The Trane Company—
Worldwide Applied Systems Group
Preface
Helical-Rotary Water Chillers
A Trane Air Conditioning Clinic
Figure 1
The Trane Company believes that it’s incumbent on manufacturers to serve the
industry by regularly disseminating information gathered through laboratory
research, testing programs and field experience.
The Trane Air Conditioning Clinic series is one means of knowledge sharing.
It’s intended to acquaint a nontechnical audience with various fundamental
aspects of heating, ventilating, and air conditioning.
We’ve taken special care to make the clinic as uncommercial and
straightforward as possible. Illustrations of Trane products only appear in cases
where they help convey the message contained in the accompanying text.
This particular clinic introduces the reader to the concept of helical-rotary water chillers.
Water chillers are used in a variety of air conditioning and process cooling
applications. They are used to make cold water that can be transported
throughout a facility using pumps and pipes. This cold water can be passed
through the tubes of coils in order to cool the air in an air conditioning
application or it can provide cooling for a manufacturing or industrial process.
Systems that employ water chillers are commonly called chilled water systems.
absorption
helical-rotary
There are several types of water chillers that are differentiated by the
refrigeration cycle they use or the type of compressor.
Absorption water chillers make use of the absorption refrigeration cycle and do
not have a mechanical compressor involved in the refrigeration cycle.
Absorption water chillers are the subject of a separate clinic.
centrifugal
Figure 3
TRG-TRC012-EN1
Introduction
notes
Water chillers using the vapor-compression refrigeration cycle vary by the type
of compressor used. Reciprocating and scroll compressors are typically used in
smaller chillers. Helical-rotary (or screw) compressors are typically used in
medium-sized chillers. Centrifugal compressors are typically used in larger
chillers.
As mentioned earlier, this particular clinic discusses helical-rotary water chillers.
Helical-Rotary Water Chillers
water-cooled
air-cooled
Figure 4
Helical-rotary water chillers can be either air-cooled or water-cooled, referring
to the method of rejecting heat to the atmosphere. Both air-cooled and watercooled helical-rotary chillers are generally available from 70 to 450 tons [200 to
1500 kW].
The primary focus in Period 1 is on the water-cooled chiller, although it includes
some discussion of air-cooled chiller components. A comparison of air-cooled
versus water-cooled chiller applications is included in Period 5.
2TRG-TRC012-EN
notes
period one
Components
Helical-Rotary Water Chillers
period one
Figure 5
Many of the components of the helical-rotary water chiller are similar to those
of other chiller types.
components of a
Helical-Rotary Water Chiller
motor
oil supply
oil supply
system
system
oil separator
oil separator
condenser
condenser
This particular helical-rotary water chiller makes use of a shell-and-tube
evaporator where refrigerant evaporates inside the shell and water flows inside
tubes. The compressor is a twin-rotor, helical-rotary compressor. It uses a
suction-gas-cooled motor to operate the compressor. Another shell-and-tube
heat exchanger is used for the condenser, where refrigerant is condensed
inside the shell and water flows inside tubes. Refrigerant is metered through
the system using an electronic expansion valve. A liquid/vapor separator can be
used to enhance the effectiveness of the refrigeration cycle. An oil supply
system provides near oil-free refrigerant to the shells to maximize heat transfer
performance while providing lubrication and rotor sealing to the helical-rotary
compressor. A control panel is also provided on the chiller, and a starter
connects the chiller motor to the electrical distribution system.
compressor
compressor
motor
evaporator
evaporator
liquid/vapor
liquid/vapor
separator
separator
control
control
panel
panel
starter
starter
Figure 6
TRG-TRC012-EN3
notes
period one
Components
compressor...
Helical Rotors
Figure 7
Compressor
The helical-rotary chiller uses 2 screw-like rotors to perform the compression
process.
compressor...
Helical Rotors
female rotor
female rotor
male rotor
male rotor
housing
housing
slide valve
slide valve
The rotors are meshed and fit, with very close tolerances, within a housing.
Only the male rotor is driven by the compressor motor. The lobes of the male
rotor engage and drive the female rotor, causing the 2 parts to counter-rotate.
Figure 8
4TRG-TRC012-EN
notes
period one
Components
compressor...
Helical Rotors
intake
intake
port
port
Figure 9
In the operation of the helical-rotary compressor, refrigerant vapor enters the
compressor housing through the intake port. The intake port in this example
is at the top of the compressor housing.
compressor...
Helical Rotors
intake
intake
port
port
pocket of refrigerant vapor
pocket of refrigerant vapor
The entering refrigerant vapor is at a low, suction pressure and fills the grooves
or pockets formed by the lobes of the rotors. As the rotors turn, they push the
pockets of refrigerant toward the discharge end of the compressor.
Figure 10
TRG-TRC012-EN5
notes
period one
Components
compressor...
Helical Rotors
intake port
intake port
discharge port
discharge port
Figure 11
Viewing the compressor from the side shows that after the pockets of
refrigerant travel to the right past the intake port area, the vapor, still at suction
pressure, is confined within the pockets by the compressor housing.
compressor...
Helical Rotors
discharge port
discharge port
meshing point
meshing point
Viewing the compressor from the top shows that rotation of the meshed rotor
lobes drives the trapped refrigerant vapor (to the right) ahead of the meshing
point.
Figure 12
6TRG-TRC012-EN
notes
period one
Components
compressor...
Helical Rotors
discharge port
discharge port
meshing point
meshing point
Continued rotation of the rotors causes the meshing point to travel toward the
discharge end of the compressor, driving the trapped refrigerant vapor ahead of
it. This action progressively reduces the volume of the pockets, compressing
the refrigerant.
Figure 13
compressor...
Helical Rotors
discharge port
discharge port
meshing point
meshing point
Finally, when the pockets of refrigerant reach the discharge port the
compressed vapor is released. As the rotors continue to rotate, the volume of
the pockets is further reduced, squeezing the remaining refrigerant from the
cavities.
Notice that the refrigerant vapor enters and exits the compressor through
ports—no valves are used. Compressors of this design are called ported
compressors.
Figure 14
TRG-TRC012-EN7
notes
period one
Components
Oil Separator
refrigerant vapor
refrigerant vapor
to condenser
to condenser
refrigerant vapor
refrigerant vapor
and oil mixture
and oil mixture
oil return to sump
oil return to sump
Oil Separator
The oil leaves the compressor entrained within the discharged refrigerant
vapor.
Figure 15
The oil is recovered from the discharged refrigerant by an oil separator, which
can have an efficiency of greater than 99%. The separator consists of a vertical
cylinder surrounding an exit passageway. As the refrigerant-and-oil mixture is
discharged into this passageway the oil is forced outward by centrifugal force,
collects on the walls of the cylinder, and drains to the bottom. This accumulated
oil drains out of the cylinder and collects in the oil sump located near the
bottom of the chiller.
The oil sump is heated to ensure proper lubrication and minimize refrigerant
condensation in the sump.
Oil Supply System
oil
refrigerant
refrigerant
vapor to
vapor to
condenser
condenser
oil tank
oil tank
sump
sump
oil filter
oil filter
oil
separator
separator
master
master
solenoid
solenoid
valve
valve
rotor bearings
rotor bearings
rotor
rotor
2
2
compressor
compressor
1
1
Figure 16
Oil that collects in the oil sump is at condensing pressure during compressor
8TRG-TRC012-EN
period one
Components
notes
operation and is, therefore, constantly moving to lower pressure areas of the
chiller. In this system, oil flows in 2 distinct paths, each performing a separate
function: 1) bearing lubrication and cooling and 2) rotor oil injection.
Oil leaves the sump and passes through an oil filter and master solenoid valve.
The master solenoid valve is used to isolate the sump from the low-pressure
side of the system when the compressor is shut down, preventing oil migration.
The first path is for lubricating and cooling the compressor bearings ➀. Oil is
routed to the bearings located in the rotor and bearing housing. Each housing is
vented to the suction side of the compressor so that oil leaving the bearings is
routed through the rotors, to the oil separator, and then back to the oil sump.
The second path is for lubricating and sealing the compressor rotors ➁. Oil is
injected along the bottom or top of the compressor rotors inside the housing.
Its main purpose is to seal the rotor-to-rotor and rotor-to-housing clearances.
This seal provides a barrier between the high- and low-pressure cavities of the
compressor. Additionally, oil lubricates the male-to-female rotor drive
arrangement.
water-cooled
Condenser
refrigerant vapor
refrigerant vapor
baffle
baffle
cooling
cooling
tower
tower
water
water
tube bundle
tube bundle
subcooler
subcooler
liquid
liquid
refrigerant
refrigerant
Figure 17
Condenser
The high-pressure refrigerant vapor, now stripped of oil droplets, leaves the oil
separator and continues on to the condenser.
In a water-cooled condenser, water is pumped through the tubes of this
shell-and-tube heat exchanger while refrigerant vapor fills the shell space
surrounding the tubes. The condenser has a baffle plate that helps distribute
the refrigerant evenly within the shell. As heat is transferred from hot, highpressure refrigerant vapor to the water, refrigerant condenses on the tube
surfaces.
The condensed liquid refrigerant then collects in the bottom of the shell where
the lower tubes are now submerged, resulting in further cooling, or subcooling,
of the refrigerant. This arrangement is called an integral subcooler.
TRG-TRC012-EN9
period one
Components
notes
Cooling water flows first through the lower tubes of the condenser and then
through the upper tubes. This produces a nearly constant temperature
difference between the downward moving refrigerant and the tube surfaces,
resulting in a uniform heat transfer rate within the tube bundle.
Subcooled liquid refrigerant leaves the condenser (subcooler) and flows
through the liquid line to the expansion device.
air-cooled
Condenser
propeller fan
propeller fan
subcooler
subcooler
In a typical air-cooled condenser, propeller-type fans are used to draw
outdoor air over a fin-tube heat transfer surface. The hot, high-pressure
refrigerant vapor flows through the tubes as heat is transferred to the cooler
outdoor air. The resulting reduction in the heat content of the refrigerant vapor
causes it to condense into liquid. Within the final few lengths of condenser
tubing the condensed liquid refrigerant is subcooled.
condenser
condenser
coil
coil
outdoor air
outdoor air
Figure 18
Again, subcooled liquid refrigerant leaves the condenser (subcooler) and flows
through the liquid line to the expansion device.
The differences between water-cooled and air-cooled chiller applications will be
discussed further in Period 5.
10TRG-TRC012-EN
notes
period one
Components
expansion device…
Electronic Expansion Valve
Figure 19
Expansion Device
An expansion device is used to maintain the pressure difference between the
high-pressure (condenser) and low-pressure (evaporator) sides of the system,
as established by the compressor. This pressure difference allows the
evaporator temperature to be low enough to absorb heat from the water being
cooled, while also allowing the refrigerant to be at a high enough temperature
in the condenser to reject heat to air or water at normally available
temperatures. High-pressure liquid refrigerant flows through the expansion
device, causing a large pressure drop that reduces the refrigerant pressure to
that of the evaporator. This pressure reduction causes a small portion of the
liquid to boil off, or flash, cooling the remaining refrigerant to the desired
evaporator temperature.
In this chiller, the expansion device used is an electronic expansion valve. In
addition to maintaining the high- and low-side pressure difference, the
electronic expansion valve controls the quantity of liquid refrigerant entering
the evaporator to ensure that it will be completely vaporized within the
evaporator.
TRG-TRC012-EN11
notes
period one
Components
expansion device…
Orifice Plates
to
orifice plates
orifice plates
H
H
The orifice plate is another type of expansion device found in helical-rotary
chillers. The column of liquid refrigerant creates a head pressure at its base,
allowing it to pass through the orifices and undergo a pressure drop equal to
the head (H) before it flashes. As the load decreases, less refrigerant is moved
throughout the chiller, causing the level of the liquid column to drop. This
causes additional flashing at the orifice plate which, in turn, results in feeding
less liquid to the evaporator.
to
evaporator
evaporator
Figure 20
Liquid/Vapor Separator
refrigerant vapor
refrigerant vapor
to compressor
to compressor
liquid refrigerant
from
from
expansion
expansion
device
device
Liquid/Vapor Separator
The mixture of liquid and vapor refrigerant that leaves the expansion device
enters a liquid/vapor separator. Here the liquid refrigerant settles to the
bottom of the chamber and the vapor is drawn off the top and routed directly to
the suction side of the compressor. The remaining liquid refrigerant is then
routed to the evaporator.
12TRG-TRC012-EN
liquid refrigerant
to evaporator
to evaporator
Figure 21
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.