Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
March 2015
SS-SVX10E-EN
Page 2
Introduction
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs). Not all refrigerants
containing these compounds have the same potential
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs such as HCFCs and
HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the
air conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
•Microchannel is now standard on 5–10 ton single
and dual compressor units. All data has been
updated to reflect this change.
•With the change to Microchannel, the Odyssey split
system now offers a new 60Hz, 7.5 ton dual
compressor model that can be matched with a new
60Hz, 7.5 ton Single Zone VAV and 2–Speed air
handler. A new 50Hz, 6.25 ton dual compressor
model is now also available and can be matched
with a new 50Hz, 6.25 ton standard air handler.
E = Dual Compressor, Dual Circuit, Tube and Fin
F = Dual Compressor, Single Circuit (Manifold Scroll
Compressors), Tube and Fin
G = Single Compressor, Single Circuit, Microchannel
This manual describes proper installation, operation,
and maintenance procedures for air-cooled systems. By
carefully reviewing the information within this manual
and following the instructions, the risk of improper
operation and/or component damage will be
minimized. It is important that periodic maintenance be
performed to help assure trouble free operation.
Should equipment failure occur, contact a qualified
service organization with qualified, experienced HVAC
technicians to properly diagnose and repair this
equipment.
IImmppoorrttaanntt:: All phases of this installation must comply
with the NATIONAL, STATE & LOCAL
CODES. In addition to local codes, the
installation must conform with National
Electric Code -ANSI/NFPA NO. 70 LATEST
REVISION.
Any individual installing, maintaining, or servicing this
equipment must be properly trained, licensed and
qualified.
IImmppoorrttaanntt:: Do not remove the VFD without first
contacting technical support! For
performance-related questions and
diagnostic support in North America call 1877-872-6363. Any return requires a claim
number FIRST. Removal of the VFD prior to
this step will void the unit’s warranties.
Installation procedures should be performed in the
sequence that they appear in this manual. Do not
destroy or remove the manual from the unit. The
manual should remain weather-protected with the unit
until all installation procedures are complete.
NNoottee:: It is not the intention of this manual to cover all
possible variations in systems that may occur or
to provide comprehensive information
concerning every possible contingency that may
be encountered during an installation. If
additional information is required or if specific
problems arise that are not fully discussed in this
manual, contact your local sales office.
Use the “Installation Checklist,” p. 43 provided In this
manual to verify that all necessary installation
procedures have been completed. Do not use the
checklist as a substitute for reading the information
contained in the manual. Read the entire manual
before beginning installation procedures.
Unit Description
These condensers come with single, dual and
manifolded compressor options. Single compressor
outdoor units feature a single refrigeration circuitry,
requiring only one set of refrigerant lines. Dual
compressor/dual circuit models give true stand-by
protection; if one compressor fails, the second will
automatically start-up. Also, the first compressor can
be serviced without shutting down the unit since the
refrigerant circuits are independent. During light load
conditions, only one compressor will operate to save
energy.The dual manifolded scroll compressors come
with two stages of capacity modulation and a single
refrigeration circuit.
SS-SVX10E-EN
7
Page 8
Pre-Installation
Unit Inspection
Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made
against the transportation company. Compare the
information that appears on the unit nameplate with
ordering and submittal data to ensure the proper unit
was shipped. Available power supply must be
compatible with electrical characteristics specified on
component nameplates. Replace damaged parts with
authorized parts only.
Inspection Checklist
To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of
the unit.
Inspect individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
Inspect the unit for concealed damage before it is
stored and as soon as possible after delivery.
Concealed damage must be reported within 15
days. If concealed damage is discovered, stop
unpacking the shipment. Do not remove damaged
material from the receiving location. Take photos of
the damage if possible. The owner must provide
reasonable evidence that the damage did not occur
after delivery.
Notify the carrier’s terminal of damage immediately
by phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.
Notify the sales representative and arrange for
repair. Do not repair the unit until the damage is
inspected by the carrier’s representative.
Testing for Leaks
All units are shipped with a holding charge of nitrogen
in each circuit and should be leak tested before
installation.
1. Remove the access panel.
2. Locate the liquid line or suction line access valve for
each circuit.
3. Install gauges to determine if the circuits are still
pressurized. If not, the charge has escaped and
should be repaired as required to obtain a leak-free
circuit.
Before preparing the unit for lifting, estimate the
approximate center of gravity for lifting safety. Because
of placement of internal components, the unit weight
may be unevenly distributed. See “Weights,” p. 20 for
approximate unit weights.
The crated unit can be moved using a forklift of suitable
capacity. For lifting the unit, attach lifting straps or
slings securely to the lifting holes at each corner (see
unit drawings in “Weights,” p. 20). Use spreader bars
to protect the unit casing from damage. Test lift the unit
to determine proper balance and stability.
Clearances
Provide enough space around the unit to allow
unrestricted access to all service points. Refer to the
“Dimensional Data,” p. 10 for unit dimensions and
minimum required service and free air clearances.
Observe the following points to ensure proper unit
operation.
1. Do not install the unit under a low overhang.
Condenser discharge must not be restricted—refer
to notes in “Dimensional Data drawings,” p. 10.
IImmppoorrttaanntt:: Do not obstruct condenser discharge
air. This can result in warm air
recirculation through the coil.
2. Do not locate the unit in a position where runoff
water can fall into the fan discharge openings.
3. Condenser intake air is supplied from three or four
sides of the unit. Adhere to the minimum required
clearances given in unit dimensional drawings (see
IImmppoorrttaanntt:: Refer to local building codes for proper
installation. All installation must comply
with local building codes.
Rooftop Mounting
If the unit will be roof mounted, determine for certain
that the structure is strong enough to support the unit
and any required accessories, see “Weights,” p. 20. The
unit should be elevated on a level, field fabricated fourinch steel or wood 4" x 4" mounting frame. Complete
the frame and secure it into position before lifting the
unit to the roof. The mounting frame must support a
minimum of three of the unit’s four sides and should
span roof supports to distribute the load on the roof.
Figure 1. Roof mounted unit
Ground Level Mounting
For ground level installation, the unit base should be
adequately supported and hold the unit near level. The
installation must meet the guidelines set forth in local
codes. The support should extend two inches beyond
the unit base channels at all points. The unit and
support must be isolated from any adjacent structure to
prevent possible noise or vibration problems. Any
ground level location must comply with required
clearances given in the unit dimensional drawings (see
Each TTA unit ships with a holding charge of dry
nitrogen. The nitrogen should be removed and the
entire system evacuated (at the proper time) to avoid
possible contamination.
1. Remove the compressor service access panel.
2. Locate the liquid and suction line service valves.
Check that the piping connection stubs on the
valves (Figure 16, p. 23) line up properly with the
holes in the unit cabinet.
Figure 16. Outdoor units - refrigerant piping (with dry
nitrogen)
5. Shut off nitrogen supply. Shut off the manifold
valve for the line that is connected to the suction
line service valve. Disconnect the line from the
gauge port on the valve.
SS-SVX10E-EN
23
Page 24
IInnssttaallllaattiioonn
Refrigerant Piping Procedures
(Indoor Unit)
Once liquid and suction lines are complete to the
refrigerant connections on the indoor unit, remove the
gauge port core(s) on the indoor unit connection stubs
to release the dry nitrogen charge.
2. Turn on nitrogen supply. Nitrogen enters through
the liquid line gauge port.
3. Braze the liquid line connections.
4. Open the gauge port on the suction line and then
braze the suction line to the connection stub.
Nitrogen will bleed out the open gauge port on the
suction line.
After the brazing operation of refrigerant lines to both
the outdoor and indoor unit is completed, the field
brazed connections must be checked for leaks.
Pressurize the system through the service valve with
dry nitrogen to 200 psi. Use soap bubbles or other leakchecking methods to ensure that all field joints are leak
free. If not, release pressure, repair and repeat leak test.
System Evacuation
1. After completion of leak check, evacuate the
system.
2. Attach appropriate hoses from manifold gauge to
gas and liquid line pressure taps.
NNoottee:: Unnecessary switching of hoses can be
avoided and complete evacuation of all lines
leading to sealed system can be
accomplished with manifold center hose and
connecting branch hose to a cylinder of R410A and vacuum pump.
3. Attach center hose of manifold gauges to vacuum
pump.
4. Evacuate the system to hold a 500 micron vacuum.
5. Close off valve to vacuum pump and observe the
micron gauge. If gauge pressure rises above 500
microns in one minute, then evacuation is
incomplete or the system has a leak.
6. If vacuum gauge does not rise above 500 microns in
10 minutes, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked off,
open valve on R-410A cylinder and allow refrigerant
pressure to build up to about 80 psig.
8. Close valve on the R-410A supply cylinder. Close
valves on manifold gauge set and remove
SS-SVX10E-EN
Page 25
IInnssttaallllaattiioonn
refrigerant charging hoses from liquid and gas
gauge ports.
9. Leak test the entire system. Using proper
procedures and caution, as described in the
previous section, repair any leaks found and repeat
the leak test.
Insulating and Isolating
Refrigerant Lines
Insulate the entire suction line with refrigerant piping
insulation. Also insulate any portion of the liquid line
exposed to temperature extremes. Insulate and isolate
liquid and suction lines from each other. Isolate
refrigerant lines from the structure and any duct work.
IImmppoorrttaanntt::
1. To prevent possible noise or vibration
problems, be certain to isolate
refrigerant lines from the building.
2. All suction and hot gas bypass piping (if
installed) should be insulated from the
termination in the air handler to the
condensing unit cabinet entry. Failure to
do so can cause condensate drip off and
performance degradation.
3. Prior to starting a unit, it is advisable to
have the approved oils available in the
event oil needs to be added to the
system.
Refrigerant Charging Procedure
If charging by weight, refer to for starting change. If
refrigerant adjustments are needed because of length
of line, refer to “Charging Charts and Superheat,” p. 38.
Charge by weight through the gauge port on the liquid
line. Once the charge enters the system, backseat
(open) the liquid line service valve and disconnect the
charging line and replace the cap on the gauge port.
NNootteess::
•R-410A should only be charged in the liquid
state.
•When possible, always charge the
refrigerant into the liquid line of the unit.
•If the entire charge can’t be charged into the
liquid line, the balance of the unit charge can
be metered through a charging manifold set
as liquid — preferably through a schrader
valve into the suction line to the compressor
— only while the compressor is running.
For units equipped with compressors containing site
glasses, the oil level must be visible through the sight
glass when the compressor is running under stabilized
conditions and a few minutes after the compressor has
stopped.
Approved Oils
Trane Oil Part Number
OIL00094 (1 quart container)
Trane Oil Part Number
OIL00079 (1 quart container)
or OIL00080 (1 gallon
container).
Figure 17. Outdoor units - refrigerant piping
SS-SVX10E-EN
25
Page 26
IInnssttaallllaattiioonn
Charging Levels
Table 4. Estimated charge levels at ARI rated line lengths (25 feet) - 50 & 60 Hz
Refrigerant Charge
Matched Set
TTA061G w/TWE076D
TTA073G w/TWE090D
TTA076G w/TWE076D
TTA076H w/TWE076E
TTA090G w/TWE090D
TTA090H w/TWE090E
TTA101G w/TWE101D
TTA101H w/TWE101E
TTA101F w/TWE101D
TTA120G w/TWE120D
TTA120H w/TWE120E
TTA120F w/TWE120D
TTA126E w/TWE126E
TTA150E w/TWE150E
TTA156E w/TWE156E
TTA156F w/TWE156E
TTA180E w/TWE180E
TTA180F w/TWE180E
TTA201E w/TWE201E
TTA201F w/TWE201E
TTA240E w/TWE240E
TTA240F w/TWE240E
TTA251F w/TWE251E
TTA300F w/TWE300E
Notes:
1. For line lengths other than 25', please refer to the Application Guide (SS-APG008-EN) for charge levels and line sizes.
2. See and for transition tube location and electrical connections.
(a)
TTA061D and TTA073D need a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8” to 1 1/8”)
(b)
TTA251F and TTA300F are provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to 2.125 inch) (1 5/8" to 2 1/
8").
(a)
(b)
Circuit 1Circuit 2
10
10
9.7
7.257.3125
9.7
7.257.3125
13.6
7.77.6
21.2
13.6
7.77.6
21.2
15.215.5
15.215.5
19.519.5
37.6
19.519.5
37.6
21.921.9
41.3
21.921.9
41.3
62.5
62.5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Liquid Line DiameterVapor Line Diameter
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.125 (1 1/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.625 (5/8”)1.625 (1 5/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.625 (5/8”)1.625 (1 5/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.625 (5/8”)1.625 (1 5/8”)
0.5 (1/2”)1.375 (1 3/8”)
0.625 (5/8”)1.625 (1 5/8”)
0.625 (5/8”)2.125 (2 1/8”)
0.625 (5/8”)2.125 (2 1/8”)
Per Circuit
26
SS-SVX10E-EN
Page 27
Figure 18. TTA 251, 300 transition tube location
IInnssttaallllaattiioonn
Figure 19. TTA251, 300 rear refrigerant and electrical connections
Liquid Charging
This procedure is accomplished with the unit
operating. Electrical connections must be complete. Do
not proceed until the system is ready to operate.
NNoottee:: The compressor access panel must be installed
when the unit is running and being charged.
Manifold hoses must be routed through
refrigerant gauge access hole(s). See
1. Turn on power to the unit. Allow the system to run
for 15 minutes to stabilize operating conditions.
2. Measure airflow across the indoor coil. Compare
the measurements with the fan performance data in
the Data/Submittal or Service Facts. Once proper
airflow is established, compare discharge pressure
and liquid temperature to the “Charging Charts,” p.
38. Add or remove refrigerant (liquid only) as
required to obtain correct discharge pressure and
liquid temperature.
3. Check suction line superheat and condenser subcooling to ensure the unit is operating properly.
4. Disconnect all power to the unit.
IImmppoorrttaanntt:: If the unit is charged and left without
power until a later date, the crankcase
heater should be energized for a
minimum of 8 hours prior to powering
the compressor(s).
Field wiring consists of providing power supply to the
unit, installing the system indoor thermostat and
providing low voltage system interconnecting wiring.
Access to electrical connection locations is shown in
“Dimensional Data,” p. 10. Determine proper wire sizes
and unit protective fusing requirements by referring to
the unit nameplate and/or the unit Service Facts. Field
wiring diagrams for accessories are shipped with the
accessory.
Unit Power Supply
The installer must provide line voltage circuit(s) to the
unit main power terminals as shown by the unit wiring
diagrams (available through e-Library or by contacting
a local sales office) or field wiring. Power supply must
include a disconnect switch in a location convenient to
the unit. Ground the unit according to local codes and
provide flexible conduit if codes require and/or if
vibration transmission may cause noise problems.
IImmppoorrttaanntt:: All wiring must comply with applicable
local and national (NEC) codes. Type and
location of disconnect switches must
comply with all applicable codes.
Mount the indoor thermostat, zone sensor, or Night
Setback Panel (NSB) in accordance with the
corresponding thermostat installation instructions.
Install color-coded, weather-proof, multi-wire cable
according to the field wiring schematics (see “Field
Wiring,” p. 30).
Electromechanical Controls
Wiring shown with dashed lines is to be furnished and
installed by the customer. All customer supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
NNoottee:: When electric heater accessory is used, single
point power entry or dual point power entry is
field optional. Single point power entry option is
through electric heater only.
Figure 20. Electromechanical jobsite connections
ReliaTel Controls
Wiring shown with dashed lines is to be furnished and
installed by the customer. All customer supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
NNootteess::
1. When electric heater accessory is used,
single point power entry or dual point power
entry is field optional. Single point power
entry option is through electric heater only.
2. ***Choose only one of the following;
Thermostat, Zone Sensor, or NSB Panel.
Figure 21. ReliaTel jobsite connections
A.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
B.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
C. Cooling only thermostat: 3 to 7 wires depending on stages of
electric heat
D. 3 to 7 wires depending on type of outdoor unit(s)
A.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
B. 3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
C. Cooling only thermostat: 3 to 7 wires depending on stages of
electric heat
D. 3 to 7 wires depending on type of outdoor unit(s)
E. Zone Sensor: 4 to 10 wires depending on zone sensor model
F. Night Setback Panel: 7 wires
(a)
For SZVAV air handlers: 4 additional wires are required (2 of which
require twisted pair or shielded wire) in order to make connections
between ReliaTel boards in the condenser and air handler.
(a)
SS-SVX10E-EN
29
Page 30
IInnssttaallllaattiioonn
Field Wiring
Figure 22. Night setback panel field wiring
Figure 23. Zone sensor field wiring
30
SS-SVX10E-EN
Page 31
Figure 24. Thermostat field wiring
IInnssttaallllaattiioonn
Figure 25. Thermostat wiring for electromechanical units
SS-SVX10E-EN
31
Page 32
IInnssttaallllaattiioonn
Refrigerant Circuit
Figure 26. Typical split system cooling refrigerant circuit — microchannel
32
SS-SVX10E-EN
Page 33
Figure 27. Typical split system cooling refrigerant circuit
IInnssttaallllaattiioonn
SS-SVX10E-EN
33
Page 34
Electrical Data
Table 5. Electrical characteristics — compressor and condenser fan motors — 60 Hz
Tons
12.5
Model
Number
TTA073G31208-230321.91361208-23013.18.1
TTA073G4146039.166.1146011.63.8
6
TTA073GK1380311.483138012.77
TTA073GW157537.455.3157511.23
TTA090G31208-2303251641208-23013.18.1
TTA090G41460312.9100146011.63.8
7.5
TTA090GK1380314.394.3138012.77
TTA090GW1575310.678157511.23
TTA090H32208-230314.683.11208-23013.18.1
TTA090H4246036.841146011.63.8
7.5
TTA090HK238038.551.8138012.77
TTA090HW257534.933157511.23
TTA120G31208-2303362671208-2301514.4
TTA120G41460319142146012.55.8
10
TTA120GK1380327160138013.47.8
TTA120GW15753171031575125.1
TTA120H32208-2303161101208-2301514.4
TTA120H4246037.852146012.55.8
10
TTA120HK2380310.465.6138013.47.8
TTA120HW25753638.91575125.1
TTA120F32208-230317.61231208-2301514.4
10
TTA120F4246039.662146012.55.8
TTA120FW257536.1401575125.1
TTA150E32208-230322.41491208-2301514.4
TTA150E42460310.675146012.55.8
TTA150EK2380311.388138013.47.8
TTA150EW257538.6541575125.1
TTA180E32208-2303251642208-2301514.4
TTA180E42460312.2100246012.55.8
15
TTA180EK2380314.394.3238013.47.8
TTA180EW257539.6782575125.1
TTA180F32208-2303251642208-2301514.4
TTA180F42460312.2100246012.55.8
15
TTA180FK2380314.394.3238013.47.8
TTA180FW257539.9782575125.1
TTA240E32208-230339.12672208-2301514.4
TTA240E42460318.6142246012.55.8
20
TTA240EK2380323.1160238013.47.8
TTA240EW2575315.41032575125.1
TTA240F32208-230339.12672208-2301514.4
TTA240F42460319.8142246012.55.8
20
TTA240FK2380323.1160238013.47.8
TTA240FW2575315.81032575125.1
No.VoltsPhase
Unit
Amps
RLALRAFLALRA
(Ea.) (Ea.)(Ea.) (Ea.)
Compressor Motor
Condenser Fan Motor
No.VoltsPhase
Amps
34
SS-SVX10E-EN
Page 35
Table 5. Electrical characteristics — compressor and condenser fan motors — 60 Hz (continued)
Tons
Note: Electrical characteristics reflect nameplate values and are calculated in accordance with cULus and ARI specifications.
Model
Number
TTA300F32208-230353.62452208-2301514.4
TTA300F42460320.7125246012.55.8
25
TTA300FK2380326.4145238013.47.8
TTA300FW2575316.41002575125.1
No.VoltsPhase
Unit
Amps
RLALRAFLALRA
(Ea.) (Ea.)(Ea.) (Ea.)
Compressor Motor
Condenser Fan Motor
Amps
No.VoltsPhase
Table 6. Unit wiring — condensing units — 60 Hz
EElleeccttrriiccaall DDaattaa
TonsUnit Model Number
TTA073G3187-25330.550
6
7.5
7.5
10
10
10
12.5
15
15
TTA073G4414-5061320
TTA073GK342-4181725
TTA073GW518-63210.515
TTA090G3187-25334.445
TTA090G4414-50617.725
TTA090GK342-41820.625
TTA090GW518-63214.520
TTA090H3187-2533650
TTA090H4414-50616.920
TTA090HK342-41821.830
TTA090HW518-63212.215
TTA120G3187-25342.660
TTA120G4414-50623.430
TTA120GK342-41828.235
TTA120GW518-63217.525
TTA120H3187-2534145
TTA120H4414-50620.125
TTA120HK342-41826.930
TTA120HW518-63215.520
TTA120F3187-25344.650
TTA120F4414-50624.130
TTA120FW518-63215.720
TTA150E3187-25355.470
TTA150E4414-50626.430
TTA150EK342-41828.835
TTA150EW518-63221.425
TTA180E3187-25366.380
TTA180E4414-50632.540
TTA180EK342-4183945
TTA180EW518-63225.630
TTA180F3187-25366.380
TTA180F4414-50632.540
TTA180FK342-4183945
TTA180FW518-63226.330
Unit Operating
Voltage Range
Minimum Circuit Ampacity
Maximum Fuse or HACR
Circuit Breaker Size
SS-SVX10E-EN
35
Page 36
EElleeccttrriiccaall DDaattaa
Table 6. Unit wiring — condensing units — 60 Hz (continued)
TonsUnit Model Number
TTA240E3187-25398110
20
20
25
Notes:
1. Electrical characteristics reflect nameplate values and are calculated in accordance with cULus and ARI specifications. 7.5 and 10 ton
values are system rated; 12.5 - 25 ton values are condensing unit only rated.
2. HACR type circuit breaker per NEC.
TTA240E4414-50646.960
TTA240EK342-41858.870
TTA240EW518-63238.745
TTA240F3187-25398110
TTA240F4414-50649.660
TTA240FK342-41858.870
TTA240FW518-63239.645
TTA300F3187-253130.6150
TTA300F4414-50651.660
TTA300FK342-41866.270
TTA300FW518-63240.945
Unit Operating
Voltage Range
Minimum Circuit Ampacity
Maximum Fuse or HACR
Circuit Breaker Size
Table 7. Electrical characteristics — compressor and condenser fan motors — 50 Hz
Table 9. TTA superheat with matched TWE air handler (continued)
Cooling Superheat
CondenserAir Handler
TTA076GTWE076D15.51—
TTA076HTWE076E10.4410.58
TTA090GTWE090D15.51—
TTA090HTWE090E10.4410.58
TTA101GTWE101D13.68—
TTA101HTWE101E15.1916.72
TTA101FTWE101D11.4—
TTA120GTWE120D13.68—
TTA120HTWE120E15.1916.72
TTA120FTWE120D11.4—
TTA126ETWE126E13.613.6
TTA150ETWE150E13.613.6
TTA156ETWE156E18.418.4
TTA156FTWE156E19.1—
TTA180ETWE180E18.418.4
TTA180FTWE180E19.1—
TTA201ETWE201E15.215.2
TTA201FTWE201E12.9—
TTA240ETWE240E15.215.2
TTA240FTWE240E12.9—
TTA251FTWE251E16.2—
TTA300FTWE251E16.2—
Notes:
1. An adjustable TXV is provided for each circuit in the TWE and TWA models. If the application causes the superheat to deviate from the values
shown above by more than 1 degree - after the system has achieved steady state - the TXV should be adjusted to provide the values shown as
measured at the compressor.
2. The values given above have been tested and are approved for the matched sets shown. If an alternate combination is used, an expansion device
should be used that provides 16-20°F degrees of superheat measured at the compressor.
3. Check and adjust superheat using this table, then compare with charging chart to determine if charge corrections are necessary.
Circuit 1Circuit 2
42
SS-SVX10E-EN
Page 43
Installation Checklist
Complete this checklist once the unit is installed to
verify that all recommended procedures have been
accomplished before starting the system. Do not
operate the system until all items covered by this
checklist are complete.
Inspect unit location for proper required service
clearances.
Inspect unit location for proper free air clearances.
Inspect unit location for secure, level mounting
position.
Remove coil protection boards on microchannel
units.
Refrigerant Piping
Properly sized/constructed liquid and suction lines
connected to stubs at both the indoor and outdoor
units?
Insulated the entire suction line?
Insulated portions of liquid line exposed to
extremes in temperature?
Performed initial leak test?
Evacuated each refrigerant circuit to 500 microns?
Charged each circuit with proper amount of R410A?
Electrical Wiring
Provided unit power wiring (with disconnect) to
proper terminals in the unit control section?
Installed system indoor thermostat?
Installed system low voltage interconnecting wiring
to proper terminals of outdoor unit, indoor unit and
system thermostat?
SS-SVX10E-EN
43
Page 44
Pre-Start
Control Circuit Features
NNoottee:: Not all of these features may be required for your
unit, check electrical schematic.
Discharge Temperature Limit (DTL)
The control’s sensor is located on the discharge line.
This device will shut off the compressor and the
outdoor fan(s) if the discharge temperature exceeds the
DTL setting. Once the discharge temperature has
returned to normal, the compressor will cycle back on.
Low Outdoor Ambient Cooling
The Evaporator Defrost Control is standard equipment
on Air Handlers and will permit low ambient cooling
down to 50°F. For cooling operation down to 0°F, use an
Accessory Head Pressure Control on the outdoor unit.
Evaporator Defrost Control (EDC)
This control is located in the Air Handler. The control’s
sensing tube is embedded vertically in the evaporator
coil, near the center. This device will stop the
compressor if the indoor coil temperature drops below
its setting. The indoor air will still circulate across the
coil bringing the temperature of the coil back up to the
cut-in temperature of the evaporator defrost control.
Low Pressure Cut-Out (LPCO)
This control’s sensor is located in the suction (gas) line,
near the compressor. This control will stop the
compressor and the outdoor fans if suction pressure
drops below the Low Pressure Cut-Out setting. Once
the suction pressure has returned to normal, the
compressor and outdoor fans will cycle back on.
High Pressure Cut-Out (HPCO)
This control’s sensor is located in the discharge line.
This device will shut off the compressor and the
outdoor fan(s) if the discharge pressure exceeds the
High Pressure Cut-Out’s setting. Once the discharge
pressure has returned to normal, the compressor will
cycle back on.
This device is embedded in the compressor. It will shut
off the compressor if the discharge temperature of the
compressor exceeds its design trip temperature.
NNoottee:: The IOL will put the compressor back in
operation once the compressor motor heat has
dropped below the trip setting; however, a check
of the refrigerant and electrical systems should
be made to determine the cause and be
corrected.
44
SS-SVX10E-EN
Page 45
Start-Up
Electromechanical Controls
The 24–volt, electromechanical controls feature a
control transformer and contactor pressure lugs for
power wiring. Once the unit is properly installed and
pre-start procedures are complete, start the unit by
turning the System Switch on the indoor thermostat to
either HHEEAATT, CCOOOOLL or AAUUTTOO. The system should
operate normally.
Operation of the system cooling (and optional heating)
cycles is controlled by the position of the system switch
on the room thermostat. Once the system switch is
placed in either the HHEEAATTor CCOOOOLL position, unit
operation is automatic. The optional automatic
changeover thermostat, when in the AAUUTTOO position,
automatically changes to heat or cool with sufficient
room temperature change.
Evaporator Fan (Indoor Supply Air)
The evaporator fan is controlled by an OONN//AAUUTTOO
switch on the room thermostat. With the switch
positioned at AAUUTTOO and the system operating in the
cooling mode, fan operation coincides with the cooling
run cycles. If the system is equipped with heat and is
operating in the heating mode while the fan switch is at
AAUUTTOO, fan operation coincides with the heating run
cycles. When the fan switch is positioned at OONN, fan
operation is continuous.
Cooling Mode
With the disconnect switch in the OONN position, current
is supplied to the compressor sump heater(s), phase
monitor and control transformer. The sump heater(s)
supplies heat to the compressor(s) during the ““OOffff””
cycle. The phase monitor looks at the incoming power
to verify that there is no reversed phase, no phase
imbalance, and no loss of phase. If the phase monitor
detects any of these three conditions, it will shut off
control voltage. The transformer steps down the line
voltage to 24V for the low voltage control circuit. When
the room thermostat system switch is positioned at
CCOOOOLL and the fan switch is at AAUUTTOO, the compressor
contactor energizes on a call for cooling. When the
contacts of the compressor contactor close, operation
of the compressor and condenser fan begins. The
evaporator fan contactor also energizes on a call for
cooling and initiates evaporator fan operation.
On units with dual circuits, the second stage of cooling
is initiated as a result of the 2-stage thermostat calling
for additional cooling.
ReliaTel Controls
The ReliaTel™ Control is a microelectronic control
feature, which provides operating functions that are
significantly different than conventional
Electromechanical units. The ReliaTel™ Refrigeration
Module (RTRM) uses Proportional/Integral control
algorithms to perform specific unit functions that
govern the unit operation in response to application
conditions.
The RTRM provides compressor anti-short cycle timing
functions through minimum ““OOffff”” and ““OOnn”” timing to
increase reliability, performance and to maximize unit
efficiency. Upon power initialization, the RTRM
performs self-diagnostic checks to ensure that all
internal controls are functioning. It checks the
configuration parameters against the components
connected to the system. The system LED located on
the RTRM module is turned ““OOnn”” within one second
after power-up if all internal operations are okay.
Once the unit is properly installed and pre-start
procedures are complete, start the unit by turning the
System Switch on the indoor thermostat to either
HHEEAATT, CCOOOOLL or AAUUTTOO. The system should operate
normally.
When the system switch is set to the CCOOOOLL position
and the zone temperature rises above the cooling
setpoint, the RTRM energizes the compressor
contactor, provided the high and low pressure and the
discharge temperature limit controls are closed. When
the compressor contacts close, the compressor and the
outdoor fan motor start to maintain the zone
temperature to within ± 2°F of the sensor setpoint at
the sensed location. On units with dual circuits, the
second stage of cooling is initiated as a result of the
Proportional/Integral control algorithms calling for
additional cooling.
SS-SVX10E-EN
45
Page 46
SSttaarrtt--UUpp
For Thermostat Control
When the room thermostat system switch is positioned
at CCOOOOLL and the fan switch is at AAUUTTOO, the RTRM
energizes the compressor contactor, provided the high
and low pressure and the discharge temperature limit
controls are closed. When the contacts of the
compressor contactor close, operation of the
compressor and condenser fan begins. The evaporator
fan contactor also energizes on a call for cooling and
initiates evaporator fan operation. On units with dual
circuits, the second stage of cooling is initiated as a
result of the 2-stage thermostat calling for additional
cooling.
NNoottee:: Irregular unit operation may occur when the unit
is controlled with a triac-switching thermostat.
Please review the approved thermostat vendor
list for all recommended relay-switching
thermostats.
Control Evaporator Fan Operation
When the fan selection switch is set to the AAUUTTOO
position, the RTRM energizes the evaporator fan relay
coil approximately 1 second after energizing the
compressor contactor coil in the cooling mode. In the
heating mode, the RTRM energizes the evaporator fan
relay coil approximately 1 second before energizing the
electric heat contactors.
The RTRM de-energizes the evaporator fan relay coil
approximately 60 seconds on dual compressor units
and 80 seconds on single compressor units after the
cooling requirement has been satisfied to enhance unit
efficiency. When the heating cycle is terminated, the
evaporator fan relay coil is de-energized at the same
time as the heater contactors. When the fan selection
switch is set to the OONN position, the RTRM keeps the
evaporator fan relay coil energized for continuous fan
motor operation.
Control Heating Operation
Electric heat is factory disabled on all split system units
with ReliaTel control (jumper placed between J2-1 and
J2-2 RTRM inputs). To configure the unit for electric
heat, cut or remove the jumper wire between J2-1 and
J2-2 on the RTRM. All split system units with ReliaTel
control are also configured from the factory for only 1stage of electric heat (jumper placed between J1-3 and
J1-6 RTRM inputs). To configure the unit for 2-stages of
electric heat, cut or remove the jumper placed between
J1-3 and J1-6 RTRM inputs.
When the system switch is set to the HHEEAATT position
and heating is required, the RTRM energizes the Heat 1
relay coil on the RTRM. When the Heat 1 relay contacts
close, the first stage electric heat contactor is
energized. If the first stage of electric heat cannot
satisfy the heating requirement, the RTRM energizes
the Heat 2 relay coil on the RTRM. When the Heat 2
relay contacts close, the second stage electric heat
contactor is energized. The first and second stages of
heat are cycled ““OOnn”” and ““OOffff”” as required to maintain
the zone.
46
SS-SVX10E-EN
Page 47
Service Test Modes for ReliaTel™™ Controls
Test Modes
Upon power initialization, the RTRM performs selfdiagnostic checks to ensure that all internal controls are
functional. It also checks the configuration parameters
against the components connected to the system. The
system LED located on the RTRM module is turned
““OOnn”” within one second of power-up if internal
operation is okay.
Use one of the following ““TTeesstt”” procedures to bypass
Step Test Mode
This method initiates the different components of the
unit, one at a time, by temporarily shorting across the
two test terminals for 2 to 3 seconds.
For the initial start-up of the unit, this method allows
the technician to cycle a component ““OOnn”” and have up
to one hour to complete the check. Service Test Mode
will be ignored if a short is present across Test 1 and
Test 2 at start-up.
some time delays and to start the unit at the control
panel. Each step of unit operation can be activated
individually by temporarily shorting across the ““TTeesstt””
terminals for 2 to 3 seconds. The system LED located
on the RTRM module will blink when the test mode has
been initiated. The unit can be left in any ““TTeesstt”” step
for up to one hour before it will automatically
terminate, or it can be terminated by opening the main
power disconnect switch. Once the test mode has been
terminated, the system LED will glow continuously and
Resistance Test Mode
This method can be used for start-up when a decade
box for variable resistance outputs is available. This
method initiates the different components of the unit,
one at a time, when a specific resistance value is placed
across the two test terminals. The unit will remain in
the specific test mode for approximately one hour even
though the resistance is left on the test terminals.
the unit will revert to the ““SSyysstteemm”” control.
There are three methods in which the ““SSeerrvviiccee TTeesstt””
can be cycled at LTB-Test 1(T1) and LTB-Test 2 (T2).
Table 10. Service test guide for component operation
TEST STEPMODEFANCOMP 1COMP 2HEAT 1HEAT 2OHMS
1FanOnOffOffOffOff2.2K
(a)
2Cool 1On
(b)
3
(b)
4
(b)
5
(a)
The condenser fans will operate any time a compressor is ON.
(b)
Steps for optional accessories and non-applicable modes in unit will be skipped.
Cool 2On
Heat 1OnOffOffOnOff10K
Heat 2OnOffOffOnOn15K
On
On
OffOffOff4.7K
(a)
On
(a)
OffOff6.8K
Auto Test Mode
This method is not recommended for start-up due to
the short timing between individual component steps.
This method initiates the different components of the
unit, one at a time, when a fixed jumper is installed
across the test terminals.
SS-SVX10E-EN
The unit will start the first test step and change to the
next step every 30 seconds. At the end of the test
mode, control of the unit will automatically revert to the
applied ““SSyysstteemm”” control method. For unit test steps,
test modes, and step resistance values to cycle the
The RTRM has the ability to provide the service
personnel with some unit diagnostics and system
status information.
Before turning the main power disconnect switch ““OOffff,,””
follow the steps below to check the ReliaTel™
Refrigeration Module (RTRM). All diagnostics & system
status information stored in the RTRM will be lost when
the main power is turned ““OOffff””.
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard
and use extreme care when performing service
procedures with the electrical power energized.
NNoottee:: The J6 & J7 screw terminals must be tightened
in order to accurately measure voltage in the
required steps.
1. Verify that the system LED on the RTRM is burning
continuously. If the LED is lit, go to Step 3.
2. If the LED is not lit, verify that 24 VAC is present
between J1-1 and J1-2. If 24 VAC is present,
proceed to Step 3. If 24 VAC is not present, check
the unit main power supply, check transformer
(TNS1). Proceed to Step 3 if necessary.
3. Utilizing “Method 1,” p. 48 or “Method 2,” p. 49 in
the System Status Checkout Procedure section,
check the following:
•System status
•Heating status
•Cooling status
NNoottee:: If a System failure is indicated, proceed to
Step 4. If no failures are indicated, proceed to
Step 5.
4. If a System failure is indicated, recheck Step 1 and
Step 2. If the LED is not lit in Step 1, and 24 VAC is
present in Step 2, then the RTRM has failed.
Replace the RTRM.
5. If no failures are indicated, use one of the TEST
mode procedures described in the “Service Test
Modes chapter,” p. 47 to start the unit. This
procedure will allow you to check all of the RTRM
outputs, and all of the external controls (relays,
contactors, etc.) that the RTRM outputs energize, for
each respective mode. Proceed to Step 6.
6. Step the system through all of the available modes,
and verify operation of all outputs, controls, and
modes. If a problem in operation is noted in any
mode, you may leave the system in that mode for
up to one hour while troubleshooting. Refer to the
sequence of operations for each mode, to assist in
verifying proper operation. Make the necessary
repairs and proceed to Step 7 and Step 8.
7. If no abnormal operating conditions appear in the
test mode, exit the test mode by turning the power
““OOffff”” at the main power disconnect switch.
8. Refer to the individual component test procedures if
other microelectronic components are suspect.
System Status Checkout
Procedure
““SSyysstteemm SSttaattuuss”” is checked by using one of the
following two methods:
Method 1
If the Zone Sensor Module (ZSM) is equipped with a
remote panel with LED status indication, you can check
the unit within the space. If the ZSM does not have
LED’s, use “Method 2,” p. 49. BAYSENS010B,
BAYSENS011B, BAYSENS119A, BAYSENS020A,
BAYSENS021A, BAYSENS023A, BAYSENS109 and
BAYSENS110 all have the remote panel indication
feature. The LED descriptions are listed below.
•LLEEDD 11 ((SSyysstteemm))
– ““OOnn”” during normal operation.
– ““OOffff”” if a system failure occurs or the LED fails.
– ““FFllaasshhiinngg”” indicates test mode
•LLEEDD 22 ((HHeeaatt))
– ““OOnn”” when the heat cycle is operating.
– ““OOffff”” when the heat cycle terminates or the LED
fails.
– ““FFllaasshhiinngg”” indicates a heating failure.
•LLEEDD 33 ((CCooooll))
– ““OOnn”” when the cooling cycle is operating.
– ““OOffff”” when the cooling cycle terminates or the
LED fails.
– ““FFllaasshhiinngg”” indicates a cooling failure.
The following information describes the complete
listing of failure indication causes.
48
SS-SVX10E-EN
Page 49
TTrroouubblleesshhoooottiinngg
System Failure
Check the voltage between terminals 6 and 9 on J6, it
should read approximately 32 VDC. If no voltage is
present, a System failure has occurred. Refer to Step 4
in the previous section for the recommended
troubleshooting procedure.
Cooling Failure
1. Cooling and heating set point (slide pot) on the
zone sensor has failed. Refer to the “Programmable
& Digital Zone Sensor Test,” p. 50.
2. Zone temperature thermistor ZTEMP on ZTS failed.
Refer to the “Programmable & Digital Zone Sensor
Test,” p. 50.
3. CC1 or CC2 24 VAC control circuit has opened,
check CC1 & CC2 coils, and any of the controls
below that apply to the unit (HPC1, HPC2, DTL1,
DTL2).
4. LPC1 has opened during the 3 minute minimum “on
time” during 4 consecutive compressor starts,
check LPC1 or LPC2 by testing voltage between the
J1-8 & J3-2 terminals on the RTRM and ground. If
24 VAC is present, the LPCs have not tripped. If no
voltage is present, LPCs have tripped.
The second method for determining system status is
done by checking voltage readings at the RTRM (J6).
The system indication descriptions and the
approximate voltages are listed below.
System Failure
Measure the voltage between terminals J6-9 & J6-6.
•NNoorrmmaall OOppeerraattiioonn = approximately 32 VDC
•SSyysstteemm FFaaiilluurree = less than 1 VDC, approximately
0.75 VDC
•TTeesstt MMooddee = voltage alternates between 32 VDC &
0.75 VDC
Heat Failure
Measure the voltage between terminals J6-7 & J6-6.
•HHeeaatt OOppeerraattiinngg = approximately 32 VDC
•HHeeaatt OOffff = less than 1 VDC, approximately 0.75 VDC
•HHeeaattiinngg FFaaiilluurree = voltage alternates between 32
VDC & 0.75 VDC
Cool Failure
Measure the voltage between terminals J6-8 & J6-6.
•CCooooll OOppeerraattiinngg = approximately 32 VDC
•CCooooll OOffff = less than 1 VDC, approximately 0.75 VDC
•CCoooolliinngg FFaaiilluurree = voltage alternates between 32
VDC & 0.75 VDC
To use LED’s for quick status information at the unit,
purchase a BAYSENS010B ZSM and connect wires with
alligator clamps to terminals 6 through 10. Connected
each respective terminal wire (6 through 10) from the
Zone Sensor to the unit J6 terminals 6 through 10.
NNoottee:: If the system is equipped with a programmable
zone sensor, (BAYSENS119A, or BAYSENS023A),
the LED indicators will not function while the
BAYSENS010A is connected.
Temperature Tests
NNoottee:: These procedures are not for programmable or
digital models and are conducted with the Zone
Sensor Module electrically removed from the
system.
Test 1 - Zone Temperature Thermistor
(ZTEMP)
This component can be tested by measuring the
resistance between terminals 1 and 2 on the Zone
Temperature Sensor. See Table 11, p. 49 for typical
indoor temperatures, and corresponding resistive
values.
Table 11. Typical indoor temperatures and values
Zone Temperature
50°F or 10.0°C19.9 Kohms
55°F or 12.8°C17.47 Kohms
60°F or 15.6°C15.3 Kohms
65°F or 18.3°C13.49 Kohms
70°F or 21.1°C11.9 Kohms
75°F or 23.9°C10.50 Kohms
80°F or 26.7°C9.3 Kohms
85°F or 29.4°C8.25 Kohms
90°F or 32.2°C7.3 Kohms
Test 2 - Cooling Set Point (CSP) and
Heating Set Point (HSP)
CCooooll SSPP = Terminals 2 and 3
Nominal Resistance
SS-SVX10E-EN
49
Page 50
TTrroouubblleesshhoooottiinngg
Range = 100 to 900 Ohms approximate
HHeeaatt SSPP = Terminals 2 and 5
Range = 100 to 900 Ohms approximate
Table 12. Test 3 - system mode and fan selection
Resistance Valves(Ohms)
2.32K
4.87K
7.68K
10.77K
13.32K
16.13K
19.48K
27.93K
35.0K
43.45K
Out of Range (Short)
Out of Range (Open)INVALID/OpenInvalid (CV), Off (VAV)
Zone Sensor Unit/Fan
ModeLocal Unit ModeLocal Fan Mode
Off/Auto
Cool/Auto
Auto/Auto
Off/On
Cool/On
Auto/On
Heat/Auto
Heat/On
Emergency Heat/AutoEmergency Heat
Emergency Heat/OnEmergency Heat
INVALID/Short
Test 3 - System Mode and Fan Selection
The combined resistance of the MMOODDEE selection switch
and the FFAANN selection switch can be measured
between terminals 2 and 4 on the Zone Sensor. The
possible switch combinations are listed in Table 12, p.
50 with their corresponding resistance values.
OffAuto
CoolAuto
AutoAuto
OffOn
CoolOn
AutoOn
HeatAuto
HeatOn
Auto
On
Invalid (CV), Auto (VAV)
Invalid
Invalid
Test 4 - LED Indicator Test (SYS ON,
HEAT, & COOL)
Testing the LED using a meter with diode test function.
Test both forward and reverse bias. Forward bias
should measure a voltage drop of 1.5 to 2.5 volts,
depending on your meter. Reverse bias will show an
Over Load, or open circuit indication if LED is
functional.
Method 2
Testing the LED with an analog Ohmmeter. Connect
Ohmmeter across LED in one direction, then reverse
the leads for the opposite direction. The LED should
have at least 100 times more resistance in reverse
direction, as compared with the forward direction. If
high resistance in both directions, LED is open. If low in
both directions, LED is shorted.
Method 3
To test LED’s with ZSM connected to unit, test voltages
at LED terminals on ZSM. A measurement of 32 VDC,
across an unlit LED, means the LED has failed.
IImmppoorrttaanntt:: Measurements should be made from LED
common (ZSM terminal 6 to respective LED
terminal).
Programmable & Digital Zone
Sensor Test
Testing Serial Communication Voltage
1. Verify 24 VAC is present between terminals J6-14 &
J6-11.
2. Disconnect wires from J6-11 and J6-12. Measure
the voltage between J6-11 and J6-12, should be
about 32 VDC.
3. Reconnect wires to terminals J6-11 and J6-12.
Measure voltage again between J6-11 and J6-12,
voltage should flash high and low every 0.5
seconds. The voltage on the low end will measure
about 19 VDC, while the voltage on the high end
will measure from approximately 24 to 38 VDC.
4. Verify all modes of operation, by running the unit
through all of the steps in “Service Test Modes for
ReliaTel Controls,” p. 47.
5. After verifying proper unit operation, exit the test
mode. Turn the fan on continuously at the ZSM, by
pressing the button with the fan symbol. If the fan
comes on and runs continuously, the ZSM is good.
If you are not able to turn the fan on, the ZSM is
defective.
RLCI Loss of Communications
If the RLCI loses input from the building management
system, the RTRM will control in the default mode after
approximately 15 minutes. If the RTRM loses the
Heating and Cooling setpoint input, the RTRM will
control in the default mode instantaneously. The
temperature sensing thermistor in the Zone Sensor
Module is the only component required for the
““DDeeffaauulltt MMooddee”” to operate.
Resetting Cooling and Heating
Lockouts
Cooling Failures and Heating Lockouts are reset in an
identical manner.“Method 1,” p. 51 explains resetting
the system from the space; “Method 2,” p. 51 explains
resetting the system at the unit.
NNoottee:: Before resetting Cooling Failures and Heating
Lockouts check the Failure Status Diagnostics by
the methods previously explained. Diagnostics
will be lost when the power to the unit is
disconnected.
Method 1
To reset the system from the space, turn the MMOODDEE
selection switch at the zone sensor to the OOFFFF position.
After approximately 30 seconds, turn the MMOODDEE
selection switch to the desired mode, i.e. HHEEAATT, CCOOOOLL,
or AAUUTTOO.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch OOFFFF and then OONN
Lockouts can be cleared through the building
management system. Refer to the building
management system instructions for more
information.
Zone Temperature Sensor (ZTS)
Service Indicator
The ZSM SERVICE LED is a generic indicator that will
signal the closing of a Normally Open switch at any
time, providing the Indoor Motor (IDM) is operating.
This indicator is usually used to indicate an airside fan
failure.
The RTRM will ignore the closing of this Normally
Open switch for 2 (±1) minutes. This helps prevent
nuisance SERVICE LED indications.
Perform all of the indicated maintenance procedures at
the intervals scheduled. This will prolong the life of the
unit and reduce the possibility of costly equipment
failure.
Monthly
Conduct the following maintenance inspections once
per month.
Check unit wiring to ensure all connections are tight
and that the wiring insulation is intact.
Inspect the condenser coils for dirt and debris. If the
coils appear dirty, clean them.
With the unit operating in the cooling mode, check
the suction and discharge pressures and compare
them with Pressure Curve values in unit Service
Facts. Record these readings on the “Maintenance
Log,” p. 54.
Annually (Cooling Season)
The following maintenance procedures must be
performed at the beginning of each cooling season to
ensure efficient unit operation.
Perform all of the monthly maintenance
inspections.
With the unit operating, check unit superheat and
record the reading in the “Maintenance Log,” p. 54.
Remove any accumulation of dust and/or dirt from
the unit casing.
Remove corrosion from any surface and repaint.
Check the gasket around the control panel door to
ensure it fits correctly and is in good condition to
prevent water leakage.
Inspect the control panel wiring to ensure that all
connections are tight and that the insulation is
intact.
NNoottee:: Condenser fan motors are permanently
lubricated.
Check refrigerant piping and fittings for leaks
Inspect the condenser coils for dirt and debris. If the
coils appear dirty, clean them.
Coil Cleaning
Regular coil maintenance, including annual cleaningenhances the unit's operating efficiency by minimizing:
•compressor head pressure and amperage draw
•water carryover
•fan brake horsepower
•static pressure losses
At least once each year — or more often if the unit is
located in a “dirty” environment — clean the coil using
the instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging
the coils.
Tube and Fin
NNoottee:: To clean refrigerant coils, use a soft brush and a
sprayer. Contact your local Parts Center for
appropriate detergents.
1. Remove enough panels from the unit to gain safe
access to coil.
2. Straighten any bent coil fins with a fin comb.
3. Remove loose dirt and debris from both sides of the
coil with a soft brush.
4. Mix the detergent with water according to the
manufacturer's instructions. If desired, heat the
solution to 150° F maximum to improve its
cleansing capability.
5. Pour the cleaning solution into the sprayer.
6. Spray the leaving-airflow side of the coil first; then
spray the opposite side of the coil. Allow the
cleaning solution to stand on the coil for five
minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be
dirty, repeat Step 7 and 8.
9. Reinstall all of the components and panels removed
52
SS-SVX10E-EN
Page 53
MMaaiinntteennaannccee
in Step 1; then restore power to the unit.
10. Using a fin comb, straighten any coil fins that were
inadvertently bent during the cleaning process.
Due to the soft material and thin walls of the MCHE
coils, the traditional field maintenance method
recommended for Round Tube Plate Fin (RTPF) coils
does not apply to microchannel coils. Moreover,
chemical cleaners are a risk factor to MCHE due to the
material of the coil. The manufacturer does not
recommend the use of chemical cleaners to clean
microchannel coils. Using chemical cleaners could lead
to warranty claims being further evaluated for validity
and failure analysis.
The recommended cleaning method for microchannel
condenser coils is pressurized water or air with a nonpinpoint nozzle and an ECU of at least 180 with
pressure no greater than 600 psi. To minimize the risk
of coil damage, approach the cleaning of the coil with
the pressure washer aimed perpendicular to the face of
the coil during cleaning. Optimum clearance between
the sprayer nozzle and the microchannel coil is 1”–3”.
SS-SVX10E-EN
53
Page 54
MMaaiinntteennaannccee
Maintenance Log
Subcooling (°F)
(at service valve)
Superheat (°F)
(at compressor)
Circuit #1Circuit #2Circuit #1Circuit #2
Discharge Pressure
(C1)(C2)(C1)(C2)
Suction Pressure
Wet
Bulb
Dry
Bulb
Evaporator Entering AirCompressor
(°F)
Temp.
Ambient
Date
Note: Perform each inspection once per month (during cooling season) while unit is operating
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.