Trane TSH 060, TSD User Manual

Voyagerâ„¢ I Rooftop Units Cooling-only TSD/TSH 060 072 102 120 Reversible WSD/WSH 060 072 090 Gas-fired YSD/YSH 060 072 090 102 120
Installation Operation Maintenance
General information
RT-SVX20A-E42
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane TSD/TSH, WSKD/WSH and YSD/YSH units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.
TSD/TSH units are designed to operate in cooling mode only, with optional auxiliary heat (electric heater or hot water coil).
WSD/WSH can operate in cooling mode or heating mode by reversing the refrigeration cycle with or without auxiliary heat.
YSD/YSH units are designed to operate In cooling mode and equipped with a gas fired heating module.
TSD/TSH, WSD/WSH and YSD/YSH units are assembled, pressure tested, dehydrated, charged and run tested before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
General information
3RT-SVX20A-E4
Reception
On arrival, inspect the unit before signing the delivery note. In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.
Reception in France only:
Concealed damage must be looked for at delivery and immediately treated as visible damage.
Reception in all countries except France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
Refrigerant
The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled.
Storage
Take precautions to prevent condensate formation inside the unit's electrical components and motors when:
1. The unit is stored before it is installed; or,
2. The unit is set on the roof curb and temporary auxiliary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up.
Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up".
The Trane Company will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
Contents
RT-SVX20A-E44
General information 2
Foreword 2 Warnings and Cautions 2 Reception 3 Warranty 3 Refrigerant 3 Maintenance contract 3 Storage 3 Training 3
Installation 6
Reception of units 6 Roof curb installation 6 Dimensions/Weights/Clearances 7 Installing the unit 9 Connection of duct network 10 Condensate drain piping 12 Gas pipework installation 13 Filter installation 14 Supply fan adjustment 14 Component air pressure drops 16 Supply fan performances 17 Electrical connection 30
Controls 33
Control wiring 33 CO2sensors 35 Remote potentiometer 39 Fire thermostat 40 Clogged filter detector 41 Smoke detector 41 High temperature safety thermostat 41 Remote fault relay 41 Thermostats 42 Communication Interfaces 43
Contents
5RT-SVX20A-E4
Unit Options 44
Hot water coil 44 Electric Heater 45 Soft Starter 45 0 - 25% fresh air hood 46 Barometric relief 47
Operation 48
Operation with a conventional thermostat 48 Setting the economizer 50 Test procedures 52 Test modes 53 Unit Start-up 54 Cooling without an Economizer 56 Low Ambient Operation 57 Cooling with an Economizer 57 Economizer Set-Up 58 ReliaTelâ„¢ Control Heating Operation 58 Ignition Module 58 Final installation checklist 59
Maintenance 60
End user routine maintenance 60 Service technician maintenance 61 Troubleshooting 62
Installation
RT-SVX20A-E46
General information:The installation must conform to all local standards and regulations.
Reception of units
Rooftop unit
There are two ways to handle the unit:
1. Use the openings in the base to handle the machine using a forklift, in accordance with applicable safety regulations.
2. Use a lifting beam correctly adjusted to fit the unit (Figure 1).
Unit handling
The units are supplied on the truck but are not unloaded. An opening is provided on each corner of the unit base to facilitate handling. Four shackles and four slings are required. Use a lifting beam to prevent the cables pressing too hard on top of the unit during lifting. The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. (Refer to Figures 1 and 2 and Tables 2 and 3.)
Important: For unit to fit on the roof curb the fork lift pockets must be removed.
Figure 1 - Unit handing
Roof curb (accessory)
Roof curbs are available as an accessory for downflow units. The curbs can be adjustable and supplied pre-assembled on wooden pallets, packed under plastic film. Two types of self-adhesive seals are provided to ensure the roof curb seal is leak-tight (40 mm wide for the perimeter, 20 mm wide for the crosspieces).
Roof curb Installation (TSD-WSD-YSD accessories)
Roof curbs are available as an accessory for "downflow" units to support the unit and ensure the water tightness between the rooftop and the roof.
The curbs can be adjustable and supplied pre-assembled on wooden pallets, packed under plastic film. Two types of self-adhesive seals are provided separate. (40 mm wide for the perimeter, 20 mm wide for the cross pieces). Make sure they are properly installed where indicated to assure an adequate curb to unit seal.
Instructions for the roof curb assembly and installation with curb dimensions are provided with each roof curb kit.
Figure 2 - Rigging
1 = Remove 2 fork lift brackets 2 = Remove 2 metal runners and 3
wooden boards
Lift the unit enough to allow the removal of two Fork Lift brackets and hardware. Remove the two Fork Lift brackets, two metal runners and three wooden boards as shown in Figure 2.
1
2
Installation
7RT-SVX20A-E4
Dimensions/Weights/ Clearances
The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. Refer to Table 2 and the space requirement plan.
Figure 3 - Minimum clearances
Table 1 - Minimum recommended clearances
Table 2 - Unit weights and center of gravity
Notes: (1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
Unit Size
Maximum weight Corner weight (1) Center of gravity
Shipping
(kg)
Net (kg)
A
(kg)B(kg)C(kg)D(kg)
Length
(mm)
Width
(mm)
TSD/TSH 060 259 235 75 56 48 56 790 480 TSD/TSH 072 365 326 107 83 58 78 970 560 TSD/TSH 090 428 389 131 101 67 89 970 530 TSD/TSH 102 445 405 133 106 72 94 990 560 TSD/TSH 120 485 445 147 115 81 104 990 560 YSD/YSH 060 285 260 81 64 54 62 810 510 YSD/YSH 072 390 350 113 90 64 83 990 560 YSD/YSH 090 458 419 139 110 75 95 970 530 YSD/YSH 102 474 434 141 114 79 100 1020 560 YSD/YSH 120 520 481 155 126 89 111 1020 560 WSD/WSH 060 266 241 77 58 49 58 790 480 WSD/WSH 072 408 368 122 93 66 87 970 560 WSD/WSH 090 418 378 128 95 67 88 970 530
Unit size Mimum clearances (mm)
12345 TSD/TSH 060 1829 1219 914 914 914 TSD/TSH 072 1829 1219 914 914 914 TSD/TSH 090 1829 1219 914 914 914 TSD/TSH 102 1829 1219 914 914 914 TSD/TSH 120 1829 1219 914 914 914 YSD/YSH 060 18 29 1219 914 914 914 YSD/YSH 072 18 29 1219 914 914 914 YSD/YSH 090 18 29 1219 914 914 914 YSD/YSH 102 18 29 1219 914 914 914 YSD/YSH 120 18 29 1219 914 914 914 WSD/WSH 060 1829 1219 914 914 914 WSD/WSH 072 1829 1219 914 914 914 WSD/WSH 090 1829 1219 914 914 914
Installation
RT-SVX20A-E48
Figure 4
Table 3 - Factory-installed options and accessories net weights (kg)
Notes: (1) Weights for options not listed are < 3 kg. (2) Net weight should be added to unit weight when ordering factory-installed accessories. (3) Some accessories are not available on all units.
Unit size Economizer
Barometric
Relief
Motorized
Outside Air
Damper
Manual
Outside Air
Damper
Roof Curb
Oversized
Motor
Electric Heaters
Hot water
coil
TSD/TSH 060 11,8 3,2 9,1 7,3 31,8 - 6,8 14,0 TSD/TSH 072 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0 TSD/TSH 090 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0 TSD/TSH 1020 16,3 4,5 13,6 11,8 52,2 3,6 13,6 19,0 TSD/TSH 120 16,3 4,5 13,6 11,8 52,2 3,6 13,6 19,0 YSD/YSH 060 11,8 3,2 9,1 7,3 31,8 - 6,8 YSD/YSH 072 16,3 4,5 13,6 11,8 52,2 3,6 13,6 YSD/YSH 090 16,3 4,5 13,6 11,8 52,2 3,6 13,6 YSD/YSH 102 16,3 4,5 13,6 11,8 52,2 3,6 13,6 YSD/YSH 120 16,3 4,5 13,6 11,8 52,2 3,6 13,6 WSD/WSH 060 11,8 3,2 9,1 7,3 31,8 - 6,8 14,0 WSD/WSH 072 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0 WSD/WSH 090 16,3 4,5 13,6 11,8 52,2 3,6 13,6 17,0
Center of
A
Center of
gravity width
gravity length
B
D
Center of
gravity
C
Installation
9RT-SVX20A-E4
Installing the unit
Discharge Conversion
If a unit is to be converted to Vertical discharge, a panel must be acquired from Trane.
If a unit is to be converted to Horizontal discharge, the following conversion must be performed:
1. Remove the return and supply duct covers.
2. Apply gasket to the return duct cover.
3. Position duct covers as shown in Figure 4. The supply duct cover is installed (insulation side down) over the downflow return opening by engaging one side of the panel under a retaining angle and securing the other side with 3 screws.
4. Slide return duct cover (insulation side up) into supply openings until outer edge of the duct cover engages with the two retaining clips on the duct flanges. Secure the outer edge of the each duct cover with two screws.
Figure 5 - Conversion to horizontal discharge
1 = Supply duct cover, insulation side
down
2 = Return duct cover with gasket
installed, insulation side up
3 = Edge of duct cover goes under
retaining angle
Unit mounting on roof
Fix the rooftop curb on the joint beam of the building's structure. Make the rooftop curb's sealing surface level using angle brackets adjusted by screw bolts, located around its perimeter. Place the adhesive seals on the curb's sealing surface (perimeter and cross pieces). Make the rooftop leak-tight around the curbs before installing the unit, in compliance with current construction standards.
Note:The unit must be installed perfectly level to ensure condensates flow from the condensate tray.
The rooftop unit nests into the curb and is supported by it. Position the unit, taking care to comply with the indicated directions: the unit's discharge and intake openings must match those of the curb.
Figure 6 - Unit mounting on roof
1 = Frame
1
3
1
2
Installation
RT-SVX20A-E410
Installing the unit on the ground
To install the unit on the ground, its base must be level and supported securely. For horizontal discharge units, a support is required such as a metal or concrete slab whose height must be determined according to the amount of snow cover, to prevent problems with condensation drainage and obstruction of the external coil. If necessary use an anti-vibration material between the rooftop unit's base and the support.
Note: Unit installation must comply to local codes
Connection of duct network
1) Downflow discharge units (TSD,WSD,YSD)
Using the rooftop curb
• The rooftop curb must be insulated on the outside walls at the discharge and intake openings to prevent condensation in the ducts.
• The rims around the discharge and intake openings make it possible to attach the flanges on the ends of the ducts. If you are using rigid duct ends recommended on the rooftop curb plan, it is essential to fix these components before installing the unit.
• For the design of the duct network, comply with recommendations currently applicable on the market, in particular:
. Installation of a section of
flexible ducts to limit transmission of the unit's vibrations
. Use of movable vanes or
deflectors to reduce the sound level.
2) Horizontal discharge units
(TSH,WSH,YSH)
• The intake and discharge ducts must be insulated (thermal insulation).
• The duct section located outside must be leak-tight.
• Provide a flexible connector to prevent transmission of the unit vibrations. This flexible duct must be installed inside the building.
Note: In case of use of units with economizer option, temperature and humidity sensors must be installed in return duct.
Economizer linkage is factory mounted but the damper position must be adjusted on site.
Figure 7 - Unit installation on the ground
1 = Concrete slab
Installation
11RT-SVX20A-E4
Table 4 - Duct dimensions for downflow units (mm)
Table 5 - Duct dimensions for downflow units (mm)
Unit size ABCD
TSH/WSH 060
591 337 375 438
YSH 060
591 337 375 438
TSH/WSH/YSH 072/090
832 425 606 489
TSH/YSH 102/120
832 425 606 489
Unit size ABCDEFlanges
TSD 060 619 357 411 459 356 32 YSD 060 610 356 394 457 356 32 WSD 060 819 357 411 459 356 32 TSD/WSD 072/090 875 451 451 875 356 31 TSD 102/120 875 451 451 875 356 31 YSD 072/090/102/120 816 444 444 838 356 31
Figure 8 - Duct dimensions for downflow units
S = Supply R = Return
Figure 9 - Duct dimensions for horizontal units
S = Supply R = Return
B
A
S
E
C
R
D
A
R
C
S
B
D
Installation
RT-SVX20A-E412
Condensate drain piping
A 3/4" condensate drain connection with P-trap is provided. Follow local codes and standard piping practices when running the drain line. Install a trap and be sure to fill with water before starting the unit. Pitch the line downward, away from the unit to avoid long, level, horizontal runs. Refer to Figure 11.
The condensate drain is reversible to allow installation of a drain tap on either side of the unit.
Figure 10 - Condensate drain location
1 = Main condensate drain location
Figure 11 - Condensate drain line location
1 = Static pressure drain pan 2 = Panel enclosure 3 = ¾ " drain 4 = Cleanout plug
1
Installation
13RT-SVX20A-E4
Gas pipework installation
The installation must conform to all standards and regulations.
The gas supply pipework and gas stop valve to be installed near the unit must be sized so as to ensure the gas pressure is sufficient at the unit inlet when operating at full load.
CAUTION! Should the pressure at the unit valve gas inlet be higher than 0.035 bar, an expansion valve must be installed.
The pipework must be self­supporting and the final connection to the burner must be made by a flexible pipe. Provide a dust protection (filter) upstream the unit connection.
CAUTION!The gas pipework must not exert any stress on the burner gas connection.
Note: Expansion valve must be adapted to the type of gas used:
• G 20: 20 mb
• G 25: 25 mb
• G 31 (Propane): 37 or 50 mb
Table 6 - Gas burner models
See Table 51 for burner performance.
Gas leak check procedure
1. Vent the gas line
2. Gas supply line pressure test: close valve 4 and open valve 2
3. Leak-check the gas pipe.
Look for gas pipe leaks using "Typol", "1000 bulles" or a similar product. Do not use soapy water.
WARNING! Never use an open flame to check for gas leaks.
Required gas pressure at the unit inlet connection are given in Table 50.
Note:To operate with propane gas, the burner is fitted with a pressure limiter (supplied by Trane)
Unit Burner size
YSD/YSH 060 G120 YSD/YSH 072 G200 YSD/YSH 090 G200 YSD/YSH 102 G250 YSD/YSH 120 G250
Figure 12 - Typical gas supply pipework
1 = Evaporator section 2 = Gas burner section 3 = Condenser section 4 = Gas supply connection 5 = Gas supply line 6, 8 = Gas stop valve (Field supplied) 7 = Expansion valve (Field supplied) 9 = Filter (Field supplied)
Installation
RT-SVX20A-E414
Filter installation
To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units.
Number and size of filters is determined by size and configuration of the unit. If disposable filters were chosen as an option, they are shipped in the supply fan section.
CAUTION! Do not operate unit without filters in place.
The maximum pressure drops allowable on filters are:
EU2/G2: 120 Pa EU4/G4: 150 Pa
Table 7 - Filter arrangement
Unit
EU2/G2 EU4/G4
Quantity Size Quantity Size
TSD/TSH/YSD/YSH/WSD/WSH 060 2 (508x762x25) 2 (500x750x25) TSD/TSH/YSD/YSH/WSD/WSH 072 4 (406x635x50) 4 (395x625x50) TSD/TSH/YSD/YSH/WSD/WSH 090 4 (406x635x50) 4 (395x625x50) TSD/TSH/YSD/YSH 102 4 (508x635x50) 4 (500x625x50) TSD/TSH/YSD/YSH 120 4 (508x635x50) 4 (500x625x50)
Supply fan adjustment
Use the following procedure to determine the proper adjustment of the supply fan for a specific application.
1. Determine total external static pressure about system and accessories.
• Obtain the design airflow rate and the design external static pressure drop through the distribution system.
• Add static pressure drop of the accessories installed on the unit. (Table 9)
• Add the total accessory static pressure drop (from step 1b) to the design external static pressure (from step 1a). The sum of these two values is the total system external static pressure.
2. Using the Tables 10 through 35 to find the external static pressure that most closely approximates total system external static pressure. Then locate the appropriate airflow rate for your unit. The value obtained represents the brake horsepower for the supply fan motor and the fan RPM.
3. Adjust motor sheave according to Table 8.
Installation
15RT-SVX20A-E4
To adjust belt
The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn.
Units with dual belts require a matched set of belts to ensure equal belt length.
When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.
Once the new belts are installed, adjust the belt tension.
Table 8 - Motor sheave / Fan speed
Fan speed (RPM)
Standard drive & motor
Unit
6 turns
Open
5 turns
Open
4 turns
Open
3 turns
Open
2 turns
Open
1 turns
Open
Closed
TSD/TSH 060 N/A 898 967 1036 1105 1174 1243 TSD/TSH 072 N/A 698 751 806 859 913 967 TSD/TSH 090 N/A 752 806 860 914 968 1020 TSD/TSH 102 N/A 688 737 786 835 885 934 TSD/TSH 120 N/A 782 838 894 950 1006 1062 YSD/YSH 060 N/A 1036 1105 1174 1243 1312 1381 YSD/YSH 072 N/A 806 860 913 968 1022 1074 YSD/YSH 090 859 913 967 1021 1075 1129 N/A YSD/YSH 102 786 836 885 934 982 1032 N/A YSD/YSH 120 894 950 1006 1062 1118 1174 N/A WSD/WSH 060 N/A 898 967 1036 1105 1174 1243 WSD/WSH 072 N/A 698 751 806 859 913 967 WSD/WSH 090 N/A 752 806 860 914 968 1020
Fan speed (RPM)
Oversized drive & motor
Unit
6 turns
Open
5 turns
Open
4 turns
Open
3 turns
Open
2 turns
Open
1 turns
Open
Closed
TSD/TSH 060 N/A 1243 1311 1379 1450 1515 1588 TSD/TSH 072 N/A 967 1021 1075 1128 1183 1235 TSD/TSH 090 1112 1182 1252 1322 1392 1460 N/A TSD/ T S H 10 2 N/A 97 1 1041 1111 118 1 1251 13 2 1 TSD/TSH 120 1062 1118 1174 1229 1285 1341 N/A YSD/YSH 060 ------­YSD/YSH 072 N/A 967 1021 1075 1128 1183 1235 YSD/YSH 090 1112 1182 1252 1322 1392 1460 N/A YS D / YS H 102 N/A 971 1041 1111 118 1 1251 1321 YSD/YSH 120 1062 1118 1174 1229 1285 1341 N/A WSD/WSH 060 N/A 1243 1311 1379 1450 1515 1588 WSD/WSH 072 N/A 967 1021 1075 1128 1183 1235 WSD/WSH 090 1112 1182 1252 1322 1392 1460 N/A
To increase airflow
Loosen variable sheave set screw and turn sheave clockwise.
To decrease airflow
Loosen variable sheave set screw and turn sheave counter-clockwise.
Component air pressure drops
Table 9 - Pressure drop through accessories
Unit
size
Airflow
(m3/h)
Filter
EU2/G2
Filter
EU4/G4
Economizer
100 %
outside air
Electric
heater
Hot water
coil
060
3060 31 50 38 17 49 34003855462155 3740 46 61 55 25 62 4080 55 66 64 30 68
072
3670 13 37 27 7 46 4080 16 42 29 9 52 4490 19 46 31 11 58 49002350331364
090
4590 19 47 33 12 66 5100 24 52 39 15 74 56102957452083 6120 35 62 52 25 92
102
5200 16 42 40 8 64 5780 20 47 50 10 72 6360 25 52 62 12 81 6940 30 57 75 15 90
120
6120 22 50 52 11 84 68002755621495 7480 33 61 73 17 106 8160 40 66 85 20 117
Installation
RT-SVX20A-E416
Installation
17RT-SVX20A-E4
Standard drive Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
Table 10 - TSD 060 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
2720 - - - - - - ----8990.439440.499850.5410230.5910600.6410930.6911260.74
3060 - - - - - - - - 904 0.49 947 0.54 988 0.58 1028 0.64 1067 0.70 1104 0.76 1138 0.82 1171 0.87
34 0 0 - - - - - - 91 8 0 . 57 95 8 0 . 6 2 99 8 0 . 67 10 3 6 0. 7 1 10 7 3 0. 76 1111 0 .8 2 114 7 0 .8 9 118 2 0. 96 1 2 15 1.0 2
3740 - - - - 930 0.65 977 0.71 1016 0.77 1053 0.82 1089 0.88 1124 0.93 1158 0.98 1191 1.03 1226 1.10 1258 1.17
4080 909 0.71 950 0.76 990 0.80 1034 0.87 1074 0.93 1110 1.00 1143 1.06 1177 1.12 1209 1.17 1241 1.23 1272 1.29 - -
325 350 375
m
3
/h kW kW kW
2720 1160 0.79 1190 0.84 1222 0.90
3060 1203 0.93 1232 0.98 1262 1.04
3400 1246 1.09 1276 1.15 1306 1.21
3740 1290 1.25 - - - -
4080 - - - - - -
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Table 11 - TSH 060 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
2720 - - - - - - 898 0.43 953 0.48 1001 0.54 1045 0.59 1087 0.65 1129 0.71 1168 0.77 1206 0.83 1241 0.89
3060 - - - - 897 0.48 953 0.54 1008 0.60 1058 0.67 1102 0.73 1143 0.79 1181 0.85 1219 0.92 1256 0.99 1291 1.05
34 0 0 - - 9 0 8 0 . 54 9 6 1 0 . 60 1 012 0 .6 7 10 62 0 . 74 1111 0 .8 1 115 7 0 .8 8 119 8 0 .9 5 1 2 37 1. 0 2 12 74 1. 0 9 13 09 1. 16 1 34 3 1.2 4
3740 923 0.63 978 0.69 1028 0.76 1075 0.83 1120 0.91 1166 0.99 1211 1.06 1254 1.14 1294 1.22 1330 1.29 - - - -
4080 997 0.80 1049 0.87 1096 0.94 1140 1.02 1183 1.10 1223 1.18 1266 1.27 - - - - - - - - - -
325 350 375
m
3
/h kW kW kW
2720 1275 0.96 1306 1.02 1338 1.09
3060 1326 1.12 1359 1.19 1390 1.26
3400 1376 1.31 - - - -
3740 - - - - - -
4080 - - - - - -
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Supply fan performances
Installation
RT-SVX20A-E418
Standard drive Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
Table 12 - TSD 072 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
3260 - - - - - - ----7260.417690.478110.528510.588890.659250.719600.77
3670 - - - - - - - - 706 0.43 751 0.49 792 0.55 832 0.61 871 0.67 908 0.74 944 0.81 978 0.87
4080 - - - - - - - - 732 0.51 777 0.58 818 0.64 856 0.71 893 0.77 930 0.84 964 0.91 998 0.99
4490 - - - - - - 715 0.54 758 0.60 802 0.68 845 0.75 883 0.82 919 0.89 953 0.96 986 1.04 1019 1.11
4890 - - - - 706 0.58 749 0.64 789 0.71 830 0.79 870 0.87 909 0.95 945 1.02 979 1.10 1011 1.18 1043 1.26
325 350 375
m
3
/h kW kW kW
3260 994 0.83 1026 0.89 1057 0.95
3670 1010 0.94 1043 1.01 1073 1.08
4080 1030 1.06 1063 1.14 1092 1.21
4490 1051 1.19 1082 1.27 1112 1.35
4890 1073 1.34 1103 1.42 1133 1.51
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Table 13 - TSH 072 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
3260 - - - - - - - - 726 0.39 771 0.45 814 0.51 857 0.57 899 0.63 939 0.70 978 0.76 1015 0.83
3670 - - - - - - 716 0.42 762 0.48 804 0.54 843 0.60 883 0.67 922 0.74 960 0.81 996 0.87 1034 0.95
4080 - - - - 701 0.45 751 0.51 798 0.59 839 0.65 877 0.71 914 0.78 950 0.85 984 0.93 1020 1.00 1055 1.08
4490 - - 710 0.51 745 0.56 788 0.62 833 0.69 875 0.77 914 0.85 949 0.91 984 0.98 1016 1.06 1049 1.14 1081 1.23
4890 726 0.58 762 0.64 795 0.70 828 0.76 869 0.82 911 0.91 950 0.99 986 1.07 1019 1.14 1051 1.22 1081 1.30 1112 1.38
325 350 375
m
3
/h kW kW kW
3260 1051 0.90 1086 0.97 1118 1.04
3670 1069 1.02 1103 1.09 1136 1.17
4080 1089 1.16 1122 1.23 1154 1.31
4490 1113 1.31 1144 1.40 1176 1.48
4890 1141 1.47 1170 1.57 1199 1.66
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Installation
19RT-SVX20A-E4
Standard drive Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
Table 14 - TSD 090 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
4080 - - - - - - - - 750 0.54 794 0.60 834 0.67 873 0.73 909 0.80 945 0.87 980 0.95 1013 1.02
4590 - - - - - - - - 787 0.66 830 0.74 871 0.82 908 0.89 943 0.96 977 1.04 1010 1.11 1043 1.19
5100 - - - - 747 0.68 789 0.74 827 0.82 867 0.90 906 0.98 944 1.06 980 1.15 1013 1.23 1045 1.31 1076 1.39
56 10 - - 7 55 0 .7 7 7 9 7 0 .8 5 8 3 6 0 .9 2 8 7 3 1. 0 0 9 0 8 1. 0 8 94 4 1. 17 98 0 1. 26 101 6 1. 35 1 05 0 1. 45 1 08 1 1.5 4 1111 1. 63
6120 771 0.88 809 0.96 848 1.06 885 1.14 921 1.22 954 1.30 986 1.39 1019 1.49 1052 1.58 1085 1.69 1116 1.79 1148 1.89
325 350 375
m
3
/h kW kW kW
4080 1046 1.10 1076 1.17 1106 1.25
4590 1074 1.27 1105 1.36 1134 1.44
5100 1105 1.47 1134 1.56 1163 1.65
5610 1141 1.72 1168 1.80 1197 1.90
6120 1177 1.99 1204 2.08 1232 2.18
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Table 15 - TSH 090 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
4080 - - - - - - 769 0.54 814 0.61 855 0.67 893 0.73 929 0.81 965 0.88 999 0.96 1035 1.04 1070 1.12
4590 - - - - 773 0.62 817 0.68 862 0.76 904 0.85 941 0.92 975 0.98 1009 1.06 1041 1.14 1073 1.22 1104 1.31
5100 771 0.68 805 0.74 837 0.81 870 0.87 912 0.94 951 1.03 989 1.12 1025 1.21 1056 1.28 1088 1.36 1117 1.44 1146 1.53
5610 842 0.89 873 0.96 903 1.03 930 1.10 963 1.17 1000 1.25 1037 1.34 1073 1.45 1106 1.55 1136 1.63 1165 1.72 1194 1.80
6120 913 1.14 942 1.22 970 1.30 996 1.37 1021 1.45 1052 1.52 1086 1.61 1121 1.71 1153 1.82 1184 1.93 1215 2.04 1242 2.13
325 350 375
m
3
/h kW kW kW
4080 1104 1.19 1137 1.27 1168 1.35
4590 1136 1.40 1167 1.48 1198 1.57
5100 1176 1.62 1205 1.72 1233 1.82
5610 1220 1.88 1248 1.98 1275 2.08
6120 1269 2.22 1295 2.31 1319 2.40
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Installation
RT-SVX20A-E420
Standard drive Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
Table 16 - TSD 102 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
4620 - - - - - - ----6950.627330.717690.818020.908331.008631.118921.21
5200 - - - - - - - - 688 0.64 725 0.73 761 0.83 796 0.93 828 1.03 861 1.13 891 1.24 919 1.35
5780 - - - - - - 689 0.68 724 0.76 759 0.86 792 0.96 825 1.07 856 1.18 887 1.28 917 1.40 946 1.51
6350 - - - - 693 0.72 729 0.82 764 0.92 795 1.01 826 1.11 857 1.22 887 1.34 916 1.46 945 1.58 974 1.70
6930 - - 706 0.80 738 0.89 770 0.98 804 1.09 834 1.19 864 1.30 892 1.40 920 1.52 948 1.64 976 1.78 1002 1.91
325 350 375 400 425 450 475 500
m
3
/h kW kW kW kW kW kW kW kW
4620 920 1.33 946 1.44 973 1.55 999 1.67 1025 1.79 1050 1.90 1073 2.02 1098 2.14
5200 946 1.46 973 1.58 999 1.71 1024 1.83 1048 1.96 1072 2.09 1096 2.22 1119 2.34
5780 974 1.63 1001 1.75 1026 1.88 1051 2.01 1074 2.14 1099 2.27 1121 2.41 1143 2.55
6350 1001 1.82 1028 1.95 1054 2.08 1079 2.20 1103 2.34 1126 2.48 1148 2.62 1170 2.76
6930 1029 2.04 1055 2.17 1081 2.30 1105 2.43 1130 2.58 1154 2.72 1176 2.85 1199 3.01
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Table 17 - TSH 102 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
4620 - - - - - - 689 0.58 734 0.67 781 0.77 826 0.88 865 0.98 898 1.07 928 1.16 956 1.25 982 1.33
5200 - - - - 693 0.64 735 0.73 773 0.82 812 0.92 855 1.03 897 1.15 934 1.27 969 1.38 999 1.49 1026 1.58
5780 - - 711 0.75 743 0.82 781 0.91 819 1.01 853 1.11 886 1.21 925 1.34 964 1.47 1000 1.60 1034 1.73 1067 1.86
6350 735 0.89 770 0.97 799 1.04 830 1.12 865 1.23 899 1.34 930 1.45 960 1.56 994 1.68 1028 1.82 1063 1.96 1098 2.11
6930 796 1.14 828 1.23 857 1.31 883 1.39 913 1.48 945 1.60 977 1.72 1006 1.84 1034 1.96 1061 2.08 1093 2.23 1125 2.38
325 350 375 400 425 450 475 500
m
3
/h kW kW kW kW kW kW kW kW
4620 1008 1.42 1033 1.51 1056 1.60 1079 1.69 1102 1.78 1125 1.87 1146 1.95 1168 2.04
5200 1052 1.68 1078 1.78 1101 1.88 1124 1.98 1146 2.08 1168 2.18 1188 2.27 1209 2.37
5780 1094 1.97 1120 2.08 1145 2.20 1168 2.31 1191 2.42 1213 2.53 1234 2.63 1254 2.74
6350 1129 2.26 1158 2.40 1185 2.53 1210 2.66 1234 2.78 1256 2.90 1278 3.03 1299 3.15
6930 1157 2.53 1188 2.70 1218 2.86 1245 3.01 1273 3.16 1297 3.31 - - - -
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Installation
21RT-SVX20A-E4
Standard drive Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
Table 18 - TSD 120 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
5440 - - - - - - ------7890.938221.038561.148871.259171.369451.47
6120 ----------7970.998291.108601.228921.349221.469511.579791.69
6800 - - - - - - 782 1.01 814 1.11 844 1.21 874 1.32 903 1.44 932 1.56 960 1.69 988 1.82 1015 1.95
7480 - - - - 803 1.14 834 1.24 864 1.36 894 1.48 922 1.59 948 1.70 975 1.82 1001 1.95 1028 2.09 1053 2.23
8160 803 1.21 833 1.31 861 1.42 887 1.52 916 1.64 945 1.77 972 1.90 997 2.02 1022 2.14 1046 2.27 1071 2.41 1095 2.55
325 350 375 400 425 450 475 500
m
3
/h kW kW kW kW kW kW kW kW
5440 973 1.60 999 1.72 1024 1.84 1048 1.97 1072 2.10 1095 2.23 1117 2.37 1140 2.51
6120 1007 1.82 1033 1.94 1059 2.07 1082 2.20 1107 2.34 1130 2.49 1152 2.63 1173 2.77
6800 1042 2.08 1068 2.21 1093 2.35 1117 2.48 1142 2.63 1164 2.76 1187 2.91 1209 3.06
7480 1078 2.38 1103 2.52 1128 2.66 1152 2.81 1176 2.95 1198 3.10 1221 3.25 - -
8160 1119 2.70 1142 2.86 1166 3.02 1189 3.17 1212 3.33 - - - - - -
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Table 19 - TSH 120 Available static pressure
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250 275 300
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW kW kW
5440 - - - - - - - - 807 0.94 844 1.04 886 1.16 926 1.28 965 1.41 1000 1.53 1029 1.64 1057 1.75
6120 - - - - 792 0.99 829 1.08 865 1.19 898 1.30 930 1.41 965 1.53 1002 1.67 1038 1.81 1072 1.95 1106 2.10
68 0 0 8 02 1. 13 8 3 3 1. 2 2 8 6 0 1.2 9 89 0 1.3 8 9 23 1. 50 9 5 6 1. 62 9 8 6 1.7 3 10 15 1. 8 5 104 4 1. 9 8 107 7 2 .1 2 1111 2 . 28 114 3 2. 4 3
7480 876 1.49 905 1.58 931 1.67 955 1.75 983 1.86 1014 1.99 1045 2.12 1072 2.25 1098 2.37 1125 2.51 1152 2.65 1182 2.81
8160 950 1.91 977 2.02 1002 2.11 1025 2.20 1048 2.30 1074 2.42 1102 2.56 1131 2.71 1156 2.84 1181 2.98 1205 3.12 1229 3.27
325 350 375 400 425 450 475 500
m
3
/h kW kW kW kW kW kW kW kW
5440 1084 1.86 1108 1.96 1132 2.06 1155 2.17 1177 2.27 1198 2.37 1219 2.48 1239 2.58
6120 1134 2.22 1160 2.35 1185 2.47 1209 2.59 1231 2.70 1252 2.82 1274 2.94 1295 3.06
6800 1174 2.58 1204 2.74 1232 2.90 1260 3.05 1283 3.18 1306 3.32 - - - -
748012112.9712413.1412703.31----------
8160 ----------------
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Loading...
+ 47 hidden pages