy binary input can be configured as NO or NC. Occupied
is the normal state. It is also the initial state at power-up and after a reset. Unoccupied is the other state. If the binary input is configured as generic, the default occupancy mode is occupied.
Generic Binary Input. The generic binary input can be configured as NO or NC. Normal state is
inactive and is also the initial state at power-up and after a reset. Active is the other state.
Not Used Input. When no device is connected to the input, configure the controller input as not
used.
Binary Outputs Wiring
Binary outputs that are required for unit operation are factory wired and commissioned.
VAV-SV P01A-E N 25
VAV Start Up/Check Out Procedure
Ventilation Flow control
See Auxiliary Duct Temperature Sensor wiring on Space temperature controller Analog Inputs
Note: If heat is installed Auxilary sensor will be located at the discharge of the VAV unit.
Flow Tracking Control
Two controls are used in Flow tracking controller. One is configured with the Space temperature control program and the other controller will be set up as flow tracking controller and it will not need any input or output device connected to the controller. See Operation section for details.
26 VAV-SVP01A-EN

Wireless Zone Sensor

2.90 in (7.35 cm)
1.08 in (2.75 cm)
4.78 in (12.14 cm)
2.62 in (6.65 cm)
Note: The dimensions are the
same for both the sensor and the receiver.
Overview
The Trane Wireless Zone Sensor set includes a sensor and a receiver that work together to provide the same functions as the equivalent Trane wired sensor, such as the standard 10 k temperature input (with the exception of the communication jack). No further software or hardware is necessary for site evaluation, installation, or maintenance.
The sensor transmits the zone temperature, all zone temperature setpoint functions, timed override Occupied (On) and timed override Unoccupied (Cancel) information to the receiver. The receiver electrically reproduces the zone temperature resistance, all zone temperature setpoint function resistances, and timed override On and timed override Cancel information as sent by the sensor.
Dimensional Diagrams
See Figure 9, p. 27 and Figure 10, p. 28 for dimensions of the Wireless Zone Sensor set. The dimensions are the same for both the sensor and the receiver.
Figure 9. Outside dimensions for sensor
VAV Start Up/Check Out Procedure
VAV-SV P01A-E N 27
VAV Start Up/Check Out Procedure
3.27 in (8.30 cm)
2.36 in (6.00 cm)
1.34 in (3.41 cm)
Note: The dimensions are the
same for both the sensor and the receiver.
Figure 10. Mounting hole dimensions for sensor
Setting the Address, Mounting, Wiring, and Associating the Receiver and Sensor
28 VAV-SVP01A-EN
The following procedure list shows the recommended order for installation:
Choosing a Location for Mounting the Sensor.
Setting the Rotary Address Switches on the Receiver and on the Sensor.
Replacing and Securing the Receiver Cover.
Powering the Sensor and Associating the Sensor to the Receiver.
Applying Power to the Receiver.
Testing Signal and Battery Strength.
Disassociation.
Choosing a Location for Mounting the Sensor
Placement of the receiver and the sensor set is critical to proper operation. In most installations, distance is not the limiting factor for proper radio signal quality. It is more greatly affected by walls, barriers, and general clutter. For best radio transmission range and reliability, wherever possible, mount the receiver and sensor in line of sight. Try to minimize the number of barriers between the pair of devices. In general, sheetrock walls and ceiling tiles offer little restriction to the propagation of the radio signal throughout the building; concrete or metal barriers offer the most restriction. The transmission range for the sensor is as follows:
Open range: 2,500 ft (762 m) (packet error rate = 2%)
Usable range: 200 ft (61 m)
Typical range: 75 ft (23 m)
Ambient considerations
Avoid locations that are outside the operating temperature and humidity range.
Location Considerations for the Sensor
When selecting a location for the sensor, consider both thermal and radio transmission characteristics of the location.
Thermal considerations
Avoid areas of direct sunlight.
Avoid areas in the direct air stream of air diffusers.
Avoid exterior walls and other walls that have a temperature differential between their two sides.
Avoid areas close to sources of heat such as sunlight, appliances, or other equipment.
Avoid drafty areas.
Avoid dead spots behind doors, projection screens, or corners.
Radio transmission considerations
Avoid metal barriers between the sensor and receiver, such as plastered walls with metal lathe. They will decrease radio signal quality.
Avoid placing the sensor inside metal enclosures.
Avoid radio transmissions through thick, solid concrete walls.
VAV Start Up/Check Out Procedure
Setting the Rotary Address Switches on the Receiver and the Sensor
Note: To expedite the installation and association process, set the addresses before applying
power to the receiver.
The process of establishing communication between the receiver and sensor is referred to as association. The receiver and the sensor must have their rotary switches set to the same address in order to enable communication between the two devices (see Figure 11, p. 30). Important limitations are as follows:
Only one associated receiver/sensor set can communicate within the reception range of the wireless system.
It is not possible to associate more than one sensor to a receiver, nor is it possible to associate more than one receiver to a sensor.
VAV-SV P01A-E N 29
VAV Start Up/Check Out Procedure
DRESS
IN
LED3
L
ED2
T
A
S
S
Figure 11. Setting the rotary address switches on the receiver and the sensor
Do not remove the insulation strip yet.
B1 +
!
LED1
SIGNAL
LED5
BATTERY STATUS
S1
ADDRESS
Pb
Pb-FREE
S3
STATUS
S4
WIRELESS INSTALL
LED4
S2
LED1
LED2
LED3
LED5
SIGNAL
POWER
S5
S1
ADD
HEATING SET FAN/SYSTEM
5
S
SETPOINT ZONE GND 24VAC/DC GND COMM + COMM -
WIRELESS
L
STAL
LED4
S4
S3
S2
C33
C34
J1
C35
R77
Setting the Receiver Address
1. Using a small screwdriver, set the three rotary address switches (locations S1, S2, S3) on the receiver (Figure 11, p. 30) to an address between 001 and 999.
Note: Do not use 000 as an address for installation. If you set the receiver address to 000, it will:
– Return the receiver outputs to their factory defaults indefinitely (zone temperature and
setpoint outputs: 72.5°F [22.5°C]).
– Remove all association knowledge.
– Make the receiver unable to associate with a sensor.
Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
Zero is at the nine o'clock position.
2. Make a notation of the address and location of the receiver.
Setting the Sensor Address
1. Using a small screwdriver, set the three rotary address switches (locations S1, S2, S3) on the sensor (Figure 11, p. 30) to the same address used for the receiver it is to be associated with.
2. Make a notation of the address and location where this sensor is to be mounted.
Note: Do not use 000 as an address for installation. If you set the address to 000, it will:
– Remove all association knowledge.
30 VAV-SVP01A-EN
– Revert to a low-power hibernation mode.
– Send a disassociation request to the receiver. If the sensor and receiver are associated and
communicating at the time the sensor is set to 000 and the Test button is pressed, the receiver will also become unassociated and will be available for re-association.
Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
Zero is at the 9 o'clock position.
3. Make a notation of the address and location of the sensor.
Factory Wiring of the Receiver to the VAV Unit Controller
The required power for the receiver is 24VAC or 24 Vdc and is less than 1 VA. The receiver is designed to be powered by the VAV VV550 Controller. See Figure 12, p. 31.
Note: A dedicated transformer is not necessary or advised.
Figure 12. Factory wiring of the receiver to the VAV VV550 controller
VAV Start Up/Check Out Procedure
VAV-SV P01A-E N 31
VAV Start Up/Check Out Procedure
Table 8. Wiring harness: wire identification
Wire Label Color Function
HEATING SET Brown
FAN SYSTEM Green Fan and system control (WDS only)
SETPOINT Red
ZONE White Zone temperature
GND-SIGNAL Black Ground for setpoint and zone signal
24VAC/DC Blue 24VAC/vdc power
GND-POWER Yellow Ground for 24VAC/dc
Replacing and Securing the Receiver Cover
1. To replace the receiver cover on the base plate, hook the cover over the top of the base plate. Apply light pressure to the bottom of the cover until it snaps in place.
2. If necessary to keep the cover securely attached, install the security screw into the bottom of the receiver (Figure 13, p. 32).
Figure 13. Snap receiver cover on base plate and attach security screw
Space temperature heating setpoint
(WDS only)
Space temperature setpoint (WDS and
W2S only)
Security screw
32 VAV-SVP01A-EN
Applying Power to the Receiver
LED5 stays constantly On
RECEIVER
LED3
LED3 will begin to blink after 10 seconds
Restore power to the VAV VV550 Controller. Observe LED5 on the receiver (Figure 14, p. 33). It will light and stay constantly On when 24 V power is normal.
Figure 14. LED5 stays on after applying power to the receiver
VAV Start Up/Check Out Procedure
Receiver Indicates Readiness to Associate
After initial power up, the receiver conducts a channel scan for 10 seconds. During this time, the receiver selects from 16 available channels the clearest channel on which to operate. LED1, LED2, and LED3 flash rapidly in succession (round-robin style) while the channel scan is in progress.
Note: Do not attempt association until the channel scan is finished. After the channel scan is
finished, LED3 will begin blinking (one-blink pattern) to show that the receiver is ready to be associated with a sensor. LED3 will stop blinking when association has been established (Figure 15, p. 33).
Figure 15. LED3 blinks when the receiver is ready to be associated with a sensor
VAV-SV P01A-E N 33
VAV Start Up/Check Out Procedure
B1 +
B2 -
IINSTALL
WIRELESS
S4
S3
S2
S1
ADDRESS
STATUS
BATTERY
LED5
SIGNAL
J1
Pb
Pb-FREE
STATUS
LED4
LED5
LED1 LED2 LED3
S5
SENSOR
+
+
Powering the Sensor and Associating the Sensor to the Receiver
1. Verify that the sensor is set to the same address as the receiver it is to be associated with.
2. Remove the insulation barrier, which is a plastic strip located between the two batteries (Figure 16, p. 34).
3. Association will automatically occur between the sensor and the receiver. If the first association attempt is unsuccessful, the sensor will automatically reattempt association with the receiver every 10 minutes.
Note: A disassociated sensor will transmit an association request every 10 minutes. An associated
sensor that has lost communication with the receiver will transmit an association request every 50 minutes.
Note: LED3 on the receiver stops blinking to indicate that association has been established.
Figure 16. Removing the insulation barrier on the sensor
34 VAV-SVP01A-EN
Testing Signal and Battery Strength
LED1 LED2 LED3
LED5
srosnes SDW ledoMsrosnes SZW dna STW ledoM
Tes t bu tt on
Push firmly, then release
Push firmly, then release
Tes t bu tt on
The following recommended test indicates signal and battery strength. It verifies that the association process was successful and that the batteries have adequate charge. (For more information on LEDs, see "Troubleshooting" chapter.)
1. Firmly press and release the Test button (S5) on the bottom of the sensor (Figure 17, p. 35).
2. View LED1, LED2, and LED3 to determine the strength of the signal. View LED5 to determine the strength of the battery.
Note: The LEDs will turn Off after 5 seconds to conserve battery strength.
3. Record the results in your commissioning statement.
Figure 17. Wireless sensors
VAV Start Up/Check Out Procedure
Disassociation
The receiver removes all stored association information, conducts a channel scan, and restarts itself, if any of the following are true:
The receiver address is changed from its current setting (001-999).
The receiver receives a disassociation notification from its associated sensor.
The receiver does not receive a communication from its associated sensor within 35 minutes.
Configuring the Wireless Sensor (Model Digital Display WDS only)
The configuration of the sensor determines which system features can be accessed and changes can be made by the tenant (for example, changes to cooling/heating mode, setpoint, or fan speed.
VAV-SV P01A-E N 35
Verify system and associated unit features before configuring the sensor.
VAV Start Up/Check Out Procedure
Configuration button
The building owner or operator may choose to limit tenant access to certain features. This can be done through configuration. Or, if a sensor is configured to match all control capabilities of the building automation system, the locking feature can be used to restrict the tenant from making changes.
Configuration Procedure
To configure settings on the model WDS sensor, follow this procedure in the order presented.
1. Press the configuration button for 3 seconds.
Figure 18. Configurations
The display will change to configuration mode. When the sensor is in configuration mode, a wrench symbol appears on the display and the menus are separated by lines, as illustrated below.
Figure 19. Configuration mode
2. Press the center button on the keypad to begin the configuration process.
36 VAV-SVP01A-EN
Figure 20. Center button
Setting Configuration options
Temperature
• Choose Fahrenheit or Celsius
• Choose the degree resolution (whole degrees, half degrees, or tenths of degrees).
Setpoint
Deadband (available for dual
setpoint system only)
Note: Deadband refers to the
minimum difference between the heating and cooling setpoints.
System a) Single setpoint
. .
.
.
.
.
dual setpoint
no
setpoint
single
setpoint
.
heat/cool setpoint offset
(1.8˚F – 10.8˚F, 1˚C – 6˚C)
3. Configure the sensor options in the order shown in the table.
Press or to scroll to the next selection.
Press or to move to the next menu.
Figure 21. Wireless configuration
VAV Start Up/Check Out Procedure
Center button
VAV-SV P01A-E N 37
VAV Start Up/Check Out Procedure
System (continued) b) Dual setpoint
c) No setpoint
Fan
Note: Fan control not available
on VAV units.
Occupancy (timed override)
Setting Configuration options
emergency heat/
heat/cool/off
heat/cool/
auto/off
emergency heat/
heat/cool/auto/off
no system
options enabled
auto/off/low
med/high
auto/off/
low/high
auto/off
off/high (on)
off/low/high off/low/
med/high
no fan options
enabled
auto/high (on)
38 VAV-SVP01A-EN
4. Review the display to ensure that you have selected the correct configuration options.
Figure 22. Configuration options
To return the display to operating mode, press the configuration button (See Step 1).
Note: The sensor will revert to operating mode if no buttons are pressed for 10 minutes.
The following example shows a configured display in operating mode.
Figure 23. Display
VAV Start Up/Check Out Procedure
The example shows a display that has been configured for:
Dual setpoint
Temperature units (Fahrenheit)
Temperature resolution to tenths of a degree
System settings: Heat, Cool, Off
Fan Settings: Auto and On
Occupied/unoccupied option enabled
Display shows the following:
Temperature units (Fahrenheit)
Temperature resolution to tenths of a degree
System setting: Cooling
Fan Setting: Auto
Occupied/Unoccupied option enabled
If an error exists, it appears at the bottom of the display between the occupancy symbols, as shown in below. SeeTable 20, p. 92 for error code definitions.
Figure 24. Error message
VAV-SV P01A-E N 39
VAV Start Up/Check Out Procedure
Arrow indicates setpoint is shown on display
Setpoint
System menu
Optional Features
Displaying Setpoint or Temperature
You can configure the sensor to display either the temperature (default) or setpoint. To select either option:
1. Verify that the sensor is in operating mode and at the home screen.
2. Press the up and down arrows for 3 seconds. The arrow indicates setpoint display, as shown in the illustration.
Figure 25. Setpoint or temperature display
Locking and Unlocking Settings
You can lock or unlock the setpoint, system, or fan setting to prevent changes.
To lock or unlock the settings:
1. Verify that the sensor is in operating mode and at the home screen.
2. Choose a setting to lock or unlock.
Select the setpoint by pressing the up or down arrow.
Figure 26. Setpoint
Select the system menu by pressing the center button. Use the left or right arrow to choose
the setting.
Figure 27. System menu
From the system menu, press the down arrow to select the fan menu. use the left or right
arrow to choose the setting.
40 VAV-SVP01A-EN
VAV Start Up/Check Out Procedure
Fan menu
Note: Fan on VAV units cannot be controlled from the zone sensor.
Figure 28. Fan menu
3. Press the left and right arrows for 4 seconds.
Figure 29. Arrows
If you try to access a feature that is locked, the lock symbol wi ll app ear on the displays. If you press a keypad button to try and change a locked setting, the locked symbol will flash.
VAV-SV P01A-E N 41

VAV VV550 Controller Programming and Operation

Chapter Overview

This chapter contains information about the following:
Accessing Rover/Comm5 LonTalk
VV550 Controller Device Home Tabs: At a Glance
Entering and Exiting the Service Mode
Overriding VAVs
Saving VAV Program
VV550 Controller Device Home Tabs: Instructions

Accessing Rover/Comm5 LonTalk

Rover Overview
Rover is a service tool that allows parameters to be viewed or adjusted in the VAV VV550 Controller. The operating and programming guide for Rover is EMTX-SVX01*-EN. Rover Comm5 is a software application for monitoring, configuring, balancing, binding and testing VAV VV550 Controllers on Comm 5 links.
Note: For Instructions on how to use Rover Comm5, refer to the Rover Comm5 online Help by
clicking Contents and Index on the Help menu.
Laptop Requirements and Complete Connection Instructions
For instructions on connecting a PC laptop to a Comm5 link, refer to the Installing Rover Service Tool Version 5.0, 3270 3275.
Note: A hard copy of this document is in the Rover package and an electronic copy
(Installation.pdf) can be found on the Rover installation CD-ROM.
To connect to a Comm5 Link
1. Insert the Comm5 card in the PC laptop.
2. Connect the cables as shown in the appropriate figure. Refer toFigure 30, p. 42 for connecting to a Comm5 controller through a zone sensor and Figure 31, p. 43 for Connecting to a Comm5 controller using alligator clips.
Note: Make sure to maintain polarity.
Figure 30. Connecting to a Comm5 controller through a zone sensor.
Comm5
Adapter cable
RJ11 plug
42 VAV-SVP01A-EN
PCMCIA card
VAV VV550 Controller Programming and Operation
Figure 31. Connecting to a Comm5 controller using alligator clips
Comm5 PCMCIA card
Red
Black
RJ11 plug
Adapter cable
3. Double-click the Rover icon on the laptop PC desktop. The Rover Service Tool screen will appear.
4. Double-click on the Comm5 Configuration Only Service Tool icon to access a Comm5 VV550. This tool allows the user to monitor, configure, and test Comm5 VV550 controller.
Note: The configuration-only Rover Comm5 software runs only in the Passive mode. This means
that you can configure setpoints and other controller parameters but cannot create bindings or set up peer-to-peer Comm5 networks. All other Rover Comm5 features are available.
Figure 32. Rover service tool
5. Rover Comm5 will launch and the Rover service tool will automatically Scan for Neron ID of Devices.
6. Once the scan is complete, the results will populate the device tree on the left-hand side of the Rover Comm5 screen.
7. Access the desired VAV VV550 Controller from the device tree.
VAV-SV P01A-E N 43
VAV VV550 Controller Programming and Operation

VV550 Controller Device Home Tabs: At a Glance

Unit Information Tab
Figure 33. Unit tab
Space Temp: The temperature, as reported by the zone sensor.
Active Setpoint: The active (or actual) setpoint currently used by the VAV VV550 Controller. Can
be either Heating or Cooling depending on operating mode.
Primary Air / Discharge Air Temperature: Shows the auxiliary temperature input.
Note: This will be defined in configuration as either Primary Air or Discharge air temperature
depending on unit control strategies. See Configuration section for more details.
Airflow: Measured in CFM. When a valid flow value is present, the controller operates under pressure independent control. If after an airflow sensor failure, the airflow returns to the valid range (airflow value greater than 10% of configured nominal airflow), the controller automatically resumes pressure independent control. When the communicated airflow setpoint is invalid, the flow sensor has failed, or calibration has failed, the controller closes the air valve if the configured
44 VAV-SVP01A-EN
VAV VV550 Controller Programming and Operation
airflow tracking offset is negative. If the configured airflow tracking offset is positive, the controller opens the air valve to the configured maximum airflow space.Once a valid differential pressure is established through the local hardwired input and then is no longer present, the controller generates a flow sensor failure diagnostic.
Airflow Setpoint: The VV550 controllers support one modulating air valve for heating and cooling operation. The controller positions the modulating air valve to deliver the desired airflow (cooling or heating capacity). The desired airflow is called the active flow setpoint. The airflow control algorithm compares the active airflow setpoint with the measured airflow and calculates the necessary air valve movement to minimize error. The airflow setpoint is limited by applicable minimum and maximum flow setpoints.
Space CO2: Communicated Value only. CO2-based demand control ventilation uses the communicated space CO2 value. The controller cannot monitor CO2 from a local CO2 sensor. The controller compares the space CO2 concentration to the configured band of CO2 values and determines the demand ventilation rate of the zone. The resulting ventilation rate is called the effective ventilation setpoint. The effective ventilation setpoint is the outdoor airflow required to provide ventilation. It is used to calculate the ventilation ratio of the zone.
Diagnostic
This is a log that records each diagnostic independently of other diagnostics.
Note: A list of diagnostics will be located in troubleshooting section of this manual.
Use the ‘Reset Diagnostic’ button to reset the diagnostic from this point. A reset clears latching diagnostics and enables the controller to try to run normally. If the latching condition is still present after the reset, the controller shuts down. A reset resets a unit that is running normally. There are five ways to reset unit diagnostics:
Manual output test at the controller
Cycling power to the controller
BAS (communicated status request, clear alarm)
Rover service tool (communicated status request, clear alarm)
A communicating device able to access the controller diagnostic reset input (communicated status request, clear alarm)
Operating Status
Occupancy Modes: There are four valid occupancy modes of the VAV VV550 Controller, and they would be displayed at under operating status. The four occupancy modes are:
Occupied mode
Unoccupied mode
Occupied standby mode
Occupied bypass mode
Control Mode Field: This is were the controller will display the heating or cooling mode of the controller. The controller can receive communicated requests for heating or cooling operation. Field options are: Heating, Cooling, and Calibration.
Pressure Dependent (or Independent) Mode: This is were the controller will display if it has a valid flow input to the controller from the flow ring and pressure transducer. The controller can operate with or without a valid flow value (either hardwired or communicated). It operates under pressure dependent control or pressure independent control.
Pressure dependent control - When a valid flow value is not present, the controller operates under pressure dependent control (position control). Pressure dependent control substitutes the air valve position for the flow measurement for all control actions.
VAV-SV P01A-E N 45
VAV VV550 Controller Programming and Operation
Pressure independent control - When a valid flow value is present, the controller operates under pressure independent control. If after an airflow sensor failure, the airflow returns to the valid range (airflow value greater than 10% of configured nominal airflow), the controller automatically resumes pressure independent control.
Initiate Calibration button: The calibration sequence enables the controller to calibrate the air valve position and the water valve position.
Unit Description
Describes the type of device being communicated to via Rover service tool. It also indicates the general program that has been placed in controller.
Outputs Tab
Figure 34. Outputs tab
Fan Status: The Fan will be shown as On, Off, or None.
Air Valve Position: Indicates air valve or damper position.
Reheat Capacity: Will indicate reheat capacity in Percentage.
46 VAV-SVP01A-EN
Ventilation Tab
Figure 35. Ventilation tab
VAV VV550 Controller Programming and Operation
Note: For more information on this Ventilation Tab and how the VAV VV550 Controller interfaces
with Tracer Summit, see CNT-SVX17*-EN
Ventilation Ratio: The Tracer Summit BAS uses the communicated ventilation ratio limit to tell the controllers how much outdoor air is in the primary air. However, the air handler may not be able to provide as much outdoor air as the system requires due, for example, to a low outdoor air temperature. If the communicated ventilation ratio limit is not sufficient, the controller can raise its minimum airflow setpoint as long as the space temperature remains under control.
Effective Ventilation Setpoint: The Tracer Summit BAS uses the effective ventilation setpoint from all the VAV boxes to calculate how much outdoor air (OA) the system needs.
Active Minimum Airflow setpoint: The active minimum airflow setpoint must be less than the active maximum airflow setpoint. The active minimum airflow setpoint and the active maximum airflow setpoint are limited to 1.2 times the configured nominal airflow
Minimum Airflow Setpoint Source: The controller selects the active minimum flow setpoint based on the occupancy mode, the use of reheat, and the control mode.
VAV-SV P01A-E N 47
VAV VV550 Controller Programming and Operation
Commissioning Tab
Figure 36. Commissioning tab
Auto-commissioning Test Sequence
The controller auto-commissioning test sequence (see Table 9 , p. 4 9 ) validates both the proper operation of all outputs and the capability to measure all inputs. The purpose of the test sequence is to minimize the labor required to commission the unit in the field.
The auto-commissioning test does not require a flow sensor or an auxiliary temperature sensor. If there is no flow sensor, the controller runs in pressure-dependent mode. An auxiliary temperature sensor in the discharge air stream is required for testing of the fan and the reheat. The fan and the reheat are not tested if the discharge air temperature sensor is not present. The fan is not tested if there is no fan. Local reheat is tested, if it is present. Remote reheat is not tested.
The sequence starts on receipt of an auto-commission command from the Rover™ service tool or the Tracer Summit™ BAS. The auto-commission command contains a time/date stamp. No third party tool can start the auto-commissioning sequence. The user then chooses to commission all VAV boxes or one VAV box. The results of auto-commissioning are contained in a structured network variable called reported auto commissioning report. The controller places the time/date stamp in the report. The structure is loaded with the default values for all of the fields when the auto
48 VAV-SVP01A-EN
VAV VV550 Controller Programming and Operation
commissioning test sequence starts. The fields are updated with the results as the sequence progresses. The data is held until the next auto-commissioning test.
If an auto-commission command is received in the middle of an auto-commissioning cycle the auto-commissioning sequence restarts. If an auto-commission command is received during calibration, calibration aborts and restarts after auto-commissioning finishes. If an abort auto­commission command is received during the calibration portion of the primary air valve test, it is honored after the air valve calibration finishes.
The mode field of reported unit status reports TEST when the controller is in the auto­commissioning sequence.
Table 9. Auto-commissioning test sequence
Item Test Action Reported Data
Primary air valve and airflow
Fan F low
Local Reheat Hydronic
Local reheat electric
(a)
(b)
(b)
(b)
1. Turn off fan and reheat.
2. Close air valve and modulating water valve (if present).
3. Calibrate the airflow sensor.
4. Open the air valve to 40% of the configured maximum airflow. Record the position of the air valve.
5. Open the air valve to 100% of the configured maximum airflow. Record the position of the air valve.
1. Record the auxiliary temperature at the configured maximum airflow.
2. Close the primary air valve.
3. Turn on the fan (if present).
4. Monitor auxiliary temperature for 3 minutes or until it changes by 10°F.
5. Record the auxiliary temperature.
1. If no fan is present, open the air valve to the configured minimum local heating airflow.
2. If the fan is present, close the air valve and turn on the fan.
3. Record the auxiliary temperature.
4. Open the water valve to 100% open.
5. Monitor the auxiliary temperature for 10 minutes or until it changes by 10°F.
1. If no fan is present, open the air valve to the configured minimum local heating airflow.
2. If the fan is present, close the air valve and turn on the fan.
3. Record the auxiliary temperature.
4. Progressively turn on each local stage 30 seconds after the previous stage until all stages are energized.
5. Record the auxiliary temperature 30 seconds after each stage is energized.
Primary air valve position at 40% and 100% flow.
Starting and ending auxiliary temperature.
Starting and ending auxiliary temperature.
Starting auxiliary temperature and the auxiliary temperature for each local stage of electric heat energized.
(a) If there is no flow sensor, the controller runs in pressure dependent mode and record 40% and 100% during this auto-commissioning step. (b) Requires a functional auxiliary sensor in the discharge air stream. The auxiliary sensor must be configured for discharge air temperature.
VAV-SV P01A-E N 49
VAV VV550 Controller Programming and Operation
Figure 37. General tab
Name Location/ID: VAV controller name
Neuron ID: Each VAV VV550 Controller will have an Echelon chip that has a distinctive
identification number called a neuron ID. This replaces the addressing that was done with dip switches on a DDC Comm 4 VAV UCM 4.2 controller.
Device State/Mode: This point indicates if Rover is communicating with controller. The two states are Configured On line or Not Communicating
Manufacturer ID: Trane will be the manufacture displayed for the VV550 controller
Software Revision: This is the controller revision programs that has been downloaded into this
controller
Note: If unit is not operating properly it could be a software issue and technical support will need
the revision number.
Self Documentation String: Indicates Tracer VV550/551 VAV controller.
50 VAV-SVP01A-EN
VAV VV550 Controller Programming and Operation

Entering and Exiting the Service Mode

Controllers must be online and in the service mode to receive an override. The service mode disables control from VAV VV550 Controller and places Rover/Comm5 in command of the controller. Controllers that are in the service mode appear in bold in the device tree on the left side of your screen. More than one controller can be in the service mode at one time.
You can place a controller in the service mode manually or let Rover/Comm5 do so automatically when you start an override. Controllers exit the service mode automatically 15 minutes after the last override or when you manually release them.
To enter the service mode:
1. Connect to the Comm5 link and scan for devices.
2. In the device list on the left side of your screen, double-click the controller that you want to place in the service mode.
3. Click the Enter Service Mode button. While the controller is in the service mode, it appears in bold in the device list.
To exit the service mode, do one of the following:
Wait for 15 minutes (Rover Comm5 does not need to be online with the controller).
For each controller in the service mode, click the Exit Service Mode button.

Overriding VAVs

When you override a controller, Rover Comm5 automatically places the controller in the service mode. The controller is automatically released from the service mode after 15 minutes or when you click the Exit Service Mode button for the device. You can manually release overrides by selecting the appropriate release command in the Override dialog box.
1. On the Tools menu, click Overrides.
2. Select override VAVs.
3. Click the units you want to override.
4. In the list of overrides, click the type of override you want to perform.
5. Click the Override button. The controller automatically enters the service mode and exits the service mode 15 minutes after receiving an override.
Saving VAV Program
Each VAV unit with a VAV VV550 Controller has been factory commissioned with a program that can be saved to your hard drive.
This can be used to save the original program for a backup in case unit needs to be put back to original specifications or to download into a VAV VV550 Controller that has like parameters that has been corrupted.
1. Select the Configure button, and the Configuration screen will appear.
VAV-SV P01A-E N 51
VAV VV550 Controller Programming and Operation
Figure 38. Configuration screen (save as)
2. Click the File menu and click Save As.
3. The Save As dialog box will appear. Name unit and click Save.
Figure 39. Save As prompt
Downloading Program Files from PC to VAV VV550 Controller
1. Select the Configure button, and the Configuration screen will appear
52 VAV-SVP01A-EN
VAV VV550 Controller Programming and Operation
Figure 40. Configuration screen (open)
2. Click the File menu and click Open.
3. The Open dialog box will appear. Select the file you wish to open and click the Open button.
4. Download to DDC VAV controller.
5. Program is now in controller.
Figure 41. Open dialogue box
VAV-SV P01A-E N 53

VAV VV550 Controller Device Home Tabs: Instructions

Chapter Overview

This chapter contains information about the following:
Setpoints Tab
•Unit Tab
•Setup Tab
Inputs Tab
•Outputs Tab
•Test Tab
•Other Tab

Configuration

To access the data fields for each tab and to make adjustments, select the Configure button. To make adjustments, find the correct parameter, change it, and download to VV550.

Setpoints Tab

Figure 42. Setpoints tab
In Rover, the setpoints can be changed by selecting the Configure button. Following are descriptions of each line on the Setpoints tab.
Default Setpoints
Unoccupied Cooling: Set points have a range of 30.0° - 100.0°F (-1.1° - 37.8°C). This cooling set point is used when the VAV VV550 Controller is unoccupied. The unoccupied cooling set point must be greater than or equal to the unoccupied heating set point plus 2.0°F 1.1°C).
54 VAV-SVP01A-EN
VAV VV550 Controller Device Home Tabs: Instructions
Occupied Standby Cooling: Based on the controller occupancy mode, the active space cooling setpoint is the occupied stand by cooling setpoint, The controller can be placed in the occupied standby mode when a communicated occupancy mode request (from a communicated occupancy override, occupancy schedule, or occupancy sensor) is combined with an occupancy request from the local (hardwired) occupancy binary input.
Note: This setpoint allows inactive spaces in the occupied mode to float to a more energy saving
setpoint until occupancy mode deems it necessary to use another setpoint as its active setpoint.
Occupied Cooling: Set points have a range of 30.0°- 100.0°F (-1.1° - 37.8°C). If a zone sensor thumbwheel set point is not being used, this set point will be used as the VAV VV550 Controller's active cooling set point during occupied times. The cooling set point must be greater than or equal to the heating set point plus 2.0°F (1.1°C).
Note: Occupied cooling and heating set points must be set within the cooling set point high limit
and the heating set point low limit in order to control to the proper setpoints.
Occupied Heating: Set points have a range of 30.0°- 100.0°F (-1.1° - 37.8°C). If a zone sensor thumbwheel set point is not being used, this set point will be used as the VAV VV550 Controller's active heating set point during occupied times. The cooling set point must be greater than or equal to the heating set point plus 2.0°F (1.1°C).
Note: Occupied cooling and heating set points must be set within the cooling set point high limit
and the heating set point low limit in order to control to the proper setpoints.
Occupied Standby Heating: Based on the controller occupancy mode, the active space heating setpoint is the occupied stand by heating setpoint, The controller can be placed in the occupied standby mode when a communicated occupancy mode request (from a communicated occupancy override, occupancy schedule, or occupancy sensor) is combined with an occupancy request from the local (hardwired) occupancy binary input.
Note: This setpoint allows inactive spaces in the occupied mode to float to a more energy saving
setpoint until occupancy mode deems it necessary to use another setpoint as its active setpoint.
Unoccupied Heating: Set points have a range of 30.0° - 100.0°F (-1.1° - 37.8°C). This heating set point is used when the VAV VV550 Controller is unoccupied. The unoccupied cooling set point must be greater than or equal to the unoccupied heating set point plus 2.0°F 1.1°C).
Active Setpoint
Space Temperature: The Active Space Temperature can be either from a local analog input, as measured by the zone sensor, or as a remote communicated value. If both are present, the controller uses the communicated value. The controller uses the network variable output space temperature to report the space temperature value that it is using.
Active setpoint: The set point cannot be edited and reflects the set point currently being used for Heating/Cooling temperature control. The Active Space Setpoint can be either from a local analog input, as measured by the zone sensor, or as a remote communicated value. If both are present, the controller uses the communicated value. The controller uses the network variable output Effective setpoint to report the space active setpoint value that it is using.
Airflow: The airflow measured by the airflow sensor in the VAV box.
Setpoint Limits:
After the controller completes all setpoint calculations, the calculated occupied setpoint is validated against the following configured space setpoint limits:
Cooling Setpoint High Limit
Cooling Setpoint Low Limit
Heating Setpoint High Limit
VAV-SV P01A-E N 55
VAV VV550 Controller Device Home Tabs: Instructions
Heating Setpoint Low Limit
These setpoint limits apply only to the occupied and occupied standby, heating and cooling setpoints. They do not apply to the unoccupied heating and cooling setpoints. When the controller is in the unoccupied mode, it always uses the unoccupied heating and cooling setpoints. Unit configuration enables or disables the local (hardwired) setpoint. This parameter provides additional flexibility to allow you to apply communicated, hardwired, or default setpoints without making physical changes to the unit. Similar to hardwired setpoints, the effective setpoint value for a communicated setpoint is determined based on the stored default setpoints, configuration values, and the controller occupancy mode.
Freeze Avoidance
Outdoor Air Low Limit: Units with hot water coils installed are susceptible to freezing. Measures must be taken to prevent the water coils from freezing. Freeze protection occurs only when the controller is in the Off state or during the unoccupied period when the primary air valve is closed and the reheat is disabled. During occupied operation, the control algorithm indirectly provides freeze protection.
Note: On Ventilation Flow control mode with hot water only
Additional Fields
Enable Thumbwheel Setpoints: Unit configuration enables or disables the local (hardwired) setpoint. This parameter provides additional flexibility to allow you to apply communicated, hardwired, or default setpoints without making physical changes to the unit. If the thumbwheel is not enabled, locally generated overrides (maximum flow or minimum flow) are not possible.
Enable Thumbwheel Star and Double Star Function: Single star and double star airflow override capability can be disabled through configuration, while leaving the thumbwheel local setpoint enabled. Positioning the thumbwheel at the single star (*) generates an override to cooling minimum flow. The override is enabled when the setpoint is greater than 88°F (31.11°C) and disabled when the setpoint is less than 87.7°F (30.94°C).
Positioning the thumbwheel at the double star (**) generates an override to cooling maximum flow. The double star function is enabled when the setpoint is less than 48.5°F (9.17°C) and disabled when the setpoint is greater than 50°F (10°C).
There is no effect on the fan and the reheat operation during the single star and double star thumbwheel airflow overrides. When the single star and double star thumbwheel airflow overrides are active, the default space setpoints are used, the reported local setpoint reports the invalid value. Setpoint values outside of the valid setpoint range (50°F to 85°F [10.0°C to 29.44°C]) are not used.
Enable Auto calibration: Calibration takes place if this auto calibration feature is enabled and either a power cycle or a transition from occupied to unoccupied has occurred. The building automation system is responsible for the staggering of the calibration sequence that is needed between units. When auto-calibration is enabled and a transition from occupied to unoccupied occurs, the calibration sequence starts after a fixed delay of three minutes. The controller effective occupancy mode is unoccupied, but runs like it is occupied during this three-minute period. The mode field of reported unit status reports shows when the controller is in the calibration sequence.
56 VAV-SVP01A-EN

Unit Tab

Figure 43. Unit tab
VAV VV550 Controller Device Home Tabs: Instructions
In Rover, the Unit Tab can be changed by selecting the Configure button. Following are descriptions of each line on the Unit tab.
Unit Configuration
This allows for selection between three operational programs. The three programs are Space Temperature, Ventilation Flow, and Flow Tracking
Note: See Operation chapter fore details on operational programs.
Default Primary Air Temperature
The selections are cooling or heating. The controller default operation (auto) can place the unit in heating or cooling mode. When the controller automatically determines the heating or cooling mode, the unit switches to the desired mode based on the primary air temperature.
Note: It can also be done with a communicated request.
Primary Air Setup
Auto Changeover Setpoint: The auto change over set point allows for switching from heating to cooling operation with the vav) If primary air temperature greater than the configured auto changeover setpoint, then primary air temperature is. (Primary air is hot enough for heating and reheat can be used.) If primary air temperature < configured auto changeover setpoint - 10°F (5.56°C), then primary air temperature is cold. (Primary air is cold enough for cooling and reheat can be used.) No change in hysteresis region.
Reheat Setup
Reheat Enable Setpoint: When the primary air temperature is greater than the configured reheat enable setpoint, reheat is turned OFF until the primary air temperature drops 5°F (2.78°C) below
VAV-SV P01A-E N 57
VAV VV550 Controller Device Home Tabs: Instructions
the configured reheat enable setpoint. The range for the Reheat enable setpoint for Hydronic heat is 70°F to 200°F (21.11°C to 93.33°C) The range for the Reheat enable setpoint for Electric heat is 70°F to 100°F [21.11°C to 37.78°C]).
Reheat Priority: Choices are Local and Remote. This area is available only if the controller is using space temperature control.
• Local: Select this option to use local reheat before remote reheat.
•Remote: Select this option to use remote reheat before local reheat.
Fan Configuration
Fan Present: This dialog box should be checked if the unit has a fan. Rover automatically changes the entry to 0 (None). When the value of this field is not None, the configuration of Output 3 is set to Normally Open.
Fan Type: Select the type of fan used by the VAV VV550 Controller. If you edit the unit type field, Valid Selections: Parallel, Series.
Parallel Fan Control: This entry will determine if a parallel fan will be controlled based on zone temperature or on flow conditions. The entry field on this line will disappear if the unit does not have a parallel fan.
Parallel Fan Setup: If "Parallel fan control" has been edited to "Space Temperature" the fan control offset will be entered as a temperature offset (.3° - 8°F) which will be added to the heating set point. If "Parallel fan control" has been edited to "Primary Flow" this line will be entered as a percent (0 to 100%)
Note: See the Sequence of Operations section of this manual for details on parallel fan operation.
Box Setup: Select the proper Setup type. The selectable item is either a "Trane F style" unit
manufactured by Trane or "Generic" if the VV550 controller is mounted on some one else's VAV unit. The unit type information is maintained in the controller's EEPROM. When Trane F style unit is selected it will also show the inlet size and type in inches. The entry field on this line will disappear if the unit does not have Trane F style unit selected
Note: See CNT-PRC003-EN if retrofitting a VV550/1 controller onto someone else's VAV unit.
58 VAV-SVP01A-EN

Setup Tab

Figure 44. Setup tab
VAV VV550 Controller Device Home Tabs: Instructions
In Rover, the Setup Tab can be changed by selecting the Configure button. Following are descriptions of each line on the Setup tab for the Device Setup.
VAV setu p
Nominal Flow: Nominal flow is the total airflow capacity of the VAV box. Nominal Flow becomes an active field when "Generic" is selected in Box Setup under the Unit Tab. Select the CFM nominal flow for the unit. This is normally used when mounting the VV551 controller on someone else's VAV unit
Note: See CNT-PRC003-EN if retrofitting a VV550/1 controller onto someone else's VAV unit.
Unit Flow Gain: The flow gain is used to calibrate the value reported by the flow sensor so that the reported airflow matches the actual airflow. The flow gain is determined during the air balancing of system. A testing, adjusting, and balancing professional will use the Rover Air and Water Balancing tool to calculate this value and balance the VAV box. Normally, you should not need to change this value here.
Tracking Offset: This field is available only if the controller is using flow tracking control. Type a tracking offset to create a positive or negative pressure in the controlled zone. The tracking offset is added to the airflow setpoint, so a positive offset decreases the pressure in the zone, and a negative offset increases the pressure in the zone. (A positive number decreases the pressure because the flow tracking VAV box is removing air from the space.
Note: See Operation section for an explanation of flow tracking control.
If the flow sensor fails, the controller will control to the minimum flow setpoint if the flow tracking offset is negative and to the maximum flow setpoint if the tracking offset is positive.
Flow Offset: The flow offset is used to calibrate the value reported by the flow sensor so that the reported flow matches the actual flow. The flow offset is determined during the air balancing process. A testing, adjusting, and balancing professional will use the Rover Air and Water
VAV-SV P01A-E N 59
VAV VV550 Controller Device Home Tabs: Instructions
Balancing tool to calculate this value and balance the VAV box. Normally, you should not need to change this value here.
Note: The flow offset is calculated only for two-point balancing, which requires reading both the
maximum and minimum airflows during balancing. Two-point balancing ensure greater accuracy over the entire range of air valve operation. Only controllers that support the Flow Measurement Offset network variable, such as the VAV VV550/551 Controller, can use two­point balancing.
Flow Gain: The flow gain is used to calibrate the value reported by the flow sensor so that the reported airflow matches the actual airflow. The flow gain is determined during the air balancing process. A testing, adjusting, and balancing professional will use the Rover Air and Water Balancing tool to calculate this value and balance the VAV box. Normally, you should not need to change this value here.
Minimum Delta: The minimum amount of change in the primary airflow required before airflow and the airflow setpoint are communicated on the Comm5 link. The percentage of change required is based on the nominal airflow. For example, if the nominal airflow is 1000 cfm and the minimum delta is 2%, the primary airflow must increase or decrease by 20 cfm before the change is communicated on the Comm5 link.
Ventilation Setup
A Tracer Summit building automation system is required for accurate ventilation control. The Tracer Summit VAS Comm5 application calculates the ventilation setpoint and coordinates the air handler and VAV boxes.
Occupied Setpoint: During the occupied mode, this setpoint is the active setpoint for ventilation.
Occupied Standby Setpoint: During the unoccupied mode, this setpoint is the active setpoint
for ventilation.
Space CO2 Setup (CO2 sensor communicated value only)
Low Limit: The controller adjusts the ventilation setpoint only when the CO2 concentration falls within the high and low limits. When the CO2 concentration falls below the low limit, this indicates that the zone is most likely unoccupied and that a minimum of ventilation air is required to ventilate the zone.
High Limit: The controller adjusts the ventilation setpoint only when the CO2 concentration falls within the high and low limits. When the CO2 concentration rises above the high limit, this indicates that the zone is most likely at its maximum design occupancy and that a maximum of ventilation air is required to ventilate the zone.
Flow Setpoints Setup
Minimum Airflow: Although the VAV VV550 Controller will read flow down to 5% of cataloged, the range of MIN FLOW settings is 0%, or 10% to 100% of cataloged. The VAV VV550 Controller will not drive its flow below this minimum flow value under normal operating conditions while in the cool mode. Cool mode occurs when cool air is in the supply duct. The entry in the Cooling Minimum field must be less than or equal to the entry in the Maximum field.
Maximum Airflow: This range is 10% to 100% of the unit's cataloged CFM size. Cooling and heating flow can be edited to zero.The VAV VV550 Controller will not drive its flow above this maximum flow value under normal operating conditions while in the Cool mode. Cool mode occurs when cool air is in the supply duct. The entry for Maximum Flow must be greater than or equal to the entry in any of the Minimum fields.
Standby Minimum Airflow: Occupied standby mode is used to reduce the heating and cooling demands during the occupied hours when the space is unoccupied. It can be activated for a classroom currently not in use. Standby Minimum is the minimum amount of airflow desired during this mode.
60 VAV-SVP01A-EN
VAV VV550 Controller Device Home Tabs: Instructions
Standby Heating Minimum Airflow: Occupied standby mode is used to reduce the heating and cooling demands during the occupied hours when the space is unoccupied. It can be activated for a classroom currently not in use. Standby Heating Minimum is the minimum amount of airflow desired when in the heat mode during this mode.
Heating Minimum Airflow: The VV550 will not drive its position/flow below this value under normal operating conditions while in the HEAT mode (warm air in the supply duct) or while it is using local heat.
Heating Maximum Airflow: The controller enters maximum flow heat on receipt of a communicated command and remains in maximum flow heat until the command changes. The controller maintains the flow rate at the heating maximum airflow. This is normally used with a rooftop unit with staged heat that needs a Max constant volume of air movement to keep the heat exchanger from overheating and tripping the heat in the rooftop unit tripping on a high limit safety.
Local Heat Minimum Airflow: If the Min Local Heat flow is enabled, then the Min Local Heat flow is used to determine the minimum position/flow instead of the Min Heating Flow when local heat is on. The entry for Min Heating Flow must be less than or equal to the entry for the Maximum Flow.
Air Valve Setup
Minimum Position Setpoint: Type the minimum position for the air valve during the pressure dependent mode.
Discharge Air Setup
Discharge Air Setpoint: Type the discharge-air setpoint. This field is available only if you selected ventilation flow control on the Unit tab. When using ventilation flow control and in the occupied mode, the VAV VV550 Controller controls to the active airflow setpoint and modulates the heating capacity to keep the discharge-air temperature at the active discharge-air temperature setpoint.

Inputs Tab

Figure 45. Inputs tab
VAV-SV P01A-E N 61
VAV VV550 Controller Device Home Tabs: Instructions
In Rover, the Inputs tab can be changed by selecting the Configure button. Following are descriptions of each line on the Inputs tab. For a factory-installed VAV VV550 Controller, all inputs and outputs are configured at the factory. For a field-installed VAV VV551 Controller, use this tab to configure the inputs.
Binary Input 1
Select the application used with Binary input 1.
Occupancy: Select this option to use binary input 1 to detect the occupancy mode from an occupancy sensor.
Generic: Select this option to use binary input 1 as a generic input.
Not Used: Select this option if binary input 1 is not used.
Device Contacts Normally Open: Select this check box if the device contacts are normally open.
Analog Input 1
This area displays Space Temperature Sensor when the analog input is connected to a zone sensor. Analog input 1 can be used only to read the space temperature from a zone sensor. The controller can receive the space temperature from either analog input 1 or as a communicated value. If both are present, the controller uses the communicated space temperature.
Analog Input 2
This area displays Space Setpoint when the analog input is connected to a zone sensor. This input can be used only to read the local space temperature setpoint from the zone sensor.
Analog Input 3
This area displays Airflow Sensor when the analog input is connected to an airflow sensor. The controller can operate without a valid airflow value (either hardwired or communicated).
Analog Input 4
Select the application used with analog input 4. The sensor must be a 10 k thermistor.
Primary Supply Air Sensor: Select this option if the sensor measures the primary air temperature. In this case, the sensor must be located upstream from the unit.
The controller can receive the primary air temperature from the analog input or as a communicated value. If both are present, the controller uses the communicated temperature. If neither is present, the controller uses the default primary air temperature defined on the Unit tab (either hot or cold).
Discharge Air Sensor: Select this option if the sensor measures the discharge-air temperature. In this case, the sensor must be located downstream. The controller can operate without a valid discharge-air temperature analog input if configured for space temperature control or flow tracking control. If the controller is using ventilation flow control with reheat, the unit shuts down if there is no valid discharge-air temperature. A ventilation flow control unit without reheat operates normally without a valid discharge-air temperature.
62 VAV-SVP01A-EN

Outputs Tab

Figure 46. Outputs tab
VAV VV550 Controller Device Home Tabs: Instructions
In Rover, the Outputs Tab can be changed by selecting the Configure button. Following are descriptions of each line on the Outputs tab. For the factory-installed VAV VV550 Controller, all inputs and outputs are configured at the factory. For the field-installed VAV VV551 Controller, click the Start button to configure the outputs.
Binary Output 1
Binary output 1 is used to drive the air valve closed. It works in conjunction with binary output 2 to modulate the air valve.
Binary Output 2
Binary output 1 is used to drive the air valve open. It works in conjunction with binary output 1 to modulate the air valve.
Output Configuration Wizard
Click the Start button to configure the outputs.
Binary Output 3& 4
This output can be configured for:
Hot-water on/off control
Hot-water modulating (3-wire) valve control (requires outputs 3 and 4)
Electric-heat staged or pulse width modulation
The output is automatically configured based on your answers in the Output Configuration Wizard.
Device Contacts Normally Open: Select this check box if the device contacts are normally open. This check box is available only for hot-water on/off control.
VAV-SV P01A-E N 63
VAV VV550 Controller Device Home Tabs: Instructions
Binary Output 5
This output can be configured for:
Parallel or series fan on/off control
Hot-water on/off control
Electric-heat staged or pulse width modulation
The output is automatically configured based on your answers in the Output Configuration Wizard.
Device Contacts Normally Open: Select this check box if the device contacts are normally open. This check box is available only for hot-water on/off control.

Test Tab

Figure 47. Test tab
Use the Test tab to exercise the binary outputs and verify that they are working correctly.
To perform a manual output test:
1. Click the Start button.
2. Click the Next Step button repeatedly to step through the test.
3. Click the Cancel button to stop the test.
64 VAV-SVP01A-EN

Other Tab

Figure 48. Other tab
VAV VV550 Controller Device Home Tabs: Instructions
In Rover, the Other Tab can be changed by selecting the Configure button. Following are descriptions of each line on the Other tab. Use this tab to calibrate sensors and set up timers.
Calibration
Space Temperature Sensor: Use this area to calibrate the space temperature. The effective value is the result of the space temperature used by the controller plus the offset value. In the Offset field, type a negative or positive number to offset the space temperature.
Hardwired Setpoint: Use this area to calibrate the setpoint from the zone sensor. The effective value is the result of the raw value of the hardwired setpoint plus the offset value. In the Offset field, type a negative or positive number to add to the hardwired setpoint. After calibration, the effective value should match the value indicated on the zone sensor thumbwheel.
Stroke Times
Primary Air Valve: Type the amount of time required to drive the air valve from fully open to fully closed or vice versa. For field-installed VAV VV551 Controllers, this value must be changed to match the specifications of the air valve.
Water Valve: Type the amount of time required to drive the water valve from fully open to fully closed or vice versa. For field-installed VAV VV551 Controllers, this value must be changed to match the specifications water valve.
Timers
Manual Override Time: Type the amount of time that the controller will remain in override. After this time passes, air- and water-valve overrides are released automatically. Fan overrides do not release automatically.
VAV-SV P01A-E N 65
VAV VV550 Controller Device Home Tabs: Instructions
Occupied Bypass Timer: Type the amount of time that the controller remains in the occupied bypass mode. If the controller is in the unoccupied mode and an occupant presses the On button at the zone sensor, the controller goes into occupied bypass mode for this amount of time.
Power-up Control Wait: Type the number of seconds you want the controller to wait after startup before starting normal operation. When power-up control wait is enabled (whenever a time is entered here), the controller remains off until one of two conditions occurs:
Controller receives communicated information on the Comm5 link
Power-up control wait time expires
Note: If auto calibration is enabled, the controller will calibrate during power-up control wait.

Overrides

Figure 49. Overrides
To access the data fields for each tab and to make adjustments, select the Overrides button.
In the Override list, select the valve or fan you want to override. The types of overrides you can perform change based on your selection.
Change/Override
In the Change/Override area, select the type of override you want to perform, then click the Override button.
Override button: Click this button to start the override.
Release button: Click this button to release any existing overrides for the VAV VV550 Controller.
If you do not release the overrides here, the controller automatically releases them after 10 hours by default for air valves and water valves. You can change this default in the Timers area on the Other tab in the Configuration dialog box. The controller does not automatically release fan overrides.
Close button: Click this button to exit the Device Overrides dialog box.
66 VAV-SVP01A-EN

Sequence of Operations

Chapter Overview

This chapter contains information about the following:
Calibration
Occupancy Modes
Space Temperature Control: Single Duct Units
Space Temperature Control: Fan-Powered Units
Ventilation Flow Control
•Flow Tracking
Normal Operation
The controller is functioning normally when it is operating in one of the three control modes (space temperature control, ventilation control, or flow tracking control) and in one of four occupancy modes (occupied mode, unoccupied mode, occupied standby mode, or occupied bypass mode).
Note: For More detail on control modes and units operation see CNT-SVX17*-EN.

Calibration

The calibration sequence enables the controller to calibrate the air valve position and the water valve position. Calibration takes place if autocalibration is enabled and either a power cycle or a transition from occupied to unoccupied has occurred.
Note: Whether or not autocalibration is enabled, the controller initiates calibration on a
communicated application mode command.
The building automation system is responsible for the staggering of the calibration sequence that is needed between units. When autocalibration is enabled and a transition from occupied to unoccupied occurs, the calibration sequence starts after a fixed delay of three minutes. The controller effective occupancy mode is unoccupied, but runs like it is occupied during this three minute period. The mode field of reported unit status reports calibration when the controller is in the calibration sequence. If autocalibration is disabled, the air valve and water valve are not driven closed and the flow sensor zero flow voltage reading is not recorded. Refer to Table 10, p. 67 for calibration actions.
Table 10. Calibration actions
I/O Device Calibration Action Taken Result After Calibration
Air valve Drive the air valve closed to the stroke time plus 20 seconds
Flow sensor Record the flow reading when the air valve is fully closed
Modulating hot water reheat Drive the water valve closed for the stroke time plus 20 seconds
Fan Ena bled Ena bled
Electric or On/Off hot water Disabled Enabled
VAV-SV P01A-E N 67
initialize the air valve position as closed when the air valve is over-driven
Subtract the zero flow reading from all subsequent readings
initialize the water valve position as closed when the water valve is over-driven
Sequence of Operations

Occupancy Modes

VAV VV550 Controllers have four valid occupancy modes: Occupied, Unoccupied, Occupied standby, and Occupied Bypass.
Occupied Mode
Occupied mode is the normal (default) operating mode for occupied spaces or daytime operation. When the controller is in the occupied mode, it uses occupied setpoints and runs in:
Occupied temperature control;
Ventilation flow control or space temperature control;
Flow tracking control.
Unoccupied Mode
Unoccupied mode (also known as night setback) is the normal operating mode for unoccupied spaces or nighttime operation. Unoccupied setpoints enable or disable occupied space temperature control.
When the controller is in the unoccupied mode and configured for space temperature control, the controller attempts to keep the space temperature between the active unoccupied heating setpoint and the active unoccupied cooling setpoint. When the controller is in the unoccupied mode and configured for ventilation flow control, it will not run in unoccupied mode, the air valve is closed, and local heat is disabled.
A flow tracking controller runs the same as when it is occupied. When the controller is in the unoccupied mode and configured for flow tracking control, it runs the same as it does in occupied mode.
Occupied Standby Mode
Occupied standby mode is used to reduce the heating and cooling demands during the occupied hours when the space is unoccupied. It can be activated for a classroom currently not in use.
The controller can be placed in the occupied standby mode when a communicated occupancy mode request (from a communicated occupancy override, occupancy schedule, or occupancy sensor) is combined with an occupancy request from the local (hardwired) occupancy binary input. Once in occupied standby mode, the controller uses the occupied standby cooling and heating setpoints, which typically cover a wider range than the occupied setpoints. The wider range reduces the demand for heating and cooling in the space.
When the communicated occupancy mode request is unoccupied, the occupancy binary input signal (if present) does not affect the controller occupancy mode. When the communicated occupancy mode request (communicated occupancy override not valid, communicated occupancy schedule occupied, or communicated occupancy sensor not valid) is occupied, the controller uses the local occupancy binary input to switch between the occupied and occupied standby modes. When the controller is in the occupied standby mode, it uses occupied standby setpoints and runs in:
Occupied temperature control;
Ventilation flow control or space temperature control;
Flow tracking control.
Occupied Bypass Mode
Occupied bypass mode is used for timed overrides. For example, if the controller is in unoccupied mode or occupied standby mode, pressing the zone sensor ON button places the controller in occupied bypass mode for 120 minutes (default configured occupied bypass time) or until someone presses the zone sensor CANCEL button. The controller can be placed in occupied bypass
68 VAV-SVP01A-EN
mode by either communicating an occupancy mode request of bypass mode (communicated occupancy override) to the controller or by using the zone sensor timed override ON button. The occupied bypass mode and the occupied mode operate similarly.
When the controller is in the unoccupied mode, pressing the zone sensor ON button places the controller in the occupied bypass mode for the duration of the configured occupied bypass time.
When the controller is in the occupied standby mode, pressing the zone sensor ON button places the controller in the occupied bypass mode for the duration of the configured occupied bypass time.

Space Temperature Control: Single Duct Units

Space temperature control (STC) is one of three supported control algorithms. Space temperature control requires a valid space temperature. If there is no valid space temperature (communicated or local), the space temperature control algorithm does not run; the unit either shuts down or goes to construction mode.
VAV VV550 Controllers use the active space temperature to maintain the space temperature at the active space cooling setpoint or the active space heating setpoint.
The controller heat/cool mode is determined by either a communicated request or by the controller itself, when the heat/cool mode is auto. When the heat/cool mode is auto, the controller compares the primary air temperature with the configured auto-changeover setpoint to determine if the primary air is hot or cold. This is called autochangeover. This determination may differ from the reported heat/cool mode, which matches the zone demand.
The control compares the active space setpoint and the active space temperature and calculates the desired capacity. The control positions the modulating air valve to deliver the desired airflow (cooling or heating capacity).
Sequence of Operations
Cooling Operation
Under space temperature control during the cooling mode (communicated heat/cool mode is cool), the controller attempts to maintain the active space temperature at the active space cooling setpoint. Based on the controller occupancy mode, the active space cooling setpoint is either the occupied cooling setpoint, the occupied standby cooling setpoint, or the unoccupied cooling setpoint.
The outputs are controlled based on the unit configuration and the required cooling capacity. At 0% required cooling capacity, the air valve is closed or at the active minimum flow setpoint. As the required cooling capacity increases, the air valve opens above the minimum position. At 100% required cooling capacity, the air valve opens to the maximum position or to the active maximum flow setpoint.
All units have a modulating air valve. The modulating air valve is used to control the volume of air flowing through the diffusers and into the space. Modulating the volume of air modulates the unit cooling capacity.
Also, units may have local or remote reheat. The reheat may be hydronic or electric. Reheat is allowed to turn On when the space temperature is below the heating setpoint
Heating Operation
Under space temperature control, during the heating mode (communicated heat/cool mode is heat), the controller attempts to maintain the space temperature at the active heating setpoint. Based on the controller occupancy mode, the active space heating setpoint is either the occupied heating setpoint, the occupied standby heating setpoint, or the unoccupied heat setpoint. All ventilation requirements are in force during occupied heating and cooling.
The outputs are controlled based on the unit configuration and the required heating capacity. At 0% required heating capacity, the air valve is at its minimum flow setpoint. As the required heating
VAV-SV P01A-E N 69
Sequence of Operations
capacity increases, the air valve opens above its minimum position. At 100% required heating capacity, the air valve opens to its maximum position.
All units have a modulating air valve. The modulating air valve is used to control how much air is flowing through the diffusers and into the space. By modulating the volume of air flowing, the unit heating capacity is modulated.
Units may also have local or remote reheat. This reheat may be hydronic or electric. Reheat is used to maintain the space temperature at the heating setpoint.
Note: Heating operation and Reheat are to different entities.
Air Valve Control in Space Temperature Control Operation
Air delivered to the space is controlled with a three-wire floating-point actuator that modulates the air valve. The controller positions the modulating air valve to deliver the desired airflow (cooling or heating capacity). The desired airflow is called the active-flow setpoint. The controller positions the modulating air valve to deliver the desired airflow (cooling and heating capacity) to within +/
-2% of nominal airflow.
The airflow control algorithm compares the active airflow setpoint with the measured airflow and calculates the necessary air valve movement to minimize error. The airflow setpoint is limited by applicable minimum and maximum flow setpoints.
Reheat Control
There are two types of reheat control: hydronic heat and electric heat. Reheat is allowed to turn On if the zone temperature is below the heating setpoint. Space temperature control can use reheat if the following conditions are all true:
The unit is not calibrating;
Reheat is enabled (communicated auxiliary heat enable);
For local reheat only, the fan, if present, is not being overridden to Off (communicated fan speed command);
The primary air temperature is less than the configured reheat enable setpoint (5°F [2.78°C]);
Local heat minimum airflow is used for both local and remote reheat.
Electric Heat
Pulse-Width Modulation of Electric Heat
One to three stages of pulse-width modulation of electric heat are available on single duct units and fan powered units up to two stages are available for PWM heat control. Energizing for a portion of a three-minute time period modulates the electric heater. This allows exact load matching for energy efficient operation, and optimum zone temperature control. The heating minimum airflow setpoint is enforced during reheat. The amount of reheat supplied is dependent on both the degree that the space temperature is below the active heating setpoint and the time that the space temperature has been below the active heating setpoint. If not already off, reheat de-energizes when the zone temperature rises more than 0.5°F (0.28°C) above the heating setpoint.
The Stage 1 "on" time is proportional to the amount of reheat required. For example, when 50% of stage 1 capacity is required, reheat is on for 90 seconds and off for 90 seconds. When 75% of stage 1 capacity is required, reheat is on for 135 seconds and off for 45 seconds. When 100% of stage 1 capacity is required, reheat is on continuously.
Stage 2 uses the same "on" time logic as stage 1 listed above, except stage 1 is always energized. For example, when 75% of unit capacity is required, stage 1 is energized continuously, and stage 2 is on for 90 seconds and off for 90 seconds. When reheat is deenergized, the cooling minimum airflow setpoint is activated.
Important: Leaving air temperatures (LAT) should not exceed 100°-110°F, with 95°F being the
optimal for zone temperature and comfort control. At elevated LATs, room
70 VAV-SVP01A-EN
Sequence of Operations
stratification may result in uneven air distribution and zone temperature complaints. See Table 11, p. 72 for single duct reheat operation and Table 12, p. 72 for fan powered reheat operation.
On/Off Electric Reheat
One, two, or three stages of staged electric reheat are available on single duct units and two sages of electric heat are available on fan powered units. The heating minimum airflow setpoint is enforced during reheat.
Stage 1 is energized when the space temperature falls below the active heating setpoint and minimum airflow requirements are met. When the zone temperature rises above the active heating setpoint by 0.5°F (0.28°C), stage 1 is de-energized.
Stage 2 energizes when the space temperature is 1°F (0.56°C) or more below the active heating setpoint, and is de-energized when the space temperature is 0.5°F (0.28°C) below the active heating setpoint.
Stage 3 energizes when the zone temperature is 2°F (1.11°C) or more below the active heating setpoint, and de-energizes when the space temperature is 1.5°F (0.83°C) below the active heating setpoint.
When reheat is de-energized, the cooling minimum airflow setpoint is activated. See Table 11 , p . 7 2 for single duct reheat operation and Table 12, p. 72 for fan powered reheat operation.
Hot Water Heat
Two types of control of hydronic heat are supported: On/Off and modulating.
Note: Steam is not supported.
Hydronic heat is enabled if there is no valid primary air temperature. Hydronic heat is disabled if the primary air temperature is greater than the configured reheat enable setpoint.
ON/Off Hot Water Heat
Refer to staged electric heat for operation. Difference is we are controlling a two position hot water valve instead of contactor energizing an electric heat strip. See Ta bl e 11 , p. 7 2 for single duct reheat operation and Table 12, p. 72 for fan powered reheat operation.
Proportional Hot Water Reheat
Proportional hot water reheat uses 3- wire floating-point-actuator technology. It is the same operation for single duct units as it is for fan powered units. The heating minimum airflow setpoint is enforced during reheat. The water valve opens as space temperature drops below the heating setpoint. A separate reheat proportional plus- integral control loop from that controlling airflow into the room is enforced. Water valve position is dependent on the degree that the space temperature is below the active heating setpoint and the time that the space temperature has been below the active heating setpoint. If not already closed, the water valve fully closes when the zone temperature rises above the active heating setpoint by 0.5 °F (0.28 °C). An additional on/off remote heat output is available and energized when the proportional valve is driven 100% open and de­energized when the proportional valve reaches 50% open. When reheat is de-energized, the cooling minimum airflow setpoint is activated See Table 11, p. 72 for single duct reheat operation and
Ta ble 12, p. 7 2 for fan powered reheat operation.
VAV-SV P01A-E N 71
Sequence of Operations
Table 11. Local heat only with no fan present
Configuration Method of control
Local Remote Stage 1 Stage 2 Stage 3
PWM electric (1 to 3 stages)
On/Off electric (1 to 3 stages)
On/Off hot water (1 stage)
Modulating hot water
Note: Abbreviations: Zt = Zone temperature; HSP = Heating setpoint
Not applicable Local PI capacity loop
Not applicable Local thermostatic
Not applicable Local thermostatic
Not applicable Local PI capacity loop
Each stage represents an equal percentage of total capacity PWM Output (one stage = 100%; two stages = 50% each; three stages = 33.33% each). Total capacity is limited by communicated auxiliary heat enable.
On: Zt < HSP Off: Zt
HSP + 0.5°F (0.28°C)
Each stage represents an equal percentage of total capacity. Total capacity is limited by communicated auxiliary heat enable.
On: Zt < HSP Off: Zt
HSP + 0.5°F (0.28°C)
Total capacity is limited by communicated auxiliary heat enable.
Modulating valve capacity = Total capacity Valve drive Incrementally open/closed Total capacity limited by communicated auxiliary heat enable
Local thermostatic On: Zt < HSP - 1°F (0.56°C) Off: Zt
HSP - 0.5°F (0.28°C)
Not applicable Not applicable
Not applicable Not applicable
Local thermostatic On: Zt < HSP - 2°F Off: Zt
HSP - 1.5°F
Not applicable
Table 12. Local heat only with parallel/series fans present
Configuration Method of control
Local Remote Stage 1 Stage 2 Stage 3
Fan Not applicable Parallel/Series Fans Not applicable Not applicable
Fan + PWM electric (1 to 2 stages)
Fan + On/Off electric (1 to 2 stages)
Fan + On/Off hot water (1 to 2 stages)
Fan + Modulating hot water
Note: Abbreviations: Zt = Zone temperature; HSP = Heating setpoint
Not applicable Parallel/Series Fans Local PI capacity loop
Not applicable Parallel/Series Fans Local thermostatic
Not applicable Parallel/Series Fans Local thermostatic
Not applicable Parallel/Series Fans
Each stage represents an equal percent of total capacity (1-stage = 100%, 2 stages = 50% each) PWM output
Total capacity is limited by communicated auxiliary heat enable.
On: Zt < HSP - 1°F (0.56°C) Off: Zt
HSP - 0.5°F (0.28°C)
Each stage represents an equal percentage of total capacity. Total capacity is limited by communicated auxiliary heat enable.
On: Zt < HSP - 1°F (0.56°C) Off: Zt
HSP - 0.5°F (0.28°C)
Total capacity is limited by communicated auxiliary heat enable
Local PI capacity loop Modulating valve capacity = Total capacity Valve drive incrementally open/closed Total capacity limited by communicated auxiliary heat enable
Local thermostatic On: Zt < HSP - 2°F (1.11°C) Off: Zt HSP - 1.5°F (0.83°C)
Not applicable
Not applicable

Space Temperature Control: Fan-Powered Units

VAV VV550/VV551 Controllers provide three fan options when in space temperature control mode:
One-speed ON/OFF series fan;
One-speed ON/OFF parallel fan;
Fan Off Delay
72 VAV-SVP01A-EN
Series Fan
Sequence of Operations
This Comm5 controller supports an Electronically Commutated Motor (ECM). The controller turns the ECM fan On and Off. It does not change the ECM fan airflow. To assist with flow balancing the fan flow rate is stored as a configuration item.
The series fan is always controlled as a one-speed ON/OFF fan. The fan operates continuously in the occupied or occupied standby mode. The fan cycles ON and OFF with calls for heating or cooling in the unoccupied mode. The series fan operates in a manner that prevents reverse rotational operation. The series fan is turned ON whenever one of the following occurs:
Target airflow control point is greater than zero;
Target air valve position is not closed;
Actual air valve position is not closed.
Series fan operation during calibration
During calibration, the series fan is OFF unless the power-up control wait timer reaches zero. When the power-up control wait timer reaches zero, the controller uses the normal series fan control logic. The series fan is turned OFF for 10 seconds during calibration after the air valve closes all the way. And, it remains OFF after the 10 seconds expires if:
Power-up control wait time is still active;
System mode (communicated application mode or communicated heat/cool mode) is ON;
Effective occupancy mode is unoccupied.
Otherwise the series fan is turned ON when the 10-second period expires.
Parallel Fan
The parallel fan is the first stage of heat. When the primary air temperature is cold, the parallel fan:
Cycles ON as the first stage of heat during occupied mode or occupied standby mode;
Cycles ON with a call for heat during unoccupied mode.
When the primary air temperature is warm or hot, the parallel fan is OFF unless the local reheat is ON. Two methods of control are supported for energizing the parallel fan. One method is based on space temperature; the other method is based on primary airflow. The parallel fan start points for each method of control are able to be configured.
Parallel fan start based on space temperature
The parallel fan turns ON when the space temperature falls below the heat setpoint plus the configured parallel fan delta temperature enable setpoint. It turns OFF when the space temperature rises above the heat setpoint plus the configured parallel fan delta temperature enable setpoint by
0.5°F (0.28°C).
Parallel fan start based on primary airflow
The parallel fan turns ON when the primary airflow falls below the configured parallel fan airflow enable setpoint or the primary airflow is less than the active minimum flow setpoint plus 2% of the configured nominal airflow. The parallel fan turns OFF when the primary airflow rises above the configured parallel fan airflow enable setpoint plus 5% of the configured nominal airflow and the primary airflow is greater than the active minimum flow setpoint plus 5% of the configured nominal airflow. In pressure dependent mode, the air valve position is substituted for the primary airflow.
Parallel fan operation during calibration
During calibration, the parallel fan is in the same state (ON or OFF) as it was before calibration started. It remains in that state until one minute after calibration ends. One minute after calibration ends, normal control of the parallel fan resumes. The one-minute period is ignored if reheat is active or if the parallel fan is overridden.
VAV-SV P01A-E N 73
Sequence of Operations
Fan Off Delay
There is a 15-second fan OFF delay. When reheat is turned OFF, the controller turns the fan OFF 15 seconds later.

Ventilation Flow Control

Ventilation flow control (VFC) is one of three supported control algorithms. It is applied to a VAV terminal and used to temper cold outdoor air (OA) that is brought into a building for ventilation purposes. The tempered air is intended to supply an air-handling unit (AHU), which provides comfort control to the zones it is serving. The VAV terminal supplies the correct amount of ventilation air and, when possible, tempers the ventilation air to reduce the load on the air handler. See Table 13, p. 74 for ventilation flow control output control.
Table 13. Ventilation flow control outputs
Occupancy mode Source temperature Air valve control Reheat control
Electric VFC staged reheat control
Staged hot water VFC staged reheat control
Modulating hot water
Electric Off
Staged hot water Off
Modulating hot water Off
Electric Off
Staged hot water
Modulating hot water
Occupy standby bypass
Unoccupied
Any
Communicated source temperature (if valid; if not valid, discharge air temperature) greater than configured OA low limit
Communicated source temperature (if valid; if not valid, discharge air temperature) less than configured OA low limit
Constant volume (if valid, communicated ventilation setpoint; if not valid, configured ventilation setpoint)
Closed, 0%
Closed, 0%
VFC modulating reheat control (same as STC capacity control)
On, 100% freeze protection
On, 100% freeze protection
The ventilation flow control process is a constant volume, variable temperature process.
Single duct VAV units with either electric or hot water reheat are used. Fan-powered units are not used for ventilation flow control.
Ventilation flow control must have an auxiliary temperature sensor that is located and configured as a discharge air temperature (DAT) sensor. The required range of discharge air temperature setpoints is 45°F to 70°F (7.22°C to 21.11°C).
Ventilation flow control staged reheat control (electric or hot water) achieves a 30-minute average discharge air temperature to within ±5°F (±2.78°C) of the discharge air temperature setpoint when the inlet temperature is within the control range. Ventilation flow control modulating reheat control (hot water only) achieves a discharge air temperature to within ±5°F (±2.78°C) of the discharge air temperature setpoint when the inlet temperature is within the control range.
Air Valve Control
Ventilation flow control uses the air valve as a constant volume device. The unit is given a constant flow setpoint for air valve control (configured ventilation setpoint); the air valve only repositions itself in response to changes in inlet static pressure. By using pressure independent control for ventilation purposes, a constant volume of fresh air can be maintained, regardless of small fluctuations in inlet static pressure. Ventilation flow control unit can use a Ventilation Setpoint from a BAS system if it is valid. If unit is stand alone the ventilation flow control uses one of the following two airflow setpoints:
If no reheat being used, it uses the configured Ventilation Setup Occupied Setpoint;
If reheat being used, it uses the configured Local Heat Minimum Airflow.
74 VAV-SVP01A-EN
Sequence of Operations
Staged Reheat Control (Electric and Hot Water)
The heat outputs of the controller are binary. Only discrete levels of discharge air temperature are possible. Since discrete discharge air temperature levels do not always provide an instantaneous temperature within the required band, staged reheat controls to a 30-minute average discharge air temperature. The discharge air temperature setpoint is limited from 20°F to 70°F.
Staged Electric Reheat Control
Units that are equipped with electric reheat should be sized so that the maximum temperature rise across the heating elements is 40°F to 48°F (22.22°C to 26.67°C); it should never exceed 50°F (27.78°C) for safety reasons. These values were selected to allow the largest control range without damage to the heater elements. Figure 14, p. 75 shows the achievable control range for ventilation flow control staged electric heat.
Table 14. Ventilation flow control staged electric heat achievable control rang
Minimum OAT for control DAT Setpoint
Some tempering is possible Achievable control range No Control possible No cooling capacity
DAT setpoint cannot be achieved
Cold OAT temperature range Hot
For staged electric ventilation flow control, the number of installed stages can range from one to three. Three stages are recommended, since finer control is available with more stages. In cases where the outdoor air temperature is more than 48°F (26.67°C) below the discharge air temperature setpoint, the controller cannot provide the requested control performance.
The controller provides no cooling capacity. If the outdoor air temperature (OAT) is above the discharge air temperature setpoint, the discharge air temperature cannot be controlled and the discharge air temperature is equal to the OAT.
Maximum
T=50°F (27.78°C)
(Electric heat only)
DAT = OAT
Staged Hot Water Reheat Control
Units equipped with hot water coils should be sized so the maximum temperature of air leaving the coil does not exceed 140°F (60°C F). Since only one stage of hot water reheat is available, staged hot water does not allow tight control of the discharge air temperature. Although the controller operates in this configuration, it is not recommended.
Staged Reheat Control Algorithm (Integral Only)
An incremental form of the integral PID algorithm computes the desired level of reheat capacity. The algorithm is run once every 10 seconds.
Modulating Reheat Control (Hot Water Only)
Units equipped with hot water coils should be sized so the maximum temperature of air leaving the coil does not exceed 140°F (60°C). If hot water reheat is installed, the preferred method of control is with a modulating valve. The modulating valve enables an instantaneous discharge air temperature within the dead band of the discharge air temperature setpoint. The reheat capacity algorithm for modulating hot water discharge air temperature control is the same algorithm used to control modulating hot water valves for a space temperature controller.
Modulating Reheat Control Algorithm (Proportional-Integral)
An incremental form of the proportional integral algorithm runs once every 10 seconds and calculates the reheat capacity required to meet the discharge air temperature setpoint. The required capacity is equal to valve position.
VAV-SV P01A-E N 75
Sequence of Operations
Freeze Protection (Hot Water Only)
Units with hot water coils installed are susceptible to freezing. It is important to prevent the water coils from freezing. Freeze protection occurs only when the controller is in the Off state or during the unoccupied period when the primary air valve is closed and the reheat is disabled. During occupied operation, the control algorithm indirectly provides freeze protection.
Note: See CNT-SVX17*-EN for details on BAS system control of VV550 controller.
Stand-alone Controller Freeze Protection
Controllers operating without communications do not have the source temperature available to them. In these cases, the discharge air temperature sensor is assumed to provide a reasonable representation of the coil temperature at conditions with no airflow if the sensor is close to the coil. If the discharge air temperature, at no airflow, falls below the configured outdoor air low limit, the hot water valve is fully opened. The hot water valve remains open until the discharge air temperature is 10°F (5.56°C) above the configured outdoor air low limit or occupied operation begins. If the communicated source temperature is invalid and the local discharge air temperature sensor has failed, freeze protection is active and the water valve is open.
Unoccupied Ventilation Flow Control
The controller closes the air valve. Local electric heat and hot water heat are disabled. The hot water valves open if needed for freeze protection. The operation of freeze protection for local hot water heat depends on whether the controller is operating as a network controller or a stand-alone controller. Table 15, p. 76 shows unoccupied VFC control freeze protection for hot water reheat.
Table 15. Unoccupied VFC control, freeze protection for hot water reheat
Controller operation Air valve position Condition
Networked and valid communicated source temperature
Stand-alone, coil temperature sensed at discharge air temperature
(a) Place the discharge temperature sensor in close proximity to the hot water coil discharge. The sensor effectively reports coil temperature when there
is no airflow through the coil. Therefore, the coil can be freeze-protected by the discharge air temperature sensor.
(a)
Closed no flow Communicated source temperature greater than configured
Closed no flow
outdoor air low limit
Communicated source temperature less than or equal to configured outdoor air low limit, freeze protection active diagnostic (with 10°F hysteresis)
Discharge air temperature greater than configured outdoor air low limit
Discharge air temperature less than or equal to configured outdoor air low limit, freeze protection active diagnostic (with 10°F hysteresis)
Hot water valve position
Closed
Open to 100%
Closed
Open to 100%

Flow Tracking

Flow Tracking Control Mode
Flow tracking control (FTC) is one of three supported control algorithms. Two VAV VV550 Controllers work together to provide flow tracking control. See Figure 50, p. 77 .The space temperature controller outputs the airflow (reported airflow). The space temperature controller airflow output (reported airflow) is bound to the flow tracking controller airflow setpoint input (communicated airflow setpoint). The flow tracking controller adds the configured airflow tracking offset (positive or negative) to the airflow setpoint (communicated airflow setpoint) and controls the airflow to this setpoint. The flow tracking controller does not require a space temperature sensor or a discharge air temperature sensor. If the calculated airflow setpoint is less than 10% of the configured nominal airflow and the configured airflow tracking offset is less than zero, the air valve is closed. If the calculated airflow setpoint is less than 10% of the configured nominal airflow and the configured airflow tracking offset is greater than or equal to zero, the air valve is positioned
76 VAV-SVP01A-EN
Sequence of Operations
at the configured minimum airflow. The maximum airflow setpoint is limited by the configured maximum airflow.
Air Valve Control in Flow Tracking Control Operation
The VAV VV550 Controllers support one modulating air valve for heating and cooling operation. Air delivered to the space is controlled with a three-wire floating-point actuator that modulates the air valve. The controller positions the modulating air valve to deliver the desired airflow (cooling or heating capacity). The desired airflow is called the active flow setpoint.
Flow tracking control is provided by two controllers working together: space temperature controller and flow tracking controller. The space temperature controller outputs the airflow as reported airflow. The airflow is determined by the airflow setpoint input (communicated airflow setpoint) of the flow tracking controller. The flow tracking controller adds a configured airflow tracking offset (positive or negative) to the communicated airflow setpoint and controls its airflow to this new airflow setpoint.
Reheat Control in Flow Tracking Control Operation
Reheat is not an option on a flow tracking controller.
Unoccupied Flow Tracking Control
In unoccupied control mode, the controller operates the air valve the same as it does in occupied control mode. The controller enters this mode from a communicated command or from a local occupancy sensor.
Figure 50. Flow tracking control
VAV-SV P01A-E N 77

Air and Water Balancing

Chapter Overview

This chapter contains information about the following:
Air Balancing
Rover Air and Water Balancing Tool

Air Balancing

After the unit has been mounted and all electrical and duct connections have been made, the air distribution system should be balanced. The proper variable air volume balancing procedures depend on the type of VAV system used and the options specified on the VariTrane unit. This section will cover the basic balancing procedures and calibrations needed to balance an air distribution system using VariTrane units. This section suggests only one balancing procedure. Since there are many possible air balancing procedures, keep in mind that these procedures are only suggestions.
Note: Before performing these balancing procedures, the calibration command should be
initiated at least 15 minutes prior to the balancing procedure.
System Checkout
Check the VAV system installation for conformity to design.
Walk the entire system from air handling equipment to the terminal unit to determine variations of installation from the plans.
Check for inadvertent obstructions in the ductwork (such as closed fire dampers).
Insure that any turning vanes, filters, and dampers (both volume and fire) are installed in the correct position.
There should be a 1.5 duct diameter long run of straight ducting into the VAV units inlet.
System Setup
Set the outside air dampers to their minimum position.
Start the supply and return air fan(s).
Before balancing the system, ensure that there is enough CFM for all zones.
1. Drive all VAV boxes MAX.
Starting with each individual branch duct, open all the VAV units in that branch duct to the
maximum cooling position.
Note: This can be done using Rover and its Air and Water Balance tool program by giving each
VAV VV550 Controller a "Drive Max " command or by rotating the Zone sensor set point knob to the " * " position, and hold the TOV ON button for two seconds. The damper will remain at its maximum set point until the zone sensor knob is moved back into the normal operating range.
2. Read airflow at the most remote unit. In most systems, this will be the VAV unit located furthest from the fan. This will be the unit in the system that will be critical from an air delivery set point. If airflow is not adequate, increase the supply fan CFM to achieve adequate airflow.
If the CFM is at or above design, the system can now be balanced. If the measured CFM is below design, insure the VariTrane unit is in full cooling position.
If the air delivery through this VariTrane unit is still below the design requirements, increase the supply fan CFM to achieve adequate airflow.
Note: To increase supply fan CFM check to make sure VFD/IGV are giving max output. If not at max
output; adjust discharge static setpoint until at max output. If already at max output then
78 VAV-SVP01A-EN
make the required adjustments to pulley sizes, motor sizes and electrical connections to accommodate fan speed changes. If any adjustment have been made, repeat step 2.
If after adjusting the fan to its maximum capacity there is still a shortage of airflow, shut off part of the system to provide enough airflow to balance the other part of the system. This can be done using Rover or the "Override to Unoccupied" command ("**") at the zone sensor.
3. After determining that there is enough CFM for all zones, drive all the VAV boxes to MIN.
Note: If the VAV boxes have already been assigned to groups and these groups are separate
thermal zones, then the balancing can be done on a group basis.
VAV Single Duct Unit Air Balancing
Select a group to balance and give the VAV units a recalibrate command and then the group a flow override Drive MAX command.
Note: If the VAV boxes have not been placed in a group, each individual VAV VV550 Controller can
be overridden to Drive MAX in the Override menu in Rover. However, this will be more time consuming.

Rover Air and Water Balancing Tool

The Rover Air and Water Balancing tool assists with air and water balancing by automating overrides, calculations, and calibration. The Air and Water Balancing tool supports VAV VV550 Controllers and other controllers that use the LonMark Space Comfort Controller (SCC) profile.
Note: For step-by-step instructions for using this tool, refer to the Air and Water Balancing Tool
Operations guide.
You must connect your computer to a Comm5 link to communicate with the equipment on the link. You can, however, view job information and reports offline. Refer to the Rover installation sheet for instructions on connecting to a Comm5 link.
Important: The Air and Water Balancing tool works only with controllers that support the SCC
profile. In addition, the controllers must support the network variables for airflow. If the Start Air Balancing button is not available on the Equipment tab, the controller is not compatible with this tool.
Air and Water Balancing
Welcome & Selection Screen
When Rover launches, click the Air and Water Balancing Tool button to launch the selection screen.
VAV-SV P01A-E N 79
Air and Water Balancing
Figure 51. Balancing tool screen
Create New Job
Click this option, then click the Create New Job button to create a new job.
Open Existing Job
Click this option, select a job from the list, then click the Open Job button to open an existing job.
Delete Existing Job
Click this option, select a job from the list, then click the Delete Job button to delete a job.
Select Job to Open
Shows a list of existing jobs. Use this list to select an existing job to open or delete.
Create New Job / Open Job / Delete Job button
This button changes depending on the option you select at the top of the screen. After selecting an option, click this button to perform the task.
Exit button
Click Exit to close the Air and Water Balancing tool.
80 VAV-SVP01A-EN
Figure 52. Create new job screen
Air and Water Balancing
Job tab
Use this tab to modify the open job.
Note: A "job" contains all the controllers on a single Comm5 link. You can open only one job at
a time. If you have more than one Comm5 link at a site, use different job names for each link.
Job Name
The name of the currently open job. You cannot change this name on the Job tab.
Address 1 and 2
Type the street address of the job.
City
Type the name of the city where the job is located.
State
Type the name of the state or province.
Zip Code
Type the postal zip code.
Project Number
Type the project number for the job.
Description
Type of description of the job or Comm5 link.
VAV-SV P01A-E N 81
Air and Water Balancing
Technician
Type the name of the technician performing the air and water balancing.
Date
The default value is the date on which the job was created in the Air and Water Balancing tool. You can change this to a different date.
Select Job Units
Click Inch-Pound to use cubic feet per minute (cfm) to measure airflow. Click International System to use SI units, such as liters per second (L/s) to measure airflow. The units you select are used only for reporting purposes in the Air and Water Balancing tool-they do not affect the units used in the controller or in Rover Comm5.
Change Airflow Units button
This button appears only if you select to use SI units. Click this button to select one of the following SI units of measurement:
Liters per second (L/s)
Cubic meters per second (m
Cubic meters per minute (m
Airflow Units
The selected SI units of measurement for airflow. This field appears only when SI units are selected.
3
/s)
3
/min.)
Save button
Click this button to save any changes you have made to the job information.
Create Report button
Click this button to create a balancing report.
Open Another Job button
Click this button to open another job.
Exit button
Click this button to close the Air and Water Balancing tool.
82 VAV-SVP01A-EN

Troubleshooting

WARN ING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Chapter Overview

This chapter contains information about the following:
Diagnosing the Problem
Diagnostic Log
Diagnostic Table
LED Operation
Troubleshooting Procedures
VV550 Failure Procedures
VV550 Communication Loss Procedures
Wired Zone Sensor Failure Procedures
Wired Zone Setpoint Failure Procedures
Wireless Zone Sensor Failure Procedures
Airflow Failure Procedures
Duct Temperature Sensor Failure Procedures
VAV Damper Failure Procedures
VAV Series Fan Failure Procedures
VAV Parallel Fan Failure Procedures
VAV Electric Heat Stage(s) Failure Procedures
VAV Proportional Hot Water Failure Procedures
Trane/Honeywell Proportional Valve Check Out Procedure
VAV Two Position Hot Water Failure Procedures

Diagnosing the Problem

Green Status LED will give you an indication if a diagnostic is present. If diagnostic is present, use Rover Service tool or Tracer Summit to access VV550 diagnostics. See Table 16, p. 85 for diagnostics. After diagnostics have been assessed, find correct procedures for troubleshooting issue.
Note: VV550 binary outputs can be exercised by Rover Service tool. See status and programming
sections for detail
VAV-SV P01A-E N 83
Troubleshooting
Diagnostic Log
The Diagnostic Log reports diagnostic and informational modes/items that are not in the unit's normal operation.
Figure 53. Diagnostic log
Some of the items reported are listed to aid in understanding current operation. Reported items are:
1) Timed Override Exists, 2) Cancel Timed Override, 3) Auxiliary Temperature Sensor Not Present,
4) Unoccupied Request from Zone Sensor ** Function, 5) Max Flow Request from Zone Sensor *
Function, 6) Calibration in Progress, and 7) Pressure Dependent Operation.
Figure 54. Items reported
84 VAV-SVP01A-EN
Troubleshooting
Diagnostic Table
Ta ble 16, p. 8 5 shows the VAV VV550/551 Controller diagnostics.
Table 16. Controller diagnostics
Diagnostic Air valve Fan Reheat
Invalid unit configuration
Controller failure Closed Off Off
Discharge air temperature failure (space temperature control) Normal Normal Normal
Discharge air temperature failure (ventilation flow control without reheat)
Discharge air temperature failure (ventilation flow control with reheat)
Discharge air temperature failure (flow tracking control) Normal Don't care Don't care
Low airflow (space temperature control) Normal Normal Local electric heat is Off;
Low airflow (ventilation flow control) Normal Don't care Local electric heat is Off;
Primary air temperature failure (space temperature control) Normal Normal Local electric heat is Off
Primary air temperature failure (ventilation flow control) Normal Don't care Normal
Primary air temperature failure (flow tracking control) Normal Don't care Don't care
Space temperature fail (space temperature control)
Space temperature fail (ventilation flow control)
Space temperature fail (flow tracking control)
Local setpoint failure Normal Normal Normal
Flow sensor failure or flow sensor calibration failure (space temperature control)
Flow sensor failure or flow sensor calibration failure (ventilation flow control)
Flow sensor failure or flow sensor calibration failure (flow tracking control)
Freeze protection active (ventilation flow control) Closed Off Off
Thumbwheel in */** position (single star position) Minimum airflow Normal Normal
Thumbwheel in */** position (double star position) Maximum airflow Normal Normal
Normal Normal Normal Normal
(a) When the unit configuration is invalid, all outputs are de-energized (0 VDC) so that they return to their normal state. (b) If system mode is heat or auto with a warm or hot primary air temperature. (c) When a temperature sensor fails after being valid, the controller generates a diagnostic to indicate the sensor loss condition. The controller automatically
clears the diagnostic once a valid sensor temperature value is present (non-latching diagnostic).
(a)
0 VDC 0 VDC 0 VDC
Normal Don't care Don't care
Closed Don't care Off
local hydronic and all remote heat is normal
local hydronic is normal; remote is Don't care
(b)
local hydronic and all remote heat is normal
(c)
(c)
(c)
Occupied: cool minimum flow setpoint Unoccupied: closed
Normal Don't care Normal
Normal Don't care Don't care
Normal pressure dependent control
Normal pressure dependent control
If the configured airflow tracking offset is positive, configure maximum airflow. If the configured airflow tracking offset is negative, configure minimum airflow
Series fan enabled; parallel fan Off
Normal Normal
Don't care Normal
Don't care Don't care
Off
;
VAV-SV P01A-E N 85
Troubleshooting
LED Operation
Resetting Diagnostics
A reset clears latching diagnostics and enables the controller to try to run normally. If the latching condition is still present after the reset, the controller shuts down. A reset resets a unit that is running normally. There are five ways to reset unit diagnostics:
Manual output test at the controller
Cycling power to the controller
BAS (communicated status request, clear alarm)
Rover service tool (communicated status request, clear alarm)
A communicating device able to access the controller diagnostic reset input (communicated status request, clear alarm)
Red Service LED
Ta b l e 17. Red service LED activity
Red Service LED Activity Description
LED is Off continuously after power is applied to the controller.
LED is On continuously, even when power is first applied to the controller.
LED flashes approximately once every two seconds.
Normal operation
Someone is pressing the Service push button or the controller failed.
Uninstalled (normal controller mode). Use the Rover™ service tool to restore the unit to normal operation. Refer to the Rover product literature for more information.
Service Push Button
Important: If the Service button is held down for more than 15 seconds, the controller will
uninstall itself from the Comm5 network. The red service LED flashing approximately once every two seconds indicates this mode (see Red service LED above). Use the Rover service tool to restore the unit to normal operation. Refer the Rover product literature for more information.
The Service push button can be used, as one of several methods, to install the controller in a communication network. Refer to the Rover service tool product literature for more information.
Green Status LED
The green status LED is typically used to indicate whether or not the controller is powered On (24VAC). This is the only LED under direct software control. The green status LED is Off when you press the Test button. The green status LED blinks during manual output testing. Table 18, p. 87 shows and describes the green status LED activity.
86 VAV-SVP01A-EN
Ta b l e 18 . Green status LED activity
Green Status LED Activity Description
On Power On, normal operation
Off One of the following:
Blinking for 10 seconds,
0.25 seconds Off; 0.25 seconds On
One blink continuously,
0.25 seconds Off; 2.25 seconds On
Two blinks continuously,
0.25 seconds Off; 0.25 seconds On
0.25 seconds Off; 1.75 seconds On
(a) The wink feature enables you to identify a controller. By sending a request from the Rover™ service tool, you can request
the controller to wink.
(b) See the diagnostic topic in this guide for a complete list of output override diagnostics.

Troubleshooting Procedures

VV550 Failure Procedures
Troubleshooting
•Power Off
• Controller failure
• Test button pressed
Wink mode
The controller is in the manual output test mode and no output-override unit diagnostic
The controller is in the manual output test mode and one or more output-override unit diagnostic
(a)
(b)
conditions
(b)
conditions exist
WARN ING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
1. Incorrect supply voltage/No voltage
Check Green Status LED.
Shows solid green when the VV550 is powered and operating normally.
If Green Status LED is off, check incoming power. Measure the power input to VV550 board
on TB1-1 24VAC input and ground TB1-2. The supply voltage should be between 19 and 30 VAC (24VAC cataloged). However, voltages at either extreme may result in system instability.
If no voltage, check up stream of controller to see were voltage has been interrupted. See
complete wiring diagrams, Figure 59, p. 107 to Figure 66, p. 114.
2. Check for short
Remove all wires from controller except incoming power.
Check device using Rover service tool to see if the VAV VV550 is operating properly. If VV550
does operate properly check inputs/outputs for a short.
3. For final step check program by downloading good program using Rover Service tool. See the Saving VAV Program-portion of the VAV VV550 Controller Programming and Operation section.
Note: For Instructions on how to use Rover, refer to the Rover Help by clicking on Rover Help
in the Help menu.
4. If controller is still failed, replace controller.
VAV-SV P01A-E N 87
Troubleshooting
VV550 Communication Loss Procedures
In the event that the VV550 is not communicating properly (No activity on Communication LED's) inspect the following:
WARN ING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
1. Incorrect supply voltage/No voltage
Check Green Status LED.
Shows solid green when the VV550 is powered and operating normally.
If Green Status LED is off, check incoming power. Measure the power input to VV550 board
on TB1-1 24VAC input and ground TB1-2.
The supply voltage should be between 19 and 30 VAC (24VAC cataloged). However, voltages at either extreme may result in system instability.
If no voltage, check up stream of controller to see were voltage has been interrupted. See
complete wiring diagrams, Figure 59, p. 107 to Figure 66, p. 114.
2. Communication link signal has interference
Communication link should not be routed near or with any voltage source.
3. Incorrect wire used
Recommended wire is twisted shielded pair. See VAV Startup/Check out Procedure chapter
for the wiring specifications for VV550
Check device using Rover service tool to see if VV550 is operating properly. If VV550 does
operate properly, check inputs/outputs for a short.
4. For final step check program by downloading good program using Rover Service tool. See the Saving VAV Program-portion of the VAV VV550 Controller Programming and Operation chapter.
Note: If still not communicating to Rover service tool and communication link, replace controller.
Communication Failure
LINK
The TX LED blinks green at the data transfer rate when the VV550 transfers data to other devices on the link.
The RX LED blinks yellow at the data transfer rate when the VV550 receives data from other devices on the link.
Wiring Best Practices
Note: See start up and check out procedures for best wiring practices.
88 VAV-SVP01A-EN
Wired Zone Sensor Failure Procedures
WARN ING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the VV550 reports an incorrect zone temperature, properly inspect the following:
1. Actual room temperature is higher or lower than what the VV550 reads
Check the location and installation of the zone sensor. Change the calibration factor in the
VAV VV550 Controller setup screens.
Note: If Zone sensor is off more than ± 2 degrees continue to number 2.
2. Zone sensor wired incorrectly
Check wiring for the correct connections. See VAV Startup/Check out Procedure chapter for
the wiring specifications for VV550
3. Defective zone sensor
Disconnect the zone sensor terminal plug from the VV550 and using an Ohmmeter, measure
the resistance across the terminals 1 and 2. Compare the resistance to temperature using
Table 19, p. 90. The resistance should shown value should be within ± 2 degrees near those
measured with an accurate temperature measuring device. If not, the zone sensor needs to be replaced.
4. Defective wiring or VV550
With wires still connected to VAV VV550, disconnect zone sensor wires and check voltage
(DC) from wires that were connected to terminals 1 and 2 of zone sensor. You should measure 5VDC. If 5VDC not present then see if the VAV VV550 is outputting 5VDC. This can be done by disconnecting the wires on the VAV VV550 on terminals TB3-1 and TB3-2 and measure the VDC. It should be 5VDC. If you have 5VDC at the VV550 the wires going to the zone have an open. If 5VDC is not present check incoming power to the VV550 board on TB1­1 24VAC input and TB1-2 should measure 24VAC ± 10%. If you measure the proper voltage at on TB1-1 24VAC input and TB1-2 and no voltage at TB3-1 and TB3-2 replace VV550.
5. Zone sensors shorted out
Check the resistance across the wires. Disconnect wires from VV550 and zone sensor making
sure the ends are not touching each other and measure resistance. It should be infinity or no conductivity. If lower resistance is shown wires are shorted together and needs to be replaced.
Troubleshooting
VAV-SV P01A-E N 89
Troubleshooting
Table 19. Zone sensor temperature resistance
Temp (oF) Thermostat Thumbwheel
Sensor Resistance (k Ohms)
Resistance (Ohms)
55 56 57 58 59
60 61 62 63 64
65 66 67 68 69
70 71 72 73 74
75 76 77 78 79
80 81 82 83 84 85
Note: Thumbwheel resistance checks are made at terminal 2 and 3 on the zone sensor. Temperature sensor resistance is
measured at terminal 1 and 2 of the zone sensor.
792 772 753 733 714
694 675 656 636 617
597 578 558 539 519
500 481 461 442 422
403 383 364 344 325
306 286 267 247 228 208
17.0
16.5
16.1
15.7
15.4
15.0
14.6
14.3
14.0
13.6
13.3
13.0
12.6
12.3
12.1
11.8
11.5
11.2
11.0
10.7
10.4
10.2
10.0
9.7
9.5
9.3
9.0
8.8
8.6
8.4
8.2
Wired Zone Setpoint Failure Procedures
WARN ING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the VV550 reports an incorrect zone setpoint, properly inspect the following:
1. Zone sensor setpoint wired incorrectly
Check wiring for the correct connections.
2. Defective zone sensor setpoint dial
90 VAV-SVP01A-EN
Disconnect the zone sensor terminal plug from the VV550 and using an Ohmmeter, measure
the resistance across the terminals 2 (common) and 3 (setpoint). Compare the resistance to specified set point on sensor using Ta b le 19, p . 9 0. The resistance shown should correlate within ± 2 degrees of setpoint shown on Table 19, p. 90 If not, the zone sensor needs to be replaced.
3. Defective wiring or VV550
With wires still connected to VAV VV550, disconnect zone sensor setpoint wires and check
voltage (DC) from wires that were connected to terminals 2 and 3 of zone sensor. You should measure 5VDC. If you do not have 5VDC then see if the VAV VV550 is outputting 5VDC. This can be done by disconnecting the wires on the VAV VV50 on terminals TB3-2 and TB3-3 and measure the VDC. It should be 5VDC. If you have 5VDC at the VV550 the wires going to the zone have an open. If 5VDC is not present check incoming power to the VV550 board on TB1­1 24VAC input and TB1-2. Voltage should measure 24VAC ± 10%. If you measure the proper voltage at on TB1-1 24VAC input and TB1-2 and no voltage at TB3-2 and TB3-3 replace VV550.
4. Zone sensor setpoint is shorted out
Check the resistance across the wires. Disconnect wires from VV550 and zone sensor making
sure the ends are not touching each other and measure resistance. It should be infinity or no conductivity. If lower resistance is shown wires are shorted together and needs to be replaced.
Wireless Zone Sensor Failure Procedures
In the event that the VV550 reports an incorrect zone Temperature/setpoint, properly inspect the following:
Note: No special tools or software are necessary to service and test the wireless zone sensor
system. The system can be testing by using the following: 1) LEDs 1, 2, 3, and 5 on the sensor and on the receiver; 2) The Test button (S5) on the sensor; 3) The address test mode on the receiver; and 4) A common volt-ohm meter.
Troubleshooting
Figure 55. Wireless sensor set components with base plates removed
LED 1
LED 2
LED 3
LED 5
LED 1
LED 2
LED 3
LED 5
Diagnostics
Note: Reading diagnostics can show if the sensor has an issue or it has not been setup properly.
Use this information as a starting point
LED1, LED2, and LED3 will respond to diagnostics by exhibiting specific blinking patterns. They will occur on the sensor as a result of pressing the Test button (S5) (Table 23, p. 93). They will occur on the receiver independently of any user action (Table 23, p. 93).
VAV-SV P01A-E N 91
Troubleshooting
Table 20. Diagnostics on the sensor
LED state when Test button is pressed
(WTS, WZS sensors)
N/A E0, E5, E7
LED1: Off LED2: Off
(a)
LED3
: 1-blink pattern repeated 3 times
LED1: Off LED2: Off
(a)
LED3
: 2-blink pattern repeated 3 times
LED1: Off LED2: Off
(a)
LED3
: 3-blink pattern repeated 3 times
LED1: Off LED2: Off
(a)
LED3
: 4-blink pattern repeated 3 times
(a) Blink pattern is On for 1/4s, Off for 1/4s, with 2s OPff between repetitions.
Error code (WDS
sensor display) Indicates…
E1
E2
E3
E4
Table 21. Diagnostics on the receiver
LED state Indicates…
LED1: Off LED2: Off LED3: 1-blink pattern repeated continuously
LED1: Off LED2: Off LED3: 2-blink pattern repeated continuously
LED1: Off LED2: Off LED3: 3-blink pattern repeated continuously
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
(a)
(a)
(a)
Sensor failure
- Replace sensor
Disassociated
- Sensor is not associated with a receiver
Address set to 000
- Address not set to between 001-999
Software error
- Replace sensor
Input voltage too high
- No RF transmission is permitted with an input battery voltage greater than 3.9V
Disassociated * Receiver is not associated, waiting for a sensor
* Receiver lost communication with sensor * Receiver has no devices on its wireless personal area network * Association with a device has been manually removed
Address set to 000 * Address not set to between 001-999
Not configured * Receiver configuration properties bot properly set (defective receiver)
1. wireless zone sensor system failure.
Observe LED5 on the receiver. LED5 will be On solid green whenever the receiver is
powered.
Make sure the receiver is properly grounded. Both the black wire (GND SIGNAL) and the
yellow wire (GND-POWER) must be grounded.
Press the Test button (S5) on the sensor. Models WTS, WZS LED5 should turn On solid green,
indicating proper battery strength. LED1, LED2, and LED3 will indicate signal strength (See
Table 23, p. 93).
Table 22. Battery status: LED5 on the sensor
User Action LED Display Indicates…
Solid green for 5 seconds Battery condition is adequate for proper operation.
Press Test Button (SS)
None
Note: 1 Blink pattern is On for ¼ s, Off for 3/4 s, with 2 s Off between repetitions.
92 VAV-SVP01A-EN
Solid red for 5 seconds Battery condition is low. Batteries should be replaced.
No light
Blinking red: 1-blink pattern times. Cycle repeats every 15 minutes.
1
repeated 5
Batteries are totally dead or not installed properly, or sensor is defective.
Battery condition is low. Approximately 14 days of operation remain before the battery is too weak to power the sensor.
Table 23. Signal quality: LED1, LED2, LED3 on the sensor
User Action LED Display Indicates…
None
Press Test Button (SS)
Press Test Button (SS)
Press Test Button (SS)
Press Test Button (SS)
LED1:Off LED2:Off LED3:Off
LED1:Off LED2:Off LED3:Off
LED1:On LED2:On LED3:On Displays for 5 seconds, then constantly off
LED1:Off LED2:On LED3:On Displays for 5 seconds, then constantly off
LED1:Off LED2:Off LED3:On Displays for 5 seconds, then constantly off
Normal state * No Test button press
Associated; no communication with receiver * Associated, but no signal from the receiver after
pressing Test button
Excellence signal quality * Adequate signal margin for reliable communication.
Marginal signal quality * Reduced battery life likely. * Consider moving the sensor or receiver to a better
location.
Poor signal quality * Unreliable communication. * Strongly recommend moving the sensor or receiver to
a better location.
Figure 56. Receiver wiring connections
Troubleshooting
Note: When checking signal strength, both LED1 and LED3 on the receiver and sensor should
illuminate in unison if the sensor and receiver are associated. Use this feature to confirm association. If not associated, see setup procedures in Wireless chapter. If unit still does not work proceed in checking Receiver and sensor with testing procedures below.
2. Procedure for Testing the Receiver
Make sure the receiver is powered.
Set the receiver address to 000 to force the zone temperature output and zone temperature
setpoint output to their test mode values (see Table 24, p. 94).
VAV-SV P01A-E N 93
Troubleshooting
Table 24. Output failure modes of operation
Situation Zone Temperature Output Zone Setpoint Output
o
Receiver address = 000
Receiver address = 001 to 999 Receiver has powered up, but has not received a communication from sensor.
Receiver address = 001 to 999 Receiver does not receive a communication within 35 minutes
from the sensor it is associated with
Receiver has no power Open Open
Thermistor in sensor has failed to either open or close
Setpoint potentiometer has failed to either open or close
11.17 kΩ, 72.5 indefinitely
11.17 kΩ, 72.5
Open Open
Open Normal value
Normal value Open
F (22.5 oC),
o
F (22.5 oC) 451 Ω, 72.5 oF (22.5 oC)
451 Ω, 72.5
o
F (22.5 oC), indefinitely
3. Measure the receiver output resistance by following the procedures
Make sure the black wire (GNS-SIGNAL) and the yellow wire (GND-POWER) are grounded
(see above for wiring diagrams).
Make sure the receiver is powered up.
Disconnect the SETPOINT wire (red) and the ZONE wire (white) from the host unit controller.
Measure resistance between the grounded GND-SIGNAL wire and either the SETPOINT or
ZONE wire. Compare resistance measurements to those presented in Table 25, p. 94.
Table 25. Receiver resistance
Zone or Setpoint Temperature
55 oF (12.8 oC) 17.47 k Ω 812 Ω
o
F (15.6 oC) 15.3 k Ω 695 Ω
60
o
F (18.3 oC) 13.49 k Ω 597 Ω
65
o
F (21.1 oC) 11.9 k Ω 500 Ω
70
o
F (23.9 oC) 10.5 k Ω 403 Ω
75
o
80
F (26.7 oC) 9.3 k Ω 305 Ω
o
F (29.4 oC) 8.25 k Ω 208 Ω
85
Nominal Zone Temperature
Output Resistance
Nominal Space Temperature
Setpoint Output Resistance
When the test is complete, reset the receiver address to its previous setting.
Press the Test button (S5) on the sensor to force re-association.
Confirm association and communication by noting LED1, LED2, and LED3 as described in "Signal Quality Test"
Pressing the Test button (S5) on the sensor initiates a signal quality test. LED1, LED2, and
LED3 respond by indicating excellent, marginal, or poor signal quality. The LEDs can be observed on both the sensor (Table 26, p. 95) and the receiver (Ta b l e 27, p. 9 5).
94 VAV-SVP01A-EN
Table 26. Signal quality: LED1, LED2, LED3 on the sensor
User Action LED Display Indicates…
None LED1:Off
Press Test Button (SS)
LED2:Off LED3:Off
LED1:Off LED2:Off LED3:Off
LED1:On LED2:On LED3:On Displays for 5 seconds, then constantly off
LED1:Off LED2:On LED3:On Displays for 5 seconds, then constantly off
LED1:Off LED2:Off LED3:On Displays for 5 seconds, then constantly off
Normal state * No Test button press
Associated; no communication with receiver * Associated, but no signal from the receiver after pressing Test button
Excellence signal quality * Adequate signal margin for reliable communication.
Marginal signal quality * Reduced battery life is likely. * Consider moving the sensor or receiver to a better location.
Poor signal quality * Unreliable communication. * Strongly recommend moving the sensor or receiver to
a better location.
Table 27. Signal quality: LED1, LED2, LED3 on the receiver
Troubleshooting
User Action LED Display Indicates…
None
Press Test Button (SS)
LED1:Off LED2:Off LED3:Off
LED1:On LED2:On LED3:On Displays for 5 seconds, then constantly off
LED1:Off LED2:On LED3:On Displays for 5 seconds, then constantly off
LED1:Off LED2:Off LED3:On Displays for 5 seconds, then constantly off
Normal state * No Test button press
Excellence signal quality * Adequate signal margin for reliable communication.
Marginal signal quality * Reduced battery life is likely. * Consider moving the sensor or receiver to a better
location.
Poor signal quality * Unreliable communication. * Strongly recommend moving the sensor or receiver to
a better location.
If sensor and receiver still do not operate properly, replace bad components. If unit passes
tests, check VV550 operation.
4. Defective VAV VV550
Disconnect the receiver sensor wires on the VAV VV550 on terminals TB3-1 and TB3-2 and
measure the VDC. It should be 5VDC. If 5VDC is not present check incoming power to the VAV VV550 Controller board on TB1-1 and TB1-2. Should measure 24VAC ± 10%. If you measure the proper voltage at TB1-1 and TB1-2 and no voltage at TB3-1and TB3-2 replace VV550.
Note: If no voltage at TB1-1 and TB1-2, see VV550 failure procedures
Disconnect the receiver sepoint wires on the VAV VV550 on terminals TB3-2 and TB3-3 and
measure the VDC. It should be 5VDC. If 5VDC is not present check incoming power to the VAV VV550 Controller board on TB1-1 and TB1-2. Should measure 24VAC ± 10%. If you measure the proper voltage at TB1-1 and TB1-2 and no voltage at TB3-2and TB3-3 replace VV550.
VAV-SV P01A-E N 95
Troubleshooting
Airflow Failure Procedures
WARN ING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the air valve is reading position instead of flow or in the event that the measured flow reads incorrectly, i.e. different from the balance report, properly inspect the following:
Recalibrate VAV unit by cycling power to unit. This can also be accomplished with Rover service tool or Tracer Summit. To Calibrate:
Note: Cycling power to the VAV board will automatically cause the unit to calibrate, however,
following the procedure outlined below will provide a more accurate calibration. It is only necessary to perform this procedure in instances where you are experiencing incorrect flow readings or if the unit reverts to pressure dependent mode despite being above 5% and below 110% of cataloged flow and performing a "normal calibration") and does not correct the problem.
1. Steps for Calibration
Log on to the VAV VV550 Controller with Rover software.
Turn the central air handler "off." If this is not possible, Trane recommends pulling the
transducer tubes off during the calibration process to simulate this.
Select the "calibrate unit" option button.
Rover software will indicate that calibration is taking place in the diagnostic log.
When calibration is complete, the box will release to auto. Drive the box open to make sure
that the box is not below 5% of its cataloged CFM. The controller is accurate in reading flow from 5% to 110% of cataloged CFM.
Release the box to auto and perform any necessary balancing work. See Rover Help for
balancing details.
Check to see if flow has been established, If flow not established or inaccurate proceed
to Step 2.
2. The tubing or flow ring is off, reversed, plugged, or has a leak.
Check with a magnehelic gauge and compare with the delta pressure (DP) chart located on
the VAV box.
96 VAV-SVP01A-EN
Figure 57. Sensor signal vs. airflow delivery
0.01
0.1
1
5
10 100 1,000 10,000
Cfm
Flow Sensor DP ( In . w g )
4"
12"10"8"6"
5"
14"16"
Troubleshooting
Check the tubing for reversal and/or leaks.
Check the flow ring for plugged holes. Blow out with compressed air if necessary.
3. Wrong unit size downloaded into the VAV VV550 Controller setup menu
Verify that the actual unit size matches the unit's nameplate.
4. Poor inlet configuration
Trane recommends 1½-duct diameters of straight duct before the inlet of the box (a 12-inch
box should have 18 inches of straight run duct before the inlet).
5. To determine whether or not the transducer has failed, perform the following steps:
Check the 24 volts AC supply at TB1-1 24VAC input and TB1-2 on the VAV VV550 Controller
board. Voltage should be between 20 volts AC and 28 volts AC.
Read the input voltage to the transducer from the VAV VV550 Controller between the green
and red wires on P1 of the VAV VV550 Controller board. The voltage should be between 4.50 volts DC and 5.50 volts DC (5 volts DC cataloged). If no voltage indicated, replace the VAV VV550 Controller.
Remove the high and low tubes from the transducer (to simulate no flow). Read the
transducer output voltage on P1 of the VAV VV550 Controller board between the green and the black wires with a voltmeter. The voltage should be between 0.20 volts DC and 0.30 volts DC (0.25 volts DC is the null voltage output of the transducer indicating zero flow). If voltage not available replace transducer
Note: The formula for the Transducer output voltage is 0.25 + 0.75 * <delta P>, where delta P
is the pressure in inches of water column. Delta P can range from 0 to 5 inches of W.C.
With flow going across the flow ring measure the differential pressure with a magnahelic
and use Transducer output voltage formula to check accuracy of reported value. Read the transducer output voltage between the green and the black wires. The measured value should correspond to the value given in the transducer output formula. If transducer is off by ± 5%, replace transducer.
VAV-SV P01A-E N 97
Troubleshooting
Duct Temperature Sensor Failure Procedures
In the event that the VV550 reports an incorrect or failed Discharge or Primary air temperature, properly inspect the following:
1. Make sure VAV VV550 has been configured for the input
2. Discharge or Primary air temperature is higher or lower than what the VV550 reads
Check the location and installation of the sensor. Change the calibration factor in the VV550
setup screens.
Note: If sensor is off more than ± 2 degrees continue to number 3.
3. Auxiliary sensor wired incorrectly
Check wiring for the correct connections. See Chapter 2 for further details on Discharge or
Primary air sensor wiring.
4. Defective sensor
Disconnect the sensor terminal plug from the VV550 and using an Ohmmeter, measure the
resistance across the auxiliary sensor wires. Compare the resistance to temperature using
Table 11, p. 72. The resistance measured should correspond to a temperature within ± 2
degrees near those measured with an accurate temperature measuring device. If not, the sensor needs to be replaced.
5. Defective wiring or VV550
See if the VAV VV550 Controller is outputting 5VDC. This can be done by disconnecting the
wires on the VAV VV550 Controller on terminals TB3-5 and TB3-6 for Discharge air temperature sensor or for supply air temperature sensor and measure the VDC. It should be 5VDC. If you have 5VDC at the VV550 the wires going to the auxiliary sensor have an open. If 5VDC is not present check incoming power to the VV550 board on TB1-1 24VAC input and TB1-2. Voltage should measure 24VAC ± 10%. If you measure the proper voltage at TB1-1 24VAC input and TB1-2 and no voltage at TB3-5 and TB3-6 for Discharge air temperature sensor or TB3-5 and TB3-6 for Supply air temperature sensor. Replace the VV550.
VAV Damper Failure Procedures
WARN ING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the air valve is not modulating, properly inspect the following:
1. Tracer Summit or Rover service tool has enabled an override function in VAV VV550
The overrides are Open, Closed, Min, or Max. Disable all overrides.
Note: See VV550 programming and operation chapter to be able to release override with Rover
service tool
VV550 is going through a recalibrate (reset) command. This is shown in the diagnostic log
in Rover service tool
Wait for calibration to finish.
2. Zone temperature is greater than the heat set point or less than the cool set point
98 VAV-SVP01A-EN
Troubleshooting
Change the heat and/or cool set points.
3. Actuator not driving full drive time
Drive time in advanced configuration not set at 90 seconds on current Varitrane units
Adjust to correct damper travel time using Rover service tool. See Operation and
programming chapter.
Damper actuator loose on shaft
Tighten damper actuator set screw to damper shaft
Measure the power input to TB1-1 24VAC input and TB1-2 on the VAV VV550 Controller
board. The supply voltage should be between 20 and 28 VAC (24VAC cataloged). However, voltages at either extreme may result in system instability and cause damper to not be driven its full range.
If no voltage, check up stream of controller to see were voltage has been interrupted. See
Figure 59, p. 107 to Figure 66, p. 114 for correct unit diagrams.
4. Actuator motor has failed
Check Voltage at J1-6 to TB1-2, you should have 24VAC. If 24VAC is not present check
incoming power to the VAV VV550 Controller board on TB1-1 and TB1-2. Should measure 24VAC ± 10%. If you measure the proper voltage at TB1-1 and TB1-2 and no voltage at J1-6 and TB1-2, replace the VAV VV550 Controller.
Check motor by applying 24VAC directly to common (blue) and jumper open (black) wire to
a ground to drive damper open.
Damper should drive open.
Check motor by applying 24VAC directly to common (blue) and jumper closed (red) wire to
a ground to drive damper closed
Damper should drive closed
Note: VV550 Outputs are switched to ground. Do not jumper 24VAC to J1-3 of J1-4 because
damage will occur.
If damper actuator does not open or close replace actuator
VAV Series Fan Failure Procedures
WARN ING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the fan output is not energizing, properly inspect the following:
1. Verify the output configuration in the VV550 setup menu.
Unit needs to be configured as Series fan
2. Outputs on the VV550 are configured as normally closed
Verify the output configuration in the VV550 setup menu.
Note: Series fan powered units in the occupied mode has the fan continuously energized. See
operation Chapter for details
VAV-SV P01A-E N 99
Troubleshooting
3. Tracer Summit has the fan output disabled
Check group, global, and/or Tracer overrides to make sure they are not inhibiting fan
operation.
4. A flow override exists locking out the fan output
Check to make sure Tracer or Rover service tool has released fan disable override.
5. If the VAV VV550 Controller is calling in the status menu for the Fan to be on and it is not then check VV550 Triac output wiring; and Relay output.
Override damper open
See if fan cycles on
Check J8 to TB1-2. Should have 24VAC; if it does not, measure the power input to TB1-
1 24VAC input and TB1-2 (ground) of the VV550 board. The supply voltage should be between 20 and 28 VAC (24VAC cataloged). However, voltages at either extreme may result in system instability.
Triac can be checked with purchasing a 24VAC light bulb and see if it lights up on call for fan, and if the light bulb does not light up replace VV550 controller.
Move fan relay wires from VV550 and apply 24VAC directly.
Fan relay should energize. If it does not energize check wiring. If wiring is OK replace fan
relay.
Notice:
Equipment Damage!
VAV VV550 Controller outputs are switched to ground. Do not jumper 24VAC to J9, J10, or J11 because damage will occur.
6. After all checks have been completed, check motor fan winding integrity and bearing failure.
VAV Parallel Fan Failure Procedures
WARN ING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
In the event that the fan output is not energizing, properly inspect the following:
1. Verify the output configuration in the VV550 setup menu.
Unit needs to be configured as parallel fan
2. Outputs on the VV550 are configured as normally closed
Verify the output configuration in the VV550 setup menu.
Note: Parallel fan can be enabled by either a differential temperature above the heating
setpoint or CFM flow. See Operation chapter for details
3. Tracer Summit has the fan output disabled
100 VAV-SVP01A-EN
Loading...