Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
March 2014
VAV-SVX01D-EN
Introduction
Read this manual thoroughlybefore operatingor servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
Proper FieldWiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situationthat could resultin
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handlingof
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrig er ant Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
•If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
This document andthe information in it arethe property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
VariTrac,VariTrane, Trane and theTrane logo are
trademarks or registered trademarks ofTrane in the United
States and other countries.Trane is a business of Ingersoll
Rand. All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
VAV-SVX01D-EN
Updated board photo and part number (BRD04939
replaced BRD02806).
Introduction
VAV-SVX01D-EN3
Table of Contents
Introduction ............................. 2
Warnings, Cautions, and Notices ........ 2
Important Environmental Concerns ..... 2
Important Responsible Refrigerant
Practices ........................... 2
General Information ..................... 6
Overview of Manual ................... 6
Chapter Overview ..................... 6
Unit Control Module 4.2 (UCM 4.2) ....... 6
Specifications ....................... 6
UCM 4.2 Enhancements ............... 6
UCM 4.2 Features .................... 7
Shipping ........................... 8
Storage ............................ 8
VAV Start Up/Check Out Procedure ........ 9
Chapter Overview ..................... 9
UCM 4.2 Pre-Power Check-Out .......... 9
Light Emitting Diode (LED) Operations ... 9
Zone Sensor Check-out ................ 10
UCM 4.2 Installation and Wiring ......... 11
Chapter Overview .................... 11
UCM 4.2 Power Wiring ................ 11
Power Requirements ................ 11
Zone Sensor Wiring ................... 11
Location and Mounting .............. 11
Wiring ............................ 11
Multiple UCM’s Per Zone Sensor ...... 12
Multiple UCM’s per Auxiliary Duct
Temperature Sensor ................ 12
Zone Sensor Hardwired Option ....... 12
Zone Sensor Wireless Option ......... 12
Communication Wiring ................ 12
Communication Link Wiring .......... 12
DIP Switch Settings ................... 13
Wireless Zone Sensor ................... 17
Overview ............................ 17
Dimensional Diagrams ................ 17
Setting the Address, Mounting, Wiring,
and Associating the Receiver and Sensor
18
Choosing a Location for Mounting
the Sensor ..........................18
Setting the Rotary Address Switches
on the Receiver and the Sensor ........19
Factory Wiring of the Receiver to
theVAVUCM .......................20
Replacing and Securing the
Receiver Cover ......................22
Applying Power to the Receiver ........22
Powering the Sensor and Associating
the Sensor to the Receiver ............23
Testing Signal and Battery Strength ....23
Disassociation ......................23
UCM Programming and Operation ........24
Chapter Overview .....................24
Accessing Rover/Comm4 ...............24
Rover Overview .....................24
Laptop Requirements and Complete
Connection Instructions ...............24
UCM Home Tabs: At a Glance ...........26
Status Tab ..........................27
Setpoints Tab .......................27
Wireless Tab ........................28
Advanced Configuration Tab ..........28
UCM Home Tabs: Instructions ...........28
Configuration .......................28
Setpoints Tab .......................28
Setup Tab ..........................30
Wireless Tab ........................33
Advanced Configuration Tab ..........34
Entering and Exiting the Service Mode ...35
Overriding VAVs ......................35
Resetting Diagnostics ..................35
Saving VAV Program ..................35
Downloading Program Files from
PCtoDDCUCM4.2 ..................36
Sequence of Operations ..................38
Chapter Overview .....................38
Single Duct Units ......................38
Override Conditions (Single Duct) .......38
Fan-Powered Units ....................39
4VAV-SVX01D-EN
Parallel Fan-Powered Units ............ 39
Occupied Units ..................... 39
Override Conditions (Parallel Fans) ..... 39
Series Fan-Powered Units ............. 40
Occupied Units ..................... 40
Override Conditions (Series Fan) ....... 40
Zone Sensor Functions ................ 40
Flow Sensor ......................... 41
Failure Modes ........................ 41
Air and Water Balancing ................ 42
Chapter Overview .................... 42
Air Balancing ........................ 42
System Checkout ................... 42
System Setup ...................... 42
VAV Single Duct Unit Air Balancing .... 42
Water Balancing ...................... 44
Troubleshooting ........................ 45
Chapter Overview .................... 45
Diagnostic Log ..................... 45
Diagnostic Table .................... 46
UCM Failure Procedures ............. 46
UCM Communication Loss Procedures . 47
Wired Zone Sensor Failure Procedures . 47
Wired Zone Setpoint Failure Procedures 48
Wireless Zone Sensor Failure Procedures 49
Airflow Failure Procedures ........... 51
Auxiliary Temperature Sensor Failure
Procedures ........................ 53
Auxiliary C02 Sensor Failure Procedures 53
VAV Damper Failure Procedures ....... 53
VAV Series Fan Failure Procedures .... 54
VAV Parallel Fan Failure Procedures . . . 54
VAV Electric Heat Stage(s) Failure
Procedures ........................ 56
VAV Proportional Hot water failure .... 56
Trane/Honeywell Proportional valve
check out procedures
Cartridge Failure .................... 57
Actuator Failure .................... 57
VAV Two Position Hot water failure .... 57
................. 57
Wiring Diagrams ......................58
Appendix ...............................66
VAV-SVX01D-EN5
General Information
Overview of Manual
Note: One copy of the document is shipped with VAV
units that have UCM 4.2 DDC controllers and is
customer property. It must be retained by the unit's
maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for delivered air systems. By
carefully reviewing the information within this manual
and following the instructions, the risk of improper
operation and/or component damage will be minimized.
Should equipment failure occur, contact a qualified
service organization with qualified, experienced HVAC
technicians to properly diagnose and repair this
equipment.
Chapter Overview
This chapter contains information about the following:
•Unit Control Module 4.2 (UCM 4.2)
•Specifications
•UCM 4.2 Enhancements
•UCM 4.2 Features
•Shipping
•Storage
Unit Control Module 4.2 (UCM
4.2)
The UCM 4.2 is a microprocessor-based, Direct Digital
Controller (DDC) for the (Variable Air Volume) VAV
terminal unit. It contains the control logic to modulate the
flow of supply air through theVAV terminal in response to
the load requirements within the VAV zone.
The function of theUCM is tocontrol theVAV terminal unit
to vary the volumetric airflow rate to the zone. Units have
been made with either pneumatic, analog electronic, or
microprocessor controls (DDC VAV).This manual
discusses only terminal units with Comm4 DDC/VAV
controls. Factory installed DDC/VAV controls are available
with all single duct terminal units, dual duct units, as well
as parallel fan-powered and series fan-powered units.Two
UCMs are required for dual duct units (one for the heating
duct and one for the cooling duct).
The UCM modulates a VAV's damper blade based on a
zone temperature, measured airflow, and airflow set
points to continuously control conditioned air delivery to
the space.The volume of incoming air is monitored and
the damper adjusts to provide accurate control
independent of the duct pressure.The damper modulates
between operator airflow set points depending on space
conditions. Additionally, fan and heat outputs may be
energized depending on the application. Available inputs
include a twisted/shielded communication link, zone
sensor, auxiliary temperature sensor (optional), CO
Sensor (optional), and Occupy/Unoccupy Sensor
(optional), and 24 VAC power.
2
Specifications
Power Requirements
The UCM 4.2 requires 24VAC,50/60 Hz NEC Class2 power.
The UCM itself consumes 8 VA. Our factory installed
devices draw from 3 to 12 VA.Typical values are 4 VA for
a damper actuator, 10 to 12 VA for an electric heat
contractor, and 6 VA for a fan relay.The NEC Class 2
transformer should be sized to handle the total VA of all
devices.The binary outputs are rated at steady-state 12VA
max.
Operating Environments - UCM 4.2
32° to 140°F (0° to 60°C), 10% to 90% relative humidity, noncondensing
Storage Environments - UCM 4.2
-40° to 150°F (-40° to 65.6°C), 10% to 90%relative humidity,
non-condensing
Mounting
Typically, the UCM 4.2 is factory installed. However, UCM
4.2 is available with retrofit kits, in which case it must be
field installed.
Tracer Summit and UCM 4.2 Communications
Link Wiring
Communications Link wiring must be 18 AWG twisted
shielded pair wire. Each conductor must be stranded
tinned copper.The maximum totalwire length is 5,000 feet
(1,524 m). See “UCM 4.2 Installation andWiring,” p. 11 for
further information about wire selection.
UCM 4.2 Enhancements
•The enhanced VAV UCM is backward compatible with
VariTrane® DVAV boxes (VXXD and VXXE) VariTrac®
dampers, and VariTrac II dampers.
•UCM 4.2 adds support for operation with VariTrane
Series F valves (¼-turn blade dampers) via 90-second
drive time.
•UCM 4.2 adds a second, C02interfacing, mode of
operation to the auxiliary analog input (TB3-5).This is
a 1 to 10 volt DC input with a mapping of input voltage
to C0
output data value of 200 parts per million (PPM)
2
of C0
per volt.The use of this new auxiliary analog
2
input as an interface to a C0
exclusive with the use of the input as auxiliary
temperature input.Therefore, the use of the C0
interfacing mode of operation is not recommended for
stand-alone applications requiring auto-changeover.
detector is mutually
2
2
6VAV-SVX01D-EN
General Information
•UCM 4.2 adds a binary 24 VAC, dry contact input. It can
be configured either as a generic input or as an
occupancy detector input.
•UCM 4.2 adds a VariTrac Bypass Damper mode of
operation. In this mode, supply air temperature and
supply air pressure is made available on the Comm4
link.The damper position is a Comm4-control
parameter. A Comm4 configurable failsafe position
was added.The supply air temperature uses a new "S"
input (TB3-7).The use of this new input is mutually
exclusive with the zone temp input (TB3-1).
•UCM 4.2 now assumes the hot water valve is closed
after reset.This prevents a reset during hot water
override from causing the valve to stop moving.This
also changes the behavior after reset, when there is a
reheat demand, the hot water valve now opens (from
assumed closed position) to the desired reheat
position.
•In a wireless system, the hard-wiredsensor can now be
configured as not present.The hard-wired sensor
failures will not be reported as long as at least one
wireless zone sensor is reporting valid temperature
values.
Note: This is an older wireless system that has been
obsoleted and not the onediscussed in the wireless
zone sensor section.
•For standalone units, series or parallel fan operation
will use the unoccupied fan control when the local
unoccupied request (** function) is received. In UCM
3.3 and prior, the fan would operate as if occupied
during local unoccupied request.
•UCM 4.2 adds a local minimum heating flow set point.
The use of and value of this set point is configurable.
UCM 4.2 Backward Compatibility
UCM 4.2 can be used to replace UCM I, UCM II, and UCM
III with no compatibility issues. However, if the
communicating device (i.e. Command Unit I or Comfort
Manager™ I) is a COM 3 device (1992 or earlier), then you
will need an upgrade chip.The Comfort Manager chip
upgrade is Kit 1511 and the Command Unit chip upgrade
is Kit 1512.
UCM 4.2 Features
UCM Outputs
UCMTriac outputs for controlling a fan or reheat are rated
at 12 VA each.
Wiring Diagram
Figure 3, p. 14 shows a typical wiring diagram for the
redesigned UCM hardware.The new service part number
is BRD04939.
Figure 1. UCM 4.2 board layout
Zone Sensor, Auxiliary Sensor, and
Thumbwheel Set Point Calibration
If there is adiscrepancy between a measured temperature
and what theUCM reports, a calibrationoffsetvalue can be
edited in the UCM setup screen to correct the displayed
value.
Flow Sensor Calibration
If there is a discrepancy between a measured flow and
what the UCMreports,the measured valuecan be entered,
which automatically calculates a calibration multiplier to
correct the displayed value.
Water Valve Override
Each UCM that has proportional or staged hot water heat
outputs can be edited to override the water valve to its
maximum position.
Ventilation Set Points and Ratio Calculation
Set point values needed for a space to satisfy indoor air
quality requirements are provided. A resultant ventilation
ratio can be used to calculate an air handler's outside air
damper minimum position or other control strategies.
VAV-SVX01D-EN7
General Information
Water Heat Output Configuration
UCMs that have hot water heat outputs can be configured
for normally open or normally closed.
Zone Sensor Functions
Zone sensor functions now include: air valve drive to
maximum, use unoccupied set points, timed override, and
cancel timed override.
Slaving of Zone Sensors
Up to three(3) UCM 4.2 may be connected to a single zone
sensor.
Generic UCM Capability
UCM 4.2 can be configured to control non-Trane VAV
boxes.
Shipping
EachVAV product and its service literature are shipped in
the same package. When unpacking, make sure that the
literature is notlost or discardedwith the packing material.
Visually inspect the individual components for obvious
defects or damage. All components are thoroughly
inspected before leaving the factory. Any claims for
damage incurred during shipment must be filed with the
carrier.
Storage
When any component of the VAV system and/or field
installed accessories must be stored for a period of time
prior to being installed, they must be protected from the
elements.The storage location temperature should be
between -40° to 150°F (-40° to 65.6°C) and the relative
humidity should be 10% to 90%, non-condensing.
The warranty will not cover damage to theVAV system or
controls due to negligence during storage. A controlled
indoor environment must be used for storage.
8VAV-SVX01D-EN
VAV Start Up/Check Out Procedure
Chapter Overview
This chapter contains information about the following:
•Unit 4.2 Pre-Power Check-Out
•Light Emitting Diode (LED) Operations
•Zone Sensor Check-Out
UCM 4.2 Pre-Power Check-Out
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
•Check the supply voltage atTB1. Proper polarity must
be maintained.TB1-1 is the hot side (+) andTB1-2 is the
ground side (-) of the 24 VAC input.The UCM cannot be
powered from a common 24 VAC transformer that is
supplying power to a device containing a full-wave
rectifier bridge in its power supply.The acceptable
voltage is 20 to 28 VAC (24 VAC cataloged). However,
voltages at either extreme may result in increased
system instability.
•Verify that communications wiring has properly been
terminated atTB2-1 (+) andTB2-2 (-). Polarity is very
important on the communications link.
•Verify that the zone sensor connections are correct as
detailed in the UCM wiring chapter.
•Verify that the proper unit DIP switch settings have
been set on each UCM.
•Verify that the tubing is properly connected to the
transducer.
Table 1.Green LED power function indication
LED StateIndication
"On”Board functioning correctly
BlinkingBoard malfunction (Replace Board)
"Off”Board does not have power
The yellow LED functions as the communication indicator.
The indication from the yellow LED is as follows:
:
Table 2.Yellow LED communication indicator function
LED StateIndication
"On”
Blinking slowly approx. 1 blink/
sec.
Blinking quickly (multiple blinks/
sec.)
"Off”
Incorrect (reversed)
communication polarity, no
connection, or shorted lines.
Communication is occurring on the
link but not for that particular UCM.
Communication is occurring on the
link, specifically with that UCM.
Polarity is correct and no
communication is occurring on the
link
Light Emitting Diode (LED)
Operations
The UCM has one green LED located nearTB3 and one
yellow LED located nearTB2 on the UCM circuit board.
These LED’s are used to help diagnose communication
(yellow) or circuit board problems (green).
The green LED (red on older boards) is a power indicator.
It is steady on when the power is on and the software is
functioning correctly. If it blinks with a 1 second on 1
second off cycle when power is applied, then the board is
not functioning and must be replaced.
VAV-SVX01D-EN9
VAV Start Up/Check Out Procedure
Zone Sensor Check-out
If an erroneous temperature isbeing reported to theUCM,
use the “Zone sensor temperature-resistance table,” p. 10
to verify the integrity of the adjustable set point
potentiometer or sensor.The resistance should be
measured across the terminals to which the device is
connected.
Note: Disconnect the zone sensor from the UCM when
making the checks listed in the table below.
Table 3.Zone sensor temperature-resistance table
Thermostat
Temp (°F)
5579217.0
5677216.5
5775316.1
5873315.7
5971415.4
6069415.0
6167514.6
6265614.3
6363614.0
6461713.6
6559713.3
6657813.0
6755812.6
6853912.3
6951912.1
7050011.8
7148111.5
7246111.2
7344211.0
7442210.7
7540310.4
7638310.2
7736410.0
783449.7
793259.5
803069.3
812869.0
822678.8
832478.6
842288.4
852088.2
Note: Thumbwheel resistance checks are made at TB3-2 and TB3-3 on the
zone sensor. Temperature sensor resistance is measured at TB3-1
and TB3-2 of the zone sensor.
Thumbwheel
Resistance (Ohms)
Sensor Resistance (k
Ohms)
10VAV-SVX01D-EN
UCM 4.2 Installation and Wiring
UCM power requirement, add the power consumption per
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
WARNING
Proper FieldWiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Chapter Overview
This chapter contains information about the following:
•UCM 4.2 Power Wiring
•Zone Sensor Wiring
•Communication Wiring
•DIP Switch Settings Selection
UCM 4.2 Power Wiring
Power Requirements
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.
Use at least 16 AWG for power wiring and connect to
terminalTB1-1 (+) andTB1-2 (-). 24 VAC is required to
power the UCM control and has an acceptable voltage
tolerance of 20 to 28 VAC. Replace the UCM control box
cover after field wiring to prevent any electromagnetic
interference.
Note: A dedicated 24 VAC, 50VA NEC class 2 transformer
is recommended to power the UCM. When
powering multiple UCM’s from one transformer,
polarity must be maintained.TerminalTB1-1 is
designated positive (+) and terminalTB1-2 is
negative (-) to the unit casing ground.
The power consumption for cooling only Series F Models
(VariTrac andVariTrane) is 12 VA (4 VA for the air valve/
actuator and 8 VA for the board).To determine the total
VAV-SVX01D-EN11
stage to the circuit board power requirement. For
example, a Series F unit containing magnetic contactors
with three stages of reheat would consume 42 VA.
Table 4.VA rating for components
StyleVolt Amps
F - Style Actuator4 VA
Air Valve Actuator C through E Style12 VA
Varitrac Actuator3 VA
Fan Power Fan Output6 VA
Hot Water Proportional4 VA
Hot Water 2 Position6.5 VA
Electric Heater Magnetic Contactor10 VA
Electric Heater Mercury Contactor12 VA
Note: VariTrane™ and VariTrac™ cooling only Series D
and E models consume 20 VA (12VA for the
actuator and 8VA for the UCM).The heating output
ratings remain the same.
See Figure 1,p. 7 for UCM terminallocations and Figure 2,
p. 13 through Figure 5, p. 16 for wiring of output devices.
Zone Sensor Wiring
Location and Mounting
A zone sensorin each control zone should belocated in the
most critical area of the zone. Sensors should not be
mounted in direct sunlight or in the area’s supply air
stream. Subdivision of the zone may be necessary for
adequate control and comfort.
Avoid mounting zone sensors in areas subject to the
following:
•Drafts or “dead spots” behind doors or corners
•Hot or cold air ducts
•Radiant heat from the sun or appliances
•Concealed pipes or chimneys
•Unheated or uncooled surfaces behindthe sensor such
as outside walls
•Air flows from adjacent zones or other units
Wiring
Each unit must be controlled by a zone sensor that is
designated specifically for use with the UCM control.Field
wiring for the zone sensors must meet the following
requirements:
•Must be 14 to 18 AWG
•Refer to the sensor instructions for terminal
connections.
•If local codes require enclosed conductors, the zone
sensor wires should be installed in conduit. Do not
UCM 4.2 Installation andWiring
route zone sensorwires in conduitwith 24VAC or other
high power conducting wires.
Multiple UCM’s Per Zone Sensor
Up to three (3) UCM’s may be connected to a single zone
sensor and thumbwheel set point.
•Connect terminal connectionsTB3-1,TB3-2, andTB33 in parallel (i.e. daisy chain) from the master UCM to
the slaved UCM(s).
Note: Proper polarity must be maintained.
•Cut jumper wires W1 and W2 on the slaved UCM’s
(never cut jumper wires W1 and W2 on master UCM).
Multiple UCM’s per Auxiliary Duct
Temperature Sensor
Up to three (3) UCMs may be connected to a single
auxiliary duct temperature sensor.
•Connect terminal connectionsTB3-5 andTB3-6 in
parallel (i.e. daisy chain) from the master UCM to the
slaved UCM(s).
Note: Proper polarity must be maintained.
•Cut jumper wire W4 on the slaved UCMs (never cut
jumper wire W4 on the master UCM).
Zone Sensor Hardwired Option
Depending on the zone sensor options used, a maximum
of five wires may be required to run from the UCM to the
zone sensor. The zone sensor options are:
•Zone sensor only (2 wires) - Part Number
X13511528010
•Sensor with night set back - Part Number
X13511530010
•Zone sensor with external adjustable - Part Number
X13511529010
•Zone sensor with external adjustable night set back,
timed override (TOV) on/cancel button - Part Number
X13511527010
•Digital zone sensor - Part Number X13790866010
•Communications jack - Part Number X13651467020
(for one box of 12)
Note: All wiring from the zone sensor to the
Communication link must be twisted shielded pair
wiring.
Zone Sensor Wireless Option
Wireless Zone Sensor
Receiver is used to receive a signal from the wireless zone
sensor and can be factory installed- Part Number
X13790855010.
The wiring harness connects the receiver to the UCM 4.2
- Part Number X19051692010.
Zone Sensor
The wireless zone sensor with night setback timed
override (TOV) on/cancel button. Also can be ordered for
Celsius and Fahrenheit setpoint adjustment - Part Number
X13790492010 (F), X13790494010 (C). DigitalWireless Part
Number: X13790822010.
Communication Wiring
Communication Link Wiring
The “Communication Link” is the communication wiring
betweenTracer Summit® and all VAV box Unit Control
Modules (UCM).Tracer Summit can be connected to the
UCM communication link in a“daisy chain” configuration.
Note: It is not necessary for each UCM to beconnected to
the line in sequential order by address. Also,
multiple communication links may be run and
terminated atTracer Summit. However, a
consistent, documented wiring path will help
troubleshoot communication problems after
installation.
Field wiring for the communication link must meet the
following requirements:
1. Communication link wiring must be at least 18 AWG
twisted shielded pair wire. Shields must be grounded
atTracer Summit or Central Control Panel (CCP) only.
More than one ground reference will cause
communications failures. Shields must be daisy
chained.Tape the shield at the lastVAV UCM to prevent
any connection between the shield and ground. Wire
specifications are as follows:
Plenum Cable
Stranded, tinned copper insulated with extruded FEP.
Conductors cabled and shielded with overall
aluminum/Mylar tape and stranded, tinned copper
drawn wire. Extruded jacket, 300 volt, 150°C NEC 7252 (b) class 2, type CL2P, 25 pF/ft.
Non-Plenum Cable
Stranded tinned copper insulated with polyethylene.
Conductors cabled and shielded with overall
aluminum/polyester tape and stranded, tinned copper
drain wire. Chrome gray PVC jacket, 300V, 60°C NEC
type CM, 24 pF/ft.
Table 5.Wire capacitance
Max. Communication
Link Wiring LengthMax. Wire Capacitance
1,000 feet (304.8m)Up to 60 pF/ft. (196.9 pF/m)
2,000 feet (609.6 m)Up to 50 pF/ft. (164.0 pF/m)
3,000 feet (914.4m)Up to 40 pF/ft. (131.2 pF/m)
4,000 feet (1,219.2 m)Up to 30 pF/ft. (98.4 pF/m)
5,000 feet (1,524 m)Up to 25 pF/ft. (82.0 pF/m)
Note: Wire capacitance must comply with this table.
12VAV-SVX01D-EN
UCM 4.2 Installation andWiring
2. The maximum wire length should not exceed 5,000
feet (1,524 m).
3. Communication link wiring cannot pass between
buildings.
4. A maximum of 63 UCMs can be connected to each
COM Link. Daisy chaining is a typical configuration.
“STAR” chaining is also acceptable.
Note: Polarity is extremely important and must be
observed on communication link connections.
5. At the VAV box, communication link wires must be
connected toTB2-1, 3 (+) andTB2-2, 4 (-) terminals on
the UCM.
6. Verify that the UCM address is properly set (DIP switch
SW1). See
Table 6, p. 13 for proper DIP switch settings.
DIP Switch Settings
DIP Switch SW1 contains six switches for addressing the
UCM.These switches allow a user to set a unique
communication address for each UCM. Each UCM on a
given communication link must have a unique address in
order forTracer Summit or the CCP to communicate to it.
Refer to Table 6, p. 13 for UCM 4.2 DIP switch settings.
Note: When using Rover™ service tool to communicate
to the UCM, you must add 64 to the DIP switch
address. For example, a UCM with the DIP switch
address set to 1 would be UCM Number 65 in
Rover.
Figure 2.Rover screen/application
Table 6.DIP switch settings for UCM 4.2
UCM
Unit #
Address123456
165OFFONONONONON
266ONOFFONONONON
367OFFOFFONONONON
468ONONOFFONONON
569OFFONOFFONONON
670ONOFFOFFONONON
771OFFOFFOFFONONON
872ONONONOFFONON
Dip
Table 6.DIP switch settings for UCM 4.2 (continued)
UCM
Unit #
Address123456
973OFFONONOFFONON
1074ONOFFONOFFONON
1175OFFOFFONOFFONON
1276ONONOFFOFFONON
1377OFFONOFFOFFONON
1478ONOFFOFFOFFONON
1579OFFOFFOFFOFFONON
1680ONONONONOFFON
1781OFFONONONOFFON
1882ONOFFONONOFFON
1983OFFOFFONONOFFON
2084ONONOFFONOFFON
2185OFFONOFFONOFFON
2286ONOFFOFFONOFFON
2387OFFOFFOFFONOFFON
2488ONONONOFFOFFON
2589OFFONONOFFOFFON
2690ONOFFONOFFOFFON
2791OFFOFFONOFFOFFON
2892ONONOFFOFFOFFON
2993OFFONOFFOFFOFFON
3094ONOFFOFFOFFOFFON
3195OFFOFFOFFOFFOFFON
3296ONONONONONOFF
3397OFFONONONONOFF
3498ONOFFONONONOFF
3599OFFOFFONONONOFF
36100ONONOFFONONOFF
37101OFFONOFFONONOFF
38102ONOFFOFFONONOFF
39103OFFOFFOFFONONOFF
40104ONONONOFFONOFF
41105OFFONONOFFONOFF
42106ONOFFONOFFONOFF
43107OFFOFFONOFFONOFF
44108ONONOFFOFFONOFF
45109OFFONOFFOFFONOFF
46110ONOFFOFFOFFONOFF
47111OFFOFFOFFOFFONOFF
48112ONONONONOFFOFF
49113OFFONONONOFFOFF
50114ONOFFONONOFFOFF
51115OFFOFFONONOFFOFF
52116ONONOFFONOFFOFF
53117OFFONOFFONOFFOFF
54118ONOFFOFFONOFFOFF
55119OFFOFFOFFONOFFOFF
56120ONONONOFFOFFOFF
57121OFFONONOFFOFFOFF
58122ONOFFONOFFOFFOFF
59123OFFOFFONOFFOFFOFF
Dip
VAV-SVX01D-EN13
UCM 4.2 Installation andWiring
Table 6.DIP switch settings for UCM 4.2 (continued)
UCM
Unit #
Address123456
60124ONONOFFOFFOFFOFF
61125OFFONOFFOFFOFFOFF
62126ONOFFOFFOFFOFFOFF
63127OFFOFFOFFOFFOFFOFF
Figure 3.Wiring diagram for single duct units with factory installed electric reheat
Dip
The following figures show wiring diagrams for typical
applications of UCM 4.2
.
HEATER STAGE
CONTACTOR(S)
3RD 2ND
3RD STG.
R
J11
ADDRESS
SWITCH
+ -
TB2-1
IN
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
NOTE:
1.
2.
1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR
WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM
TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE
COMMUNICATIONS INTERFACE.
6.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
7.
S TERMINAL NOT TO BE USED WITH VARITRANE.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
8.
MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONTROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
CONTACTORS ARE 24 VAC: 12VA MAX/COIL (MERCURY CONTACTORS). 10VA MAX/COIL
9.
(MAGNETIC CONTACTORS)
10.
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORMER LOCATED IN HEATER.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
11.
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
OPTIONAL
9.
TRANSFORMER
1ST
HOT
1ST STG.
2ND STG.
V
J10
Y
-2
O
TB1
BR
J1
J7
J8
J9
CONTROL BOARD
+
-
+ -
-4
TB2-3
TB2-5
TB2
TB2-2
IN
OUT
OUT
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
BL
1-1
B
T
D.D.C.\U.C.M.
TB2-6
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
DAMPER
10.
ACTUATOR
WIRING
T
PEN
O
HOT
HO
CLOSE
1
1-2
4-1
B
T
TB1-1
TB
ACT
YEL GRN
OPTIONAL FACTORY INSTALLED
BIP
GND
ZONE
TB3-1
WIRELESS
24V
GNDA/CO2
-2
TB3
-5
3-3
TB3
TB
J3
PRESS
1
GNDSET
6
TB3-
TB3-5
AUX TEMP SENSOR
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
PRESSURE
TRANSDUCER
R
+
BK
VOUT
G
-
S
7.
D.D.C.\U.C.M.
CONTROL BOX
TB3-6
6.
OPTIONAL
UCM or EI Board
TB3-3
TB2-5
11.
TB3-3
3.
DUCT
MOUNTED
MOUNTED
+
0
V
Y
TB3-2
3 2 1
TB3-2
2 1
4.
(TB1-1) 24V
(TB3-6) GND
(TB3-5) A/CO2
BL
Y
BL
1-1
TB1-2
TB
24V
GND
TB3-1
TB3-1
OPTIONAL
8.
FACTORY
INSTALLED
WIRELESS
24VAC
TB2-6
TB1-1
TB1-2
114.7106
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5
1(-)2(+)3
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
LL
6.
WA
24V
CO2
GND
SENSOR
OUT
OPTIONAL FIELD INSTALLED
CO2 SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÃA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
14VAV-SVX01D-EN
Figure 4.Wiring diagram for fan-powered units with field installed reheat
UCM 4.2 Installation andWiring
VAV-SVX01D-EN15
UCM 4.2 Installation andWiring
Figure 5.Wiring diagram for fan-powered units with factory installed electric reheat
2ND STG HEAT
V
J10
J11
ADDRESS
SWITCH
+ -+
TB2-2
TB2-1
IN
1ST STG HEAT
O
J9
IN
HEATER
TERMINAL
BOX WIRING
J7
J8
-+
B2-4
T
TB2-3
T
OU
OUT
ACTUATOR
BR-HOT
J1
ACT
1
B4-1
T
BIP
D.D.C.\U.C.M.
CONTROL BOARD
-
YEL
2-5
B
TB2-6
T
GRN
DAMPER
WIRING
OT
OPEN
HOT
H
TB1-2
GND
ZONESETGND
3-1
B
T
TB3-3
6.
TB3-2
3 2
Y
Y
TB1-2
GND
TB3-2
3 2 1
TB3-1
1
TB3-1
BL
BL
1-1
B
T
24V
OPTIONAL
FAN CONTROL
BOX WIRING
E
LOS
C
R-FAN
1-1
B
T
24V
A/CO2
GND
3-3
B3-5
B
B3-2
T
TB3-6
T
T
ESS
PR
24 VAC
J3
1
S
BR
TRANSDUCER
R
BK
G
7.
Y
BL
PRESSURE
+
VOUT
-
D.D.C.\U.C.M.
CONTROL BOX
FACTORY
INSTALLED
WIRELESS
24VAC
UCM or EI Board
TB2-6
TB1-1
TB1-2
TB2-5
11
10 7 6
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5
TB3-3
1(-)2(+)
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3. 4.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
SHIELDED
TWISTED PAIR
COMMUNICATIONS
WIRING
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
OPTIONAL FACTORY INSTALLED
WIRELESS
TB3-6TB3-5
6.
OPTIONAL
AUX TEMP SENSOR
SENSOR
NOTE:
1.
1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
2.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS
JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM TRANSFORMER.
THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS
INTERFACE.
6.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
7.
S TERMINAL NOT TO BE USED WITH VARITRANE.
8.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS
JACK EQUIPPED ZONE SENSOR OPTION.
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
6.
WALL
DUCT
MOUNTED
MOUNTED
24V
GND
OUT
CO2 SENSOR
+
0
V
(TB3-6) GND
CO2
OPTIONAL FIELD INSTALLED
(TB1-1) 24V
(TB3-5) A/CO2
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÃA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
WARNING
AVERTISSEMENT
ADVERTENCIA
16VAV-SVX01D-EN
Wireless Zone Sensor
Overview
TheTraneWireless Zone Sensor set includes a sensor and
a receiver that work together to provide the same
functions as the equivalentTrane wired sensor (#4190-
1090), such as the standard 10 k temperature input (with
the exception of the communication jack). No further
software or hardware is necessary for site evaluation,
installation, or maintenance.
The sensor transmits the zone temperature, all zone
temperature setpoint functions, timed override Occupied
Figure 6.Outside dimensions for sensor
2.90 in (7.35 cm)
(On) and timed override Unoccupied (Cancel) information
to the receiver.The receiver electrically reproduces the
zone temperature resistance, all zone temperature
setpoint function resistances, and timed override On and
timed override Cancel information as sent by the sensor.
Dimensional Diagrams
See Figure 6,p. 17 and Figure 7, p. 18 fordimensions of the
Wireless Zone Sensor set.The dimensions are the same
for both the sensor and the receiver.
1.08 in (2.75 cm)
4.78 in (12.14 cm)
2.62 in (6.65 cm)
Note: The dimensions are the
same for both the sensor
and the receiver.
VAV-SVX01D-EN17
Wireless Zone Sensor
Figure 7.Mounting hole dimensions for sensor
3.27 in (8.30 cm)
2.36 in (6.00 cm)
1.34 in (3.41 cm)
Setting the Address, Mounting,
Wiring, and Associating the
Receiver and Sensor
The following procedure list shows the recommended
order for installation:
•Choosing a location for mounting the sensor
•Settingthe rotary address switches on the receiver and
on the sensor
•Replacing and securing the receiver cover
•Powering the sensor and associating the sensor to the
receiver
•Applying power to the receiver
• Testing signal and battery strength
•Disassociation
Note: The dimensions are the
same for both the sensor
and the receiver.
Choosing a Location for Mounting the
Sensor
Placement of the receiver and the sensor set is critical to
proper operation. In most installations, distance is not the
limiting factor for proper radio signal quality. It is more
greatly affected by walls, barriers, and general clutter. For
best radio transmission range and reliability, wherever
possible, mount the receiver andsensor in line of sight.Try
to minimize the number of barriers between the pair of
devices. In general, sheetrock walls and ceiling tiles offer
little restriction to the propagation of the radio signal
throughout the building; concrete or metal barriers offer
the most restriction.Thetransmission range for the sensor
is as follows:
•Open range: 2,500 ft (762 m) (packet error rate = 2%)
•Usable range: 200 ft (61 m)
• Typical range: 75 ft (23 m)
18VAV-SVX01D-EN
Wireless Zone Sensor
DRESS
IN
LED3
L
ED2
T
A
Ambient considerations
Avoidlocations that are outside theoperating temperature
and humidity range (see Table 14, p. 48).
Location Considerations for the Sensor
When selecting a location for the sensor, consider both
thermal and radio transmission characteristics of the
location.
Thermal considerations
•Avoid areas of direct sunlight
•Avoid areas in the direct air stream of air diffusers
•Avoid exterior walls and other walls that have a
temperature differential between their two sides
•Avoid areas close to sources of heat such as sunlight,
appliances, or other equipment
•Avoid drafty areas
•Avoid dead spots behind doors, projection screens, or
corners
Radio transmission considerations
•Avoid placing the sensor inside metal enclosures
•Avoid radio transmissions through thick, solid
concrete walls
Setting the Rotary Address Switches on
the Receiver and the Sensor
Note: To expedite the installation and association
process, set the addresses before applying power
to the receiver.
The process of establishing communication between the
receiver and sensor is referred to as association.The
receiver and the sensormust have their rotary switches set
to the same address in order to enable communication
between the two devices (see Figure 8, p. 19). Important
limitations are as follows:
•Only one associated receiver/sensor set can
communicate within the reception range of the
wireless system.
•It is not possible to associate more than one sensor to
a receiver, nor is it possibleto associate morethan one
receiver to a sensor.
•Avoid metal barriers between the sensor and receiver,
such as plastered walls with metal lathe as they will
decrease radio signal quality.
Figure 8.Setting the rotary address switches on the receiver and the sensor
Do not remove the
insulation strip yet.
B1 +
WIRELESS
L
STAL
LED1
LED2
LED3
LED5
SIGNAL
POWER
S5
S1
ADD
HEATING SET
FAN/SYSTEM
5
S
SETPOINT
ZONE
GND
24VAC/DC
GND
COMM +
COMM -
S2
C33
LED4
S4
S3
C34
J1
C35
R77
Setting the Receiver Address
1. Using a small screwdriver, set the three rotaryaddress
switches (locations S1, S2, S3) on the receiver
(Figure 8, p. 19) to an address between 001 and 999.
Note: Do not use 000 as an address for installation. If
you set the receiver address to 000, it will:
– Return the receiver outputs to their factory
defaults indefinitely (zone temperature and
setpoint outputs: 72.5°F [22.5°C])
!
Pb
S1
ADDRESS
Pb-FREE
S3
LED4
S2
STATUS
S4
WIRELESS
INSTALL
LED1
SIGNAL
LED5
BATTERY
STATUS
– Make the receiver unable to associate with a
sensor
• Read the switches from left to right in the order in
which they are numbered (S1, S2, S3).
• Zero is at the 9 o'clock position.
2. Make a notation of the address and location of the
receiver.
– Remove all association knowledge
VAV-SVX01D-EN19
Wireless Zone Sensor
Setting the Sensor Address
1. Using a small screwdriver, set the three rotaryaddress
switches (locations S1, S2, S3) on thesensor (Figure 8,
p. 19) to the same address used for the receiver it is to
be associated with.
2. Make a notation of the address and locationwhere this
sensor is to be mounted.
Note: Do not use 000 as an address for installation. If
you set the address to 000, it will:
– Remove all association knowledge
– Revert to a low-power hibernation mode.
– Send a disassociation request to the receiver. If
the sensor and receiver are associated and
communicating at the time the sensor is set to
000 and theTest button is pressed, the receiver
will also become unassociated and will be
available for re-association.
• Read the switches from left to right in the order in
which they are numbered (S1, S2, S3).
• Zero is at the 9 o'clock position.
3. Make a notation of the address and location of the
sensor.
Factory Wiring of the Receiver to the VAV
UCM
The required power for the receiver is 24 VAC or 24 Vdc
and is less than 1 VA.The receiver is designed to be
powered by the VAV UCM controller.
Note: A dedicated transformer is not necessary or
advised.
20VAV-SVX01D-EN
Figure 9.Factory wiring of the receiver to the VAV UCM
Wireless Zone Sensor
W (HOT)
TO J8
BK (CLOSE)
TO J9
R (OPEN)
TO J10
OPTIONAL FIELD INSTALLED
PROPORTIONAL WATER VALVE
J10
J11
ADDRESS
SWITCH
TB2-2
TB2-1
IN
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
TB3-5
AUX TEMP SENSOR
NOTE:
1.
2.
1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TW ISTED PAIR
WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPT ION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
THE OPTIONAL BINARY INPUT CONNECTS BETW EEN TB4-1 (BIP) AND 24VAC (HOT) FROM
TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE
COMMUNICATIONS INTERFACE.
6.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
7.
S TERMINAL NOT TO BE USED WIT H VARITRANE.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
8.
MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONT ROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORM ER WIRING. WIRINGS GOES THRU TO
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
11.
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
PROP.
WATER
VALVE
24VAC
12VA MAX
J1
8
J9
J7
J
ACT
D.D.C.\U.C.M.
CONTROL BOARD
+ -+ -
TB2-3
OUTINOUT
TB2-4
TB3-6
-
+
TB2-6
TB2-5
6.
OPTIONAL
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
DAMPER
ACTUATOR
WIRING
T
HO
HOT
1
4-1
TB
BIP
GND
ZONE
YEL
GRN
3-1
TB
OPTIONAL FACTORY INSTALLED
WIRELESS
TB2-6
TB2-5
2(+)
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
Table 7.Wiring harness: wire identification
PEN
O
1-2
TB
GND
TB3-3
CLOSE
TB1-1
24V
SETGND
TB3-3
TB3-2
TB3-1
TB3-2
231(-)1
4.3.
A/CO2
TB3-5
J3
RESS
P
1
3-6
TB
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
PRESSURE
TRANSDUCER
R
+
BK
VOUT
G
-
S
7.
D.D.C.\U.C.M.
CONTROL BOX
6.
WALL
24V
CO2
GND
SENSOR
OUT
OPTIONAL FIELD INSTALLED
CO2 SENSOR
2ND STG.
TO J10
1ST STG.
TO J9
HOT
TO J8
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
TO J9
TO J8
OPTIONAL FIELD INSTALLED
0N-OFF WATER VALVE
D
MOUNTE
8.
D
UNTE
DUCT
MO
(TB1-1) 24V
+
(TB3-6) GND
0
(TB3-5) A/CO2
V
HEATER STAGE
CONTACTOR(S)
24VAC, 12VA
MAX/COIL
ON - OFF
WATER VALVE
24 VAC
12VA MAX
OPTIONAL
FACTORY
INSTALLED
WIRELESS
24VAC
OPTIONAL
FUSE, DISCONNECT
& TRANSFORMER
OPTIONAL POWER
TRANSFORMER
(50VA)
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
TB2-6
TB1-1
TB1-2
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÃA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
Y
Y
TB1-2
GND
UCM or EI Board
(BK)
W)
(
or
or
L
Y
B
BK
UCM or EI Board
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED