Tracer ZN517 Unitary Controller Installation and Operation
This guide and the information in it are the property of American Standard Inc. and may not be used or reproduced in whole or in part,
without the written permission of American Standard Inc. Trane, a business of American Standard, Inc., has a policy of continuous
product and product data improvement and reserves the right to change design and specification without notice.
Although Trane has tested the hardware and software described in this guide, no guarantee is offered that the hardware and software
are error free.
Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trane may have patents or patent applications covering items in this publication. By providing this document, Trane does not imply
giving license to these patents.
The following are trademarks or registered trademarks of Trane: Trane, Tracer, Tracker, Rover.
®
™
The following are trademarks or registered trademarks of their respective companies or organizations: LonTalk and Neuron
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully:
WARNING
Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment damage or property damage.
The following format and symbol conventions appear at appropriate sections throughout this manual:
IMPORTANT
Alerts installer, servicer, or operator to potential actions that could cause the product or system to
operate improperly but will not likely result in potential for damage.
Note:
A note may be used to make the reader aware of useful information, to clarify a point, or to describe
options or alternatives.
◆This symbol precedes a procedure that consists of only a single step.
This guide provides installation and configuration information for the
Tracer ZN517 unitary controller, as well as a description of its operations.
The overview includes a product description, specifications, and descriptions of ancillary products that may be necessary.
Product description
The Tracer ZN517 is an application-specific controller that provides
direct digital, zone temperature control. The controller can operate as a
stand-alone device or as part of a building automation system (BAS).
Communication between the controller and a BAS occurs via a LonTalk
communication link, which is based on the LonTalk
The controller is designed to be field-installed and is sent from the factory
configured for a 2-heat/2-cool application. You can change this configuration using the DIP switches located on the circuit board. The Tracer
ZN517 supports the following three configurations:
®
protocol.
•2-heat/2-cool with optional economizer control
•4-cool with optional economizer control
•Heat pump with optional economizer control
Features such as discharge air tempering and demand control ventilation
can be configured using the Rover service tool.
Note:
For information about using the Rover service tool, see the
Rover Operation and Programming guide (EMTX-SVX01BEN).
Dimensions
Plastic-cover model dimensions
For complete dimensional drawing, see Figure 1 on page 3.
•Height: 5.375 in. (137 mm)
•Width: 6.875 in. (175 mm)
•Depth: 2 in. (51 mm)
CNT-SVX12C-EN1
Chapter 1 Overview and specifications
Metal-cover model dimensions
For complete dimensional drawing, see Figure 2 on page 3.
•Height: 9.0 in (25 mm)
•Width: 10.37in. (263 mm)
•Depth: 2.25 in. (58 mm)
Clearances
For wiring, ventilation, and maintenance, provide the following minimum
clearances for the module:
Plastic-cover model
(see Figure 1 on page 3)
•Front: 4.0 in. (102 mm)
•Each side: 1.0 in. (25 mm)
•Top and bottom: 4.0 in. (102 mm)
Metal-cover model
(see Figure 2 on page 3)
•Front: 24.0 in. (610 mm)
•Each side: 2.0 in. (51 mm)
•Top and bottom: 1.0 in. (25 mm)
Power
The transformer must meet the following minimum requirements for the
controller and its output devices:
•19–30 Vac (24 Vac nominal)
•50/60 Hz
•9 VA and 12 VA maximum per binary output utilized
Operating environment
Operate a Tracer ZN517 unitary controller in an indoor environment that
meets the following requirements:
•Temperature: From –40°F to 160°F (–40°C to 70°C)
•Relative humidity: From 5–90%, noncondensing
2CNT-SVX12C-EN
Figure 1. Plastic-cover model dimensions and clearances
1 in.
(25 mm)
Operating environment
4 in
(102 mm)
5.625 in
(143 mm)
5.375 in (137 mm)
Clearances
Dimensions
6.31 in.
(160 mm)
Figure 2. Metal-cover model dimensions and clearances
1 in.
(25 mm)
4 in
(102 mm)
1. 875 in.
(48 mm)
4 in
(102 mm)
6.5 in.
(165 mm)
6.875 in
(175 mm)
2 in. (51 mm)
9 in.
(229 mm)
2 in.
(51 mm)
24 in.
(610 mm)
Clearances
Dimensions
CNT-SVX12C-EN3
10.37 in.
(263 mm)
width with cover
1 in.
(25 mm)
2 in.
(51 mm)
1 in.
(25 mm)
2.25 in.
(58 mm)
7 in.
(178 mm)
0.28 in.
(7 mm)
9 in.
(229 mm)
10. 25 in .
(260 mm)
width without cover
Chapter 1 Overview and specifications
Storage environment
If you are storing a Tracer ZN517 unitary controller for a substantial
amount of time, store it in an indoor environment that meets the
following requirements:
•Temperature: From –40° to 185°F (–40° to 85°C)
•Relative humidity: From 5–95%, noncondensing
Agency listing/compliance
CE—Immunity: EN50082-2:1995
CE—Emissions: EN61000-3-2:1995
UL and C-UL 916 listed:
Energy management equipment
UL 94-5V (UL flammability rating for plenum use)
EN61000-6-2:1999
EN61000-3-3:1995
EN50081-1:1992 (CISPR 22)
EN55011:1998, Class B
FCC Part 15, Class A, CFR 47
Factory default temperature setpoints
The Tracer ZN517 unitary controller relies on a number of temperature
setpoints to control HVAC equipment. Table 1 gives the factory defaults
for these setpoints, which can all be edited with the Rover service tool or a
BAS.
Table 1. Factory default temperature setpoints
Setpoints
Default setpoints
Occupied cooling74.0°F (23.3°C)
Occupied standby cooling78.0°F (25.6°C)
Unoccupied cooling85.0°F (29.4°C)
Occupied heating71.0°F (21.7°C)
Occupied standby heating67.0°F (19.4°C)
Unoccupied heating60.0°F (15.6°C)
Occupied setpoint limits
Cooling setpoint high limit110.0°F (43.3°C)
Cooling setpoint low limit40.0°F (44.4°C)
Factory defaults
°F (°C)
4CNT-SVX12C-EN
Factory default temperature setpoints
Table 1. Factory default temperature setpoints
Setpoints
Heating setpoint high limit105.0°F (40.6°C)
Heating setpoint low limit40.0°F (44.4°C)
Discharge air limits
High limit170.6°F (77.0°C)
Low limit37.4°F (3.0°C)
Control point high limit150.8°F (66.0°C)
Control point low limit44.6°F (7.0°C)
Outdoor air damper setup
Economizer enable temperature53.6°F (12.0°C)
Factory defaults
°F (°C)
CNT-SVX12C-EN5
Chapter 1 Overview and specifications
Additional components
The following components are required for proper equipment operation.
They are not included with the Tracer ZN517 unitary controller. Additional components may also be required besides those described in this
section, depending on your application.
Power transformer
A transformer providing 24 Vac is required to power the Tracer ZN517
unitary controller and associated output relays and valve and damper
actuators (see “AC power wiring” on page 85).
Zone temperature sensors
Table 2 shows some of the Trane zone temperature sensors that are supported by the Tracer ZN517 unitary controller. Contact your Trane sales
office for information about other compatible zone sensors.
Table 2. Trane zone temperature sensor options
Zone
BAS order
number
4190 1086xxx
4190 1087x
4190 1088xxxx
4190 1089xx
4190 1090xxxxx
4190 1094xxx
4190 7015
(stainless
steel wall
plate)
Setpoint
thumbwheel
Temperature
sensor
x
Timed override
buttons
Comm
jack
OnCancel
Discharge air temperature sensors
Discharge air temperature sensors must be Trane 10 kΩ (at 25°C) thermistors. The discharge air temperature (DAT) input may use a sealed
temperature sensor (part number 4190 1100) or a duct/immersion temperature sensor (part number 4190 1103).
Damper actuators (optional)
Actuators cannot exceed 12 VA draw at 24 Vac. Use actuators with on/off
action and spring return (to normally open or closed position), based on
the desired default position.
6CNT-SVX12C-EN
Chapter 2
Mounting the controller
This chapter gives recommendations and requirements for mounting the
Tracer ZN517 unitary controller.
Location recommendations
For rooftop and heat pump applications, the controller can be mounted
inside the unit or at a convenient location inside the building. Trane
recommends locating the Tracer ZN517 unitary controller:
•Near the controlled piece of equipment to reduce wiring costs
•Where it is easily accessible for service personnel
•Where public access is restricted to minimize the possibility of tam-
pering or vandalism
CNT-SVX12C-EN7
Chapter 2 Mounting the controller
Mounting recommendations
Mounting recommendations are as follows:
IMPORTANT
Mount the Tracer ZN517 unitary controller with the cover on to avoid
the possibility of damaging the circuit board during installation.
•Mount the controller in any direction, other than with the front of the
cover facing downward.
•Mount using the two
(see Figure 3). Mounting fasteners are not included.
•Attach the controller securely so it can withstand vibrations of associ-
ated HVAC equipment.
•When the controller is mounted in a small enclosed compartment,
complete all wiring connections before securing the controller in the
compartment.
Figure 3. Mounting the Tracer ZN517 unitary controller
3
/16in. (4.8 mm) radius mounting holes provided
8CNT-SVX12C-EN
Chapter 3
Applications for the
2-heat/2-cool configuration
This chapter provides information for wiring input and output terminals
and setting DIP switches for typical 2-heat/2-cool applications. The function of inputs and outputs is also defined for these applications.
The types of 2-heat/2-cool applications supported by the Tracer ZN517
unitary controller are:
•Rooftop units with or without economizers
•Split systems with or without economizers
CNT-SVX12C-EN9
Chapter 3 Applications for the 2-heat/2-cool configuration
Wiring requirements and options
Table 3 shows required controller inputs for minimal proper operation of
all 2-heat/2-cool applications.
Table 3. Required controller inputs for all 2-heat/2-cool applications
FunctionInput source
24 Vac powerTerminals: GND, 24 V“AC power wiring” on
Zone temperatureTerminals: ZN, GND
or communicated
For more information,
see:
page 85
“ZN: Zone temperature” on page 18
Table 4 shows optional controller inputs and outputs for specific
applications.
Table 4. Optional controller inputs and outputs for specific applications
* In order to use this function, the economizing function must be enabled.
Input: DAT“Discharge air tem-
Input:
AI1 (CO
sensor)
2
For more information,
see:
“Economizing” on
page 23
pering” on page 24
“Demand control
ventilation” on
page 24
trol” on page 20
Figure 4 on page 11 shows a wiring diagram for the Tracer ZN517 that
includes all required and all optional components for 2-heat/2-cool applications.
10CNT-SVX12C-EN
ZONE SENSOR
ANALOG INPUTS
HVAC UNIT
BINARY INPUTS
BINARY OUTPUT
AC OUT
AC POWER
24 Vac
Wiring requirements and options
Figure 4. Wiring diagram for 2-heat/2-cool applications
Powe r*
Tr i- s t at e
modulating
economizer
(optional)
Common
H
N
24V
GND
24V
OPN
ECONOMIZERAC OUT
24V
GND
AC POWER
GND
CLS
R
RhRc1G4325NO 5COM
Fan
G
Y1
HVAC UNIT
Compressor 1 contactor
Compressor 2 contactor
Heat stage 1
Heat stage 2
Y2
W1 W2
Generic binary output (optional)
BINARY OUTPUT
STATUS5NC
LED
SERVICE
LED
PIN
LonTalk
In
Out
*Terminals Rc and Rh are provided as
inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh
for heat and Rc for cooling. If combined, use only Rc (see “HVAC unit
electrical circuit wiring” on page 82).
COMM5
A BBA
Occupancy
or generic
(optional)
BINARY INPUTS
-BI2-SET-BI1-ZN
ANALOG INPUTS
AI1-DAT-
+20GND
GND
+
Typical 3-wire
sensor
(optional)
(optional)
Fan status
(default:
normally closed
Dry contacts
only
closed = no flow
open = flow)
or generic
_
-AI2-
Discharge air
temperature
Outdoor air
temperature
(optional)
ZONE SENSOR
GND
COMM5
LED
LonTalk
1
2
3
4
5
On
Cancel
CNT-SVX12C-EN11
Chapter 3 Applications for the 2-heat/2-cool configuration
DIP switch settings
Set the DIP switches on the circuit board for the 2-heat/2-cool configuration. The correct settings are shown in Figure 5.
Figure 5. DIP switch settings for the 2-heat/2-cool configuration
ON DIP
1234
ON DIP
1234
ON DIP
1234
2-heat/2-cool
without economizer
2-heat/2-cool with
economizer
12CNT-SVX12C-EN
Binary outputs for 2-heat/2-cool applications
Binary outputs for 2-heat/2-cool
applications
This configuration supports rooftop units and split systems applications
that have the following components:
•Economizer
•Supply fan
•Cool 1
•Cool 2
•Heat 1
•Heat 2
•Exhaust
The Tracer ZN517 controller has eight binary outputs. Each binary output is a relay with a rating of 12 VA. Table 5 describes the function of
each output for 2-heat/2-cool applications.
Table 5. Binary outputs for 2-heat/2-cool applications
Use the Rover service tool to configure binary output 5 (5NO/5COM/5NC)
in one of the following ways. It is the only output that can be configured
as a generic binary output.
•Not used.
•Exhaust fan: Will energize when the economizer outside air damper
position is greater than the user-defined control point.
•Occupancy: Will energize when the Tracer ZN517 is in the occupied
mode.
•Generic: Can be monitored only by a BAS and has no direct effect on
Tracer ZN517 operation.
CNT-SVX12C-EN13
Chapter 3 Applications for the 2-heat/2-cool configuration
Overriding binary outputs
Use the manual output test to manually control the outputs in a defined
sequence. For more information about the manual output test, see “Manual output test” on page 74.
Binary inputs for 2-heat/2-cool
applications
The Tracer ZN517 unitary controller has two binary inputs. Each binary
input associates an input signal of 0 Vac with open contacts and 24 Vac
with closed contacts. Table 6 gives the function of each binary input for
2 heat/2 cool applications. Each function is explained in the succeeding
paragraphs. For an explanation of the diagnostics generated by each
binary input, see “Table of diagnostics” on page 79. For more information
about how the controller operates, see Chapter 4, “Sequence of operations
for the 2-heat/2-cool configuration”.”
Table 6. Binary inputs for 2-heat/2-cool applications
Binary input
terminal label
BI1Occupancy or generic
BI2Fan status
Function
BI1: Occupancy or generic
The function of the occupancy input is to save energy by increasing the
range of zone setpoints when the zone is unoccupied. BI1 is used for two
occupancy-related functions. For stand-alone controllers, this binary
input can be hard-wired to a binary switch, clock, or occupancy sensor to
determine the occupancy mode—either occupied or unoccupied. For controllers receiving a BAS-communicated occupancy request, the function of
BI1 is to change the mode from occupied to occupied standby. (For more
information on occupancy-related functions, see “Occupancy modes” on
page 20.) An occupancy sensor with a binary output may be used.
BI1 is the only input that can be configured as a generic binary input.
When configured as a generic binary input, it can be monitored only by a
BAS, and has no direct effect on Tracer ZN517 operation.
BI2: Fan status
The fan status input provides feedback to the controller regarding the
fan’s operating status. If BI2 is wired to a fan status switch and the input
indicates that the fan is not operating when the controller has the fan
controlled to on, the controller will generate a Local Fan Switch Failure
diagnostic. (For more information, see “Fan status” on page 25.)
14CNT-SVX12C-EN
Analog inputs for 2-heat/2-cool applications
Analog inputs for 2-heat/2-cool
applications
The Tracer ZN517 controller has five analog inputs. Table 7 describes the
function of each input for 2-heat/2-cool applications. Each function is
explained in the succeeding paragraphs. For an explanation of the diagnostics generated by each analog input, see “Table of diagnostics” on
page 79. For more information about how the controller operates, see
Chapter 4, “Sequence of operations for the 2-heat/2-cool configuration”.
Table 7. Analog inputs for 2-heat/2-cool applications
Analog input
terminal label
AI1Universal analog input
AI2Outdoor air temperature
DATDischarge air temperature
ZNZone temperature (required)
SETTemperature setpoint
Note:
Use a GND terminal as the common ground for all zone sensor
analog inputs. See Figure 4 on page 11.
Function
AI1: Universal 4–20 mA
The AI1 analog input can be configured in one of the three ways shown in
Table 8.
Table 8. AI1 configuration options and associated measurement ranges
ConfigurationMeasurement range
Generic 4–20 mA input0–100%
(4 mA=0%; 20 mA=100%)
CO2 measurement0–2000 ppm
(4 mA=0 ppm; 20 mA=2000 ppm)
Relative humidity (RH) measurement0–100%
(4 mA=0% RH; 20 mA=100% RH)
CNT-SVX12C-EN15
If this input is not needed for an application, configure it as Not Used.
This disables the generation of diagnostics.
Note:
AI1 is polarity sensitive.
For the generic input configuration, a 4–20 mA sensor must be hardwired to the AI1 terminal. (Wiring is dependent on the specific applica-
Chapter 3 Applications for the 2-heat/2-cool configuration
tion.) The sensor communicates a value of 0–100% to the BAS. This configuration has no direct effect on Tracer ZN517 operation.
For the CO
measurement configuration, a 4–20 mA sensor must be hard-
2
wired to the AI1 terminal as shown in Figure 6. The sensor will transmit
a 0–2000 ppm value to the BAS. This configuration has no direct effect on
Tracer ZN517 operation. If a valid value is established and then is no
longer present, the controller generates a CO
Sensor Failure diagnostic.
2
Figure 6. AI1 terminal wiring: CO
Tracer ZN517
CO
sensor
2
(Trane part number:
4190 4100 or 4190 4101)
measurement
2
24 Vac
{{
24 Vac
GND
+20GND
Out
AI1
For the RH measurement configuration, a hard-wired 4–20 mA zone
humidity sensor (see Figure 7) must provide a value to the controller. If a
valid hard-wired or communicated relative humidity value is established
and then is no longer present, the controller generates an RH Sensor Failure diagnostic and disables the dehumidification function. The RH sensor
is used only to provide a valid humidity reading to a BAS; it does not
affect the operation of the Tracer ZN517.
Figure 7. AI1 terminal wiring: RH measurement
Figure Note:
The +20 terminal provides 20 ±2 Vdc that is used to power a Trane RH sensor (part
numbers 4190 1109, 4190 7011, 4190 7012, 4190 7014).
16CNT-SVX12C-EN
+20GND
+
AI1
–
Tracer ZN517
RH sensor
Analog inputs for 2-heat/2-cool applications
AI2: Outdoor air temperature or generic temperature
The AI2 analog input can functions as either:
•An outdoor air temperature input
•A generic temperature input
If AI2 is configured as the local (hard-wired) outdoor air temperature
input, the controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input AI2. An outdoor air temperature value communicated by means of a LonTalk link can also be used for
controllers operating on a BAS. If both hard-wired and communicated
outdoor air temperature values are present, the controller uses the communicated value.
If you set DIP switch 3 to
on page 12), you automatically configure AI2 as an outdoor air temperature input. Economizing (free cooling) is a function whereby outdoor air is
used as a source of cooling before hydronic or DX cooling is used. The
Tracer ZN517 uses the outdoor air temperature value to determine
whether economizing is feasible. Economizing is not possible without a
valid outdoor air temperature. (For more information, see “Economizing”
on page 23.)
ON for economizing (see “DIP switch settings”
If AI2 is configured as a generic temperature input, it can be monitored
by a BAS. The controller receives the temperature as a resistance signal
from a 10 kΩ thermistor wired to analog input AI2. The generic temperature input can be used with any Trane 10 kΩ thermistor. The thermistor
can be placed in any location and has no effect on the operation of the controller. If you set DIP switch 3 to
page 12), you automatically configure AI2 as a generic temperature input.
Note:
AI2 is not polarity sensitive; you can connect either terminal to
either sensor lead.
OFF (see “DIP switch settings” on
DAT: Discharge air temperature
The DAT analog input functions as the local discharge air temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor wired to analog input DAT. The thermistor is typically
located downstream from all unit heating and cooling coils at the unit discharge area.
Trane recommends the use of a discharge air temperature sensor to utilize the cascade control function (see “Cascade zone control” on page 20).
Cascade control is a more accurate method of temperature control. If no
discharge air temperature sensor is used, the controller will default to
control based solely on the zone temperature (see “Simplified zone control” on page 20).
CNT-SVX12C-EN17
Note:
DAT is not polarity sensitive; you can connect either terminal
to either sensor lead.
Chapter 3 Applications for the 2-heat/2-cool configuration
ZN: Zone temperature
The ZN analog input functions as the local (hard-wired) zone temperature
input. The controller receives the temperature as a resistance signal from
a 10 kΩ thermistor in a standard Trane zone sensor wired to analog input
ZN. A communicated zone temperature value via the LonTalk communications link can also be used for controllers operating on a BAS. When
both a hard-wired and communicated zone temperature value is present,
the controller uses the communicated value. If neither a hard-wired nor a
communicated zone temperature value is present, the controller generates a Space Temperature Failure diagnostic.
The ZN analog input is also used to communicate timed override requests
and cancel requests to the controller for applications utilizing a Trane
zone sensor with the ON and CANCEL button option.
SET: Temperature setpoint
The SET analog input functions as the local (hard-wired) temperature
setpoint input for applications utilizing a Trane zone sensor with a temperature setpoint thumbwheel. Use the Rover service tool or a BAS to
enable or disable the local setpoint input. A communicated setpoint value
via the LonTalk communications link can also be used for controllers
operating on a BAS. If both a hard-wired and a communicated setpoint
value are present, the controller uses the communicated value. If neither
a hard-wired nor a communicated setpoint value is present, the controller
uses the stored default setpoints (configurable using the Rover service
tool or a BAS). If a valid hard-wired or communicated setpoint value is
established and then is no longer present, the controller generates a Local
Space Setpoint Failure diagnostic.
18CNT-SVX12C-EN
Loading...
+ 81 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.