Trane Tracer VV550, Tracer VV551 Installation Manual

Tracer™ Controls
Tracer VV550/551 VAV Controllers
October 2005
CNT-PRC003-EN
®
Introduction
Tracer VV550 and Tracer VV551 variable air volume (VAV) controllers provide single-duct digital control for VAV boxes. They support the following VAV control sequences:
• Space temperature control
• Flow tracking
• Ventilation flow control
The Tracer VV550 VAV controller is available factory-installed on Trane VariTrane VAV boxes (Figure 1). The Tracer VV551 VAV controller is available for field installation for a variety of VAV applications (Figure 2).
Figure 1. Tracer VV550 controller
Figure 2. Tracer VV551 controller (uses same board as Tracer VV550)
Because the Tracer VV550 and Tracer VV551 VAV controllers use the same logic controller, both offer the same wide range of application and control flexibility. The Tracer VV551 VAV controller includes additional labor­saving packaging features for field­installed applications.
Tracer VV550/551 VAV controllers can operate as part of a Trane Integrated Comfort™ system (ICS), as part of a building management system from another manufacturer, or as a standalone device.
When it is part of a Trane ICS, a Tracer VV550/551 VAV controller enables the building automation system (BAS) to perform functions such as scheduling, trending, alarming, remote communications, and VAV air system (VAS) coordination. The controller communicates with a Tracer Summit BAS over the LonTalk
®
communications link. The controller can also communicate with other building control systems that are compliant with the LonMark® Space Comfort Controller (SCC) profile.
Tracer VV550/551 VAV controllers can be configured using the Rover service tool. They have the following inputs and outputs (Figure 3 on page 6):
Analog inputs:
• Space temperature (10 kΩ thermistor)
• Space setpoint (1 kΩ potentiometer)
• Primary/discharge air temperature
(10 k thermistor)
• Primary air flow
Binary inputs:
• Occupancy or generic
Binary outputs:
• Air valve close
• Air valve open
•Heat 1
•Heat 2
• Heat 3 or fan On/Off
© 2005 American Standard All rights reserved
™ ® The following are trademarks or registered trademarks of their respective compa­nies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; LonMark, LonTalk, and LonWorks of the Echelon Corporation.
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and benefits . . . . . . . . . . . . . . . . 4
Automatic calibration. . . . . . . . . . . . . . . . . . . . . . . . . 4
Ventilation flexibility . . . . . . . . . . . . . . . . . . . . . . . . . 4
Flow tracking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ventilation flow control with tempering . . . . . . . . . 4
Local versus remote reheat flexibility . . . . . . . . . . . 4
Occupied and unoccupied operation . . . . . . . . . . . . 4
Timed override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Service pin from the Trane zone sensor . . . . . . . . . 4
Auto-commissioning sequence . . . . . . . . . . . . . . . . 5
Manual test function . . . . . . . . . . . . . . . . . . . . . . . . . 5
Drive minimum and maximum from zone sensor . 5
Trane controller compatibility. . . . . . . . . . . . . . . . . . 5
Interoperability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
®
Wiring diagram for Tracer VV550/551 VAV
controllers. . . . . . . . . . . . . . . . . . . . . . . . . . 6
Network architecture . . . . . . . . . . . . . . . . . 7
Zone sensor options . . . . . . . . . . . . . . . . . 8
Dimensions and specifications . . . . . . . . . 9
Power requirements. . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating environment . . . . . . . . . . . . . . . . . . . . . . . 9
Storage environment . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Weight with enclosure (Tracer VV551) . . . . . . . . . . . 9
Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Binary input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Binary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Agency listings/compliance. . . . . . . . . . . . . . . . . . . . 9
Data lists . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CNT-PRC003-EN 3
®
Features and benefits
Automatic calibration
Tracer VV550/551 VAV controllers automatically calibrate the flow transducer each time the box transitions to the unoccupied state. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which case the Tracer Summit building automation system can be used to initiate/schedule calibration.
Ventilation flexibility
Tracer VV550/551 VAV controllers can manage ventilation in the following ways:
• Fixed occupancy ventilation setpoint
• Scheduled (or otherwise calculated) ventilation setpoint
• Occupancy sensor to switch between normal and reduced ventilation
•CO
sensor for demand-controlled
2
ventilation
This flexibility gives owners and facility managers an option to simply select one of several effective solutions for managing ventilation.
Flow tracking
Tracer VV550/551 VAV controllers can easily be applied in flow tracking applications. In a flow tracking application, supply and exhaust boxes are paired together for the purpose of maintaining either positive or negative space static pressure. This feature allows the installer to quickly define the relationship of the supply and exhaust air boxes without the need for custom programming.
Ventilation flow control with tempering
Tracer VV550/551 VAV controllers have been designed for ventilation flow control applications. These applications pair a fresh air unit or self-contained unit with ventilation boxes to provide fresh (tempered) air to a floor/area. With this feature, the installer can quickly configure the flow control boxes and set up the system without the need for custom programming.
Local versus remote reheat flexibility
Tracer VV550/551 VAV controllers can be configured to have local and/or remote heat. This configuration flexibility enables the controllers to be applied across a broad range of VAV applications.
Occupied and unoccupied operation
The occupancy input on a Tracer VV550/ 551 VAV controller works with a motion (occupancy) sensor or a time clock to determine the occupancy mode. An occupancy request can also be communicated from a building automation system to determine the mode of the controller. Whether stand­alone or combined with a communicated occupancy request, a Tracer VV550/551 controller can be used with an occupancy sensor to save energy whenever a space is vacant.
Timed override
The timed override function for after­hours operation allows users to request unit operation by the touch of a button on the unit zone sensor. Additionally, users can press the CANCEL button at any time to place the unit back into unoccupied mode. This occupancy feature minimizes energy use by running the system only as scheduled or as demanded after hours.
Service pin from the Trane zone sensor
Certain installation scenarios require access to the SERVICE button on the controller. Access to this button typically requires a ladder or a lift. The Tracer VV550/551 VAV controller allows a technician to replicate pressing the SERVICE button by pressing the zone sensor ON button. This feature eliminates the need for accessing the SERVICE button, saving the technician time and energy.
Loading...
+ 8 hidden pages