Trane VAV-IN-24, VAV User Manual

Installation
Unit Control Module (UCM) 4.2 Retrofit Model VAV
Models
“A” and later Design Sequence
VAV
July 2005
VAV-IN-24
Notice
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING – Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION – Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury. It may also be used to alert
against unsafe practices.
CAUTION – Indicates a situation that may result in
equipment or property-damage-only accidents.
General
The purpose of this installation manual is to provide application, functional and calibration information for the Trane Retrofit package. Examples and charts are provided to enhance the understanding of this information.
Introduction
The DDC/VAV retrofit kit consists of the UCM control assembly, a Honeywell™ or Belimo™ actuator (both optional), and various accessories such as zone sensors, transformers, flow sensors, etc. This manual is intended to show how to apply, install and configure the DDC/VAV Retrofit kit. It is intended to provide information specific to the VAV retrofit. Refer to VAV-SVX01C-EN for complete DDC/VAV system wiring, installation and programming instructions.
Applications
The retrofit kit may be applied to pneumatic terminals by replacing the pneumatic actuator with an electric actuator or electrically controlled terminals by either using the existing electric actuator or by replacing it with one provided by Trane.
The kit may be used on existing shutoff, shutoff hot water reheat, shutoff with up to three stages of electric heat, and fan powered (both parallel and series) cooling only, hot water, and electric reheat units.
Note: Fan powered units have only two stages of reheat available.
Dual duct units may also be retrofitted using two sets of controllers. The kit has also been applied to constant volume reheat systems where the retrofit kit is used to control duct coils.
The kit has been tested on VAV terminals of several major manufacturers. It is mandatory for unit to have an external shaft to function properly with the direct coupled actuators offered.
Contents
Installation/Startup/Commissioning
Notice/Introduction
Application
Hardware 4
Installation 5
Commissioning 6
2
2
2
VAV-IN-24 3

Hardware

UCM 4.2 Retrofit Kit
The UCM 4.2 retrofit kit is available in three basic kits.
• Retrofit Kit with a Honeywell actuator
• Retrofit Kit with a Belimo actuator
• Retrofit Kit with no actuator
The kit may also be ordered in a pres­sure dependent version on a special basis. Both the Belimo and Honeywell actuators are direct coupled actuators.
Honeywell Actuator
Key benefits and features of the Hon­eywell actuator are:
• Selectable 45°, 60°, and 90° angles of rotation
• 35-inch-pound torque capacity
• 3/8-inch to 1/2-inch shaft size capa­bility
• 90-second drive time over 90° rota­tion
• Magnetic coupled motor provides 45-inch-pounds stall
• 2 VA at 24-volts power consumption
• Manual clutch to disengage the ac­tuator from the motor
Control Assembly
The actual control assembly consists of UCM and Delta P transducer mount­ed in a sheet metal enclosure. The ac­cessories offered with the kit are zone sensors with the same options as Trane DDC/VAV: flow bars for use with units without a flow sensor and con­trol power transformers.
Belimo Actuator
The Belimo actuator’s principle benefit is flexibility. Belimo is designed with the following features:
• Direct coupled with universal clamp fitting shaft sizes, 3/8-inch to 1/2­inch shaft size.
• Manual clutch to disengage the ac­tuator from the motor
• Motor reversing switch to change rotation
• Adjustable mechanical stops
• 35-inch-pounds torque capacity
• 3 VA at 24-volts power consumption
• 95-second run time

Installation

WARNING
Hazardous Service Procedures!
The maintenance and Trouble Shooting procedures recommend­ed in this section of the manual could result in exposure to electri­cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern­ing these procedures. When possi­ble, disconnect all electrical power including remote discon­nects and discharge all motor start/run capacitors before servic­ing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently ener­gized. When necessary to work with live electrical components, have a qualified licensed electri­cian or other individual who has been trained in handling live elec­trical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects and discharge all motor start/run ca­pacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in­advertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
Pre-Installation
The existing unit controls will require removal prior to installing the UCM 4.2 retrofit kit. This includes pneumatic ac­tuators, volume regulators and any miscellaneous auxiliary controls.
CAUTION
Local and N.A.C. electrical codes should be observed when install­ing the UCM 4.2 retrofit kit.
Control Box Mounting
The next phase is to begin the installa­tion of the kit. The controller should be mounted at any convenient location on the existing unit. Keep in mind the controller must be mounted in a verti­cal plane to the flow transducer will function properly. In a typical installa­tion, the controller is mounted on one side of the unit, and the actuator on the other side due to space limitations. However, Trane’s controller may be mounted on the ductwork adjacent to the terminal unit. The only require­ment is the flow sensor tubing cannot exceed 10-feet.
Actuator Installation
When installing the actuator, the con­vention of the damper rotation is as­sumed as:
• Clockwise rotation of the damper shaft will close the damper.
• Counterclockwise rotation of the damper shaft will open the damper
All of the wiring diagrams assume this convention, Figure 1.
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects and discharge all motor start/run ca­pacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in­advertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
Actuator Installation
To install the actuator, slip the actuator over the shaft of the damper and use a sheet metal screw to secure the actua­tor to the base of the terminal unit. Ro­tate both the actuator and damper shaft fully clockwise and ensure that the damper is fully closed. When the damper is fully closed, tighten the set screws of the actuator onto the damp­er shaft.
When following the clockwise-closed convention, wiring terminations for the actuator are shown in Table 1.
Table 1:
UCM 4.2 Actuator Color Code Function
TB4-1 COM White Hot
TB4-2 CCW Black Open
TB4-3 CW Red Closed
The actuator is now configured for clockwise operation (with the actuator closing the damper). If the damper is a 90° rotating damper, the actuator will close the damper.
Note: If the damper angle of rotation is counterclockwise to close, follow the above procedure except reverse the open and closed wires at the actuator terminal block.
The communications power and zone sensor wiring should be pulled to the unit. The wiring procedures and guidelines used are outlined in the VAV-SVX01C-EN manual.
VAV-IN-24 5

Commissioning

Commissioning
For commissioning and configuration, contact the local Trane service techni­cian, or refer to VAV-SVX01C-EN.
Figure 1: UCM 4.2 Wiring Diagram
Commissioning
Figure 2: Sensor signal vs. airflow delivery
5
1
0.1
Flow Sensor DP (In. wg)
0.01 10 100 1,000 10,000
4"
Cfm
5"
12"10"8"6"
14" 16"
Note: Refer to manufacturer of competitive terminal for Delta P vs. airflow delivery.
VAV-IN-24 7
Trane A Business of American Standard Companies www.trane.com
Literature Order Number VAV-IN-24
File Number SV-TD-000-VAV-IN-24-0705
Supersedes SV-TD-0 00-VAV-IN-24-0693
Stocking Location Inland
For more information, contact your local district office or e-mail us at comfort@trane.com
Trane has a policy of continuous product and data improvement and reserves the right to change design and specifications without notice.
Loading...