Trane BAYHTRS409, BAYHTRS318, BAYHTRS418, BAYHTRS427, BAYHTRS436 Installer's Manual

...
Page 1
Installer’s Guide
Electric Heaters
6-10 Ton Packaged Cooling
November 2009
Model Number Used With
See ‘General Information’ section in this guide
ACC-SVN67D-EN
Page 2
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.\ Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage-only
accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
© 2009 Trane All rights reserved ACC-SVN67D-EN
Page 3
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2. TCO-A replaced for Horizontal Duct Configuration . . . . . . . . . . . . . . . 8
Table 3. Air temperature rise (60 hz). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4. Unit wiring with electric heat (single point connection) - standard effi­ciency Table 5. Unit wiring with electric heat - heat pump - (single point connection) ­standard efficiency Table 6. Unit wiring with electric heat (single point connection) - high efficiency
- 6-10 tons
Table 7. Air temperature rise 380/415 Volt (50 hz) . . . . . . . . . . . . . . . . . . . . . 18
Table 8. Air temperature rise 380/415 Volt (50 hz) . . . . . . . . . . . . . . . . . . . . . 18
Table 9. Cooling only units with electric heater — single power source — 380/415 Volt (50hz) Table 10. Heat pump units with electric heater — single power source — 380/415 Volt (50hz)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
ACC-SVN67D-EN 3
Page 4
General Information
Ta b le 1 .
Model Number Used With
BAYHTRS309
BAYHTRS318
BAYHTRS327
BAYHTRS336
BAYHTRS409
BAYHTRS418
BAYHTRS436
BAYHTRSW09
BAYHTRSW18
BAYHTRSW27
BAYHTRSW36
BAYHTRT309
BAYHTRT318
BAYHTRT327
BAYHTRT336
BAYHTRT409
BAYHTRT418
BAYHTRT427 TSC092E4 TSC102E4 TSC102ED
BAYHTRT436 TSC120ED WSC120ED
BAYHTRT454
BAYHTRTW18
BAYHTRTW36
BAYHTRA318
BAYHTRA327 TSC120E3
BAYHTRA336 TSC120E3
BAYHTRA354 TSC120E3
BAYHTRA418 TSC120E4
BAYHTRA427 TSC120E4
BAYHTRA436 TSC120E4
BAYHTRA454 TSC120E4
BAYHTRAW18 TSC120EW
BAYHTRAW36 TSC120EW
BAYHTRAW54 TSC120EW
BAYHTRB318 WSC120E3
BAYHTRB327 WSC120E3
BAYHTRB336 WSC120E3
BAYHTRB354 WSC120E3
BAYHTRB418 WSC120E4
BAYHTRB427 WSC120E4
BAYHTRB436 WSC120E4
BAYHTRB454 WSC120E4
TSC072E3
TSC072E4
TSC072E4
TSC072EW
TSC092E3 TSC102E3
TSC092E4 TSC102E4
TSC120ED WSC120ED
TSC092EW TSC102EWBAYHTRTW27
TSC120E3
TSC072ED
WSC072ED
WSC090ED
TSC090EDBAYHTRS427
4 ACC-SVN67D-EN
Page 5
Ta b le 1 .
BAYHTRBW18 WSC120EW
BAYHTRBW36 WSC120EW
BAYHTRBW54 WSC120EW
BAYHTRD309 THC092E3 THC102E3
BAYHTRD318 THC092E3 THC102E3 THC120E3
BAYHTRD327 THC092E3 THC102E3 THC120E3
BAYHTRD336 THC092E3 THC102E3 THC120E3
BAYHTRD354 THC120E3
BAYHTRD409 THC092E4 THC102E4
BAYHTRD418 THC092E4 THC102E4 THC120E4
BAYHTRD427 THC092E4 THC102E4 THC120E4
BAYHTRD436 THC092E4 THC102E4 THC120E4
BAYHTRD454 THC120E4
BAYHTRU309 THC072E3 WSC090E3
BAYHTRU318 THC072E3 WSC090E3
BAYHTRU327 THC072E3 WSC090E3
BAYHTRU336 THC072E3 WSC090E3
BAYHTRU409 THC072E4 WSC090E4
BAYHTRU418 THC072E4 WSC090E4
BAYHTRU427 THC072E4 WSC090E4
BAYHTRU436 THC072E4 WSC090E4
BAYHTRUW18 THC072EW WSC090EW
BAYHTRUW27 THC072EW WSC090EW
BAYHTRUW36 THC072EW WSC090EW
BAYHTRW309 TSC090E3 WSC072E3
BAYHTRW318 TSC090E3 WSC072E3
BAYHTRW327 TSC090E3 WSC072E3
BAYHTRW336 TSC090E3 WSC072E3
BAYHTRW409 TSC090E4 WSC072E4
BAYHTRW418 TSC090E4 WSC072E4
BAYHTRW427 TSC090E4 WSC072E4
BAYHTRW436 TSC090E4 WSC072E4
BAYHTRWW18 TSC090EW WSC072EW
BAYHTRWW27 TSC090EW WSC072EW
BAYHTRWW36 TSC090EW WSC072EW
General Information
ACC-SVN67D-EN 5
Page 6
General Information
General
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Installer must mark unit nameplate with Heater Information per instructions on nameplate.
Note: If digit 9 in the unit model number equals "E" (Electro Mechanical Control), accessory relay
Figure 1. Electro Mechanical wiring diagram
BAY24X042 is required if the thermostat does not energize the fan circuit in the heating mode. See Figure 1 for wiring information.
Inspection
1. Unpack all components of the kit.
2. Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company.
3. Check the heater nameplate model number and compare with Tab l e 4 , p . 14 , Table 5, p. 16,
Table 6, p. 17, Table 9, p. 19, or Tab le 10 , p . 1 9. Ensure that the available power supply and unit's
model number complies with the particular heater being used.
6 ACC-SVN67D-EN
Page 7
Installation
Horizontal Supply Cover
Control Box Access Panel
Removable Insulation
Removable Panel
Heat Section Access Panel
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
WARNING
Fire Hazard!
The BAYHTRA, BAYHTRB, BAYHTRD, BAYHTRU, and BAYHTRW heater kits require a one inch clearance from the supply ductwork to any combustible materials. Failure to allow proper clearance could result in combustible materials catching on fire which could result in death, serious injury, or property damage.
1. Remove heater compartment access panel and unit control box access panel. See Figure 2.
Figure 2. Control covers and access panels
Note: On downflow units with or without duct work installed or horizontal units without ductwork
installed, remove horizontal supply cover from the rear of the heater compartment.
2. Remove insulation to expose perimeter of removable panel in the vestibule panel. See Figure 2.
3. Clip or cut the retaining tabs around the perimeter of the removable panel.
4. Remove the panel.
5. Check the opening in the vestibule panel. Remove any metal burrs or slivers that could damage or pinch the heater elements resulting in a short circuit when elements are installed in the opening.
Note: Locator tabs on the vestibule panel support the electric heat assembly and secure the
inward edge of the electric heat accessory control panel. Slits in the insulation should allow the tabs to protrude through the insulation and be visible. However, it may be necessary to work the insulation back from the tabs and slightly bend the tabs outward if difficulty is encountered engaging the electric heater panel or the electric heat accessory control panel.
ACC-SVN67D-EN 7
See Figure 3.
Page 8
Installation
Figure 3. Electric heater element panel
6. The electric heater element assembly has "BOTTOM" stamped in the mounting panel to identify the proper position for mounting.
7. Refer to Ta b le 2 . If the unit/heater combination being installed is the same as any in this table and the application is for horizontal airflow, the limit control TCO-A must be replaced with the extra limit control shipped with the heater. Replace TCO-A following the instructions in steps 8 and 9. If the unit/heater combination being installed does not correspond to any in this table or if the application is for downflow airflow, skip steps 8 and 9 and go on to step 10.
Table 2. TCO-A replaced for Horizontal Duct Configuration
Unit Model Number
TSC120E4**B BAYHTRA427, 436, 454 Right
TSC120EW**B BAYHTRAW36, W54 Right
WSC120EW BAYHTRBW36, W54 Right
THC072E4, WSC090E4 BAYHTRU427, 436 Center
WSC090EW BAYHTRUW27, W36 Center
WSC072E3 BAYHTRW327, 336 Center
TSC090E4, WSC072E4 BAYHTRW427, 436 Center
TSC090EW, WSC072EW BAYHTRWW27, W36 Center
Electric Heater Model
Number
TCO-A
location
8. TCO-A is the limit control located in the center or right part of the heater mounting plate that is located on the bottom of the two heater element assemblies. See Figure 4. To replace this device, first remove the two wires connected to the terminals. Next, remove the two screws which secure it to the heater element mounting plate. Once TCO-A has been removed from the heater element mounting plate, discard this device.
8 ACC-SVN67D-EN
Page 9
Figure 4.
TCO-A LOCATED ON THE RIGHT
TCO-A LOCATED IN THE CENTER
Installation
9. Obtain the replacement TCO-A which is secured with a wire tie near the unit/heater terminal block located on the electric heater control panel. Attach it to the heater element mounting plate with the two screws that were removed in step 8. Connect the two wires that were un-hooked in step 8 to the terminals on the new TCO-A. Refer to the heater package wiring diagram to assure that the wiring is connected properly.
Note: The back of the electric heater element assembly is supported by a factory installed Electric
Heat Support Rod Hanger or other sheet metal device in the unit.
10. Tilt the back of the electric heater element assembly slightly upward as it is positioned in the opening to engage the support rod with the support rod hanger. The BAYHTRA, BAYHTRB, and BAYHTRD models will have a guide rod and a support bracket to help with the installation. See
Figure 5. Be very careful to avoid dragging the heater element on the edges of the opening in
vestibule panel, as this could damage or pinch the heater elements resulting in a short circuit. Engage the bottom edge of heater element panel with the two locator tabs. See Figure 3. BAYHTRB and BAYHTRD kits will have 4 locator tabs along the top, a filler panel to be placed below the heater, and 12 screws to attach the assembly in place. See Figure 6.
ACC-SVN67D-EN 9
Page 10
Installation
GUIDE RODGUIDE ROD
SUPPORT BRACKETSUPPORT BRACKET
Figure 5.
Figure 6.
LOCATOR TABS
SCREWS NOT REQUIRED ALONG THE TOP
SCREWS
SCREWS
FILLER PANEL
11. Secure the electric heater element assembly with the necessary amount of screws.
12. Slide the electric heater control panel/access door assembly inward until the rear edge engages with retaining clips. See Figure 3. For the BAYHTRS, BAYHTRT, BAYHTRU, and BAYHTRW kits, secure the outer edge with 2 screws. The BAYHTRA, BAYHTRB, and BAYHTRD kits will secure the control panel with screws at the top against the vestibule panel and against the indoor divider panel. See Figure 7.
10 ACC-SVN67D-EN
Page 11
Figure 7.
Screws
Installation
13. To install the hinged door stops, loosen one existing screw from the upper left side of the electric heater compartment opening. Position each door stop with outer tab flush against center post and secure each door stop with 1 or 2 screws. See zoom view in Figure 8 or Figure 9.
Figure 8. Single point power
ACC-SVN67D-EN 11
Page 12
Installation
CC1
ROUTE WIRES THROUGH THE HOLE IN THE PANEL
HINGED DOOR STOP
Figure 9.
CC1
ROUTE WIRES THROUGH THE HOLE IN THE PANEL
HINGED DOOR STOP
14. Remove the wire nuts from W1, W2 and W3.
15. For models with the control box in the outdoor section, route the wires through the wire access opening in the divider panel, then up to the unit control box entering through the bottom wire access opening on the left side. See Figure 8. For models with the control box above the heat exchanger section, route the wires through the hole in the panel separating the heater compartment and the control box compartment. See Figure 9. Secure wires to the existing harness.
16. In the unit control box, route the wires along the existing harness to contactor CC1. Secure wires to existing harness.
17. Locate the low voltage wire harness with polarized plug in the electric heater section compartment. Remove the factory installed jumper. Connect the low voltage polarized plug from the unit to the polarized plug on the electric heater assembly.
18. Wire the heater element assembly to the electric heater control panel according to the wiring diagram attached to the electric heater control panel door.
19. Secure the green ground wire from the electric heat control panel to the right hand wall of electric heater compartment with star washer and #10 grounding screw.
20. Wire W1, W2 and W3 wires to CC1 according to the wiring diagram attached to the unit control panel door.
21. Route single point power entry wires through the front access opening of the support panel adjacent to the electric heater section compartment. Using good installation practices, provide strain relief for high voltage wires where necessary. See Figure 8 or Figure 9.
NOTICE
Use only copper conductors!
Unit terminals are not designed to accept any other wiring. Failure to use copper conductors may result in equipment damage.
12 ACC-SVN67D-EN
Page 13
Installation
WARNING
Ground Wire!
All field-installed wiring must be completed by qualified personnel. All field-installed wiring must comply with NEC and applicable local codes. Failure to follow this instruction could result in death or serious injuries.
22. Wire according to the wiring diagram attached to the electric heater control panel door. Ground unit at grounding lug provided on electric heater control panel assembly.
Important: After heater is installed and before applying power, verify that heating elements are
not damaged or pinched and that heating elements are not short circuited to each other or to the heater frame or equipment cabinet by doing the following: Test every heater element with ohmmeter and verify that heater element terminals are electrically isolated from cabinet and ground (infinite resistance). On downflow units with or without duct work installed or horizontal units without ductwork installed, remove horizontal supply cover and carefully inspect elements after installation for damage or proximity to supporting structure or cabinet. At least 1/4” clearance is required around electric heater coils.
Important: Be sure to check tightness of all terminal connections, clamps, screws, etc., as these
may have become loose in shipment. Retighten all electrical connections after equipment has been in operation and components have reached operating temperature.
23. Install the magnets into the door as seen in Figure 8 or Figure 9. Magnets should lock into place once installed. Close electric heater control panel access door, replace heat section access panel and unit control box access panel. Replace horizontal supply cover. Be careful when replacing cover and make sure gasketing is not torn or missing. Gasket must make water tight seal.
24. Scratch out the square on unit nameplate showing heater model installed in unit.
ACC-SVN67D-EN 13
Page 14
Electrical Data
Table 3. Air temperature rise (60 hz)
6 Ton 7 1/2 Ton 7 1/2 Ton 8 1/2 Ton 10 Ton
2000 CFM (2) 3000 CFM 3000 CFM 3400 CFM 4000 CFM
(See Note 2) (See Note 3) (See note 4) (See note 5)
Nominal
kW Input
9.0 1 14.2 14.2 9.5 9.5 9.5 8.4
11.3 1 14.9 14.9 11.9 11.9
16.9 2 22.3 22.3 17.8 17.8 15.7 15.7 13.4 13.4
18.0 1 28.5 28.5 19.0 19.0 19.0 16.7 14.2 14.2
22.6 2 29.8 29.8 23.8 23.8 21.0 7.9 17.9
27.0 2 42.7 42.7 28.5 28.5 28.5 25.1 21.3 21.3
33.80 2 26.7 26.7
36.00 2 56.9 56.9 37.9 37.9 37.9 33.5 28.5 28.5
54.00 2 42.7 42.7
1. The air temperature rise (F) across the heaters is: (Heater kW x 3414)/(1.08 x CFM)
2. The minimum allowable airflow for TSC072E with a 36.0 kW heater is 2200 CFM
3. The minimum allowable airflow for WSC072E with a 36.0 kW heater is 2450 CFM
4. The minimum allowable airflow for a TSC120E***B and THC120E with a 54kW heater is 3400 CFM.
5. The minimum allowable airflow for a WSC120 with a 54kW heater is 4000 CFM.
No. of
Capacity
Stages
TH/SC072E3 TH/SC072E4
TH/SC072EW
WSC072E3 WSC072E4
WSC072EW
TSC090E3 TSC090E4
TSC090EW
WSC090E3 WSC090E4
WSC090EW
TH/SC092E3 TH/SC092E4
TH/SC092EW
TH/SC102E3 TH/SC102E4
TH/SC102EW
TH/SC120E3 TH/SC120E4
TH/SC120EW
Table 4. Unit wiring with electric heat (single point connection) - standard efficiency
WSC120E3 WSC120E4
WSC120EW
Standard Indoor Motor Oversized Indoor Motor
Unit Model
Tons
Number
6 TSC072E3 BAYHTRS309* 6.8/9.0 1 36.5/36.5 50/50 37.8/37.8 60/60
6 TSC072E3 BAYHTRS318* 13.5/18.0 1 53.1/60.4 60/70 54.8/62.0 60/70
6 TSC072E3 BAYHTRS327* 20.3/27.0 2 76.6/87.5 80/90 78.3/89.1 80/90
6 TSC072E3 BAYHTRS336* 27.0/36.0 2 100.1/114.5 110/125 101.8/116.1 110/125
TSC090E3 BAYHTRW309* 6.8/9.0 1 38.2/38.2 60/60 44.0/44.0 60/60
TSC090E3 BAYHTRW318* 13.5/18.0 1 51.4/58.6 60/60 58.6/65.9 60/70
TSC090E3 BAYHTRW327* 20.3/27.0 2 74.9/85.8 80/90 82.1/93.0 90/100
TSC090E3 BAYHTRW336* 27.0/36.0 2 98.4/112.8 100/125 105.6/120.0 110/125
(2)
TSC092E3 BAYHTRT309* 6.8/9.0 1 43.3/43.3 50/50 46.4/46.4 60/60
(2)
TSC092E3 BAYHTRT318* 13.5/18.0 1 54.8/62.0 60/70 58.6/65.9 60/70
(2)
TSC092E3 BAYHTRT327* 20.3/27.0 2 78.3/89.1 80/90 82.1/93.0 90/100
(2)
TSC092E3 BAYHTRT336* 27.0/36.0 2 101.8/116.1 110/125 105.6/120.0 110/125
8.5 TSC102E3 BAYHTRT309* 6.8/9.0 1 46.3/46.3 60/60 49.4/49.4 60/60
8.5 TSC102E3 BAYHTRT318* 13.5/18.0 1 54.8/62.0 60/70 58.6/65.9 60/70
8.5 TSC102E3 BAYHTRT327* 20.3/27.0 2 78.3/89.1 80/90 82.1/93.0 90/100
8.5 TSC102E3 BAYHTRT336* 27.0/36.0 2 101.8/116.1 110/125 105.6/120.0 110/125
10 TSC120E3 BAYHTRA318* 13.5/18.0 1 57.5/64.8 60/70 —/— —/—
10 TSC120E3 BAYHTRA327* 20.3/27.0 2 81.0/91.9 90/100 —/— —/—
10 TSC120E3 BAYHTRA336* 27.0/36.0 2 104.5/118.9 110/125 —/— —/—
10 TSC120E3 BAYHTRA354* 40.6/54.0 2 151.4/140.5 175/150 —/— —/—
Heater Model
Number
Heater kW
Rating
(1)
208-230 Volts three phase voltage
Control
Stages MCA
Max Circuit
Breaker MCA
Max Fuse Size or
Max Fuse Size or
Max Circuit
Breaker
14 ACC-SVN67D-EN
Page 15
Electrical Data
Table 4. Unit wiring with electric heat (single point connection) - standard efficiency (continued)
Standard Indoor Motor Oversized Indoor Motor
Max Fuse Size or
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
(1)
Control
Stages MCA
Max Circuit
Breaker MCA
480 Volts Three Phase
6 TSC072E4 BAYHTRS409* 9.0 1 18.2 25 18.8 25
6 TSC072E4 BAYHTRS418* 18.0 1 30.3 35 31.0 35
6 TSC072E4 BAYHTRS427* 27.0 2 43.8 45 44.5 45
6 TSC072E4 BAYHTRS436* 36.0 2 57.3 60 58.0 60
TSC090E4 BAYHTRW409* 9.0 1 19.5 30 22.4 35
TSC090E4 BAYHTRW418* 18.0 1 29.3 30 32.9 35
TSC090E4 BAYHTRW427* 27.0 2 42.8 45 46.4 50
TSC090E4 BAYHTRW436* 36.0 2 56.3 60 59.9 60
(2)
TSC092E4 BAYHTRT409* 9.0 1 21.5 25 23.0 30
(2)
TSC092E4 BAYHTRT418* 18.0 1 31.0 35 32.9 35
(2)
TSC092E4 BAYHTRT427* 27.0 2 44.5 45 46.4 50
(2)
TSC092E4 BAYHTRT436* 36.0 2 58.0 60 59.9 60
TSC102E4 BAYHTRT409* 9.0 1 21.9 25 23.4 30
TSC102E4 BAYHTRT418* 18.0 1 31.0 35 32.9 35
TSC102E4 BAYHTRT427* 27.0 2 44.5 45 46.4 50
TSC102E4 BAYHTRT436* 36.0 2 58.0 60 59.9 60
10 TSC120E4 BAYHTRA418* 18.0 1 32.5 35
10 TSC120E4 BAYHTRA427* 27.0 2 46.0 50
10 TSC120E4 BAYHTRA436* 36.0 2 59.5 60
10 TSC120E4 BAYHTRA454* 54.0 2 70.4 80
575 Volts Three Phase
6 TSC072EW BAYHTRSW09* 9.0 1 13.0 20 14.0 20
6 TSC072EW BAYHTRSW18* 18.0 1 23.8 25 24.8 25
6 TSC072EW BAYHTRSW27* 27.0 2 34.6 35 35.6 40
6 TSC072EW BAYHTRSW36* 36.0 2 45.4 50 46.4 50
TSC090EW BAYHTRWW18* 18.0 1 23.4 25
TSC090EW BAYHTRWW27* 27.0 2 34.3 35
TSC090EW BAYHTRWW36* 36.0 2 45.0 45
(2)
(1) No optional motors available for 3-5 tons. The standard motor for 1-phase models is a Multispeed, Direct Drive Motor. The Standard Motor for the 3-
(2) Dual refrigeration system.
TSC092EW BAYHTRTW18* 18.0 1 24.8 25 26.3 30
(2)
TSC092EW BAYHTRTW27* 27.0 2 35.6 40 37.1 40
(2)
TSC092EW BAYHTRTW36* 36.0 2 46.4 50 47.9 50
TSC102EW BAYHTRTW18* 18.0 1 24.8 25 26.3 30
TSC102EW BAYHTRTW27* 27.0 2 35.6 40 37.1 40
TSC102EW BAYHTRTW36* 36.0 2 46.4 50 47.9 50
10 TSC120EW BAYHTRAW18* 18.0 1 27.0 30
10 TSC120EW BAYHTRAW36* 36.0 2 48.6 50
10 TSC120EW BAYHTRAW54* 54.0 2 57.4 60
phase models is a Belt Drive Motor.
Max Fuse Size or
Max Circuit
Breaker
ACC-SVN67D-EN 15
Page 16
Electrical Data
Table 5. Unit wiring with electric heat - heat pump - (single point connection) - standard efficiency
Standard Indoor Motor Oversized Indoor Motor
Max Fuse Size or
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
Control
Stages MCA
Max Circuit
Breaker MCA
208/230 Volts Three Phase
6 WSC072E3 BAYHTRW309A 6.8/9.0 1 59.8/63.4 70/80 61.1/64.7 70/80
6 WSC072E3 BAYHTRW318A 13.5/18.0 1 83.2/90.4 90/100 84.5/91.7 90/100
6 WSC072E3 BAYHTRW327A 20.3/27.0 2 106.7/117.6 110/125 108.0/118.9 110/125
6 WSC072E3 BAYHTRW336A 27.0/36.0 2 130.2/144.6 150/150 131.5/145.9 150/150
WSC090E3 BAYHTRU309A 6.8/9.0 1 61.9/65.5 80/80 67.7/71.3 80/90
WSC090E3 BAYHTRU318A 13.5/18.0 1 85.2/92.5 100/100 91.0/98.3 100/100
WSC090E3 BAYHTRU327A 20.3/27.0 2 108.7/119.6 110/125 114.5/125.4 125/150
WSC090E3 BAYHTRU336A 27.0/36.0 2 132.2/146.6 150/150 138.0/152.4 150/175
10 WSC120E3 BAYHTRB318A 13.5/18.0 1 98.8/106.1 100/110 —/— —/—
10 WSC120E3 BAYHTRB327A 20.3/27.0 2 122.3/133.2 125/150 —/— —/—
10 WSC120E3 BAYHTRB336A 27.0/36.0 2 145.8/160.2 150/175 —/— —/—
10 WSC120E3 BAYHTRB354A 40.6/54.0 2 192.7/181.8 200/200 —/— —/—
480 Volts Three Phase
6 WSC072E4 BAYHTRW409A 9.0 1 33.8 40 34.4 40
6 WSC072E4 BAYHTRW418A 18.0 1 47.4 50 48.0 50
6 WSC072E4 BAYHTRW427A 27.0 2 60.9 70 61.5 70
6 WSC072E4 BAYHTRW436A 36.0 2 74.4 80 75.0 80
WSC090E4 BAYHTRU409A 9.0 1 32.5 40 35.4 40
WSC090E4 BAYHTRU418A 18.0 1 46.1 50 49.0 50
WSC090E4 BAYHTRU427A 27.0 2 59.6 60 62.5 70
WSC090E4 BAYHTRU436A 36.0 2 73.1 80 76.0 80
10 WSC120E4 BAYHTRB418A 18.0 1 53.2 60
10 WSC120E4 BAYHTRB427A 27.0 2 66.7 70
10 WSC120E4 BAYHTRB436A 36.0 2 80.2 90
10 WSC120E4 BAYHTRB454A 54.0 2 91.1 100
575 Volts Three Phase
6 WSC072EW BAYHTRWW18A 18.0 1 34.0 35 34.9 35
6 WSC072EW BAYHTRWW27A 27.0 2 44.9 45 45.8 50
6 WSC072EW BAYHTRWW36A 36.0 2 55.6 60 56.5 60
WSC090EW BAYHTRUW18A 18.0 1 36.1 40 38.1 40
WSC090EW BAYHTRUW27A 27.0 2 47.0 50 49.0 50
WSC090EW BAYHTRUW36A 36.0 2 57.7 60 59.7 60
10 WSC120EW BAYHTRBW18A 18.0 1 42.7 45
10 WSC120EW BAYHTRBW36A 36.0 2 64.4 70
10 WSC120EW BAYHTRBW54A 54.0 2 73.1 80
Max Fuse Size or
Max Circuit
Breaker
16 ACC-SVN67D-EN
Page 17
Table 6. Unit wiring with electric heat (single point connection) - high efficiency - 6-10 tons
Electrical Data
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
(1)
Control
Stages MCA
Standard
Indoor Motor
Max Fuse Size or Max Circuit
Breaker MCA
Oversize
Indoor Motor
Max Fuse Size or Max Circuit
208/230 Volts Three Phase
6 THC072E3 BAYHTRU309A 6.8/9.0 1 33.9/33.9 50/50 35.2/35.2 50/50
6 THC072E3 BAYHTRU318A 13.5/18.0 1 53.1/60.4 60/70 54.8/62.0 70/60
6 THC072E3 BAYHTRU327A 20.3/27.0 2 76.6/87.5 80/90 78.3/89.1 90/80
6 THC072E3 BAYHTRU336A 27.0/36.0 2 100.1/114.5 110/125 101.8/116.1 125/110
THC092E3 BAYHTRD309A 6.8/9.0 1 42.7/42.7 50/50 —/— —/—
THC092E3 BAYHTRD318A 13.5/18.0 1 57.5/64.8 60/70 —/— —/—
THC092E3 BAYHTRD327A 20.3/27.0 2 81.0/91.9 90/100 —/— —/—
THC092E3 BAYHTRD336A 27.0/36.0 2 104.5/118.9 110/125 —/— —/—
THC102E3 BAYHTRD309A 6.8/9.0 1 44.7/44.7 60/60 —/— —/—
THC102E3 BAYHTRD318A 13.5/18.0 1 57.5/64.8 60/70 —/— —/—
THC102E3 BAYHTRD327A 20.3/27.0 2 81.0/91.9 90/100 —/— —/—
THC102E3 BAYHTRD336A 27.0/36.0 2 104.5/118.9 110/125 —/— —/—
10 THC120E3 BAYHTRD318A 13.5/18.0 1 57.5/64.8 60/70 —/— —/—
10 THC120E3 BAYHTRD327A 20.3/27.0 2 81.0/91.9 90/100 —/— —/—
10 THC120E3 BAYHTRD336A 27.0/36.0 2 104.5/118.9 110/125 —/— —/—
10 THC120E3 BAYHTRD354A 40.6/54.0 2 151.4/140.5 175/150 —/— —/—
460 Volts Three Phase
6 THC072E4 BAYHTRU409A 9.0 1 16.6 25 17.4 25
6 THC072E4 BAYHTRU418A 18.0 1 30.3 35 31.0 35
6 THC072E4 BAYHTRU427A 27.0 2 43.8 45 44.5 45
6 THC072E4 BAYHTRU436A 36.0 2 57.3 60 58.0 60
7½2 THC092E4 BAYHTRD409A 9.0 1 19.8 25
THC092E4 BAYHTRD418A 18.0 1 32.5 35
THC092E4 BAYHTRD427A 27.0 2 46.0 50
THC092E4 BAYHTRD436A 36.0 2 59.5 60
THC102E4 BAYHTRD409A 9.0 1 22.9 30
THC102E4 BAYHTRD418A 18.0 1 32.5 35
THC102E4 BAYHTRD427A 27.0 2 46.0 50
THC102E4 BAYHTRD436A 36.0 2 59.5 60
10 THC120E4 BAYHTRD418A 18.0 1 32.5 35
10 THC120E4 BAYHTRD427A 27.0 2 46.0 50
10 THC120E4 BAYHTRD436A 36.0 2 59.5 60
10 THC120E4 BAYHTRD454A 54.0 2 70.4 80
(1) Heater kW ratings are at 208/240V for 208/230V units, 480V for 460V units.
Breaker
ACC-SVN67D-EN 17
Page 18
Electrical Data
Table 7. Air temperature rise 380/415 Volt (50 hz)
(Degrees C)
7
(Degrees F)
6 Ton 7.5 Ton 10 Ton 6 Ton 7.5 Ton 10 Ton
4100
M3/H
5100
M3/H
6800
M3/H
WSC072EDWSC090EDWSC120
kW Voltage Stages
11.3 380-415/50/3 1 8.3 6.6 --- 11.3 380-415/50/3 1 14.9 11.9 ---
12.5 380-415/50/3 1 9.1 7.3 --- 12.5 380-415/50/3 1 16.5 13.2 ---
13.5 380-415/50/3 1 9.9 7.9 --- 13.5 380-415/50/3 1 17.8 14.2 ---
16.9 380-415/50/3 2 12.4 9.9 7.4 16.9 380-415/50/3 2 22.3 17.8 13.4
18.8 380-415/50/3 2 13.8 11.0 8.3 18.8 380-415/50/3 2 24.8 19.8 14.9
20.2 380-415/50/3 2 14.8 11.8 8.9 20.2 380-415/50/3 2 26.6 21.3 16.0
22.6 380-415/50/3 2 16.5 13.2 9.9 22.6 380-415/50/3 2 29.8 23.8 17.9
25.0 380-415/50/3 2 18.3 14.6 11.0 25.0 380-415/50/3 2 32.9 26.3 19.8
26.9 380-415/50/3 2 19.7 15.7 11.8 26.9 380-415/50/3 2 35.4 28.3 21.3
33.9 380-415/50/3 2 --- --- 14.9 33.9 380-415/50/3 2 --- --- 26.8
37.5 380-415/50/3 2 --- --- 16.5 37.5 380-415/50/3 2 --- --- 29.6
40.4 380-415/50/3 2 --- --- 17.7 40.4 380-415/50/3 2 --- --- 31.9
6. For minimum design airflow, see performance table for each unit.
7. To calculate the temperature rise in Celsius at different airflow, use the following formula: Temperature rise (C) across electric heater = (kW x 2985)/
(M3 / H).
8. To calculate the temperature rise in Fahrenheit at different airflow, use the following formula: Temperature rise (F) across electric heater = (kW x 3414)/ (1.08 / H).
ED kW Voltage Stages
8
2400CFM3000CFM4000CF
M
WSC072 EDWSC090EDWSC120
ED
Table 8. Air temperature rise 380/415 Volt (50 hz)
(Degrees C)
Kw Voltage Stages
11.3 /
13.5
16.9 /
20.2
22.6 /
26.9
33.8 /
40.4
9. For minimum design airflow, see performance table for each unit.
10.To calculate the temperature rise in Celsius at different airflow, use the following formula: Temperature rise (C) across electric
heater = (kW x 2985)/(M3 / H).
11.To calculate the temperature rise in Fahrenheit at different airflow, use the following formula: Temperature rise (F) across electric heater = (kW x 3414)/(1.08 / H).
10
380-
415/50/3
380-
415/50/3
380-
415/50/3
380-
415/50/3
6 Ton
4100
3
M
TSC07
2ED
8.3 /
1
2
2
2 --- --- ---
9.9
12.4 /
14.8
16.5 /
19.7
/ H
Ton
5100
M3 / H
TSC09
0ED
6.6 /
7.9
9.9 /
11.8
13.2 /
15.7
7.5
8.5
Ton 10 Ton 6 Ton 7.5 Ton 8.5 Ton 10 Ton
5800
M3 / H
TSC10
2ED
--- ---
8.7 /
10.4
11.7 /
13.9
(Degrees F)
6800
M3 / H
TSC12
0ED KW Voltage Stages
11.3 /
13.5
7.4 /
8.9
9.9 /
11.8
14.8 /
17.7
16.9 /
20.2
22.6 /
26.9
33.8 /
40.4
11
380-
415/50/3
380-
415/50/3
380-
415/50/3
380-
415/50/3
2400CFM3000CFM3400CFM4000CF
TSC072EDTSC090EDTSC102EDTSC120
1
2
2
2 --- --- ---
14.9 /
17.8
22.3 /
26.6
29.8 /
35.4
11.9 /
14.2
17.8 /
21.3
23.8 /
28.3
--- ---
15.7 /
18.8
21.0 /
25.0
M
ED
13.4 /
16.0
17.9 /
21.3
26.7 /
31.9
18 ACC-SVN67D-EN
Page 19
Table 9. Cooling only units with electric heater — single power source — 380/415 Volt (50hz)
Standard Indoor Fan Motor Oversized Indoor Fan Motor
Maximum
Fuse Size Or
Maximum
Circuit
Breaker
Minimum
Circuit
Ampacity
Unit
Model No.
Heater Model
No.
Heater12
kW Rating
380/415 Volts Three Phase
BAYHTRS418 11.3 / 13.5 39 / 47 1 26.9 / 28.9 35 / 35 28.1 / 30.1 35 / 35
TSC072ED
TSC090ED
TSC102ED
TSC120ED
12.kW and MBH shown for 380V / 415V
BAYHTRS427 16.9 / 20.2 58 / 69 2 37.5 / 40.5 40 / 45 38.8 / 41.8 40 / 45
BAYHTRS436 22.6 / 26.9 78 / 92 2 48.3 / 52.1 50 / 60 49.5 / 53.4 50 / 60
BAYHTRS418 11.3 / 13.5 39 / 47 1 28.1 / 30.1 35 / 35 30.3 / 32.3 35 / 35
BAYHTRS427 16.9 / 20.2 58 / 69 2 38.8 / 41.8 40 / 45 40.9 / 43.9 45 / 45
BAYHTRS436 22.6 / 26.9 78 / 92 2 49.5 / 53.4 50 / 60 51.6 / 55.5 60 / 60
BAYHTRT427 16.9 / 20.2 58 / 69 2 38.8 / 41.8 40 / 45 40.9 / 43.9 45 / 45
BAYHTRT436 22.6 / 26.9 78 / 92 2 49.5 / 53.4 50 / 60 51.6 / 55.5 60 / 60
BAYHTRT427 16.9 / 20.2 58 / 69 2 40.9 / 43.9 45 / 45 40.9 / 43.9 45 / 45
BAYHTRT436 22.6 / 26.9 78 / 92 2 51.6 / 55.5 60 / 60 51.6 / 55.5 60 / 60
BAYHTRT454 33.8 / 40.4 116 / 138 2 73.1 / 79.0 80 / 80 73.1 / 79.0 80 / 80
Heater12
MBH
Control
Stages
Minimum
Circuit
Ampacity
Electrical Data
Maximum
Fuse Size Or
Maximum
Circuit
Breaker
Table 10. Heat pump units with electric heater — single power source — 380/415 Volt (50hz)
Standard Indoor Fan Motor Oversized Indoor Fan Motor
Maximum
Fuse Size Or
Maximum
Circuit
Breaker
Minimum
Ampacity
Unit Model
No.
Heater Model
No.
kW Rating
380/415 Volts Three Phase
BAYHTRS418 11.3/13.5 39/47 1 43.4/45.4 50/50 44.4/46.4 50/50
WSC072ED
WSC090ED
WSC120ED
13.kW and MBH shown for 380V / 415V
BAYHTRS427 16.9/20.2 58/69 2 54.1/57.1 60/60 55.1/58.1 60/60
BAYHTRS436 22.6/26.9 78/92 2 64.8/68.7 70/70 65.8/69.7 70/70
BAYHTRS418 11.3/13.5 39/47 1 46.3/48.3 50/50 48.0/50.0 50/50
BAYHTRS427 16.9/20.2 58/69 2 56.9/59.9 60/60 58.6/61.6 60/60
BAYHTRS436 22.6/26.9 78/92 2 67.7/71.6 70/70 69.4/73.3 70/70
BAYHTRT427 16.9/20.2 58/69 2 63.3/66.3 70/70 - -
BAYHTRT436 22.6/26.9 78/92 2 74.0/77.9 80/80 - -
BAYHTRT454 33.9/40.4 116/138 2 95.5/101.4 100/110 - -
Heater13
Heater13
MBH
Control
Stages
Minimum
Circuit
Ampacity
Circuit
Maximum
Fuse Size Or
Maximum
Circuit
Breaker
ACC-SVN67D-EN 19
Page 20
Literature Order Number ACC-SVN67D-EN
Date November 2009
Supersedes ACC-SVN67D-EN (August 2009)
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this literature.
Loading...