Trane TRG-TRC012-EN User Manual

Page 1
Air Conditioning Clinic
Helical-Rotary Water Chillers
One of the Equipment Series
TRG-TRC012-EN
Page 2
Helical-Rotary Water Chillers
One of the Equipment Series
The Trane Company— Worldwide Applied Systems Group
Page 3
Preface
Helical-Rotary Water Chillers
A Trane Air Conditioning Clinic
Figure 1
The Trane Company believes that it’s incumbent on manufacturers to serve the industry by regularly disseminating information gathered through laboratory research, testing programs and field experience.
The Trane Air Conditioning Clinic series is one means of knowledge sharing. It’s intended to acquaint a nontechnical audience with various fundamental aspects of heating, ventilating, and air conditioning.
We’ve taken special care to make the clinic as uncommercial and straightforward as possible. Illustrations of Trane products only appear in cases where they help convey the message contained in the accompanying text.
This particular clinic introduces the reader to the concept of helical-rotary water chillers.
© 1999 American Standard Inc. All rights reserved
ii
TRG-TRC012-EN
Page 4
Contents
Introduction ............................................................1
period one Components ...........................................................3
Compressor .............................................................4
Oil Separator ............................................................8
Condenser ...............................................................9
Expansion Device ...................................................11
Liquid/Vapor Separator ...........................................12
Evaporator .............................................................13
Controls and Starter ...............................................15
period two Refrigeration Cycle .............................................16
period three Compressor Capacity Control .........................21
period four Maintenance Considerations ...........................25
period five Application Considerations ..............................31
Air-Cooled or Water-Cooled Condensing .................31
Condensing Temperature Control ...........................33
Constant or Variable Evaporator Water Flow ...........35
Short Evaporator Water Loops ................................36
Equipment Certification Standards ..........................38
period six Review ....................................................................40
Quiz ..........................................................................44
Answers .................................................................46
Glossary .................................................................47
TRG-TRC012-EN iii
Page 5
iv TRG-TRC012-EN
Page 6
notes
Introduction
Chilled Water System
Figure 2
Water chillers are used in a variety of air conditioning and process cooling applications. They are used to make cold water that can be transported throughout a facility using pumps and pipes. This cold water can be passed through the tubes of coils in order to cool the air in an air conditioning application or it can provide cooling for a manufacturing or industrial process.
Systems that employ water chillers are commonly called chilled water systems.
absorption
helical-rotary
There are several types of water chillers that are differentiated by the refrigeration cycle they use or the type of compressor.
Absorption water chillers make use of the absorption refrigeration cycle and do not have a mechanical compressor involved in the refrigeration cycle. Absorption water chillers are the subject of a separate clinic.
centrifugal
Figure 3
TRG-TRC012-EN 1
Page 7
Introduction
notes
Water chillers using the vapor-compression refrigeration cycle vary by the type of compressor used. Reciprocating and scroll compressors are typically used in smaller chillers. Helical-rotary (or screw) compressors are typically used in medium-sized chillers. Centrifugal compressors are typically used in larger chillers.
As mentioned earlier, this particular clinic discusses helical-rotary water chillers.
Helical-Rotary Water Chillers
water-cooled
air-cooled
Figure 4
Helical-rotary water chillers can be either air-cooled or water-cooled, referring to the method of rejecting heat to the atmosphere. Both air-cooled and water­cooled helical-rotary chillers are generally available from 70 to 450 tons [200 to 1500 kW].
The primary focus in Period 1 is on the water-cooled chiller, although it includes some discussion of air-cooled chiller components. A comparison of air-cooled versus water-cooled chiller applications is included in Period 5.
2 TRG-TRC012-EN
Page 8
notes
period one
Components
Helical-Rotary Water Chillers
period one
Figure 5
Many of the components of the helical-rotary water chiller are similar to those of other chiller types.
components of a
Helical-Rotary Water Chiller
motor
oil supply
oil supply
system
system
oil separator
oil separator
condenser
condenser
This particular helical-rotary water chiller makes use of a shell-and-tube evaporator where refrigerant evaporates inside the shell and water flows inside tubes. The compressor is a twin-rotor, helical-rotary compressor. It uses a suction-gas-cooled motor to operate the compressor. Another shell-and-tube heat exchanger is used for the condenser, where refrigerant is condensed inside the shell and water flows inside tubes. Refrigerant is metered through the system using an electronic expansion valve. A liquid/vapor separator can be used to enhance the effectiveness of the refrigeration cycle. An oil supply system provides near oil-free refrigerant to the shells to maximize heat transfer performance while providing lubrication and rotor sealing to the helical-rotary compressor. A control panel is also provided on the chiller, and a starter connects the chiller motor to the electrical distribution system.
compressor
compressor
motor
evaporator
evaporator
liquid/vapor
liquid/vapor
separator
separator
control
control
panel
panel
starter
starter
Figure 6
TRG-TRC012-EN 3
Page 9
notes
period one
Components
compressor...
Helical Rotors
Figure 7
Compressor
The helical-rotary chiller uses 2 screw-like rotors to perform the compression process.
compressor...
Helical Rotors
female rotor
female rotor
male rotor
male rotor
housing
housing
slide valve
slide valve
The rotors are meshed and fit, with very close tolerances, within a housing.
Only the male rotor is driven by the compressor motor. The lobes of the male rotor engage and drive the female rotor, causing the 2 parts to counter-rotate.
Figure 8
4 TRG-TRC012-EN
Page 10
notes
period one
Components
compressor...
Helical Rotors
intake
intake
port
port
Figure 9
In the operation of the helical-rotary compressor, refrigerant vapor enters the compressor housing through the intake port. The intake port in this example is at the top of the compressor housing.
compressor...
Helical Rotors
intake
intake
port
port
pocket of refrigerant vapor
pocket of refrigerant vapor
The entering refrigerant vapor is at a low, suction pressure and fills the grooves or pockets formed by the lobes of the rotors. As the rotors turn, they push the pockets of refrigerant toward the discharge end of the compressor.
Figure 10
TRG-TRC012-EN 5
Page 11
notes
period one
Components
compressor...
Helical Rotors
intake port
intake port
discharge port
discharge port
Figure 11
Viewing the compressor from the side shows that after the pockets of refrigerant travel to the right past the intake port area, the vapor, still at suction pressure, is confined within the pockets by the compressor housing.
compressor...
Helical Rotors
discharge port
discharge port
meshing point
meshing point
Viewing the compressor from the top shows that rotation of the meshed rotor lobes drives the trapped refrigerant vapor (to the right) ahead of the meshing point.
Figure 12
6 TRG-TRC012-EN
Page 12
notes
period one
Components
compressor...
Helical Rotors
discharge port
discharge port
meshing point
meshing point
Continued rotation of the rotors causes the meshing point to travel toward the discharge end of the compressor, driving the trapped refrigerant vapor ahead of it. This action progressively reduces the volume of the pockets, compressing the refrigerant.
Figure 13
compressor...
Helical Rotors
discharge port
discharge port
meshing point
meshing point
Finally, when the pockets of refrigerant reach the discharge port the compressed vapor is released. As the rotors continue to rotate, the volume of the pockets is further reduced, squeezing the remaining refrigerant from the cavities.
Notice that the refrigerant vapor enters and exits the compressor through
ports—no valves are used. Compressors of this design are called ported compressors.
Figure 14
TRG-TRC012-EN 7
Page 13
notes
period one
Components
Oil Separator
refrigerant vapor
refrigerant vapor
to condenser
to condenser
refrigerant vapor
refrigerant vapor
and oil mixture
and oil mixture
oil return to sump
oil return to sump
Oil Separator
The oil leaves the compressor entrained within the discharged refrigerant vapor.
Figure 15
The oil is recovered from the discharged refrigerant by an oil separator, which can have an efficiency of greater than 99%. The separator consists of a vertical cylinder surrounding an exit passageway. As the refrigerant-and-oil mixture is discharged into this passageway the oil is forced outward by centrifugal force, collects on the walls of the cylinder, and drains to the bottom. This accumulated oil drains out of the cylinder and collects in the oil sump located near the bottom of the chiller.
The oil sump is heated to ensure proper lubrication and minimize refrigerant condensation in the sump.
Oil Supply System
oil
refrigerant
refrigerant
vapor to
vapor to
condenser
condenser
oil tank
oil tank
sump
sump
oil filter
oil filter
oil
separator
separator
master
master
solenoid
solenoid
valve
valve
rotor bearings
rotor bearings
rotor
rotor
2
2
compressor
compressor
1
1
Figure 16
Oil that collects in the oil sump is at condensing pressure during compressor
8 TRG-TRC012-EN
Page 14
period one
Components
notes
operation and is, therefore, constantly moving to lower pressure areas of the chiller. In this system, oil flows in 2 distinct paths, each performing a separate function: 1) bearing lubrication and cooling and 2) rotor oil injection.
Oil leaves the sump and passes through an oil filter and master solenoid valve. The master solenoid valve is used to isolate the sump from the low-pressure side of the system when the compressor is shut down, preventing oil migration.
The first path is for lubricating and cooling the compressor bearings . Oil is
routed to the bearings located in the rotor and bearing housing. Each housing is vented to the suction side of the compressor so that oil leaving the bearings is routed through the rotors, to the oil separator, and then back to the oil sump.
The second path is for lubricating and sealing the compressor rotors . Oil is
injected along the bottom or top of the compressor rotors inside the housing. Its main purpose is to seal the rotor-to-rotor and rotor-to-housing clearances. This seal provides a barrier between the high- and low-pressure cavities of the compressor. Additionally, oil lubricates the male-to-female rotor drive arrangement.
water-cooled
Condenser
refrigerant vapor
refrigerant vapor
baffle
baffle
cooling
cooling
tower
tower
water
water
tube bundle
tube bundle
subcooler
subcooler
liquid
liquid
refrigerant
refrigerant
Figure 17
Condenser
The high-pressure refrigerant vapor, now stripped of oil droplets, leaves the oil separator and continues on to the condenser.
In a water-cooled condenser, water is pumped through the tubes of this shell-and-tube heat exchanger while refrigerant vapor fills the shell space surrounding the tubes. The condenser has a baffle plate that helps distribute the refrigerant evenly within the shell. As heat is transferred from hot, high­pressure refrigerant vapor to the water, refrigerant condenses on the tube surfaces.
The condensed liquid refrigerant then collects in the bottom of the shell where the lower tubes are now submerged, resulting in further cooling, or subcooling, of the refrigerant. This arrangement is called an integral subcooler.
TRG-TRC012-EN 9
Page 15
period one
Components
notes
Cooling water flows first through the lower tubes of the condenser and then through the upper tubes. This produces a nearly constant temperature difference between the downward moving refrigerant and the tube surfaces, resulting in a uniform heat transfer rate within the tube bundle.
Subcooled liquid refrigerant leaves the condenser (subcooler) and flows through the liquid line to the expansion device.
air-cooled
Condenser
propeller fan
propeller fan
subcooler
subcooler
In a typical air-cooled condenser, propeller-type fans are used to draw outdoor air over a fin-tube heat transfer surface. The hot, high-pressure refrigerant vapor flows through the tubes as heat is transferred to the cooler outdoor air. The resulting reduction in the heat content of the refrigerant vapor causes it to condense into liquid. Within the final few lengths of condenser tubing the condensed liquid refrigerant is subcooled.
condenser
condenser
coil
coil
outdoor air
outdoor air
Figure 18
Again, subcooled liquid refrigerant leaves the condenser (subcooler) and flows through the liquid line to the expansion device.
The differences between water-cooled and air-cooled chiller applications will be discussed further in Period 5.
10 TRG-TRC012-EN
Page 16
notes
period one
Components
expansion device…
Electronic Expansion Valve
Figure 19
Expansion Device
An expansion device is used to maintain the pressure difference between the high-pressure (condenser) and low-pressure (evaporator) sides of the system, as established by the compressor. This pressure difference allows the evaporator temperature to be low enough to absorb heat from the water being cooled, while also allowing the refrigerant to be at a high enough temperature in the condenser to reject heat to air or water at normally available temperatures. High-pressure liquid refrigerant flows through the expansion device, causing a large pressure drop that reduces the refrigerant pressure to that of the evaporator. This pressure reduction causes a small portion of the liquid to boil off, or flash, cooling the remaining refrigerant to the desired evaporator temperature.
In this chiller, the expansion device used is an electronic expansion valve. In addition to maintaining the high- and low-side pressure difference, the electronic expansion valve controls the quantity of liquid refrigerant entering the evaporator to ensure that it will be completely vaporized within the evaporator.
TRG-TRC012-EN 11
Page 17
notes
period one
Components
expansion device…
Orifice Plates
to
orifice plates
orifice plates
H
H
The orifice plate is another type of expansion device found in helical-rotary chillers. The column of liquid refrigerant creates a head pressure at its base, allowing it to pass through the orifices and undergo a pressure drop equal to the head (H) before it flashes. As the load decreases, less refrigerant is moved throughout the chiller, causing the level of the liquid column to drop. This causes additional flashing at the orifice plate which, in turn, results in feeding less liquid to the evaporator.
to
evaporator
evaporator
Figure 20
Liquid/Vapor Separator
refrigerant vapor
refrigerant vapor
to compressor
to compressor
liquid refrigerant
from
from
expansion
expansion
device
device
Liquid/Vapor Separator
The mixture of liquid and vapor refrigerant that leaves the expansion device enters a liquid/vapor separator. Here the liquid refrigerant settles to the bottom of the chamber and the vapor is drawn off the top and routed directly to the suction side of the compressor. The remaining liquid refrigerant is then routed to the evaporator.
12 TRG-TRC012-EN
liquid refrigerant
to evaporator
to evaporator
Figure 21
Page 18
period one
Components
notes
By removing the vapor portion of the mixture before it gets to the evaporator the separator enhances the effectiveness of the evaporation process.
Flooded Evaporator
chilled
refrigerant vapor
refrigerant vapor
liquid
liquid
refrigerant
refrigerant
tube bundle
tube bundle
chilled
chilled
water
water
return
return
liquid level
liquid level
sensor
sensor
Evaporator
In the flooded shell-and-tube evaporator cool, low-pressure liquid refrigerant enters the distribution system inside the shell and is distributed uniformly over the tubes, absorbing heat from relatively warm water that flows through the tubes. This transfer of heat boils the film of liquid refrigerant on the tube surfaces and the resulting vapor is drawn back to the compressor. The cooled water can now be used in a variety of comfort or process applications.
chilled
water
water
supply
supply
Figure 22
A sensor can monitor the level of liquid refrigerant in this type of evaporator and the electronic expansion valve can be used to carefully meter the liquid
refrigerant flow to the evaporator’s distribution system in order to maintain a relatively low level of refrigerant in the evaporator shell.
TRG-TRC012-EN 13
Page 19
notes
period one
Components
Direct Expansion Evaporator
chilled
chilled
water
water
supply
supply
baffles
baffles
tube bundle
tube bundle
Another type of evaporator found in helical-rotary chillers is the direct expansion (DX) shell-and-tube evaporator. In this type of evaporator the
cool, low-pressure liquid refrigerant flows through the tubes and water fills the surrounding shell. As heat is transferred from the water to the refrigerant, the refrigerant boils inside the tubes and the resulting vapor is drawn to the compressor. Baffles within the shell direct the water in a rising and falling flow path over the tubes that carry the refrigerant. The resulting turbulence improves heat transfer.
chilled
chilled
water
water
return
return
refrigerant
refrigerant
vapor
vapor
liquid
liquid
refrigerant
refrigerant
Figure 23
Since the tubes of a flooded evaporator contain water, they can be mechanically cleaned without removing the refrigerant charge. The tubes of a direct expansion evaporator must be chemically cleaned. Additionally, flooded evaporators are typically more effective, but are more costly.
14 TRG-TRC012-EN
Page 20
notes
period one
Components
Controls And Starter
control
control
panel
panel
starter
starter
Figure 24
Controls and Starter
A microprocessor-based control panel is provided on the chiller to provide accurate chilled water control as well as monitoring, protection, and adaptive
limit functions. These controls monitor the chiller’s operation and prevent the chiller from operating outside of its limits. They can compensate for unusual operating conditions while keeping the chiller running by modulating system components, rather than simply tripping off due to a safety setting. Furthermore, when problems do occur, diagnostic messages aid in troubleshooting.
This control system not only provides accurate, optimized control and protection for the chiller, but permits interfacing with a building automation system for integrated system control. In a chilled water system, optimal control is a system-wide issue, not just a chiller issue.
Because compressor motors create such a large electrical load, they cannot be started and stopped using a simple switch or plug. A starter provides a linkage between the motor and the electrical distribution system. Its primary function is to connect (start) and disconnect (stop) the chiller from the line. The starter also includes a transformer that provides power to the chiller control panel and components to perform overload protection and current-limiting functions. Finally, the application of a chiller starter also requires considering a means of disconnect and short circuit protection.
TRG-TRC012-EN 15
Page 21
notes
period two
Refrigeration Cycle
Helical-Rotary Water Chillers
period two
Figure 25
A pressure-enthalpy (p-h) chart illustrates the refrigeration cycle of the helical­rotary water chiller.
helical-rotary water chiller
Refrigeration Cycle
liquid/vapor
liquid/vapor
separator
separator
compressor
compressor
expansion
expansion
device
device
But first, lets review the components of the helical-rotary chiller’s refrigeration cycle...
Refrigerant vapor leaves the evaporator and flows to the compressor where it is compressed to a higher pressure and temperature. Oil is removed from refrigerant vapor in the oil separator and the refrigerant travels to the condenser while the oil is recirculated back to the compressor.
In the condenser, the refrigerant vapor rejects heat to water or air and leaves as a sub-cooled liquid. The pressure drop created by the expansion device causes a portion of the liquid refrigerant to evaporate and the resulting mixture of liquid and vapor refrigerant enters the liquid/vapor separator. Here the vapor is
evaporator
evaporator
condenser
condenser
oil separator
oil separator
Figure 26
16 TRG-TRC012-EN
Page 22
period two
Refrigeration Cycle
notes
separated from the mixture and routed directly to the suction side of the compressor and the remaining liquid refrigerant enters the evaporator.
In the evaporator, the liquid refrigerant boils as it absorbs heat from water. The resulting vapor is drawn back to the compressor to repeat the cycle.
Pressure–Enthalpy (
subcooled
subcooled
liquid
liquid
pressure
pressure
147.5
147.5
[1.02
[1.02
psia
psia
MPa]]
MPa
$
46.4 Btu/lblb
46.4 Btu/
[256.4 kJ/kg]
[256.4 kJ/kg]
mixture of
mixture of
liquid and
liquid and
vapor
vapor
enthalpy
enthalpy
p-h)
%
116.6 Btu/lblb
116.6 Btu/
[419.6 kJ/kg]
[419.6 kJ/kg]
Chart
superheated
superheated
vapor
vapor
Figure 27
The pressure-enthalpy chart is simply a plot of the saturated properties of a refrigerant. It plots refrigerant pressure (vertical axis) versus enthalpy (horizontal axis). Enthalpy is a measurement of the heat content, both sensible and latent, per pound [kg] of refrigerant.
liquid
For example, A represents the heat content of saturated
HFC-134a
refrigerant at 147.5 psia [1.02 MPa] and 104°F [40°C]. B represents the heat content of saturated
vapor
HFC-134a refrigerant at the same pressure and
temperature. The difference in heat content, or enthalpy, between A and B— that is, 70.2 Btu/pound [163.2 kJ/kg]—is the amount of heat required to transform 1 pound [1 kg] of saturated liquid refrigerant to saturated refrigerant vapor at the same pressure and temperature.
If the heat content of the refrigerant at any pressure falls to the right of the curve, the vapor is superheated. Similarly, if the heat content of the refrigerant falls to the left of the curve, the liquid is subcooled. Finally, when the heat content of the refrigerant falls inside the curve the refrigerant exists as a liquid/ vapor mixture.
TRG-TRC012-EN 17
Page 23
notes
period two
Refrigeration Cycle
helical-rotary water chiller
Refrigeration Cycle
condenser
condenser
4
4
liquid/vapor
liquid/vapor
separator
separator
evaporator
evaporator
3
3
1
1
expansion
expansion
device
device
pressure
pressure
5
5
7
7
6
6
2
2
compressor
compressor
enthalpy
enthalpy
The theoretical vapor-compression refrigeration cycle for a helical-rotary water chiller can be plotted on a pressure-enthalpy chart.
The refrigerant leaves the evaporator as saturated vapor and flows to the
suction end of the compressor where it enters the compartment for the suction­gas-cooled motor. Here the refrigerant flows across and cools the motor, then enters the compression chamber. The refrigerant vapor is compressed in the
compressor to a high pressure and temperature . Energy input to the motor
and compressor is imparted to the refrigerant as superheat. Superheated refrigerant vapor leaves the compressor and enters the condenser.
Water or air flowing through the condenser absorbs heat from the hot, high­pressure refrigerant. This reduction in the heat content of the refrigerant vapor
causes it to desuperheat , condense into liquid , and further sub-cool
before leaving the condenser to travel to the expansion device.
The pressure drop created by the expansion process causes a portion of the liquid refrigerant to evaporate. The evaporating refrigerant absorbs heat from the remaining liquid refrigerant. The resulting mixture of cold liquid and vapor
refrigerant enters the liquid/vapor separator . Here the vapor is separated from the mixture and routed directly to the suction side of the compressor and the remaining liquid refrigerant enters the evaporator ➆.
The cool low-pressure liquid refrigerant enters the distribution system in the evaporator shell and is distributed over the tubes in the evaporator tube bundle, absorbing heat from water that flows through the tubes. This transfer of heat boils the film of liquid refrigerant on the tube surfaces and the resulting
vapor is drawn back to the compressor to repeat the cycle.
Figure 28
18 TRG-TRC012-EN
Page 24
notes
period two
Refrigeration Cycle
helical-rotary water chillers…
Refrigerants
HCFC-22HFC-134aHFC-404aHFC-407cHFC-410a
Figure 29
Manufacturers are continuously improving their designs of helical-rotary water chillers. New chillers need to be designed around the characteristics of the refrigerant. Today there are 5 strong candidates for use with positive­displacement, helical-rotary chillers. They are HCFC-22, HFC-134a, HFC-404a, HFC-407c and HFC-410a.
TRG-TRC012-EN 19
Page 25
notes
period two
Refrigeration Cycle
refrigerants…
Thermodynamic Characteristics
160
160
140
140
120
120
100
100
80
80
percent
percent
60
60
40
40
20
20
0
0
HCFC-22
HCFC-22
efficiency
efficiency
HFC-134a
HFC-134a
capacity
capacity
HFC-404a
HFC-404a
pressure
pressure
HFC-407c
HFC-407c
HFC-410a
HFC-410a
Figure 30
Today the most commonly used refrigerant in helical-rotary chillers is HCFC-22. Due to the scheduled phaseout of HCFC-22, most helical-rotary chillers will be redesigned using HFC refrigerants. Many challenges are encountered when redesigning a chiller to use a refrigerant with different thermodynamic characteristics. This is due to the different efficiency, capacity, and operating pressure characteristics of each of the refrigerants.
Take a closer look at each of these issues by examining the effects of using different refrigerants in the same helical-rotary chiller designed for use with HCFC-22.
Efficiency – In order to meet today’s high standards of energy efficiency,
chillers using refrigerants with a lower thermal efficiency, such as HFC-404a and HFC-410a, will require larger heat exchangers and more efficient compressors. These changes add to the product cost and increase the physical size of the chiller.
Capacity – HFC-134a has a lower capacity compared to HCFC-22, which
means more refrigerant needs to be pumped through the chiller to achieve the same capacity. This can be accomplished by using a larger compressor or increasing the speed of the compressor. Both tend to increase product cost and design complexity. On the other hand, HFC-410a has a higher capacity compared to HCFC-22, which means less refrigerant needs to be pumped through the chiller to achieve the same capacity. The advantage is that smaller, less expensive compressors can be used.
Operating Pressure – A refrigerant that operates at a higher pressure
requires heat exchangers and pressure vessels to be designed for the higher pressure. This adds cost. Conversely, higher pressure refrigerants have a greater density. As density increases, the required amount of refrigerant decreases, meaning that smaller or slower-speed compressors can be used. Lower pressure refrigerants, such as HFC-134a, will require larger or higher­speed compressors in order to achieve the same capacity as a similar chiller using HCFC-22.
20 TRG-TRC012-EN
Page 26
notes
period three
Compressor Capacity Control
Helical-Rotary Water Chillers
period three
Figure 31
The capacity of the helical-rotary compressor presented in this clinic is controlled by a slide valve that is an integral part of the compressor housing.
Other helical-rotary compressor designs may use a variety of methods to vary capacity. Some of these methods are similar in function to the slide valve presented in this period. One major difference is whether the compressor is designed to unload in steps, like a reciprocating compressor, or if it has variable unloading.
Slide Valve
axial
axial
discharge
discharge
port
port
slide valve
slide valve
The position of the slide valve along the rotors controls the volume of refrigerant vapor being delivered by the compressor, by varying the amount of rotor length actually being used for compression.
Note that the compressor discharge has 2 components. First, a port within the slide valve provides a radial discharge path. Second, a port within the end­plate of the compressor housing provides an axial discharge path.
TRG-TRC012-EN 21
radial
radial
discharge
discharge
port
port
Figure 32
Page 27
notes
period three
Compressor Capacity Control
slide valve position...
Full Load
compressor
compressor
discharge
discharge
slide valve
(closed)
At full load, the slide valve is closed. The compressor pumps its maximum volume of refrigerant, discharging it through both the radial and axial ports.
axial port
axial portaxial port
radial port
radial portradial port
Figure 33
slide valve position...
Part Load
compressor
compressor
discharge
to suction
to suction
valve
valve
opening
opening
At part load, the slide valve modulates toward the open position. The opening created by the valve movement allows refrigerant vapor to bypass from the rotor pockets back to the suction side of the compressor. This reduces the volume of vapor available for the compression process. It also reduces the amount of rotor length available for compression. In this manner, the volume of refrigerant that is pumped by the compressor is varied, unloading it to balance the existing chiller load.
slide valve
open
discharge
axial port
axial port
radial port
radial port
Figure 34
22 TRG-TRC012-EN
Page 28
notes
period three
Compressor Capacity Control
compressor capacity control...
Unloading
compressor
compressor
discharge
to suction
to suction
valve
valve
opening
opening
As the slide valve continues to open, further unloading the compressor, its radial discharge port eventually travels past the opening in the compressor housing. Once this occurs, all of the refrigerant vapor being pumped by the
compressor is discharged through the axial port in the compressor’s end-plate.
slide valve
open
discharge
radial port
radial port
Figure 35
The compressor discharge ports and slide valve are designed to allow the compressor to operate efficiently over a wide range of conditions.
TRG-TRC012-EN 23
Page 29
notes
period three
Compressor Capacity Control
Slide Valve Operation
high-pressure
high-pressure
refrigerant vapor
refrigerant vapor
slide valve
slide valve
operator
operator
shaft
shaft
spring
spring
The slide valve is operated by a piston and cylinder assembly. Extension and retraction of the operator shaft positions the slide valve along the compressor rotors.
piston
piston
cylinder
cylinder
load
load
valve
valve
unload
unload
valve
valve
to low-
to low-
pressure
pressure
compressor
compressor
housing
housing
Figure 36
High-pressure refrigerant vapor, controlled by 2 solenoid valves, is fed to or bled from this assembly in order to position the valve. To close the slide valve and load the compressor, the load valve is opened and the unload valve is closed. This allows high-pressure refrigerant vapor to enter the cylinder from the discharge of the compressor, extending the operator shaft and moving the slide valve so that it covers more of the rotor length.
Conversely, to open the slide valve and unload the compressor, the load valve is closed and the unload valve is opened. This allows the high-pressure refrigerant vapor to bleed out of the cylinder into the low-pressure area within the compressor housing. A spring helps return the piston, retracting the operator shaft and moving the slide valve such that the rotors are more uncovered. This reduces the effective length of the rotors, which are compressing vapor.
On shutdown the unload solenoid valve is energized and the spring drives the slide valve to the fully-unloaded position. This ensures that the compressor always starts fully unloaded.
When both solenoid valves are closed, the operator shaft holds the slide valve at its current position.
24 TRG-TRC012-EN
Page 30
notes
period four
Maintenance Considerations
Helical-Rotary Water Chillers
period four
Figure 37
This period discusses general maintenance requirements of helical-rotary water chillers. Although some of the information applies specifically to the design presented in this clinic, requirements for other helical-rotary chiller designs are also included.
helical-rotary water chillers
Maintenance Considerations
Operating logMechanical
components
Heat transfer
surfaces
Fluid analysis
Figure 38
Once a helical-rotary chiller is installed and put into operation, it usually continues to function without a full-time attendant. In many cases, the machine starts and stops on a schedule controlled by the building automation system or a simple time clock. The only daily maintenance requirement is to check the operating log.
Water chillers are designed for maximum reliability with a minimum amount of maintenance. Like all large mechanical systems, however, certain routine maintenance procedures are either required or recommended.
TRG-TRC012-EN 25
Page 31
notes
period four
Maintenance Considerations
operating log
ASHRAE Guideline 3
Chilled water inlet and outlet
temperatures and pressures
Chilled water flowEvaporator refrigerant
temperature and pressures
Evaporator approach
temperature
Condenser water inlet and
outlet temperatures and pressures
Condenser water flow
Condenser refrigerant
temperature and pressures
Condenser approach
temperature
The American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) has published Guideline 3 titled
Refrigerants in Refrigeration and Air Conditioning Equipment and Systems
This guideline includes a recommended list of data points to be logged daily for
each chiller. Much of this data may be available through the chiller’s control panel.
Compressor ref r igerant suction
and discharge temperatures
Refrigerant lev e lOil pressures, temperature, and
levels
Addition of refrigerantAddition of oilVibration levels
Reducing Emission of Halogenated
Figure 39
.
Special attention should be given to the following:
Review the operating log and trends
Measure the oil pressure drop to determine if the oil filter needs to be
replaced
Measure refrigerant superheat and subcooling
Measure both the refrigerant and oil charges
26 TRG-TRC012-EN
Page 32
notes
period four
Maintenance Considerations
maintenance considerations
Mechanical Components
Required maintenance
Compressor and motor: no maintenance required
Controls: no maintenance or calibration required
Recommended maintenance
Visually inspect overall unit
Inspect safety controls and electrical components
Tighten electrical connections
Check for leaks
Test vent piping
Figure 40
Direct-drive, semi-hermetic compressor designs require no periodic maintenance on the compressor/motor assembly. The compressor contains only 3 main moving parts: the male and female rotors and the slide valve. The semi-hermetic motor eliminates the need for external shaft seals associated with open motors. These seals are a prime source of oil and refrigerant leaks. It also eliminates annual coupling and seal inspections, alignment, and shaft seal replacement.
With the advent of microprocessor-based controls, the control panel and auxiliary controllers require no recalibration or maintenance. Remote-mounted electronic sensors send information to the unit controller, which can be connected to a building automation system in order to communicate information and allow for system-level optimization. These systems can notify the operator with an alarm or diagnostic message when a problem occurs.
Like any mechanical equipment, a daily visual inspection of the chiller is recommended to look for oil leaks, condensation, loosened electrical or control wiring, or signs of corrosion. Special attention should be given to the safety controls and electrical components.
It is recommended that a qualified service technician check the chiller annually for leaks. In the normal service of any air conditioning system, the Unites States EPA mandates that whenever a refrigeration circuit is opened, recovery of the refrigerant is required.
Finally, the vent piping of all pressure relief valves should be leak-tested annually for the presence of refrigerant to detect improperly sealed valves. Leaking relief valves should be replaced.
TRG-TRC012-EN 27
Page 33
notes
period four
Maintenance Considerations
maintenance considerations
Mechanical Components
Other design-specific requirements:
Change oil when oil analysis dictates
Replace oil filter periodically
Replace filter drier periodically
Clean oil strainers annually
Check shaft alignment annually
Check coupling annually
Replace shaft seal every 2 to 4 years
Compressor teardown inspection every 5 to 10 years
Figure 41
Some helical-rotary compressor designs do require periodic maintenance of mechanical system components. This includes oil and refrigerant filter changes, oil strainer changes, and a compressor rotor inspection.
Open-motor compressor designs require shaft alignment, coupling inspection, bearing lubrication, and cleaning of the motor windings, rotor ends, and fan blades on a quarterly or annual basis.
In all cases, strictly follow the manufacturer’s published maintenance requirements and recommendations.
maintenance considerations
Heat Transfer Surfaces
Recommended maintenance
Use a qualified water treatment
specialist
Clean condenser tubes as
needed (water-cooled)
Clean water-side strainers
Test tubes every 3 years
Clean condenser coils as
needed (air-cooled)
Figure 42
Optimum performance of heat transfer components depends on keeping the heat transfer surfaces free from scale and sludge. Even a very thin deposit of scale can substantially reduce heat transfer capacity. Owners of water-cooled chillers should engage the services of a qualified water treatment specialist to
28 TRG-TRC012-EN
Page 34
period four
Maintenance Considerations
notes
determine the level of water treatment required to remove contaminants from the cooling tower water.
Scale deposits are best removed by chemical means. The water-cooled condenser is commonly isolated from the rest of the cooling tower water circuit by valves, and a pump circulates cleaning solution through the condenser tubes.
Sludge is removed mechanically. This involves removing the water boxes from the condenser and loosening the deposits with a stiff-bristled brush. The loosened material is then flushed from the tubes with clear water. As part of this procedure, the strainers on both the chilled water and cooling tower water circuits should be cleaned every year.
Every 3 years, or more frequently for process or critical applications, it is recommended that a qualified service organization perform non-destructive tube inspections on both the evaporator and condenser tubes. The eddy­current tube test is a common method.
Rarely, problems may arise that cause refrigerant or water leaks. These must be repaired immediately.
For air-cooled chillers, the condenser coils should be cleaned at least annually in order to maintain proper efficiencies and operating conditions. Follow the
manufacturer’s instructions to avoid damage to the coils.
maintenance considerations
Fluid Analysis
Oil analysis
Conduct annual analysis to verify
system integrity
Measure oil pressure drop to
determine if filter needs changing
Measure charge
Refrigerant charge
Measure charge and trim as
necessary
Measure superheat and subcooling
Figure 43
Probably the most important annual maintenance task required for helical­rotary water chillers is an oil analysis. It may be conducted more frequently for chillers that run continuously or more often than normal. This test, performed by a qualified laboratory, verifies the integrity of the refrigeration system by testing the moisture, acidity, and metal concentration levels. This analysis can determine where problems exist or could potentially develop. By taking oil samples on a regular basis, normal operating trends for the compressor and bearing metals can be analyzed. As opposed to changing the oil once a year whether it needs it or not, regular oil analyses can be used to determine proper oil change intervals as well as predict major problems before they occur.
TRG-TRC012-EN 29
Page 35
period four
Maintenance Considerations
notes
Refrigerant analysis measures contamination levels and determines suitability for continued use. It can also determine the acceptability of recycled refrigerant for reuse. Refrigerant analysis helps extend the life of the existing charge and ensures that the chiller is operating at peak efficiency.
Logging the oil and refrigerant charges, and examining the trends of this data, can help identify potential problems before they occur.
maintenance considerations
Fluid Analysis
Why perform regular oil analyses?
Helps reduce maintenance costs
Detects problems without
compressor disassembly
Extends service life of oil charge
Reduces environmental problems
related to oil disposal
Helps maintain compressor
efficiency and reliability
Helps lower refrigerant emissions
Figure 44
An oil analysis is a key preventive maintenance measure and should be conducted at least annually. It will help the compressor last longer while improving chiller efficiency and reducing refrigerant emissions. A certified chemical laboratory has years of experience in analyzing oil and refrigerant from all types of compressors.
Often the chiller manufacturer can provide this service.
30 TRG-TRC012-EN
Page 36
notes
period five
Application Considerations
Helical-Rotary Water Chillers
period five
Figure 45
There are several considerations to address when applying helical-rotary water chillers, including:
Air-cooled or water-cooled condensing
Condensing temperature control
Constant or variable evaporator water flow
Short evaporator water loops
Equipment certification standards
This section is by no means the entire list of considerations, but is representative of some of the key issues.
condenser types…
Air-Cooled or Water-Cooled
Figure 46
Air-Cooled or Water-Cooled Condensing
Although this is not a new consideration, the question of which condenser type to apply continues to receive attention. A major advantage of air-cooled chillers
TRG-TRC012-EN 31
Page 37
period five
Application Considerations
notes
is the elimination of the cooling tower. This eliminates the concerns and maintenance requirements associated with water treatment, makeup water availability and quality, tower mechanical maintenance, freeze protection, and chiller condenser tube cleaning. This reduced maintenance requirement is particularly attractive since it can substantially reduce operating costs.
Another advantage of an air-cooled chiller is its delivery as a “packaged system.” Reduced design time, simplified installation, higher reliability, and single-source responsibility are all factors that make the factory packaging of the condenser, compressor, and evaporator a major benefit. A water-cooled chiller has the additional requirement of condenser water piping, pump, cooling tower, and controls.
Air-cooled chillers are often selected in buildings with a requirement for year­round cooling that cannot be met with an air-side economizer. Air-cooled condensers have the ability to operate in below-freezing weather without the problems associated with operating the cooling tower in low-ambient conditions. Cooling towers may require special sequences of operation, basin heaters, or even an indoor sump for safe operation in freezing weather.
air-cooled or water-cooled
Comparison
air-cooled
Lower maintenancePackaged systemBetter low am bient
operation
Water-cooled chillers are generally more energy efficient. The efficiency advantage of a water-cooled chiller, however, is much less when the additional cooling tower and condenser pump energy costs are considered. Additionally, this efficiency advantage may lessen at part-load conditions since the dry bulb temperature tends to drop faster than the wet bulb temperature and the air­cooled chiller benefits from greater condenser relief.
Performing a comprehensive energy analysis is the best method of estimating the system operating cost difference between air-cooled and water-cooled systems.
Water-cooled chillers typically last longer than air-cooled chillers. This difference is due to the fact that the air-cooled chiller is installed outdoors, whereas the water-cooled chiller is installed indoors. Also, using water as the condensing fluid allows the water-cooled chiller to operate at lower pressures
32 TRG-TRC012-EN
water-cooled
Greater energy efficiencyLonger equipment life
Figure 47
Page 38
period five
Application Considerations
notes
and temperatures that the air-cooled chiller. Generally, air-cooled chillers last 15 to 20 years, while water-cooled chillers last 20 to 25 years.
To summarize the comparison of air-cooled and water-cooled helical-rotary chillers, air-cooled chiller advantages include lower maintenance cost, a pre­packaged system for easier design and installation, and better low ambient operation. Water-cooled chiller advantages include greater energy efficiency (at least at design conditions) and longer equipment life.
Condensing Temperature Control
cooling tower
cooling tower
condenser
condenser
water
water
pump
pump
Condensing Temperature Control
All chillers require a minimum pressure difference between the evaporator and condenser to ensure proper management of oil and refrigerant. This minimum pressure difference depends on the chiller design and controls. The most common method of maintaining this pressure difference at the various load conditions is to control the condensing temperature by varying the temperature or flow rate of water (or air) flowing through the condenser. By controlling the condensing temperature, most helical-rotary water chillers can start and operate over a wide range of conditions.
condenser
condenser
Figure 48
Controlling condensing temperature: 1) maintains chiller efficiency, 2) maintains the required pressure differential between the evaporator and condenser for controlled flow through the refrigerant metering system, and 3) prevents the pressure imbalance that could cause oil loss problems.
Controlling the refrigerant pressure difference between the evaporator and condenser of an air-cooled chiller is accomplished by varying the flow rate of the air flowing through the condenser coils. This control is an integral part of the chiller design.
TRG-TRC012-EN 33
Page 39
notes
period five
Application Considerations
condensing temperature control
Cooling Tower Bypass
40°F
40°F
[4°C]
[4°C]
55°F
55°F
[13°C]
[13°C]
Controlling the refrigerant pressure difference between the evaporator and condenser of a water-cooled chiller is accomplished by varying the temperature or flow rate of the water flowing through the condenser. The following are 5 common methods used to control condensing temperature:
cooling tower
cooling tower
bypass
bypass
condenser
condenser
diverting
diverting
valve
valve
65°F
65°F
[18°C]
[18°C]
Figure 49
1) Controlling the temperature of the water leaving the cooling tower by cycling or varying the speed of the cooling tower fans
2) Using a cooling tower bypass pipe to mix warmer leaving-condenser water with the colder tower water and control the temperature entering the condenser as illustrated in the accompanying slide
3) Modulating a throttling valve to restrict the flow of water through the condenser
4) Using a chiller bypass pipe to vary the flow rate of water through the condenser
5) Employing a variable-speed drive on the condenser water pump to vary the water flow rate through the condenser
Each of these strategies has its advantages and disadvantages, and selection of the appropriate condensing temperature control scheme depends on the specific application.
The water flow rate through the chiller’s condenser must stay between the minimum and maximum condenser bundle flow rates as specified by the chiller manufacturer.
34 TRG-TRC012-EN
Page 40
notes
period five
Application Considerations
evaporator water flow…
Constant or Variable Flow
chilled
chilled
water
water
pump
pump
variable
variable
speed
speed
drive
drive
Constant or Variable Evaporator Water Flow
In previous designs, chillers were required to maintain a constant flow rate of water through the evaporator. This requirement has changed due to advances in chiller controls. Increased sensing and control capabilities now allow chiller manufacturers to design controls that monitor, and respond faster to, fluctuating conditions.
evaporator
evaporator
Figure 50
While the chiller may be able to handle variable water flow through the evaporator, the specific application of a chilled water system may not warrant variable flow. As always, each application should be analyzed to determine if variable evaporator water flow is warranted.
variable evaporator water flow
Limitations
Maintain minimum and maximum water flow
rates through the chiller evaporator
Rate at which evaporator water flow changes
must be kept below the corresponding limit to:
Maintain the chilled water set point control
Keep the chiller on line
Protect the chiller from damage
Figure 51
The controls on many current chiller designs can properly control the chiller in response to varying evaporator flow rates, with the following limitations:
TRG-TRC012-EN 35
Page 41
period five
Application Considerations
notes
1) The water flow rate through the chiller’s evaporator must stay between the minimum and maximum evaporator bundle flow rates as specified by the chiller manufacturer. These limits depend on the specific details of the actual evaporator bundle, such as the number of tubes, number of passes, and geometry of the bundle. A method for sensing evaporator water flow through each chiller is the only way to make sure the water flow rate stays within these limits.
2) The rate which the evaporator water flow rate changes must be kept below a specified level, which is dependent on the level of protection desired. For example, the maximum rate of change in order to maintain chilled water setpoint is more stringent than the maximum rate of change in order to keep the chiller on line. There are 3 common levels of protection desired: maintaining chilled water setpoint control, keeping the chiller on line, and protecting the chiller from damage.
The limits for these different levels of protection should be obtained from the chiller manufacturer.
Short Evaporator Water Loops
load
load
chilled
chilled
water
water
pump
pump
evaporator
evaporator
Figure 52
Short Evaporator Water Loops
Proper chilled water temperature control requires that the temperature of the chilled water returning to the evaporator not change any faster than the chiller controls can respond. The volume of water in the evaporator loop acts as a buffer and ensures a slowly changing return water temperature and, therefore, stable temperature control. If there is not a sufficient volume of water in the loop to provide an adequate buffer, temperature control can be lost, resulting in erratic system operation.
The chiller manufacturer should be consulted for volume requirements of the evaporator water loop.
36 TRG-TRC012-EN
Page 42
notes
period five
Application Considerations
Short Evaporator Water Loops
load
load
tank
tank
chilled
chilled
water
water
pump
pump
Short water loops may be unavoidable in close-coupled or very small applications, particularly in systems where the load consists of only a few air handlers or processes.
evaporator
evaporator
Figure 53
To prevent the effect of a short water loop, a storage tank or large header pipe can be added to the system to increase the volume of water in the loop and act as a buffer to ensure a slowly changing return water temperature.
TRG-TRC012-EN 37
Page 43
notes
period five
Application Considerations
equipment certification standards
ARI Standard 550/590
Purpose
Establish definitions and
testing and rating requirements
Scope
Factory designed and
prefabricated water chillers
Vapor-compression
refrigeration
Air-cooled and water-cooled
condensing
Figure 54
Equipment Certification Standards
The Air Conditioning & Refrigeration Institute (ARI) establishes rating standards for packaged HVAC equipment. ARI also certifies and labels equipment through
programs that involve random testing of a manufacturer’s equipment to verify published performance.
The overall objective of ARI Standard 550/590–1998 is to promote consistent rating and testing methods for all types and sizes of water chillers with an accurate representation of actual performance. It covers factory-designed, prefabricated water chillers, both air-cooled and water-cooled, using the vapor­compression refrigeration cycle.
38 TRG-TRC012-EN
Page 44
notes
period five
Application Considerations
equipment certification standards
ARI Standard 550/590
Standard rating conditions
Common system conditions for published ratings
Integrated Part Load Value (IPLV)
Part-load efficiency rating
Based on an “average” single-chiller installation
Standard operating conditions
Figure 55
The standard rating conditions used for ARI certification represent typical design temperatures and flow rates for which water-cooled and air-cooled systems are designed. They are not suggestions for good design practice for a given system, they are simply a common rating point. Trends toward improved humidity control and energy efficiency have changed some of the actual conditions selected for specific applications.
ARI’s part-load efficiency rating system establishes a single, blended estimate of stand-alone chiller performance. The Integrated Part Load Value (IPLV) calculator predicts chiller efficiency at the ARI standard rating conditions using weighted averages representing a broad range of geographic locations, building types, and operating-hour scenarios, both with and without an airside economizer. While the weighted averages place greater emphasis on the part­load operation of an average, single-chiller installation, they will not—by definition—represent any particular installation.
Additionally, ARI notes that more than 80 percent of all chillers are installed in multiple-chiller plants. Chillers in these plants exhibit different unloading characteristics than the IPLV weighted formula indicates. Appendix D of the Standard explains this further:
...The [IPLV] equation was derived to provide a representation of the average part-load efficiency for a single chiller only. However, it is best to use a comprehensive analysis that reflects actual weather data, building load characteristics, operational hours, economizer capabilities, and energy drawn by auxiliaries such as pumps and cooling towers, when calculating the chiller and system efficiency. This becomes increasingly important with multiple chiller systems because individual chillers operating within multiple chiller systems are more heavily loaded than single chillers within single chiller systems.
Remember that the ARI rating is a standardized representation. Many chillers do not run at standard rating conditions and few are applied in single-chiller installations. Performing a comprehensive energy analysis is the best method of comparing the system operating cost difference between 2 chillers.
TRG-TRC012-EN 39
Page 45
notes
period six
Review
Helical-Rotary Water Chillers
period six
Figure 56
Let’s review the main concepts that were covered in this clinic on helical-rotary water chillers.
Review—Period 1
motor
oil supply
oil supply
system
system
oil separator
oil separator
condenser
condenser
In Period 1, the following components of a helical-rotary water chiller were discussed: compressor, oil separator, oil supply system, condenser, expansion device, liquid/vapor separator, evaporator, starter, and controls.
compressor
compressor
motor
evaporator
evaporator
liquid/vapor
liquid/vapor
separator
separator
control
control
panel
panel
starter
starter
Figure 57
40 TRG-TRC012-EN
Page 46
notes
period six
Review
Review—Period 2
expansion
expansion
device
device
pressure
pressure
condenser
5
5
7
7
6
6
condenser
4
4
liquid/vapor
liquid/vapor
separator
separator
evaporator
evaporator
3
3
1
1
2
2
compressor
compressor
enthalpy
enthalpy
Figure 58
In Period 2, the refrigeration cycle of the helical-rotary water chiller was examined on a pressure-enthalpy chart. Also, the performance characteristics of the various refrigerants were compared.
Review—Period 3
axial
axial
discharge
discharge
port
port
slide valve
slide valve
In Period 3, the operation of the modulating slide valve was explained. The slide
valve is one method by which a helical-rotary compressor’s capacity is controlled.
radial
radial
discharge
discharge
port
port
Figure 59
TRG-TRC012-EN 41
Page 47
notes
period six
Review
Review—Period 4
Maintenance considerations
Operating log
Mechanical components
Heat transfer surfaces
Fluid analysis
Figure 60
In Period 4, the general maintenance requirements of a helical-rotary water chiller were discussed, including:
Recommended data to be logged daily
Required and recommended maintenance of the mechanical components
Required and recommended maintenance of the heat transfer surfaces
Recommended analysis of the oil and refrigerant
Review—Period 5
Application considerations
Air-cooled or water-cooled
Condensing temperature control
Constant or variable evaporator water flow
Short evaporator water loops
Equipment certification standards
Figure 61
In Period 5, several considerations in the application of helical-rotary water chillers were presented. These included air-cooled or water-cooled condensing, condensing temperature control, constant or variable evaporator water flow, short evaporator water loops, and equipment certification standards.
42 TRG-TRC012-EN
Page 48
notes
period six
Review
Figure 62
For more information, refer to the following references:
Trane product catalogs for helical-rotary water chiller products
(Trane literature order numbers RLC-DS-1, RLC-DS-2, RLC-DS-4, and RLC-DS-6)
®
Water-Cooled Series R
(RLC-EB-16)
®
Series R
(RLC-EB-4)
Multiple Chiller System Design And Control (CON-AM-21)
ARI Standard 550/590–1998: Implications For Chilled-Water Plant Design
(Trane
ASHRAE Handbook—Refrigeration
ASHRAE Handbook—Systems and Equipment
Visit the ASHRAE Bookstore at www.ashrae.org.
For information on additional educational materials available from Trane, contact your local Trane sales office (request a copy of the Educational Materials price sheet — Trane order no. EM-ADV1) or visit our online bookstore at www.trane.com/bookstore/.
CenTraVac® Chiller Condensing Water Temperature Control
Engineers Newsletter
Chiller—Model RTHC Mechanical Operation
, 1999—volume 28, no. 1)
TRG-TRC012-EN 43
Page 49
Quiz
Questions for Period 1
1 What components of the helical-rotary compressor are used to compress
the refrigerant?
2 What are the 2 functions of the oil supply system presented in this clinic?
3 In a flooded shell-and-tube evaporator, is the refrigerant flowing inside or
outside of the tubes?
4 Name 2 types of expansion devices commonly found in helical-rotary water
chillers.
Questions for Period 2
5
pressure
pressure
5
3
4
4
7
7
6
6
enthalpy
enthalpy
3
2
2
1
1
Figure 63
5 Using the pressure-enthalpy diagram in Figure 63, identify the following
processes of the helical-rotary water chiller’s refrigeration cycle:
a) to b) to c) to d) to
6 Referring again to Figure 63, after the vapor is removed in the liquid/vapor
separator, to which point in the refrigeration cycle does it travel?
44 TRG-TRC012-EN
Page 50
Quiz
Questions for Period 3
7 At full load, is the slide valve fully closed or fully open?
8 Explain how the slide valve varies the refrigerant flow rate through the
helical-rotary compressor.
Questions for Period 4
9 What document recommends the data points to be logged daily for each
chiller?
10 List 3 advantages to performing a regular oil analysis on a helical-rotary
water chiller.
Questions for Period 5
11 List 3 common methods of controlling condensing pressure in a water-
cooled chiller.
12 What are the 2 primary limitations with varying the flow rate of water
through the chiller evaporator?
TRG-TRC012-EN 45
Page 51
Answers
1 Male and female screw rotors
2 Bearing lubrication and cooling, and rotor oil injection
3 Outside of the tubes
4 Electronic expansion valve and orifice plate
5) a) compression
b) condensation (desuperheat, condense, subcool)
c) expansion
d) evaporation
6 Point 1, the suction inlet of the compressor
7 Fully closed
8 At part load, the opening created by the slide valve movement allows
refrigerant vapor to bypass from the rotor pockets back to the suction side of the compressor. This reduces the volume of vapor available for the compression process. It also reduces the amount of rotor length available for compression.
9 ASHRAE Guideline 3
10 Helps reduce maintenance costs, detects problems without compressor
disassembly, oil charges last longer, less environmental problems with
disposing of used oil, helps maintain the compressor’s efficiency and reliability, and helps lower refrigerant emissions.
11 Cycling or varying the speed of the cooling tower fans, using a cooling
tower bypass pipe, modulating a throttling valve, using a chiller bypass pipe, or employing a variable-speed drive on the condenser water pump.
12 The water flow rate through the chiller’s evaporator must stay between the
minimum and maximum evaporator bundle flow rates as specified by the chiller manufacturer. The rate which the evaporator water flow rate changes must be kept below a specified level.
46 TRG-TRC012-EN
Page 52
Glossary
air-cooled condenser A type of condenser that rejects the heat of the
refrigerant to air flowing through it.
ARI Air Conditioning & Refrigeration Institute
ARI Standard 550/590 A publication, titled “Standard for Water Chilling
Packages Using the Vapor-Compression Cycle”, used to promote consistent rating and testing methods for all types and sizes of water chillers. It covers factory-designed, prefabricated water chillers, both air-cooled and water­cooled, using the vapor-compression refrigeration cycle.
ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers
ASHRAE Guideline 3 A publication, titled “Reducing Emission of Halogenated Refrigerants in Refrigeration and Air Conditioning Equipment and Systems”, that includes a recommended list of data points to be logged daily for each water chiller.
compressor The mechanical device used by the chiller to increase the pressure and temperature of the refrigerant vapor.
condenser The region of the chiller where refrigerant vapor is converted to liquid as it rejects heat to water or air.
control panel The microprocessor-based panel that monitor the chiller’s operation, protects it from damage, provides the operator with data and diagnostic messages, and permits interfacing with a building automation system.
direct expansion (DX) shell-and-tube evaporator A type of evaporator where refrigerant flows through the tubes and water fills the surrounding shell.
electronic expansion valve A type of expansion device that uses an electronically-actuated valve to sense and control the flow rate of liquid refrigerant to the evaporator.
enthalpy The property of a refrigerant indicating its total heat content, both sensible and latent.
evaporator The region of the chiller where the system chilled water is continuously cooled by flashing the refrigerant to vapor as it picks up heat from the returning chilled water.
expansion device The component of the chiller used to reduce the pressure and temperature of the refrigerant.
flooded shell-and-tube evaporator A type of evaporator where water flows through the tubes and refrigerant fills the surrounding shell.
liquid/vapor separator The component of the chiller used to remove vapor from the refrigerant mixture after it passes through the expansion device. This
TRG-TRC012-EN 47
Page 53
Glossary
vapor is directed back to the compressor while the liquid refrigerant travels on to the evaporator.
oil separator The component of the chiller used to remove oil from the refrigerant vapor after it is discharged from the compressor. This oil is directed back to the compressor.
orifice plate A type of expansion device that uses a fixed plate with holes drilled in it to meter the flow rate of refrigerant to the evaporator.
ported compressors A type of compressor where the refrigerant vapor enters
and exits through ports—no valves are used.
pressure-enthalpy diagram A graphical representation of the saturated properties of a refrigerant, plotting refrigerant pressure versus enthalpy.
rotor The part of the helical-rotary compressor used to trap and compress the refrigerant vapor. The male and female rotors mesh together forming pockets of refrigerant to move through the compressor.
slide valve The part of the helical-rotary compressor used to vary the flow rate of refrigerant vapor through it.
subcooler The lower portion of the condenser that further cools the saturated liquid refrigerant.
water-cooled condenser A type of condenser that rejects the heat of the refrigerant to water flowing through it.
48 TRG-TRC012-EN
Page 54
BUSINESS REPLY MAIL
FIRST-CLASS MAIL LA CROSSE, WIPERMIT NO. 11
POST AGE WILL BE PAID BY ADDRESSEE
THE TRANE COMPANY Attn: Applications Engineering 3600 Pammel Creek Road La Crosse WI 54601-9985
NO POSTAGE NECES SARY IF MAILED IN THE UNITED STATES
BUSINESS REPLY MAIL
FIRST-CLASS MAIL LA CROSSE, WIPERMIT NO. 11
POST AGE WILL BE PAID BY ADDRESSEE
THE TRANE COMPANY Attn: Applications Engineering 3600 Pammel Creek Road La Crosse WI 54601-9985
NO POSTAGE NECES SARY IF MAILED IN THE UNITED STATES
Page 55
Comment Card
We want to ensure that our educational materials meet your ever-changing resource development needs. Please take a moment to comment on the effectiveness of this Air Conditioning Clinic.
Helical-Rotary Water Chillers
One of the Equipment Series
TRG-TRC012-EN
About me … Type of business _________________________________________________________
Give the completed card to the presenter or drop it in the mail. Thank you!
Level of detail (circle one) Too basic Just right Too difficult
Rate this clinic from 1–Needs Improvement to 10–Excellent …
Content 1 2 3 4 5 6 7 8 9 10
Booklet usefulness12345678910
Slides/illustrations 1 2 3 4 5 6 7 8 9 10
Presenters ability 12345678910
Training environment 1 2 3 4 5 6 7 8 9 10
Other comments? _________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________
Job function _________________________________________________________ Optional: name _________________________________________________________
phone _________________________________________________________ address _________________________________________________________
The Trane Company • Worldwide Applied Systems Group 3600 Pammel Creek Road • La Crosse, WI 54601-7599 www.trane.com
An American-Standard Company
Response Card
We offer a variety of HVAC-related educational materials and technical references, as well as software tools that simplify system design/analysis and equipment selection. To receive information about any of these items, just complete this postage-paid card and drop it in the mail.
Education materials Air Conditioning Clinic series About me …
Engineered Systems Clinic series Name ____________________________________________
Trane Air Conditioning Manual Title ____________________________________________
Trane Systems Manual Business type ____________________________________________
Software tools Equipment selection Phone/fax _____________________ _____________________
System design & analysis E-mail address ____________________________________________
Periodicals Engineers Newsletter Company ____________________________________________
Other? _____________________________ Address ____________________________________________
Thank you for your interest!
____________________________________________ ____________________________________________
The Trane Company • Worldwide Applied Systems Group 3600 Pammel Creek Road • La Crosse, WI 54601-7599 www.trane.com
An American-Standard Company
Page 56
The Trane Company
Worldwide Applied Systems Group 3600 Pammel Creek Road La Crosse, WI 54601-7599 www.trane.com
An American Standard Company
Literature Order Number TRG-TRC012-EN
File Number E/AV-FND-TRG-TRC012-899-EN
Supersedes 2803-15-888
Stocking Location Inland-La Crosse
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
Loading...