Tracer VV550 and Tracer VV551 variable
air volume (VAV) controllers provide
single-duct digital control for VAV boxes.
They support the following VAV control
sequences:
• Space temperature control
• Flow tracking
• Ventilation flow control
The Tracer VV550 VAV controller is
available factory-installed on Trane
VariTrane VAV boxes (Figure 1). The
Tracer VV551 VAV controller is available
for field installation for a variety of VAV
applications (Figure 2).
Figure 1. Tracer VV550 controller
Figure 2. Tracer VV551 controller
(uses same board as Tracer VV550)
Because the Tracer VV550 and Tracer
VV551 VAV controllers use the same
logic controller, both offer the same
wide range of application and control
flexibility. The Tracer VV551 VAV
controller includes additional laborsaving packaging features for fieldinstalled applications.
Tracer VV550/551 VAV controllers can
operate as part of a Trane Integrated
Comfort™ system (ICS), as part of a
building management system from
another manufacturer, or as a
standalone device.
When it is part of a Trane ICS, a Tracer
VV550/551 VAV controller enables the
building automation system (BAS) to
perform functions such as scheduling,
trending, alarming, remote
communications, and VAV air system
(VAS) coordination. The controller
communicates with a Tracer Summit
BAS over the LonTalk
®
communications
link. The controller can also
communicate with other building control
systems that are compliant with the
LonMark® Space Comfort Controller
(SCC) profile.
Tracer VV550/551 VAV controllers can be
configured using the Rover™ service
tool. They have the following inputs and
outputs (Figure 3 on page 6):
™ ® The following are trademarks or registered trademarks of their respective companies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; LonMark,
LonTalk, and LonWorks of the Echelon Corporation.
Tracer VV550/551 VAV controllers
automatically calibrate the flow
transducer each time the box transitions
to the unoccupied state. This eliminates
the need to initiate/schedule calibration
for most installations. The exception is
24/7 sites, in which case the Tracer
Summit building automation system can
be used to initiate/schedule calibration.
Ventilation flexibility
Tracer VV550/551 VAV controllers can
manage ventilation in the following
ways:
• Occupancy sensor to switch between
normal and reduced ventilation
•CO
sensor for demand-controlled
2
ventilation
This flexibility gives owners and facility
managers an option to simply select one
of several effective solutions for
managing ventilation.
Flow tracking
Tracer VV550/551 VAV controllers can
easily be applied in flow tracking
applications. In a flow tracking
application, supply and exhaust boxes
are paired together for the purpose of
maintaining either positive or negative
space static pressure. This feature
allows the installer to quickly define the
relationship of the supply and exhaust
air boxes without the need for custom
programming.
Ventilation flow control
with tempering
Tracer VV550/551 VAV controllers have
been designed for ventilation flow
control applications. These applications
pair a fresh air unit or self-contained unit
with ventilation boxes to provide fresh
(tempered) air to a floor/area. With this
feature, the installer can quickly
configure the flow control boxes and set
up the system without the need for
custom programming.
Local versus remote reheat
flexibility
Tracer VV550/551 VAV controllers can be
configured to have local and/or remote
heat. This configuration flexibility
enables the controllers to be applied
across a broad range of VAV
applications.
Occupied and unoccupied
operation
The occupancy input on a Tracer VV550/
551 VAV controller works with a motion
(occupancy) sensor or a time clock to
determine the occupancy mode. An
occupancy request can also be
communicated from a building
automation system to determine the
mode of the controller. Whether standalone or combined with a
communicated occupancy request, a
Tracer VV550/551 controller can be used
with an occupancy sensor to save
energy whenever a space is vacant.
Timed override
The timed override function for afterhours operation allows users to request
unit operation by the touch of a button
on the unit zone sensor. Additionally,
users can press the CANCEL button at
any time to place the unit back into
unoccupied mode. This occupancy
feature minimizes energy use by running
the system only as scheduled or as
demanded after hours.
Service pin from the Trane
zone sensor
Certain installation scenarios require
access to the SERVICE button on the
controller. Access to this button typically
requires a ladder or a lift. The Tracer
VV550/551 VAV controller allows a
technician to replicate pressing the
SERVICE button by pressing the zone
sensor ON button. This feature
eliminates the need for accessing the
SERVICE button, saving the technician
time and energy.
4CNT-PRC003-EN
Page 5
®
Auto-commissioning
sequence
Tracer VV550/551 VAV controllers
provide an automatic commissioning
sequence. With a discharge air
temperature sensor installed, this
feature exercises the air valve, fan, and
heat in the box and records the
discharge air temperature before and
after the action. This allows the installer
to easily checkout the operation of the
box and commission by exception. The
data from this test is retained in the
controller for immediate reports or
retrieval at a later date (for comparison
purposes).
Manual test function
A Tracer VV550/551 VAV controller
includes a manual test button, which
enables a technician to easily exercise
the outputs of the controller. On
consecutive button presses, the
controller steps through a predefined
sequence that exercises all of the
controller outputs.
Drive minimum and
maximum from zone sensor
When applied with a Trane zone sensor
module that includes a thumbwheel
setpoint, a Tracer VAV VV550/551
controller can easily be overridden to
minimum and maximum flow. By simply
turning the thumbwheel to ∗, the
controller drives the air valve to the
minimum cooling flow setpoint.
Similarly, turning the thumbwheel to ∗∗
drives the air valve to the maximum
cooling flow setpoint. This simple
override feature is most useful during
the checkout and balancing phases of a
project.
Trane controller
compatibility
Tracer VV550/551 VAV controllers are
compatible with the latest generation of
Trane control products. The controllers
communicate over a LonTalk
communications link. This allows Tracer
VV550/551 VAV controllers to exist on
the same communication wire as other
Trane controllers and to share data with
them as required.
®
Interoperability
Tracer VV550/551 VAV controllers are
designed with LonWorks
and are LonMark
the guidelines of the LonMark
Comfort Controller (SCC) profile. As
such, the Tracer VV550/551 controllers
enable control system integration
flexibility.
®
®
technology
certified. They follow
®
Space
Wiring diagram
See Figure 3 on page 6.
Wiring diagram 2
CNT-PRC003-EN5
Page 6
®
Figure 3. Tracer VV550/551 wiring diagram
24V
GND
Wiring diagram for Tracer
VV550/551 VAV controllers
Binary outputs
{
{
Binary
input
Rover
service tool
6CNT-PRC003-EN
{
In
Out
®
LonTalk
communication
link
On
Cancel
Trane zone
sensor
{
Analog inputs
1
2
3
Page 7
Network architecture
®
Tracer VV550/551 VAV controllers can
operate on a Tracer Summit BAS, on a
building management system from
another manufacturer, on a peer-to-peer
network, or as stand-alone devices. The
Rover service tool can configure the
Figure 4. Network architecture with Tracer VV551 VAV controllers
Tracer Summit PC Workstation
LAN (Ethernet or ARCNET)
Building
control unit
(BCU)
Building
control unit
(BCU) with
operator
display
controllers at any accessible location on
the LonTalk
®
communication link (Figure
4).
o
o o
ROVER
Rover service tool
TM
60
65
55
70
50
75
*
*
80
5
8
*
Zone
LonTalk
®
link
ON
Cancel
sensor
Tracer VV551Tracer VV551
VAV box
CNT-PRC003-EN7
LonTalk
link
®
VAV b ox
60
65
55
70
75
80
5
8
*
ON
Cancel
50
*
*
Zone
sensor
60
65
55
70
50
75
*
*
80
5
8
*
Zone
ON
sensor
Cancel
Tracer VV551
VAV b ox
Page 8
®
Zone sensor options
Zone sensors are available in a variety of
configurations. Table 1 describes the
features of the five Trane zone sensors
that are available for use with Tracer
VV550/551 VAV controllers. The same
five sensors are shown in Figure 5.
Contact your Trane sales office about
other compatible zone sensors.
Table 1. Zone sensors for use with Tracer VV550/551
GCC order
number
4190 1087xx
4190 1088xxxx
4190 1090xxxxx
4190 1094xxx
4190 1120xxxxxx
Figure 5. Zone sensors for use with Tracer VV550/551
4190 1090
Setpoint
thumbwheel
Zone
Temperature
sensor
4190 1094
Timed override
buttons
LCDComm jack
ONCANCEL
4190 1088
8CNT-PRC003-EN
4190 1087
4190 1120
Page 9
Dimensions and specifications
®
Power requirements
Supply: 18–32 Vac (24 Vac nominal) at
50/60 Hz
Operating environment
Temperature:
32 to 140°F (0 to 60°C)
Relative humidity:
From 5 to 95% non-condensing
Storage environment
Temperature:
-40 to 185°F (-40 to 85°C)
Relative humidity:
From 5 to 95% non-condensing
Dimensions
(See Figure 6 on page 10.)
Board only
Height: 4.5 in. (11.4 cm)
Width: 5.5 in. (13.8 cm)
Depth: 2 in. (5.1 cm)
With enclosure (VV551)
Height: 7.5 in. (13.7 cm)
Width: 6.5 in. (16.7 cm)
Depth: 5.5 in. (14.0 cm)
Weight with enclosure
(Tracer VV551)
With no actuator: 3.9 lb (1.77 kg)
With Belimo actuator: 5.0 lb (2.27 kg)
With Trane actuator: 5.2 lb (2.36 kg)
Binary input
Occupancy or generic (dry contact)
Binary outputs
Air valve close:
maximum output rating: 12 VA
Air valve open:
maximum output rating: 12 VA
Heat stage 1:
maximum output rating: 12 VA
Heat stage 2:
maximum output rating: 12 VA
Heat stage 3/Fan on/off:
maximum output rating: 12 VA
Agency listings/compliance
Tracer VV550:
UL 873 and CSA C22.2 No. 24-93:
Temperature Indicating and Regulating
Equipment
Tracer VV551:
UL-916-PAZX—energy management
CUL-C22.2—signal devices—Canada
UL 94-5V (UL flammability rating for
plenum use)
FCC Part 15, Class A
CE marked
CNT-PRC003-EN9
Analog inputs
Space temperature; thermistor:
10 k Ω@ 77°F (25°C)
From 14 to 122°F (-10 to 50°C)
Space setpoint; potentiometer:
1 kΩ
From 50 to 90°F (-10 to 32.2°C)
Primary/discharge air temperature;
thermistor:
10 k Ω@ 77°F (25°C)
From -40 to 212°F (-40 to 100°C)
Primary air flow; pressure transducer:
From 0 to 2 in. water (0 to 498 Pa)
Page 10
®
Figure 6. Tracer VV551 dimensions
Cover off
7.5 in. (19.2 cm)
6.5 in. (16.7 cm)
5.5 in. (14.0 cm)
Cover on
7.5 in. (19.2 cm)
6.5 in. (16.7 cm)
10CNT-PRC003-EN
Page 11
Data lists
®
Table 2 provides an input/output listing
for Tracer VV550/551 VAV controllers.
Table 3 provides the configuration
properties for the controller. The content
LonMark® SCC functional profile 8500
and the LonMark
®
node object.
of the lists conforms to both the
Table 2. Input/output listing
Input descriptionInputSNVT typeOutput descriptionOutputSNVT type
Fan speed commandnviFanSpeedCmdSNVT_switchTerminal loadnvoTerminalLoadSNVT_lev_percent
Auxiliary heat enablenviAuxHeatEnableSNVT_switchSpace CO
Valve overridenviValveOverrideSNVT_hvac_overidEffective air flow
Flow overridenviFlowOverrideSNVT_hvac_overidAir flownvoAirFlowSNVT_flow
Emergency overridenviEmergOverrideSNVT_hvac_emergFile table addressnvoFileDirectory*SNVT_address
Source temperaturenviSourceTempSNVT_temp_pObject statusnvoStatus*SNVT_obj_status
Space CO
Clear alarms/
Air flow setpoint inputnviAirFlowSetptSNVT_flow
Ventilation ratio limitnviVentRatioLimSNVT_lev_percent
Ventilation for the zone
nviSpaceCO2SNVT_ppmAlarm messagenvoAlarmMessageSNVT_str_asc
nviRequest*SNVT_obj_request* Part of the node object.
nviVentSetptSNVT_flow
nvoDischAirTempSNVT_temp_p
nvoSpaceCO2SNVT_ppm
nvoEffectFlowSPSNVT_flow
Table 3. Configuration properties
Configuration property
description
Send heartbeatnciSndHrtBtSNVT_time_secSCPTmaxSendTime (49)
Occ temperature setpointsnciSetpointsSNVT_temp_setptSCPTsetPnts (60)
Minimum send timenciMinOutTmSNVT_time_secSCPTminSendTime (52)
Receive heartbeatnciRecHrtBtSNVT_time_secSCPTmaxRcvTime (48)
Location labelnciLocationSNVT_str_ascSCPTlocation (17)
Local bypass timenciBypassTimeSNVT_time_minSCPTbypassTime (34)
Manual override timenciManualTimeSNVT_time_minSCPTmanOverTime (35)
Space CO
Nominal air flownciNomFlowSNVT_flowSCPTnomAirFlow (57)
Air flow measurement gainnciFlowGainSNVT_multiplierSCPTsensConstVAV (67)
Minimum air flownciMinFlowSNVT_flowSCPTminFlow (54)
Maximum air flownciMaxFlowSNVT_flowSCPTmaxFlow (51)
Minimum air flow for heatnciMinFlowHeatSNVT_flowSCPTminFlowHeat (55)
Maximum air flow for heatnciMaxFlowHeatSNVT_flowSCPTmaxFlowHeat (37)
Minimum flow for standbynciMinFlowStdbySNVT_flowSCPTminFlowStby (56)
Firmware major versionnciDevMajVer*n/aSCPTdevMajVer (165)
Firmware minor versionnciDevMinVer*n/aSCPTdevMinVer (166)
Flow offset for tracking applicationsnciFlowOffsetSNVT_flow_fSCPToffsetFlow (265)
Local heating minimum air flownciMinFlowUnitHtSNVT_flowSCPTminFlowUnitHeat (270)
* Part of the node object.
CNT-PRC003-EN11
limitnciSpaceCO2LimSNVT_ppmSCPTlimitCO2 (42)
2
Configuration propertySNVT typeSCPT reference
Page 12
Trane
A business of American Standard Inc.
www.trane.com
For more information, contact your local Trane
office or e-mail us at comfort@trane.com
Literature Order Number CNT-PRC003-EN
File NumberPL-ES-CNT-PRC003-1005
SupersedesCNT PRC003-EN April 2004
Stocking LocationInland
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.