Trane Tracer ZN524 Installation Owner Diagnostics

Page 1
Installation Owner Diagnostics
Tracer®ZN524 for water-source heat pumps
Order No: CNT-SVX11A-EN Date: August 2003
Page 2
2 UV-SVN001-EN
Notice
Notice
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
- Indicates a potentially hazordous situation which, if not avoided, could result in death or serious injury
WARNING
CAUTION
- Indicates a potentially hazordous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION
- Indicates a situation that may result in equipment or property damage only accidents.
Page 3
Contents
CNT-SVX11A-EN 3
Start-up Procedures 4 General Information 5 Control Circuit Board Features 6 Control Features 7 Communication Configurations 8 Installation and Wiring 10
Typical Wiring Diagram— 18
Waterside Ecomomizer
Typical Wiring Diagram— 19
Hot Gas Reheat
Configuration 20 Location Identifier 23 Unit Operation 24 Troubleshooting 32 Replacing Circuit Boards 42 Appendix 43 Appendix—Binary Configuration 44 Appendix—Unit Operation 45 Appendix—Data Lists 47 Appendix—Location Identifier 48
Page 4
Start-up Procedures
4 CNT-SVX11A-EN
Installation of New Units
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power can not be inadvertently energized. Failure to dis­connect power before servicing could result in death or serious injury.
1. Follow all instruction for installation of the water-source heat pump as detailed in the unit’s installation guide. (Installation Operation Diagnostics manual).
2. Disconnect power or disable the cir­cuit breaker to unit.
3. Run communication link wire when required. (See wiring diagram in the unit).
4. Install zone sensor when required. (See wiring diagram in the unit and zone sensor submittals).
5. Reapply power.
6. Check for GREEN Status LED opera­tion to ensure power has been made to the Tracer
TM
ZN524 unit controller.
7. Check for YELLOW Comm LED opera­tion to help ensure communication has been made to the Tracer ZN524 unit controller when applicable.
8. Write the Unit Identification number, using the IDENTIFICATION TAG on the unit, in the Appendix of this document, or on building plans for future location use.
Power Up Sequence
Manual output test can be initiated at any time in the power up sequence or during normal operation.
When 24 VAC power is initially applied to the controller, the following sequence occurs:
1. Green Status LED turns on.
2. All outputs are controlled Off.
3. The controller reads input values to determine initial values.
4. Stand-alone control is assumed unless occupancy data is communicat­ed.
5. Random start timer expires (5 to 30 seconds, random).
6. Power-up control Wait feature is applied. When power up control Wait is enabled, the controller waits 2-minutes to allow ample time for communicated control data to arrive. If, after 2-min­utes, the controller does not receive a communicated occupancy request, the unit assumes standalone operation.
7. All valves and damper calibrate closed.
8. Normal operation begins after 290 (potentially) seconds have passed.
Note: Manual output test can be initiated at any time.
Page 5
General Information
CNT-SVX11A-EN 5
Tracer® ZN524 Overview
The Trane Tracer® ZN524 controller is a factory-installed and commissioned, direct-digital controller (DDC) offering for single or dual compressor water­source heat pump systems. (See Figure 1: “Tracer ZN524 Control Board”)
Trane offers a complete solution to space comfort control with the flexibili­ty of Integrated Comfort System (ICS) and stand-alone control packages. The ICS control package combines HVAC equipment and building management into one environmental comfort sys­tem.
Integrating the Tracer ZN524 on water­source heat pumps and tying them to a Tracer Summit® system will provide a complete building management sys­tem. The stand-alone control package offers the features and functionality of the direct digital control without a front-end building automation system, while providing future considerations for ICS.
Equipment problems can often be diag­nosed on each unit without having to access the unit componets. These diag­nostics can be received remotely via a modem with a Tracer Summit building automation system, thus reducing the number of actual on-site service calls; through the Rover® service tool con­nected to a communication jack located inside the Trace zone sensor; or con­nected to the unit.
The Tracer ZN524 is factory-mounted, tested, wired, configured and commis­sioned for the selected application.
The Tracer ZN524 configuration has flexible point and product configura­tions. For example, with point configu­ration, a specific binary point can be configured to accept input from either a time clock or some type of generic device.
Figure 1: Tracer ZN524 control board
Page 6
Controller Circuit Board and Features
6 CNT-SVX11A-EN
Figure 2: Tracer ZN524 unit controller circuit board
A
B
E
D
C
H
F
G
Controller features:
A. Power Connections B. Generic Connections (BOP) C. Status LED
D. Auto Test Button E. Zone Sensor Connections F. Service Button/LED G. Communications Connections H. Communications LED
Page 7
CNT-SVX11A-EN 7
Controller Features
Each Tracer ZN524 unit controller circuit board is equipped with enhancements to help facilitate service, testing, and diagnosis. Each board has:
• Manual test button,
• Status LED,
• Communication status LED,
• Service button,
• Quick terminal connectors, and
• Easy to read screen printing. (See Figure 2: Page 6).
Service
The Trane Tracer ZN524 unit controller is serviced using Rover®, the software service tool. Rover is designed to sup­port the Tracer ZN524 unit controller on a single or dual compressor water­source heat pump.
For “remote” access to the communi­cating units, the zone sensors offered with the Tracer ZN524 have a telephone style (RJ-11) connector allowing field connection between Rover and the zone sensor; however, the RJ-11 connector must be connected to the communica­tions terminals on the Tracer ZN524 unit controller.(See Figure 3: “Rover service tool connected to the RJ-11 communi­cation jack in a zone sensor”)
The zone sensor may also be used when trying to locate a unit. By press­ing the on button on the zone sensor for 5 seconds or using the “wink” com­mand in Rover, the circuit board receives the signal causing the status LED to “wink.” Winking allows visual identifier on the board for service tech­nicians.
The Tracer ZN524 also includes features such as a test output to manually test all of the end devices. (See “Manual Output Test” on page 32, for more infor­mation.)
Typical Components
A typical water-source heat pump sys­tem with a DDC package consists of the following physical components, in addi­tion to the mechanical equipment:
• Tracer ZN524—contains the sensor input circuits, service adjustments, microprocessor control electronics, and communications hardware. Power is supplied by a separately mounted 24 VAC transformer.
• Sensor Modules—a variety of analog sensors that provide temperature and optional humidity sensing and CO2 sensor; and an operator interface to the Tracer ZN524 for operating modes, status, and temperature set points.
• Standard End Devices—a variety of devices that help to gather informa­tion and control capacity are used by the Tracer ZN524 in its control algorithm to condition the space to the desired temperature and relative humidity level.
Note: The Tracer ZN524 is a config­ured controller. It will not operate without a valid downloaded config­uration file.
The Tracer ZN524 controller supports ICS and peer-to-peer communications as well as stand-alone operation. A number of control features may be con­figured at the factory or by using the Rover service tool. (See “Configuration” on page 20, for more information.)
Figure 3: Rover service tool connected to the RJ-11 communication jack in a zone sensor
Page 8
Communication Configurations
8 CNT-SVX11A-EN
Integrated Comfort System
Note: The Tracer ZN524 controller may only be used with Tracer Summit version 11.0 or greater with a Comm5 communications card.
Water-source heat pumps can operate as part of a large building automation system controlled by Tracer Summit. The Tracer ZN524 is linked directly to the Tracer Summit via a twisted pair communication wire. Each Tracer Summit building automation system can connect to a maximum of 120 Tracer ZN524 controllers.
Communications link wire
The ICS system allows for complete communication with the water-source heat pumps via Tracer ZN524 unit con­troller. All points connected to the Tracer ZN524 may be observed from the Tracer Summit front-end controller. The Tracer Summit can also initiate an alarm on a loss of performance or equipment malfunctions.
The ICS system also allows all of the water-source heat pumps to share infor­mation without the presence of hard­wired sensors at each unit. Some typi­cal shared points include outside air temperature, entering water tempera­ture, and occupancy schedules.
Peer-to-Peer Communications
On a peer-to-peer communication sys­tem, multiple Tracer ZN524 controllers may share data, via a twisted pair com­munication wire, without the need for a Tracer Summit system. (See Figure 5: “Peer-to-peer communication connec­tions”)
Peer-to-peer communications allows features such as master/slave opera­tion, in which multiple units operate off of a single zone sensor. This is typically seen in large spaces requiring multiple units.
The Rover service tool is required to set up peer-to-peer communications.
Figure 4: Communications link wire
Figure 5: Peer-to-peer communication connections
Twisted pair wire used in installation of controller in water-source heat pump
Page 9
CNT-SVX11A-EN 9
Communication Interface
Important! To help ensure optimal performance of the Rover service tool, please use the latest version. To obtain the latest version con­tact your local Trane sales repre­sentative or service technician.
Note: Refer to the Tracer system manuals for more information on communications.
The Tracer ZN524 communicates via Comm5 (LonTalk) to a building man­agement system, the Rover service tool, and other unit controllers on the communications link. Each Tracer ZN524 requires a unique address for the system to operate properly. Every Tracer ZN524 has this address (Neuron ID) embedded in the microprocessor, which eliminates the need for field­addressing of the units. Each unit also ships from the factory with a unit iden­tification tag. (See “Location Identifier” on page 23, for more information.)
Building automation system
Trane offers a state-of the art front-end building automation system designed to coordinate and monitor Trane equip­ment and controllers: Tracer Summit. The Tracer Summit system allows the user to monitor and/or change Tracer ZN524:
• status, parameters, sensor data, diagnostics, and internal variables; and
• setpoints, operating modes, and out puts.
Service tool
Trane also offers a service tool to work in conjunction with the Tracer Summit system or with peer-to-peer and stand­alone systems: the Rover service tool.
Communication to the Tracer ZN524, or multiple controllers, can also be accom­plished by using the ICS software serv­ice tool.
A personal computer running Rover may be directly connected to a stand­alone Tracer ZN524; connected to the communications jack in the Trane zone sensor; or connected to a communicat-
ing unit’s Tracer ZN524 unit controller, to access all of the units on a com­municating link.
Rover allows the user to interface with the Tracer ZN524, but will not allow any advanced control (e.g. equipment schedul­ing or trending). To pur­chase a copy of the ICS software service tool, contact the BAS depart­ment at your local Trane dealer.
Stand-Alone
In a stand-alone configuration, com­mands for operation are determined based on input from the zone sensor, humidity sensor, and field-mounted timeclock (See Figure 6).
• Timeclock can be wired to the Tracer ZN524 to index the unit between occupied and unoccupied modes.
• A unit-mounted, analog, leaving water temperature sensor is used to initiate the boilerless control or the optional waterside economizer routines.
These sensors are required for proper system operation and are provided as standard on stand-alone units. Typical water-source heat pump instal­lation
Interoperability
Trane has lead the industry with BACnet interoperability and Trane is now expanding the realm of interopera­ble solutions by offering LonMark certi­fied unit controllers. The Tracer ZN524 controller conforms to the LonMark Space Comfort Controller profile. (See “Appendix—Data Lists” on page 47, for more information.) This allows the ZN524 to be used as a unit controller on other control systems that support LonTalk and the SCC profile. Now build­ing owners have more choices and design engineers have more flexibility to meet the challenges of building automation.
Communication Configurations
Figure 6: Standard GEH (horizontal water-source
heat pump) with single control
Page 10
10 CNT-SVX11A-EN
Specifications
Dimensions
Tracer ZN524 board and mounting hardware:
• Height: 5.25 inches (133 mm.)
• Width: 5.50 inches (140 mm)
• Depth: 2.25 inches (57 mm)
Power Requirements
• 18 to 32 VAC (24 VAC nominal)
• 50 or 60 Hz
• 570 mA AC
Operating Environment
• 32° to 140°F (0× to 60°C)
• 5% to 95% relative humidity, non-condensing
Storage Environment
• -40° to 185°F (-40° to 85°C)
• 5% to 95% relative humidity, non­condensing
Agency Listings
• UL and CUL 916 Energy Management System
• Agency Compliance IEC 1000-4-2 (ESD), IEC 1000-4-4(EFT), IEC 1000-4-5 (Surge)
Installation & Wiring
Figure 7: Tracer ZN524 circuit board schematic
Page 11
Installation & Wiring
CNT-SVX11A-EN 11
Binary input Pin Location Function Configuration Valid range
BI 1 J2 - 1 24 VAC Low evaporation temperature Normally open
J2 - 2 Input Normally closed
BI 2 J2 - 3 24 VAC Condensate overflow Normally open
J2 - 4 Input Normally closed
BI 3 J2 - 5 24 VAC Occupancy/Generic Normally open
J2 - 6 Input Normally closed
BI 4 J2 - 7 24 VAC Fan status or not used Normally open
J2 - 8 Input Normally closed
1. Trane Rover service tool uses the unit type to help determine and download the proper default binary input configuration.
Binary Inputs
Each binary input associates an input signal of 0 VAC with open contact and 24 VAC with closed contacts.
Binary Outputs
Outputs are load side switching triacs. The triac acts as a switch, either making or breaking the circuit between the load (valve, damper, contactor, relay) and ground.
Table 1: Binary input summary for the J2 terminal board connections
1
Binary Pin Function Valid range Output Load Load
Output Location Rating Energized De-Energized
BOP-1 J1-1 Fan NA 12VA 1 VAC RMS 24 VAC RMS
BOP-2 J1-2 Reversing valve NA 12VA 1 VAC RMS 24 VAC RMS
BOP-3 J1-3 Electric heat or reheat NA 12VA 1 VAC RMS 24 VAC RMS
J1-4 (Key) NA 12VA 1 VAC RMS 24 VAC RMS
BOP-4 J1-5 Compressor 1 Normally open or 12VA 1 VAC RMS 24 VAC RMS
normally closed
2
BOP-5 J1-6 Compressor 2 NA 12VA 1 VAC RMS 24 VAC RMS
BOP-6 J1-9 Isolation valve 1 Normally open or 12VA 1 VAC RMS 24 VAC RMS
normally closed
2
BOP-7 J1-10 Isolation valve 2
4
NA 12VA 1 VAC RMS 24 VAC RMS
BOP-8 J1-11 Economizer valve NA 12VA 1 VAC RMS 24 VAC RMS
BOP-9 J1-12 Outdoor air damper NA 12VA 1 VAC RMS 24 VAC RMS
BOP-10
3
TB4-1/ Generic output NA 12VA 1 VAC RMS 24 VAC RMS
TB4-2
Table 2: Binary output summary
1
1. Trane Rover service tool uses the unit type to help determine and download the proper default binary output configuration.
2. The normally open/closed configuration item refers to the inactive state of the controller output.
3. BOP-10 is a generic output but requires a 24 VAC source for usage.
4. Typical factory installation has only one (1) ISO valve.
Page 12
12 CNT-SVX11A-EN
Installation & Wiring
Description Terminals Function Range
Zone TB3-1 Space temperature input 5× to 122×F
(-15× to 50×C)
Ground TB3-2 Analog ground NA
Set TB3-3 Local setpoint input 40× to 115×F
(4.4× to 46.1×C)
Fan TB3-4 Fan switch input 4821 to 4919 V (Off)
2297 to 2342 V (Auto) 15137 to 16463 V (High)
Ground TB3-6 Analog ground NA
Analog Inputs
Table 3: Analog Inputs (Zone Sensor)
Analog input Terminal Function Range
AI 1 J3 - 1 Entering water temperature or -40 to 2120F (-400to 1000C)
J3 - 2 outside air temperature -40 to 2120F (-400to 1000C)
AI 2 J3 - 3 Discharge air temperature -40 to 212
0
F (-400to 1000C)
J3 - 4
AI 3 J3 - 5 Leaving water temperature -40 to 212
0
F (-400to 1000C)
J3 - 6
AI 4 J3 - 7 Universal 4-20mA input 4-20ma
J3 - 8 Humidity 0-100% J3 - 9 CO
2
0 - 2000 ppm
Table 4: Analog Inputs with terminal connections
1,2
1. Trane Rover service tool uses the unit type to help determine and download the proper default analog input configuration.
2. Analog input 3 (AI 3) configured as generic temperature input does not affect unit operation. When configured, the TracerTMZN524 unit con-
troller communicates the generic temperature value to Rover or Tracer Summit and displays it as generic temperature.
Page 13
CNT-SVX11A-EN 13
Installation & Wiring
Mounting
The Tracer ZN524 circuit board is locat­ed in the control box, which is mounted behind the front panel of the water­source heat pump (See Figures 9 and 10 for more information). The sheet metal mounting plate has raised embosses to accept the mounting feet on the circuit board. (See Figure 8: For close-up of horseshoe embosses and circuit board mounting feet.) This design allows the Tracer ZN524 con­troller to be secured with a minimal number of sheet metal screws
.
The mounting position on the vertical water-source heat pump allows com­plete access to the Tracer ZN524 by removing the front panel - six screws
total. (See Figure 9) Removing the screws and panel allows access to the components of the control board.
The mounting plate on both the hori­zontal and vertical water-source heat pumps allow complete access to the Tracer ZN524 by removing the front panel - also six screws total. (See Figure 10) Removing the screws and panel allows access to the components of the control board.
For additional convenience, quick con­nects and modular wire harnesses are used on the control board and mount­ing plate. These quick connects help facilitate ease of wiring devices (e.g., zone sensor) to the control board, and helps add accessibility to major compo­nents.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power can not be inadvertently energized. Failure to dis­connect power before servicing could result in death or serious injury.
Figure 8: A) Cut-away view of the ZN524 control mounted on the control box panel. B) Close-up of mounting shoe on backside of control which slide into the horseshoe brackets (C) on the control panel.
Figure 9: Removing front panel of verti­cal unit to access control panel.
Figure 10: Removing front panel of horizontal unit to access control panel.
A
C
B
Page 14
14 CNT-SVX11A-EN
Installation & Wiring
Wiring
Live Electrical Components!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in han­dling live electrical components per­form these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Important! All wiring must comply with state, local, and federal guidelines. Contact the appropriate local agency for further information.
Important! Wires for temperature sensors, communication lines, 24 VAC, and contact closure sensing inputs should not be bundled with or run near high voltage wiring.
• To prevent damage to the unit, refer to the diagram provided on the unit’s inside access panel for specific wiring information. Most control components are factory-wired. Zone sensors and communication wiring is to be installed by the contractor.
• Power wiring must be separated from the Tracer ZN524 and all low voltage wires. External input wires should be run in separate conduits from high voltage wires.
• Wires connected to pin headers should be formed and routed so as to cause minimum strain on the Tracer ZN524 connector.
• A minimum of 1.5" clearance (from the pin centerline) for wires up to 16 AWG is recommended for bending and forming wires.
• All sensor and input circuits are at or near ground potential. Do not connect any sensor or input circuit to an external ground connection.
• A close-coupled ground connection is
required for the Tracer ZN524.
• Table 5: Tracer ZN524 Wiring Requirements, shows Tracer ZN524 wire types and lengths.
Power
The Tracer ZN524 controller is powered by 24 VAC. (See Table 5: “Tracer ZN524 wiring requirements”)A total of two 1/4­inch quick-connect terminals are provid­ed for 24 VAC connection to the board.
Figure 10: Power connections to the Tracer ZN524 unit controller
Application Wire Type Length
Contact 18 AWG Up to Closure 1000 ft.
24 VAC 16-22 AWG Up to
1000 ft.
Zone 16-22 AWG Up to
Sensor 200 ft.
Communications Belden 8760 Up to
or 5000 ft.
equivalent
ZN524
WARNING
CAUTION
Table 5: Tracer ZN524 wiring
requirements
Page 15
CNT-SVX11A-EN 15
Installation & Wiring
Installing the Wall-Mounted Zone Sensor (Optional)
Zone sensor location is an important element of effective room control and comfort.
The best sensor location is typically on a wall, remote from the HVAC unit. Readings at this location assure that the desired setpoint is achieved across the space, not just near the unit itself.
Note: It may be necessary to subdivide the zone with multiple units to ensure adequate control and comfort throughout the space.
The following are typical areas where the zone sensor should not be mounted:
• Near drafts or “dead spots” (e.g., behind doors or corners);
• Near hot or cold air ducts;
• Near radiant heat (e.g., heat emitted from appliances or the sun);
• Near concealed pipes or chimneys;
• On outside walls or other non­conditioned surfaces; or
• In air flows from adjacent zones or other units.
The communications link is not con­nected in the factory. Communications could be wired to the wall-mounted sensor if desired.
Figure 11: Proper zone sensor placement
Page 16
16 CNT-SVX11A-EN
Installation & Wiring
Zone Sensor Features Fan Switch (Optional)
The zone sensor fan switch provides the controller with an occupied (and occupied standby) fan request signal of off or auto. If the fan control request is communicated to the controller, the controller ignores the hardwired fan switch input and uses the communicat­ed value. The zone sensor fan switch signal can be enabled or disabled through configuration in the ZN524 controller.
ON or CANCEL Buttons
Momentarily pressing the on button during unoccupied mode places the controller in occupied bypass mode for 120 minutes. You can adjust the number of minutes in the unit controller config­uration using Trane’s service tool, Rover. The controller remains in occu­pied standby mode until the override timer expires or until the cancel button is pressed.
Communication Jack
Use the RJ-11 communication jack as the connection point from Rover to the communication link (when the commu­nication jack is wired to the communi­cation link at the controller). By access­ing the communication jack via Rover, entrance to all controllers on the link may be gained.
Table 6: Zone Sensor Options
Part number: X13510628010
Description:
• Space temperature (0.2 C resolution)
• Internal setpoint
• Communication jack
• Vertical case with Trane logo
Part number: X13510606010
Description:
• Space temperature (0.2 C resolution)
• External setpoint
• Communication jack
• Vertical case with Trane logo
Page 17
CNT-SVX11A-EN 17
Installation & Wiring
Table 6: Zone Sensor Options - continued
Part number: X13510606020
Description:
• Space temperature (0.2 C resolution)
• ON and CANCEL buttons
• External setpoint
• Communication jack
• Vertical case with Trane logo
Part number: X13510635010
Description:
• Space temperature (0.2 C resolution)
• ON and CANCEL buttons
• Fan switch (OFF and AUTO)
• External setpoint
• Communication jack
• Vertical case with Trane logo
Page 18
18 CNT-SVX11A-EN
Typical wiring diagram
Figure 12: Wiring
diagram with Waterside Economizer option
Page 19
CNT-SVX11A-EN 19
Typical wiring diagram
Figure 13: Wiring
diagram with Hot Gas Reheat option
Page 20
20 CNT-SVX11A-EN
Configuration
Table 7: Typical Applications Supported
1
Trane configures the Tracer® ZN524 Unit Controller at the factory per the selected unit configuration. The con­troller is applied to water-source heat pumps designed for cooling only or standard heat pump usage, in both sin­gle or dual-compressor design. The controller also supports the useage of
water-side economizer, hot gas reheat, electric heat or boilerless units. Table 7 defines the configuration options sup­ported by the ZN524 controls.
Configurable parameters
Rover service tool uses the unit type to determine and download many other aspects of the unit configuration, such as the default analog input configura­tion, the default binary input configura­tion, and the default binary output con­figuration.
Cooling source
• DX Cooling
• Waterside economizer
Heating source
• None
• Electric heat
• DX Heating
Unit Water-side Hot Gas Electric Boilerless
Economizer Reheat Heat
Cooling Only X
X
X XX XX
Heat X
Pump X
X
X XX XX X X
1. Information applies to both single or dual compressor design
Page 21
CNT-SVX11A-EN 21
Configuration
Fan configuration Default Valid range
Fan operation in heating Continuous Continuous
1
Cycling with capacity
Fan operation in cooling Continuous Continuous (during occupied)
Cycling with capacity (unoccupied)
Number of fan speeds One 1
Configurable fan speed heating High Off, high, auto
Configurable fan speed cooling High Off, high, auto
Zone sensor fan switch Enable Disable or enable
Table 8: Fan configuration ranges
Setpoint Default Valid range
Occupied heating setpoint 71°F 40 to 115°F
Occupied cooling setpoint 74°F 40 to 115°F Occupied standby heating setpoint 67°F 40 to 115°F Occupied standby cooling setpoint 78°F 40 to 115°F
Unoccupied heating setpoint 60°F 40 to 115°F Unoccupied cooling setpoint 85°F 40 to 115°F
Heating setpoint low limit
1
40°F 40 to 115°F
Cooling setpoint low limit
1
40°F 40 to 115°F
Heating setpoint high limit
1
105°F 40 to 115°F
Cooling setpoint high limit
1
110°F 40 to 115°F
Thumbwheel setpoint Enable Disable or enable
Economizer setpoint 50°F 40 to 100°F
Humidity setpoint 60% 0 to 100%
Table 9: Setpoint defaults
1. The heating and cooling setpoint high and low limits only apply to the occupied and occupied standby setpoints and are not applied to the unoccupied setpoints.
Table 10: Discharge air limit ranges
Default Valid Range
Low Limit
1
45°F 30 to 50°F
1. The low limit is the temperature at which the controller shuts down the unit to prevent the coil from frosting.
1. Fan will cycle when unoccupied
Page 22
22 CNT-SVX11A-EN
Configuration
Table 11: Bypass timer range
Default Valid Range
Occupancy bypass timer
1
120 minutes 30 to 240 minutes
( 1-minute resolution)
1. The occupied bypass timer is used for timed override applications.
Occupied Bypass Timer
Table 12: Control wait timer
Default Valid Range
Power up control wait (2 minutes) 120 seconds Disable or enable
Power-up Control Wait
Table 13: Maintenance timer range
1
Default Valid Range
Maintenance timer 0 0 to 10,000 hours
Maintenance Timers
1. Based on fan run hours.
Page 23
CNT-SVX11A-EN 23
Location Identifier
Unit Identification Tag
The unit identification tag is factory mounted and provided for easy identifi­cation of an installed unit. It contains model number, tagging, and location information.
The unit identification tag remains per­manently affixed to the unit for identifi­cation purposes. The bottom portion of the tag provides pertinent information that can be written to in building plans or in the
“Appendix—Location
Identifier” on page 48.
This provides identification history about the unit’s location for quick reference.
These tags provide information about:
• unit serial number (A)
• NID (neuron identification number)— The NID is similar to the serial number of the unit but is specific to the identifi­cation of the Tracer ZN524 unit con­troller circuit board (B)
• unit location—The location identifica­tion is a customer defined, clear English description, of the unit’s physi­cal location. This is a 27 character description, including spaces, of the location. For example, if the location identification for a unit is “Conference Room 101”, the ZN524, Rover (the Trane Loop Controller service tool), and Tracer Summit, will recognize this clear English description. (C)
If location identification is not defined, it will default to the unit serial number. This unit identification tag provides some information so the user has mul­tiple references to the unit. The blank location is provided for field modifica­tion in case the unit is moved from the initial location.
Winking
Winking a device causes the green sta­tus LED on the device selected to blink at a rate of twice per second for approximately 10 seconds. This feature is useful when a discrepancy in device location exists. As part of the trou­bleshooting process, one person can wink the device while another can observe the blinking and verify the device’s physical location.
Important! If the status LED on the ZN524 does not blink, the device may not be communicating or it may not be the device you selected according to the stored address.
A Tracer ZN524 unit controller may be set to wink by pressing zone sensor On button for 5 seconds and using Rover, Trane’s communication service tool or the Tracer Loop Controller.
Figure 14: Water-source heat pump unit identification tag.
A
C
B
Page 24
24 CNT-SVX11A-EN
Unit Operation
Power-Up
When 24 VAC is initially applied to the controller, the following sequence of events occurs:
• Green status LED turns on.
• All outputs are controlled OFF.
• The controller reads input values to
determine initial values.
• Random-start timer expires
(5 to 30 seconds).
• When
POWER-UP CONTROL WAIT is
enabled, the controller waits 0-120 seconds (depending on configuration) to allow ample time for communicated control data to input. If the controller does not receive communi-cated information, stand alone control is assumed.
• All valves and dampers are closed.
N
ORMAL operation begins.
Occupancy
The valid occupancy modes for the Tracer ZN524 controller are:
OCCUPIED
- Normal operating mode for occupied spaces or daytime operation.
U
NOCCUPIED - Normal operating mode
for unoccupied spaces or nighttime operation.
O
CCUPIED STANDBY - Mode used to
reduce the heating and cooling demands during the occupied hours when the space is vacant or is unoccupied.
O
CCUPIED BYPASS -Used to
temporarily transition the unit from unoccupied to occupied operation.
The occupancy mode can be hardwired to the controller via the occupancy binary input or communicated to the controller.
O
CCUPIED mode
When the controller is in the
OCCUPIED
mode, the unit attempts to maintain the space temperature at the active occu-
pied heating or cooling setpoint.
O
CCUPIED mode is the default mode of
the Tracer ZN524 controller.
U
NOCCUPIED
mode
When the controller is in the
UNOCCUPIED mode, the unit attempts to
maintain space temperature at the stored unoccupied heating or cooling setpoint (i.e., configurable through Tracer Summit or the Rover service tool) regardless of the presence of a hardwired or communicated setpoint. When the space temperature exceeds the stored unoccupied setpoint, the controller brings on 100% of the pri­mary heating or cooling capacity.
The
UNOCCUPIED mode can be initiated
through a hardwired signal to the occu­pancy binary input or by a communi­cated request.
O
CCUPIED STANDBY mode
The
OCCUPIED STANDBY mode allows the
unit to operate at a heating or cooling setpoint between the occupied and unoccupied setpoints to help maintain the environment while decreasing ener­gy consumption.
This mode can decrease the energy consumption for heating or cooling during brief periods of vacancy in the space. Unit operation in this mode is similar to the occupied mode except for the different heating and cooling set­points.
The
OCCUPIED STANDBY mode is initiated
only when occupancy is communicated to the Tracer ZN524 controller and the hardwired signal to the occupancy input is calling for unoccupied opera­tion.
O
CCUPIED BYPASS mode
The OCCUPIED BYPASS mode is used to transition the unit from the UNOCCUPIED mode to the occupied mode for a peri­od of time from 0 to 4 hours (config­urable through Rover. Default=2 HRS).
The controller can be placed in
OCCUPIED BYPASS mode by either com-
municating an occupancy request of bypass or by using the
TIMED OVERRIDE
(i.e., ON) button on the Trane zone sen­sor.
O
N and CANCEL Buttons
Some Trane zone sensors have ON and C
ANCEL buttons for timed override
operation. Pressing the On button on the zone sensor when the unit is in the
UNOCCUPIED mode initiates the OCCUPIED BYPASS mode and initializes
the bypass timer. The cancel button is used to send the unit back into
UNOCCUPIED mode before the bypass
timer has expired.
The On button may also be used for the unit identification or the “WINK” fea- ture. When the Tracer ZN524 controller is connected to a Tracer Summit sys­tem, Loop Controller, or the Rover serv­ice tool, the On button may be used in place of the service pin for easy unit identification.
Heating And Cooling Changeover Logic
The Tracer™ ZN524 Unit Controller can receive communicated requests for heating or cooling operation. The com­municated variable nviApplicMode is used to communicate the requests for the controller's operating mode based on the following values: 0 = Auto (mode determined by con­troller) 1 = Heat (uses heating setpoints) 2 = Morning Warm-up 3 = Cool (uses cooling setpoints) 5 = Pre-cool (morning cool down) 6 = Off (no unit operation allowed) 7 = Test (special test mode) 9 = Fan Only (no heating or cooling)
Page 25
CNT-SVX11A-EN 25
Unit Operation
All other numers will be interpreted as Auto.
As the controller automatically deter­mines its heating or cooling mode, it changes from cool to heat or from heat to cool, while the error (integrated over time between the active setpoint and the space temperature) is (900
°F • Sec).
Integration only begins once the heat­ing and cooling capacity is equal to 0% (See Figure 15).
Heat/Cool Changeover Logic
If the measured space temperature is 69
°F and the active cooling setpoint is
72
°F, the error between the space tem-
perature and the setpoint is three degrees. If the same error exists for one minute (60 seconds), the integration term is (3
°F • 60 Sec) or (180°F • Sec).
The Tracer™ ZN524 Unit Controller changes from heating to cooling and cooling to heating when the integration term exceeds (900
°F • Sec). Along with
satisfying the integration for heating and cooling changeover, the measured space temperature must fall outside the setpoint range. This means the space temperature must be greater than the active cooling setpoint or lower than the active heating setpoint.
Example: If the cooling setpoint is 75
°F
and the heating setpoint 70°F, any space temperature greater than 75
°F or less
than 70
°F is outside the setpoint range.
Once the integration term is satisfied and the space temperature is outside the setpoint range, the controller changes modes. However, before the unit's heating or cooling capacity ramps up, the controller checks to make sure it is capable of heating or cooling.
In instances where waterside economizers or boilerless controls are in use, it is necessary to verify the water temperature before unit opera­tion is allowed.
Figure 15: Heat/Cool Changeover logic
Page 26
26 CNT-SVX11A-EN
Unit Operation
Cooling Operation
During the COOLING mode, the Tracer ZN524 controller attempts to maintain the space temperature at the active cooling setpoint, which is one of the following:
• Occupied cooling
• Occupied standby cooling
• Unoccupied cooling
The controller uses the measured space temperature, the active cooling setpoint along with the control algorithm to determine the requested cooling capac­ity of the unit (0-100%). The outputs are controlled based on the unit configura­tion and the requested cooling capacity.
Heating Operation
During the heating mode, the Tracer ZN524 controller attempts to maintain the space temperature at the active heating setpoint, which is one of the following:
• Occupied heating
• Occupied standby heating
• Unoccupied heating
The controller uses the measured space temperature, the active heating setpoint along with the control algorithm to determine the requested heating capac­ity of the unit (0-100%). The outputs are controlled based on the unit configura­tion and the requested heating capacity.
Fan Operation
The Tracer ZN524 controller also allows the fan speed to be configured as auto. When the fan speed switch is in the auto position and the default fan speed is configured as auto, the unit may change between cycling and continu­ous, depending on how the default fan speeds are configured for heating and cooling modes.
The fan mode request can be either hardwired or communicated to the Tracer ZN524 controller. When both are present, the communicated request has priority over the hardwired input.
During o
CCUPIED, OCCUPIED STANDBY,
and
OCCUPIED BYPASS modes, the fan
will operate as configured (cycling or continuous). The fan may be controlled off in these mode when the MANUAL
OUTPUT TEST
has been initiated, a latch­ing diagnostic is present, or the com­municated or hardwired fan speed is off.
During the UNOCCUPIED
mode, the unit
fan is controlled off. When capacity is required to maintain the U
NOCCUPIED
heating or cooling setpoint, the unit fan is controlled on until the UNOCCUPIED setpoint is satisfied.
Fan Off Delay
If the fan is configured for cycling and the heating output is controlled off, the Tracer ZN524 Unit Controller automati­cally holds the fan on for an additional 30 seconds. This 30-second delay gives the fan time to blow off any residual heat from the heating source.
Entering Water Temperature Sampling Function
The Tracer ZN524 controller will sample the Entering Water Temperature (EWT) to determine proper control action for units equipped with boilerless electric heat or Waterside Economizer (WSE). Each unit is treated as having isolation valves - whether present or not. If the EWT is communicated to the controller via a BAS system, then no sampling will be required.
If the EWT is present as a hardwired input and communicated from a BAS, the communicated value will be used. When the EWT sample is used, the iso­lation valve on circuit 1 will be driven open for 3 minutes and the EWT read­ing will be taken at that time.
To avoid sampling each time a new cooling/heating request is initiated, the last EWT value recorded is used for the next (1)hour. During boilerless control heating, if setpoint has not been met following the hour, a new EWT reading is made and the appropriate control action is taken.
During WSE and DX operation, the EWT is refreshed as often as the analog imput is polled. NOTE: If the WSE is dis­able due to enable setpoint AND DX cooling is in operation, DX cooling will not be disabled until the load is met. This will occur even if the EWT has lowered to the point the WSE can be used. Refer to the WSE documentation for further details.
Sampling for Waterside Economizer Units
EWT is used to determine if WSE opera­tion is feasible. If the EWT meets the configured Enable setpoint, WSE opera­tion is possible.
Page 27
CNT-SVX11A-EN 27
Unit Operation
EWT sampling will be invoked when the following conditions have been met:
• EWT is not communicated via a BAS and:
• Unit is equipped with a WSE
The the following must occur:
• There is a new control request for cooling and isolation valve 1 is not open and more than 1-hour has elapsed since the last EWT sample
When these conditions are met, circuit 1 isolation valve is opened for 3-min­utes and the EWT reading is taken and WSE operation feasability is deter­mined. The isolation valve will remain open regardless.
Sampling for Electric Heat Units
For units equipped with electric Heat and configured for boilerless control, EWT is used to determine whether DX heating should be disabled and electric heat enabled. EWT sampling is invoked when the folowing conditions are met:
• EWT is not communication via a BAS and:
• Unit is equipped with electric heat configured for boilerless control and is not a cooling only unit
Then the following must occur:
• There is a new control request for heating and isolation valve 1 is not open and more than 1-hour has elapsed since the last EWT sample or:
• Boilerless electric heat is running and more than 1-hour has elapsed since the last EWT sample
When these conditions are met, circuit 1 isolation valve is opened for 3-min­utes, the EWT reading is taken and electric heat operation feasability is determined. If boilerless electric heat is enabled, the isolation valve will be closed, halting water flow to the unit.
The following chart provides a quick reference to unit configurations in which EWT is enabled:
Water-side Economizer Operation
The ZN524 supports the use of a 2-posi­tion Water Side Economizer (WSE). The WSE is only active in cooling mode and the EWT setpoint has been met. If the zone requires cooling and the WSE is enabled, the WSE valve will open and begin controlling the zone. If the WSE capacity can not cool the zone, then 1­stage of compressor cooling will be allowed to operate with the WSE. The second stage of compressor cooling will not be allowed to run, under any circumstances, when the WSE is in operation. Note: If the zone tempera­ture continues to rise, the WSE enable setpoint may need to be redueced in order to increase unit capacity.
When the WSE and the compressor are running simultaneously, coil frosting may occur. The ZN524 controls two devices to prevent this from occuring.
Coil Icing Protection
A fixed temperature device is mounted to the evaporator coil and wired to a binary input on the ZN524 controller. When the binary input on the ZN524
trips ( in alarm situations) the following actions will occur:
Note: The fan will remain on during this operation
This low-level diagnostic will automati­cally rest when the binary input changes to the normal state. The com­pressor minimum on and off times (3 minutes) will be enforced during this mode.
Low Leaving Air Protection
This mode is activated during WSE operation and controlled by the dis­charge air sensor. If the discharge air temperature drops below 45 F for 1­minute while the unit is economizing, the following actions will occur:
Note: The fan will remain on during this operation
This low-level diagnostic will reset when the discharge air temperature has risen above 50 F. The compressor mini­mum on and off times (3 minutes) will be enforced during this mode.
EWT
Sampling
Enabled
Unit Build Configuration
No Heat pump (HP)
Yes HP with WSE
Yes HP + electric heat (boilerless)
Yes HP + electric heat + WSE
No HP + electric heat (concurrent)
Yes HP + electric heat (concurrent) + WSE
No Cooling only
Yes Cool only with WSE
No Cool + electric heat (boilerless)
Yes Cool + electric heat (boilerless) + WSE
Cooling Mode Control Action
Economizer None
Economizer & 1-stage DX Disable 1st Stage DX
1st and 2nd stage DX
Disable DX
stages 1 and 2
Cooling Mode Control Action
Economizer None
Economizer & 1-stage DX Disable 1st Stage DX
1st and 2nd stage DX None
Page 28
28 CNT-SVX11A-EN
Unit Operation
Electric Heat Operation
The Tracer ZN524 supports 1-stage elec­tric heat in one of three ways: Supplemental, Boilerless and Main heat.
Supplemental
When applied, the electric heat is cycled on as the last stage of heating. Compressor 1 and 2 (where applicable) will be energized and the electric heat will operate concurrently with the com­pressors as needed to maintain space temperature.
Boilerless
When applied, the electric heat will be enabled based on EWT. The compres­sor(s) and electric heat is not allowed to operate at the same time. Boilerless electric heat is controlled by the EWT and compressor heat disable setpoint. If the unit is in the heating mode and the EWT falls below the compressor heat disable setpoint, then the com­pressor will be disabled for heating and the electric heat will be cycled to main­tain temperature.
Boilerless control will be disabled if the EWT rises 5 F above the compressor heat disable setpoint. The EWT value can be either local or communicated. In applications where the local water sen­sor is used, the unit may utilize the Entering Water Temperature Sampling function to verify water temperature.
Main Heat
The electric heat will be utilized as the only form of heat for the unit. The com­pressor and electric heat will not oper­ate at the same time. When in the heat­ing mode the electric heat cycle to maintain space temperature.
Compressor (DX) Cooling
The ZN524 controller supports two stages of DX cooling. The control is pro­portional and based on an error rate of 3 F for single compressor operation and 5 F for 2-compressor units. Zone temperature is compared against active setpoints for compressor operation:
O
FF, pulse width modulation or ON.
Note: When the control is in the dehumidification mode only O
FF
and ONare valid compressor states.
At start-up or during mode transition, if both compressors are requested to run, compressor 1 will be energized first. Compressor 2 waits until the next con­trol cycle (10 seconds) to energize.
Water Isolation Valves
The ZN524 supports the operation of water isolation valves for varialble speed pumping systems. Up to 2 isola­tion valves are supported, one for each compressor circuit. The valves are spring return and normally closed. The ZN524 operates as if isolation vlalves are present. The presence or absence of isolation valves is not a configuration factor.
Under normal operation, the ZN524 opens the isolation valve(s) under the following conditions:
• DX Heating request
• DX Cooling or WSE request
• When control is in DX heat or cool mode AND is controlling with pulse width modulation, the valves will remain open during the pulse width modulation cycle.
• Dehumidification request
• EWT sampling request. Valves will remain open for 3 minutes.
• Manual testing
• During DX operation. The valves will open for 20 seconds to ensure adequate water flow before energizing the compressor outputs.
• Upon opening, the valves remain open for a 10 minute minimum to reduce excessive valve cycling.
Note: If only a single isolation valve is used on a two-circuit heat unit, it must be wired to the isola­tion valve 1 output.
Isolation valve 1 must remain open as long as the control is in an active cool­ing, heating, or dehumidification. If cir­cuit/compressor 1 is taken off-line, iso­lation valve 1 will remain open to allow operation of circuit 2.
Under normal operation, isolation valves will be closed under the follow­ing conditions:
• Compressor and WSE are controlled
O
FF
and the 10-minute minimum on has expired. Note: If the WSE is disabled due to economizer enable paramenter or through BAS system and cooling demand is still present, the isolation valve will remain open for compressor operation.
• Isolation valve 2 will close if compressor 2 is taken off-line due to a diagnostic or no capacity call and the 10-minute minimum on has expired
• Power is lost, valves de-energize to the closed position
• Manual test off
There is no time delay when an isola­tion valve is to be closed. The ouptut will be de-energized and the valve will spring return closed.
Page 29
CNT-SVX11A-EN 29
Unit Operation
Other Modes
DEHUMIDIFICATION
The ZN524 controller controls the zone to the active cooling setpoint using pro­portional control. The ZN524 also con­trols one stage of DX cooling in con­junction with one stage of reheat. The only supported dehumidification type during this period is hot gas reheat.
The factory-supplied ZN524 supports one binary output for the control of a two-position hot gas reheat solenoid valve. This valve is normally closed and will open when energized providing the flow of hot refrigerant gas through the reheat coil. The reheat coil is sized to provide neutral air at 75 F loop condi­tion with 75 F dry bulb return air at 75% relative humidity. When in the dehu­midification mode, only the first stage DX cooling will be allowed to run on two stage units.
Active dehumidification can only occur when the controller is in the cooling mode. Active dehumidification is not allowed in heating mode. Dehumidification can be active during all time of day schedules.
A humidity transmitter is used to meas­ure the zone relative humidity and is compared against the relative humidity enable/disable setpoints. Relative humidity level can be communicated to the ZN524 from a Tracer Summit sys­tem. The default values for dehumidifi­cation enable is 60% relative humidity. Disable point is 52% relative humidity. These values are configurable.
To avoid subcooling the space if the reheat is not sized properly or during certain system conditions, a low limit temp is established to exit dehumidifi­cation mode. The low limit is the active cooling setpoint in the O
CCUPIED and
UNOCCUPIED standby modes.
In the U
NOCCUPIED
mode, the default
O
CCUPIED cooling setpoint is used as the
low limit. This enables extended dehu­midification during unoccupied modes which allows sub-cooling the space to the default O
CCUPIED setpoint. If the
zone temperature reaches the low limit the DX cooling and reheat will be turned off. The zone temperature must then rise 0.75 F above the low limit before the DX cooling and reheat are allowed to operate again.
Note: While in the dehumidification mode, if there is a call for capacity by the unit, the zone temperature setpoint will take priority over the relative humidity setpoints.
Dehumidification will occur during the following:
• Unit mode = cooling
• Relative humidity > Enable setpoint
Reheat in the dehumidification mode is utilized under the following conditions:
• Zone temp is above the active cooling setpoint
• Zone temp error < 1.5 F above the active cooling setpoint
The compressor will be energized 100% of the time during dehumidification mode. No pulse width modulation is used during dehumidification.
Dehumidification will occur during the following:
• Unit mode = cooling
• Relative humidity > Enable setpoint
Reheat in the dehumidification mode is utilized under the following conditions:
• Zone temp is above the active cooling setpoint
• Zone temp error < 1.5 F above the active cooling setpoint
Compressor 2 will not be on at the
same time as the reheat solenoid. No pulse width modulation is used during dehumidification.
For both single and two-stage cool­ing, the following conditions will cause the ZN524 to transition out of dehumid­ification mode:
• Relative humidity [ disable setpoint
• Zone temp á 1.5 F
• Unit mode = heating
Note: For both single and two­stage cooling, the occupied cool­ing and occupied heating setpoints can be the same, which may create some risk of switching over to heating mode unless the transition.
D
EFROST
For defrost operation, a sensor is wired to BIP 1. When a defrost condition is detected, the compressor(s) are dis­abled, and the unit is placed in the
DEFROST mode.
During DEFROST the compressor(s) are off, and the fan will continue to operate as continuous. The unit will remain in the
DEFROST mode until the sensor
resets. The unit will return to NORMAL operation after the mode is discontin­ued.
P
RE-HEAT
The Tracer ZN524 controller keeps the 2-position outdoor air damper closed anytime during the OCCUPIED mode when the space temperature is 3°F or more below the heating setpoint.
The damper remains closed indefinitely during morning pre-heat until the space temperature is within 2°F of the effec­tive heating setpoint. The unit runs at full capacity until setpoint is met.
Page 30
30 CNT-SVX11A-EN
Unit Operation
PRE
-COOL
The Tracer ZN524 controller keeps the 2-position outdoor air damper closed for up to one hour at every transition from unoccupied to occupied mode when the space temperature is 3°F or more above the cooling setpoint.
The damper remains closed during pre­cool until the space temperature is within 2°F of the effective cooling set­point. The unit runs at full capacity until setpoint is met.
Output Overrides
Manual Output Test
Manual output test allows the binary outputs to be energized in a predefined sequence. (For more information see, Manual Output Test, on pages 32-33 for more information.)
Fan Status
There are two ways to do fan status monitoring:
1. The status of the fan is reported based on the state of the binary out put(s) dedicated to fan control. The fan status is reported as
ON
whenever the corresponding binary output is directed on. The fan status is reported as off when the fan output is directed
ON.
2. The Tracer ZN524 controller has a binary input available for a fan status device (current sensing relay) which can provide feedback of fan operation. If the device does not indicate fan operation after 1 minute as commanded
ON, a unit shut down
is initiated, and the unit is latched
OFF.
Filter Status/Maintenance Timer
The unit filter status\maintenance timer is based on the cumulative run hours of the unit fan. The controller compares the fan run time against an adjustable fan run hour limit and recommends unit maintenance as required.
The Rover service tool is used to edit the maintenance required setpoint time. Once the setpoint limit is exceed­ed, the controller generates a mainte­nance required informational diagnos­tic. When the
MAINTENANCE REQUIRED set-
point time is set to zero, the controller disables this feature.
The Tracer Summit, Tracker or the Rover service tool are required to clear the
MAINTENANCE REQUIRED
informational diagnostic. Once the diagnostic is cleared, the controller resets the fan run time to zero and begins accumulat­ing fan run hours again.
Note: If at any time the unit loses power, the timer is reset to zero.
Page 31
CNT-SVX11A-EN 31
Unit Operation
Figure 16: Simple data sharing application
Figure 17: More complex data sharing application
ZN524
ZN524
ZN524
Master
Comm5 Link
Zone Sensor
Slave
Slave
Slave
B1
Slave
A2
Slave
A1
Master
A
Master
B
Tracer Summit
Zone
Sensor
Zone
Sensor
Zone BZone A
Data Sharing—LonWorks
Tracer ZN524 allows peer-to-peer data communication through the use of LonWork’s technology. Data such as space temperature setpoint, occupancy, etc. can be shared from a master con­troller to a peer controller over a twist­ed pair of communication wire with or without the presence of a front end building management system. (See
Figure 16: “Simple data sharing appli­cation”) This ability allows units to operate with the same data to prevent conflicting control.
Data sharing is established through the use of “bindings”. Bindings are set up through the Rover service tool.
The Tracer ZN524 controller includes a network variable for master/slave oper­ation. This variable includes all of the
information required for the slave units to operate with master controller. (See Figure 17: “More complex data sharing application”)
For more information on establishing bindings, see the Rover service tool manual. For a complete listing on shared points see
“Appendix—Data
Lists” on page 47.
Page 32
32 CNT-SVX11A-EN
Troubleshooting
Important! When viewing the Tracer ZN524 through the Rover service tool, it is important that the version be up-to-date. To help ensure that your version is the most recent, contact you local Trane sales representative or service center.
WARNING
Live Electrical Components
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in han­dling live electrical components per­form these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Led Operation
Table 15:
Red Service LED
Black Service Push Button
Note: If the Service push button is held down for more than 15
seconds, the Tracer ZN524 Unit Controller will uninstall itself from the ICS communication network and shut down all unit operation. This mode is indicated by the red Service LED flashing once every second. See the Red Service LED section. Use Rover service tool to restore the unit to normal operation.
The Service push button, located at the bottom center of the con­troller, can be used to install the Tracer ZN524 Unit Controller in a communication network. Refer to the Rover and Tracer Summit product literature for more information.
Green Status LED
The green LED normally indicates whether or not the controller is pow­ered on (24 VAC).
Table 16:
Green status LED activity
Yellow Comm LED
The yellow Comm LED blinks at the rate the controller receives communica­tion. The yellow LED does not blink when the controller is transmitting communication data.
Table 17:
Yellow comm LED activity
Manual Output Test
The test sequence verifies output and end device operation. The manual out­put test can be conducted to verify out­put wiring and actuator operation, with­out using the Rover service tool, by pressing the test button.
Many service calls are initiated due to unit diagnostics, so the test sequence attempts to clear unit diagnostics and restore normal unit operation prior to testing the outputs. If the diagnostics remain after an attempt to clear diag­nostics, the status LED lights in a two­blink pattern, indicating the diagnostic condition is still present.
See Table 18, Page 33 for more details.
Yellow LED Description
activity
LED off Controller is not detecting
continuously. any communication.
(Normal for standalone applications.)
LED blinks or . The controller detects flickers communication. (Normal
for communicating applications, including data sharing.)
LED on Abnormal condition or continuously. extremely high traffic on
the link.
Red LED Description
activity
LED is off continuously after power is Normal operation. applied to the controller.
LED is on continuously, Someone is pressing even when the Service push button power is first or the controller has applied to the failed. controller.
Un-install (normal
controller mode). Use LED flashes Rover service tool to about once restore the unit to normal every second. operation. Refer to the
Rover product literature
for more information.
Green LED Description
activity
LED is on Power on continuously. (normal operation).
LED blinks The controller is in (1 blink per manual output test mode. second) No diagnostics present.
The controller is in manual LED blinks output test mode. (2 blinks One or more diagnostics per second). are present.
LED blinks Wink mode 1/4 second on, 1/4 second off for 10 seconds
Power is off. LED off Controller failure.
Test button is pressed.
Figure 19:
Blue
test button
Figure 18:
Black service button
Page 33
CNT-SVX11A-EN 33
Troubleshooting
If a two-blink pattern remains after an attempt to clear diagnostics, the diag­nostic condition is still present and may affect the manual output test. The diag­nostic must then be cleared using another method. (See “Resetting Diagnostics” on page 35 for more information.)
Test Procedure
The procedure for testing is:
1. Press and hold the Test button for at least two seconds, then release the button to start the test mode.
2. When manual output test mode begins, the controller turns off all out puts and calibrates end devices closed.
3. Press the Test button once to advance through each step of the test sequence.
Note: To help ensure accurate testing do not press the test button more than once per second.
Alternatively, the manual output test can be controlled over the communica­tions network by using Rover. When conducting the manual output test via communications network, the sequence must start with Step 1 (
OFF), as shown
in Table 18.
Step Fan Reversing Elec. Heat/ Compressor Compressor Isolation Isolation Water-side Outside Air Generic
Valve Reheat 1 2 Valve 1 Valve 2 Economizer Damper
BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10
1. Off
1
Off Off Off Off Off Off Off Off Off Off
2. Fan
2
On
3. Isolation On On Valve 1
4. Waterside On On On
Economizer
5. Isolation On On On Valve 1 & 2
6. Reversing On On On On Valve
7. 1st Stage On On On On On
Cool
8. 1st & 2nd On On On On On On
Stage Cool
9. Heat Mode:
See Table Below
10.
Compressor
3
On On On
11. 1st Stage On On On On
Heat
12. 2nd Stage On On On On On
Heat
13. Outside
4
On On
Air Damp.
14. Generic
5
On On
Output
1. Upon entering manual output test mode, the controller turns off all fan outputs and drives all dampers and valves closed (if required).
2. At the beginning of Step 2, the controller attempts to clear all diagnostics.
3. This stage helps avoid an abrupt transition from cooling to heating by turning off the compressors prior to changing the reversing valve state.
4. Binary output 9 (BOP9) will be controlled during this step regardless of its configuration.
5. After the generic output setup, the test sequence performs the exit step. This initiates a reset and attempts to return the controller to normal operation.
9. Hot Gas On On On On On On
9. No Heat/ On On On On
Boilerless
9. Concurrent On On On On On On
Heat Type
Table 18: Test sequence
Page 34
34 CNT-SVX11A-EN
Troubleshooting
Diagnostics
Fan Failure
A “Low Air Flow—Fan Failure” diagnos­tic is generated when a fan status device is present and fails to close after 1 minute of unit start-up or when it opens for more than 1 minute during normal unit operation.
Space Temperature Failure
If the Tracer ZN524 has validated a space temperature input and then the input becomes invalid, a space temper­ature failure diagnostic occurs.
Entering Water Temperature Failure
If the Tracer ZN524 has validated an entering water temperature input and then the input becomes invalid, an entering water temperature failure diag­nostic occurs.
Discharge Air Temperature Limit
When the discharge air exceeds the low limit setpoint and the unit can not cor­rect it by altering capacity, a “Discharge Air Temp Limit” diagnostic is generated.
Outdoor Air Temperature Failure
If the Tracer ZN524 has validated an outdoor air temperature input and then the input becomes invalid, an outdoor air temperature failure diagnostic occurs.
Humidity Input Failure
If the Tracer ZN524 has validated a rela­tive humidity input and then the input becomes invalid, a humidity input fail­ure diagnostic occurs.
CO
2
Sensor Failure
If the Tracer ZN524 has validated a CO
2
input and then the input becomes invalid, a CO2input failure diagnostic occurs.
Generic AIP Failure
If the Tracer ZN524 has validated a generic analog input and then the input becomes invalid, a generic analog input failure diagnostic occurs.
Defrosting-Compressor Lockout
The defrost stat used with Tracer ZN524 on DX units is wired in series with the condensing unit. When it opens to indi­cate a frost condition, the Tracer ZN524 senses the open circuit and de-ener­gizes the compressor output. A defrost­ing diagnostic is generated at this point.
Maintenance Required
Note: If power to the unit is cycled or discontinued for any reason, all maintenance timers are automati­cally reset.
The “Maintenance Required” diagnostic is generated when the fan run-time exceeds the configurable limit. This diagnostic is useful for filter change notification.
Local Fan Mode Failure
If the hardwired fan mode input to the Tracer ZN524 controller is present and then becomes invalid, a local fan mode failure diagnostic is generated.
Local Setpoint Failure
If the hardwired setpoint input to the Tracer ZN524 controller is present and then becomes invalid, a local setpoint failure diagnostic is generated.
Generic Temperature Failure
If the Tracer ZN524 has validated a generic temperature input and then the input becomes invalid, a generic tem­perature input failure diagnostic occurs.
Invalid Unit Configuration
If the Tracer ZN524 has been configured improperly or loses its configuration, an invalid unit configuration diagnostic is generated. The unit must be re-con­figured with a valid configuration to correct this problem.
Page 35
CNT-SVX11A-EN 35
Troubleshooting
Diagnostic Unit Response Latching/ Reset
non-latching
Fan—off Auto reset once within 24 hrs.
Valves—closed If safety generates a diagnostic High/Low Pressure Compressor - off Latching more than once a communicated Cutout
2
or manual reset will be necessary
Fan—off Low Air Flow/ Valves—closed Fan Failure
2
Compressors—off Latching Communicated or manual reset
Space Fan—off
Temperature Valves—closed
Failure
2,3
Compressors—off Non-latching Communicated or manual reset
Entering Fan—enabled Water Temperature Boilerless control—disabled Failure
2,3
Waterside Economizer—enabled Non-latching Communicated or manual reset
Discharge Air Fan—on Auto reset once within 24hrs.
Temperature Compressor—disable If safety generates a diagnostic
Limit Waterside Economizer—enabled Non-Latching more than once a communicated
or manual reset will be necessary.
Discharge Fan—enable Air Temperature Failure
2,3
Compressors—enabled Non-latching Communicated or manual reset
Outdoor Air Fan—enable
Temperature Compressor—enable Non-latching Communicated or manual reset
Failure
2,3
Table 19: Tracer ZN524 Unit Controller diagnostics
1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics. 2: During manual output test, these diagnostics make the green status LED flash in a two-blink pattern. For more information see, Manual Output Test, on page 32. 3: These diagnostics are non-latching and automatically reset when the input is present and valid.
Page 36
36 CNT-SVX11A-EN
Troubleshooting
Diagnostic Unit Response Latching/ Reset
non-latching
Fan—enabled
Valves—enabled Humidity Input Failure
3
Compressor—enabled Non-latching Communicated or manual reset
Reheat—disabled
CO2 Sensor Fan—enabled Failure
3
Valves—enabled Non-latching Communicated or manual reset
Compressor—enabled
Generic AIP No Unit Reaction Non-latching Communicated or manual reset Failure
3
Maintenance Fan—enabled Required Valves—enabled Non-latching Communicated or manual reset
Compressor—enabled
Local Fan—enabled Fan Mode Valves—enabled Non-latching Communicated or manual reset Failure
3
Compressor—enabled
Local Fan—enabled Setpoint Valves—enabled Non-latching Communicated or manual reset Failure
3
Outdoor air damper—enabled
Invalid Fan—disabled Unit Valves—disabled Latching Communicated or manual reset Configuration
2
Compressor—disabled
Fans—enabled Normal Valves—enabled Non-latching N/A
Compressor—enabled
Table 19: Tracer ZN524 Unit Controller diagnostics - continued
1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics. 2: During manual output test, these diagnostics make the green status LED flash in a two-blink pattern. For more information see, Manual Output Test, on page 32. 3: These diagnostics are non-latching and automatically reset when the input is present and valid.
Page 37
CNT-SVX11A-EN 37
Troubleshooting
Translating Multiple Diagnostics
The controller senses and records each diagnostic independently of other diag­nostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur.
Resetting Diagnostics
There are many ways to reset unit diag­nostics:
• Automatically by the controller
• By initiating a manual output test at the controller
• By cycling power to the controller
• By using a building automation system
• By using the Rover service tool
• By cycling the fan switch from off to
ON or AUTO
High/Low Pressure Cutout
The Tracer™ ZN524 Unit Controller includes an automatic diagnostic reset function. This function attempts to auto­matically recover a unit when the High/Low Pressure Cutout diagnostic occurs. When this diagnostic occurs, the controller responds as defined in Table 19: Tracer™ ZN524 Unit Controller diagnostics.
After the controller detects the High/Low Pressure Cutout diagnostic, the unit waits 30 minutes before invok­ing the automatic diagnostic reset func­tion. The automatic diagnostic reset function clears the High/Low Pressure Cutout diagnostic and attempts to restore the controller to normal opera­tion. The controller resumes normal operation until another diagnostic occurs.
If a High/Low Pressure Cutout diagnos­tic reoccurs within 24 hours after an automatic diagnostic reset, you must manually reset the diagnostic. See other possible methods for resetting diagnostics in this section.
Manual output test
The test button on the controller may be used either during installation to verify proper end device operation or during troubleshooting.
When the Test button is pressed, the controller exercises all outputs in a pre­defined sequence. The first and last steps of the sequence reset the con­troller diagnostics. (See “Manual Output Test” on page 32 for more infor­mation.)
Cycling power
When turned-off, the controller's 24 VAC power, and power is reapplied, the unit cycles through a power-up sequence and clears all timers. By default, the controller attempts to reset all diagnostics at power-up.
Diagnostics present at power-up and those that occur after power-up are handled according to the defined unit diagnostics sequences (For more infor­mation see,Table 19).
Building automation system
Some building automation systems (i.e., Tracer Summit, Tracker or Tracer Loop Controller building automation system) can reset diagnostics in the Tracer ZN524 unit controller. For more complete information, refer to the prod­uct literature for the building automa­tion system.
Rover service tool
Rover service tool can reset diagnostics in the Tracer ZN524 unit controller. For more complete information, refer to the Rover Installation, Operation, and Programming manual.
Diagnostic reset
Any device that can communicate the network variable nviRequest (enumera­tion “clear_alarm”) can reset diagnos­tics in the Tracer ZN524 unit controller. The controller also attempts to reset diagnostics whenever power is cycled.
Cycling the fan switch
If the user cycles the fan speed switch from off to
ON or AUTO, the controller
resets all diagnostics. Diagnostics may recur immediately if the problem still exists.
Page 38
38 CNT-SVX11A-EN
Troubleshooting
Probable cause Possible Explanation
Unit wiring The wiring between the controller outputs and the fan contactor must be present and correct
for normal fan operation
No power to the controller If the controller does not have power, the unit fan does not operate. For the Tracer ZN524 Unit
Controller to operate normally, it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have sufficient power or has failed.
Unit configuration The controller must be properly configured based on the actual installed end devices and application.
When the unit configuration does not match the actual end devices, the fans may not work correctly.
Random-start observed After power-up, the controller always observes a random-start from 5 to 30 seconds. The controller
remains off until the random-start time expires.
Power-up control wait When power-up control wait is enabled (non-zero time), the controller remains off until one of two
conditions occurs:
1. The controller exits power-up control wait once it receives communicated information.
2. The controller exits power-up control wait once the power-up control wait time expires.
Diagnostic present A specific list of diagnostics affects fan operation. For more information see, Table 19: Tracer ZN524
Unit Controller diagnostics, page 33.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and
associated output wiring. However, based on the current step in the test sequence, the unit fan may not be on. For more information see, Manual Output Test, on page 32 for more information.)
Fan mode off When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the off
position controls the unit off.
Requested mode off You can communicate a desired operating mode (such as off, heat, and cool) to the controller. When off
is communicated to the controller, the unit controls the fan off. There is no heating or cooling.
Unoccupied operation When the controller is in the unoccupied mode, the fan is cycled.
Cycling fan operation/continuous The controller can cycle fan with unit capacity. If no capacity is present, the fan will be de-energized
Table 19:
Fan Outputs do not energize
Fans
Page 39
CNT-SVX11A-EN 39
Troubleshooting
Probable cause Possible Explanation
Unit wiring The wiring between the controller outputs and the valve(s) must be present and correct for normal
valve operation.
Random-start observed After power-up, the controller always observes a random-start from 5 to 30 seconds. The controller
remains off until the random-start time expires.
Power-up control wait When power-up control wait is enabled (non-zero time), the controller remains off until one of two
conditions occurs:
1. The controller exits power-up control wait once it receives communicated information.
2. The controller exits power-up control wait once the power-up control wait time expires.
Diagnostic present A specific list of diagnostic affects valve operation. For more information see, Table 19 for more
information
Manual output test The controller includes a manual output test sequence you can use to verify output operation and
associated output wiring. However, based on the current step in the test sequence, the valve(s) may not be open. For more information see, Manual Output Test, on page 32 for more information.)
Fan mode off When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the off
position controls the unit off and valves to close.
Requested mode off You can communicate a desired operating mode (such as off, heat, and cool) to the controller. When off
is communicated to the controller, the unit controls the fan off. There is no heating or cooling (valves are closed).
Sampling logic The controller includes entering water temperature sampling logic which is automatically invoked
when a waterside economizer or boilerless control is present. For more information see, Entering Water Temperature Sampling, on Sampling logic page 26 for more information.)
Table 20:
Isolation valves stay closed
Probable cause Possible Explanation
Unit wiring The wiring between the controller outputs and the valve(s) must be present and correct for normal
valve operation.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and
associated output wiring. However, based on the current step in the test sequence, the valve(s) may be open. For more information see, Manual Output Test, on page 32 for more information.)
Sampling logic The controller includes entering water temperature sampling logic which automatically invoked during
when waterside economizer or boilerless control is present. For more information see, Entering Water Temperature Sampling, on page 26 for more information.)
Normal operation The controller opens and closes the valves to meet the unit capacity requirements.
Table 21:
Isolation valves stay open
Valve s
Page 40
40 CNT-SVX11A-EN
Troubleshooting
Probable cause Possible Explanation
Unit wiring The wiring between the controller outputs and the end devices must be present and correct for normal
operation.
Unit configuration The controller must be properly configured based on the actual installed end devices and application.
When the unit configuration does not match the actual end devices, the unit may not work correctly.
Diagnostic present A specific list of diagnostics affect compressor and electric heat operation. For more information see,
Table 19, page 35 for more information.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and
associated output wiring. However, based on the current step in the test sequence, the DX or electric outputs may be off. For more information see, Manual Output Test, on page 32 for more information.)
Normal operation The controller energizes the outputs only as needed to meet the unit capacity requirements.
Table 22:
Compressor or electric heat output(s) do not energize
DX/Electric Heat
Probable cause Possible Explanation
Unit wiring The wiring between the controller outputs and the outdoor air damper must be present and correct for
normal damper operation.
Unit configuration The controller must be properly configured based on the actual installed end devices and application.
When the unit configuration does not match the actual end devices, the damper may not work correctly.
Random-start observed After power-up, the controller always observes a random-start from 5 to 30 seconds. The controller
remains off until the random-start time expires.
Power-up control wait When power-up control wait is enabled (non-zero time), the controller remains off until one of two
conditions occurs:
1. The controller exits power-up control wait once it receives communicated information.
2. The controller exits power-up control wait once the power-up control wait time expires.
Diagnostic present A specific list of diagnostics affects outdoor air operation. For more information see, Table 19
on page 35 for more information.)
Manual output test The controller includes a manual output test sequence you can use to verify output operation and
associated output wiring. However, based on the current step in the test sequence, the unit damper may not be open. For more information see, Manual Output Test, on page 32 for more information.)
Fan mode off When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the off
position controls the unit off and damper to close.
Table 23:
Outside air damper stays closed
Outside Air Damper
Page 41
CNT-SVX11A-EN 41
Troubleshooting
Probable cause Possible Explanation
Requested mode off You can communicate a desired operating mode (such as off, heat, and cool) to the controller. When off
is communicated to the controller, the unit controls the fan off. There is no heating or cooling (valves are closed).
Unoccupied mode When the controller is in the unoccupied mode, the outdoor air damper remains closed.
Warm up and cool-down The controller includes both a morning warm up and cool-down sequence to keep the outdoor air
damper closed during the transition from unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible.
The controller opens and closes the outdoor air damper based on the controller's occupancy mode and
Normal operation fan operation. Normally, the outdoor air damper is open during occupied, occupied standby, and
occupied bypass mode when the fan is running and closed during unoccupied mode.
Table 23:
Outdoor air damper stays closed - continued
Probable cause Possible Explanation
Unit wiring The wiring between the controller outputs and the outdoor air damper must be present and correct for
normal damper operation.
Unit configuration The controller must be properly configured based on the actual installed end devices and application.
When the unit configuration does not match the actual end devices, the damper may not work correctly.
Manual output test The controller includes a manual output test sequence you can use to verify output operation and
associated output wiring. However, based on the current step in the test sequence, the unit damper may be open. For more information see, Manual Output Test, on page 32 for more information.)
The controller opens and closes the outdoor air damper based on the controller's occupancy mode and fan operation. Normally, the outdoor air damper is open during occupied, occupied standby, and
Normal operation occupied bypass mode when the fan is running and closed during unoccupied mode unless the
controller is economizing.
Table 24:
Outdoor air damper stays open
Probable cause Possible Explanation
Sensor reading too low
Unit economizing without much cooling capacity or unit stops DX heating early and switches to boiler­less electric heat.
Sensor reading too high
Unit not utilizing economizer capacity when possible or DX heating stays on longer than possible for boilerless electric heat unit.
Reading out of range Boilerless electric heat or waterside economizer disabled.
Table 25:
Entering Water Temperature sensor read-out error
Page 42
42 CNT-SVX11A-EN
Replacing Circuit Boards
Tracer ZN524 Unit Controller Replacement
WARNING Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout proce­dures to ensure the power can not be inadvertently energized. Failure to dis­connect power before servicing could result in death or serious injury.
1. Disconnect power or disable the
circuit breaker to unit.
2. Remove bad or questionable
Tracer ZN524 controller circuit board.
3. Install controller in the unit with
the heat-sink placement at the top of the control box.
4. Connect the power to the circuit
board ONLY.
5. Connect Rover and properly
configure the controller, unless a previously configured board is purchased.
6. Power down.
7. Connect the remaining input and output wiring to the controller and comm wire.
8. Reapply power.
9. Complete sequence 7 and 8 above in the installation section of this manual.
10. Record NID numbers and unit location
11. Refer to BAS manual for instructions on how to configure the new ZN524 into BAS system.
Page 43
CNT-SVX11A-EN 43
Appendix
Resistance (VV) Setpoint (°F)
889.4 50
733.6 58
577.9 66 500 70
422.1 74
344.2 78
266.4 82
188.5 86
110.6 90
Hardwired Setpoint Adjustment
Table 26: Hardwired setpoint adjustment
Fan Switch Resistance Values
Table 27: Resistance Values
Resistance (VV) Switch Position
16,300 High 10,700 Low
2,320 Auto 4,870 Off
Resistance (VV) Temperature
87.5kV 0°F
74.6kV 5°F
63.8kV 10
°F
54.6kV 15°F
46.9kV 20°F
40.4kV 25
°F
34.8kV 30°F
30.2kV 35°F
26.2kV 40
°F
22.8kV 45
°F
20.0kV 50°F
17.5kV 55
°F
15.3kV 60
°F
13.5kV 65°F
11.9kV 70
°F
10.5kV 75°F
Resistance (VV) Temperature
10.0kV 77°F
9.3kV 80°F
8.2kV 85°F
7.3kV 90°F
6.5kV 95°F
5.8kV 100°F
5.2kV 105
°F
4.7kV 110 °F
4.2kV 11 5 °F
3.8kV 120
°F
3.4kV 125
°F
3.1kV 130°F
2.8kV 135
°F
2.5kV 140
°F
2.3kV 145°F
2.1kV 150°F
Hardwired Thermistor Values
Table 28: Hardwired 10kV thermistor values
Page 44
44 CNT-SVX11A-EN
Appendix - Binary Configuration
Binary input Function Configuration Description
or output
BI 1 Low temp detection Normally closed Closed: BIP 1 is Normal (no diagnostic)
Open: BIP 1 is Active (diagnostic)
BI 2 Condensate overflow Normally closed Closed: BIP 2 is Normal (no diagnostic)
Open: BIP 2 is Active (diagnostic)
BI 3 Occupancy/Generic Normally closed Closed: BIP 3 is Normal (Occupied)
Open: BIP 3 is Active (Unoccupied)
1
Normally open Open: BIP 3 is Normal (Occupied)
Closed: BIP 3 is Active (Unoccupied)
1
BI 4 Fan status
2
Normally open When the controller commands the fan on and the binary input
remains open for one minute, BIP is normal (diagnostic). When the controller commands the fan on and the binary input closes, BIP is active (no diagnostic).
J1-1 Fan Normally open De-energized: Fan off
Energized: Fan on
J1-2 RV Normally open De-energized: Heat
Energized: Cool
J1-3 Electric Heat/ Normally open De-energized: Off
Reheat Energized: Electric Heat/Reheat active
TB4-1 and TB4-2 Generic binary output Normally open De-energized: Output off (de-energized)
Energized: Output on (energized)
1. The occupancy input applications vary for standalone and communicated instances. For more information, see Occupancy arbitration tables in the Appendix.
2. The fan status device is normally closed during normal fan operation. When the fan is off either from a fan failure or the controller com­manding the fan off, the binary input device opens.
Binary Configuration
Table 29: Binary configuration details
Page 45
CNT-SVX11A-EN 45
Appendix - Unit Operation
Unit Operation Based On The Effective H
EAT/C
OOL Output
Table 30: Unit operation based on H
EAT
/C
OOL
ouput
Application Heat/cool mode input Effective heat/ cool Unit Operation mode input
(nviHeatCool) mode output
(nviApplicMode) (nvoHeatCool)
Auto Determined by controller Fan—Enabled
Heating—Enabled Cooling—Enabled Damper—Enabled
Heat Heating Fan—Enabled
Heating—Enabled Cooling—Disabled Damper—Enabled
Morning warm up Pre-heat Fan—Enabled
Heating—Enabled Cooling—Disabled Damper—Disabled
Cooling Cooling Fan—Enabled
Heating—Disabled
1
Cooling—Enabled Damper—Enabled
Auto Pre-cool Pre-cool Fan—Enabled
Heating—Disabled
1
Cooling—Enabled Damper—Disabled
Off Off Fan—Disabled
Heating—Disabled Cooling—Disabled Damper—Disabled
Test Test Fan—Enabled
Heating—Enabled Cooling—Enabled Damper—Enabled
Fan only Fan only Fan—Enabled
Heating—Disabled Cooling—Disabled Damper—Enabled
Not present Determined by controller Fan—Enabled
Heating—Enabled Cooling—Enabled Damper—Enabled
Heat Any state Heating Fan—Enabled
Heating—Enabled Cooling—Disabled Damper—Enabled
Morning warm up Any state Pre-heat Fan—Enabled
Heating—Enabled Cooling—Disabled Damper—Disabled
Page 46
46 CNT-SVX11A-EN
Appendix - Unit Operation
Application Heat/cool mode input Effective heat/ cool Unit Operation mode input
(nviHeatCool) mode output
(nviApplicMode) (nvoHeatCool)
Cool Any state Cool Fan—Enabled
Heating—Disabled Cooling—Enabled Damper—Enabled
Pre-cool Any state Pre-cool Fan—Enabled
Heating—Disabled Cooling—Enabled Damper—Disabled
Off Any state Off Fan—Disabled
Heating—Disabled Cooling—Disabled Damper—Disabled
Test Any state Determined by controller Fan—Enabled
Heating—Enabled Cooling—Enabled Damper—Enabled
Fan only Any state Fan only Fan—Enabled
Heating—Disabled Cooling—Disabled Damper—Enabled
Note: Night purge, Emergency heat, and Nul modes are not supported by the Tracer ZN524 Unit Controller. If one of these modes is received by the controller, it is interpreted as Auto.
Table 30: Unit operation based on H
EAT/COOL
ouput - continued
Page 47
CNT-SVX11A-EN 47
Appendix ­Data Lists
Table 31: Input/Output listing
Data Lists
Table 31 provides an input/output list­ing for the Tracer ZN524 unit controller. The content of the lists conforms to both the LonMark Space Comfort Controller Functional Profile and the LonMark node object
Table 32: Configuration properties
Configuration property SNVT type SCPT reference Description
nciSndHrtBt
1
SNVT_time_sec SCPTmaxSendTime (49) Send heartbeat
nciSetpoints
1
SNVT_temp_setpt SCPTsetPnts (60) Occupancy temperature set
points
nciUnitType
1
SNVT_hvac_type SCPThvacUnitType (169) Unit type nciMinOutTm SNVT_time_sec SCPTminSendTime (52) Minimum send time nciRcvHrtBt SNVT_time_sec SCPTmaxRcvTime (48) Receive heartbeat nciLocation SNVT_str_asc SCPTlocation (17) Location label nciBypassTime SNVT_time_min SCPTbypassTime (34) Local bypass time nciSpaceRHSetpt SNVT_lev_percent SCPThumSetPT(36) Space RH Setpoint
Input SNVT type Output SNVT type
nviRequest SNVT_obj_request nvoStatus SNVT_obj_status
nviSpaceTemp
1
SNVT_temp_p nvoFileDirectory SNVT_address
nviSetpoint SNVT_temp_p nvoSpaceTemp
1
SNVT_temp_p
nviSetptOffset SNVT_temp_p nvoUnitStatus
1
SNVT_hvac_status
nviOccSchedule SNVT_tod_event nvoEffectSetpt SNVT_temp_p
nviOccManCmd SNVT_occupancy nvoEffectOccup SNVT_occupancy
nviOccSensor SNVT_occupancy nvoHeatCool SNVT_hvac_mode
nviApplicMode SNVT_hvac_mode nvoSetpoint SNVT_temp_p
nviHeatCool SNVT_hvac_mode nvoDischAirTemp SNVT_temp_p
nviFanSpeedCmd SNVT_switch nvoLoadAbsK SNVT_power_kilo
nviComprEnable SNVT_switch nvoTerminalLoad SNVT_lev_percent
nviAuxHeatEnable SNVT_switch nvoSpaceRH SNVT_lev_percent
nviEconEnable SVNT_switch nvoOutdoorTemp SNVT_temp_p
nviEmergOverride SNVT_hvac_emerg nvoSpaceCO2 SNVT_ppm
nviSourceTemp SNVT_temp_p nvoEnterWaterTemp SNVT_temp_p
nviSpaceRH SNVT_lev_percent nvoLeaveWaterTemp SNVT_temp_p
nviOutdoorTemp SNVT_temp_p
1. Required points under Space Comfort Controller profile. All other points are optional.
Page 48
48 CNT-SVX11A-EN
Location Identifier
Page 49
CNT-SVX11A-EN 49
Location Identifier
Page 50
50 CNT-SVX11A-EN
Location Identifier
Page 51
CNT-SVX11A-EN 51
Location Identifier
Page 52
Literature Order Number CNT-SVX11A-EN
Date August 2003
Supercedes New
Stocking Location Inland
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Trane A business of American Standard Companies www.trane.com
For more information, contact your local district office or e-mail us at comfort@trane.com
Loading...