Tracer ZN517 Unitary Controller Installation and Operation
This guide and the information in it are the property of American Standard Inc. and may not be used or reproduced in whole or in part,
without the written permission of American Standard Inc. Trane, a business of American Standard, Inc., has a policy of continuous
product and product data improvement and reserves the right to change design and specification without notice.
Although Trane has tested the hardware and software described in this guide, no guarantee is offered that the hardware and software
are error free.
Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trane may have patents or patent applications covering items in this publication. By providing this document, Trane does not imply
giving license to these patents.
The following are trademarks or registered trademarks of Trane: Trane, Tracer, Tracker, Rover.
®
™
The following are trademarks or registered trademarks of their respective companies or organizations: LonTalk and Neuron
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully:
WARNING
Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment damage or property damage.
The following format and symbol conventions appear at appropriate sections throughout this manual:
IMPORTANT
Alerts installer, servicer, or operator to potential actions that could cause the product or system to
operate improperly but will not likely result in potential for damage.
Note:
A note may be used to make the reader aware of useful information, to clarify a point, or to describe
options or alternatives.
◆This symbol precedes a procedure that consists of only a single step.
This guide provides installation and configuration information for the
Tracer ZN517 unitary controller, as well as a description of its operations.
The overview includes a product description, specifications, and descriptions of ancillary products that may be necessary.
Product description
The Tracer ZN517 is an application-specific controller that provides
direct digital, zone temperature control. The controller can operate as a
stand-alone device or as part of a building automation system (BAS).
Communication between the controller and a BAS occurs via a LonTalk
communication link, which is based on the LonTalk
The controller is designed to be field-installed and is sent from the factory
configured for a 2-heat/2-cool application. You can change this configuration using the DIP switches located on the circuit board. The Tracer
ZN517 supports the following three configurations:
®
protocol.
•2-heat/2-cool with optional economizer control
•4-cool with optional economizer control
•Heat pump with optional economizer control
Features such as discharge air tempering and demand control ventilation
can be configured using the Rover service tool.
Note:
For information about using the Rover service tool, see the
Rover Operation and Programming guide (EMTX-SVX01BEN).
Dimensions
Plastic-cover model dimensions
For complete dimensional drawing, see Figure 1 on page 3.
•Height: 5.375 in. (137 mm)
•Width: 6.875 in. (175 mm)
•Depth: 2 in. (51 mm)
CNT-SVX12C-EN1
Page 14
Chapter 1 Overview and specifications
Metal-cover model dimensions
For complete dimensional drawing, see Figure 2 on page 3.
•Height: 9.0 in (25 mm)
•Width: 10.37in. (263 mm)
•Depth: 2.25 in. (58 mm)
Clearances
For wiring, ventilation, and maintenance, provide the following minimum
clearances for the module:
Plastic-cover model
(see Figure 1 on page 3)
•Front: 4.0 in. (102 mm)
•Each side: 1.0 in. (25 mm)
•Top and bottom: 4.0 in. (102 mm)
Metal-cover model
(see Figure 2 on page 3)
•Front: 24.0 in. (610 mm)
•Each side: 2.0 in. (51 mm)
•Top and bottom: 1.0 in. (25 mm)
Power
The transformer must meet the following minimum requirements for the
controller and its output devices:
•19–30 Vac (24 Vac nominal)
•50/60 Hz
•9 VA and 12 VA maximum per binary output utilized
Operating environment
Operate a Tracer ZN517 unitary controller in an indoor environment that
meets the following requirements:
•Temperature: From –40°F to 160°F (–40°C to 70°C)
•Relative humidity: From 5–90%, noncondensing
2CNT-SVX12C-EN
Page 15
Figure 1. Plastic-cover model dimensions and clearances
1 in.
(25 mm)
Operating environment
4 in
(102 mm)
5.625 in
(143 mm)
5.375 in (137 mm)
Clearances
Dimensions
6.31 in.
(160 mm)
Figure 2. Metal-cover model dimensions and clearances
1 in.
(25 mm)
4 in
(102 mm)
1. 875 in.
(48 mm)
4 in
(102 mm)
6.5 in.
(165 mm)
6.875 in
(175 mm)
2 in. (51 mm)
9 in.
(229 mm)
2 in.
(51 mm)
24 in.
(610 mm)
Clearances
Dimensions
CNT-SVX12C-EN3
10.37 in.
(263 mm)
width with cover
1 in.
(25 mm)
2 in.
(51 mm)
1 in.
(25 mm)
2.25 in.
(58 mm)
7 in.
(178 mm)
0.28 in.
(7 mm)
9 in.
(229 mm)
10. 25 in .
(260 mm)
width without cover
Page 16
Chapter 1 Overview and specifications
Storage environment
If you are storing a Tracer ZN517 unitary controller for a substantial
amount of time, store it in an indoor environment that meets the
following requirements:
•Temperature: From –40° to 185°F (–40° to 85°C)
•Relative humidity: From 5–95%, noncondensing
Agency listing/compliance
CE—Immunity: EN50082-2:1995
CE—Emissions: EN61000-3-2:1995
UL and C-UL 916 listed:
Energy management equipment
UL 94-5V (UL flammability rating for plenum use)
EN61000-6-2:1999
EN61000-3-3:1995
EN50081-1:1992 (CISPR 22)
EN55011:1998, Class B
FCC Part 15, Class A, CFR 47
Factory default temperature setpoints
The Tracer ZN517 unitary controller relies on a number of temperature
setpoints to control HVAC equipment. Table 1 gives the factory defaults
for these setpoints, which can all be edited with the Rover service tool or a
BAS.
Table 1. Factory default temperature setpoints
Setpoints
Default setpoints
Occupied cooling74.0°F (23.3°C)
Occupied standby cooling78.0°F (25.6°C)
Unoccupied cooling85.0°F (29.4°C)
Occupied heating71.0°F (21.7°C)
Occupied standby heating67.0°F (19.4°C)
Unoccupied heating60.0°F (15.6°C)
Occupied setpoint limits
Cooling setpoint high limit110.0°F (43.3°C)
Cooling setpoint low limit40.0°F (44.4°C)
Factory defaults
°F (°C)
4CNT-SVX12C-EN
Page 17
Factory default temperature setpoints
Table 1. Factory default temperature setpoints
Setpoints
Heating setpoint high limit105.0°F (40.6°C)
Heating setpoint low limit40.0°F (44.4°C)
Discharge air limits
High limit170.6°F (77.0°C)
Low limit37.4°F (3.0°C)
Control point high limit150.8°F (66.0°C)
Control point low limit44.6°F (7.0°C)
Outdoor air damper setup
Economizer enable temperature53.6°F (12.0°C)
Factory defaults
°F (°C)
CNT-SVX12C-EN5
Page 18
Chapter 1 Overview and specifications
Additional components
The following components are required for proper equipment operation.
They are not included with the Tracer ZN517 unitary controller. Additional components may also be required besides those described in this
section, depending on your application.
Power transformer
A transformer providing 24 Vac is required to power the Tracer ZN517
unitary controller and associated output relays and valve and damper
actuators (see “AC power wiring” on page 85).
Zone temperature sensors
Table 2 shows some of the Trane zone temperature sensors that are supported by the Tracer ZN517 unitary controller. Contact your Trane sales
office for information about other compatible zone sensors.
Table 2. Trane zone temperature sensor options
Zone
BAS order
number
4190 1086xxx
4190 1087x
4190 1088xxxx
4190 1089xx
4190 1090xxxxx
4190 1094xxx
4190 7015
(stainless
steel wall
plate)
Setpoint
thumbwheel
Temperature
sensor
x
Timed override
buttons
Comm
jack
OnCancel
Discharge air temperature sensors
Discharge air temperature sensors must be Trane 10 kΩ (at 25°C) thermistors. The discharge air temperature (DAT) input may use a sealed
temperature sensor (part number 4190 1100) or a duct/immersion temperature sensor (part number 4190 1103).
Damper actuators (optional)
Actuators cannot exceed 12 VA draw at 24 Vac. Use actuators with on/off
action and spring return (to normally open or closed position), based on
the desired default position.
6CNT-SVX12C-EN
Page 19
Chapter 2
Mounting the controller
This chapter gives recommendations and requirements for mounting the
Tracer ZN517 unitary controller.
Location recommendations
For rooftop and heat pump applications, the controller can be mounted
inside the unit or at a convenient location inside the building. Trane
recommends locating the Tracer ZN517 unitary controller:
•Near the controlled piece of equipment to reduce wiring costs
•Where it is easily accessible for service personnel
•Where public access is restricted to minimize the possibility of tam-
pering or vandalism
CNT-SVX12C-EN7
Page 20
Chapter 2 Mounting the controller
Mounting recommendations
Mounting recommendations are as follows:
IMPORTANT
Mount the Tracer ZN517 unitary controller with the cover on to avoid
the possibility of damaging the circuit board during installation.
•Mount the controller in any direction, other than with the front of the
cover facing downward.
•Mount using the two
(see Figure 3). Mounting fasteners are not included.
•Attach the controller securely so it can withstand vibrations of associ-
ated HVAC equipment.
•When the controller is mounted in a small enclosed compartment,
complete all wiring connections before securing the controller in the
compartment.
Figure 3. Mounting the Tracer ZN517 unitary controller
3
/16in. (4.8 mm) radius mounting holes provided
8CNT-SVX12C-EN
Page 21
Chapter 3
Applications for the
2-heat/2-cool configuration
This chapter provides information for wiring input and output terminals
and setting DIP switches for typical 2-heat/2-cool applications. The function of inputs and outputs is also defined for these applications.
The types of 2-heat/2-cool applications supported by the Tracer ZN517
unitary controller are:
•Rooftop units with or without economizers
•Split systems with or without economizers
CNT-SVX12C-EN9
Page 22
Chapter 3 Applications for the 2-heat/2-cool configuration
Wiring requirements and options
Table 3 shows required controller inputs for minimal proper operation of
all 2-heat/2-cool applications.
Table 3. Required controller inputs for all 2-heat/2-cool applications
FunctionInput source
24 Vac powerTerminals: GND, 24 V“AC power wiring” on
Zone temperatureTerminals: ZN, GND
or communicated
For more information,
see:
page 85
“ZN: Zone temperature” on page 18
Table 4 shows optional controller inputs and outputs for specific
applications.
Table 4. Optional controller inputs and outputs for specific applications
* In order to use this function, the economizing function must be enabled.
Input: DAT“Discharge air tem-
Input:
AI1 (CO
sensor)
2
For more information,
see:
“Economizing” on
page 23
pering” on page 24
“Demand control
ventilation” on
page 24
trol” on page 20
Figure 4 on page 11 shows a wiring diagram for the Tracer ZN517 that
includes all required and all optional components for 2-heat/2-cool applications.
10CNT-SVX12C-EN
Page 23
ZONE SENSOR
ANALOG INPUTS
HVAC UNIT
BINARY INPUTS
BINARY OUTPUT
AC OUT
AC POWER
24 Vac
Wiring requirements and options
Figure 4. Wiring diagram for 2-heat/2-cool applications
Powe r*
Tr i- s t at e
modulating
economizer
(optional)
Common
H
N
24V
GND
24V
OPN
ECONOMIZERAC OUT
24V
GND
AC POWER
GND
CLS
R
RhRc1G4325NO 5COM
Fan
G
Y1
HVAC UNIT
Compressor 1 contactor
Compressor 2 contactor
Heat stage 1
Heat stage 2
Y2
W1 W2
Generic binary output (optional)
BINARY OUTPUT
STATUS5NC
LED
SERVICE
LED
PIN
LonTalk
In
Out
*Terminals Rc and Rh are provided as
inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh
for heat and Rc for cooling. If combined, use only Rc (see “HVAC unit
electrical circuit wiring” on page 82).
COMM5
A BBA
Occupancy
or generic
(optional)
BINARY INPUTS
-BI2-SET-BI1-ZN
ANALOG INPUTS
AI1-DAT-
+20GND
GND
+
Typical 3-wire
sensor
(optional)
(optional)
Fan status
(default:
normally closed
Dry contacts
only
closed = no flow
open = flow)
or generic
_
-AI2-
Discharge air
temperature
Outdoor air
temperature
(optional)
ZONE SENSOR
GND
COMM5
LED
LonTalk
1
2
3
4
5
On
Cancel
CNT-SVX12C-EN11
Page 24
Chapter 3 Applications for the 2-heat/2-cool configuration
DIP switch settings
Set the DIP switches on the circuit board for the 2-heat/2-cool configuration. The correct settings are shown in Figure 5.
Figure 5. DIP switch settings for the 2-heat/2-cool configuration
ON DIP
1234
ON DIP
1234
ON DIP
1234
2-heat/2-cool
without economizer
2-heat/2-cool with
economizer
12CNT-SVX12C-EN
Page 25
Binary outputs for 2-heat/2-cool applications
Binary outputs for 2-heat/2-cool
applications
This configuration supports rooftop units and split systems applications
that have the following components:
•Economizer
•Supply fan
•Cool 1
•Cool 2
•Heat 1
•Heat 2
•Exhaust
The Tracer ZN517 controller has eight binary outputs. Each binary output is a relay with a rating of 12 VA. Table 5 describes the function of
each output for 2-heat/2-cool applications.
Table 5. Binary outputs for 2-heat/2-cool applications
Use the Rover service tool to configure binary output 5 (5NO/5COM/5NC)
in one of the following ways. It is the only output that can be configured
as a generic binary output.
•Not used.
•Exhaust fan: Will energize when the economizer outside air damper
position is greater than the user-defined control point.
•Occupancy: Will energize when the Tracer ZN517 is in the occupied
mode.
•Generic: Can be monitored only by a BAS and has no direct effect on
Tracer ZN517 operation.
CNT-SVX12C-EN13
Page 26
Chapter 3 Applications for the 2-heat/2-cool configuration
Overriding binary outputs
Use the manual output test to manually control the outputs in a defined
sequence. For more information about the manual output test, see “Manual output test” on page 74.
Binary inputs for 2-heat/2-cool
applications
The Tracer ZN517 unitary controller has two binary inputs. Each binary
input associates an input signal of 0 Vac with open contacts and 24 Vac
with closed contacts. Table 6 gives the function of each binary input for
2 heat/2 cool applications. Each function is explained in the succeeding
paragraphs. For an explanation of the diagnostics generated by each
binary input, see “Table of diagnostics” on page 79. For more information
about how the controller operates, see Chapter 4, “Sequence of operations
for the 2-heat/2-cool configuration”.”
Table 6. Binary inputs for 2-heat/2-cool applications
Binary input
terminal label
BI1Occupancy or generic
BI2Fan status
Function
BI1: Occupancy or generic
The function of the occupancy input is to save energy by increasing the
range of zone setpoints when the zone is unoccupied. BI1 is used for two
occupancy-related functions. For stand-alone controllers, this binary
input can be hard-wired to a binary switch, clock, or occupancy sensor to
determine the occupancy mode—either occupied or unoccupied. For controllers receiving a BAS-communicated occupancy request, the function of
BI1 is to change the mode from occupied to occupied standby. (For more
information on occupancy-related functions, see “Occupancy modes” on
page 20.) An occupancy sensor with a binary output may be used.
BI1 is the only input that can be configured as a generic binary input.
When configured as a generic binary input, it can be monitored only by a
BAS, and has no direct effect on Tracer ZN517 operation.
BI2: Fan status
The fan status input provides feedback to the controller regarding the
fan’s operating status. If BI2 is wired to a fan status switch and the input
indicates that the fan is not operating when the controller has the fan
controlled to on, the controller will generate a Local Fan Switch Failure
diagnostic. (For more information, see “Fan status” on page 25.)
14CNT-SVX12C-EN
Page 27
Analog inputs for 2-heat/2-cool applications
Analog inputs for 2-heat/2-cool
applications
The Tracer ZN517 controller has five analog inputs. Table 7 describes the
function of each input for 2-heat/2-cool applications. Each function is
explained in the succeeding paragraphs. For an explanation of the diagnostics generated by each analog input, see “Table of diagnostics” on
page 79. For more information about how the controller operates, see
Chapter 4, “Sequence of operations for the 2-heat/2-cool configuration”.
Table 7. Analog inputs for 2-heat/2-cool applications
Analog input
terminal label
AI1Universal analog input
AI2Outdoor air temperature
DATDischarge air temperature
ZNZone temperature (required)
SETTemperature setpoint
Note:
Use a GND terminal as the common ground for all zone sensor
analog inputs. See Figure 4 on page 11.
Function
AI1: Universal 4–20 mA
The AI1 analog input can be configured in one of the three ways shown in
Table 8.
Table 8. AI1 configuration options and associated measurement ranges
ConfigurationMeasurement range
Generic 4–20 mA input0–100%
(4 mA=0%; 20 mA=100%)
CO2 measurement0–2000 ppm
(4 mA=0 ppm; 20 mA=2000 ppm)
Relative humidity (RH) measurement0–100%
(4 mA=0% RH; 20 mA=100% RH)
CNT-SVX12C-EN15
If this input is not needed for an application, configure it as Not Used.
This disables the generation of diagnostics.
Note:
AI1 is polarity sensitive.
For the generic input configuration, a 4–20 mA sensor must be hardwired to the AI1 terminal. (Wiring is dependent on the specific applica-
Page 28
Chapter 3 Applications for the 2-heat/2-cool configuration
tion.) The sensor communicates a value of 0–100% to the BAS. This configuration has no direct effect on Tracer ZN517 operation.
For the CO
measurement configuration, a 4–20 mA sensor must be hard-
2
wired to the AI1 terminal as shown in Figure 6. The sensor will transmit
a 0–2000 ppm value to the BAS. This configuration has no direct effect on
Tracer ZN517 operation. If a valid value is established and then is no
longer present, the controller generates a CO
Sensor Failure diagnostic.
2
Figure 6. AI1 terminal wiring: CO
Tracer ZN517
CO
sensor
2
(Trane part number:
4190 4100 or 4190 4101)
measurement
2
24 Vac
{{
24 Vac
GND
+20GND
Out
AI1
For the RH measurement configuration, a hard-wired 4–20 mA zone
humidity sensor (see Figure 7) must provide a value to the controller. If a
valid hard-wired or communicated relative humidity value is established
and then is no longer present, the controller generates an RH Sensor Failure diagnostic and disables the dehumidification function. The RH sensor
is used only to provide a valid humidity reading to a BAS; it does not
affect the operation of the Tracer ZN517.
Figure 7. AI1 terminal wiring: RH measurement
Figure Note:
The +20 terminal provides 20 ±2 Vdc that is used to power a Trane RH sensor (part
numbers 4190 1109, 4190 7011, 4190 7012, 4190 7014).
16CNT-SVX12C-EN
+20GND
+
AI1
–
Tracer ZN517
RH sensor
Page 29
Analog inputs for 2-heat/2-cool applications
AI2: Outdoor air temperature or generic temperature
The AI2 analog input can functions as either:
•An outdoor air temperature input
•A generic temperature input
If AI2 is configured as the local (hard-wired) outdoor air temperature
input, the controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input AI2. An outdoor air temperature value communicated by means of a LonTalk link can also be used for
controllers operating on a BAS. If both hard-wired and communicated
outdoor air temperature values are present, the controller uses the communicated value.
If you set DIP switch 3 to
on page 12), you automatically configure AI2 as an outdoor air temperature input. Economizing (free cooling) is a function whereby outdoor air is
used as a source of cooling before hydronic or DX cooling is used. The
Tracer ZN517 uses the outdoor air temperature value to determine
whether economizing is feasible. Economizing is not possible without a
valid outdoor air temperature. (For more information, see “Economizing”
on page 23.)
ON for economizing (see “DIP switch settings”
If AI2 is configured as a generic temperature input, it can be monitored
by a BAS. The controller receives the temperature as a resistance signal
from a 10 kΩ thermistor wired to analog input AI2. The generic temperature input can be used with any Trane 10 kΩ thermistor. The thermistor
can be placed in any location and has no effect on the operation of the controller. If you set DIP switch 3 to
page 12), you automatically configure AI2 as a generic temperature input.
Note:
AI2 is not polarity sensitive; you can connect either terminal to
either sensor lead.
OFF (see “DIP switch settings” on
DAT: Discharge air temperature
The DAT analog input functions as the local discharge air temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input DAT. The thermistor is typically
located downstream from all unit heating and cooling coils at the unit discharge area.
Trane recommends the use of a discharge air temperature sensor to utilize the cascade control function (see “Cascade zone control” on page 20).
Cascade control is a more accurate method of temperature control. If no
discharge air temperature sensor is used, the controller will default to
control based solely on the zone temperature (see “Simplified zone control” on page 20).
CNT-SVX12C-EN17
Note:
DAT is not polarity sensitive; you can connect either terminal
to either sensor lead.
Page 30
Chapter 3 Applications for the 2-heat/2-cool configuration
ZN: Zone temperature
The ZN analog input functions as the local (hard-wired) zone temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor in a standard Trane zone sensor wired to analog input
ZN. A communicated zone temperature value via the LonTalk communications link can also be used for controllers operating on a BAS. When
both a hard-wired and communicated zone temperature value is present,
the controller uses the communicated value. If neither a hard-wired nor a
communicated zone temperature value is present, the controller generates a Space Temperature Failure diagnostic.
The ZN analog input is also used to communicate timed override requests
and cancel requests to the controller for applications utilizing a Trane
zone sensor with the ON and CANCEL button option.
SET: Temperature setpoint
The SET analog input functions as the local (hard-wired) temperature
setpoint input for applications utilizing a Trane zone sensor with a temperature setpoint thumbwheel. Use the Rover service tool or a BAS to
enable or disable the local setpoint input. A communicated setpoint value
via the LonTalk communications link can also be used for controllers
operating on a BAS. If both a hard-wired and a communicated setpoint
value are present, the controller uses the communicated value. If neither
a hard-wired nor a communicated setpoint value is present, the controller
uses the stored default setpoints (configurable using the Rover service
tool or a BAS). If a valid hard-wired or communicated setpoint value is
established and then is no longer present, the controller generates a Local
Space Setpoint Failure diagnostic.
18CNT-SVX12C-EN
Page 31
Chapter 4
Sequence of operations for the
2-heat/2-cool configuration
A Tracer ZN517 unitary controller configured to control a 2-heat/2-cool
unit will operate to maintain the zone temperature setpoint. This chapter
discusses many of the operational sequences the controller uses to accomplish this goal.
Power-up sequence
When 24 Vac power is initially applied to the Tracer ZN517 unitary controller, the following sequence occurs:
1. The Status (green) LED goes on.
2. All outputs are controlled off.
3. The controller reads all input local values to determine initial values.
4. The power-up control wait function begins automatically if the configured power-up control wait time is greater than zero. When this function is enabled, the controller waits for the configured amount of time
(from 10 to 120 seconds) to allow a communicated occupancy request
to arrive. If a communicated occupancy request arrives, normal operation can begin. If a communicated occupancy request does not arrive,
the controller assumes stand-alone operation.
5. The Status LED goes off.
6. The wait timer expires.
7. The Status LED goes on.
8. If a hard-wired zone-temperature value is not detected, the controller
begins to wait for a communicated value. (This can take several minutes [15-minute default] and occurs concurrently with the remainder
of the power-up sequence.) If a communicated zone-temperature
value arrives, normal operation can begin when the power-up
sequence has concluded. If a communicated zone-temperature value
does not arrive, the binary outputs remain off and a Space Temperature Failure diagnostic is generated (normal operation cannot begin
without a valid zone temperature value).
9. Normal operation begins assuming no diagnostics have been generated.
CNT-SVX12C-EN19
Page 32
Chapter 4 Sequence of operations for the 2-heat/2-cool configuration
Cascade zone control
Cascade zone control maintains zone temperature by controlling the discharge air temperature to control the zone temperature. The controller
uses the difference between the measured zone temperature and the
active zone temperature setpoint to produce a discharge air temperature
setpoint. The controller compares the discharge air temperature setpoint
with the discharge air temperature and calculates a unit heating/cooling
capacity accordingly (see Figure 8). The end devices (outdoor air damper,
valves, etc.) operate in sequence based on the unit heating/cooling capacity (0–100%).
Figure 8. Cascade zone control
Active zone
temperature
setpoint
Diffe rence
Measured
zone
temperature
Calculated
discharge air
temperature
setpoint
Difference
Measured
discharge air
temperature
Calculated unit
heating/cooling
capacity
If the discharge air temperature falls below the Discharge Air Control
Point Low Limit (configurable using the Rover service tool) and cooling
capacity is at a minimum, available heating capacity will be used to raise
the discharge air temperature to the low limit (see “Discharge air tempering” on page 24).
Simplified zone control
In the absence of a discharge air temperature sensor, the controller uses
simplified zone control to maintain the zone temperature. In the unoccupied mode, the controller maintains the zone temperature by calculating
the required heating or cooling capacity (0–100%) according to the measured zone temperature and the active zone temperature setpoint. The
active zone temperature setpoint is determined by the current operating
modes, which include occupancy and heat/cool modes.
Occupancy modes
Occupancy modes can be controlled by any of the following:
•The state of the local (hard-wired) occupancy binary input BI1 (see
•A timed override request from a Trane zone sensor (see “Timed over-
20CNT-SVX12C-EN
“BI1: Occupancy or generic” on page 50)
ride control” on page 22)
Page 33
Occupancy modes
•A communicated signal from a peer device (see “Peer-to-peer commu-
nication” on page 23)
•A communicated signal from a BAS
A communicated request, either from a BAS or a peer controller, takes
precedence over local requests. If a communicated occupancy request has
been established and is no longer present, the controller reverts to the
default (occupied) occupancy mode after 15 minutes (if no hard-wired
occupancy request exists). The Tracer ZN517 has the following occupancy
mode options:
•Occupied
•Unoccupied
•Occupied standby
•Occupied bypass
Occupied mode
In occupied mode, the controller maintains the zone temperature based
on the occupied heating or cooling setpoints. The controller uses the occupied mode as a default when other modes of occupancy request are not
present. The fan runs as configured (continuous or cycling). The outdoor
air damper closes when the fan is off. The temperature setpoints can be
local (hard-wired), communicated, or stored default values (configurable
using the Rover service tool or a BAS).
Unoccupied mode
In unoccupied mode, the controller attempts to maintain the zone temperature based on the unoccupied heating or cooling setpoint. The fan cycles
between high speed and off. The outdoor air damper remains closed. The
controller always uses the stored default setpoint values (configurable
using the Rover service tool or a BAS), regardless of the presence of a
hard-wired or communicated setpoint value.
Occupied standby mode
The controller is placed in occupied standby mode only when a communicated occupied request is combined with an unoccupied request from
occupancy binary input BI1. In occupied standby mode, the controller
maintains the zone temperature based on the occupied standby heating
or cooling setpoints. Because the occupied standby setpoints are typically
spread 2°F (1.1°C) in either direction and the outdoor air damper is
closed, this mode reduces the demand for heating and cooling the space.
The fan runs as configured (continuous or cycling) for occupied mode. The
controller always uses the stored default setpoint values (configurable
using the Rover service tool or a BAS), regardless of hard-wired or communicated setpoint values.
CNT-SVX12C-EN21
Page 34
Chapter 4 Sequence of operations for the 2-heat/2-cool configuration
Occupied bypass mode
The controller is placed in occupied bypass mode when the controller is
operating in the unoccupied mode and either the timed override ON button on the Trane zone sensor is pressed or the controller receives a communicated occupied bypass signal from a BAS. In occupied bypass mode,
the controller maintains the zone temperature based on the occupied
heating or cooling setpoints. The fan runs as configured (continuous or
cycling). The outdoor air damper closes when the fan is off. The controller
will remain in occupied bypass mode until either the CANCEL button is
pressed on the Trane zone sensor or the occupied bypass time (configurable using the Rover service tool or a BAS) expires. The temperature
setpoints can be local (hard-wired), communicated, or stored default values (configurable using the Rover service tool or a BAS).
Timed override control
If the zone sensor has a timed override option (ON/CANCEL buttons),
pushing the ON button momentarily shorts the zone temperature signal
to the controller. This short is interpreted as a timed override on request.
A timed override on request changes the occupancy mode from unoccupied mode to occupied bypass mode. In occupied bypass mode, the controller controls the zone temperature based on the occupied heating or
cooling setpoints. The occupied bypass time, which resides in the Tracer
ZN517 and defines the duration of the override, is configurable (using the
Rover service tool or a BAS) from 0 to 240 minutes (default value is
120 minutes). When the occupied bypass time expires, the unit changes
from occupied bypass mode to unoccupied mode. Pushing the CANCEL
button momentarily sends a fixed resistance of 1.5 kΩ to the ZN analog
input of the controller, which is interpreted as a timed override cancel
request. A timed override cancel request will end the timed override
before the occupied bypass time has expired and will transition the unit
from occupied bypass mode to unoccupied mode.
If the controller is in any mode other than unoccupied when the ON button is pressed, the controller still starts the occupied bypass timer without changing the mode to occupied bypass. If the controller is placed in
unoccupied mode before the occupied bypass timer expires, the controller
will be placed in occupied bypass mode and remain in that mode until
either the CANCEL button is pressed on the Trane zone sensor or the
occupied bypass time expires.
Outdoor air damper operation
The Tracer ZN517 does not support a two-position outdoor air damper
actuator. However, a modulating, triac, 3-wire floating point actuator
with spring return can be used for two-position control. Two-position control can function only when an outdoor air temperature (either hardwired or communicated) does not exist, and by setting the damper minimum position (using the Rover service tool) to the desired value. To con-
22CNT-SVX12C-EN
Page 35
Fan operation
trol an air damper actuator for two-position control, configure the Tracer
ZN517 for economizing (economizing will not function).
Fan operation
The Tracer ZN517 can be configured to run continuously at a single speed
or to cycle on and off automatically. If configured for continuous operation, the fan runs continuously during the occupied, occupied standby,
and occupied bypass modes. If configured for cycling operation, the fan
will cycle if the temperature is away from setpoint during the occupied,
occupied standby, and occupied bypass modes. During the unoccupied
mode, the fan cycles regardless of the fan configuration.
Peer-to-peer communication
Tracer ZN517 unitary controllers have the ability to share data with
other LonTalk-based controllers. Multiple controllers can be bound as
peers, using the Rover service tool, to share:
•Setpoint
•Zone temperature
•Heating/cooling mode
•Fan status
•Unit capacity control
Shared data is communicated from one controller to any other controller
that is bound to it as a peer. Applications having more than one unit serving a single zone can benefit by using this feature; it allows multiple units
to share a single zone temperature sensor and prevents multiple units
from simultaneously heating and cooling.
Economizing
Economizing (also referred to as “free cooling”) uses outside air for cooling. The Tracer ZN517 provides two triac (3-wire floating point) outputs
to control the damper actuator. One output opens the actuator; the other
closes it. The controller also provides analog inputs for both a discharge
air temperature sensor and an outside air temperature sensor. While
economizing is enabled, the controller uses a discharge air temperature
(DAT) control loop to maintain proper temperature control. The controller
opens the outside air damper, turns on the fan, and attempts to maintain
a user-defined discharge air temperature. If the outside air is unsuitable
for economizer operation, the outside air damper will close and normal
operation (DX cooling) will be activated. Economizing plus DX cooling is
initiated only when economizing alone cannot meet the zone’s cooling
requirements.
To enable this function, set DIP switch 3 to
on page 12).
ON (see “DIP switch settings”
CNT-SVX12C-EN23
Page 36
Chapter 4 Sequence of operations for the 2-heat/2-cool configuration
Discharge air tempering
Discharge air tempering (also called supply air tempering) prevents occupant discomfort caused by cold outside air being brought into a space
through the outside air damper. This is an important feature in cold climates because the outside air damper is never fully closed for ventilation
purposes. Discharge air tempering starts when:
•The controller is in heating mode.
•The space is otherwise satisfied (no heating or cooling required).
•Ventilation air is passing through the unit
•The discharge air temperature falls 10°F (5.6°C) below the occupied
heating setpoint.
Tempering stops when the occupied heating setpoint is exceeded. To
enable this function, use the Rover service tool to select Supply Air Tempering Enabled.
Demand control ventilation
The Tracer ZN517 unitary controller modulates the outside air damper
position in direct response to the CO
door air allowed to enter. This function is referred to as demand control
ventilation. Demand control ventilation requires that the two triac (3wire floating point) outputs be used to control the damper actuator. The
minimum damper position will increase as CO
500 ppm. The function executes with a 3-minute loop frequency to allow
time for the sensor to respond.
To enable this function, use the Rover service tool to configure the Tracer
ZN517 as follows:
level, regulating the amount of out-
2
levels rise above
2
•Configure AI1 as a carbon dioxide sensor
•Enter a minimum CO
(factory default: 500 ppm).
•Enter a maximum CO
(factory default: 1500 ppm).
When the CO
100% open.
level reaches the threshold, the minimum position is
2
level (Control Point)
2
threshold (Threshold)
2
Unit protection strategies
The following strategies are initiated when specific conditions exist in
order to protect the unit or building from damage:
•Filter maintenance timer
•Fan off delay
•Fan status
24CNT-SVX12C-EN
Page 37
Unit protection strategies
Filter-maintenance timer
The filter-maintenance timer tracks the amount of time (in hours) that
the fan is enabled. The Maintenance Required Timer Setpoint (Maint Req
Time Setpoint), configured with the Rover service tool, is used to set the
amount of time until maintenance (typically, a filter change) is needed. If
the setpoint is configured to zero, the filter-maintenance timer is disabled.
The controller compares the fan-run time to Maintenance Required Timer
Setpoint. Once the setpoint is reached, the controller generates a Maintenance Required diagnostic. When the diagnostic is cleared, the controller
resets the filter-maintenance timer to zero, and the timer begins accumulating fan-run time again.
Fan off delay
The fan stays on for an additional 30 seconds (adjustable with the Rover
service tool) to allow the residual cooling or heating energy to be circulated through the system.
Fan status
The controller monitors fan status to protect equipment from overheating. If fan or airflow is not detected for 30 seconds when needed, the
equipment shuts down.
CNT-SVX12C-EN25
Page 38
Chapter 4 Sequence of operations for the 2-heat/2-cool configuration
26CNT-SVX12C-EN
Page 39
Chapter 5
Applications for the 4-cool
configuration
This chapter provides information for wiring input and output terminals
and setting DIP switches for typical 4-cool applications. The function of
inputs and outputs is also defined for these applications.
The types of 4-cool applications supported by the Tracer ZN517 unitary
controller are rooftop units with or without economizers.
CNT-SVX12C-EN27
Page 40
Chapter 5 Applications for the 4-cool configuration
Wiring requirements and options
Table 9 shows required controller inputs for minimal proper operation of
all 4-cool applications.
Table 9. Required controller inputs for all 4-cool applications
FunctionInput source
24 Vac powerTerminals: GND, 24 V“AC power wiring” on
Zone temperatureTerminals: ZN, GND
or communicated
For more information,
see:
page 85
“ZN: Zone temperature” on page 36
Table 10 shows optional controller inputs and outputs for specific
applications.
Table 10. Optional controller inputs and outputs for specific
applications
* In order to use this function, the economizing function must be enabled.
Input: DAT“Discharge air tem-
Input:
AI1 (CO
sensor)
2
For more information,
see:
“Economizing” on
page 23
pering” on page 24
“Demand control
ventilation” on
page 24
trol” on page 20
Figure 9 on page 29 show typical applications that include all required
and all optional components for 4-cool applications.
28CNT-SVX12C-EN
Page 41
ZONE SENSOR
ANALOG INPUTS
HVAC UNIT
BINARY INPUTS
BINARY OUTPUT
AC OUT
AC POWER
24 Vac
Wiring requirements and options
Figure 9. Wiring diagram for 4-cool applications
Powe r*
Tr i- s t at e
modulating
economizer
(optional)
Common
H
N
24V
GND
24V
OPN
ECONOMIZERAC OUT
24V
GND
AC POWER
GND
CLS
R
RhRc1G4325NO 5COM
Fan
Y1
G
HVAC UNIT
Compressor 1 contactor
Compressor 2 contactor
Compressor 3 contactor
Compressor 4 contactor
Y4
Y3
Y2
Generic binary output (optional)
BINARY OUTPUT
STATUS5NC
LED
SERVICE
LED
PIN
LonTalk
In
Out
*Terminals Rc and Rh are provided as
inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh
for heat and Rc for cooling. If combined, use only Rc (see “HVAC unit
electrical circuit wiring” on page 82).
COMM5
Occupancy
or generic
(optional)
BINARY INPUTS
A BBA
ANALOG INPUTS
AI1-DAT-
GND
+20GND
_
+
-BI2-SET-BI1-ZN
Typical 3-wire
sensor
(optional)
Fan status or
generic
(optional)
Dry contacts
only
-AI2-
ZONE SENSOR
Discharge air
temperature
Outdoor air
temperature
(optional)
GND
COMM5
LED
LonTalk
1
2
3
4
5
On
Cancel
CNT-SVX12C-EN29
Page 42
Chapter 5 Applications for the 4-cool configuration
DIP switch settings
Set the DIP switches on the circuit board for the 4-cool configuration. The
correct settings are shown in Figure 10.
Figure 10. DIP switch settings for the 4-cool configuration
ON DIP
1234
ON DIP
1234
ON DIP
1234
4-cool without
economizer
4-cool with
economizer
30CNT-SVX12C-EN
Page 43
Binary outputs for 4-cool applications
Binary outputs for 4-cool applications
This configuration supports rooftop unit applications that have the following components:
•Economizer
•Supply fan
•Cool 1
•Cool 2
•Cool 3
•Cool 4
•Exhaust fan
The Tracer ZN517 controller has seven binary outputs. Each binary output is a relay with a rating of 12 VA. Table 11 describes the function of
each output for 4-cool applications.
Use the Rover service tool to configure binary output 5 (5NO/5COM/5NC)
in one of the following ways. It is the only output that can be configured
as a generic binary output.
•Not used.
•Exhaust fan: Will energize when the economizer outside air damper
position is greater than the user-defined control point.
•Occupancy: Will energize when the Tracer ZN517 is in the occupied
mode.
•Generic: Can be monitored only by a BAS and has no direct effect on
Tracer ZN517 operation.
Overriding binary outputs
Use the manual output test to manually control the outputs in a defined
sequence. For more information about the manual output test, see “Manual output test” on page 74.
CNT-SVX12C-EN31
Page 44
Chapter 5 Applications for the 4-cool configuration
Binary inputs for 4-cool applications
The Tracer ZN517 unitary controller has two binary inputs. Each binary
input associates an input signal of 0 Vac with open contacts and 24 Vac
with closed contacts. Table 12 gives the function of each binary input for
4-cool applications. Each function is explained in the succeeding paragraphs. For an explanation of the diagnostics generated by each binary
input, see “Table of diagnostics” on page 79. For more information about
how the controller operates, see Chapter 6, “Sequence of operations for
the 4-cool configuration”.”
Table 12. Binary inputs for 4-cool applications
Binary input
terminal label
BI1Occupancy or generic
BI2Fan status
Function
BI1: Occupancy or generic
The function of the occupancy input is to save energy by increasing the
range of zone setpoints when the zone is unoccupied. BI1 is used for two
occupancy-related functions. For stand-alone controllers, this binary
input can be hard-wired to a binary switch, clock, or occupancy sensor to
determine the occupancy mode—either occupied or unoccupied. For controllers receiving a BAS-communicated occupancy request, the function of
BI1 is to change the mode from occupied to occupied standby. (For more
information on occupancy-related functions, see “Occupancy modes” on
page 38.)
BI1 is the only input that can be configured as a generic binary input.
When configured as a generic binary input, it can be monitored only by a
BAS, and has no direct effect on Tracer ZN517 operation.
BI2: Fan status
The fan status input provides feedback to the controller regarding the
fan’s operating status. If BI2 is wired to a fan status switch and the input
indicates that the fan is not operating when the controller has the fan
controlled to on, the controller will generate a Local Fan Switch Failure
diagnostic. (For more information, see “Fan status” on page 43.)
32CNT-SVX12C-EN
Page 45
Analog inputs for 4-cool applications
Analog inputs for 4-cool applications
The Tracer ZN517 controller has five analog inputs. Table 13 describes
the function of each input for 4-cool applications. Each function is
explained in the succeeding paragraphs. For an explanation of the diagnostics generated by each analog input, see “Table of diagnostics” on
page 79. For more information about how the controller operates, see
Chapter 6, “Sequence of operations for the 4-cool configuration”.
Table 13. Analog inputs for 4-cool applications
Analog input
terminal label
AI1Universal analog input
AI2Outdoor air temperature
DATDischarge air temperature
ZNZone temperature (required)
SETTemperature setpoint
Function
Note:
Use a GND terminal as the common ground for all zone sensor
analog inputs. See Figure 9 on page 29.
AI1: Universal 4–20 mA
The AI1 analog input can be configured in one of the three ways shown in
Table 14.
Table 14. AI1 configuration options and associated measurement
ranges
ConfigurationMeasurement range
Generic 4–20 mA input0–100%
(4 mA=0%; 20 mA=100%)
CO2 measurement0–2000 ppm
(4 mA=0 ppm; 20 mA=2000 ppm)
Relative humidity (RH) measurement0–100%
(4 mA=0% RH; 20 mA=100% RH)
CNT-SVX12C-EN33
If this input is not needed for an application, configure it as Not Used.
This disables the generation of diagnostics.
Note:
AI1 is polarity sensitive.
For the generic input configuration, a 4–20 mA sensor must be hardwired to the AI1 terminal. (Wiring is dependent on the specific application.) The sensor communicates a value of 0–100% to the BAS. This configuration has no direct effect on Tracer ZN517 operation.
Page 46
Chapter 5 Applications for the 4-cool configuration
T
For the CO2 measurement configuration, a 4–20 mA sensor must be hardwired to the AI1 terminal as shown in Figure 11 on page 34. The sensor
will transmit a 0–2000 ppm value to the BAS. This configuration has no
direct effect on Tracer ZN517 operation. If a valid value is established
and then is no longer present, the controller generates a CO
ure diagnostic.
Sensor Fail-
2
Figure 11. AI1 terminal wiring: CO
Tracer ZN517
CO2 sensor
(Trane part number:
4190 4100 or 4190 4101)
For the RH measurement configuration, a hard-wired 4–20 mA zone
humidity sensor (see Figure 12) must provide a value to the controller. If
a valid hard-wired or communicated relative humidity value is established and then is no longer present, the controller generates an RH Sensor Failure diagnostic and disables the dehumidification function. The
RH sensor is used only to provide a valid humidity reading to a BAS; it
does not affect the operation of the Tracer ZN517.
measurement
2
24 Vac
{{
24 Vac
GND
+20GND
Out
AI1
34CNT-SVX12C-EN
Figure 12. AI1 terminal wiring: RH measurement
AI1
+20GND
–
+
Figure Note:
he +20 terminal provides 20 ±2 Vdc that is used to power a Trane RH sensor (part
AI2: Outdoor air temperature or generic temperature
The AI2 analog input can function as either:
•An outdoor air temperature input
•A generic temperature input
If AI2 is configured as the local (hard-wired) outdoor air temperature
input, the controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input AI2. An outdoor air temperature value communicated by means of a LonTalk link can also be used for
controllers operating on a BAS. If both hard-wired and communicated
outdoor air temperature values are present, the controller uses the communicated value.
If you set DIP switch 3 to
on page 30), you automatically configure AI2 as an outdoor air temperature input. Economizing (free cooling) is a function whereby outdoor air is
used as a source of cooling before hydronic or DX cooling is used. The
Tracer ZN517 uses the outdoor air temperature value to determine
whether economizing is feasible. Economizing is not possible without a
valid outdoor air temperature. (For more information, see “Economizing”
on page 41.)
ON for economizing (see “DIP switch settings”
If AI2 is configured as a generic temperature input, it can be monitored
by a BAS. The controller receives the temperature as a resistance signal
from a 10 kΩ thermistor wired to analog input AI2. The generic temperature input can be used with any Trane 10 kΩ thermistor. The thermistor
can be placed in any location and has no effect on the operation of the controller. If you set DIP switch 3 to
page 30), you automatically configure AI2 as a generic temperature input.
Note:
AI2 is not polarity sensitive; you can connect either terminal to
either sensor lead.
OFF (see “DIP switch settings” on
DAT: Discharge air temperature
The DAT analog input functions as the local discharge air temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input DAT. The thermistor is typically
located downstream from all unit heating and cooling coils at the unit discharge area.
Trane recommends the use of a discharge air temperature sensor to utilize the cascade control function (see “Cascade zone control” on page 38).
Cascade control is a more accurate method of temperature control. If no
discharge air temperature sensor is used, the controller will default to
control based solely on the zone temperature (see “Simplified zone control” on page 38).
CNT-SVX12C-EN35
Note:
DAT is not polarity sensitive; you can connect either terminal
to either sensor lead.
Page 48
Chapter 5 Applications for the 4-cool configuration
ZN: Zone temperature
The ZN analog input functions as the local (hard-wired) zone temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor in a standard Trane zone sensor wired to analog input
ZN. A communicated zone temperature value via the LonTalk communications link can also be used for controllers operating on a BAS. When
both a hard-wired and communicated zone temperature value is present,
the controller uses the communicated value. If neither a hard-wired nor a
communicated zone temperature value is present, the controller generates a Space Temperature Failure diagnostic.
The ZN analog input is also used to communicate timed override requests
and cancel requests to the controller for applications utilizing a Trane
zone sensor with the ON and CANCEL button option.
SET: Temperature setpoint
The SET analog input functions as the local (hard-wired) temperature
setpoint input for applications utilizing a Trane zone sensor with a temperature setpoint thumbwheel. Use the Rover service tool or a BAS to
enable or disable the local setpoint input. A communicated setpoint value
via the LonTalk communications link can also be used for controllers
operating on a BAS. If both a hard-wired and a communicated setpoint
value are present, the controller uses the communicated value. If neither
a hard-wired nor a communicated setpoint value is present, the controller
uses the stored default setpoints (configurable using the Rover service
tool or a BAS). If a valid hard-wired or communicated setpoint value is
established and then is no longer present, the controller generates a Local
Space Setpoint Failure diagnostic.
36CNT-SVX12C-EN
Page 49
Chapter 6
Sequence of operations for
the 4-cool configuration
A Tracer ZN517 unitary controller configured to control a 4-cool unit will
operate to maintain the zone temperature setpoint. This chapter discusses many of the operational sequences the controller uses to accomplish this goal.
Power-up sequence
When 24 Vac power is initially applied to the Tracer ZN517 unitary controller, the following sequence occurs:
1. The Status (green) LED goes on.
2. All outputs are controlled off.
3. The controller reads all input local values to determine initial values.
4. The power-up control wait function begins automatically if the configured power-up control wait time is greater than zero. When this function is enabled, the controller waits for the configured amount of time
(from 10 to 120 seconds) to allow a communicated occupancy request
to arrive. If a communicated occupancy request arrives, normal operation can begin. If a communicated occupancy request does not arrive,
the controller assumes stand-alone operation.
5. The Status LED goes off.
6. The wait timer expires.
7. The Status LED goes on.
8. If a hard-wired zone-temperature value is not detected, the controller
begins to wait for a communicated value. (This can take several minutes [15-minute default] and occurs concurrently with the remainder
of the power-up sequence.) If a communicated zone-temperature
value arrives, normal operation can begin when the power-up
sequence has concluded. If a communicated zone-temperature value
does not arrive, the binary outputs remain off and a Space Temperature Failure diagnostic is generated (normal operation cannot begin
without a valid zone temperature value).
9. Normal operation begins assuming no diagnostics have been generated.
CNT-SVX12C-EN37
Page 50
Chapter 6 Sequence of operations for the 4-cool configuration
Cascade zone control
Cascade zone control maintains zone temperature by controlling the discharge air temperature to control the zone temperature. The controller
uses the difference between the measured zone temperature and the
active zone temperature setpoint to produce a discharge air temperature
setpoint. The controller compares the discharge air temperature setpoint
with the discharge air temperature and calculates a unit heating/cooling
capacity accordingly (see Figure 13). The end devices (outdoor air damper,
valves, etc.) operate in sequence based on the unit heating/cooling capacity (0–100%).
Figure 13. Cascade zone control
Active zone
temperature
setpoint
Diffe rence
Measured
zone
temperature
Calculated
discharge air
temperature
setpoint
Difference
Measured
discharge air
temperature
Calculated unit
heating/cooling
capacity
If the discharge air temperature falls below the Discharge Air Control
Point Low Limit (configurable using the Rover service tool) and cooling
capacity is at a minimum, available heating capacity will be used to raise
the discharge air temperature to the low limit (see “Discharge air tempering” on page 42).
Simplified zone control
In the absence of a discharge air temperature sensor, the controller uses
simplified zone control to maintain the zone temperature. In the unoccupied mode, the controller maintains the zone temperature by calculating
the required heating or cooling capacity (0–100%) according to the measured zone temperature and the active zone temperature setpoint. The
active zone temperature setpoint is determined by the current operating
modes, which include occupancy and heat/cool modes.
Occupancy modes
Occupancy modes can be controlled by any of the following:
•The state of the local (hard-wired) occupancy binary input BI1 (see
•A timed override request from a Trane zone sensor (see “Timed over-
38CNT-SVX12C-EN
“BI1: Occupancy or generic” on page 32)
ride control” on page 40)
Page 51
Occupancy modes
•A communicated signal from a peer device (see “Peer-to-peer commu-
nication” on page 41)
•A communicated signal from a BAS
A communicated request, either from a BAS or a peer controller, takes
precedence over local requests. If a communicated occupancy request has
been established and is no longer present, the controller reverts to the
default (occupied) occupancy mode after 15 minutes (if no hard-wired
occupancy request exists). The Tracer ZN517 has the following occupancy
mode options:
•Occupied
•Unoccupied
•Occupied standby
•Occupied bypass
Occupied mode
In occupied mode, the controller maintains the zone temperature based
on the occupied heating or cooling setpoints. The controller uses the occupied mode as a default when other modes of occupancy request are not
present. The fan runs as configured (continuous or cycling). The outdoor
air damper closes when the fan is off. The temperature setpoints can be
local (hard-wired), communicated, or stored default values (configurable
using the Rover service tool or a BAS).
Unoccupied mode
In unoccupied mode, the controller attempts to maintain the zone temperature based on the unoccupied heating or cooling setpoint. The fan cycles
between high speed and off. The outdoor air damper remains closed. The
controller always uses the stored default setpoint values (configurable
using the Rover service tool or a BAS), regardless of the presence of a
hard-wired or communicated setpoint value.
Occupied standby mode
The controller is placed in occupied standby mode only when a communicated occupied request is combined with an unoccupied request from
occupancy binary input BI1. In occupied standby mode, the controller
maintains the zone temperature based on the occupied standby heating
or cooling setpoints. Because the occupied standby setpoints are typically
spread 2°F (1.1°C) in either direction and the outdoor air damper is
closed, this mode reduces the demand for heating and cooling the space.
The fan runs as configured (continuous or cycling) for occupied mode.
CNT-SVX12C-EN39
Page 52
Chapter 6 Sequence of operations for the 4-cool configuration
Occupied bypass mode
The controller is placed in occupied bypass mode when the controller is
operating in the unoccupied mode and either the timed override ON button on the Trane zone sensor is pressed or the controller receives a communicated occupied bypass signal from a BAS. In occupied bypass mode,
the controller maintains the zone temperature based on the occupied
heating or cooling setpoints. The fan runs as configured (continuous or
cycling). The outdoor air damper closes when the fan is off. The controller
will remain in occupied bypass mode until either the CANCEL button is
pressed on the Trane zone sensor or the occupied bypass time (configurable using the Rover service tool or a BAS) expires. The temperature
setpoints can be local (hard-wired), communicated, or stored default values (configurable using the Rover service tool or a BAS).
Timed override control
If the zone sensor has a timed override option (ON/CANCEL buttons),
pushing the ON button momentarily shorts the zone temperature signal
to the controller. This short is interpreted as a timed override on request.
A timed override on request changes the occupancy mode from unoccupied mode to occupied bypass mode. In occupied bypass mode, the controller controls the zone temperature based on the occupied heating or
cooling setpoints. The occupied bypass time, which resides in the Tracer
ZN517 and defines the duration of the override, is configurable (using the
Rover service tool or a BAS) from 0 to 240 minutes (default value is 120
minutes). When the occupied bypass time expires, the unit changes from
occupied bypass mode to unoccupied mode. Pushing the CANCEL button
momentarily sends a fixed resistance of 1.5 kΩ to the ZN analog input of
the controller, which is interpreted as a timed override cancel request. A
timed override cancel request will end the timed override before the occupied bypass time has expired and will transition the unit from occupied
bypass mode to unoccupied mode.
If the controller is in any mode other than unoccupied when the ON button is pressed, the controller still starts the occupied bypass timer without changing the mode to occupied bypass. If the controller is placed in
unoccupied mode before the occupied bypass timer expires, the controller
will be placed in occupied bypass mode and remain in that mode until
either the CANCEL button is pressed on the Trane zone sensor or the
occupied bypass time expires.
Outdoor air damper operation
The Tracer ZN517 does not support a two-position outdoor air damper
actuator. However, a modulating, triac, 3-wire floating point actuator
with spring return can be used for two-position control. Two-position control can function only when an outdoor air temperature (either hardwired or communicated) does not exist, and by setting the damper minimum position (using the Rover service tool) to the desired value. To con-
40CNT-SVX12C-EN
Page 53
Fan operation
trol an air damper actuator for two-position control, configure the Tracer
ZN517 for economizing (economizing will not function).
Fan operation
The Tracer ZN517 can be configured to run continuously at a single speed
or to cycle on and off automatically. If configured for continuous operation, the fan runs continuously during the occupied, occupied standby,
and occupied bypass modes. If configured for cycling operation, the fan
will cycle if the temperature is away from setpoint during the occupied,
occupied standby, and occupied bypass modes. During the unoccupied
mode, the fan cycles regardless of the fan configuration.
Peer-to-peer communication
Tracer ZN517 unitary controllers have the ability to share data with
other LonTalk-based controllers. Multiple controllers can be bound as
peers, using the Rover service tool, to share:
•Setpoint
•Zone temperature
•Heating/cooling mode
•Fan status
•Unit capacity control
Shared data is communicated from one controller to any other controller
that is bound to it as a peer. Applications having more than one unit serving a single zone can benefit by using this feature; it allows multiple units
to share a single zone temperature sensor and prevents multiple units
from simultaneously heating and cooling.
Economizing
Economizing (also referred to as “free cooling”) uses outside air for cooling. The Tracer ZN517 provides two triac (3-wire floating point) outputs
to control the damper actuator. One output opens the actuator; the other
closes it. The controller also provides analog inputs for both a discharge
air temperature sensor and an outside air temperature sensor. While
economizing is enabled, the controller uses a discharge air temperature
(DAT) control loop to maintain proper temperature control. The controller
opens the outside air damper, turns on the fan, and attempts to maintain
a user-defined discharge air temperature. If the outside air is unsuitable
for economizer operation, the outside air damper will close and normal
operation (DX cooling) will be activated. Economizing plus DX cooling is
initiated only when economizing alone cannot meet the zone’s cooling
requirements.
To enable this function, set DIP switch 3 to
on page 30).
ON (see “DIP switch settings”
CNT-SVX12C-EN41
Page 54
Chapter 6 Sequence of operations for the 4-cool configuration
Discharge air tempering
Discharge air tempering (also called supply air tempering) prevents occupant discomfort caused by cold outside air being brought into a space
through the outside air damper. This is an important feature in cold climates because the outside air damper is never fully closed for ventilation
purposes. Discharge air tempering starts when:
•The controller is in heating mode.
•The space is otherwise satisfied (no heating or cooling required).
•Ventilation air is passing through the unit
•The discharge air temperature falls 10°F (5.6°C) below the occupied
heating setpoint.
Tempering stops when the occupied heating setpoint is exceeded. To
enable this function, use the Rover service tool to select Supply Air Tempering Enabled.
Demand control ventilation
The Tracer ZN517 unitary controller modulates the outside air damper
position in direct response to the CO
door air allowed to enter. This function is referred to as demand control
ventilation. Demand control ventilation requires that the two triac (3wire floating point) outputs be used to control the damper actuator. The
minimum damper position will increase as CO
500 ppm. The function executes with a 3-minute loop time to allow time
for the sensor to respond.
To enable this function, use the Rover service tool to configure the Tracer
ZN517 as follows:
level, regulating the amount of out-
2
levels rise above
2
•Configure AI1 as a carbon dioxide sensor
•Enter a minimum CO
(factory default: 500 ppm).
•Enter a maximum CO
(factory default: 1500 ppm).
When the CO
100% open.
level reaches the threshold, the minimum position is
2
level (Control Point)
2
threshold (Threshold)
2
Unit protection strategies
The following strategies are initiated when specific conditions exist in
order to protect the unit or building from damage:
•Filter maintenance timer
•Fan off delay
•Fan status
42CNT-SVX12C-EN
Page 55
Unit protection strategies
Filter-maintenance timer
The filter-maintenance timer tracks the amount of time (in hours) that
the fan is enabled. The Maintenance Required Timer Setpoint (Maint Req
Time Setpoint), configured with the Rover service tool, is used to set the
amount of time until maintenance (typically, a filter change) is needed. If
the setpoint is configured to zero, the filter-maintenance timer is disabled.
The controller compares the fan-run time to Maintenance Required Timer
Setpoint. Once the setpoint is reached, the controller generates a Maintenance Required diagnostic. When the diagnostic is cleared, the controller
resets the filter-maintenance timer to zero, and the timer begins accumulating fan-run time again.
Fan off delay
The fan stays on for an additional 30 seconds (adjustable with the Rover
service tool) to allow the residual cooling energy to be circulated through
the system.
Fan status
The controller monitors fan status to protect equipment from overheating. If fan or airflow is not detected for 30 seconds when needed, the
equipment shuts down.
CNT-SVX12C-EN43
Page 56
Chapter 6 Sequence of operations for the 4-cool configuration
44CNT-SVX12C-EN
Page 57
Chapter 7
Applications for the heat
pump configuration
This chapter provides information for wiring input and output terminals
and setting DIP switches for typical heat pump applications. The function
of inputs and outputs is also defined for these applications.
The types of heat pump applications supported by the Tracer ZN517 unitary controller are heat pumps with:
•One or two compressors with reversing valves
•Optional auxiliary heat control
•Optional economizer control
CNT-SVX12C-EN45
Page 58
Chapter 7 Applications for the heat pump configuration
Wiring requirements and options
Table 15 shows required controller inputs for minimal proper operation of
all heat pump applications.
Table 15. Required controller inputs for proper operation
FunctionInput source
24 Vac powerTerminals: GND, 24 V“AC power wiring” on
Zone temperatureTerminals: ZN, GND
or communicated
For more information,
see:
page 85
“ZN: Zone temperature” on page 54
Table 16 shows optional controller inputs and outputs for specific
applications.
Table 16. Optional controller inputs and outputs for specific
applications
* In order to use this function, the economizing function must be enabled.
Input: DAT“Discharge air tem-
Input:
AI1 (CO
sensor)
2
For more information,
see:
“Economizing” on
page 23
pering” on page 24
“Demand control
ventilation” on
page 24
trol” on page 20
Figure 14 on page 47 shows all required and optional components connected for heat pump applications.
46CNT-SVX12C-EN
Page 59
ZONE SENSOR
ANALOG INPUTS
HVAC UNIT
BINARY INPUTS
BINARY OUTPUT
AC OUT
AC POWER
24 Vac
Wiring requirements and options
Figure 14. Wiring diagram for heat pump applications
Powe r*
Tri-state
modulating
economizer
(optional)
Common
H
N
24V
GND
24V
OPN
ECONOMIZERAC OUT
24V
GND
AC POWER
GND
CLS
R
RhRc1G4325NO 5COM
Fan
G
Y1
HVAC UNIT
Compressor 1 contactor
Compressor 2 contactor
Reversing valve
Auxiliary heat
Y2
O
W1
Generic binary output (optional)
BINARY OUTPUT
STATUS5NC
LED
SERVICE
LED
PIN
LonTalk
In
Out
*Terminals Rc and Rh are provided as
inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh
for heat and Rc for cooling. If combined, use only Rc (see “HVAC unit
electrical circuit wiring” on page 82).
COMM5
A BBA
Occupancy
or generic
(optional)
BINARY INPUTS
-BI2-SET-BI1-ZN
Dry contacts
only
ANALOG INPUTS
AI1-DAT-
+20GND
_
GND
+
Typical 3-wire
sensor
(optional)
Fan status or
generic
(optional)
-AI2-
Discharge air
ZONE SENSOR
temperature
Outdoor air
temperature
(optional)
GND
COMM5
LED
LonTalk
1
2
3
4
5
On
Cancel
CNT-SVX12C-EN47
Page 60
Chapter 7 Applications for the heat pump configuration
DIP switch settings
Set the DIP switches on the circuit board for the heat pump configuration. The correct settings are shown in Figure 15.
Figure 15. DIP switch settings for heat pump configuration
ON DIP
1234
ON DIP
1234
ON DIP
1234
Heat pump
without economizer
Heat pump with
economizer
48CNT-SVX12C-EN
Page 61
Binary outputs for heat pump applications
Binary outputs for heat pump
applications
This configuration supports heat pump applications that have the following components:
•Economizer
•Supply fan
•One or two compressors
•Reversing valve
•Auxiliary heat
•Exhaust fan
The Tracer ZN517 controller has eight binary outputs. Each binary output is a relay with a rating of 12 VA. Table 17 describes the function of
each output for heat pump applications.
Table 17. Binary outputs for 2-heat/2-cool applications
Use the Rover service tool to configure binary output 5 (5NO/5COM/5NC)
in one of the following ways. It is the only output that can be configured
as a generic binary output.
•Not used.
•Exhaust fan: Will energize when the economizer outside air damper
position is greater than the user-defined control point.
•Occupancy: Will energize when the Tracer ZN517 is in the occupied
mode.
•Generic: Can be monitored only by a BAS and has no direct effect on
Tracer ZN517 operation.
CNT-SVX12C-EN49
Overriding binary outputs
Use the manual output test to manually control the outputs in a defined
sequence. For more information about the manual output test, see “Manual output test” on page 74.
Page 62
Chapter 7 Applications for the heat pump configuration
Binary inputs for heat pump
applications
The Tracer ZN517 unitary controller has two binary inputs. Each binary
input associates an input signal of 0 Vac with open contacts and 24 Vac
with closed contacts. Table 18 gives the function of each binary input for
4-cool applications. Each function is explained in the succeeding paragraphs. For an explanation of the diagnostics generated by each binary
input, see “Table of diagnostics” on page 79. For more information about
how the controller operates, see Chapter 8, “Sequence of operations for
the heat pump configuration”.”
Table 18. Binary inputs for heat pump applications
Binary input
terminal label
BI1Occupancy or generic
BI2Fan status
Function
BI1: Occupancy or generic
The function of the occupancy input is to save energy by increasing the
range of zone setpoints when the zone is unoccupied. BI1 is used for two
occupancy-related functions. For stand-alone controllers, this binary
input can be hard-wired to a binary switch, clock, or occupancy sensor to
determine the occupancy mode—either occupied or unoccupied. For controllers receiving a BAS-communicated occupancy request, the function of
BI1 is to change the mode from occupied to occupied standby. (For more
information on occupancy-related functions, see “Occupancy modes” on
page 56.)
BI1 is the only input that can be configured as a generic binary input.
When configured as a generic binary input, it can be monitored only by a
BAS, and has no direct effect on Tracer ZN517 operation.
BI2: Fan status
The fan status input provides feedback to the controller regarding the
fan’s operating status. If BI2 is wired to a fan status switch and the input
indicates that the fan is not operating when the controller has the fan
controlled to on, the controller will generate a Local Fan Switch Failure
diagnostic. (For more information, see “Fan status” on page 62.)
50CNT-SVX12C-EN
Page 63
Analog inputs for heat pump applications
Analog inputs for heat pump
applications
The Tracer ZN517 controller has five analog inputs. Table 19 describes
the function of each input for heat pump applications. Each function is
explained in the succeeding paragraphs. For an explanation of the diagnostics generated by each analog input, see “Table of diagnostics” on
page 79. For more information about how the controller operates, see
Chapter 8, “Sequence of operations for the heat pump configuration”.
Table 19. Analog inputs for heat pump applications
Analog input
terminal label
AI1Universal analog input
AI2Outdoor air temperature
DATDischarge air temperature
ZNZone temperature (required)
SETTemperature setpoint
Note:
Use a GND terminal as the common ground for all zone sensor
analog inputs. See Figure 14 on page 47.
Function
AI1: Universal 4–20 mA
The AI1 analog input can be configured in one of the three ways shown in
Table 20.
Table 20. AI1 configuration options and associated measurement
ranges
ConfigurationMeasurement range
Generic 4–20 mA input0–100%
(4 mA=0%; 20 mA=100%)
CO2 measurement0–2000 ppm
(4 mA=0 ppm; 20 mA=2000 ppm)
Relative humidity (RH) measurement0–100%
(4 mA=0% RH; 20 mA=100% RH)
CNT-SVX12C-EN51
If this input is not needed for an application, configure it as Not Used.
This disables the generation of diagnostics.
Note:
AI1 is polarity sensitive.
For the generic input configuration, a 4–20 mA sensor must be hardwired to the AI1 terminal. (Wiring is dependent on the specific applica-
Page 64
Chapter 7 Applications for the heat pump configuration
tion.) The sensor communicates a value of 0–100% to the BAS. This configuration has no direct effect on Tracer ZN517 operation.
For the CO
measurement configuration, a 4–20 mA sensor must be hard-
2
wired to the AI1 terminal as shown in Figure 16. The sensor will transmit
a 0–2000 ppm value to the BAS. This configuration has no direct effect on
Tracer ZN517 operation. If a valid value is established and then is no
longer present, the controller generates a CO
Sensor Failure diagnostic.
2
Figure 16. AI1 terminal wiring: CO
Tracer ZN517
sensor
CO
2
(Trane part number:
4190 4100 or 4190 4101)
measurement
2
24 Vac
{{
24 Vac
GND
+20GND
Out
AI1
For the RH measurement configuration, a hard-wired 4–20 mA zone
humidity sensor (see Figure 17) must provide a value to the controller. If
a valid hard-wired or communicated relative humidity value is established and then is no longer present, the controller generates a RH Sensor
Failure diagnostic and disables the dehumidification function. The RH
sensor is used only to provide a valid humidity reading to a BAS; it does
not affect the operation of the Tracer ZN517.
Figure 17. AI1 terminal wiring: RH measurement
Figure Note:
The +20 terminal provides 20 ±2 Vdc that is used to power a Trane RH sensor (part
numbers 4190 1109, 4190 7011, 4190 7012, 4190 7014).
52CNT-SVX12C-EN
+20GND
+
AI1
–
Tracer ZN517
RH sensor
Page 65
Analog inputs for heat pump applications
AI2: Outdoor air temperature or generic temperature
The AI2 analog input can function as either:
•An outdoor air temperature input
•A generic temperature input
If AI2 is configured as the local (hard-wired) outdoor air temperature
input, the controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input AI2. An outdoor air temperature value communicated by means of a LonTalk link can also be used for
controllers operating on a BAS. If both hard-wired and communicated
outdoor air temperature values are present, the controller uses the communicated value.
If you set DIP switch 3 to
on page 48), you automatically configure AI2 as an outdoor air temperature input. Economizing (free cooling) is a function whereby outdoor air is
used as a source of cooling before hydronic or DX cooling is used. The
Tracer ZN517 uses the outdoor air temperature value to determine
whether economizing is feasible. Economizing is not possible without a
valid outdoor air temperature. (For more information, see “Economizing”
on page 60.)
ON for economizing (see “DIP switch settings”
If AI2 is configured as a generic temperature input, it can be monitored
by a BAS. The controller receives the temperature as a resistance signal
from a 10 kΩ thermistor wired to analog input AI2. The generic temperature input can be used with any Trane 10 kΩ thermistor. The thermistor
can be placed in any location and has no effect on the operation of the controller. If you set DIP switch 3 to
page 48), you automatically configure AI2 as a generic temperature input.
Note:
AI2 is not polarity sensitive; you can connect either terminal to
either sensor lead.
OFF (see “DIP switch settings” on
DAT: Discharge air temperature
The DAT analog input functions as the local discharge air temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input DAT. The thermistor is typically
located downstream from all unit heating and cooling coils at the unit discharge area.
Trane recommends the use of a discharge air temperature sensor to utilize the cascade control function (see “Cascade zone control” on page 56).
Cascade control is a more accurate method of temperature control. If no
discharge air temperature sensor is used, the controller will default to
control based solely on the zone temperature (see “Simplified zone control” on page 56).
CNT-SVX12C-EN53
Note:
DAT is not polarity sensitive; you can connect either terminal
to either sensor lead.
Page 66
Chapter 7 Applications for the heat pump configuration
ZN: Zone temperature
The ZN analog input functions as the local (hard-wired) zone temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor in a standard Trane zone sensor wired to analog input
ZN. A communicated zone temperature value via the LonTalk communications link can also be used for controllers operating on a BAS. When
both a hard-wired and communicated zone temperature value is present,
the controller uses the communicated value. If neither a hard-wired nor a
communicated zone temperature value is present, the controller generates a Space Temperature Failure diagnostic.
The ZN analog input is also used to communicate timed override requests
and cancel requests to the controller for applications utilizing a Trane
zone sensor with the ON and CANCEL button option.
SET: Temperature setpoint
The SET analog input functions as the local (hard-wired) temperature
setpoint input for applications utilizing a Trane zone sensor with a temperature setpoint thumbwheel. Use the Rover service tool or a BAS to
enable or disable the local setpoint input. A communicated setpoint value
via the LonTalk communications link can also be used for controllers
operating on a BAS. If both a hard-wired and a communicated setpoint
value are present, the controller uses the communicated value. If neither
a hard-wired nor a communicated setpoint value is present, the controller
uses the stored default setpoints (configurable using the Rover service
tool or a BAS). If a valid hard-wired or communicated setpoint value is
established and then is no longer present, the controller generates a Local
Space Setpoint Failure diagnostic.
54CNT-SVX12C-EN
Page 67
Chapter 8
Sequence of operations for
the heat pump configuration
A Tracer ZN517 unitary controller configured to control a heat pump will
operate to maintain the zone temperature setpoint. This chapter discusses many of the operational sequences used to accomplish this goal.
Power-up sequence
When 24 Vac power is initially applied to the Tracer ZN517 unitary controller, the following sequence occurs:
1. The Status (green) LED goes on.
2. All outputs are controlled off.
3. The controller reads all input local values to determine initial values.
4. The power-up control wait function begins automatically if the configured power-up control wait time is greater than zero. When this function is enabled, the controller waits for the configured amount of time
(from 10 to 120 seconds) to allow a communicated occupancy request
to arrive. If a communicated occupancy request arrives, normal operation can begin. If a communicated occupancy request does not arrive,
the controller assumes stand-alone operation.
5. The Status LED goes off.
CNT-SVX12C-EN55
6. The wait timer expires.
7. The Status LED goes on.
8. If a hard-wired zone-temperature value is not detected, the controller
begins to wait for a communicated value. (This can take several minutes [15-minute default] and occurs concurrently with the remainder
of the power-up sequence.) If a communicated zone-temperature
value arrives, normal operation can begin when the power-up
sequence has concluded. If a communicated zone-temperature value
does not arrive, the binary outputs remain off and a Space Temperature Failure diagnostic is generated (normal operation cannot begin
without a valid zone temperature value).
9. Normal operation begins assuming no diagnostics have been generated.
Page 68
Chapter 8 Sequence of operations for the heat pump configuration
Cascade zone control
Cascade zone control maintains zone temperature by controlling the discharge air temperature to control the zone temperature. The controller
uses the difference between the measured zone temperature and the
active zone temperature setpoint to produce a discharge air temperature
setpoint. The controller compares the discharge air temperature setpoint
with the discharge air temperature and calculates a unit heating/cooling
capacity accordingly (see Figure 18). The end devices (outdoor air damper,
valves, etc.) operate in sequence based on the unit heating/cooling capacity (0–100%).
Figure 18. Cascade zone control
Active zone
temperature
setpoint
Diffe rence
Measured
zone
temperature
Calculated
discharge air
temperature
setpoint
Difference
Measured
discharge air
temperature
Calculated unit
heating/cooling
capacity
If the discharge air temperature falls below the Discharge Air Control
Point Low Limit (configurable using the Rover service tool) and cooling
capacity is at a minimum, available heating capacity will be used to raise
the discharge air temperature to the low limit (see “Discharge air tempering” on page 60).
Simplified zone control
In the absence of a discharge air temperature sensor, the controller uses
simplified zone control to maintain the zone temperature. In the unoccupied mode, the controller maintains the zone temperature by calculating
the required heating or cooling capacity (0–100%) according to the measured zone temperature and the active zone temperature setpoint. The
active zone temperature setpoint is determined by the current operating
modes, which include occupancy and heat/cool modes.
Occupancy modes
Occupancy modes can be controlled by any of the following:
•The state of the local (hard-wired) occupancy binary input BI1 (see
•A timed override request from a Trane zone sensor (see “Timed over-
56CNT-SVX12C-EN
“BI1: Occupancy or generic” on page 50)
ride control” on page 58)
Page 69
Occupancy modes
•A communicated signal from a peer device (see “Peer-to-peer commu-
nication” on page 61)
•A communicated signal from a BAS
A communicated request, either from a BAS or a peer controller, takes
precedence over local requests. If a communicated occupancy request has
been established and is no longer present, the controller reverts to the
default (occupied) occupancy mode after 15 minutes (if no hard-wired
occupancy request exists). The Tracer ZN517 has the following occupancy
mode options:
•Occupied
•Unoccupied
•Occupied standby
•Occupied bypass
Occupied mode
In occupied mode, the controller maintains the zone temperature based
on the occupied heating or cooling setpoints. The controller uses the occupied mode as a default when other modes of occupancy request are not
present. The fan runs as configured (continuous or cycling with compressor operation). The outdoor air damper closes when the fan is off. The
temperature setpoints can be local (hard-wired), communicated, or stored
default values (configurable using the Rover service tool or a BAS).
Unoccupied mode
In unoccupied mode, the controller operates to maintain the zone temperature based on the unoccupied heating or cooling setpoint. The fan cycles
with compressor operation. The outdoor air damper remains closed. The
controller always uses the stored default setpoint values (configurable
using the Rover service tool or a BAS), regardless of the presence of a
hard-wired or communicated setpoint value.
Occupied standby mode
The controller is placed in occupied standby mode only when a communicated occupied request is combined with an unoccupied request from
occupancy binary input BI1. In occupied standby mode, the controller
maintains the zone temperature based on the occupied standby heating
or cooling setpoints. Because the occupied standby setpoints are typically
spread 2°F (1.1°C) in either direction and the outdoor air damper is
closed, this mode reduces the demand for heating and cooling the space.
The fan runs as configured (continuous or cycling with the compressor).
CNT-SVX12C-EN57
Page 70
Chapter 8 Sequence of operations for the heat pump configuration
Occupied bypass mode
The controller is placed in occupied bypass mode when the controller is
operating in the unoccupied mode and either the timed override ON button on the Trane zone sensor is pressed or the controller receives a communicated occupied bypass signal from a BAS. In occupied bypass mode,
the controller maintains the zone temperature based on the occupied
heating or cooling setpoints. The fan runs as configured (continuous or
cycling with the compressor). The outdoor air damper closes when the fan
is off. The controller will remain in occupied bypass mode until either the
CANCEL button is pressed on the Trane zone sensor or the occupied
bypass time (configurable using the Rover service tool or a BAS) expires.
The temperature setpoints can be local (hard-wired), communicated, or
stored default values (configurable using the Rover service tool or a BAS).
Timed override control
If the zone sensor has a timed override option (ON/CANCEL buttons),
pushing the ON button momentarily shorts the zone temperature signal
to the controller. This short is interpreted as a timed override on request.
A timed override on request changes the occupancy mode from unoccupied mode to occupied bypass mode. In occupied bypass mode, the controller controls the zone temperature based on the occupied heating or
cooling setpoints. The occupied bypass time, which resides in the Tracer
ZN517 and defines the duration of the override, is configurable (using the
Rover service tool or a BAS) from 0 to 240 minutes (default value is 120
minutes). When the occupied bypass time expires, the unit changes from
occupied bypass mode to unoccupied mode. Pushing the CANCEL button
momentarily sends a fixed resistance of 1.5 kΩ to the ZN analog input of
the controller, which is interpreted as a timed override cancel request. A
timed override cancel request will end the timed override before the occupied bypass time has expired and will transition the unit from occupied
bypass mode to unoccupied mode.
If the controller is in any mode other than unoccupied when the ON button is pressed, the controller still starts the occupied bypass timer without changing the mode to occupied bypass. If the controller is placed in
unoccupied mode before the occupied bypass timer expires, the controller
will be placed in occupied bypass mode and remain in that mode until
either the CANCEL button is pressed on the Trane zone sensor or the
occupied bypass time expires.
Outdoor air damper operation
The Tracer ZN517 does not support a two-position outdoor air damper
actuator. However, a modulating, triac, 3-wire floating point actuator
with spring return can be used for two-position control. Two-position control can function only when an outdoor air temperature (either hardwired or communicated) does not exist, and by setting the damper minimum position (using the Rover service tool) to the desired value. To con-
58CNT-SVX12C-EN
Page 71
Heating or cooling mode
trol an air damper actuator for two-position control, configure the Tracer
ZN517 for economizing (economizing will not function).
Heating or cooling mode
The heating or cooling mode can be determined in one of two ways:
•By a communicated signal from a BAS or a peer controller
•Automatically, as determined by the controller
A communicated heating signal permits the controller to heat only. A
communicated cooling signal permits the controller to cool only. A communicated auto signal allows the controller to automatically change from
heating to cooling and vice versa.
In heating and cooling mode, the controller maintains the zone temperature based on the active heating setpoint and the active cooling setpoint,
respectively. The active heating and cooling setpoints are determined by
the occupancy mode of the controller.
When no communicated signal is present (stand-alone operation) or the
communicated signal is auto, the controller automatically determines the
heating or cooling mode.
Fan operation
The Tracer ZN517 can be configured to run continuously at a single speed
or to cycle on and off automatically. If configured for continuous operation, the fan runs continuously during the occupied, occupied standby,
and occupied bypass modes. If configured for cycling operation, the fan
will cycle if the temperature is away from setpoint during the occupied,
occupied standby, and occupied bypass modes. During the unoccupied
mode, the fan cycles regardless of the fan configuration.
Compressor operation
The Tracer ZN517 supports heat pump applications with one or two compressors. The compressor(s) will cycle to meet zone temperature requirements. Compressor operation will be overridden by a preset 3-minute
minimum on/off time delay in order to maintain oil return when the unit
is either initially energized, manually reset, switched between modes, or
cycled within a single mode.
Reversing valve operation
The reversing valve is configurable to energize in either the cooling mode
(typical of Trane units) or the heating mode. Be sure to configure the
reversing valve operation based on the heat pump manufacturer’s design.
An energized valve will remain energized until a mode change (either
CNT-SVX12C-EN59
Page 72
Chapter 8 Sequence of operations for the heat pump configuration
from cooling to heating or vice versa) is initiated. The reversing-valve
operation is delayed after compressor shutdown to reduce noise due to
refrigerant migration. The reversing valve will de-energize when a power
failure occurs, or when the controller is set to off either through a communicated off signal or when the fan switch is set to
Economizing
Economizing (also referred to as “free cooling”) uses outside air for cooling. The Tracer ZN517 provides two triac (3-wire floating point) outputs
to control the damper actuator. One output opens the actuator; the other
closes it. The controller also provides analog inputs for both a discharge
air temperature sensor and an outside air temperature sensor. While
economizing is enabled, the controller uses a discharge air temperature
(DAT) control loop to maintain proper temperature control. The controller
opens the outside air damper, turns on the fan, and attempts to maintain
a user-defined discharge air temperature. If the outside air is unsuitable
for economizer operation, the outside air damper will close and normal
operation (DX cooling) will be activated. Economizing plus DX cooling is
initiated only when economizing alone cannot meet the zone’s cooling
requirements.
OFF.
To enable this function, set DIP switch 3 to
on page 48).
ON (see “DIP switch settings”
Discharge air tempering
Discharge air tempering (also called supply air tempering) prevents occupant discomfort caused by cold outside air being brought into a space
through the outside air damper. This is an important feature in cold climates because the outside air damper is never fully closed for ventilation
purposes. Discharge air tempering starts when:
•The controller is in heating mode.
•The space is otherwise satisfied (no heating or cooling required).
•Ventilation air is passing through the unit
•The discharge air temperature falls 10°F (5.6°C) below the occupied
heating setpoint.
Tempering stops when the occupied heating setpoint is exceeded. To
enable this function, use the Rover service tool to select Supply Air Tempering Enabled.
Demand control ventilation
The Tracer ZN517 unitary controller modulates the outside air damper
position in direct response to the CO
door air allowed to enter. This function is referred to as demand control
ventilation. Demand control ventilation requires that the two triac (3-
level, regulating the amount of out-
2
60CNT-SVX12C-EN
Page 73
Peer-to-peer communication
wire floating point) outputs be used to control the damper actuator. The
minimum damper position will increase as CO
500 ppm. The function executes with a 3-minute loop frequency to allow
time for the sensor to respond.
To enable this function, use the Rover service tool to configure the Tracer
ZN517 as follows:
levels rise above
2
•Configure AI1 as a carbon dioxide sensor
•Enter a minimum CO
(factory default: 500 ppm).
•Enter a maximum CO
(factory default: 1500 ppm).
When the CO
100% open.
level reaches the threshold, the minimum position is
2
level (Control Point)
2
threshold (Threshold)
2
Peer-to-peer communication
Tracer ZN517 unitary controllers have the ability to share data with
other LonTalk-based controllers. Multiple controllers can be bound as
peers, using the Rover service tool, to share:
•Setpoint
•Zone temperature
•Heating/cooling mode
•Fan status
•Unit capacity control
Shared data is communicated from one controller to any other controller
that is bound to it as a peer. Applications having more than one unit serving a single zone can benefit by using this feature; it allows multiple units
to share a single zone temperature sensor and prevents multiple units
from simultaneously heating and cooling.
Unit protection strategies
The following strategies are initiated when specific conditions exist in
order to protect the unit or building from damage:
•Filter-maintenance timer
•Fan off delay
•Fan status
Filter-maintenance timer
The filter-maintenance timer tracks the amount of time (in hours) that
the fan is enabled. The Maintenance Required Timer Setpoint (Maint Req
Time Setpoint), configured with the Rover service tool, is used to set the
amount of time until maintenance (typically, a filter change) is needed. If
the setpoint is configured to zero, the filter-maintenance timer is disabled.
CNT-SVX12C-EN61
Page 74
Chapter 8 Sequence of operations for the heat pump configuration
The controller compares the fan-run time to Maintenance Required Timer
Setpoint. Once the setpoint is reached, the controller generates a Maintenance Required diagnostic. When the diagnostic is cleared, the controller
resets the filter-maintenance timer to zero, and the timer begins accumulating fan-run time again.
Fan off delay
The fan stays on for an additional 30 seconds (adjustable with the Rover
service tool) to allow the residual cooling or heating energy to be circulated through the system.
Fan status
The controller monitors fan status to protect equipment from overheating. If fan or airflow is not detected for 30 seconds when needed, the
equipment shuts down.
62CNT-SVX12C-EN
Page 75
Chapter 9
PID control
This chapter will help you set up, tune, and troubleshoot proportional,
integral, derivative (PID) control loops used in the Tracer ZN517 unitary
controller. For more information about PID loops, see BAS-APG002, PID Control in Tracer Multi-Purpose Controllers.
PID control requires the use of a Rover service tool. All PID factory
defaults can be restored by clicking the Use Defaults button.
What PID loops do
A PID loop automatically controls an output to maintain a measured
value at its setpoint by monitoring the error (the difference between the
measured value and the setpoint). The loop performs proportional, integral, and derivative calculations to determine how aggressively to change
the output.
The goal of PID control is to reach the setpoint as quickly as possible
without overshooting the setpoint or destabilizing the system and to
maintain the setpoint consistently over time. If the system is too aggressive, it will overshoot the setpoint as shown in Figure 19. If it is not
aggressive enough, the time to reach the setpoint will be unacceptably
slow.
Figure 19. The effects of PID aggressiveness
Too aggressive (overshoot)
Setpoint
Measured value
Initial point
CNT-SVX12C-EN63
Ideal response
Too slow
Time
Page 76
Chapter 9 PID control
PID calculations
PID algorithms perform three calculations: the proportional calculation,
the integral calculation, and the derivative calculation. These calculations are independent of each other but are combined to determine the
response of the controller to the error.
Proportional calculation
The proportional calculation responds to how far the measured value is
from the setpoint. The larger the error, the larger the output of the calculation. The proportional calculation has a much stronger effect on the
result of the PID algorithm than either the integral or derivative calculations. It determines the responsiveness (or aggressiveness) of a control
system. Though some systems use only proportional control, most Trane
controllers use a combination of proportional and integral control.
Proportional-only control loops require an error to produce an output. If
the setpoint and the process variable are the same, the error is zero, so
the system does not have an output. In an HVAC system, this can cause
an actuator to open or close. The integral calculation solves this problem.
The recommended range for the proportional calculation in the Tracer
ZN517 is 4–16. Restore PID factory defaults by clicking the Use Defaults
button.
Integral calculation
The integral calculation responds to the length of time the measured
value is not at setpoint. The longer the measured value is not at setpoint,
the larger the output of the calculation.
The integral calculation uses the sum of past errors to maintain an output when the error is zero. Line 1 in Figure 20 on page 65 shows that with
proportional-only control, when the error becomes zero, the PID output
also goes to zero. Line 2 in Figure 20 shows the integral output added to
the proportional output. Because the integral calculation is the sum of
past errors, the output remains steady rather than dropping to zero when
the error is zero. The benefit of this is that the integral calculation keeps
the output at the appropriate level to maintain an error of zero.
The value of the integral calculation can build up over time (because it is
the sum of all past errors), and this built-up value must be overcome
before the system can change direction. This prevents the system from
over-reacting to minor changes, but can potentially slow the system down.
The recommended range for the integral calculation in the Tracer ZN517
is 1–10. Restore PID factory defaults by clicking the Use Defaults button.
64CNT-SVX12C-EN
Page 77
Sampling frequency
Figure 20. Integral output added to proportional output
Error ≠ 0
Proportional + integral
output
2
Output
1
Proportional-only
output
Time
Error = 0
Proportional + integral
output if proportional
output has gone to zero
Derivative calculation
The derivative calculation responds to the change in error. In other
words, it responds to how quickly the measured value is approaching setpoint. The derivative calculation can be used to smooth an actuator
motion or cause an actuator to react faster.
However, derivative control has several disadvantages:
•It can react to noise in the input signal.
•Setting derivative control requires balancing between two extremes;
too much derivative gain and the system becomes unstable, too little
and the derivative gain has almost no effect.
•The lag in derivative control makes tuning difficult.
•Large error deadbands, common in HVAC applications, render deriv-
ative control ineffective.
Because of these disadvantages, derivative control is rarely used in HVAC
applications (with the exception of steam valve controllers, which use
derivative control to force the steam valve to react faster to changes).
CNT-SVX12C-EN65
Sampling frequency
The sampling frequency is the rate at which the input signal is sampled
and PID calculations are performed. Using the right sampling frequency
is vital to achieving a responsive and stable system. Problems can arise if
the sampling frequency is too slow or too fast in comparison to time lags
in the system.
Sampling too slowly can cause an effect called aliasing in which not
enough data is sampled to form an accurate picture of changes in the
Page 78
Chapter 9 PID control
Figure 21. Sampling too slowly
measured value. The system may miss important information and reach
setpoint slowly or not at all.
Figure 21 and Figure 22 show how aliasing can affect system response. In
Figure 21 the sampling frequency is too slow. Because of this, many of the
actual changes in duct static pressure are missed. In Figure 22 the sampling frequency is fast enough that the changes in static pressure are
tracked accurately.
Sampling points
Duct static pressure
Figure 22. Sampling at the correct rate
Sampling points
Changes missed
by system
Time
Duct static pressure
Problems also arise from sampling too quickly. Some systems have naturally slow response times, such as when measuring room temperature.
Slow response times can also be caused by equipment lags. Since PID
loops respond to error and changes in error over time, if the process variable (measured value) changes slowly, then the error will remain constant
for an extended period of time. If the process variable is sampled repeatedly during this time, the proportional output remains about the same,
but the integral output becomes larger (because it is the sum of past
errors). When the control system does respond, the response is out of proportion to the reality of the situation, which can destabilize the system.
66CNT-SVX12C-EN
Time
Page 79
Sampling frequency
The control system should always wait to process the result of a change
before making another change.
Figure 23 shows the process variable if sampling times are too fast,
acceptable, and barely acceptable. If the sampling frequency is too fast (2
seconds), the process variable begins to oscillate and finally destabilizes
because the PID loop output drives the actuator to extremes.
Figure 23. System stability with different sampling times
Sampling freq. = 10 sSampling freq. = 20 s
Sampling freq. = 2 s
(system destabilizes if
sampling freq. is too fast)
Process variable
Time
CNT-SVX12C-EN67
Page 80
Chapter 9 PID control
PID loop action
The action of a PID loop determines how it reacts to a change in the process variable (such as a room temperature). A controller using direct
action increases the output when the process variable increases. A controller using reverse action decreases the output when the process variable increases.
Direct action
Figure 24 shows the temperature when a system is cooling a space. If the
error is large and the PID output is at 100%, the actuator and valve combination are fully open. As the process variable (room temperature)
decreases, the error becomes smaller, and the controller closes the valve
to reduce or stop cooling. Since the PID output and process variable move
in the same direction (both decreasing), the loop is direct acting.
Figure 24. Cooling a space
Process variable
(temperature)
Temperature
Setpoint
Error
Time
Reverse action
Figure 25 shows the temperature when a system is heating a space. If the
error is large and the PID output is at 100%, the actuator and valve combination are fully open. If the process variable (room temperature)
increases, reducing the error, the controller closes the valve to reduce
heating. Since the PID output and process variable move in opposite
directions, the loop is reverse acting.
Figure 25. Heating a space
Time
Setpoint
Error
Temperature
Process variable
(temperature)
68CNT-SVX12C-EN
Page 81
Figure 26. Error deadband
Process
Error
Error deadband
variable
Error deadband
Error deadband
Error deadband is typically used to minimize actuator activity. It can also
be used to allow for some “slop” in the system sensors and actuator
mechanics. Error deadband prevents the PID output from changing if the
absolute value of the error is less than the error deadband. For example,
in Figure 26 the error deadband is set at 2.0°F (1.1°C). As long as the
absolute value of the error is less than the 2.0°F (1.1°C), the PID output
cannot change. If the absolute value of the error does exceed 2.0°F
(1.1°C), the PID output can change.
Control
Setpoint
Control
As can be seen from Figure 26, error deadband is a means of limiting how
often an actuator is controlled. If a PID loop controls a chilled water
valve, this is not so important. But if a PID loop controls how many stages
of cooling are being used, it is important to limit equipment cycling.
Adjusting error deadband for modulating outputs
In most applications, start with an error deadband of five or ten times the
sensor resolution. For example, thermistors have a resolution of approximately 0.1°F (0.06°C), so a good error deadband is 0.5°F (0.3°C). This setting ensures that the sensor reading has changed an adequate amount
before the controller responds.
IMPORTANT
The error deadband should not be smaller than the sensor resolution or
the controller will react to noise.
Adjusting error deadband for staged outputs
This section shows how to adjust the error deadband for staging applications.
CNT-SVX12C-EN69
Finding the best error deadband for staged output applications is more
difficult than for modulating outputs. Instead of using a continuous actuator, such as a chilled water valve, staged systems use binary outputs to
start and stop pieces of equipment, such as fans in a cooling tower. Each
Page 82
Chapter 9 PID control
piece of equipment contributes a set amount to the final output. When
setting the error deadband for staged outputs, the main goal is to reduce
equipment cycling.
Follow these guidelines when adjusting the error deadband:
•Ask how tight control should be. A smaller error deadband results in
tighter control, but control should not be so tight that the stages cycle
on and off too frequently.
For example, for a VAV air-handler turning on cooling stages, control
can be somewhat loose. The individual VAV boxes control their valve
to the space depending on the supply air temperature. If the supply
air temperature is relatively warm, the VAV box allows more air flow.
If the supply air temperature is somewhat cool, the VAV box constricts the air flow.
•The contribution of each stage can change depending on external cir-
cumstances, so make adjustments under worst case conditions.
Adjust the error deadband for cooling tower fan stages on very warm
days, and adjust the error deadband for boiler stages on very cold
days.
With the preceding guidelines in mind, use the following procedure to
determine error deadband.
To adjust the error deadband for staged outputs:
1. Run the system manually.
If possible, do so under worst-case conditions for the site. Although it
is not always possible for a technician to do this, it is possible for a
well-trained customer.
2. Find the smallest change in temperature, ∆T, that the first stage can
contribute (the quantity could also be building static pressure for fans
or flow for pumps).
Pay attention to possible changes in external circumstances, such as
the amount of water flow. If the system uses a lead-lag approach to
the equipment, it will be necessary to find the minimum ∆T for all
stages.
3. Multiply ∆T by 0.45 (the error deadband should be slightly less than
half of ∆T).
Keep in mind the resolution of the sensor. You may need to round the
error deadband to a more reasonable value.
4. Run the system with the new error deadband.
Cycling should be reduced as much as possible.
70CNT-SVX12C-EN
Page 83
Other PID settings
Other PID settings
You can also use these settings to manage PID loops:
•Proportional bias, which takes the place of derivative gain in propor-
tional-only control
•Minimum and maximum output, which limit the range of output of
the PID algorithm
•Enabled and disabled modes, which enable the PID output or disable
it to a default value
•Fail-safe mode sets the PID output to a “safe” value if the hardware
input that provides the process variable fails.
For more information, see BAS-APG002, PID Control in Tracer Multi-Purpose Controllers.
Troubleshooting procedure
IMPORTANT
Remember to change only one thing at a time.
Follow these steps to troubleshoot a PID loop:
1. Make sure that the system is not in override.
2. Graph the process variable, setpoint, and valve position over time to
determine how the system performs.
Look at the big picture. Can the system do what’s expected of it? What
is happening to the process variable? Is it oscillating or failing to
reach setpoint? Is the output oscillating?
3. Check for failure conditions that are always true.
4. Check PID settings for:
•Output minimum incorrectly set to 100%
•Output maximum incorrectly set to 0%
•Sampling time that is too fast or too slow
5. Check the system for disturbances from:
•Bad actuator linkages
•Faulty sensors
6. Change PID gains.
•Reduce gains if experiencing system overshoot, output at mini-
mum or maximum, or cycling of output around setpoint
•Increase gains if experiencing system undershoot
CNT-SVX12C-EN71
Page 84
Chapter 9 PID control
Tips for specific problems
Table 21 provides tips for troubleshooting specific problems.
Table 21. Tips for specific problems
ProblemTips
Measured value is cycling
around setpoint
Overshooting setpointReduce gains
Undershooting setpointIncrease gains
Output at maximumEnsure that minimum output is not set to 100%
Output at minimumEnsure that maximum output is not set to 0%
• Slow the sampling frequency
• Decrease PID gains
Changing the sampling frequency
The major cause of actuator cycling is time lags in the system. If a 10%
change in PID output requires two minutes to affect the process variable,
it does no good to have the sampling frequency set to two seconds. The
integral contribution will build up before any significant change in error
can be measured. A sampling frequency of 30 to 60 seconds would work
much better in this situation. In other words, to fix a cycling system, slow
down the loop! See “Sampling frequency” on page 65 for more information.
Changing the gains
Be careful when changing PID gains. Never change gains unless the
effects can be measured. Use a doubling/halving technique when increasing or decreasing gains. If the PID gains are set to 4, 1, and 0 respectively,
and you are going to reduce them, try 2, 0.5, and 0. If the system now
undershoots, try gains of 3, 0.75, and 0 respectively.
72CNT-SVX12C-EN
Page 85
Chapter 10
Status indicators for
operation and
communication
This chapter describes the operation and communication status indicators on the Tracer ZN517 unitary controller, including:
•A description of the location and function of the Test button and Ser-
vice Pin button and the light-emitting diodes (LEDs)
•A complete list of the diagnostics that can occur, their effect on con-
troller outputs, and an explanation of how to clear diagnostics and
restore the device to normal operation
Test button
Use the Test button to perform the manual output test (see “Manual output test” on page 74), which verifies that the controller is operating properly. Figure 27 shows its location.
Chapter 10 Status indicators for operation and communication
Manual output test
The manual output test sequentially turns off and on all binary outputs
to verify their operation. The test overrides normal operation of the controller, which is suspended while the test is being performed.
Use the manual output test to:
•Verify output wiring and operation.
•Force compressor operation so that a technician can use test equip-
ment to verify unit operation.
•Clear diagnostics and restore normal operation (although not a pri-
mary function of the manual output test).
Perform the manual output test either by repeatedly pressing the Test
button to proceed through the test sequence or by using the Rover service
tool. Table 22 on page 75, Table 23 on page 75, and Table 24 on page 76
list the outputs in the sequence in which they are verified for the 2-heat/
2-cool, 4-cool, and heat pump configurations, respectively.
To perform a manual output test:
1. Press and hold the Test button for 3 to 4 seconds, then release the
button to start the test mode. The green LED light goes off when the
Test button is pressed, and then it blinks (as described in Table 26 on
page 77) when the button is released to indicate the controller is in
manual test mode.
2. Press the Test button (no more than once per second) to advance
through the test sequence. Table 22 shows the resulting activities of
the binary outputs.
3. The controller exits the test mode after the final step or after 1 hour
passes, whichever comes first.
Note:
The outputs are not subject to minimum on or off times during
the test sequence. However, the test sequence permits only one
step per second, which enforces a minimum output time.
Service Pin button
Use the Service Pin button to verify that the controller is communicating
on the network communications link, and to add devices and identify
existing devices on the network communications link. See Figure 27 on
page 73 for the location of the Service Pin button.
For more information about the function of the Service Pin button, see the
Rover Operation and Programming guide (EMTX-SVX01B-EN) or the
Tracker Building Automation System Hardware Installation guide
(BMTK-SVN01A-EN).
74CNT-SVX12C-EN
Page 87
Service Pin button
Table 22. Manual output test sequence for 2-heat/2-cool configurations
Step (number of times
Test button is pressed
in sequence)
1Begins test modeOffOffOffOffOffOffOff
Fan on
1
2
3Compressor 1OnOffOnOffOffOffOff
4Compressor 2OnOffOnOnOffOffOff
5Heat 1OnOffOffOffOnOffOff
6Heat 2OnOffOffOffOnOnOff
7Outdoor air damperOnOnOffOffOffOffOff
8Generic/exhaust fan/occupancyOnOffOffOffOffOffOn
Exit
2
9
1
At the beginning of Step 2, the controller attempts to clear all diagnostics.
2
This step exits the manual output test and initiate a reset to restore the controller to normal operation.
Result
Fan (G)
Economizer (OPN)
Cool stage 1 (1)
Cool stage 2 (2)
Heat stage 1 (3)
OnOffOffOffOffOffOff
OffOffOffOffOffOffOff
Heat stage 2 (4)
Exhaust fan/generic/
occupancy
(5NO/5COM/5NC)
Table 23. Manual output test sequence for 4-cool configurations
Step (number of times
Test button is pressed
in sequence)
1Begins test modeOffOffOffOffOffOffOff
Fan on
1
2
3Compressor 1OnOffOnOffOffOffOff
4Compressor 2OnOffOnOnOffOffOff
5Compressor 3OnOffOnOnOnOffOff
6Compressor 4OnOffOnOnOnOnOff
7Outdoor air damperOnOnOffOffOffOffOff
8Generic/exhaust fan/occupancyOnOffOffOffOffOffOn
Exit
2
9
1
At the beginning of Step 2, the controller attempts to clear all diagnostics.
2
This step exits the manual output test and initiate a reset to restore the controller to normal operation.
Result
Fan (G)
Economizer (OPN)
Cool stage 1 (1)
Cool stage 2 (2)
Heat stage 1 (3)
OnOffOffOffOffOffOff
OffOffOffOffOffOffOff
Heat stage 2 (4)
Exhaust fan/generic/
occupancy
(5NO/5COM/5NC)
CNT-SVX12C-EN75
Page 88
Chapter 10 Status indicators for operation and communication
Table 24. Manual output test sequence for heat pump configurations
Step (number of times
Test button is pressed
in sequence)
1Begins test modeOffOffOffOffOffOffOff
Fan on
1
2
3Reversing valve onOnOffOffOffOnOffOff
4Compressor 1OnOffOnOffOnOffOff
5Compressor 2OnOffOnOnOnOffOff
6Compressors offOnOffOffOffOffOffOff
7Auxiliary heatOnOffOffOffOffOnOff
8Outdoor air damperOnOnOffOffOffOffOff
9Generic/exhaust fan/occupancyOnOffOffOffOffOffOn
10
1
At the beginning of Step 2, the controller attempts to clear all diagnostics.
2
This step exits the manual output test and initiate a reset to restore the controller to normal operation.
Exit
2
Result
Fan (G)
Economizer (OPN)
Cool stage 1 (1)
Cool stage 2 (2)
Heat stage 1 (3)
OnOffOffOffOffOffOff
OffOffOffOffOffOffOff
Heat stage 2 (4)
Exhaust fan/generic/
occupancy
(5NO/5COM/5NC)
Interpreting LEDs
The red LED on the Tracer ZN517 unitary controller (see Figure 27 on
page 73) indicates whether the controller is not working properly (see
Table 25).
Table 25. Red LED: Service indicator
LED activityExplanation
LED is off continuously when power
is applied to the controller.
LED is on continuously when power
is applied to the controller.
LED flashes once every second.The controller is not executing the
1
Restore the controller to normal operation using the Rover service tool. Refer to
EMTX-SVX01B-EN for more information.
The controller is operating normally.
The controller is not working properly, or someone is pressing the Service button.
application software because the network connections and addressing
have been removed.
1
76CNT-SVX12C-EN
Page 89
Interpreting LEDs
The green LED on the Tracer ZN517 unitary controller (see Figure 27 on
page 73) indicates whether the controller has power applied to it and if
the controller is in manual test mode (see Table 26).
Table 26. Green LED: Status indicator
LED activityExplanation
LED is on continuously.Power is on (normal operation).
LED blinks (one recurring blink).Manual output test mode is being
performed and no diagnostics are
present.
LED blinks (blinks twice as a recurring sequence).
LED blinks (1/4 second on,
1/4 second off for 10 seconds).
LED is off continuously.Either the power is off,
1
By sending a request from the Rover service tool, you can request the controller’s
green LED to blink (“wink”), a notification that the controller received the signal
and is communicating.
Manual output test mode is being
performed and one or more diagnostics are present.
The Auto-wink option is activated,
and the controller is communicat-
1
ing.
the controller has malfunctioned, or
the Test button is being pressed.
The yellow LEDs on the Tracer ZN517 unitary controller (see Figure 27
on page 73) indicate the controller’s communications status (see
Table 27).
Table 27. Yellow LED: Communications indicator
LED activityExplanation
LED is off continuouslyThe controller is not detecting any
communication (normal for standalone applications).
LED blinks.The controller detects communica-
tion (normal for communicating
applications, including data sharing).
LED is on continuously.Abnormal condition.
CNT-SVX12C-EN77
Page 90
Chapter 10 Status indicators for operation and communication
Diagnostics
In response to a diagnostic, the controller attempts to protect the equipment it is controlling by disabling all the outputs. When the diagnostic
clears, the controller resumes normal operation.
Diagnostic types
The Tracer ZN517 has two types of diagnostics: informational and automatic (also referred to as nonlatching). Informational diagnostics provide
information about the status of the controller. They do not affect machine
operation. They can be cleared from the controller in one of the following
ways:
•By using the Rover service tool (see “Resetting a diagnostic” in
EMTX-SVX01B-EN, Rover Operation and Programming guide.)
•Through a building automation system (see product literature)
•By initiating a manual output test at the controller (see “Manual out-
put test” on page 74)
•By cycling power to the controller. When the 24 Vac power to the con-
troller is cycled off and then on again, a power-up sequence occurs.
Automatic (nonlatching) diagnostics clear automatically when the problem that generated the diagnostics is solved.
78CNT-SVX12C-EN
Page 91
Table of diagnostics
Table 28 describes each diagnostic that can be generated by the Tracer
ZN517.
Table 28. Diagnostics for the ZN517 unitary controller
Diagnostics
DiagnosticProbable causeConsequences
P NormalDefault value until power-up
control wait expires
NormalDefault value after power-up
control wait expires
Local Space Setpoint FailureInvalid or missing value for
space setpoint
Maintenance RequiredThe maintenance required
timer has expired
Local Fan Switch FailureBI2 has not seen a contact
closure for 60 seconds, indicating fan proving
CO2 Sensor FailureCO2 input is invalid or
missing
Discharge Air Temp FailureDischarge air temperature
input is invalid or missing
Invalid Unit ConfigurationInvalid DIP switch settingController will not operate.Automatic
RH Sensor FailureRelative humidity input is
invalid or missing
Space Temperature FailureSpace temperature sensor
is invalid or missing
NoneN/A
NoneN/A
The controller uses default values.Informational
Informational warning only.Informational
All binary outputs are disabled.Automatic
Demand control ventilation is
disabled.
All binary outputs are disabled.Automatic
Dehumidification is disabled.Automatic
All binary outputs are disabled.Automatic
Diagnostic
type
Automatic
CNT-SVX12C-EN79
Page 92
Chapter 10 Status indicators for operation and communication
80CNT-SVX12C-EN
Page 93
Chapter 11
General wiring information
This chapter provides specifications and general information about wiring the Tracer ZN517 unitary controller. The controller requires wiring
for:
•Input/output terminals
•AC power to the controller
•Communication-link wiring, if the controller is to communicate with a
building automation system (BAS)
Input/output terminal wiring
All input/output terminal wiring for the Tracer ZN517 unitary controller
is application specific and dependant on the configuration of the controller. For application-specific wiring information and diagrams, see Chapter
3, “Applications for the 2-heat/2-cool configuration”,” Chapter 5, “Applications for the 4-cool configuration”,” and Chapter 7, “Applications for the
heat pump configuration”.”
Wiring specifications
Input/output terminal wiring must meet the following requirements:
•All wiring must comply with the National Electrical Code and local
codes.
•Use only 18 AWG twisted-pair wire with stranded, tinned-copper con-
ductors. (Shielded wire is recommended.)
•Binary input and output wiring must not exceed 1000 ft (300 m).
•Analog input wiring must not exceed 300 ft (100 m).
•Do not run input/output wires in the same wire bundle with any ac
power wires.
CNT-SVX12C-EN81
Page 94
Chapter 11 General wiring information
HVAC unit electrical circuit wiring
The terminals labeled Rc and Rh are provided as inputs for 24 Vac power
from the transformer(s) of the HVAC system.
Note:
The Tracer ZN517 is shipped from the factory with terminals
Rc and Rh coupled with the jumper at J1 on the controller circuit board.
Packaged units
If the HVAC unit combines heating and cooling (referred to as a “packaged” unit), it will typically have one “R” transformer. For 24 Vac wiring
of packaged units, the Rc terminal must be wired as shown in this
procedure:
1. Locate the jumper at J1 on the controller circuit board (Figure 28 on
2. Wire the Rc terminal to the transformer on the unit (Figure 30 on
page 83). Place the jumper on both pins at J1 on the circuit board
(Figure 29 on page 83).
page 84).
Split systems
If the unit is a split system (a unit with physically separate heating and
cooling sections), there is typically a separate transformer for each function. For 24 Vac wiring of split systems, the Rc and Rh terminals must be
wired as show in this procedure:
1. Locate the jumper at J1 on the controller circuit board (Figure 28 on
page 83). Remove the jumper from the pins at J1 on the circuit board
(Figure 29 on page 83).
2. Replace the jumper on one of the pins at J1 for possible future use.
3. Wire Rc to the transformer for the cooling section of the unit
(Figure 31 on page 84).
4. Wire Rh to the transformer for the heating section of the unit
(Figure 31 on page 84).
82CNT-SVX12C-EN
Page 95
Input/output terminal wiring
Figure 28. Location of J1 on Tracer ZN517 circuit board
J1 (location of
jumper for Rc,
Rh terminals)
For packaged units
Place the jumper on
both pins at J1.
Figure 29. Coupling and uncoupling terminals Rc and Rh for 24 Vac
wiring of the HVAC unit
J1J1
For split systems
Remove the jumper from
one of the pins at J1.
(Leave it on one of the pins
for possible future use.)
CNT-SVX12C-EN83
Page 96
Chapter 11 General wiring information
Figure 30. Wiring for packaged heating and cooling units
Secondary, 24 Vac
Primar y
24 Vac
24 Vac
Tri-state
modulating
economizer
(optional)
H
N
Fan
Compressor 1 contactor
Compressor 2 contactor
Heat stage 1
Heat stage 2
R
Y2
Y1
G
W1 W2
Generic binary output (dry contact)
Figure 31. Wiring for split system applications
Primary
Secondary, 24 Vac
Tri-state
modulating
economizer
(optional)
H
N
Rc
Rh
G
Fan*
Compressor 1 contactor
Compressor 2 contactor
Heat stage 1
Y2
Y1
W1
Heat stage 2
W2
Generic binary output (dry contact)
Primary
Secondary, 24 Vac
*Wire the fan (G) to the appropriate section of the split system.
84CNT-SVX12C-EN
Page 97
AC power wiring
AC power wiring
CAUTION
Equipment damage!
Complete input/output wiring before applying power to the Tracer
ZN517 unitary controller. Failure to do so may cause damage to the controller or power transformer due to inadvertent connections to power
circuits.
CAUTION
Hazardous voltage!
Make sure that the 24 Vac transformer is properly grounded. Failure to
do so may result in damage to equipment and/or minor or moderate
injury.
IMPORTANT
Do not share 24 Vac between controllers.
All wiring must comply with National Electrical Code and local codes.
The ac power connections are in the top left corner of the Tracer ZN517
unitary controller (see Figure 32).
Figure 32. Connecting ac power wires to the controller
24 Vac unit
transformer
If you are providing a new transformer for power, use a UL-listed Class 2
power transformer supplying a nominal 24 Vac (19–30 Vac). The transformer must be sized to provide adequate power to the Tracer ZN517 unitary controller (9 VA) and output devices, including relays and valve
actuators, to a maximum of 12 VA per output utilized. The Tracer ZN517
may be powered by an existing transformer integral to the controlled heat
pump, provided the transformer has adequate power available and adequate grounding is observed.
H
N
CNT-SVX12C-EN85
Page 98
Chapter 11 General wiring information
Communication-link wiring and
addressing
The Tracer ZN517 unitary controller communicates with a BAS and with
other LonTalk controllers via a LonTalk communication link. For instructions on LonTalk communication wiring and addressing, follow the
requirements given in the Tracer Summit Hardware and Software Instal-
lation guide (BMTX-SVN01A-EN) or the Tracker Building Automation
System Hardware Installation guide (BMTK-SVN01D-EN) or another
BAS installation manual.
86CNT-SVX12C-EN
Page 99
Chapter 12
Troubleshooting
This chapter outlines some general troubleshooting steps that should be
performed if there is a problem with the operation of the equipment controlled by the Tracer ZN517 unitary controller. This chapter describes
some common problems; however, it cannot describe every possible
problem.
If you encounter operational problems with the Tracer ZN517, you must
first perform initial troubleshooting steps; see “Initial troubleshooting” on
page 88. After this procedure, consult the tables in “Diagnosing operational problems” on page 88 for further troubleshooting assistance.
CNT-SVX12C-EN87
Page 100
Chapter 12 Troubleshooting
Initial troubleshooting
Always perform the initial troubleshooting steps listed in Table 29 before
moving on to the specific area of trouble. Perform the steps in the order
they are listed.
Table 29. Initial troubleshooting steps
Step numberActionProbable cause
Step 1Look at the red Service LED. If it is flashing once per second, the controller is
not executing the application software because the network connections and
addressing have been removed. For a complete explanation of this LED’s
behavior, see Table 25 on page 76.
Use the Rover service tool or a BAS to restore normal operation. See EMTXSVX01B-EN for more information.
Step 2Look at the green Status LED. It should be on continuously during normal
operation. A blinking Status LED indicates the Tracer ZN517 is performing a
manual output test. For a complete explanation of this LED’s behavior, see
Table 26 on page 77.
Step 3Take your meter (set to measure ac voltage) and measure the voltage across
the ac-power terminals on the Tracer ZN517 (with ac wires connected). See
Figure 32 on page 85.
If you see approximately 24 V (21–27 V) on those terminals, the board is
receiving adequate input power and you likely have a Tracer ZN517 circuit
board problem.
Step 4Disconnect the ac wires from the input power terminals. Take your meter (set
to measure ac voltage) and measure the voltage across the ac wires. If you
see approximately 0 V, the board is not receiving the power it needs to run.
Step 5Reconnect the ac wires to the input power terminals. Perform the manual
output test, which is described in “Manual output test” on page 74.
If the outputs on the controller do not behave as described in the manual
output test (page 74), then you are likely to have a Tracer ZN517 circuit board
problem.
Tracer ZN517 is
not configured
Tracer ZN517 is in
manual output test
mode
Tracer ZN517 circuit board problem
Input power problem
Tracer ZN517 circuit board problem
Diagnosing operational problems
After you have performed the initial troubleshooting steps, refer to the
succeeding tables in this chapter to further diagnose the following operational problems:
•Fan does not energize (Table 30 on page 89)
•Heat does not energize (Table 31 on page 90)
•An outdoor air damper stays closed (Table 32 on page 90)
•An outdoor air damper stays open (Table 33 on page 91)
88CNT-SVX12C-EN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.