Trane TRG-TRC010-EN User Manual

Page 1
Air Conditioning Clinic
Centrifugal Water Chillers
One of the Equipment Series
TRG-TRC010-EN
Page 2
BUSINESS REPLY MAIL
FIRST-CLASS MAIL LA CROSSE, WIPERMIT NO. 11
POSTAGE WILL BE PAID BY ADDRESSEE
THE TRANE COMPANY Attn: Applications Engineering 3600 Pammel Creek Road La Crosse WI 54601-9985
BUSINESS REPLY MAIL
FIRST-CLASS MAIL LA CROSSE, WIPERMIT NO. 11
POSTAGE WILL BE PAID BY ADDRESSEE
THE TRANE COMPANY Attn: Applications Engineering 3600 Pammel Creek Road La Crosse WI 54601-9985
&URSWRZLGWKRIµ
Page 3
3HUIRUDWLRQµIURPHGJH 3HUIRUDWLRQµIURPERWWRPWRS
'SQQIRX'EVH
;I[ERXXSIRWYVIXLEXSYVIHYGEXMSREPQEXIVMEPWQIIX]SYVIZIVGLERKMRKVIWSYVGIHIZIPSTQIRXRIIHW 4PIEWIXEOIEQSQIRXXSGSQQIRXSRXLIIJJIGXMZIRIWWSJXLMW%MV'SRHMXMSRMRK'PMRMG
'IRXVMJYKEP;EXIV'LMPPIVW
3RISJXLI)UYMTQIRX7IVMIW
86+86')2
%FSYXQI|
+MZIXLIGSQTPIXIHGEVHXSXLI TVIWIRXIVSVHVSTMXMRXLIQEMP 8LERO]SY
0IZIPSJHIXEMPGMVGPISRI 8SSFEWMG .YWXVMKLX 8SSHMJJMGYPX
6EXIXLMWGPMRMGJVSQr2IIHW-QTVSZIQIRXXSr)\GIPPIRX|
'SRXIRX  &SSOPIXYWIJYPRIWW  7PMHIWMPPYWXVEXMSRW  4VIWIRXIVWEFMPMX]  8VEMRMRKIRZMVSRQIRX  3XLIVGSQQIRXW# CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
8]TISJFYWMRIWW CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC .SFJYRGXMSR CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC 3TXMSREP REQI CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
TLSRI CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC EHHVIWW CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
8LI8VERI'SQTER]w;SVPH[MHI%TTPMIH7]WXIQW+VSYT 4EQQIP'VIIO6SEHw0E'VSWWI;-  [[[XVERIGSQ
%R%QIVMGER7XERHEVH'SQTER]
6IWTSRWI'EVH
;ISJJIVEZEVMIX]SJ,:%'VIPEXIHIHYGEXMSREPQEXIVMEPWERHXIGLRMGEPVIJIVIRGIWEW[IPPEWWSJX[EVIXSSPW XLEXWMQTPMJ]W]WXIQHIWMKREREP]WMWERHIUYMTQIRXWIPIGXMSR8SVIGIMZIMRJSVQEXMSREFSYXER]SJXLIWI MXIQWNYWXGSQTPIXIXLMWTSWXEKITEMHGEVHERHHVSTMXMRXLIQEMP
)HYGEXMSRQEXIVMEPW
7SJX[EVIXSSPW
4IVMSHMGEPW
3XLIV#
8LERO]SYJSV]SYVMRXIVIWX
%MV'SRHMXMSRMRK'PMRMGWIVMIW )RKMRIIVIH7]WXIQW'PMRMGWIVMIW 2EQI CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC 8VERI%MV'SRHMXMSRMRK1ERYEP 8MXPI CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC 8VERI7]WXIQW1ERYEP &YWMRIWWX]TI CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
)UYMTQIRXWIPIGXMSR 4LSRIJE\ CCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCC 7]WXIQHIWMKREREP]WMW )QEMPEHHVIWW CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
)RKMRIIVW2I[WPIXXIV 'SQTER] CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
CCCCCCCCCCCCCCCCCCCCCCCCCCCCC %HHVIWW CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
%FSYXQI|
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
8LI8VERI'SQTER]w;SVPH[MHI%TTPMIH7]WXIQW+VSYT 4EQQIP'VIIO6SEHw0E'VSWWI;-  [[[XVERIGSQ
%R%QIVMGER7XERHEVH'SQTER]
Page 4
Centrifugal Water Chillers
One of the Equipment Series
A publication of
The Trane Company— Worldwide Applied Systems Group
Page 5
Preface
Centrifugal Water Chillers
A Trane Air Conditioning Clinic
Figure 1
The Trane Company believes that it is incumbent on manufacturers to serve the industry by regularly disseminating information gathered through laboratory research, testing programs, and field experience.
The Trane Air Conditioning Clinic series is one means of knowledge sharing.
It’s intended to acquaint a nontechnical audience with various fundamental aspects of heating, ventilating, and air conditioning.
We’ve taken special care to make the clinic as uncommercial and straightforward as possible. Illustrations of Trane products only appear in cases where they help convey the message contained in the accompanying text.
This particular clinic introduces the concept of centrifugal water chillers.
© 1999 American Standard Inc. All rights reserved
ii
TRG-TRC010-EN
Page 6
Contents
Introduction ........................................................... 1
period one Components .......................................................... 3
Compressor ............................................................ 4
Condenser .............................................................. 7
Expansion Device .................................................... 8
Economizer ............................................................. 9
Evaporator ............................................................ 11
Motor ................................................................... 12
Controls and Starter .............................................. 13
period two Refrigeration Cycle ............................................ 15
Refrigerants .......................................................... 19
Purge System ....................................................... 20
period three Compressor Capacity Control ........................ 22
period four Maintenance Considerations .......................... 30
period five Application Considerations ............................. 36
Condensing Temperature Control .......................... 37
Constant or Variable Evaporator Water Flow .......... 39
Short Evaporator-Water Loops ............................... 40
Heat Recovery ...................................................... 42
Free Cooling .......................................................... 44
Equipment Certification Standards ......................... 46
period six Review ................................................................... 48
Quiz ......................................................................... 52
Answers ................................................................ 54
Glossary ................................................................ 55
TRG-TRC010-EN iii
Page 7
iv TRG-TRC010-EN
Page 8
notes
Introduction
Chilled Water System
Figure 2
Water chillers are used in a variety of air conditioning and process cooling applications. They are used to make cold water that can be transported throughout a facility using pumps and pipes. This cold water can be passed through the tubes of coils to cool the air in an air conditioning application, or it can provide cooling for a manufacturing or industrial process.
Systems that employ water chillers are commonly called chilled water systems.
absorption
helical-rotary
There are several types of water chillers. They differ from each other based on the refrigeration cycle or the type of compressor they use.
Absorption water chillers make use of the absorption refrigeration cycle and do not have a mechanical compressor involved in the refrigeration cycle.
centrifugal
Figure 3
TRG-TRC010-EN 1
Page 9
Introduction
notes
Water chillers using the vapor-compression refrigeration cycle vary by the type of compressor used. Reciprocating and scroll compressors are typically used in small chillers. Helical-rotary (or screw) compressors are typically used in medium-sized chillers. Centrifugal compressors are typically used in large chillers.
As mentioned earlier, this particular clinic discusses centrifugal water chillers.
Centrifugal Water Chillers
Figure 4
Centrifugal water chillers can also be divided into two types based on the method used to reject heat to the atmosphere: water-cooled or air-cooled. Since most centrifugal chillers are water-cooled, they are the primary focus of this clinic. Water-cooled centrifugal chillers are generally available from 100 to 3,000 tons [350 to 10,500 kW] as prefabricated machines, and up to 8,500 tons [30,000 kW] as built-up machines.
2 TRG-TRC010-EN
Page 10
notes
period one
Components
Centrifugal Water Chillers
period one
Figure 5
Many of the components of the centrifugal water chiller are similar to those of other chiller types.
components of a
Centrifugal Water Chiller
compressor
compressor
condenser
condenser
control
control
panel
panel
evaporator
evaporator
This particular centrifugal water chiller makes use of a shell-and-tube evaporator where refrigerant absorbs heat from the water flowing through the tubes. The compressor is made up of 1 or more centrifugal impellers. A second shell-and-tube heat exchanger serves as the water-cooled condenser, where refrigerant is condensed inside the shell and water flows inside tubes. Refrigerant is metered through the system using an expansion device such as a fixed orifice plate. An economizer can be used to enhance the efficiency of a chiller with multiple compressor impellers. A control panel is also provided on the chiller and a starter is either mounted on the chiller or located remotely.
motor
motor
starter
starter
Figure 6
TRG-TRC010-EN 3
Page 11
notes
period one
Components
Compressor
Figure 7
Compressor
The centrifugal compressor uses the principle of dynamic compression, which involves converting energy from one form to another, to increase the pressure and temperature of the refrigerant. It converts kinetic energy to static energy.
Impeller
blades
blades
Figure 8
The core component of a centrifugal compressor is the rotating impeller. The center, or eye, of the impeller is fitted with blades that draw refrigerant vapor into radial passages that are internal to the impeller body.
4 TRG-TRC010-EN
Page 12
notes
period one
Components
Centrifugal Compressor
volute
volute
diffuser
diffuser
passage
passage
impeller
impeller
passages
passages
Figure 9
The rotation of the impeller causes the refrigerant vapor to accelerate within the impeller passages, increasing its velocity and kinetic energy.
The accelerated refrigerant vapor leaves the impeller and enters the diffuser passages. These passages start out small and become larger as the refrigerant travels through them. As the size of the diffuser passages increases, the velocity, and therefore the kinetic energy, of the refrigerant decreases.
The first law of thermodynamics states that energy is not destroyed—only converted from one form to another. Thus, the refrigerant’s kinetic energy is converted to static energy or static pressure.
Refrigerant, now at a higher pressure, collects in a larger space around the perimeter of the compressor called the volute. The volute also becomes larger as the refrigerant travels through it. Again, as the size of the volute increases, the kinetic energy is converted to static pressure.
Due to its pressure and temperature, the refrigerant leaving the compressor is in a condition that allows its heat to be rejected from the chiller.
TRG-TRC010-EN 5
Page 13
notes
period one
Components
centrifugal compressor
Energy Conversion
refrigerant
refrigerant
enters
enters
diffuser
diffuser
velocity
velocity
refrigerant
refrigerant
refrigerant
enters impeller
enters impeller
static pressure
static pressure
path through compressor
path through compressor
Again, in the passages of the rotating impeller, the refrigerant vapor accelerates, increasing its velocity and kinetic energy. As the area increases in the diffuser passages, the velocity, and therefore the kinetic energy, of the refrigerant decreases. This reduction in kinetic energy is offset by an increase in
the refrigerant’s static energy or static pressure. Finally, the high pressure refrigerant collects in the volute around the perimeter of the compressor, where further energy conversion takes place.
refrigerant
enters volute
enters volute
Figure 10
The resulting pressure and temperature of the refrigerant is now high enough that its heat can be rejected from the chiller.
Multistage Compressor
Figure 11
Centrifugal compressors use 1 or more impellers to compress the refrigerant. A multistage compressor uses 2 or 3 impellers to increase the pressure of the refrigerant in steps instead of performing the task within a single impeller. Compressed refrigerant vapor travels from the outlet of the first-stage compressor impeller to the inlet of the second-stage compressor impeller. After
6 TRG-TRC010-EN
Page 14
period one
Components
notes
the accelerated refrigerant vapor leaves the last impeller, it collects in the compressor volute and travels on to the condenser.
Condenser
refrigerant vapor
refrigerant vapor
baffle
baffle
cooling
cooling
tower
tower
water
water
liquid
tube
tube
bundle
bundle
Condenser
The high-pressure refrigerant vapor is discharged from the compressor into a heat exchanger that acts as a condenser.
In a water-cooled condenser, water is pumped through the tubes of the shell- and-tube heat exchanger while refrigerant vapor fills the shell space surrounding the tube bundle. A baffle inside the condenser helps distribute the refrigerant evenly. As heat transfers from the hot, high-pressure refrigerant vapor to the water, refrigerant condenses on the tube surfaces.
liquid
refrigerant
refrigerant
Figure 12
Cooling water flows first through the lower tubes and then through the upper tubes. This produces a nearly constant temperature difference between the downward-moving refrigerant and the tube surfaces, resulting in a uniform heat transfer rate within the tube bundle.
Condensed liquid refrigerant collects in the bottom of the shell and flows through the liquid line to the expansion devices and economizer.
TRG-TRC010-EN 7
Page 15
notes
period one
Components
expansion device
Orifice Plates
orifice plates
orifice plates
H
H
1
1
Expansion Device
An expansion device is used to maintain the pressure difference between the high-pressure (condenser) and low-pressure (evaporator) sides of the refrigeration system, as established by the compressor. This pressure difference allows the evaporator temperature to be low enough for the refrigerant to absorb heat from the water being cooled, and the condenser temperature to be high enough for the refrigerant to reject heat to water at normally available temperatures. High-pressure liquid refrigerant flows through the expansion device, causing a pressure drop that reduces the refrigerant pressure to that of the evaporator. This pressure reduction causes a small
portion of the liquid to boil off, or “flash,” cooling the remaining refrigerant to the evaporator temperature.
to
to
evaporator
evaporator
Figure 13
The expansion device is also used as a liquid refrigerant metering system, balancing the refrigerant flow rate with the evaporator load condition. In our example centrifugal chiller, the expansion device used is a set of 2 orifice plates. At full load, a large amount of refrigerant is moving through the chiller. The column of liquid refrigerant in the liquid line pressurizes the liquid at its base. During passage through the orifice plates, the liquid refrigerant undergoes a pressure drop equal to the head (H vapor.
8 TRG-TRC010-EN
) before some of it flashes to
1
Page 16
notes
period one
Components
expansion device
Orifice Plates
orifice plates
orifice plates
H
H
2
2
As the load decreases, less refrigerant moves through the chiller and the level of the liquid column drops. Now, as the liquid refrigerant passes through the orifice plates, it only undergoes a pressure drop equal to the lower head (H before some of it flashes to vapor. This causes additional flashing at the orifice plate which, in turn, feeds less liquid to the evaporator.
to
to
evaporator
evaporator
Figure 14
)
2
Other types of expansion devices found in centrifugal chillers include: float valves, expansion valves (thermostatic or electronic), and variable orifices.
2-stage chiller
Economizer
refrigerant vapor
refrigerant vapor
to second stage
to second stage
of compression
of compression
liquid refrigerant
orifice
orifice
liquid refrigerant
liquid refrigerant
from condenser
from condenser
Economizer
An economizer can be used in conjunction with multiple expansion devices to improve the efficiency of a multistage chiller. In a chiller with a 2-stage compressor, the expansion process can be separated into 2 steps with an economizer chamber between.
liquid refrigerant
to evaporator
to evaporator
Figure 15
TRG-TRC010-EN 9
Page 17
period one
Components
notes
Liquid refrigerant from the condenser enters the first expansion device, which reduces the pressure of the refrigerant to that of the second-stage impeller inlet. This pressure drop causes a portion of the liquid refrigerant to evaporate, or flash, and the resulting mixture of liquid and vapor enters the economizer chamber. Here, the vapor is separated from the mixture and is routed directly to the inlet of the second stage impeller. The remaining liquid travels on to the second expansion device and evaporator.
Just before entering the evaporator, the liquid refrigerant flows through a second expansion device that reduces its pressure and temperature to evaporator conditions.
Flashing a portion of the refrigerant prior to the economizer reduces the amount of compressor power required, since the refrigerant vapor generated in the economizer only needs to be compressed by the second-stage impeller.
The benefit of the economizer will be discussed in greater detail in Period 2.
3-stage chiller
Economizer
refrigerant vapor
refrigerant vapor
to third stage
to third stage
of compression
of compression
refrigerant vapor
refrigerant vapor
to second stage
to second stage
of compression
of compression
liquid refrigerant
orifice
orifice
liquid refrigerant
liquid refrigerant
from condenser
from condenser
In a chiller with a 3-stage compressor, the expansion process can be separated into 3 steps with separate economizer chambers between the steps.
Liquid refrigerant from the condenser enters the first orifice (expansion device), which reduces the pressure of the refrigerant to that of the third-stage impeller inlet. This pressure drop causes a portion of the liquid refrigerant to flash, and the resulting mixture of liquid and vapor enters the high-pressure chamber of the economizer. Here, the vapor is separated from the mixture and is then routed directly to the inlet of the third-stage impeller. The remaining liquid travels on to the second expansion device.
The second expansion device further reduces the pressure of the refrigerant to that of the second-stage impeller inlet. This pressure drop causes a portion of the liquid refrigerant to flash, and the resulting mixture of liquid and vapor enters the low-pressure chamber of the economizer. Here, the vapor is separated from the mixture and routed directly to the inlet of the second-stage impeller. The remaining liquid travels on to the third expansion device and evaporator.
10 TRG-TRC010-EN
orifice
orifice
liquid refrigerant
to evaporator
to evaporator
Figure 16
Page 18
period one
Components
notes
Again, the final expansion device reduces the pressure and temperature of the refrigerant to evaporator conditions.
Evaporator
tube bundle
tube bundle
liquid
liquid
refrigerant
refrigerant
chilled
chilled
water
water
return
return
liquid
liquid
distributor
distributor
eliminator
eliminator
Evaporator
In the flooded shell-and-tube evaporator shown, the low-pressure mixture of liquid refrigerant and refrigerant vapor enters the distribution system that runs the entire length of the shell. Small openings and baffles in the passage of the liquid distributor provide an even spray of refrigerant over the surfaces of the tubes inside the evaporator shell, where the refrigerant absorbs heat from relatively warm water flowing through the tube bundle. This transfer of heat boils the liquid refrigerant on the tube surfaces. The resulting vapor passes through an eliminator that prevents liquid from being drawn upward. The vapor collects in a large chamber at the top of the shell and is drawn back to the compressor. The now-cool water can be used in a variety of comfort or process applications.
orifice system
orifice system
Figure 17
Some chiller designs may make use of a direct expansion (DX) shell-and­tube evaporator. In this type of evaporator, liquid refrigerant flows through
the tubes and water fills the surrounding shell. As heat is transferred from the water to the refrigerant, the refrigerant boils inside the tubes and the resulting vapor is drawn to the compressor.
TRG-TRC010-EN 11
Page 19
notes
period one
Components
Motor
motor
motor
gear-drive
impeller
impeller
motor
motor
impellers
impellers
direct-drive
gears
gears
Figure 18
Motor
A motor is used to rotate the impeller(s). A direct-drive motor is connected directly to the impeller shaft and the impeller rotates at the same speed as the motor. A gear-drive motor transfers its energy to the impeller shaft using a set of gears. This allows the impeller to rotate at a higher speed than the motor.
The direct-drive motor requires fewer bearings and does not incur gear losses. Additionally, since the compressor rotates at a lower speed, it can be much quieter.
Direct-drive compressors are, however, only practical in centrifugal chillers that use low-pressure refrigerants.
Hermetic Motor Cooling
stator
stator
rotor
rotor
liquid
liquid
refrigerant
refrigerant
Another important difference in compressor motors is the issue of hermetic versus open. A hermetic motor is totally enclosed within the chiller’s
refrigeration system. An open motor is mounted externally—outside of the
drain
drain
Figure 19
12 TRG-TRC010-EN
Page 20
period one
Components
notes
chiller’s refrigeration system—and uses a coupling to connect the motor and compressor shafts.
The heat generated by the hermetic motor is absorbed by liquid refrigerant that flows around, through, and over the motor. The heat must be rejected by the chiller’s condenser.
The heat generated by the open motor is rejected to the air drawn in from the equipment room. This heat must still be rejected from the equipment room, either by mechanical ventilation or, if the room is conditioned, the building’s cooling system. In some designs, this air is simply drawn into the motor housing by the rotating motor shaft. The vent passages tend to get dirty and clog, resulting in higher operating temperatures and hot spots that adversely affect motor efficiency and reliability. Other designs, such as totally-enclosed fan-cooled (TEFC) and totally-enclosed air-over (TEAO), use a separate fan with a protective housing to cool the motor.
Hermetic compressor motors eliminate the need for the shaft couplings and external shaft seals that are associated with open motors. The coupling needs precise alignment, and these seals are a prime source of oil and refrigerant leaks. On the other hand, if a motor burns out, a hermetic chiller will require thorough cleaning, while a chiller with an open motor will not.
Controls and Starter
starter
control
control
panel
panel
starter
Figure 20
Controls and Starter
A microprocessor-based control panel is provided on the chiller to provide accurate chilled-water control as well as monitoring, protection, and adaptive limit functions. These controls monitor chiller operation and prevent the chiller from operating outside its limits. They can compensate for unusual operating conditions, keeping the chiller running by modulating system components rather than simply shutting it down when a safety setting is violated. When serious problems occur, diagnostic messages aid troubleshooting.
Modern control systems not only provide accurate, optimized control and protection for the chiller, but can also interface with a building automation system for integrated system control. In a chilled water system, optimal
TRG-TRC010-EN 13
Page 21
period one
Components
notes
performance is a system-wide issue, not just a matter of chiller design and control.
A starter links the chiller motor and the electrical distribution system. Its primary function is to connect (start) and disconnect (stop) the chiller from line
power—similar to what a switch does for a light bulb. The starter, however, handles much more current and must have the appropriate interlocks to work with the chiller control panel and oil pump.
Every electrically driven chiller requires a starter. It must be compatible with the characteristics of both the compressor motor and the electrical circuitry of the chiller. There are many types of starters, including star-delta, across-the-line, auto-transformer, primary reactor, and solid state. A variable-speed drive, which is used to modulate the speed of the motor during normal operation, also serves as a starter. Important characteristics to consider when selecting a starter include first cost, reliability, line voltage, and available current.
Starters
line power
line power
control power
control power
wiring
wiring
starter
starter
line power
line power
unit-mounted
control power
control power
wiring
wiring
remote-mounted
Figure 21
The starter may be mounted on, or remotely from, the chiller. Use of a unit­mounted starter reduces electrical installation costs. It may also improve reliability and save system design time, since all of the components are pre­engineered and factory mounted.
Depending on the type of starter selected, there are several options that can simplify installation. Disconnects allow the starter to be isolated from the electrical distribution system, and short-circuit protection can be provided using fuses or a circuit breaker.
14 TRG-TRC010-EN
Page 22
notes
period two
Refrigeration Cycle
Centrifugal Water Chillers
period two
Figure 22
A pressure–enthalpy (p-h) chart illustrates the refrigeration cycle of the centrifugal water chiller.
2-stage centrifugal chiller
Refrigeration Cycle
2-stage
2-stage
compressor
compressor
economizer
economizer
condenser
evaporator
evaporator
expansion devices
expansion devices
First, let’s review the components of a 2-stage centrifugal chiller in the context of the refrigeration cycle.
Refrigerant vapor leaves the evaporator and flows to the compressor, where it is compressed to a higher pressure and temperature. High-pressure refrigerant vapor then travels to the condenser where it rejects heat to water, and then leaves as a saturated liquid. The pressure drop created by the first expansion device causes part of the liquid refrigerant to evaporate and the resulting mixture of liquid and vapor enters the economizer. Here, the vapor is separated from the mixture and routed directly to the inlet of the second-stage impeller. The remaining saturated liquid refrigerant enters the second expansion device.
condenser
Figure 23
TRG-TRC010-EN 15
Page 23
period two
Refrigeration Cycle
notes
The pressure drop created by the second expansion device lowers the pressure and temperature of the refrigerant to evaporator conditions, causing a portion of the liquid refrigerant to evaporate. The resulting mixture of liquid and vapor enters the evaporator. In the evaporator, the liquid refrigerant boils as it absorbs heat from water and the resulting vapor is drawn back to the compressor to repeat the cycle.
Pressure-Enthalpy (
subcooled
subcooled
liquid
liquid
pressure
pressure
$
15.5 Btu/lblb
15.5 Btu/
[201.0 kJ/kg]
[201.0 kJ/kg]
[0.034
[0.034
psia
5 5 psia
MPa]]
MPa
mixture of
mixture of
liquid and
liquid and
vapor
vapor
enthalpy
enthalpy
p-h)
%
92.4 Btu/lblb
92.4 Btu/
[380.4 kJ/kg]
[380.4 kJ/kg]
Chart
superheated
superheated
vapor
vapor
Figure 24
The pressure-enthalpy chart plots the properties of a refrigerant—refrigerant pressure (vertical axis) versus enthalpy (horizontal axis). Enthalpy is a measure of the heat content, both sensible and latent, per pound [kg] of refrigerant.
liquid
For example, A represents the heat content of saturated
HCFC-123
refrigerant at 5 psia [0.034 MPa] and 34°F [1.1°C]. B represents the heat content
vapor
of saturated
HCFC-123 refrigerant at the same pressure and temperature.
The difference in heat content, or enthalpy, between A and B—that is, 76.9 Btu/ pound [179.4 kJ/kg]—is the amount of heat required to transform 1 pound of saturated liquid refrigerant to saturated refrigerant vapor at the same pressure and temperature.
If the heat content of the refrigerant at any pressure falls to the right of the curve, the vapor is superheated. Similarly, if the heat content of the refrigerant falls to the left of the curve, the liquid is subcooled. Finally, when the heat content of the refrigerant falls inside the curve, the refrigerant exists as a mixture of liquid and vapor.
Let’s plot the theoretical vapor-compression refrigeration cycle for a 2-stage centrifugal water chiller on a pressure-enthalpy chart.
16 TRG-TRC010-EN
Page 24
notes
period two
Refrigeration Cycle
2-stage centrifugal chiller
Refrigeration Cycle
condenser
6
condenser
P
P
c
c
pressure
pressure
P
P
1
1
P
P
e
e
expansion
expansion
devices
devices
6
5
economizer
economizer
8
8
7
7
9
9
evaporator
evaporator
5
3
3
1
1
4
4
2-stage
2-stage
2
2
compressor
compressor
enthalpy
enthalpy
Figure 25
Refrigerant leaves the evaporator as saturated vapor and flows to the first-
stage impeller of the compressor. There, the refrigerant vapor is compressed to a higher pressure (P
) and temperature . Cooler refrigerant vapor that flashed
1
within the economizer is mixed with the refrigerant discharged from the first-
stage impeller, reducing the heat content of the mixture . The second stage of
compression further elevates the pressure (P
) and temperature of the
c
refrigerant ➃.
Energy provided to the compressor is imparted to the refrigerant as an increase in pressure and superheat. Superheated refrigerant vapor leaves the compressor and enters the condenser.
Water flowing through the condenser absorbs heat from the hot, high-pressure
refrigerant vapor, causing it to desuperheat and condense into saturated liquid before leaving the condenser to travel to the first expansion device.
The first expansion device reduces the pressure (➅ to ➆) of the refrigerant to
the second-stage impeller inlet pressure (P
). This pressure drop causes a
1
portion of the liquid refrigerant to evaporate, or flash. The evaporating refrigerant absorbs heat from the remaining liquid refrigerant, reducing its
enthalpy from ➆ to ➇. The resulting mixture of liquid and vapor enters the economizer . Here, the vapor is separated from the mixture and routed directly to the second-stage impeller inlet and the remaining liquid travels on to the second expansion device ➇.
Just before it enters the evaporator, the liquid refrigerant flows through a second expansion device that reduces its pressure (P
) and temperature to
e
evaporator conditions . The cool, low-pressure mixture of liquid and vapor
enters the distribution system in the evaporator shell and absorbs heat from water that flows through the tubes. This transfer of heat boils the liquid refrigerant, and the resulting saturated refrigerant vapor is drawn back to the
compressor to repeat the cycle.
TRG-TRC010-EN 17
Page 25
notes
period two
Refrigeration Cycle
2-stage centrifugal chiller
Refrigeration Cycle
condenser
6
condenser
P
P
c
c
pressure
pressure
P
P
1
1
P
P
e
e
expansion
expansion
devices
devices
6
5
economizer
economizer
8
8
7
7
10
10
9
9
evaporator
evaporator
5
3
3
1
1
4
4
2-stage
2-stage
2
2
compressor
compressor
&%
enthalpy
enthalpy
$
Figure 26
The change in enthalpy from C to A that occurs during the refrigeration cycle is called the refrigeration effect. This is the amount of heat that each pound [kg] of liquid refrigerant will absorb when it evaporates.
The benefit of the economizer can be demonstrated by comparing the refrigeration cycles with and without an economizer.
Without an economizer, refrigerant from the condenser expands directly to evaporator conditions , producing a smaller refrigeration effect (B to A). Some chiller designs may subcool the liquid refrigerant in the condenser (
moves to the left) to increase this refrigeration effect.
Also, in a chiller without an economizer, all of the refrigerant vapor must go through both stages of compression to return to condensing conditions. In a chiller with an economizer, refrigerant vapor that flashes in the economizer bypasses the first stage of compression, resulting in an overall energy savings of 3 to 4 percent.
18 TRG-TRC010-EN
Page 26
notes
period two
Refrigeration Cycle
Refrigerant Operating Pressures
HCFC-22
HCFC-22
HFC-134a
HFC-134a
pressure
pressure
HCFC-123
HCFC-123
atmospheric
atmospheric
pressure
pressure
temperature
temperature
Refrigerants
When selecting which refrigerant to use in a centrifugal water chiller, the manufacturer considers efficiency, operating pressures, compatibility with materials, heat transfer properties, stability, toxicity, flammability, cost, availability, and environmental impact.
Figure 27
Refrigerants commonly used in centrifugal chillers can be classified as low, medium, or high pressure based on the normal operating pressures in the refrigeration cycle.
Chillers using a high-pressure refrigerant like HCFC-22, or a medium-pressure refrigerant like HFC-134a, operate at pressures that are well above atmospheric pressure. As we are about to see, some sections of chillers that use a low­pressure refrigerant such as HCFC-123 operate at below-atmospheric pressure.
TRG-TRC010-EN 19
Page 27
notes
period two
Refrigeration Cycle
20 TRG-TRC010-EN
Page 28
notes
period three
Compressor Capacity Control
Multistage Compressor
impellers
impellers
inlet vanes
inlet vanes
In a multistage centrifugal compressor, the operating characteristics of
each impeller are modulated by the impeller’s own set of inlet vanes.
Figure 33
This example shows 2 impellers in series. These impellers share the task of compressing the refrigerant. Centrifugal water chillers are generally available with 1, 2, or 3 impellers.
Impeller
V
V
r
r
R
R
V
V
t
t
Figure 34
The forces that act on the refrigerant vapor within the centrifugal compressor impeller can be broken down into 2 components. One component acts to move the refrigerant away from the impeller in a radial direction. This component is called radial velocity (V
The second component acts to move the refrigerant in the direction of impeller rotation. This component is called tangential velocity (V
Together, these components generate the resultant velocity vector (R), the length of which is proportional to the amount of kinetic energy in the
).
r
).
t
TRG-TRC010-EN 23
Page 29
period three
Compressor Capacity Control
notes
refrigerant. Recall that kinetic energy is converted to static energy, or static pressure.
Impeller Dynamics
V
refrigerant flow rate
refrigerant flow rate
V
r
r
V
V
r
r
R
R
V
V
t
t
rotational
rotational
speed
speed
The radial velocity (V
) for a given compressor is directly proportional () to the
r
flow rate of refrigerant vapor through the compressor.
The tangential velocity (V
) is proportional to the product of impeller rotational
t
speed and impeller diameter.
Therefore, the static-pressure-producing capacity of a compressor can be adjusted by changing the flow rate of refrigerant, the impeller speed, or the diameter of the impeller.
rotational speed × diameter
V
rotational speed × diameter
V
t
t
diameter
diameter
refrigerant
refrigerant
flow rate
flow rate
Figure 35
24 TRG-TRC010-EN
Page 30
notes
period three
Compressor Capacity Control
Compressor Unloading
V
V
r
R
R
V
V
t
t
r
R
R
V
V
t
t
V
V
r
r
full load
part load
Figure 36
Consider a given-diameter compressor impeller that rotates at a constant speed. As the load on the chiller decreases, the inlet vanes partially close and the flow rate of refrigerant through the compressor drops. Radial velocity (V
),
r
which is proportional to refrigerant flow, decreases as well.
Even though the speed of rotation and diameter of the impeller are constant, the tangential velocity (V
) (which is proportional to the product of impeller
t
rotational speed and impeller diameter) drops because of the pre-swirling of the refrigerant caused by the inlet vanes.
The result is a shorter resultant velocity vector (R), which means that less static pressure is generated.
TRG-TRC010-EN 25
Page 31
notes
period three
Compressor Capacity Control
Surge
V
V
r
r
R
R
V
V
t
t
As the load and the corresponding refrigerant flow rate continue to fall, the radial velocity (force) drops, too. At some point, the radial force becomes smaller than the generated static pressure, letting the pressurized refrigerant vapor flow backward from the diffuser passages into the impeller. This instantaneously reduces the pressure within the passages below the radial force and the compressor is able to re-establish the proper direction of refrigerant flow.
V
< static pressure
V
< static pressure
rr
Figure 37
This condition is known as surge. So long as this unstable load condition exists, the refrigerant alternately flows backward and forward through the compressor impeller, generating noise and vibration.
Compressor Map
e
e
g
g
r
r
u
u
s
s
51
51
36
10
10
14
pressure difference
pressure difference
14
25
25
refrigerant flow rate
refrigerant flow rate
36
vane position
vane position
(degrees)
(degrees)
These curves represent the performance of a typical 2-stage compressor over a range of inlet vane positions. The pressure difference between the compressor inlet (evaporator) and outlet (condenser) is on the vertical axis and the refrigerant flow rate is on the horizontal axis. The dashed line represents the
90
90
75
75
63
63
Figure 38
26 TRG-TRC010-EN
Page 32
period three
Compressor Capacity Control
notes
conditions that cause the compressor to surge. Any operating point that falls to the right of this line is satisfactory for stable operation.
Operating Point
operating
operating
point
point
pressure difference
pressure difference
refrigerant flow rate
refrigerant flow rate
To balance the load on the chiller, the compressor must pump a certain quantity of refrigerant vapor at evaporator pressure and elevate it to the pressure dictated by the condensing conditions.
The intersection of the refrigerant flow rate and the pressure difference between the inlet and outlet of the compressor identifies the compressor operating point.
Figure 39
compressor map for a
2-Stage Compressor
operating
operating
point
point
e
e
g
g
r
r
u
u
s
s
51
51
36
10
10
14
pressure difference
pressure difference
14
25
25
refrigerant flow rate
refrigerant flow rate
36
vane position
vane position
(degrees)
(degrees)
Superimposing the operating point on the previous compressor performance curves establishes the point at which the compressor will balance the load. In this example, the compressor will balance the load with its inlet vanes open
90°.
TRG-TRC010-EN 27
90
90
75
75
63
63
Figure 40
Page 33
notes
period three
Compressor Capacity Control
compressor map for a
2-Stage Compressor
$
e
e
g
g
r
r
u
u
s
s
&
10
10
14
pressure difference
pressure difference
14
25
25
unloading line
unloading line
%
51
51
36
36
90
90
75
75
63
63
refrigerant flow rate
refrigerant flow rate
Figure 41
The starting point (A) is the full-load operating point. As the load on the chiller decreases, the inlet vanes partially close, reducing the flow rate of refrigerant vapor through the compressor and balancing the chiller capacity with the new load (B).
Less refrigerant, and therefore less heat, is transferred to the condenser. Since the heat rejection capacity of the condenser is now greater than required, the refrigerant condenses at a lower temperature and pressure. This reduces the pressure difference between the evaporator and the condenser.
Continuing along the unloading line, the compressor remains within its stable operating range until it reaches the surge region at C.
28 TRG-TRC010-EN
Page 34
notes
period three
Compressor Capacity Control
Adjustable-Frequency Drives
inlet vanes only
inlet vanes only
AFD + inlet vanes
AFD + inlet vanes
power consumption
power consumption
load
load
An adjustable-frequency drive (AFD), or variable-speed drive, is another device used to vary the capacity of a centrifugal compressor. AFDs are widely used with fans and pumps, and with the advancement of microprocessor-based controls for chillers, they are now being applied to centrifugal water chillers.
Figure 42
Using an AFD with a centrifugal chiller can degrade the chiller’s full-load efficiency. It will, however, offer energy savings by reducing motor speed at low-load conditions when cooler condenser water is available. An AFD also controls the inrush current at start-up, reducing stress on the compressor motor.
Certain system characteristics favor the application of an adjustable frequency drive, including:
A substantial number of part-load operating hours
The availability of cooler condenser water
Chilled-water reset control
High electrical charges
Performing a comprehensive energy analysis is the best method of determining if an adjustable-frequency drive is desirable. Depending on the application, it may make sense to take the additional money needed to purchase an AFD and use it to purchase a more efficient chiller instead.
TRG-TRC010-EN 29
Page 35
notes
period four
Maintenance Considerations
Centrifugal Water Chillers
period four
Figure 43
This period discusses general maintenance requirements of centrifugal water chillers. Although some of the information applies specifically to the design presented in this clinic, requirements for other centrifugal chiller designs are also included.
Maintenance Considerations
Operating logMechanical componentsHeat-transfer surfacesFluid analysis
Figure 44
Once a centrifugal chiller is installed and put into operation, it usually continues to function without a full-time attendant. In many cases, the machine starts and stops on a schedule controlled by a building automation system or a simple time clock. The only daily maintenance requirement is to complete and review the operating log.
Water chillers are designed for maximum reliability with a minimum amount of maintenance. Like all large mechanical systems, however, certain routine maintenance procedures are either required or recommended.
30 TRG-TRC010-EN
Page 36
notes
period four
Maintenance Considerations
operating log
ASHRAE Guideline 3
Chilled water inlet and outlet
temperatures and pressures
Chilled water flowEvaporator refrigerant
temperature and pressures
Evaporator approach
temperature
Condenser water inlet and
outlet temperatures and pressures
Condenser water flow
Condenser refrigerant
temperature and pressures
Condenser approach
temperature
Oil pressures, temperature, and
levels
Addition of refrigerantAddition of oilVibration levels
Figure 45
Guideline 3, “
and Air Conditioning Equipment and Systems
Reducing Emission of Halogenated Refrigerants in Refrigeration
,” is one of several advisory documents published by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). This guideline includes a list of recommended data points to be logged daily for each chiller. Much of this data may be available from the display on the chiller control panel.
Special attention should be given to:
Reviewing the operating log and trends
Observing the oil pressure drop to determine if the oil filter needs to be
replaced
Monitoring evaporator and condenser approach temperatures
Observing and recording the oil level
Monitoring purge pump-out operation
TRG-TRC010-EN 31
Page 37
notes
period four
Maintenance Considerations
maintenance considerations
Mechanical Components
Required maintenance
Compressor and motor: no maintenance required
Controls: no maintenance or calibration required
Recommended maintenance
Visually inspect overall unit
Inspect safety controls and electrical components
Tighten electrical connections
Check for leaks
Figure 46
The compressor/motor assembly in direct-drive, hermetic compressor designs requires little periodic maintenance. The hermetic motor eliminates the need for external shaft seals associated with open motors. (These seals are a prime source of oil and refrigerant leaks and should be inspected on a regular basis.) Hermetic motor designs also eliminate the annual coupling and seal inspections, alignment, and shaft seal replacement associated with open motors.
With the advent of microprocessor-based controls, the control panel and auxiliary controllers require no recalibration or maintenance. Remotely­mounted electronic sensors send information to the unit controller, which can be connected to a building automation system to communicate information and allow system-level optimization. These systems can notify the operator with an alarm or diagnostic message when a problem occurs.
As for any mechanical equipment, a daily visual inspection of the chiller is recommended to look for oil leaks, condensation, loosened electrical or control wiring, or signs of corrosion. Special attention should be given to safety controls and electrical components.
A qualified service technician should check the chiller annually for leaks. The United States Environmental Protection Agency (EPA) mandates refrigerant recovery whenever a refrigeration circuit is opened during the normal service of any air conditioning system.
32 TRG-TRC010-EN
Page 38
notes
period four
Maintenance Considerations
maintenance considerations
Mechanical Components
Other design-specific requirements
Change oil when oil analysis dictates
Replace oil filter periodically
Replace filter drier periodically
Clean oil strainers annually
Check shaft alignment annually
Check coupling annually
Replace shaft seal every 2 to 4 years
Compressor teardown inspection every 5 to 10 years
Figure 47
Some centrifugal compressor designs do require periodic maintenance of mechanical system components. This includes oil and refrigerant filter changes, oil strainer changes, and a compressor inspection.
Open-motor compressor designs require shaft alignment, coupling inspection, bearing lubrication, and cleaning of the motor windings on a quarterly or annual basis.
In all cases, strictly follow the maintenance requirements and recommendations published by the manufacturer.
maintenance considerations
Heat Transfer Surfaces
Recommended maintenance
Use a qualified water treatment
specialist
Clean condenser tubes as
needed
Clean water-side strainers
Test tubes every 3 years
Figure 48
To ensure optimum heat transfer performance, the heat transfer surfaces must be kept free of scale and sludge. Even a thin deposit of scale can substantially reduce heat transfer capacity. Engage the services of a qualified water treatment specialist to determine the level of water treatment required to remove contaminants from the cooling tower water.
TRG-TRC010-EN 33
Page 39
period four
Maintenance Considerations
notes
Scale deposits are best removed by chemical means. During this process, the water-cooled condenser is commonly isolated from the rest of the cooling­tower-water circuit by valves, while a pump circulates cleaning solution through the condenser tubes.
Sludge is removed mechanically. This typically involves removing the water boxes from the condenser and loosening the deposits with a stiff-bristled brush. The loosened material is then flushed from the tubes with clear water. As part of this procedure, the strainers in both the chilled-water and cooling-tower­water circuits should be cleaned every year.
Every 3 years (more frequently in process or critical applications), a qualified service organization should perform nondestructive inspections of the evaporator and condenser tubes. The eddy-current tube test is a common method.
Rarely, problems may arise that cause refrigerant or water leaks. These must be repaired immediately.
Fluid Analysis
Oil analysis
Conduct annual analysis to verify
system integrity
Measure oil pressure drop to
determine if filter needs changing
Measure charge
Refrigerant charge
Conduct analysis of refrigerant
Inspect purge system
Figure 49
Oil analysis is an important annual maintenance task required for centrifugal water chillers. It may be conducted more frequently for chillers that run continuously or more often than normal. This test, performed by a qualified laboratory, verifies the integrity of the refrigeration system by testing the concentrations of moisture, acidity, and metal. This analysis can determine where problems exist or could potentially develop. By taking oil samples on a regular basis, normal operating trends for the compressor and bearing metals
can be analyzed. Instead of adopting a “change the oil once a year whether it needs it or not” approach, regular oil analyses can be used to determine proper oil change intervals and predict major problems before they occur.
Refrigerant analysis measures contamination levels and determines suitability for continued use. It can also determine if recycled refrigerant is suitable for reuse. Refrigerant analysis helps extend the life of the existing charge and ensures that the chiller is operating at peak efficiency.
34 TRG-TRC010-EN
Page 40
period four
Maintenance Considerations
notes
Regularly logging oil and refrigerant charges, and examining the trends of this data, can help identify potential problems before they occur.
Oil Analysis
Why perform regular oil analysis?
Helps reduce maintenance costs
Detects problems without
compressor disassembly
Extends service life of oil charge
Reduces environmental problems
related to oil disposal
Helps maintain compressor
efficiency and reliability
Helps lower refrigerant emissions
Figure 50
An oil analysis is a key preventive maintenance measure and should be conducted at least annually. It will help the compressor last longer while maintaining chiller efficiency and reducing refrigerant emissions.
A certified chemical laboratory can be contracted to perform the analysis for all types of compressors. Often the chiller manufacturer can provide this service.
TRG-TRC010-EN 35
Page 41
notes
period five
Application Considerations
Centrifugal Water Chillers
period five
Figure 51
Several considerations must be addressed when applying centrifugal water chillers, including:
Condensing temperature control
Constant or variable evaporator-water flow
Short evaporator-water loops
Heat recovery
Free cooling
Equipment certification standards
While not all-inclusive, this list of considerations does represent some of the key issues.
36 TRG-TRC010-EN
Page 42
notes
period five
Application Considerations
Condensing Temperature Control
51
51
(degrees)
(degrees)
$
90
90
75
75
63
63
Figure 52
e
e
g
g
r
r
u
u
s
s
%
10
10
14
pressure difference
pressure difference
14
25
25
unloading line
unloading line
refrigerant flow rate
refrigerant flow rate
&
36
36
vane position
vane position
Condensing Temperature Control
To achieve stable compressor unloading over a wide range of conditions, a reduction in condensing pressure (condenser relief) must accompany a reduction in load.
The starting point (A) is the full-load operating point. As the chiller load decreases, the flow rate of refrigerant vapor through the compressor also decreases. In turn, the pressure difference between the evaporator and the condenser moves the operating point downward toward B.
If the condenser pressure had been controlled to a constant value instead, the compressor would have unloaded along a nearly constant pressure line toward C. This would result in a greatly reduced range of operation.
Condenser relief is, however, only beneficial to a certain point. ALL chillers require a minimum pressure difference between the evaporator and condenser to ensure proper management of oil and refrigerant. This minimum pressure
difference depends on the chiller’s design and controls. The most common method of maintaining this pressure difference at various load conditions is to control the condensing temperature by varying the temperature or flow rate of water through the condenser. By controlling condensing temperature, most centrifugal water chillers can start and operate over a wide range of conditions.
Controlling condensing temperature: (1) maintains chiller efficiency, (2) maintains the required pressure differential between the evaporator and condenser for controlled flow through the refrigerant metering system, and (3) prevents the pressure imbalance that could cause oil loss problems.
TRG-TRC010-EN 37
Page 43
notes
period five
Application Considerations
condensing temperature control
Cooling Tower Bypass
40°F
40°F
[4°C]
[4°C]
55°F
55°F
[13°C]
[13°C]
Controlling the refrigerant pressure difference between the evaporator and condenser of a water-cooled chiller is accomplished by varying the temperature or flow rate of the water flowing through the condenser. The following are 5 common methods used to control condensing temperature:
cooling tower
cooling tower
bypass
bypass
condenser
condenser
diverting
diverting
valve
valve
65°F
65°F
[18°C]
[18°C]
Figure 53
1) Cycling or varying the speed of the cooling tower fans to control the temperature of the water leaving the cooling tower
2) Using a cooling tower bypass pipe to mix warmer leaving-condenser water with the colder tower water and control the temperature entering the condenser as illustrated here
3) Modulating a throttling valve to restrict the flow of water through the condenser
4) Using a chiller bypass pipe to vary the flow rate of water through the condenser
5) Using a variable-speed drive on the condenser water pump to vary the water flow rate through the condenser
Each of these strategies has its advantages and disadvantages. Selecting the appropriate condensing temperature control scheme will depend on the specific requirements of the application.
The water flow rate through the chiller condenser must stay between the minimum and maximum condenser bundle flow rates specified by the chiller manufacturer.
38 TRG-TRC010-EN
Page 44
notes
period five
Application Considerations
evaporator water flow
Constant or Variable Flow
chilled
chilled
water
water
pump
pump
variable-
variable-
speed
speed
drive
drive
Constant or Variable Evaporator Water Flow
Previous chiller designs required that a constant flow rate of water be maintained through the evaporator. This requirement has changed due to advances in chiller controls. Increased sensing and control capabilities now allow chiller manufacturers to design controls that monitor, and respond faster to, fluctuating conditions.
evaporator
evaporator
Figure 54
While the chiller may be able to handle variable water flow through the evaporator, the specific application of the chilled water system may not warrant variable flow. As always, each application should be analyzed to determine if variable evaporator water flow is warranted.
variable evaporator water flow
Limitations
Maintain minimum and maximum water flow
rates through the chiller evaporator
Rate at which the evaporator water flow
changes must be kept below the corresponding limit to:
Maintain the chilled water set point control
Keep the chiller on line
Protect the chiller from damage
Figure 55
The controls on many current chiller designs can properly control the chiller in response to varying evaporator flow rates, with the following limitations:
TRG-TRC010-EN 39
Page 45
period five
Application Considerations
notes
1) The water flow rate through the chiller evaporator must stay between the minimum and maximum flow rates for the evaporator bundle, as specified by the chiller manufacturer. These limits depend on the specific design variables of the actual evaporator bundle such as the number of tubes, number of passes, and geometry. Implementation of a method for sensing evaporator water flow through each chiller is the only way to make sure that the water flow rate stays within these limits.
2) The rate of change for the evaporator water flow rate must not exceed a specified level, depending on the level of protection desired. For example, the maximum rate of change to maintain the chilled water set point is more stringent than the maximum rate of change to keep the chiller on line. There are 3 common levels of protection desired: maintaining chilled water set point control, keeping the chiller on line, and protecting the chiller from damage.
The limits for these different levels of protection should be obtained from the chiller manufacturer.
Short Evaporator-Water Loops
load
load
chilled
chilled
water
water
pump
pump
evaporator
evaporator
Figure 56
Short Evaporator-Water Loops
Proper chilled water temperature control requires that the temperature of the chilled water returning to the evaporator not change any faster than the chiller controls can respond. The volume of water in the evaporator loop acts as a buffer, ensuring that the return water temperature changes slowly and, therefore, providing stable temperature control. If there is not a sufficient volume of water in the loop to provide an adequate buffer, temperature control can be lost, resulting in erratic system operation.
The chiller manufacturer should be consulted for volume requirements of the evaporator-water loop.
40 TRG-TRC010-EN
Page 46
notes
period five
Application Considerations
Short Evaporator-Water Loops
load
load
tank
tank
chilled
chilled
water
water
pump
pump
Short water loops may be unavoidable in close-coupled or very small applications, particularly in systems where the load consists of only a few air handlers or processes.
evaporator
evaporator
Figure 57
To prevent the effect of a short water loop, a storage tank or large header pipe can be added to the system to increase the volume of water in the loop and ensure a slowly changing return water temperature.
A second solution is to reduce the water flow rate in the chilled water loop
while using the same size pipes. This also increases the loop time—the time it takes a particle of water to travel through the chilled water loop—and ensures that the return water temperature changes slowly. This solution has the added benefit of reduced pumping energy requirements.
TRG-TRC010-EN 41
Page 47
notes
period five
Application Considerations
Heat Recovery
heat-recovery
heat-recovery
condenser
condenser
cooling
cooling
tower
tower
water
water
standard
standard
condenser
condenser
Figure 58
Heat Recovery
Salvaging usable heat from the refrigeration cycle—heat that would normally be rejected to the atmosphere—can significantly reduce the operating costs of many buildings.
Heat recovery is most commonly accomplished using 2 condensers and the fact that hot refrigerant vapor migrates to the area with the lowest temperature. Raising the refrigerant condensing temperature in the standard condenser prompts the refrigerant to flow instead to the second condenser, where it rejects its heat to the water flowing through the tubes. The condensing temperature in the standard condenser is controlled by varying the temperature or the flow rate of the cooling tower water.
Typical uses for the hot water from the second condenser include: heat for spaces around the perimeter of the building, reheat coils in air conditioning systems, and bathroom, laundry, or kitchen requirements. Any building with a simultaneous heating and cooling load is a potential candidate for heat recovery.
42 TRG-TRC010-EN
Page 48
notes
period five
Application Considerations
Heat-Recovery Chiller Options
heat-recovery (dual) condenser
Second, full-
size condenser
Large heating
loads
High hot water
temperatures
Controlled
Degrades
chiller efficiency
auxiliary condenser
Second, smaller
size condenser
Preheating loads
Moderate
hot water temperatures
Uncontrolled
Improves chiller
efficiency
heat pump
No extra
condenser
Large base heating
loads or continuous operation
High hot water
temperatures
Controlled
Chiller efficiency
preserved
Figure 59
Three types of heat-recovery chillers are commonly available:
The dual-condenser, or double-bundle, heat-recovery chiller contains a second, full-size condenser that serves a separate hot water loop. It is capable of more heat rejection and higher leaving-water temperatures. This type of chiller allows the amount of heat being rejected to be controlled, although chiller efficiency is sacrificed for higher hot water temperatures.
Similarly, an auxiliary-condenser heat-recovery chiller makes use of a second, smaller condenser bundle. It is not capable of rejecting as much heat as the dual-condenser chiller. Since its leaving-water temperatures are also lower, it is typically used to preheat returning hot water before it goes to the primary heating equipment or to preheat incoming water prior to entering a traditional water heater. It requires no additional controls and actually improves chiller efficiency.
A heat-pump chiller is a standard chiller (no extra shells are required) applied where the useful heat transfer occurs in the condenser, not the evaporator. The evaporator is connected to the chilled water loop, typically upstream of other chillers, but it only removes enough heat from the chilled water loop to handle the heating load served by the condenser water loop. This application is useful in a multiple-chiller installation, where there is a base or year-round comfort or process load, or where the quantity of heat required is significantly less than the cooling load. Chiller efficiency is not compromised.
TRG-TRC010-EN 43
Page 49
notes
period five
Application Considerations
Free Cooling
air-side economizer
Most efficient
Requires larger
outdoor air, return, and exhaust duct systems
strainer cycle
Coldest water
temperatures
Potential fouling
in chilled water loop
Requires
additional piping, valves, and controls
plate-and-frame heat exchanger
Potential fouling
limited to heat exchanger
Requires additional
heat exchanger, piping, valves, and controls
Can operate
simultaneously with chiller
Figure 60
Free Cooling
Many buildings require some form of year-round cooling to handle interior spaces or other loads. When the outdoor air temperature falls below the indoor dew point temperature, it is possible to use an air-side economizer to satisfy
these cooling requirements. This method of “free cooling” involves using outdoor air for cooling instead of recirculating warmer indoor air. It is the most efficient method of free cooling because it allows all of the chilled water and/or refrigeration system components to be turned off. This method, however, requires larger duct systems to deliver the outdoor air to the air handler and to return and exhaust this larger amount of air.
A second method of applying free cooling is to pump water from the cooling tower loop directly into the chilled water loop when its temperature is low enough to satisfy the cooling load. This is commonly called the strainer cycle because a strainer or filter is needed to prevent debris and contaminants carried by the cooling tower water from entering the chilled water loop. Although this method is very efficient, the contamination common in open cooling tower systems causes concern about “fouling” (deposits of scale or sludge) inside the chilled water coils. Ongoing treatment of the chilled water loop is required.
Another method of providing free cooling is similar to the strainer cycle but involves the use of a plate-and-frame heat exchanger, or water-side economizer, to isolate the chilled water loop from the cooling tower loop. This is a popular method of free cooling because it is efficient and eliminates potential contamination of the chilled water loop. In addition, the heat exchanger can be operated simultaneously with the chiller.
44 TRG-TRC010-EN
Page 50
notes
period five
Application Considerations
free cooling
Refrigerant Migration
from
from
compressor
compressor
condenser
condenser
to
to
compressor
compressor
evaporator
evaporator
Figure 61
This leads to the discussion of a free cooling principle called refrigerant migration. It involves adapting a water chiller so that it functions as a simple
heat exchanger.
When the available condenser water is cooler than the desired chilled water temperature, the compressor is turned off and bypass valves in the chiller refrigerant circuit are opened to let the refrigerant circulate without help from the compressor. Because refrigerant migrates to the area with the lowest temperature, refrigerant boils in the evaporator and the vapor flows to the cooler condenser bundle. After the refrigerant condenses, it flows (by gravity) back to the evaporator.
The advantages of refrigerant migration are these: no extra components are required in the system, control is performed by the chiller itself, and there are no additional fouling concerns. It is possible for the free cooling chiller to satisfy many cooling load requirements without operating the compressor, especially when the system can accommodate warmer chilled water temperatures at part­load conditions.
TRG-TRC010-EN 45
Page 51
notes
period five
Application Considerations
equipment certification standards
ARI Standard 550/590
Purpose
Establish definitions, testing,
and rating requirements
Scope
Factory designed and
prefabricated water chillers
Vapor-compression
refrigeration
Air-cooled and water-cooled
condensing
Figure 62
Equipment Certification Standards
The Air Conditioning & Refrigeration Institute (ARI) establishes rating standards for packaged HVAC equipment. ARI also certifies and labels equipment through
programs that involve random testing of a manufacturer’s equipment to verify published performance.
The overall objective of ARI Standard 550/590–1998 is to promote consistent rating and testing methods for all types and sizes of water chillers, with an accurate representation of actual performance. It covers factory-designed, prefabricated water chillers, both air-cooled and water-cooled, using vapor­compression refrigeration. This generally includes chillers with centrifugal, helical-rotary (screw), reciprocating, or scroll compressors.
equipment certification standards
ARI Standard 550/590
Standard rating conditions
Common system conditions for published ratings
Fouling factor
Integrated Part Load Value (IPLV)
Part-load efficiency rating
Based on an “average” single-chiller installation
Standard operating conditions
Figure 63
The standard rating conditions used for ARI certification represent typical design temperatures and flow rates for which water-cooled and air-cooled systems are designed. They are not suggestions for good design practice for a
46 TRG-TRC010-EN
Page 52
period five
Application Considerations
notes
given system—they simply define a common rating point to aid comparisons. Trends toward improved humidity control and energy efficiency have changed some of the actual conditions selected for specific applications.
Impurities in the chilled- and condenser-water systems eventually deposit on evaporator and condenser tube surfaces, impeding heat transfer. Catalogued performance data includes a fouling factor that accounts for this effect to more closely predict actual chiller performance.
ARI’s part-load efficiency rating system establishes a single, blended estimate of stand-alone chiller performance. The Integrated Part Load Value (IPLV) predicts chiller efficiency at the ARI standard rating conditions using weighted averages representing a broad range of geographic locations, building types, and operating-hour scenarios, both with and without an air-side economizer. While the weighted averages place greater emphasis on the part-load operation of an average, single-chiller installation, they will not—by definition—represent any particular installation.
Additionally, ARI notes that more than 80 percent of all chillers are installed in multiple-chiller plants. Chillers in these plants exhibit different unloading characteristics than the IPLV weighted formula indicates. Appendix D of the Standard explains this further:
...The [IPLV] equation was derived to provide a representation of the average part-load efficiency for a single chiller only. However, it is best to use a comprehensive analysis that reflects actual weather data, building load characteristics, operational hours, economizer capabilities, and energy drawn by auxiliaries such as pumps and cooling towers, when calculating the chiller and system efficiency. This becomes increasingly important with multiple chiller systems because individual chillers operating within multiple chiller systems are more heavily loaded than single chillers within single chiller systems.
Remember that the ARI rating is a standardized representation. Many chillers do not run at standard rating conditions and few are applied in single-chiller installations. Performing a comprehensive energy analysis is the best method of comparing the system operating cost difference between 2 chillers.
TRG-TRC010-EN 47
Page 53
notes
period six
Review
Centrifugal Water Chillers
period six
Figure 64
Let’s review the main concepts that were covered in this clinic on centrifugal water chillers.
Review—Period 1
compressor
compressor
condenser
condenser
control
control
panel
panel
evaporator
evaporator
Period 1 introduced the following components of a centrifugal water chiller: compressor, condenser, expansion device, economizer, evaporator, motor, control panel, and starter.
motor
motor
starter
starter
Figure 65
48 TRG-TRC010-EN
Page 54
notes
period six
Review
Review—Period 2
P
P
c
c
expansion
expansion
devices
devices
pressure
pressure
P
P
1
1
P
P
e
e
condenser
6
condenser
6
5
economizer
economizer
8
8
7
7
9
9
evaporator
evaporator
5
3
3
1
1
4
4
2-stage
2-stage
2
2
compressor
compressor
enthalpy
enthalpy
Figure 66
Period 2 described the refrigeration cycle of 2-stage centrifugal water chillers with a pressure-enthalpy chart. The operation of the purge system for low­pressure chillers was also presented.
Review—Period 3
impellers
impellers
inlet vanes
inlet vanes
Period 3 further explained the operation of the centrifugal compressor. It described the use of impeller inlet vanes as one method for controlling centrifugal compressor capacity. Surge, multistage compressors, and adjustable-frequency drives were also discussed.
Figure 67
TRG-TRC010-EN 49
Page 55
notes
period six
Review
Review—Period 4
Maintenance considerations
Operating log
Mechanical components
Heat-transfer surfaces
Fluid analysis
Figure 68
Period 4 described the general maintenance requirements of a centrifugal water chiller, including:
Recommended data for a daily log
Required and recommended maintenance for mechanical components
Recommended maintenance for heat transfer surfaces
Required analyses for the oil and refrigerant
Review—Period 5
Application considerations
Condensing temperature control
Constant or variable evaporator-water flow
Short evaporator-water loops
Heat recovery
Free cooling
Equipment certification standards
Figure 69
Period 5 presented several considerations in the application of centrifugal water chillers. These included condensing temperature control for water-cooled chillers, constant or variable evaporator-water flow, short evaporator-water loops, heat recovery, free cooling, and equipment certification standards.
50 TRG-TRC010-EN
Page 56
notes
period six
Review
Figure 70
For more information, refer to the following references:
Trane product catalogs for centrifugal water chiller products
(Trane literature order numbers CTV-DS-1 and CTV-DS-2)
Condensing Water Temperature Control (CTV-EB-84)
Multiple Chiller System Design and Control (CON-AM-21)
Principles of Centrifugal Chiller Heat Recovery Operation (AM-REF-2)
ARI Standard 550/590–1998: Implications For Chilled-Water Plant Design
Engineers Newsletter
(Trane
Variable-Primary-Flow Systems (Trane
1999–volume 28, no. 3)
Chilled Water Systems
ASHRAE Handbook—Refrigeration
ASHRAE Handbook—Systems and Equipment
Visit the ASHRAE Bookstore at www.ashrae.org.
For information on additional educational materials available from Trane, contact your local Trane sales office (request a copy of the Educational Materials price sheet — Trane order no. EM-ADV1) or visit our online bookstore at www.trane.com/bookstore/.
, 1999–volume 28, no. 1)
Engineers Newsletter
Engineered Systems Clinics
,
(CWS-CLC-1, 2, 3, and 4)
TRG-TRC010-EN 51
Page 57
Quiz
Questions for Period 1
1) A centrifugal compressor converts ___________ energy to ____________
energy.
2) Does the refrigerant velocity increase in the impeller, diffuser passages, or
volute of the compressor?
3) What is the benefit of using an economizer cycle with a multistage
centrifugal compressor?
4) What is the difference between a hermetic and an open motor?
Questions for Period 2
6
pressure
pressure
6
5
5
8
8
7
7
9
9
enthalpy
enthalpy
3
3
1
1
4
4
2
2
Figure 71
5) Using the pressure-enthalpy diagram in Figure 71, identify the following
process of the 2-stage centrifugal chiller’s refrigeration cycle:
a) to b) to c) to
6) Air, moisture, and other noncondensable gases are removed from a
_____-pressure chiller by what component?
Questions for Period 3
7) What velocity component is directly proportional to the refrigerant flow rate
through the compressor?
52 TRG-TRC010-EN
Page 58
Quiz
8) What velocity component is directly proportional to the impeller’s rotational
speed times its diameter?
9) What are the 2 most common devices used to vary the capacity of a
centrifugal compressor?
Questions for Period 4
10)Explain why proper water treatment is important.
Questions for Period 5
11)The refrigerant migration method of free cooling works because refrigerant
migrates from the area of __________ temperature to the area of __________ temperature.
12)What is the purpose of a fouling factor?
TRG-TRC010-EN 53
Page 59
Answers
1) kinetic energy to static energy
2) impeller
3) By flashing a portion of the refrigerant prior to entering the evaporator, the
economizer reduces the compressor power required since the refrigerant vapor generated in the economizer only needs to be compressed by the higher-stage impeller.
4) A hermetic motor is totally enclosed within the chiller’s refrigeration system
and the heat it generates is absorbed by liquid refrigerant. An open motor is mounted externally—outside of the chiller’s refrigeration system—and uses a coupling to connect the motor and compressor shafts. The heat generated by the open motor is rejected to the air drawn in from the equipment room.
5) a) first stage of compression or first-stage impeller
b) economizer
c) evaporator
6) low-pressure chiller; purge system
7) radial velocity (V
8) tangential velocity (V
)
r
)
t
9) inlet vanes and adjustable-frequency (or variable-speed) drive
10)The heat transfer (tube) surfaces inside the chiller must be kept free of scale
and sludge to ensure optimum performance. Even a thin deposit of scale can substantially reduce heat transfer capacity.
11)higher; lower
12)It is used to more closely predict actual chiller performance by accounting
for the effect of impurities in the chilled- and condenser-water systems. These impurities will eventually deposit on evaporator and condenser tube surfaces, impeding (fouling) heat transfer.
54 TRG-TRC010-EN
Page 60
Glossary
adjustable-frequency drive (AFD) A device used to vary the capacity of a
centrifugal compressor by varying the speed of the motor that rotates the impeller(s).
air-side economizer A method of free cooling that involves using cooler outdoor air for cooling instead of recirculating warmer indoor air.
ARI Air Conditioning & Refrigeration Institute
ARI Standard 550/590 A publication titled
Packages Using the Vapor-Compression Cycle,”
rating and testing methods for all types and sizes of water chillers. It covers factory-designed, prefabricated water chillers, both air-cooled and water­cooled, using the vapor-compression refrigeration cycle.
ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers
ASHRAE Guideline 3 A publication titled
Refrigerants in Refrigeration and Air Conditioning Equipment and Systems,”
that includes a recommended list of data points to be logged daily for each water chiller.
compressor The mechanical device used by the chiller to increase the pressure and temperature of the refrigerant vapor.
condenser The region of the chiller where refrigerant vapor is converted to liquid as it rejects heat to water or air.
control panel The microprocessor-based panel that monitors the chiller’s operation, protects it from damage, provides the operator with data and diagnostic messages, and permits interfacing with a building automation system.
diffuser passages Passages inside the centrifugal compressor that start out small and become larger as the refrigerant travels through them. As the size of the diffuser passages increases, the velocity, and therefore the kinetic energy, of the refrigerant decreases. This kinetic energy is converted to static energy or static pressure.
“Standard for Water Chilling
used to promote consistent
“Reducing Emission of Halogenated
direct-drive motor A type of motor that is connected directly to the compressor shaft, in which the impeller rotates at the same speed as the motor.
direct expansion (DX) shell-and-tube evaporator A type of evaporator where refrigerant flows through the tubes and water fills the surrounding shell.
dynamic compression A method of compression that involves converting energy from one form to another to increase the pressure and temperature of the refrigerant vapor.
TRG-TRC010-EN 55
Page 61
Glossary
economizer The component of a multistage centrifugal chiller used to remove
vapor from the refrigerant mixture after it passes through an expansion device. This reduces the compressor power required since the refrigerant vapor generated in the economizer only needs to be compressed by the higher-stage impeller(s).
enthalpy The property of a refrigerant indicating its heat content, both sensible and latent.
evaporator The region of the chiller where the system chilled water is continuously cooled by boiling the refrigerant as it picks up heat from the returning system water.
expansion device The component of the chiller used to reduce the pressure and temperature of the refrigerant.
flash The process of liquid refrigerant being vaporized by a sudden reduction of pressure.
flooded shell-and-tube evaporator A type of evaporator where water flows through the tubes and refrigerant fills the surrounding shell.
gear-drive motor A type of motor that transfers its energy to the impeller shaft using a set of gears, allowing the impeller to rotate at a higher speed than the motor.
hermetic motor A type of motor that is totally enclosed within the chiller’s refrigeration system and rejects its heat to the liquid refrigerant.
impeller The rotating component of a centrifugal compressor that draws refrigerant vapor into its internal passages and accelerates the refrigerant as it rotates, increasing its velocity and kinetic energy.
inlet vanes A device used to vary the capacity of a centrifugal compressor by “pre-swirling” the refrigerant in the direction of rotation before it enters the impeller, lessening its ability to take in the refrigerant vapor.
loop time The amount of time it takes a particle of water to travel through the chilled water loop.
multistage centrifugal compressor A centrifugal compressor that uses more than 1 impeller to share the task of compressing the refrigerant.
open motor A type of motor that is mounted externally—outside of the chiller’s refrigeration system—and uses a coupling to connect the motor and compressor shafts. It rejects its heat to air drawn in from the equipment room.
orifice plate A type of expansion device that uses a fixed plate with holes drilled in it to reduce the pressure and temperature of the refrigerant to the conditions of the evaporator.
56 TRG-TRC010-EN
Page 62
Glossary
notes
pressure-enthalpy chart A graphical representation of the saturated properties of a refrigerant, plotting refrigerant pressure versus enthalpy.
purge A device used to remove air, moisture, and other noncondensable gases that may leak into a low-pressure chiller.
refrigerant migration A method of free cooling that allows the chiller to be used as a heat exchanger, without operation of the compressor. It is possible, when the condensing temperature of the refrigerant is low enough, for refrigerant to migrate from the evaporator to the condenser.
refrigeration effect The amount of heat that each pound [kg] of liquid refrigerant will absorb when it evaporates.
starter A device used to connect and disconnect the chiller motor and the electrical distribution system.
surge A condition of unstable compressor operation where the refrigerant alternately flows backward and forward through the compressor impeller, generating noise and vibration.
variable-speed drive See adjustable-frequency drive.
volute A large space around the perimeter of a centrifugal compressor that
collects refrigerant vapor after compression.
water-cooled condenser A type of condenser that rejects the heat of the refrigerant to water flowing through it.
TRG-TRC010-EN 57
Page 63
The Trane Company
Worldwide Applied Systems Group 3600 Pammel Creek Road La Crosse, WI 54601-7599 www.trane.com
An American Standard Company
Literature Order Number TRG-TRC010-EN
File Number E/AV-FND-TRG-TRC010-999-EN
Supersedes 2803-10-983
Stocking Location Inland-La Crosse
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
Loading...