Service Model Number Description .................. 4 – 14
General Information ............................................... 15
Literature Contents
Receiving and Handling
Warnings and Cautions Explanations
Unit Information ............................................. 16 – 17
Single-Duct Units
Dual-Duct Units
Fan-Powered and Low-Height Units
Unit Installation .............................................. 18 – 31
Hanging Bracket Locations
Unit Weights
Water Coil Connections
Unit Accessibility
Clearances
Actuator Mounting
Unit Setup ...................................................... 32 – 46
Flow Sensor ∆P vs. Airflow Delivery
Maximum Fan Motor Amperage
(SCR) Motor Speed Control Adjustment Procedure
Electrically Commutated Motor (ECM)
ECM CFM Tables
WARNING: ALL INSULATED UNITS
(except closed-cell foam insulation)
CONTAIN FIBERGLASS WOOL! Read
this literature prior to installation for
proper instruction. Disturbing the
insulation in this product during
installation, maintenance or repair will
expose you to airborne particles of
glass wool fibers and ceramic fibers
known to the state of California to
cause cancer through inhalation. Glass
wool fibers may also cause respiratory,
skin or eye irritation.
Digit 19—Outlet Plenum (Connection is
Slip & Drive)
0None
A1 Outlet RH
B1 Outlet END
C1 Outlet LH
D2 Outlets, 1 RH, 1 END
E2 Outlets, 1 LH, 1 END
F2 Outlets, 1 RH, 1 LH
H3 Outlets, 1 LH, 1 RH, 1 END
J4 Outlets, 1 LH, 1 RH, 2 END
Note
:
See unit drawings for outlet sizes/
damper information.
Digit 20—Not Used
0N/A
Digit 21—Water Coil
0None
11-Row
22-Row
Digit 22—Electrical Connections (VCCF,
VCWF can be flipped in the field to
achieve opposite-hand connection)
LLeft (Airflow hitting you in the
face)
RRight (Airflow hitting you in the
face)
0Opposite side connection – coil
and control
Service Model
Number Description
Digit 23—Transformer
0None
1120/24 volt (50 VA)
2208/24 volt (50 VA)
3240/24 volt (50 VA)
4277/24 volt (50 VA)
5480/24 volt (50 VA)
6347/24 Volt (50 VA)
7575/24 Volt (50 VA)
8380/24 Volt (50 VA)
Note: For VCEF units with transformers
the VA depends on the staging, control,
and contactor type (ranges are 40 VA
to 75 VA)
Digit 19—Outlet Plenum (Connection is
slip & drive)
0none
A1 outlet–RH
B1 outlet–END
C1 outlet–LH
D2 outlets–1 RH, 1 END
E2 outlets–1 LH, 1 END
F2 outlets–1 RH, 1 LH
G2 outlets - END
H3 outlets–1 LH, 1 RH, 1 END
J4 outlets–1 LH, 1 RH, 2 END
Note: See unit drawings for outlet sizes/
damper information.
Digit 20—Not Used
0N/A
Digit 21—Not Used
0N/A
Digit 22—Not Used
0N/A
Digit 23—Transformer
0None
1120/24 volt (50 VA)
2208/24 volt (50 VA)
3240/24 volt (50 VA)
4277/24 volt (50VA)
5480/24 volt (50 VA)
6347/24 volt (50 VA)
7575/24 volt (50 VA)
Digit 24—Disconnect Switch
0None
WWith Toggle
Digit 25—Power Fuse
0None
WWith
6
VAV-SVN01E-EN
Fan-Powered Parallel Units
Digit 1, 2—Unit Type
VPVariTrane fan-powered parallel
Digit 3—Reheat
CCooling Only
EElectric Heat
WHot Water Heat
Digit 4—Development Sequence
FSixth
Digit 5, 6—Primary Air Valve
055" inlet (350 max cfm)
066" inlet (500 max cfm)
088" inlet (900 max cfm)
1010" inlet (1400 max cfm)
1212" inlet (2000 max cfm)
1414" inlet (3000 max cfm)
1616" inlet (4000 max cfm)
Digit 7, 8—Secondary Air Valve
00N/A
Digit 9—Fan
P02SQ fan (500 nominal cfm)
Q03SQ fan (1100 nominal cfm)
R04SQ fan (1350 nominal cfm)
S05SQ fan (1550 nominal cfm)
T06SQ fan (1850 nominal cfm)
U07SQ fan (2000 nominal cfm)
Digit 10, 11—Design Sequence
J0 Design Sequence (Factory
assigned)
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed DDC
or analog
ENCL ENON with controls enclosure
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – cooling only
DD02 DDC – N.C. on/off water control
DD03 DDC – prop hot water control
DD04 DDC – on/off electric heat
control
DD05 DDC – pulse-width modulation
electric heat control
DD07 DDC – N.O. on/off hot water
control
DD11 LonTalk DDC Controller—
Coolingonly
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Control–on/off
electric heat control
Service Model
Number Description
DD15 LonTalk DDC Controller w/
pulse-width modulation electric heat
control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM customer actuator & control
FM01 FM Trane actuator w/ customersupplied controller
VMA2 FM Johnson Controls
VMA-1420
PWR1 FM Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM Seimens 540-100 w/ Trane
actuator
PWR5 FM Seimens 540-100 w/
GDE131.1U actuator
AT01 FM Automated Logic U341V+
AT02 FM Automated Logic U141V+
EI05Analog – fan-powered parallel
with optional on/off reheat
PN00 PN – N.O. Trane pneumatic
actuator, R.A. stat
PN05 PN – N.O. PVR, R.A. stat
Notes:
N.C. =Normally-closed
N.O =Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
PN =Pneumatic
FM =Factory installation of customer-
0None
124-volt magnetic
224-volt mercury
3PE with magnetic
4PE with mercury
Digit 32—Airflow Switch
0None
WWith
Service Model
Number Description
8
VAV-SVN01E-EN
Fan-Powered Series Units
Digit 1, 2—Unit Type
VSVariTrane fan-powered series
Digit 3—Reheat
CCooling Only
EElectric Heat
WHot Water Heat
Digit 4—Development Sequence
FSixth
Digit 5, 6—Primary Air Valve
044" inlet (225 max cfm)
055" inlet (350 max cfm)
066" inlet (500 max cfm)
088" inlet (900 max cfm)
1010" inlet (1400 max cfm)
1212" inlet (2000 max cfm)
1414" inlet (3000 max cfm)
1616" inlet (4000 max cfm)
Digit 7, 8—Secondary Air Valve
00N/A
Digit 9—Fan
P02SQ fan (700 nominal cfm)
Q03SQ fan (1200 nominal cfm)
R04SQ fan (1550 nominal cfm)
S05SQ fan (1900 nominal cfm)
T06SQ fan (2600 nominal cfm)
U07SQ fan (3000 nominal cfm)
Fan Note: See fan curves for specific
airflows
Digit 10, 11—Design Sequence
J0 Design Sequence
(Factory assigned)
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed DDC
or analog
ENCL ENON with control enclosure
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – cooling only
DD02 DDC – N.C. on/off water control
DD03 DDC – prop hot water control
DD04 DDC – on/off electric heat
control
DD05 DDC – pulse-width modulation
electric heat control
DD07 DDC N.O. on/off hot water
control
DD11 LonTalk DDC Controller—
Cooling only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
Service Model
Number Description
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Controller–on/off
electric heat control
DD15 LonTalk DDC Controller w/
pulse-width modulation electric
heat control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM customer actuator & control
FM01 FM Trane actuator w/ customer-
supplied controller
VMA2 FM Johnson controls VMA-1420
PWR1 FM Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM Seimens 540-100 w/ Trane
actuator
PWR5 FM Seimens 540-100 w/
GDE131.1U actuator
AT01 FM Automated Logic U341V+
AT02 FM Automated Logic U141V+
EI71Analog fan-powered series
with optional on/off reheat
PN00 PN – N.O. Trane pneumatic
actuator, R.A. stat
PN51 PN – N.O. PVR, duct pressure
switch, R.A. stat
PN52 PN – N.O. PVR, dual pressure
main, R.A. stat
Notes:
N.C. =Normally-closed
N.O. =Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic t-stat
(by others)
PN =Pneumatic
FM =Factory installation of customer-
0None
124-Volt magnetic
224-Volt mercury
3PE with magnetic
4PE with mercury
Digit 32—Air Flow Switch
0None
WWith
14
VAV-SVN01E-EN
General
WARNING
CAUTION
CAUTION
Information
Literature Contents
This manual describes the installation
of VariTrane VAV units with recommended wiring, piping, and mounting
of Single-Duct, Dual-Duct, Fan-Powered, Low-Height terminal units and
diffusers.
Receiving and Handling
VariTrane Units are shipped completely
assembled with the exceptions of
optional attenuators for fan-powered
units and accessories.
Upon receiving the equipment,
complete the following:
y Locate the nameplate and refer to the
model and sales order number and
check that the correct units have been
delivered.
y Inspect the control enclosures and air
valve casing for dents or punctures.
y Verify that all options have been
included, such as filters, controls,
heating coils, water valves, etc. Also
check that the unit voltages agree with
the building parameters.
y Manually rotate the fan (if applicable) to
assure that there are no obstructions
within the housing.
y Claims for in-transit damage must be
filed immediately with the delivery
carrier.
y For hot water re-heat units, check the
coil fins and make sure that coils are
not damaged.
y Locate and verify that the correct zone
sensors are with the order. These will be
marked with an orange “Accessories
Enclosed” label. Store in a secure
location until needed. Accessories lost
at the jobsite are NOT covered by
Trane’s warranty.
y If a discrepancy occurs between what
was ordered and what is received,
contact you local Trane representative
immediately.
y Read the appropriate section in this
manual for installation procedures prior
to actual starting of equipment.
Upon receiving the equipment, please
inspect each unit and components for
external or internal damage. Refer to
the bill of lading to insure all equipment
and accessories have been received.
Contact your local Trane sales
representative and notify the trucking
company immediately of any short ship
or damaged equipment.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
WARNING
– Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
CAUTION
– Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury. It may also be used
to alert against unsafe practices.
CAUTION
– Indicates a situation that may result in equipment or
property-damage-only accidents.
VAV-SVN01E-EN 15
Unit
Information
Single-Duct Units
The basic unit consists of a sheet metal
casing with an air valve, which is used
to modulate the air being delivered into
the occupied zone. The unit is designed
to modulate either cooling or heating
air between the temperatures of 40°F
and 140°F. Air enters the air valve
through the round or rectangular inlet
and exits into the sheet metal casing to
be distributed to the zone either
through integral round outlets in the
casing or through rectangular duct
attached to the discharge of the unit.
The basic unit can also be ordered with
factory-mounted electric or hot water
heating coils attached to the discharge.
(See Figure 1.)
These re-heat units are used primarily
to reheat air-to-zone temperature when
the load in the occupied space is low.
Primary air is modulated through the
VariTrane air valve by rotating the
damper blade. All air valves have a
round/rectangular inlet for easy fit-up
with incoming ductwork.
Figure 1 – Typical Single-Duct Units
VCCF
VCWF
VCEF
Dual-Duct Units
Dual-duct units provide two air valves:
one as heating primary air and the
other as cooling primary air. Both
discharge into the common outlet,
which leads to the zone being controlled. (See Figure 2.)
The units are provided with a slip and
drive rectangular duct connection or
can be ordered with integral outlet
plenum.
Sequencing of the hot and cold air
valve is dependent upon job
requirements. One typical control is the
valves working in conjunction with each
other to respond to zone temperature.
When the cooling valve becomes fully
closed or reaches a specified minimum,
then the heating valve will begin to
modulate or vice versa. The typical
result is that air flowing to the zone
varies from the maximum down to a
minimum and back up to a maximum
as the load varies and as the controls
would cause one air valve to close and
the other to open.
Another typical application is when the
unit provides a constant volume to the
zone. When the zone sensor is tied
directly to the heating valve, it will
modulate the heating valve according
to the zone temperature.
When the heating valve is fully closed
or there is a call for cooling in the zone,
the cooling valve will be at constant
supply. As the space becomes too cool,
the heating valve will modulate open,
decreasing the cooling valve flow. The
typical result is that the air flowing into
the zone stays at a constant flow
whether the unit is heating or cooling.
Figure 2 – Typical Dual-Duct Unit
VDDF
16
VAV-SVN01E-EN
Unit
Information
Fan-Powered and Fan-Powered
Low-Height Units
VariTrane fan-powered and low-height
fan-powered units can be either parallel
or series, with or without re-heat. (See
Figure 3.)
The fan on a series unit runs
continuously whenever the main air
handler unit is in operation. There are
various options for starting the fan. The
fan can be started three ways: 1)
remotely, 2) by a duct pressure switch,
or 3) by a combination of both. The
particular fan control method may vary
from unit to unit, depending upon job
needs.
Typically, the heater is off while the air
valve modulates primary air and
responds to zone temperature. If zone
temperature decreases to the point
where a decrease in primary air will not
maintain the desired temperature, the
re-heat will be activated to increase the
temperature of the discharge air.
On a parallel unit, the VariTrane air valve
delivers primary cooling air to the unit
outlet. When the space temperature
decreases beyond air valve control, the
fan is turned on as the first stage of
heat. The fan delivers plenum air from
above the occupied space to the unit
outlet, which is mixed with primary air
and delivered to the occupied space.
VariTrane fan-powered unit fan sizes
02SQ–05SQ and 08SQ–10SQ were
performance tested at .12 in. w.g. and
sizes 06SQ and 07SQ were tested at .15
in. w.g. Units are not designed to
operate unducted and below these
tested static pressures.
Note: Fan-powered units are available
with rectangular discharge connection
only. The optional heater is mounted on
the discharge of the unit. Hot water coils
are connected to either the plenum inlet
or on the discharge on parallel units, and
to the discharge of series units.
Figure 3 – Typical Fan-Powered Units
VSCF
VPCF
Note: Either the fan, the air valve, or both
can deliver airflow into the occupied
space. In order to prevent primary airflow
from exiting through the fan when the
fan is not running on a parallel unit, a
back draft damper is provided. When the
fan is not running, the efficiency of this
system is the same as a standard singleduct VAV unit.
Typically, the control systems applied to
parallel units cause the air valve to
close to zero or a minimum flow before
the fan is activated. After the fan is
activated, the optional heat will be
activated upon further reduction in
zone temperature. Therefore, minimal
primary air is mixed with the heated air.
VAV-SVN01E-EN 17
VSEF
VSWF
VPEF
VPWF
Unit
Installation
Due to their weight, the VAV terminal
units should be suspended from the
uppermost ceiling, independent of the
false ceiling grid. Suspension devices
are to be supplied by the installer. Units
must be installed level and upright.
Failure to level the unit properly may
prevent proper operation of the
controls and/or terminal unit. Units are
not designed to be installed vertically.
Consequently, this will also void the UL
ratings and any warranty on the unit.
Single-Duct
Depending upon the size and weight of
the single-duct unit, it may be capable
of being supported by the ductwork
that is connected to it. No hanger
brackets are provided on these units
since the unit should be supported by
means of a hanger strap. The hanger
strap should be secured directly to the
unit casing as shown in Figure 4.
For cooling only single-duct units or
single-duct units with hot water coil, the
unt may be rotated 180° for opposite
side connections.
For units with electric heat, the unit
must be ordered from the factory
designating either right- or left-hand
connections.
Dual-Duct
Dual-duct units should be supported by
either hanger straps or by using a
threaded rod in conjunction with the
hanger brackets that are provided on
the unit. See Figure 5.
Figure 5
Dual-Duct Hanger Bracket Locations
AIR
VALV E
COOLING
AIR
VALV E
HEATING
CA
B
Figure 4
Single-Duct Hanging
Recommendations
18
Inlet Size
5" thru 10"
12" thru 16"
TOP VIEW
BCA
25.25" (641 mm)23.154" (588 mm)
25.154" (639 mm)1.376" (35 mm)
37.25" (946 mm)
1.376" (35 mm)
VAV-SVN01E-EN
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.