The Trane Company believes that it is incumbent on manufacturers to serve the
industry by regularly disseminating information gathered through laboratory
research, testing programs, and field experience.
The Trane Air Conditioning Clinic series is one means of knowledge sharing.
It is intended to acquaint a nontechnical audience with various fundamental
aspects of heating, ventilating, and air conditioning. We have taken special
care to make the clinic as uncommercial and straightforward as possible.
Illustrations of Trane products only appear in cases where they help convey the
message contained in the accompanying text.
This particular clinic introduces the concept of variable air volume or “VAV” systems.
A variable-air-volume (VAV) air-conditioning system varies the volume of
constant-temperature air that is supplied to meet the changing load conditions
of the space.
Constant-Volume,
Variable-Temperature System
cooling
supply
supply
fan
fan
SA
thermostat
thermostat
For the purpose of comparison, we will look at a traditional constant-volume
(CV), variable-air-temperature system.
This system delivers a constant volume of air to the space and, to maintain the
required space temperature at all load conditions, varies the temperature of this
air. In this example, the temperature of the air is varied by controlling the
capacity of the central cooling coil.
cooling
coil
coil
space
OA
RA
Figure 3
TRG-TRC014-EN1
notes
period one
What Is Variable Air Volume?
Constant Volume–Full Load
Supply
Airflow
Supply
Airflow
Supply
Airflow
This equation describes the performance of a constant-volume, variabletemperature system at various load conditions.
Supply Airflow (cfm)
With these design conditions:
space sensible heat gain = 40,000 Btu/hr [11,724 W]
space dry-bulb (DB) temperature = 75°F [23.9°C]
supply air dry-bulb (DB) temperature = 55°F [12.8°C]
constant = 1.085 [1,210]
the system balances the load with 1,840 cfm [0.87 m
supply air.
Rearranging the equation and using the constant supply airflow of 1,840 cfm
[0.87 m
Btu/hr [5,862 W] space sensible load is:
Therefore, as the space sensible load drops from 40,000 Btu/hr to 20,000 Btu/hr
[11,724 W to 5,862 W], this system modulates the temperature of the constant
1,840 cfm [0.87 m
Removing less energy from the air takes less energy from the central system.
Therefore, with this particular system, refrigeration energy savings are realized
at part load conditions, although control of space humidity levels suffers due to
the warmer supply air condition.
3
/s], the supply air temperature required to balance a lesser 20,000
Supply DBSpace DB
Supply DB75° F
Supply DB23.9°C
Space
=
DB
75°F –
=
23.9°C –
=
1.085 × 1,840 cfm
3
/s] supply air from 55°F to 65°F [12.8°C to 18.3°C].
However, because this type of system can respond to the demands of only one
thermostat, it can serve only those building spaces with similar cooling
requirements. If a building has many spaces with diverse cooling needs, each
must be served by its own system.
I’m
I’m
fine.
fine.
I’m
I’m
freezing!
freezing!
Figure 6
Constant Volume–Multiple Spaces
80°F
80°F
[26.7°C]
[26.7°C]
55°F
55°F
[12.8°C]
[12.8°C]
air mixing
air mixingair mixing
65°F
65°F
[18.3°C]
[18.3°C]
65°F
55°F
55°F
[12.8°C]
[12.8°C]
reheat coil
reheat coilreheat coil
Other constant-volume system designs can serve the cooling requirements of
more than one space with a central fan and cooling coil. However, to do so, the
cool primary air must be either reheated or mixed with warm air to produce the
supply temperatures needed to balance the various space cooling loads.
4TRG-TRC014-EN
65°F
[18.3°C]
[18.3°C]
Figure 7
notes
period one
What Is Variable Air Volume?
Terminal Reheat System
EA
supply
cooling
cooling
coil
coil
thermostat
thermostat
supply
fan
fan
OA
The terminal reheat system uses a central air handler and cooling coil to deliver
cool primary air to all the spaces. Each space has its own heating coil to temper
the air to satisfy the space load. Of course, any heat added to meet the part-load
requirements of a space becomes a cooling load that the refrigeration system
must overcome. This can result in a nearly constant refrigeration load, even
when the building is at part-load conditions.
Therefore, reheating cooled air to achieve part-load supply air temperature
control is not very energy efficient and is used only in special constant-volume
applications, or when there is a “free” source of heat (i.e., heat recovery).
Primary air (PA) is the air delivered by a central supply fan to a terminal unit.
Supply air (SA) is the air delivered to a space.
PA
SA
RA
reheat
reheat
coil
coil
Figure 8
TRG-TRC014-EN5
notes
period one
What Is Variable Air Volume?
Variable-Air-Volume (VAV) System
EA
supply
cooling
cooling
coil
coil
supply
fan
fan
variable--
variable
speed drive
speed drive
thermostat
thermostat
OA
In contrast, a variable-air-volume (VAV) system delivers the primary air at a
constant temperature and varies the airflow to maintain the required space
temperature at all load conditions.
PA
VAV
VAV
box
box
SA
RA
Figure 9
VAV–Full Load
Supply
Airflow
40,000 Btu/hr
=
1.085 × (75°F – 55°F)
1,840 cfm
=
Supply
Airflow
Similar to the constant-volume system, at design conditions the VAV system
will balance the same 40,000 Btu/hr [11,724 W] space sensible load with the
same 1,840 cfm [0.87 m
6TRG-TRC014-EN
=
1,210 × (23.9°C – 12.8°C)
11,724 W
3
/s] of 55°F [12.8°C] supply air.
0.87 m3/s
=
Figure 10
notes
period one
What Is Variable Air Volume?
VAV–Part Load
Supply
Airflow
Supply
Airflow
However, at part load, the VAV system produces a balance by modulating the
volume of constant 55°F [12.8°C] supply air.
In this example, the air volume required to balance the lesser 20,000 Btu/hr
[5,862 W] space sensible load is:
Supply Airflow
Supply Airflow
That is, 920 cfm [0.43 m3/s] of 55°F [12.8°C] supply air.
One reason to use a VAV system is the potential for part-load energy savings.
The part-load energy savings inherent with the VAV system are twofold. First,
TRG-TRC014-EN7
period one
What Is Variable Air Volume?
notes
the air volume reduction creates an opportunity to reduce the fan energy
required to move this air. The amount of energy saved depends on the method
used to modulate the capacity of the fan (to be discussed in Period Four).
Second, the reduced airflow across the cooling coil causes the refrigeration
system to throttle back in order to stabilize the primary air temperature. In turn,
this results in a reduction in refrigeration energy compared to full load.
Why VAV? Comfort
▲ Dedicated terminal units
I’m
▲ Dedicated thermostats
It’s nice
It’s nice
in here!
in here!
I’m
I’m
fine.
fine.
Another reason for VAV is to cost-effectively provide improved comfort. A VAV
system is capable of controlling space temperature in many spaces with
dissimilar cooling and heating requirements, while using only one central air
handling unit (AHU). This is accomplished by providing one VAV terminal unit
and thermostat for each independently controlled space. When the sun is
beating against the west side of the building in the late afternoon, a VAV system
can provide an increased amount of cool supply air to keep the spaces on the
west exposure comfortable, while throttling back the airflow to the spaces on
the east exposure so as not to overcool them.
I’m
quite
quite
cozy.
cozy.
Ahhh!
Ahhh!
Figure 13
8TRG-TRC014-EN
notes
period one
What Is Variable Air Volume?
System Comparison
constant--
constant
single zone
single zone
◆
◆
◆
◆
◆
◆
volume,
volume,
Constant fan
Constant fan
energy
energy
Refrigeration
Refrigeration
energy
energy
savings
savings
Delivers comfort
Delivers comfort
to only one
to only one
thermal zone
thermal zone
constant--
constant
terminal reheat
terminal reheat
◆
◆
◆
◆
◆
◆
◆
◆
volume,
volume,
Constant fan
Constant fan
energy
energy
Nearly constant
Nearly constant
refrigeration
refrigeration
energy
energy
Delivers comfort
Delivers comfort
to many spaces
to many spaces
inefficiently
inefficiently
Reheat energy
Reheat energy
increases at part
increases at part
load
load
VAV
VAV
Fan energy
◆
◆
Fan energy
savings
savings
Refrigeration
◆
◆
Refrigeration
energy
energy
savings
savings
Delivers comfort
◆
◆
Delivers comfort
to many spaces
to many spaces
efficiently
efficiently
Figure 14
Contrasting the three systems discussed in this example, the simple, constantvolume, variable-temperature system consumes constant fan energy while
providing refrigeration energy savings at part load. However, it can only deliver
comfort to spaces with similar loads.
The terminal reheat system can serve many spaces with dissimilar load
requirements, but consumes constant fan energy and nearly constant
refrigeration energy at part load. It also uses an increasing amount of reheat
energy at part load.
On the other hand, the variable-air-volume system is capable of providing both
fan and refrigeration energy savings at part load, making it the most energy
efficient of these three systems. In addition, the VAV system can efficiently
serve many spaces with dissimilar cooling and heating load requirements.
TRG-TRC014-EN9
notes
period one
What Is Variable Air Volume?
VAV Building Characteristics
▲ Variable thermal load profiles
▲ Multiple, independently-controlled spaces
▲ Common return air path
Figure 15
There are some basic building characteristics that favor the application of VAV
systems. We will discuss three:
n Variable thermal load profiles in the spaces.
n The need for multiple, independently-controlled spaces.
n The existence of a common return air path.
Variable Thermal Load Profiles
east--
facing
east
100
100
75
75
50
50
25
25
percent space loadpercent space load
A key feature of a VAV system is its ability to realize both fan and refrigeration
energy savings at part-load conditions. A building with construction and
utilization characteristics that cause the thermal load profiles of the spaces to
vary throughout the day and year is an excellent application for a VAV system.
facing
space
space
0
0
6126
6126
a.m.
a.m.
noon
noon
west--
west
space
space
p.m.
p.m.
facing
facing
Figure 16
The fact that the west-facing space in this example has a very different load
profile than the east-facing space allows the VAV system to take advantage of
this energy savings at all hours of the day.
10TRG-TRC014-EN
notes
period one
What Is Variable Air Volume?
Independent Space Control
▲ Dedicated terminal units
▲ Dedicated thermostats
Figure 17
Another feature of the VAV system is the ability to efficiently satisfy the comfort
requirements of many different spaces within the building. As we saw from the
comparison of the VAV and terminal reheat systems, the VAV system is the
most efficient at performing this task.
Common Return Air Path
Space 1
Space 1
Because the VAV system uses one central cooling coil and fan to serve many
spaces, the need for a common path to allow the air to return from these spaces
is significant. A return air plenum is commonly used. If return ductwork is
required to connect each conditioned space to the central air handling unit, the
system becomes more difficult to balance and control.
Space 2
Space 2
Space 3
Space 3
Figure 18
TRG-TRC014-EN11
notes
period two
Components of a VAV System
VAV Systems
period two
Components of a VAV System
Figure 19
Next, we will examine the individual components that compose a VAV system.
Components of a VAV System
return air path
return air path
relief
relief
fan
fan
supply
VAV
VAV
box
box
supply
ductwork
ductwork
Figure 20
supply
supply
fan
fan
central
central
air handler
air handler
thermostat
thermostat
A simple VAV system includes the following:
n Central air handler with a variable-volume supply fan, a cooling coil,
possibly a heating coil, controls, filters, a mixing box, and a return or relief
fan
n Supply duct
n VAV terminal unit, or “box,” with a thermostat and supply diffusers for each
independently controlled space
n Thermostat and unit controller for each terminal unit
n Return plenum or duct
The VAV terminal units modulate the airflow supplied to each space.
12TRG-TRC014-EN
notes
period two
Components of a VAV System
VAV Terminal Units
primary
primary
air
air
controller
controller
VAV Terminal Units
A VAV terminal unit is a sheet-metal assembly installed upstream of its
respective space diffusers. The unit consists of an air-modulation device,
control hardware and, depending on the system application, possibly a heating
coil, a filter, and a small terminal mixing fan. Modulating the airflow to each
individual space is accomplished using a temperature-controlled mechanical
device that varies the airflow resistance in the supply duct to that space. The
rotating blade damper changes airflow resistance by rotating the damper
into the air stream, restricting the size of the air passage to the space. It is very
cost-effective and flexible. Typically, either a pneumatic or electric controller
can be used to adjust the damper. An understanding of the common VAV
terminal unit types is important to understanding VAV systems.
▲ Heating coil
▲ Filter
▲ Mixing fan
airflow
airflow
modulation
modulation
device
device
supply
supply
air
air
Figure 21
TRG-TRC014-EN13
notes
period two
Components of a VAV System
Single Duct, Cooling Only
primary
primary
air
air
supply
supply
air
air
The simplest of all VAV terminal units is the single-duct, cooling-only
terminal unit. It consists of an airflow modulation device with controls
packaged in a sheet-metal enclosure. The unit can only modulate the primary
airflow to the space. The primary air is supplied by a single, central air handler.
This VAV terminal unit is typically used for those zones that require year-round
cooling, like the interior zones of a building. It is the most common and basic
type of single-duct VAV terminal unit.
Figure 22
Single Duct, Cooling Only
remote source of heat
100%
% airflow to space
0%
heating load
remote source of heat
design
heatingtempering
heating
space load
tempering
primary air
primary air
This graph indicates how the air supplied to the space by the terminal unit
varies as the space loads change. The vertical axis indicates the total airflow
supplied to the space. The horizontal axis indicates the space load.
The supply airflow to the space is reduced as the cooling load in the space
decreases. Responding to the space thermostat, the primary airflow is
modulated between maximum and minimum settings. The maximum setting is
14TRG-TRC014-EN
maximum
primary
airflow
minimum
primary
airflow
design
cooling load
Figure 23
period two
Components of a VAV System
notes
determined by the design cooling load of the space and the minimum setting is
normally determined by the space ventilation requirement or minimum airflow
for proper diffuser selection.
Most cooling-only units are applied to spaces that have no need for heat. These
units would operate in the region on the right-hand portion of this chart,
modulating between design and minimum primary airflow. When cooling-only
units are applied to spaces that do have heating requirements, the heat is
provided by a remote source such as finned radiation along the wall. In these
spaces, when the cooling load drops below the minimum airflow setting for the
unit, overcooling the space, the remote heat source activates. When space
heating is required, the remote heat source satisfies the space heating load.
Most terminal unit controllers provide an output signal to control this remote
source of heat.
Space Heating with a VAV System
terminal
terminal
mixing fan
mixing fan
plenum air
plenum air
remote
heating
heating
coil
coil
In addition to controlling this remote source of heat (perimeter baseboard
radiation, in this example), single-duct VAV terminal units can directly provide
heat to a space. This can be accomplished by adding a heating coil to each
cooling-only unit or by mixing the primary air with warm plenum air before it is
delivered to the space.
TRG-TRC014-EN15
remote
heat source
heat source
Figure 24
notes
period two
Components of a VAV System
VAV Reheat
primary
primary
air
air
terminal
terminal
heating coil
heating coil
supply
supply
air
air
VAV r e heat terminal units provide supply-air tempering or space heating by
reheating the cool primary air. This is accomplished by adding an electric, or
hot-water, heating coil to the discharge of a cooling-only unit.
Figure 25
The VAV reheat terminal unit is typically used for those zones that require
seasonal cooling and heating, such as exterior zones of a building.
VAV Reheat
heating coil active
design
heating coil active
heatingtempering
heating
space load
tempering
primary air
primary air
100%
% airflow to space
0%
heating load
In the cooling mode, the unit is controlled in the same manner as the coolingonly unit. The supply airflow is reduced as the cooling load in the space
decreases. When the space cooling load drops below the minimum primary
airflow setting for the unit, overcooling the space, the heating coil warms
(tempers) the primary air to balance the low space cooling load. When space
heating is required, the heating coil further warms the primary air to satisfy the
space heating load.
maximum
primary
airflow
minimum
heating
airflow
minimum
cooling
airflow
design
cooling load
Figure 26
16TRG-TRC014-EN
period two
Components of a VAV System
notes
During the heating mode, the primary airflow must often be greater than the
minimum setting of the unit for the cooling mode. When warm, buoyant air is
supplied from the ceiling, a certain velocity is required to effectively deliver
it down to the occupied portion of the space. Increased airflow may also be
needed to meet the minimum requirement for proper operation of the
heating coil.
VAV reheat is more efficient than the constant-volume reheat system discussed
earlier because heat is provided at reduced airflow and only when required.
Fan-Powered Terminal Units
warm
warm
plenum air
plenum air
cool
cool
primary air
primary air
parallel
series
Figure 27
Another method that a single-duct VAV terminal unit can employ to heat a
space is to mix warm plenum air with cool primary air. Because this method
uses a small fan to draw warm air from the plenum and mix it with the primary
air, they are called fan-powered terminal units.
They come in two configurations, parallel and series.
TRG-TRC014-EN17
notes
period two
Components of a VAV System
Parallel, Fan-Powered
plenum
plenum
air
air
primary
primary
air
air
A parallel, fan-powered terminal unit consists of a primary airflow
modulation device and a small, integral, constant-volume fan packaged to
provide parallel airflow paths.
supply
supply
air
air
terminal
terminal
mixing fan
mixing fan
Figure 28
Parallel, Fan-Powered
design
cooling load
maximum
primary
airflow
minimum
primary
airflow
Figure 29
100%
% airflow to space
0%
design
heating load
heating
heating
plenum air
plenum air
space load
tempering
tempering
primary air
primary air
In the cooling mode, the unit is controlled in the same manner as the coolingonly unit. Primary airflow is reduced as the cooling load in the space decreases.
When the space cooling load drops below the minimum primary airflow setting
for the unit, overcooling the space, the small fan activates to mix warm plenum
air with the cool primary air. This increases the total airflow to the space and
creates a warmer supply air condition. If additional heating is required, with the
terminal fan on, a heating coil can be used to further warm the supply air.
Operating the fan is a form of energy recovery. It tempers the supply air with
heat from the building and lights carried by the return air, rather than with
“new” energy, thus delaying the start of the heating coil.
18TRG-TRC014-EN
period two
Components of a VAV System
notes
When in cooling mode, the supply airflow to the space equals the primary
airflow. When in tempering and heating modes, the space receives a constant
supply airflow equal to the minimum primary airflow plus the plenum airflow
delivered by the terminal fan. Usually the primary airflow is not allowed to shut
off completely because of the space requirement for ventilation air.
Series, Fan-Powered
primary
primary
air
air
plenum
plenum
air
air
A series, fan-powered terminal unit consists of an airflow modulation device
and a small, constant-volume fan, packaged so that their airflow paths are in
series. The terminal unit fan operates continuously whenever the space is
occupied. The fan draws air from either the primary air stream or the plenum,
based on the thermostat in the space. This results in a constant volume of
supply air delivered to the space at all times.
terminal
terminal
mixing fan
mixing fan
supply
supply
air
air
Figure 30
TRG-TRC014-EN19
notes
period two
Components of a VAV System
Series, Fan-Powered
design
cooling load
maximum
primary
airflow
minimum
primary
airflow
Figure 31
100%
tempering
tempering
primary air
primary air
% airflow to space
0%
design
heating load
heating
heating
plenum air
plenum air
space load
In the cooling mode, the primary airflow is reduced as the cooling load in the
space decreases. The total supply airflow to the space remains constant, a
combination of cool primary air and warm plenum air. If the space cooling load
drops below the minimum primary airflow setting for the unit, or if space
heating is required, a heating coil can be used to further warm the supply air to
the space.
The maximum airflow for the airflow modulation device typically equals the
terminal fan airflow. This means that at the design cooling load, primary airflow
equals supply airflow.
Parallel Versus Series Fan-Powered
▲ Constant airflow to the space
▲ Acoustics
▲ Fan energy consumption
Figure 32
Series, fan-powered units are generally considered the premium VAV system
because while the central system operates as a variable-volume system, the
spaces receive constant supply airflow. Increased air motion in the space
improves comfort at all load conditions and the constant airflow simplifies
diffuser selection.
20TRG-TRC014-EN
period two
Components of a VAV System
notes
Most designers also believe that series units offer improved acoustical
conditions in the space. The constant sound of the series unit, with the fan
operating whenever the space is occupied, is generally preferred to the on-off
sound generated by the cycling fan in the parallel unit.
However, because the fan runs continuously whenever the space is occupied, a
series fan-powered unit consumes more energy than a parallel fan-powered
unit. The development of high-efficiency motors has lessoned the energy
consumption difference. The fan in a series fan-powered unit also costs more
than an equivalent parallel fan-powered unit because it generally requires a
larger terminal fan.
Fan-powered terminal units without a heating coil are typically used to provide
tempering for those zones that require year-round cooling and have relatively
high minimum airflow settings, such as the densely occupied interior zones of a
building (i.e., a conference room). A fan-powered terminal unit with a heating
coil is typically used for spaces that require seasonal cooling and heating, such
as the exterior zones of a building. Units with heating coils are the most
common of the fan-powered terminal units.
Single-Duct VAV Systems
central air handler
central air handler
55°F
90°F
90°F
[32.2°C]
[32.2°C]
OA
PA
55°F
[12.8°C]
[12.8°C]
VSD
VSD
single--
EA
RA
80°F
80°F
[26.7°C]
[26.7°C]
duct
single
duct
VAV terminal units
VAV terminal units
Figure 33
The types of terminal units discussed so far are used in single-duct VAV
systems. Single-duct VAV systems use a central return-air path that allows the
air from the spaces to come back to the air handler. At the air handler, a portion
of this return air is recirculated and mixed with outdoor air (introduced for
space ventilation purposes). This mixture of outdoor and recirculated return air,
or primary air, is then conditioned and delivered to the VAV terminal units
through the supply duct system.
The remainder of the return air is exhausted from the building.
TRG-TRC014-EN21
notes
period two
Components of a VAV System
Dual-Duct
warm
warm
primary air
primary air
cool
cool
primary air
primary air
supply
supply
air
air
A dual-duct terminal unit consists of two airflow modulation devices with
controls packaged in a sheet-metal enclosure. One controls the cool primary air
and the other controls the warm primary air. Depending on the method of
control, these two air streams may mix in the dual-duct unit before proceeding
downstream to the space.
Figure 34
This VAV terminal unit is intended for zones that require seasonal cooling and
heating, typically the exterior zones of a building. It is seldom used because of
the high first cost incurred to provide two duct systems.
A dual-duct terminal unit can be controlled to provide either a variable volume
or a constant volume of supply air to the space.
22TRG-TRC014-EN
notes
period two
Components of a VAV System
Variable Air Volume to the Space
100%
% airflow to space
0%
design
heating load
As before, this graph indicates how the air supplied to the space by the terminal
unit varies as the space loads change. The vertical axis indicates the total
airflow (cool primary air plus warm primary air) supplied to the space. The
horizontal axis indicates the space load.
To deliver a variable volume of supply air to the space in a two-fan, dual-duct
system in the cooling mode, the dual-duct unit is controlled in the same manner
as the cooling-only unit. The cool primary airflow is reduced as the cooling load
in the space decreases. When the space cooling load drops below the minimum
cool primary airflow setting for the unit, overcooling the space, the second
modulating device begins to open. This allows the warm primary air to mix
with the cool primary air and provide warmer supply air to the space.
heating
heating
warm
warm
primary air
primary air
cool
cool
space load
tempering
tempering
primary air
primary air
maximum
primary
airflow
minimum
primary
airflow
design
cooling load
Figure 35
As the cooling load decreases further and the space requires heating, more
warm primary air is mixed with the minimum amount of cool primary air.
TRG-TRC014-EN23
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.