Trane Tracer VV550, Tracer VV551 Installation Manual

Page 1
Tracer™ Controls
Tracer VV550/551 VAV Controllers
October 2005
CNT-PRC003-EN
Page 2
®
Introduction
Tracer VV550 and Tracer VV551 variable air volume (VAV) controllers provide single-duct digital control for VAV boxes. They support the following VAV control sequences:
• Space temperature control
• Flow tracking
• Ventilation flow control
The Tracer VV550 VAV controller is available factory-installed on Trane VariTrane VAV boxes (Figure 1). The Tracer VV551 VAV controller is available for field installation for a variety of VAV applications (Figure 2).
Figure 1. Tracer VV550 controller
Figure 2. Tracer VV551 controller (uses same board as Tracer VV550)
Because the Tracer VV550 and Tracer VV551 VAV controllers use the same logic controller, both offer the same wide range of application and control flexibility. The Tracer VV551 VAV controller includes additional labor­saving packaging features for field­installed applications.
Tracer VV550/551 VAV controllers can operate as part of a Trane Integrated Comfort™ system (ICS), as part of a building management system from another manufacturer, or as a standalone device.
When it is part of a Trane ICS, a Tracer VV550/551 VAV controller enables the building automation system (BAS) to perform functions such as scheduling, trending, alarming, remote communications, and VAV air system (VAS) coordination. The controller communicates with a Tracer Summit BAS over the LonTalk
®
communications link. The controller can also communicate with other building control systems that are compliant with the LonMark® Space Comfort Controller (SCC) profile.
Tracer VV550/551 VAV controllers can be configured using the Rover service tool. They have the following inputs and outputs (Figure 3 on page 6):
Analog inputs:
• Space temperature (10 kΩ thermistor)
• Space setpoint (1 kΩ potentiometer)
• Primary/discharge air temperature
(10 k thermistor)
• Primary air flow
Binary inputs:
• Occupancy or generic
Binary outputs:
• Air valve close
• Air valve open
•Heat 1
•Heat 2
• Heat 3 or fan On/Off
© 2005 American Standard All rights reserved
™ ® The following are trademarks or registered trademarks of their respective compa­nies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; LonMark, LonTalk, and LonWorks of the Echelon Corporation.
Page 3
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and benefits . . . . . . . . . . . . . . . . 4
Automatic calibration. . . . . . . . . . . . . . . . . . . . . . . . . 4
Ventilation flexibility . . . . . . . . . . . . . . . . . . . . . . . . . 4
Flow tracking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ventilation flow control with tempering . . . . . . . . . 4
Local versus remote reheat flexibility . . . . . . . . . . . 4
Occupied and unoccupied operation . . . . . . . . . . . . 4
Timed override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Service pin from the Trane zone sensor . . . . . . . . . 4
Auto-commissioning sequence . . . . . . . . . . . . . . . . 5
Manual test function . . . . . . . . . . . . . . . . . . . . . . . . . 5
Drive minimum and maximum from zone sensor . 5
Trane controller compatibility. . . . . . . . . . . . . . . . . . 5
Interoperability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
®
Wiring diagram for Tracer VV550/551 VAV
controllers. . . . . . . . . . . . . . . . . . . . . . . . . . 6
Network architecture . . . . . . . . . . . . . . . . . 7
Zone sensor options . . . . . . . . . . . . . . . . . 8
Dimensions and specifications . . . . . . . . . 9
Power requirements. . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating environment . . . . . . . . . . . . . . . . . . . . . . . 9
Storage environment . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Weight with enclosure (Tracer VV551) . . . . . . . . . . . 9
Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Binary input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Binary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Agency listings/compliance. . . . . . . . . . . . . . . . . . . . 9
Data lists . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CNT-PRC003-EN 3
Page 4
®
Features and benefits
Automatic calibration
Tracer VV550/551 VAV controllers automatically calibrate the flow transducer each time the box transitions to the unoccupied state. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which case the Tracer Summit building automation system can be used to initiate/schedule calibration.
Ventilation flexibility
Tracer VV550/551 VAV controllers can manage ventilation in the following ways:
• Fixed occupancy ventilation setpoint
• Scheduled (or otherwise calculated) ventilation setpoint
• Occupancy sensor to switch between normal and reduced ventilation
•CO
sensor for demand-controlled
2
ventilation
This flexibility gives owners and facility managers an option to simply select one of several effective solutions for managing ventilation.
Flow tracking
Tracer VV550/551 VAV controllers can easily be applied in flow tracking applications. In a flow tracking application, supply and exhaust boxes are paired together for the purpose of maintaining either positive or negative space static pressure. This feature allows the installer to quickly define the relationship of the supply and exhaust air boxes without the need for custom programming.
Ventilation flow control with tempering
Tracer VV550/551 VAV controllers have been designed for ventilation flow control applications. These applications pair a fresh air unit or self-contained unit with ventilation boxes to provide fresh (tempered) air to a floor/area. With this feature, the installer can quickly configure the flow control boxes and set up the system without the need for custom programming.
Local versus remote reheat flexibility
Tracer VV550/551 VAV controllers can be configured to have local and/or remote heat. This configuration flexibility enables the controllers to be applied across a broad range of VAV applications.
Occupied and unoccupied operation
The occupancy input on a Tracer VV550/ 551 VAV controller works with a motion (occupancy) sensor or a time clock to determine the occupancy mode. An occupancy request can also be communicated from a building automation system to determine the mode of the controller. Whether stand­alone or combined with a communicated occupancy request, a Tracer VV550/551 controller can be used with an occupancy sensor to save energy whenever a space is vacant.
Timed override
The timed override function for after­hours operation allows users to request unit operation by the touch of a button on the unit zone sensor. Additionally, users can press the CANCEL button at any time to place the unit back into unoccupied mode. This occupancy feature minimizes energy use by running the system only as scheduled or as demanded after hours.
Service pin from the Trane zone sensor
Certain installation scenarios require access to the SERVICE button on the controller. Access to this button typically requires a ladder or a lift. The Tracer VV550/551 VAV controller allows a technician to replicate pressing the SERVICE button by pressing the zone sensor ON button. This feature eliminates the need for accessing the SERVICE button, saving the technician time and energy.
Page 5
®
Auto-commissioning sequence
Tracer VV550/551 VAV controllers provide an automatic commissioning sequence. With a discharge air temperature sensor installed, this feature exercises the air valve, fan, and heat in the box and records the discharge air temperature before and after the action. This allows the installer to easily checkout the operation of the box and commission by exception. The data from this test is retained in the controller for immediate reports or retrieval at a later date (for comparison purposes).
Manual test function
A Tracer VV550/551 VAV controller includes a manual test button, which enables a technician to easily exercise the outputs of the controller. On consecutive button presses, the controller steps through a predefined sequence that exercises all of the controller outputs.
Drive minimum and maximum from zone sensor
When applied with a Trane zone sensor module that includes a thumbwheel setpoint, a Tracer VAV VV550/551 controller can easily be overridden to minimum and maximum flow. By simply turning the thumbwheel to , the controller drives the air valve to the minimum cooling flow setpoint. Similarly, turning the thumbwheel to ∗∗ drives the air valve to the maximum cooling flow setpoint. This simple override feature is most useful during the checkout and balancing phases of a project.
Trane controller compatibility
Tracer VV550/551 VAV controllers are compatible with the latest generation of Trane control products. The controllers communicate over a LonTalk communications link. This allows Tracer VV550/551 VAV controllers to exist on the same communication wire as other Trane controllers and to share data with them as required.
®
Interoperability
Tracer VV550/551 VAV controllers are designed with LonWorks and are LonMark the guidelines of the LonMark Comfort Controller (SCC) profile. As such, the Tracer VV550/551 controllers enable control system integration flexibility.
®
®
technology
certified. They follow
®
Space
Wiring diagram
See Figure 3 on page 6.
Wiring diagram 2
CNT-PRC003-EN 5
Page 6
®
Figure 3. Tracer VV550/551 wiring diagram
24V
GND
Wiring diagram for Tracer VV550/551 VAV controllers
Binary outputs
{
{
Binary input
Rover service tool
{
In
Out
®
LonTalk communication link
On
Cancel
Trane zone sensor
{
Analog inputs
1
2
3
Page 7
Network architecture
®
Tracer VV550/551 VAV controllers can operate on a Tracer Summit BAS, on a building management system from another manufacturer, on a peer-to-peer network, or as stand-alone devices. The Rover service tool can configure the
Figure 4. Network architecture with Tracer VV551 VAV controllers
Tracer Summit PC Workstation
LAN (Ethernet or ARCNET)
Building control unit (BCU)
Building control unit (BCU) with operator display
controllers at any accessible location on the LonTalk
®
communication link (Figure
4).
o
o o
ROVER
Rover service tool
TM
60
65
55
70
50
75
*
*
80
5 8
*
Zone
LonTalk
®
link
ON
Cancel
sensor
Tracer VV551 Tracer VV551
VAV box
CNT-PRC003-EN 7
LonTalk
link
®
VAV b ox
60
65
55
70
75
80
5 8
*
ON
Cancel
50
*
*
Zone sensor
60
65
55
70
50
75
*
*
80
5 8
*
Zone
ON
sensor
Cancel
Tracer VV551
VAV b ox
Page 8
®
Zone sensor options
Zone sensors are available in a variety of configurations. Table 1 describes the features of the five Trane zone sensors that are available for use with Tracer VV550/551 VAV controllers. The same five sensors are shown in Figure 5. Contact your Trane sales office about other compatible zone sensors.
Table 1. Zone sensors for use with Tracer VV550/551
GCC order
number
4190 1087 xx
4190 1088 xxx x
4190 1090 xxxx x
4190 1094 xx x
4190 1120 xxxxxx
Figure 5. Zone sensors for use with Tracer VV550/551
4190 1090
Setpoint
thumbwheel
Zone
Temperature
sensor
4190 1094
Timed override
buttons
LCD Comm jack
ON CANCEL
4190 1088
4190 1087
4190 1120
Page 9
Dimensions and specifications
®
Power requirements
Supply: 18–32 Vac (24 Vac nominal) at 50/60 Hz
Operating environment
Temperature: 32 to 140°F (0 to 60°C)
Relative humidity: From 5 to 95% non-condensing
Storage environment
Temperature:
-40 to 185°F (-40 to 85°C)
Relative humidity: From 5 to 95% non-condensing
Dimensions
(See Figure 6 on page 10.)
Board only
Height: 4.5 in. (11.4 cm) Width: 5.5 in. (13.8 cm) Depth: 2 in. (5.1 cm)
With enclosure (VV551)
Height: 7.5 in. (13.7 cm) Width: 6.5 in. (16.7 cm) Depth: 5.5 in. (14.0 cm)
Weight with enclosure (Tracer VV551)
With no actuator: 3.9 lb (1.77 kg) With Belimo actuator: 5.0 lb (2.27 kg) With Trane actuator: 5.2 lb (2.36 kg)
Binary input
Occupancy or generic (dry contact)
Binary outputs
Air valve close:
maximum output rating: 12 VA
Air valve open:
maximum output rating: 12 VA
Heat stage 1:
maximum output rating: 12 VA
Heat stage 2:
maximum output rating: 12 VA
Heat stage 3/Fan on/off:
maximum output rating: 12 VA
Agency listings/compliance
Tracer VV550:
UL 873 and CSA C22.2 No. 24-93: Temperature Indicating and Regulating Equipment
Tracer VV551:
UL-916-PAZX—energy management
CUL-C22.2—signal devices—Canada
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Class A
CE marked
CNT-PRC003-EN 9
Analog inputs
Space temperature; thermistor:
10 k @ 77°F (25°C) From 14 to 122°F (-10 to 50°C)
Space setpoint; potentiometer:
1 k From 50 to 90°F (-10 to 32.2°C)
Primary/discharge air temperature; thermistor:
10 k @ 77°F (25°C) From -40 to 212°F (-40 to 100°C)
Primary air flow; pressure transducer:
From 0 to 2 in. water (0 to 498 Pa)
Page 10
®
Figure 6. Tracer VV551 dimensions
Cover off
7.5 in. (19.2 cm)
6.5 in. (16.7 cm)
5.5 in. (14.0 cm)
Cover on
7.5 in. (19.2 cm)
6.5 in. (16.7 cm)
Page 11
Data lists
®
Table 2 provides an input/output listing for Tracer VV550/551 VAV controllers. Table 3 provides the configuration properties for the controller. The content
LonMark® SCC functional profile 8500 and the LonMark
®
node object.
of the lists conforms to both the
Table 2. Input/output listing
Input description Input SNVT type Output description Output SNVT type
Space temperature nviSpaceTemp SNVT_temp_p Space temperature nvoSpaceTemp SNVT_temp_p Setpoint nviSetpoint SNVT_temp_p Unit status, mode nvoUnitStatus SNVT_hvac_status Occupancy, schedule nviOccSchedule SNVT_tod_event Effective setpoint nvoEffectSetpt SNVT_temp_p Occupancy, manual
command Occupancy sensor nviOccSensor SNVT_occupancy Heat cool mode nvoHeatCool SNVT_hvac_mode Application mode nviApplicMode SNVT_hvac_mode Setpoint nvoSetpoint SNVT_temp_p Heat/cool mode input nviHeatCool SNVT_hvac_mode Discharge air
Fan speed command nviFanSpeedCmd SNVT_switch Terminal load nvoTerminalLoad SNVT_lev_percent Auxiliary heat enable nviAuxHeatEnable SNVT_switch Space CO Valve override nviValveOverride SNVT_hvac_overid Effective air flow
Flow override nviFlowOverride SNVT_hvac_overid Air flow nvoAirFlow SNVT_flow Emergency override nviEmergOverride SNVT_hvac_emerg File table address nvoFileDirectory* SNVT_address Source temperature nviSourceTemp SNVT_temp_p Object status nvoStatus* SNVT_obj_status Space CO Clear alarms/
Air flow setpoint input nviAirFlowSetpt SNVT_flow Ventilation ratio limit nviVentRatioLim SNVT_lev_percent Ventilation for the zone
* Part of the node object.
2
diagnostics
input
nviOccManCmd SNVT_occupancy Effective occupancy nvoEffectOccup SNVT_occupancy
temperature
2
setpoint
nviSpaceCO2 SNVT_ppm Alarm message nvoAlarmMessage SNVT_str_asc nviRequest* SNVT_obj_request * Part of the node object.
nviVentSetpt SNVT_flow
nvoDischAirTemp SNVT_temp_p
nvoSpaceCO2 SNVT_ppm nvoEffectFlowSP SNVT_flow
Table 3. Configuration properties
Configuration property
description
Send heartbeat nciSndHrtBt SNVT_time_sec SCPTmaxSendTime (49) Occ temperature setpoints nciSetpoints SNVT_temp_setpt SCPTsetPnts (60) Minimum send time nciMinOutTm SNVT_time_sec SCPTminSendTime (52) Receive heartbeat nciRecHrtBt SNVT_time_sec SCPTmaxRcvTime (48) Location label nciLocation SNVT_str_asc SCPTlocation (17) Local bypass time nciBypassTime SNVT_time_min SCPTbypassTime (34) Manual override time nciManualTime SNVT_time_min SCPTmanOverTime (35) Space CO Nominal air flow nciNomFlow SNVT_flow SCPTnomAirFlow (57) Air flow measurement gain nciFlowGain SNVT_multiplier SCPTsensConstVAV (67) Minimum air flow nciMinFlow SNVT_flow SCPTminFlow (54) Maximum air flow nciMaxFlow SNVT_flow SCPTmaxFlow (51) Minimum air flow for heat nciMinFlowHeat SNVT_flow SCPTminFlowHeat (55) Maximum air flow for heat nciMaxFlowHeat SNVT_flow SCPTmaxFlowHeat (37) Minimum flow for standby nciMinFlowStdby SNVT_flow SCPTminFlowStby (56) Firmware major version nciDevMajVer* n/a SCPTdevMajVer (165) Firmware minor version nciDevMinVer* n/a SCPTdevMinVer (166) Flow offset for tracking applications nciFlowOffset SNVT_flow_f SCPToffsetFlow (265) Local heating minimum air flow nciMinFlowUnitHt SNVT_flow SCPTminFlowUnitHeat (270) * Part of the node object.
CNT-PRC003-EN 11
limit nciSpaceCO2Lim SNVT_ppm SCPTlimitCO2 (42)
2
Configuration property SNVT type SCPT reference
Page 12
Trane A business of American Standard Inc. www.trane.com
For more information, contact your local Trane office or e-mail us at comfort@trane.com
Literature Order Number CNT-PRC003-EN
File Number PL-ES-CNT-PRC003-1005
Supersedes CNT PRC003-EN April 2004
Stocking Location Inland
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Loading...