Trane VAV-SVX02B-EN User Manual

Page 1
Installation/ Operation Maintenance
VariTrane
Pneumatic Controls
March 2002
VAV-SVX02B-EN
Page 2
Thermostat
20
(137.9)
(103.4)
Thermostat Selection and Location
In general, both one- and two-pipe thermostats have a gain of 2.5 psi per degree Fahrenheit, unless special thermostats are used that provide a different gain. The major difference between them is that a one-pipe thermostat is considered a low­capacity thermostat and a two-pipe thermostat is considered a high­capacity thermostat.
When selecting between one-pipe and two-pipe thermostats consider the following:
Use one-pipe thermostat when:
tubing runs are less than 50 feet from
thermostat to controller.
a single thermostat will control no
more than three controllers.
slower response is desired from the
thermostat.
Use two-pipe thermostat when:
tubing runs exceed 50 feet from
thermostat to controller.
a single thermostat will control four or
more controllers.
high capacity air is required due to
restrictions in the air line.
Thermostat Piping
The two-pipe thermostat (Figure 1) includes a restrictor (internally). Attach supply air line and output pressure (branch) line to the thermostat.
The one-pipe thermostat (Figure 2) requires an external restrictor tee. Connect main air supply to restricted leg of restrictor tee. Connect branch line from restrictor tee to the thermostat.
Figure 1–Two-Pipe Remote Thermostat (Reverse-Acting)
Tee
S
Figure 2–Typical One-Pipe Thermostat (Reverse-Acting)
Restrictor
Tee
Tee
Restricted Leg
S
20
Fan
(137.9)
P.E.
Switch–1
(N.O.)
9 PSI
(62.06 kPa)
Two-Pipe
Remote-Mounted
T-Stat
(Reverse-Acting)
One-Pipe
Remote-Mounted
T-Stat
(Reverse-Acting)
2
Page 3
Thermostat
Specifications
TP970 Series Pneumatic T-stats
Maximum Safe Air Pressure:
25psi (172 kPa)
Maximum Safe Air Temperature:
150°F (66°C)
Throttling Range:
2–10°F (1–5°C)
Gain:
2.5 psi/°F Adjustable
Operation
Pneumatic thermostats modulate output air pressure in response to room air temperature. Pneumatic thermo­stats fall into two categories: direct­acting or reverse-acting. This section describes how thermostat output pressure responds to changes in room temperature.
Figure 3 graphically illustrates the relationship between room temperature and output pressure of a direct-acting thermostat. The graph in Figure 3 shows that as the room temperature increases, so does the output pressure of the thermostat.
Figure 3–Direct-Acting Thermostat Response
Output Pressure
Figure 4 illustrates the pressure/ temperature characteristics for a reverse-acting thermostat. As room temperature increases, the thermostat output pressure decreases.
Figure 4 –Reverse-Acting Thermostat Response
Output Pressure
Input Temperature
A thermostat in proper working order will be able to output a pressure ranging from approximately .5 psi to supply air pressure depending on distance from indicated setpoint.
Input Temperature
3
Page 4
Reversing Relay
Installation and Operation
The reversing relay is a proportional, non-bleeding device for use in pneu­matic control systems where a propor­tional signal from a controlling device must be reversed (see Figure 5). The most common use of the reversing relay is to change the action of a pneumatic thermostat.
Figure 5 –Pneumatic Reversing Relay Trane Part No. RLY-755
The reversing relay requires three piping connections: main/supply air, input signal air, and output branch air (see Figure 6). The branch line pressure decreases in direct proportion to an increase in the input signal pressure and vice-versa. The input signal is also amplified, thereby minimizing any pneumatic line transmission lag (see Figure 7).
Input pressure to the relay and output pressure to the PR should always add up to a constant, which is usually set between 16 and 25 psi. For example, with a constant of 18, six-pound input signal will result in a 12 pound branch signal. A bias adjustment screw is provided to retard or advance the out signal.
Figure 6 –Reversing Relay Connections
Output
S
Branch
20
(137.9)
Input
Branch
Figure 7 – Reversing Relay Characteristics
15
Inc.
12
3
Output Branch Pressure
3
Input Pressure Signal
B
Reversing
M
S
6
Relay
9 PSI In
(62.06 kPa)
9 PSI Out
(62.06 kPa)
15
Inc.
4
Page 5
Reversing Relay
Calibration
By using the “bias” adjustment on the relay, the factory-set 8.0–9.0 “cross­over” can be changed. To recalibrate, the relay should be connected as illustrated in Figure 8.
Pressure
Regulator
M
If the new desired “cross-over” pressure is 11.0 psi, this must be applied to port #3 by adjusting the pressure regulator. The “bias” adjustment is then turned until 11.0 psi is obtained on the output gage. Turning the “bias” adjust­ment “CW” increases the out put; “CCW” decreases it.
This 11.0 psi “cross-over” would yield the following operational chart:
Chart
Figure 8 – Recalibrating Reversing Relay
Gage
M
1
C
3
New Cross-over pressure
Bias
Adjustment
Screw
Input: 1234567891011121314151617181920 Output: 2019181716151413121110987654321
Specifications
Maximum Pressure:
30 psig
Connections:
3/16" (4.& mm) nipples for ¼" (6.4 mm) OD polyethylene tubing
Air Consumption:
0.5 SCFH (.236 L/M) @ 20 psig
Material:
ABS
Ambient Limits:
+40°F/+120°F operating (+4°C/+49°C)
Mounting:
In-line via air connections
Factory Settings:
9 psig in./9 psig out and 8 psig in./8 psig out
Bias Adjustment:
+/-15 psi
Weight:
3 ½ oz
5
Page 6
Model 3011—Pneumatic
C
N
I
N
I
C
Volume Regulator
Model 3011
The model 3011 Pneumatic Volume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats.
Installation
1. Attach bracket either vertically or horizontally to the illustration surface. Horizontal is preferred, vertical is acceptable, any other position is not acceptable (see Figure 9).
2. Insert controller into its bracket. Controller may be face up, face down, face left, or face right. The controller LO and HI stat delta P must be calibrated in the same position that it is mounted.
Figure 9–Acceptable Installation Positions
Connections
Figure 10 illustrates a typical piping diagram of a normally-open or normally­closed unit.
Figure 10–Typical Piping Diagram of Normally-Open or Normally-Closed Unit
Normally-Open Unit or
Normally-Closed Unit
One-Pipe
Remote-Installed
T-Stat
Restricted Leg
H
DAMPER
NC
Volume
Regulator
N
C
T
LO STAT
HI STAT
C
RESET SPAN
Restrictor
Tee
P
P
LO
HI
Actuator
B
M
Airflow Sensor
G
S
20
S
20
Selecting Direct- or Reverse-Acting Thermostat (3011)
The model 3011 PVR must be calibrated to operate with either a direct-acting or reverse-acting thermostat. The control must also be changed when used with a normally-open or normally-closed air valve.
6
Page 7
Model 3011—Pneumatic
C
I
N
RESET SPAN
C
I
N
Volume Regulator
Use the following procedure to set-up the PVR:
1. Select damper action (NO or NC). Loosen damper selection switch screw and align to either the NO or NC pointer with damper pointer and tighten screw.
2. Now determine the type of thermostat that will be used. If a direct-acting thermostat is used, the reset start pressure is ty pically 8 psi. If a reverse-acting thermostat is used, the reset start pressure is typically 3 psi (see Figure 11).
3. With an accurate gage (0-10 psi) connected to port “G”, regulate the thermostat pressure to port “T” to desired start point pressure.
4. Adjust reset start to indicate 0 psi on port “G” and continuing adjusting to indicate a pressure slightly higher than 0 psi, (i.e., 0.1 psi).
Figure 11–Adjusting Reset Star t
Adjust to obtain 0–0.1 psi at port G
psi
10
0
Connect 0–10 psi Gage
Connect Hand Pump
B
NC
NO
M
DAMPER
G
RESET START LO STAT P
I
N
HI STAT P
I
N
R
R
C
C
RESET SPAN
0–20 psi
Handpump
Input desired LO stat pressure at t-stat port
Factory-set at 5 psi
Adjustable (0–10 psi)
NOTE: The arrows on the damper selector must be aligned
exactly or the range of the controller will be limited .0 psi
Adjusting the Reset Span (3011)
The reset span is factory-set at 5 psi. This is the thermostat pressure difference from which the PVR delivers flow from minimum to maximum setpoints. This range is not normally changed unless a special control scheme is used where control operation must be changed.
To field adjust a different reset span, follow these steps:
1. Connect an accurate gage to port “G”.
2. Apply 20 psi to port “T”.
3. Adjust reset span to indicate the desired span on port “G” (see Figure 12).
4. LO-stat and HI-stat delta P must now be readjusted (see following calibration procedure)
Figure 12– Adjusting Reset Span
Apply 20 psi
H
B
NC
N
NO
M
DAMPER
T
RESET START
P
LO STAT
HI STAT
R
P
N
C
PSI
G
100
Adjust to obtain desired reset span
7
Page 8
Calibration
C
I
N
C
I
N
P
Procedures
Calibration Procedure (Steps 1–4 apply to all thermostat models)
1. Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. See Figure 9 for unit application.
2. Remove the caps on the tees which are connected to the lines to the flow sensor. Connect a 0–2" magnehelic gage to monitor flow sensor delta P. The higher-pressure port is further upstream on the air valve inlet.
3. Remove the thermostat line and connect a hand pump with a 0–20 psi gage to port “T”.
4. Tee a 0–20 psi gage in the line from port “B” on the volume regulator to the air valve actuator.
Normally-Open Valve
Direct-Acting Thermostat
(See Figure 13 for proper connections)
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat mini­mum) adjustment to desired minimum.
7. Set port “T” input at 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (maxi­mum) adjustment to desired maximum flow. If the actuator pressure is less than 3 psi, the air valve is wide open and duct pressure must increase to increase flow.
9. Set port “T” at 0 psi.
10. Monitor the minimum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Reverse-Acting Thermostat
(See Figure 13 for proper connections):
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat delta P (maximum) adjustment to desired maximum. If the actuator pressure is less than 3 psi, the air valve is wide open and duct pressure must increase to increase flow.
7. Set prot “T” to 16 psi
or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (mini­mum) adjustment to desired minimum flow.
9. Set port “T” at 0 psi.
10.Monitor the maximum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Normally-Open Valve
Direct-Acting Thermostat
(See Figure 14 for proper connections):
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat (mini­mum) adjustment to desired minimum.
7. Set port “T” input at 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (maximum) adjustment to desired maximum flow. If the actuator pressure is greater than 13 psi, the air valve is wide open and duct pressure must increase to increase flow.
9. Set port “T” at 0 psi.
10.Monitor the minimum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Reverse-Acting Thermostat
(See Figure 14 for proper connections):
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat delta P (maximum) adjustment to desired maximum flow. If the actuator pressure is greater than 13 psi, the air valve is wide open and duct pressure must increase to increase flow.
7. Set prot “T” to 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (mini­mum) adjustment to desired minimum flow.
9. Set port “T” at 0 psi.
10.Monitor the maximum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Figure 13–Connections of Direct/Reverse-Acting
Thermostat with Normally-Open Valve
0–2' Magnahelic Gage
LO
HI
Normally-Open Unit
LO
HI
Actuator
Airflow Sensor
Volume
Regulator
H
B
NC
R
N
NO
M
DAMPER
G
S
20
8
RESET START
LO STAT
Apply 20 psi
T
P
HI STAT
PSI
0 10
Connect 0–20 psi Gage
Connect Hand Pump
0–2 psi
Handpump
Figure 14–Connections of Direct/Reverse-Acting
Thermostat with Normally-Closed Valve
0–2' Magnahelic Gage
LO
HI
Normally-Closed Unit
Airflow Sensor
LO
HI
Actuator
Volume
Regulator
H
B
NO
R
N
NC
M
DAMPER
G
S
20
RESET START LO STAT
C
Apply 20 psi
T
P
HI STAT
PSI
0 10
Connect 0–20 psi Gage
Connect Hand Pump
0–2 psi
Handpump
Page 9
Specifications (3011)
Specifications (3011)
Differential Pressure Range:
0 to 1.0 in. wg
Minimum Setpoint Range:
0 to 1.0" H2O
Maximum Setpoint Range:
minimum to 1.0 in. wg
Operating Static Range:
0.25–6.0 in. wg
Normal Supply Air Pressure:
20.0 psi
Minimum Supply air Pressure:
15.0 psi
Maximum Supply Air Pressure:
30.0 psi
Average Supply Air Consumption:
28.8 scim at 20 psi
Thermostat Pressure Input Range:
Adjustable 0–10 psi band from 0–20 psi
Reset Start Point Range:
0–10 psi
Reset Span Range:
0–10 psi
Maximum Safe Thermostat Input:
30 psi (closed chamber)
Operating Temperature:
+40/+120°F
Storage Temperature:
-40/+140°F
Main, Thermostat, Actuator and Static Pick-up Connections:
.250 O.D.
VAV-SVX02B-EN 9
Page 10
Model 3501—Pneumatic Volume Regulator
Model 3501
The model 3501 Pneumatic Volume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats.
Installation
1. Attach bracket either vertically or horizontally to the installation surface. Horizontal is preferred, vertical is acceptable, any other position is not acceptable.
2. Insert controller into its bracket. Controller may be face up, face down, face left, or face right. The controller LO and HI stat delta P must be calibrated in the same position that it is installed.
Selecting Direct- or Reverse-Acting Thermostat (3501)
The model 3501 PVR must be calibrated to operate with either a direct-acting or reverse-acting thermostat. The control must also be changed when used with a normally-open or normally-closed air valve.
Use the following procedure to set-up the PVR:
1. Select damper action (NO or NC). Loosen damper selection switch screw and align to either the NO or NC pointer with damper pointer and tighten screw.
2. Now determine the type of thermostat that will be used. If a direct-acting thermostat is used, the reset start pressure is typically 8 psi. If a reverse­acting thermostat is used, the reset start pressure is typically 3 psi.
3. With an accurate gage (0–30 psi) connected to port “G”, regulate the thermostat pressure to port “T” to
10.5 psi.
4. Adjust reset start to indicate 2.5 psi on port “G”
Adjusting the Reset Span (3501)
The reset span is factory-set at 5 psi. This is the thermostat pressure differ­ence from which the PVR delivers flow from minimum to maximum setpoints. This range is not normally changed unless a special control scheme is used where control operation must be changed.
To field adjust a different reset span, follow these steps:
1. Connect an accurate gage to port “G”.
2. Apply 20 psi to port “T”.
3. Adjust reset span to indicate the desired span on port “G”.
4. LO-stat and HI-stat delta P must now be readjusted (see following calibration procedure).
VAV-SVX02B-EN10
Page 11
Calibration Procedures
Calibration Procedure (Steps 1–4 apply to all thermostat models)
1. Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports.
2. Remove the caps on the tees, which are connected to the lines to the flow sensor. Connect a 0–2" magnehelic gage to monitor flow sensor delta P. The higher-pressure port is further upstream on the air valve inlet.
3. Remove the thermostat line and connect a hand pump with a 0–20 psi gage to port “T“.
4. Tee a 0–20 psi gage in the line from port “B” on the volume regulator to the air valve actuator.
Normally-Open Valve
Direct-Acting Thermostat
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat (minimum) adjustment to desired minimum.
7. Set port “T” input at 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (maximum) adjustment to desired maximum flow. If the actuator pressure is less than 3 psi, the air valve is wide open and duct pressure must increase to increase flow.
9. Set port “T” at 0 psi.
10. Monitor the minimum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Reverse-Acting Thermostat
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat delta P (maximum) adjustment to desired maximum. If the actuator pressure is less than 3 psi, the air valve is wide open and duct pressure must increase to increase flow.
7. Set prot “T” to 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (minimum) adjustment to desired minimum flow.
9. Set port “T” at 0 psi.
10. Monitor the maximum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Direct-Acting Thermostat
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat (minimum) adjustment to desired minimum.
7. Set port “T” input at 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (maximum) adjustment to desired maximum flow. If the actuator pressure is greater than 13 psi, the air valve is wide open and duct pressure must increase to increase flow.
9. Set port “T” at 0 psi.
10. Monitor the minimum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
Normally-Closed
Reverse-Acting Thermostat
5. Set port “T” at 0 psi.
6. Monitor the delta P and adjust the LO-stat delta P (maximum) adjustment to desired maximum. If the actuator pressure is greater than 13 psi, the air valve is wide open and duct pressure must increase to increase flow.
7. Set prot “T” to 16 psi or greater with the hand pump.
8. Monitor the delta P and adjust the HI-stat (minimum) adjustment to desired minimum flow.
9. Set port “T” at 0 psi.
10.Monitor the maximum flow delta P. If it is not correct, adjust the LO-stat adjustment knob.
VAV-SVX02B-EN 11
Page 12
Specifications (3501)
Specifications (3501)
Differential Pressure Range:
0 to 1.0 in. wg
Minimum Setpoint Range:
0 to 1.0" H2O
Maximum Setpoint Range:
minimum to 1.0 in. wg
Maximum Setpoint Range:
6.0 in. wg
Normal Supply Air Pressure:
20.0 psi
Minimum Supply air Pressure:
15.0 psi
Maximum Supply Air Pressure:
30.0 psi
Output Sensitivity:
5 psi/.02
Average Supply Air Consumption:
43.2 scim at 20 psi
Reset Start Point Range:
0–10 psi
Reset Span Range:
0–7 psi
Operating Temperature:
+40/+120°F
Storage Temperature:
-40/+140°F
VAV-SVX02B-EN12
Page 13
MCP-3631—Rotary Pneumatic Damper Actuator
MCP-3631—Rotary Pneumatic Damper Actuator
Description:
Rotary actuators mounts to a standard ½" diameter shaft by a locking collar and bushing.
Models:
MCP-3631-5000 8–13 psi range (55–90 kPa) Normally-Closed operation
MCP-3631-8000 3–8 psi range (21–55 kPa) Normally-Open operation
Installation Method:
Slide collar onto shaft. Slide actuator onto shaft noting directional rotation. Slide bushing onto shaft into actuator, aligns actuator with damper, lock collar and bushing set screws, and install bracket.
Maintenance:
No routine maintenance is required.
Specif ications:
Effective Area:
8 sq in. (52 sq cm)
Normal Rotation:
100 deg
Supply Pressure:
0 to 20 psig (138 kPa) operating 30 psig (207 kPa) max
Spring Ranges:
Retracted/extended Torque (Based on 0 & 20 psi applied)
8–13 psi (55–90 kPa); 68/59 in. lbs (8/7 Nm) @ 90 deg
3– 8 psi (21–55 kPa); 25/102 in. lbs (3/12 Nm) @ 90 deg
Supply Connection:
3/16" (5 mm) nipple for ¼" (6 mm) OD polyethylene tubing
Material:
Body Glass-filled nylon Diaphragm Neoprene
Weight:
1.5 lbs (0.68 kg)
Ambient Limits:
Operating -20°F –120°F (-29°C–49°C) Shipping -40°F –140°F (-40°C –60°C)
VAV-SVX02B-EN 13
Page 14
Constant-Volume Dual-Duct
Val
Calibration (3011)
Constant Volume Dual-Duct Calibration (3011)
This calibration procedure is used when a constant volume of air must be maintained through a unit. On a dual­duct unit, a constant-volume discharge sensor is used to measure the air leaving the unit. The PVR controlling to a constant-volume of air leaving the unit uses the discharge sensor to maintain the specified cfm.
Figure 15 –Typical Constant-Volume Dual-Duct Piping Diagram
Outlet
vegV l
Normally-
Open
LO
HI
LO
HI
Cooling
Valve
Normally-
Open
This PVR does not require a thermostat connected to the PVR.
The following procedure must be used when calibrating a constant-volume dual-duct unit. See Figure 15 for a typical piping diagram.
1. Set t-stat to full heat.
2. Set LO thermostat (maximum) to the desired maximum flow on the heating deck.
Constant-Volume
Flow Ring
3. Set t-stat to full cool.
4. Set HI thermostat (minimum) to the desired minimum flow on the heating deck.
5. Set LO thermostat adjustment knob on cooling deck (CV deck) to desired constant-volume.
6. Exercise the system to check flows for proper operation.
Actuator
S
20
(137.9)
H
L
B
Volume
Regulator
T
Actuator
S
20
(137.9)
Two-Pipe
Remote-Mounted
T-Stat
(Direct-Acting)
VAV-SVX02B-EN14
Volume
Regulator
T
Restrictor
Tee
S
20
(137.9)
H
L
B
Page 15
Variable Air Volume Dual-Duct
Heating
Val
Normally-
O
Normally-
O
Cooling
Val
Calibration (3011)
Var iable-Air-Volume Dual­Duct Calibration (3011)
Figure 16 is a typical piping diagram of a VAV dual-duct unit. The unit has a thermostat piped to both pneumatic volume regulators (PVR) which will operate the heating deck from a thermostat signal of 3–8 psi. The cooling deck will operate from a thermostat signal of 8–13 psi. With normal calibration of the PVR, the unit will have both the heating and cooling deck at minimum with a thermostat signal of 8 psi.
In order to have a unit minimum cfm and still have 0 cfm minimums on both the heating and cooling deck, special calibration is required. The PVR has a “reset start” adjustment knob, which allows the unit to be calibrated to a minimum cfm. This is achieved by crossing over the thermostat ranges. Figure 17 illustrates this concept.
Figure 17– Example
N.O. Heating Valve
Min 0 cfm
Max 1000 cfm
Max
Unit Min
Valve Min
47912
Figure 16–Typical VAV Dual-Duct Piping Diagram
Outlet
LO
HI
Actuator
vegV l
penO
(137.9)
vegV l
penO
LO
HI
G
Volume
Regulator
T
Restrictor
Tee
H
L
B
20
Thermostat Range: 3– 8 psi Heating Valve = 5 psi range
Thermostat Range: 8–13 psi
Unit Minimum 400 cfm
Cooling Valve = 5 psi range Approximately 1000 cfm divided by 5 psi =
200 cfm/1b*
N.O. Cooling Valve
Min 0 cfm
Max 1000 cfm
*Due to the relationship between velocity pressure and cfm; for both the cooling and heating PVR, a linear relationship between cfm and psi does not exist.
To obtain a unit minimum cfm of 400 cfm, the heating deck volume regulator must have its thermostat range changed from 3–8 psi to 4–9 psi. This is adjusted by changing the “reset start” point from 3 psi to approximately 4 psi.
The cooling deck volume regulator must have its
8
thermostat range changed from 8–13 psi to 7–12 psi. This is adjusted by changing the “reset start” point from 8 psi to approximately 7 psi.
By overlapping the thermostat spring ranges, we were able to have 0 cfm minimum settings on both the heat and cool deck and still maintain the required unit minimum cfm of 400 cfm.
The calibration of the PVR is the same as the normal calibration procedures previously described in this manual.
S
20
(137.9)
Actuator
S
20
(137.9)
Two-Pipe
Remote-Mounted
T-Stat
(Direct-Acting)
Volume
Regulator
T
H
L
B
VAV-SVX02B-EN 15
Page 16
Constant-Volume Single-Duct VAV (VCV 3011)
Constant-Volume Single­Duct VAV ( VCV 3011)
This is used when a constant volume of air is required to supply a zone. A thermostat is still often required to modulate a reheat coil to maintain temperature control. The thermostat is
1. Be sure there is 0 psi at the “T” port.
2. Set LO thermostat adjustment knob to desired unit cfm.
The unit will now modulate to the calibrated cfm setting. See Figure 18 for typical constant volume single-duct piping diagram.
never connected to the “T” port on the volume regulator. The following procedure is used to calibrate this type of unit with a PVR.
Figure 18 –Typical Constant-Volume Single-Duct Piping Diagram
HI
B
M
S
20
(137.9)
H L
Volume
Regulator
Flow Ring
LO
Actuator
T
S
20
(137.9)
Tee
Trane An American Standard Company www.trane.com
For more information contact your local district office or e-mail us at comfort@trane.com
Two-Pipe
Remote-Mounted
T-Stat
(Reverse-Acting)
Literature Order Number VAV- SVX02B- EN
File Number SV-TD-VAV000- SVX02B-EN- 0302
Super sedes VAV-SVX02A-EN & VAV-IOM-6
Stoc king Location La Crosse
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform installation and servicing of equipment referred to in this publication.
11
(75.8)
Stage 1
12.5
(86.2)
Stage 2
14
(96.5)
Stage 3
Electric Heater Terminal Box
Airflow
Safety Switch
P.E. Stage Switch(es)
(Normally-Open)
Loading...