Trane VAV-SVX02B-EN User Manual

Installation/ Operation Maintenance
VariTrane
Pneumatic Controls
March 2002
VAV-SVX02B-EN
Thermostat
20
(137.9)
(103.4)
Thermostat Selection and Location
In general, both one- and two-pipe thermostats have a gain of 2.5 psi per degree Fahrenheit, unless special thermostats are used that provide a different gain. The major difference between them is that a one-pipe thermostat is considered a low­capacity thermostat and a two-pipe thermostat is considered a high­capacity thermostat.
When selecting between one-pipe and two-pipe thermostats consider the following:
Use one-pipe thermostat when:
tubing runs are less than 50 feet from
thermostat to controller.
a single thermostat will control no
more than three controllers.
slower response is desired from the
thermostat.
Use two-pipe thermostat when:
tubing runs exceed 50 feet from
thermostat to controller.
a single thermostat will control four or
more controllers.
high capacity air is required due to
restrictions in the air line.
Thermostat Piping
The two-pipe thermostat (Figure 1) includes a restrictor (internally). Attach supply air line and output pressure (branch) line to the thermostat.
The one-pipe thermostat (Figure 2) requires an external restrictor tee. Connect main air supply to restricted leg of restrictor tee. Connect branch line from restrictor tee to the thermostat.
Figure 1–Two-Pipe Remote Thermostat (Reverse-Acting)
Tee
S
Figure 2–Typical One-Pipe Thermostat (Reverse-Acting)
Restrictor
Tee
Tee
Restricted Leg
S
20
Fan
(137.9)
P.E.
Switch–1
(N.O.)
9 PSI
(62.06 kPa)
Two-Pipe
Remote-Mounted
T-Stat
(Reverse-Acting)
One-Pipe
Remote-Mounted
T-Stat
(Reverse-Acting)
2
Thermostat
Specifications
TP970 Series Pneumatic T-stats
Maximum Safe Air Pressure:
25psi (172 kPa)
Maximum Safe Air Temperature:
150°F (66°C)
Throttling Range:
2–10°F (1–5°C)
Gain:
2.5 psi/°F Adjustable
Operation
Pneumatic thermostats modulate output air pressure in response to room air temperature. Pneumatic thermo­stats fall into two categories: direct­acting or reverse-acting. This section describes how thermostat output pressure responds to changes in room temperature.
Figure 3 graphically illustrates the relationship between room temperature and output pressure of a direct-acting thermostat. The graph in Figure 3 shows that as the room temperature increases, so does the output pressure of the thermostat.
Figure 3–Direct-Acting Thermostat Response
Output Pressure
Figure 4 illustrates the pressure/ temperature characteristics for a reverse-acting thermostat. As room temperature increases, the thermostat output pressure decreases.
Figure 4 –Reverse-Acting Thermostat Response
Output Pressure
Input Temperature
A thermostat in proper working order will be able to output a pressure ranging from approximately .5 psi to supply air pressure depending on distance from indicated setpoint.
Input Temperature
3
Reversing Relay
Installation and Operation
The reversing relay is a proportional, non-bleeding device for use in pneu­matic control systems where a propor­tional signal from a controlling device must be reversed (see Figure 5). The most common use of the reversing relay is to change the action of a pneumatic thermostat.
Figure 5 –Pneumatic Reversing Relay Trane Part No. RLY-755
The reversing relay requires three piping connections: main/supply air, input signal air, and output branch air (see Figure 6). The branch line pressure decreases in direct proportion to an increase in the input signal pressure and vice-versa. The input signal is also amplified, thereby minimizing any pneumatic line transmission lag (see Figure 7).
Input pressure to the relay and output pressure to the PR should always add up to a constant, which is usually set between 16 and 25 psi. For example, with a constant of 18, six-pound input signal will result in a 12 pound branch signal. A bias adjustment screw is provided to retard or advance the out signal.
Figure 6 –Reversing Relay Connections
Output
S
Branch
20
(137.9)
Input
Branch
Figure 7 – Reversing Relay Characteristics
15
Inc.
12
3
Output Branch Pressure
3
Input Pressure Signal
B
Reversing
M
S
6
Relay
9 PSI In
(62.06 kPa)
9 PSI Out
(62.06 kPa)
15
Inc.
4
Reversing Relay
Calibration
By using the “bias” adjustment on the relay, the factory-set 8.0–9.0 “cross­over” can be changed. To recalibrate, the relay should be connected as illustrated in Figure 8.
Pressure
Regulator
M
If the new desired “cross-over” pressure is 11.0 psi, this must be applied to port #3 by adjusting the pressure regulator. The “bias” adjustment is then turned until 11.0 psi is obtained on the output gage. Turning the “bias” adjust­ment “CW” increases the out put; “CCW” decreases it.
This 11.0 psi “cross-over” would yield the following operational chart:
Chart
Figure 8 – Recalibrating Reversing Relay
Gage
M
1
C
3
New Cross-over pressure
Bias
Adjustment
Screw
Input: 1234567891011121314151617181920 Output: 2019181716151413121110987654321
Specifications
Maximum Pressure:
30 psig
Connections:
3/16" (4.& mm) nipples for ¼" (6.4 mm) OD polyethylene tubing
Air Consumption:
0.5 SCFH (.236 L/M) @ 20 psig
Material:
ABS
Ambient Limits:
+40°F/+120°F operating (+4°C/+49°C)
Mounting:
In-line via air connections
Factory Settings:
9 psig in./9 psig out and 8 psig in./8 psig out
Bias Adjustment:
+/-15 psi
Weight:
3 ½ oz
5
Loading...
+ 11 hidden pages