Trane VAV-UCM 4.2 Installation and Maintenance Manual

Installation, Operation, and Maintenance
VAV-UCM 4.2
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air­conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
March 2014

Introduction

Read this manual thoroughlybefore operatingor servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper FieldWiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could resultin equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handlingof all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrig er ant Practices

Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved VAV-SVX01D-EN
Copyright
This document andthe information in it arethe property of Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
VariTrac,VariTrane, Trane and theTrane logo are
trademarks or registered trademarks ofTrane in the United States and other countries.Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
VAV-SVX01D-EN
Updated board photo and part number (BRD04939 replaced BRD02806).
Introduction
VAV-SVX01D-EN 3
Table of Contents
Introduction ............................. 2
Warnings, Cautions, and Notices ........ 2
Important Environmental Concerns ..... 2
Important Responsible Refrigerant
Practices ........................... 2
General Information ..................... 6
Overview of Manual ................... 6
Chapter Overview ..................... 6
Unit Control Module 4.2 (UCM 4.2) ....... 6
Specifications ....................... 6
UCM 4.2 Enhancements ............... 6
UCM 4.2 Features .................... 7
Shipping ........................... 8
Storage ............................ 8
VAV Start Up/Check Out Procedure ........ 9
Chapter Overview ..................... 9
UCM 4.2 Pre-Power Check-Out .......... 9
Light Emitting Diode (LED) Operations ... 9
Zone Sensor Check-out ................ 10
UCM 4.2 Installation and Wiring ......... 11
Chapter Overview .................... 11
UCM 4.2 Power Wiring ................ 11
Power Requirements ................ 11
Zone Sensor Wiring ................... 11
Location and Mounting .............. 11
Wiring ............................ 11
Multiple UCM’s Per Zone Sensor ...... 12
Multiple UCM’s per Auxiliary Duct
Temperature Sensor ................ 12
Zone Sensor Hardwired Option ....... 12
Zone Sensor Wireless Option ......... 12
Communication Wiring ................ 12
Communication Link Wiring .......... 12
DIP Switch Settings ................... 13
Wireless Zone Sensor ................... 17
Overview ............................ 17
Dimensional Diagrams ................ 17
Setting the Address, Mounting, Wiring, and Associating the Receiver and Sensor
18
Choosing a Location for Mounting
the Sensor ..........................18
Setting the Rotary Address Switches
on the Receiver and the Sensor ........19
Factory Wiring of the Receiver to
theVAVUCM .......................20
Replacing and Securing the
Receiver Cover ......................22
Applying Power to the Receiver ........22
Powering the Sensor and Associating
the Sensor to the Receiver ............23
Testing Signal and Battery Strength ....23
Disassociation ......................23
UCM Programming and Operation ........24
Chapter Overview .....................24
Accessing Rover/Comm4 ...............24
Rover Overview .....................24
Laptop Requirements and Complete
Connection Instructions ...............24
UCM Home Tabs: At a Glance ...........26
Status Tab ..........................27
Setpoints Tab .......................27
Wireless Tab ........................28
Advanced Configuration Tab ..........28
UCM Home Tabs: Instructions ...........28
Configuration .......................28
Setpoints Tab .......................28
Setup Tab ..........................30
Wireless Tab ........................33
Advanced Configuration Tab ..........34
Entering and Exiting the Service Mode ...35
Overriding VAVs ......................35
Resetting Diagnostics ..................35
Saving VAV Program ..................35
Downloading Program Files from
PCtoDDCUCM4.2 ..................36
Sequence of Operations ..................38
Chapter Overview .....................38
Single Duct Units ......................38
Override Conditions (Single Duct) .......38
Fan-Powered Units ....................39
4 VAV-SVX01D-EN
Parallel Fan-Powered Units ............ 39
Occupied Units ..................... 39
Override Conditions (Parallel Fans) ..... 39
Series Fan-Powered Units ............. 40
Occupied Units ..................... 40
Override Conditions (Series Fan) ....... 40
Zone Sensor Functions ................ 40
Flow Sensor ......................... 41
Failure Modes ........................ 41
Air and Water Balancing ................ 42
Chapter Overview .................... 42
Air Balancing ........................ 42
System Checkout ................... 42
System Setup ...................... 42
VAV Single Duct Unit Air Balancing .... 42
Water Balancing ...................... 44
Troubleshooting ........................ 45
Chapter Overview .................... 45
Diagnostic Log ..................... 45
Diagnostic Table .................... 46
UCM Failure Procedures ............. 46
UCM Communication Loss Procedures . 47
Wired Zone Sensor Failure Procedures . 47
Wired Zone Setpoint Failure Procedures 48
Wireless Zone Sensor Failure Procedures 49
Airflow Failure Procedures ........... 51
Auxiliary Temperature Sensor Failure
Procedures ........................ 53
Auxiliary C02 Sensor Failure Procedures 53
VAV Damper Failure Procedures ....... 53
VAV Series Fan Failure Procedures .... 54
VAV Parallel Fan Failure Procedures . . . 54
VAV Electric Heat Stage(s) Failure
Procedures ........................ 56
VAV Proportional Hot water failure .... 56
Trane/Honeywell Proportional valve check out procedures
Cartridge Failure .................... 57
Actuator Failure .................... 57
VAV Two Position Hot water failure .... 57
................. 57
Wiring Diagrams ......................58
Appendix ...............................66
VAV-SVX01D-EN 5

General Information

Overview of Manual

Note: One copy of the document is shipped with VAV
units that have UCM 4.2 DDC controllers and is customer property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for delivered air systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.

Chapter Overview

This chapter contains information about the following:

Unit Control Module 4.2 (UCM 4.2)

Specifications
UCM 4.2 Enhancements
UCM 4.2 Features
Shipping
Storage
Unit Control Module 4.2 (UCM
4.2)
The UCM 4.2 is a microprocessor-based, Direct Digital
Controller (DDC) for the (Variable Air Volume) VAV terminal unit. It contains the control logic to modulate the flow of supply air through theVAV terminal in response to the load requirements within the VAV zone.
The function of theUCM is tocontrol theVAV terminal unit
to vary the volumetric airflow rate to the zone. Units have been made with either pneumatic, analog electronic, or microprocessor controls (DDC VAV).This manual discusses only terminal units with Comm4 DDC/VAV controls. Factory installed DDC/VAV controls are available with all single duct terminal units, dual duct units, as well as parallel fan-powered and series fan-powered units.Two UCMs are required for dual duct units (one for the heating duct and one for the cooling duct).
The UCM modulates a VAV's damper blade based on a
zone temperature, measured airflow, and airflow set points to continuously control conditioned air delivery to the space.The volume of incoming air is monitored and the damper adjusts to provide accurate control independent of the duct pressure.The damper modulates between operator airflow set points depending on space conditions. Additionally, fan and heat outputs may be energized depending on the application. Available inputs
include a twisted/shielded communication link, zone sensor, auxiliary temperature sensor (optional), CO Sensor (optional), and Occupy/Unoccupy Sensor (optional), and 24 VAC power.
2

Specifications

Power Requirements
The UCM 4.2 requires 24VAC,50/60 Hz NEC Class2 power. The UCM itself consumes 8 VA. Our factory installed
devices draw from 3 to 12 VA.Typical values are 4 VA for a damper actuator, 10 to 12 VA for an electric heat contractor, and 6 VA for a fan relay.The NEC Class 2 transformer should be sized to handle the total VA of all devices.The binary outputs are rated at steady-state 12VA max.
Operating Environments - UCM 4.2
32° to 140°F (0° to 60°C), 10% to 90% relative humidity, non­condensing
Storage Environments - UCM 4.2
-40° to 150°F (-40° to 65.6°C), 10% to 90%relative humidity, non-condensing
Mounting
Typically, the UCM 4.2 is factory installed. However, UCM
4.2 is available with retrofit kits, in which case it must be field installed.
Tracer Summit and UCM 4.2 Communications
Link Wiring
Communications Link wiring must be 18 AWG twisted shielded pair wire. Each conductor must be stranded tinned copper.The maximum totalwire length is 5,000 feet (1,524 m). See “UCM 4.2 Installation andWiring,” p. 11 for further information about wire selection.

UCM 4.2 Enhancements

The enhanced VAV UCM is backward compatible with VariTrane® DVAV boxes (VXXD and VXXE) VariTrac®
dampers, and VariTrac II dampers.
UCM 4.2 adds support for operation with VariTrane
Series F valves (¼-turn blade dampers) via 90-second drive time.
UCM 4.2 adds a second, C02interfacing, mode of
operation to the auxiliary analog input (TB3-5).This is a 1 to 10 volt DC input with a mapping of input voltage to C0
output data value of 200 parts per million (PPM)
2
of C0
per volt.The use of this new auxiliary analog
2
input as an interface to a C0 exclusive with the use of the input as auxiliary temperature input.Therefore, the use of the C0 interfacing mode of operation is not recommended for stand-alone applications requiring auto-changeover.
detector is mutually
2
2
6 VAV-SVX01D-EN
General Information
UCM 4.2 adds a binary 24 VAC, dry contact input. It can be configured either as a generic input or as an occupancy detector input.
UCM 4.2 adds a VariTrac Bypass Damper mode of operation. In this mode, supply air temperature and supply air pressure is made available on the Comm4 link.The damper position is a Comm4-control parameter. A Comm4 configurable failsafe position was added.The supply air temperature uses a new "S" input (TB3-7).The use of this new input is mutually exclusive with the zone temp input (TB3-1).
UCM 4.2 now assumes the hot water valve is closed after reset.This prevents a reset during hot water override from causing the valve to stop moving.This also changes the behavior after reset, when there is a reheat demand, the hot water valve now opens (from assumed closed position) to the desired reheat position.
In a wireless system, the hard-wiredsensor can now be configured as not present.The hard-wired sensor failures will not be reported as long as at least one wireless zone sensor is reporting valid temperature values.
Note: This is an older wireless system that has been
obsoleted and not the onediscussed in the wireless zone sensor section.
For standalone units, series or parallel fan operation will use the unoccupied fan control when the local unoccupied request (** function) is received. In UCM
3.3 and prior, the fan would operate as if occupied during local unoccupied request.
UCM 4.2 adds a local minimum heating flow set point.
The use of and value of this set point is configurable.
UCM 4.2 Backward Compatibility
UCM 4.2 can be used to replace UCM I, UCM II, and UCM III with no compatibility issues. However, if the communicating device (i.e. Command Unit I or Comfort Manager™ I) is a COM 3 device (1992 or earlier), then you will need an upgrade chip.The Comfort Manager chip upgrade is Kit 1511 and the Command Unit chip upgrade is Kit 1512.

UCM 4.2 Features

UCM Outputs
UCMTriac outputs for controlling a fan or reheat are rated at 12 VA each.
Wiring Diagram
Figure 3, p. 14 shows a typical wiring diagram for the
redesigned UCM hardware.The new service part number is BRD04939.
Figure 1. UCM 4.2 board layout
Zone Sensor, Auxiliary Sensor, and
Thumbwheel Set Point Calibration
If there is adiscrepancy between a measured temperature and what theUCM reports, a calibrationoffsetvalue can be edited in the UCM setup screen to correct the displayed value.
Flow Sensor Calibration
If there is a discrepancy between a measured flow and what the UCMreports,the measured valuecan be entered, which automatically calculates a calibration multiplier to correct the displayed value.
Water Valve Override
Each UCM that has proportional or staged hot water heat outputs can be edited to override the water valve to its maximum position.
Ventilation Set Points and Ratio Calculation
Set point values needed for a space to satisfy indoor air quality requirements are provided. A resultant ventilation ratio can be used to calculate an air handler's outside air damper minimum position or other control strategies.
VAV-SVX01D-EN 7
General Information
Water Heat Output Configuration
UCMs that have hot water heat outputs can be configured for normally open or normally closed.
Zone Sensor Functions
Zone sensor functions now include: air valve drive to maximum, use unoccupied set points, timed override, and cancel timed override.
Slaving of Zone Sensors
Up to three(3) UCM 4.2 may be connected to a single zone sensor.
Generic UCM Capability
UCM 4.2 can be configured to control non-Trane VAV boxes.

Shipping

EachVAV product and its service literature are shipped in the same package. When unpacking, make sure that the literature is notlost or discardedwith the packing material.
Visually inspect the individual components for obvious
defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred during shipment must be filed with the carrier.

Storage

When any component of the VAV system and/or field
installed accessories must be stored for a period of time prior to being installed, they must be protected from the elements.The storage location temperature should be between -40° to 150°F (-40° to 65.6°C) and the relative humidity should be 10% to 90%, non-condensing.
The warranty will not cover damage to theVAV system or
controls due to negligence during storage. A controlled indoor environment must be used for storage.
8 VAV-SVX01D-EN

VAV Start Up/Check Out Procedure

Chapter Overview

This chapter contains information about the following:
Unit 4.2 Pre-Power Check-Out
Light Emitting Diode (LED) Operations
Zone Sensor Check-Out

UCM 4.2 Pre-Power Check-Out

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Check the supply voltage atTB1. Proper polarity must be maintained.TB1-1 is the hot side (+) andTB1-2 is the ground side (-) of the 24 VAC input.The UCM cannot be powered from a common 24 VAC transformer that is supplying power to a device containing a full-wave rectifier bridge in its power supply.The acceptable voltage is 20 to 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in increased system instability.
Verify that communications wiring has properly been terminated atTB2-1 (+) andTB2-2 (-). Polarity is very important on the communications link.
Verify that the zone sensor connections are correct as detailed in the UCM wiring chapter.
Verify that the proper unit DIP switch settings have been set on each UCM.
Verify that the tubing is properly connected to the transducer.
Table 1. Green LED power function indication
LED State Indication
"On” Board functioning correctly
Blinking Board malfunction (Replace Board)
"Off” Board does not have power
The yellow LED functions as the communication indicator. The indication from the yellow LED is as follows:
:
Table 2. Yellow LED communication indicator function
LED State Indication
"On”
Blinking slowly approx. 1 blink/
sec.
Blinking quickly (multiple blinks/
sec.)
"Off”
Incorrect (reversed)
communication polarity, no
connection, or shorted lines.
Communication is occurring on the link but not for that particular UCM.
Communication is occurring on the
link, specifically with that UCM.
Polarity is correct and no
communication is occurring on the
link

Light Emitting Diode (LED) Operations

The UCM has one green LED located nearTB3 and one
yellow LED located nearTB2 on the UCM circuit board.
These LED’s are used to help diagnose communication
(yellow) or circuit board problems (green).
The green LED (red on older boards) is a power indicator.
It is steady on when the power is on and the software is functioning correctly. If it blinks with a 1 second on 1 second off cycle when power is applied, then the board is not functioning and must be replaced.
VAV-SVX01D-EN 9
VAV Start Up/Check Out Procedure

Zone Sensor Check-out

If an erroneous temperature isbeing reported to theUCM, use the “Zone sensor temperature-resistance table,” p. 10 to verify the integrity of the adjustable set point potentiometer or sensor.The resistance should be measured across the terminals to which the device is connected.
Note: Disconnect the zone sensor from the UCM when
making the checks listed in the table below.
Table 3. Zone sensor temperature-resistance table
Thermostat
Temp (°F)
55 792 17.0
56 772 16.5
57 753 16.1
58 733 15.7
59 714 15.4
60 694 15.0
61 675 14.6
62 656 14.3
63 636 14.0
64 617 13.6
65 597 13.3
66 578 13.0
67 558 12.6
68 539 12.3
69 519 12.1
70 500 11.8
71 481 11.5
72 461 11.2
73 442 11.0
74 422 10.7
75 403 10.4
76 383 10.2
77 364 10.0
78 344 9.7
79 325 9.5
80 306 9.3
81 286 9.0
82 267 8.8
83 247 8.6
84 228 8.4
85 208 8.2
Note: Thumbwheel resistance checks are made at TB3-2 and TB3-3 on the
zone sensor. Temperature sensor resistance is measured at TB3-1 and TB3-2 of the zone sensor.
Thumbwheel
Resistance (Ohms)
Sensor Resistance (k
Ohms)
10 VAV-SVX01D-EN

UCM 4.2 Installation and Wiring

UCM power requirement, add the power consumption per
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARNING
Proper FieldWiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.

Chapter Overview

This chapter contains information about the following:
UCM 4.2 Power Wiring
Zone Sensor Wiring
Communication Wiring
DIP Switch Settings Selection

UCM 4.2 Power Wiring

Power Requirements

NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Use at least 16 AWG for power wiring and connect to terminalTB1-1 (+) andTB1-2 (-). 24 VAC is required to power the UCM control and has an acceptable voltage tolerance of 20 to 28 VAC. Replace the UCM control box cover after field wiring to prevent any electromagnetic interference.
Note: A dedicated 24 VAC, 50VA NEC class 2 transformer
is recommended to power the UCM. When powering multiple UCM’s from one transformer, polarity must be maintained.TerminalTB1-1 is designated positive (+) and terminalTB1-2 is negative (-) to the unit casing ground.
The power consumption for cooling only Series F Models
(VariTrac andVariTrane) is 12 VA (4 VA for the air valve/ actuator and 8 VA for the board).To determine the total
VAV-SVX01D-EN 11
stage to the circuit board power requirement. For example, a Series F unit containing magnetic contactors with three stages of reheat would consume 42 VA.
Table 4. VA rating for components
Style Volt Amps
F - Style Actuator 4 VA
Air Valve Actuator C through E Style 12 VA
Varitrac Actuator 3 VA
Fan Power Fan Output 6 VA
Hot Water Proportional 4 VA
Hot Water 2 Position 6.5 VA
Electric Heater Magnetic Contactor 10 VA
Electric Heater Mercury Contactor 12 VA
Note: VariTrane™ and VariTrac™ cooling only Series D
and E models consume 20 VA (12VA for the actuator and 8VA for the UCM).The heating output ratings remain the same.
See Figure 1,p. 7 for UCM terminallocations and Figure 2,
p. 13 through Figure 5, p. 16 for wiring of output devices.

Zone Sensor Wiring

Location and Mounting

A zone sensorin each control zone should belocated in the most critical area of the zone. Sensors should not be mounted in direct sunlight or in the area’s supply air stream. Subdivision of the zone may be necessary for adequate control and comfort.
Avoid mounting zone sensors in areas subject to the following:
Drafts or “dead spots” behind doors or corners
Hot or cold air ducts
Radiant heat from the sun or appliances
Concealed pipes or chimneys
Unheated or uncooled surfaces behindthe sensor such as outside walls
Air flows from adjacent zones or other units

Wiring

Each unit must be controlled by a zone sensor that is designated specifically for use with the UCM control.Field wiring for the zone sensors must meet the following requirements:
Must be 14 to 18 AWG
Refer to the sensor instructions for terminal connections.
If local codes require enclosed conductors, the zone sensor wires should be installed in conduit. Do not
UCM 4.2 Installation andWiring
route zone sensorwires in conduitwith 24VAC or other high power conducting wires.

Multiple UCM’s Per Zone Sensor

Up to three (3) UCM’s may be connected to a single zone sensor and thumbwheel set point.
Connect terminal connectionsTB3-1,TB3-2, andTB3­3 in parallel (i.e. daisy chain) from the master UCM to the slaved UCM(s).
Note: Proper polarity must be maintained.
Cut jumper wires W1 and W2 on the slaved UCM’s (never cut jumper wires W1 and W2 on master UCM).
Multiple UCM’s per Auxiliary Duct
Temperature Sensor
Up to three (3) UCMs may be connected to a single auxiliary duct temperature sensor.
Connect terminal connectionsTB3-5 andTB3-6 in parallel (i.e. daisy chain) from the master UCM to the slaved UCM(s).
Note: Proper polarity must be maintained.
Cut jumper wire W4 on the slaved UCMs (never cut jumper wire W4 on the master UCM).

Zone Sensor Hardwired Option

Depending on the zone sensor options used, a maximum of five wires may be required to run from the UCM to the zone sensor. The zone sensor options are:
Zone sensor only (2 wires) - Part Number X13511528010
Sensor with night set back - Part Number X13511530010
Zone sensor with external adjustable - Part Number X13511529010
Zone sensor with external adjustable night set back, timed override (TOV) on/cancel button - Part Number X13511527010
Digital zone sensor - Part Number X13790866010
Communications jack - Part Number X13651467020 (for one box of 12)
Note: All wiring from the zone sensor to the
Communication link must be twisted shielded pair wiring.

Zone Sensor Wireless Option

Wireless Zone Sensor
Receiver is used to receive a signal from the wireless zone sensor and can be factory installed- Part Number X13790855010.
The wiring harness connects the receiver to the UCM 4.2
- Part Number X19051692010.
Zone Sensor
The wireless zone sensor with night setback timed
override (TOV) on/cancel button. Also can be ordered for Celsius and Fahrenheit setpoint adjustment - Part Number X13790492010 (F), X13790494010 (C). DigitalWireless Part Number: X13790822010.

Communication Wiring

Communication Link Wiring

The “Communication Link” is the communication wiring
betweenTracer Summit® and all VAV box Unit Control Modules (UCM).Tracer Summit can be connected to the UCM communication link in a“daisy chain” configuration.
Note: It is not necessary for each UCM to beconnected to
the line in sequential order by address. Also, multiple communication links may be run and terminated atTracer Summit. However, a consistent, documented wiring path will help troubleshoot communication problems after installation.
Field wiring for the communication link must meet the following requirements:
1. Communication link wiring must be at least 18 AWG twisted shielded pair wire. Shields must be grounded atTracer Summit or Central Control Panel (CCP) only. More than one ground reference will cause communications failures. Shields must be daisy chained.Tape the shield at the lastVAV UCM to prevent any connection between the shield and ground. Wire specifications are as follows:
Plenum Cable
Stranded, tinned copper insulated with extruded FEP. Conductors cabled and shielded with overall aluminum/Mylar tape and stranded, tinned copper drawn wire. Extruded jacket, 300 volt, 150°C NEC 725­2 (b) class 2, type CL2P, 25 pF/ft.
Non-Plenum Cable
Stranded tinned copper insulated with polyethylene. Conductors cabled and shielded with overall aluminum/polyester tape and stranded, tinned copper drain wire. Chrome gray PVC jacket, 300V, 60°C NEC type CM, 24 pF/ft.
Table 5. Wire capacitance
Max. Communication
Link Wiring Length Max. Wire Capacitance
1,000 feet (304.8m) Up to 60 pF/ft. (196.9 pF/m)
2,000 feet (609.6 m) Up to 50 pF/ft. (164.0 pF/m)
3,000 feet (914.4m) Up to 40 pF/ft. (131.2 pF/m)
4,000 feet (1,219.2 m) Up to 30 pF/ft. (98.4 pF/m)
5,000 feet (1,524 m) Up to 25 pF/ft. (82.0 pF/m)
Note: Wire capacitance must comply with this table.
12 VAV-SVX01D-EN
UCM 4.2 Installation andWiring
2. The maximum wire length should not exceed 5,000 feet (1,524 m).
3. Communication link wiring cannot pass between buildings.
4. A maximum of 63 UCMs can be connected to each COM Link. Daisy chaining is a typical configuration. “STAR” chaining is also acceptable.
Note: Polarity is extremely important and must be
observed on communication link connections.
5. At the VAV box, communication link wires must be connected toTB2-1, 3 (+) andTB2-2, 4 (-) terminals on the UCM.
6. Verify that the UCM address is properly set (DIP switch SW1). See
Table 6, p. 13 for proper DIP switch settings.

DIP Switch Settings

DIP Switch SW1 contains six switches for addressing the UCM.These switches allow a user to set a unique communication address for each UCM. Each UCM on a given communication link must have a unique address in order forTracer Summit or the CCP to communicate to it. Refer to Table 6, p. 13 for UCM 4.2 DIP switch settings.
Note: When using Rover™ service tool to communicate
to the UCM, you must add 64 to the DIP switch address. For example, a UCM with the DIP switch address set to 1 would be UCM Number 65 in Rover.
Figure 2. Rover screen/application
Table 6. DIP switch settings for UCM 4.2
UCM
Unit #
Address 1 2 3 4 5 6
1 65 OFF ON ON ON ON ON
2 66 ON OFF ON ON ON ON
3 67 OFF OFF ON ON ON ON
4 68 ON ON OFF ON ON ON
5 69 OFF ON OFF ON ON ON
6 70 ON OFF OFF ON ON ON
7 71 OFF OFF OFF ON ON ON
8 72 ON ON ON OFF ON ON
Dip
Table 6. DIP switch settings for UCM 4.2 (continued)
UCM
Unit #
Address 1 2 3 4 5 6
9 73 OFF ON ON OFF ON ON
10 74 ON OFF ON OFF ON ON
11 75 OFF OFF ON OFF ON ON
12 76 ON ON OFF OFF ON ON
13 77 OFF ON OFF OFF ON ON
14 78 ON OFF OFF OFF ON ON
15 79 OFF OFF OFF OFF ON ON
16 80 ON ON ON ON OFF ON
17 81 OFF ON ON ON OFF ON
18 82 ON OFF ON ON OFF ON
19 83 OFF OFF ON ON OFF ON
20 84 ON ON OFF ON OFF ON
21 85 OFF ON OFF ON OFF ON
22 86 ON OFF OFF ON OFF ON
23 87 OFF OFF OFF ON OFF ON
24 88 ON ON ON OFF OFF ON
25 89 OFF ON ON OFF OFF ON
26 90 ON OFF ON OFF OFF ON
27 91 OFF OFF ON OFF OFF ON
28 92 ON ON OFF OFF OFF ON
29 93 OFF ON OFF OFF OFF ON
30 94 ON OFF OFF OFF OFF ON
31 95 OFF OFF OFF OFF OFF ON
32 96 ON ON ON ON ON OFF
33 97 OFF ON ON ON ON OFF
34 98 ON OFF ON ON ON OFF
35 99 OFF OFF ON ON ON OFF
36 100 ON ON OFF ON ON OFF
37 101 OFF ON OFF ON ON OFF
38 102 ON OFF OFF ON ON OFF
39 103 OFF OFF OFF ON ON OFF
40 104 ON ON ON OFF ON OFF
41 105 OFF ON ON OFF ON OFF
42 106 ON OFF ON OFF ON OFF
43 107 OFF OFF ON OFF ON OFF
44 108 ON ON OFF OFF ON OFF
45 109 OFF ON OFF OFF ON OFF
46 110 ON OFF OFF OFF ON OFF
47 111 OFF OFF OFF OFF ON OFF
48 112 ON ON ON ON OFF OFF
49 113 OFF ON ON ON OFF OFF
50 114 ON OFF ON ON OFF OFF
51 115 OFF OFF ON ON OFF OFF
52 116 ON ON OFF ON OFF OFF
53 117 OFF ON OFF ON OFF OFF
54 118 ON OFF OFF ON OFF OFF
55 119 OFF OFF OFF ON OFF OFF
56 120 ON ON ON OFF OFF OFF
57 121 OFF ON ON OFF OFF OFF
58 122 ON OFF ON OFF OFF OFF
59 123 OFF OFF ON OFF OFF OFF
Dip
VAV-SVX01D-EN 13
UCM 4.2 Installation andWiring
Table 6. DIP switch settings for UCM 4.2 (continued)
UCM
Unit #
Address 1 2 3 4 5 6
60 124 ON ON OFF OFF OFF OFF
61 125 OFF ON OFF OFF OFF OFF
62 126 ON OFF OFF OFF OFF OFF
63 127 OFF OFF OFF OFF OFF OFF
Figure 3. Wiring diagram for single duct units with factory installed electric reheat
Dip
The following figures show wiring diagrams for typical
applications of UCM 4.2
.
HEATER STAGE
CONTACTOR(S)
3RD 2ND
3RD STG.
R
J11
ADDRESS
SWITCH
+ -
TB2-1
IN
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
NOTE:
1.
2.
1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS INTERFACE.
6.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
7.
S TERMINAL NOT TO BE USED WITH VARITRANE.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
8. MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONTROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
CONTACTORS ARE 24 VAC: 12VA MAX/COIL (MERCURY CONTACTORS). 10VA MAX/COIL
9.
(MAGNETIC CONTACTORS)
10.
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORMER LOCATED IN HEATER.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
11. WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
OPTIONAL
9.
TRANSFORMER
1ST
HOT
1ST STG.
2ND STG.
V
J10
Y
-2
O
TB1
BR
J1
J7
J8
J9
CONTROL BOARD
+
-
+ -
-4
TB2-3
TB2-5
TB2
TB2-2
IN
OUT
OUT
5.
R (HOT) O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
FACTORY WIRING FIELD WIRING OPTIONAL OR ALTERNATE WIRING
BL
1-1 B T
D.D.C.\U.C.M.
TB2-6
(TB1-1) 24VAC
(TB4-1) BIP (TB1-1) 24VAC (TB1-2) GND
NOT CONNECTED
DAMPER
10.
ACTUATOR
WIRING
T
PEN O
HOT
HO
CLOSE
1
1-2
4-1
B T
TB1-1
TB
ACT
YEL GRN
OPTIONAL FACTORY INSTALLED
BIP
GND
ZONE
TB3-1
WIRELESS
24V
GND A/CO2
-2
TB3
-5
3-3
TB3
TB
J3
PRESS
1
GNDSET
6
TB3-
TB3-5
AUX TEMP SENSOR
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
PRESSURE
TRANSDUCER
R
+
BK
VOUT
G
-
S
7.
D.D.C.\U.C.M.
CONTROL BOX
TB3-6
6.
OPTIONAL
UCM or EI Board
TB3-3
TB2-5
11.
TB3-3
3.
DUCT
MOUNTED
MOUNTED
+
0
V
Y
TB3-2
3 2 1
TB3-2
2 1
4.
(TB1-1) 24V
(TB3-6) GND
(TB3-5) A/CO2
BL
Y
BL
1-1
TB1-2
TB
24V
GND
TB3-1
TB3-1
OPTIONAL
8.
FACTORY INSTALLED WIRELESS
24VAC
TB2-6
TB1-1
TB1-2
114.710 6
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5
1(-)2(+) 3
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
LL
6.
WA
24V
CO2
GND
SENSOR
OUT
OPTIONAL FIELD INSTALLED
CO2 SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURS À DISTANCE, PUIS SUIVRE LES PROCÉDURES DE VERROUILLAGE ET DES ÉTIQUETTES AVANT TOUTE INTERVENTION. VÉRIFIER QUE TOUS LES CONDENSATEURS DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS À VITESSE VARIABLE, SE REPORTER AUX INSTRUCTIONS DE L'ENTRAÎNEMENT POUR DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE PRÉCAUTION PEUT ENTRAÎNER DES BLESSURES GRAVES POUVANT ÊTRE MORTELLES.
ADVERTENCIA
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÃA ELÉCTRICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE DE QUE TODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO EL VOLTAJE ALMACENADO. PARA LAS UNIDADES CON TRANSMISIÓN DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARA LA DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE INDICADO, PODRÃA OCASIONAR LA MUERTE O SERIAS LESIONES PERSONALES.
14 VAV-SVX01D-EN
Figure 4. Wiring diagram for fan-powered units with field installed reheat
UCM 4.2 Installation andWiring
VAV-SVX01D-EN 15
UCM 4.2 Installation andWiring
Figure 5. Wiring diagram for fan-powered units with factory installed electric reheat
2ND STG HEAT
V
J10
J11
ADDRESS
SWITCH
+ - +
TB2-2
TB2-1
IN
1ST STG HEAT
O
J9
IN
HEATER
TERMINAL
BOX WIRING
J7
J8
- +
B2-4 T
TB2-3
T OU
OUT
ACTUATOR
BR-HOT
J1
ACT
1
B4-1 T
BIP
D.D.C.\U.C.M.
CONTROL BOARD
-
YEL
2-5 B
TB2-6
T
GRN
DAMPER
WIRING
OT
OPEN
HOT
H
TB1-2
GND
ZONE SETGND
3-1 B T
TB3-3
6.
TB3-2
3 2
Y
Y
TB1-2
GND
TB3-2
3 2 1
TB3-1
1
TB3-1
BL
BL
1-1 B T
24V
OPTIONAL
FAN CONTROL
BOX WIRING
E
LOS C
R-FAN
1-1 B T
24V
A/CO2
GND
3-3
B3-5
B
B3-2 T
TB3-6
T
T
ESS PR
24 VAC
J3
1
S
BR
TRANSDUCER
R
BK
G
7.
Y
BL
PRESSURE
+ VOUT
-
D.D.C.\U.C.M.
CONTROL BOX
FACTORY INSTALLED WIRELESS
24VAC
UCM or EI Board
TB2-6
TB1-1
TB1-2
TB2-5
11
10 7 6
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5
TB3-3
1(-)2(+)
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3. 4.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
SHIELDED
TWISTED PAIR
COMMUNICATIONS
WIRING
5.
R (HOT)
O (COMMON) GR (NC CONTACT) BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
(TB1-1) 24VAC
(TB4-1) BIP (TB1-1) 24VAC (TB1-2) GND
NOT CONNECTED
OPTIONAL FACTORY INSTALLED
WIRELESS
TB3-6TB3-5
6.
OPTIONAL
AUX TEMP SENSOR
SENSOR
NOTE:
1.
1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
2.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM TRANSFORMER.
THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS INTERFACE.
6.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
7.
S TERMINAL NOT TO BE USED WITH VARITRANE.
8.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
FACTORY WIRING FIELD WIRING OPTIONAL OR ALTERNATE WIRING
6.
WALL
DUCT
MOUNTED
MOUNTED
24V
GND
OUT
CO2 SENSOR
+
0
V
(TB3-6) GND
CO2
OPTIONAL FIELD INSTALLED
(TB1-1) 24V
(TB3-5) A/CO2
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT IN DEATH OR SERIOUS INJURY.
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURS À DISTANCE, PUIS SUIVRE LES PROCÉDURES DE VERROUILLAGE ET DES ÉTIQUETTES AVANT TOUTE INTERVENTION. VÉRIFIER QUE TOUS LES CONDENSATEURS DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS À VITESSE VARIABLE, SE REPORTER AUX INSTRUCTIONS DE L'ENTRAÎNEMENT POUR DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE PRÉCAUTION PEUT ENTRAÎNER DES BLESSURES GRAVES POUVANT ÊTRE MORTELLES.
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÃA ELÉCTRICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE DE QUE TODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO EL VOLTAJE ALMACENADO. PARA LAS UNIDADES CON TRANSMISIÓN DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARA LA DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE INDICADO, PODRÃA OCASIONAR LA MUERTE O SERIAS LESIONES PERSONALES.
WARNING
AVERTISSEMENT
ADVERTENCIA
16 VAV-SVX01D-EN

Wireless Zone Sensor

Overview

TheTraneWireless Zone Sensor set includes a sensor and
a receiver that work together to provide the same functions as the equivalentTrane wired sensor (#4190-
1090), such as the standard 10 k temperature input (with the exception of the communication jack). No further software or hardware is necessary for site evaluation, installation, or maintenance.
The sensor transmits the zone temperature, all zone
temperature setpoint functions, timed override Occupied
Figure 6. Outside dimensions for sensor
2.90 in (7.35 cm)
(On) and timed override Unoccupied (Cancel) information to the receiver.The receiver electrically reproduces the zone temperature resistance, all zone temperature setpoint function resistances, and timed override On and timed override Cancel information as sent by the sensor.

Dimensional Diagrams

See Figure 6,p. 17 and Figure 7, p. 18 fordimensions of the
Wireless Zone Sensor set.The dimensions are the same
for both the sensor and the receiver.
1.08 in (2.75 cm)
4.78 in (12.14 cm)
2.62 in (6.65 cm)
Note: The dimensions are the
same for both the sensor and the receiver.
VAV-SVX01D-EN 17
Wireless Zone Sensor
Figure 7. Mounting hole dimensions for sensor
3.27 in (8.30 cm)
2.36 in (6.00 cm)
1.34 in (3.41 cm)
Setting the Address, Mounting,
Wiring, and Associating the
Receiver and Sensor
The following procedure list shows the recommended
order for installation:
Choosing a location for mounting the sensor
Settingthe rotary address switches on the receiver and on the sensor
Replacing and securing the receiver cover
Powering the sensor and associating the sensor to the receiver
Applying power to the receiver
• Testing signal and battery strength
Disassociation
Note: The dimensions are the
same for both the sensor and the receiver.

Choosing a Location for Mounting the Sensor

Placement of the receiver and the sensor set is critical to proper operation. In most installations, distance is not the limiting factor for proper radio signal quality. It is more greatly affected by walls, barriers, and general clutter. For best radio transmission range and reliability, wherever possible, mount the receiver andsensor in line of sight.Try to minimize the number of barriers between the pair of devices. In general, sheetrock walls and ceiling tiles offer little restriction to the propagation of the radio signal throughout the building; concrete or metal barriers offer the most restriction.Thetransmission range for the sensor is as follows:
Open range: 2,500 ft (762 m) (packet error rate = 2%)
Usable range: 200 ft (61 m)
• Typical range: 75 ft (23 m)
18 VAV-SVX01D-EN
Wireless Zone Sensor
DRESS
IN
LED3
L
ED2
T
A
Ambient considerations
Avoidlocations that are outside theoperating temperature
and humidity range (see Table 14, p. 48).
Location Considerations for the Sensor
When selecting a location for the sensor, consider both
thermal and radio transmission characteristics of the location.
Thermal considerations
Avoid areas of direct sunlight
Avoid areas in the direct air stream of air diffusers
Avoid exterior walls and other walls that have a temperature differential between their two sides
Avoid areas close to sources of heat such as sunlight, appliances, or other equipment
Avoid drafty areas
Avoid dead spots behind doors, projection screens, or corners
Radio transmission considerations
Avoid placing the sensor inside metal enclosures
Avoid radio transmissions through thick, solid concrete walls

Setting the Rotary Address Switches on the Receiver and the Sensor

Note: To expedite the installation and association
process, set the addresses before applying power to the receiver.
The process of establishing communication between the
receiver and sensor is referred to as association.The receiver and the sensormust have their rotary switches set to the same address in order to enable communication between the two devices (see Figure 8, p. 19). Important limitations are as follows:
Only one associated receiver/sensor set can communicate within the reception range of the wireless system.
It is not possible to associate more than one sensor to a receiver, nor is it possibleto associate morethan one receiver to a sensor.
Avoid metal barriers between the sensor and receiver, such as plastered walls with metal lathe as they will decrease radio signal quality.
Figure 8. Setting the rotary address switches on the receiver and the sensor
Do not remove the insulation strip yet.
B1 +
WIRELESS
L
STAL
LED1
LED2
LED3
LED5
SIGNAL
POWER
S5
S1
ADD
HEATING SET FAN/SYSTEM
5
S
SETPOINT ZONE GND
24VAC/DC GND COMM + COMM -
S2
C33
LED4
S4
S3
C34
J1
C35
R77
Setting the Receiver Address
1. Using a small screwdriver, set the three rotaryaddress switches (locations S1, S2, S3) on the receiver (Figure 8, p. 19) to an address between 001 and 999.
Note: Do not use 000 as an address for installation. If
you set the receiver address to 000, it will:
– Return the receiver outputs to their factory
defaults indefinitely (zone temperature and setpoint outputs: 72.5°F [22.5°C])
!
Pb
S1
ADDRESS
Pb-FREE
S3
LED4
S2
STATUS
S4
WIRELESS INSTALL
LED1
SIGNAL
LED5
BATTERY STATUS
– Make the receiver unable to associate with a
sensor
Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
Zero is at the 9 o'clock position.
2. Make a notation of the address and location of the receiver.
– Remove all association knowledge
VAV-SVX01D-EN 19
Wireless Zone Sensor
Setting the Sensor Address
1. Using a small screwdriver, set the three rotaryaddress switches (locations S1, S2, S3) on thesensor (Figure 8,
p. 19) to the same address used for the receiver it is to
be associated with.
2. Make a notation of the address and locationwhere this sensor is to be mounted.
Note: Do not use 000 as an address for installation. If
you set the address to 000, it will:
– Remove all association knowledge
– Revert to a low-power hibernation mode.
– Send a disassociation request to the receiver. If
the sensor and receiver are associated and communicating at the time the sensor is set to 000 and theTest button is pressed, the receiver will also become unassociated and will be available for re-association.
Read the switches from left to right in the order in
which they are numbered (S1, S2, S3).
Zero is at the 9 o'clock position.
3. Make a notation of the address and location of the sensor.

Factory Wiring of the Receiver to the VAV UCM

The required power for the receiver is 24 VAC or 24 Vdc
and is less than 1 VA.The receiver is designed to be powered by the VAV UCM controller.
Note: A dedicated transformer is not necessary or
advised.
20 VAV-SVX01D-EN
Figure 9. Factory wiring of the receiver to the VAV UCM
Wireless Zone Sensor
W (HOT)
TO J8
BK (CLOSE)
TO J9
R (OPEN)
TO J10
OPTIONAL FIELD INSTALLED
PROPORTIONAL WATER VALVE
J10
J11
ADDRESS
SWITCH
TB2-2
TB2-1
IN
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
TB3-5
AUX TEMP SENSOR
NOTE:
1.
2.
1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TW ISTED PAIR WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPT ION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
THE OPTIONAL BINARY INPUT CONNECTS BETW EEN TB4-1 (BIP) AND 24VAC (HOT) FROM TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS INTERFACE.
6.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
7.
S TERMINAL NOT TO BE USED WIT H VARITRANE.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
8. MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONT ROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORM ER WIRING. WIRINGS GOES THRU TO
9.
NEXT COMPONENT WHEN OPTIONS ARE NOT CHOSEN/
10.
TRANSFORMER WIRE COLORS: 120V - W, 208V - R, 240V - O, 277V - BR, 480V - R/BK 575V -R, 190V - R, 220V - R, 347V - R.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
11.
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
PROP. WATER VALVE 24VAC
12VA MAX
J1
8
J9
J7
J
ACT
D.D.C.\U.C.M.
CONTROL BOARD
+ -+ -
TB2-3
OUTINOUT
TB2-4
TB3-6
-
+
TB2-6
TB2-5
6.
OPTIONAL
FACTORY WIRING FIELD WIRING OPTIONAL OR ALTERNATE WIRING
DAMPER
ACTUATOR
WIRING
T HO
HOT
1
4-1 TB
BIP
GND
ZONE
YEL
GRN
3-1 TB
OPTIONAL FACTORY INSTALLED
WIRELESS
TB2-6
TB2-5
2(+)
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
Table 7. Wiring harness: wire identification
PEN O
1-2 TB
GND
TB3-3
CLOSE
TB1-1
24V
SET GND
TB3-3
TB3-2
TB3-1
TB3-2
231(-) 1
4.3.
A/CO2
TB3-5
J3
RESS P
1
3-6 TB
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
PRESSURE
TRANSDUCER
R
+
BK
VOUT
G
-
S
7.
D.D.C.\U.C.M.
CONTROL BOX
6.
WALL
24V
CO2
GND
SENSOR
OUT
OPTIONAL FIELD INSTALLED
CO2 SENSOR
2ND STG.
TO J10
1ST STG.
TO J9
HOT
TO J8
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
TO J9 TO J8
OPTIONAL FIELD INSTALLED
0N-OFF WATER VALVE
D
MOUNTE
8.
D
UNTE
DUCT
MO
(TB1-1) 24V
+
(TB3-6) GND
0
(TB3-5) A/CO2
V
HEATER STAGE CONTACTOR(S)
24VAC, 12VA
MAX/COIL
ON - OFF
WATER VALVE
24 VAC
12VA MAX
OPTIONAL
FACTORY INSTALLED WIRELESS
24VAC
OPTIONAL FUSE, DISCONNECT & TRANSFORMER
OPTIONAL POWER
TRANSFORMER
(50VA)
5.
R (HOT) O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
TB2-6
TB1-1
TB1-2
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING. INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE. UNITS WITH VARIABLE SPEED DRIVE, REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET OUVRIR LES SECTIONNEURS À DISTANCE, PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS LES CONDENSATEURS DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX INSTRUCTIONS DE L'ENTRAÎNEMENT POUR DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE PRÉCAUTION PEUT ENTRAÎNER DES BLESSURES GRAVES POUVANT ÊTRE MORTELLES.
ADVERTENCIA
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÃA ELÉCTRICA, INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS LOS CAPACITORES DEL MOTOR HAYAN DESCARGADO EL VOLTAJE ALMACENADO. PARA LAS UNIDADES CON TRANSMISIÓN DE VELOCIDAD VARIABLE, CONSULTE LAS INSTRUCCIONES PARA LA DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE INDICADO, PODRÃA OCASIONAR LA MUERTE O SERIAS LESIONES PERSONALES.
Y
Y
TB1-2
GND
UCM or EI Board
(BK)
W)
(
or
or
L
Y
B
BK
UCM or EI Board
(TB1-1) 24VAC (TB4-1) BIP (TB1-1) 24VAC (TB1-2) GND NOT CONNECTED
TB3-3
TB2-5
TB3-2
4. 11.
BL
GREEN
GROUND
SCREW
OPTIONAL DISCONNECT SWITCH
BK
BL
Y
TB1-2
GND
TB3-1
BL
TB1-1
24V
OPTIONAL
FUSE
TB1-1
24V
1231011 7 6
Table 7. Wiring harness: wire identification (continued)
Wire Label Color Function
HEATING SET N/A Not used. For future use.
FAN/SYSTEM N/A Not used. For future use.
SETPOINT Red Space temperature setpoint
ZONE White Zone temperature
GND-SIGNAL Black Ground for setpoint and zone signal
Wire Label Color Function
24 VAC/DC Blue 24 VAC/Vdc power
GND-POWER Yellow Ground for 24 VAC/dc
COMM + N/A Not used. For future use.
COMM - N/A Not used. For future use.
Note: Both GND-SGNAL and GND-POWER must be wired for the receiver to
operate (See Figure 3, p. 14, Figure 4, p. 15,Figure 5, p. 16).
VAV-SVX01D-EN 21
Loading...
+ 47 hidden pages