Trane RT-SVX19A-E4 User Manual

Voyager™ II Rooftop units Cooling only TKD/TKH 155 175 200 250 Reversible WKD/WKH 125 155 200 Gas-Fired YKD/YKH 155 175 200 250 R22 - R407C Refrigerant
Installation Operation Maintenance
RT-SVX19A-E4
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane TKD/TKH, WKD/WKH and YKD/YKH units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.
TKD/TKH units are designed to operate in cooling mode only, with optional auxiliary heat (electric heater or hot water coil).
WKD/WKH can operate in cooling mode or heating mode by reversing the refrigeration cycle with or without auxiliary heat.
YKD/YKH units are designed to operate In cooling mode and equipped with a gas fired heating module.
TKD/TKH, WKD/WKH and YKD/YKH units are assembled, pressure tested, dehydrated, charged and run tested before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter "Installation". Always provide a pressure regulator.
2. Disconnect the main power supply before any servicing on the unit.
3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery note.
In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery.
Reception in France only:
Concealed damage must be looked for at delivery and immediately treated as visible damage.
Reception in all countries except France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.
General information
RT-SVX19A-E42
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
Refrigerant
The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Storage
Take precautions to prevent condensate formation inside the unit's electrical components and motors when:
1. The unit is stored before it is installed; or,
2. The unit is set on the roof curb and temporary auxiliary heat is provided in the building.
Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up.
Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up".
The Trane Company will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
General information
3RT-SVX19A-E4
RT-SVX19A-E44
Contents
Foreword 2 Warnings and Cautions 2 Safety recommendations 2 Reception 2 Warranty 3 Refrigerant 3 Maintenance contract 3 Storage 3 Training 3
Installation 6
Reception of units 6 Roof curb installation 7 Dimensions/Weights/Clearances 8 Installing the unit 10 Connection of duct network 11 Condensate drain piping 12 Gas pipework installation 13 Filter installation 14 Supply fan adjustment 15 Component air pressure drops 17 Supply fan performances 20 Electrical connection 26
Controls 31
Control wiring 31 CO2sensors 33 Remote potentiometer 36 Fire thermostat 37 Clogged filter detector 38 Smoke detector 38 High temperature safety thermostat 38 Remote fault relay 38 Thermostats 38 Communication Interfaces 39
Contents
5RT-SVX19A-E4
Unit Options 40
Hot water coil 40 Electric Heater 41 Soft Starter 41 0 - 25% fresh air hood 42 Barometric relief 43
Operation 44
Operation with a conventional thermostat 44 Setting the economizer 47 Test procedures 49 Test modes 50 Unit start-up 51 Cooling without an Economizer 54 Low Ambient Operation 55 Cooling with an Economizer 55 Economizer Set-Up 56 ReliaTel™ Control Heating Operation 56 Ignition Module 56 Final installation checklist 57
Maintenance 58
End user routine maintenance 58 Service technician maintenance 59 Troubleshooting 60
Installation
RT-SVX19A-E46
General information :The installation must conform to all local standards and regulations.
Reception of units
Rooftop unit
The unit is supplied on a wooden frame. It is recommended to check the machine's condition upon reception.
There are two ways to handle the unit:
1. Use the openings in the wooden frame to handle the machine using a fork lift, in accordance with applicable safety regulations.
2. Use a lifting beam correctly adjusted to fit the unit (Figure 1a).
Unit handling
The units are supplied on the truck but are not unloaded. An opening is provided on each corner of the unit base to facilitate handling. 4 shackles and 4 slings are required. Use a lifting beam to prevent the cables pressing too hard on top of the unit during lifting.
Figure 1a indicates the position of the center of gravity and the lifting recommendations.
Important: For unit to fit on the roof curb the fork lift pockets must be removed.
Figure 1a - Unit handling
1 = Clevis 2 = Base Rail 3 = Spreader Bar L = Length (Center of Gravity) W = Width (Center of Gravity)
Refer to Table 2 for weights and center of gravity.
A
B
Roof curb Installation (TKD-WKD-YKD accessories)
Roof curbs are available as an accessory for "downflow" units to support the unit and ensure the water tightness between the rooftop and the roof. Two types of roof curbs are available: The standard version to allow the installation of the unit on a flat roof and the adjustable version for a sloped roof installation. (See Figure 1b for the maximum slope correction of adjustable roofcurb.)
The adjustable roof curbs are supplied pre-assembled on a skid.
Two types of self-adhesive seals are provided separately. (40 mm wide for the perimeter, 20 mm wide for the cross pieces). Make sure they are properly installed where indicated to assure an adequate curb to unit seal.
Instructions for the roof curb assembly and installation with curb dimensions are provided with each roof curb kit.
Table 1 - Sling lengths and maximum unit weight
Figure 1b - Maximum slope correction of adjustable roof curb.
Figure 2 - Waterproofing
1 = Roofcurb 2 = Roof membrane 3 = Seal 4 = Rooftop
Unit size A (mm) B (mm)
Maximm weight
kg
125 3000 1900 644 155 3000 1900 773 175 3000 1900 810 400 3500 2200 1001 500 3500 2200 1027
Installation
7RT-SVX19A-E4
3
4
1
2
Installation
RT-SVX19A-E48
Dimensions/Weights/Clearances
Figure 3 - Minimum clearances
Table 2 - Minimum clearances (mm)
The structure accommodating the unit(s) must be designed to support the equipment in operation, as a minimum. Refer to Table 3a and the space requirement plan.
Minimum clearance
UNIT 1 2 3 4 5 YKD/YKH 155 1900 1800 1220 1000 1300 YKD/YKH 175 1900 1800 1220 1000 1300 YKD/YKH 200 1900 1800 1220 1000 1300 YKD/YKH 250 1900 1800 1220 1000 130 0 TKD/TKH 155 1900 1800 1220 1000 1300 TKD/TKH 175 1900 1800 1220 1000 1300 TKD/TKH 200 1900 1800 1220 1000 1300 TKD/TKH 250 1900 1800 1220 1000 1300
WKD/WKH 125 1900 1800 1220 1000 1300 WKD/WKH 155 1900 1800 1220 1000 1300 WKD/WKH 200 1900 1800 1220 1000 1300
Installation
9RT-SVX19A-E4
Installation
Table 3a - Weigths & center of gravity (Figure 1)
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
Table 3b - Weights of Options & accessories
Notes : Net weight should be added to unit weight when ordering factory installed accessories. To estimate shipping weight add 2.3 kg to net weight.
UNIT
Standard Roof
Curb
Adjustable Roof
Curb Economizer
Manual Outside
Air Damper
Motorized
Outside Air
Damper Electric heater Hot water coil YKD 155 93 220 30 15 27 YKD 175 93 220 30 15 27 YKD 200 107 260 37 15 34 YKD 250 107 260 37 15 34 YKH 155 30 15 27 YKH 175 30 15 27 YKH 200 37 15 34 YKH 250 37 15 34 TKD 155 93 220 30 15 27 14 85 TKD 175 93 220 30 15 27 14 85 TKD 200 107 260 37 15 34 18 11 0 TKD 250 107 260 37 15 34 18 11 0 TKH 155 30 15 27 14 TKH 175 30 15 27 14 TKH 200 37 15 34 18 TKH 250 37 15 34 18
WKD 125 93 180 20 15 27 18 85 WKD 155 93 220 30 15 27 18 85 WKD 200 107 260 37 15 34 18 11 0 WKH 125 20 15 27 18 WKH 155 30 15 27 18 WKH 200 37 15 34 18
Maximum weight Corner Weight (1) Center of Gravity
Shipping Net A B C D Length (L) Width (W)
UNIT (kg) (kg) (kg) (kg) (kg) (kg) (mm) (mm) YKD/YKH 155 866 698 243 176 118 162 11 43 737 YKD/YKH 175 902 735 251 188 127 169 116 8 737 YKD/YKH 200 112 8 920 324 242 151 203 1321 838 YKD/YKH 250 115 4 946 327 251 159 208 1346 838 TKD/TKH 155 790 623 219 159 10 3 142 114 3 711 TKD/TKH 175 827 660 227 17 2 112 149 11 68 711 TKD/TKH 200 1050 841 297 221 138 185 1321 838 TKD/TKH 250 1075 866 300 230 145 206 1346 838
WKD/WKH 125 792 625 218 159 10 5 144 114 3 711 WKD/WKH 155 809 642 228 162 10 5 147 114 3 711 WKD/WKH 200 1080 871 291 226 155 199 1346 889
Installation
RT-SVX19A-E410
Installing the unit
1) Unit mounting on roof
Fix the rooftop curb on the joint beam of the building's structure. Make the rooftop curb's sealing surface level using angle brackets adjusted by screw bolts, located around its perimeter. Place the adhesive seals on the curb's sealing surface (perimeter and cross pieces). Make the rooftop leak-tight around the curbs before installing the unit, in compliance with current construction standards.
Note: The unit must be installed perfectly level to ensure condensates flow from the condensate tray.
The rooftop unit nests into the curb and is supported by it. Position the unit, taking care to comply with the indicated directions: the unit's discharge and intake openings must match those of the curb.
2) Installing the unit on the ground
To install the unit on the ground, its base must be level and supported securely.
For horizontal discharge units, a support is required such as a metal or concrete slab whose height must be determined according to the amount of snow cover, to prevent problems with condensation drainage and obstruction of the external coil. If necessary use an anti-vibration material between the rooftop unit's base and the support.
Note: Unit installation must comply to local codes
Figure 4
1 = Frame
Figure 5
1 = Concrete slab
RT-SVX19A-E4
Installation
11RT-SVX19A-E4RT-SVX19A-E4
Connection of duct network
1) Downflow discharge units (TKD,WKD,YKD)
Using the rooftop curb
The rooftop curb must be insulated on the outside walls at the discharge and intake openings to prevent condensation in the ducts.
The rims around the discharge and intake openings make it possible to attach the flanges on the ends of the ducts. If you are using rigid duct ends recommended on the rooftop curb plan, it is essential to fix these components before installing the unit.
For the design of the duct network, comply with recommendations currently applicable on the market, in particular:
. Installation of a section of
flexible ducts to limit transmission of the unit's vibrations
. Use of movable vanes or
deflectors to reduce the sound level.
2) Horizontal discharge units (TKH,WKH,YKH)
The intake and discharge ducts must be insulated (thermal insulation).
The duct section located outside must be leak-tight.
Provide a flexible connector to prevent transmission of the unit vibrations. This flexible duct must be installed inside the building.
Note: In case of use of TKH, WKH or YKH units with economizer option, temperature and humidity sensors must be installed in return duct. Economizer linkage is factory mounted but the damper position must be adjusted on site.
Figure 6 - Condensate Drain location
1 = Condensate drain connection A = TKH/YKH 155, 175, 200, 250 - WKH 125,155, 200 B = TKD/YKD 155, 175, 200, 250 - WKD 125,155,200
Installation
RT-SVX19A-E412
Figure 7 - Condensate drain line connection
1 = Static pressure drain pan 2 = Panel enclosure 3 = 42mm PVC drain 4 = Cleanout plug
RT-SVX19A-E4
Condensate drain piping
A 42mm PVC condensate drain connection with P-trap is provided.
Follow local codes and standard piping practices when running the drain line. Install a trap and be sure to fill with water before starting the unit. Pitch the line downward, away from the unit to avoid long, level, horizontal runs. Refer to Figure 7.
Installation
13RT-SVX19A-E4
Gas pipework installation
The installation must conform to all standards and regulations.
The gas supply pipework and gas stop valve to be installed near the unit must be sized so as to assure the gas pressure is sufficient at the unit inlet when operating at full load.
CAUTION! Should the pressure at the unit valve gas inlet be higher than 0.035 bar, an expansion valve must be installed.
The pipework must be self­supporting and the final connection to the burner must be made by a flexible pipe. Provide a dust protection (filter) upstream the unit connection.
CAUTION!The gas pipework must not exert any stress on the burner gas connection.
Note: Expansion valve must be adapted to the type of gas used:
G 20 : 20 mb
G 25 : 25 mb
G 31 : (Propane): 37 or 50 mb
Table 4 - Gas burner models
See Table 38 for burner performance.
Gas leak check procedure
1. Vent the gas line
2. Gas supply line pressure test: close valve 4 and open valve 2
3. Leak-check the gas pipe
Look for gas pipe leaks using "Typol", "1000 bulles" or a similar product. Do not use soapy water.
WARNING! Never use an open flame to check for gas leaks. Required gas pressure at the unit inlet connection are given in Table 37.
Note:To operate with propane gas, the burner is fitted with a pressure limiter (supplied by Trane)
Unit Burner size
YKD/H 155 G350A YKD/H 175 G350A YKD/H 200 G350A YKD/H 250 G350A
Figure 8 - Typical gas supply Pipework
1 = Evaporator section 2 = Gas burner section 3 = Condenser section 4 = Gas supply connection
5 = Gas supply line 6,8 = Gas stop valve (Field supplied) 7 = Expansion valve (Field supplied) 9 = Filter (Field supplied)
Installation
RT-SVX19A-E414
CAUTION! Do not operate unit without filters in place.
The maximum pressure drops allowable on filters are:
EU2/G2: 120 Pa EU4/G4: 150 Pa
Filter installation
To gain access to filters, remove the supply fan access panel on downflow units and the filter access panel on the end for horizontal units.
Each unit ships with 40 or 50 mm thick filters. Number and size of filters is determined by size and configuration of the unit.
Table 5 - Filter arrangement
UNIT
EU2/G2 EU4/G4
Qty Size Qty Size
YKH/YKD 155
2 (508x508x50) 2 (498x498x40) 4 (508x635x50) 4 (500x625x50)
YKH/YKD 175
2 (508x508x50) 2 (498x498x40) 4 (508x635x50) 4 (500x625x50)
YKH 200 8 (508x635x50) 8 (500x625x50)
YKD 200
4 (508x508x50) 4 (498x498x40) 4 (508x635x50) 4 (500x625x50)
YKH 250 8 (508x635x50) 8 (500x625x50)
YKD 250
4 (508x508x50) 4 (498x498x40) 4 (508x635x50) 4 (500x625x50)
TKH/TKD 155
2 (508x508x50) 2 (498x498x40) 4 (508x635x50) 4 (500x625x50)
TKH/TKD 175
2 (508x508x50) 2 (498x498x40) 4 (508x635x50) 4 (500x625x50)
TKH 200 8 (508x635x50) 8 (500x625x50)
TKD 200
4 (508x508x50) 4 (498x498x40) 4 (508x635x50) 4 (500x625x50)
TKH 250 8 (508x635x50) 8 (500x625x50)
TKD 250
4 (508x508x50) 4 (498x498x40) 4 (508x635x50) 4 (500x625x50)
WKH/WKD 125
2 (508x508x50) 2 (498x498x40) 4 (508x635x50) 4 (500x625x50)
WKH/WKD 155
2 (508x508x50) 2 (498x498x40) 4 (508x635x50) 4 (500x625x50)
WKH 200 8 (508x635x50) 8 (500x625x50)
WKD 200
4 (508x508x50) 4 (498x498x40) 4 (508x635x50) 4 (500x625x50)
Installation
15RT-SVX19A-E4
Supply fan adjustment
Use the following procedure to determine the proper adjustment of the supply fan for a specific application.
1. Determine total external static pressure about system and accessories.
a. Obtain the design airflow rate
and the design external static pressure drop through the distribution system.
b. Add static pressure drop of the
accessories installed on the unit. (Table 7,8 & 9)
c. Add the total accessory static
pressure drop (from step 1b) to the design external static pressure (from step 1a). The sum of these two values is the total system external static pressure.
2. Using the Tables 10 through 20 to find the external static pressure that most closely approximates total system external static pressure. Then locate the appropriate airflow rate for your unit. The value obtained represents the brake horsepower for the supply fan motor and the fan RPM.
3. Adjust motor sheave according to Table 6.
Table 6 - Motor sheave / Fan speed
Fan Speed (RPM)
Standard Drive
6 turns 5 turns 4 turns 3 turns 2 turns 1 turns
UNIT Open Open Open Open Open Open Closed
YKD/YKH 155 566 601 637 672 708 74 3 N/A YKD/YKH 175 724 76 9 815 860 906 951 N/A YKD/YKH 200 513 550 586 623 659 696 N/A YKD/YKH 250 588 619 650 681 712 74 3 N/A TKD/TKH 155 566 601 637 672 708 74 3 N/A TKD/TKH 175 724 769 815 860 906 951 N/A TKD/TKH 200 513 550 586 623 659 696 N/A TKD/TKH 250 588 619 650 681 712 74 3 N/A WKD/WKH 125 533 566 600 633 667 700 N/A WKD/WKH 155 566 601 637 672 708 74 3 N/A WKD/WKH 200 513 550 586 623 659 696 N/A
Fan Speed (RPM)
Oversized Drive
6 turns 5 turns 4 turns 3 turns 2 turns 1 turns
UNIT Open Open Open Open Open Open Closed
YKD/YKH 155 672 714 756 798 840 882 N/A YKD/YKH 175 791 840 890 939 989 1038 N/A YKD/YKH 200 680 711 74 2 773 804 835 N/A YKD/YKH 250 690 722 754 786 818 850 N/A TKD/TKH 155 672 714 756 798 840 882 N/A TKD/TKH 175 791 840 890 939 989 1038 N/A TKD/TKH 200 680 711 74 2 773 804 835 N/A TKD/TKH 250 690 722 754 786 818 850 N/A WKD/WKH 125 724 76 9 815 860 906 951 N/A WKD/WKH 155 513 550 586 623 659 696 N/A WKD/WKH 200 588 619 650 681 712 74 3 N/A
Installation
RT-SVX19A-E416
To increase airflow
Loosen variable sheave set screw and turn sheave clockwise.
To decrease airflow
Loosen variable sheave set screw and turn sheave counter-clockwise.
To increase belt tension
Loosen the nut (next to the idler sheave) that secures the sheave in place. With a wrench, apply pressure clockwise on the outside nut (round headed one), until tension desired is reached. While holding pressure with the tension nut, retighten the nut next to the idler sheave.
Figure 9 - Typical fan, motor, and sheave assembly
A = Fan Housing B = Terminal Block C = Fan Sheave D = Plastic Bushing E = Belt Tension Adjustment Bolt F = Idler Pulley
Table 6b - Belt tensioning
TK* / YK* /
WK*
Motor kW
Fan pulley
Ty p e /
diam. (mm)
Fan pulley
Ty p e /
diam. (mm)
Belt type
/ lengh (mm)
Belt
deflexion
(mm)
Deflexion
effort
mini kg
Deflexion
effort
maxi kg
Belt tension
mini
N
Belt tension
maxi
N
125 1,5 BK90 / 222 1VP44 / 105 BX68 / 1727 5,89 2,4 2,9 400 500 155 1,5 BK85 / 210 1VP44 / 105 BX68 / 1727 6 2,4 2,9 400 500 175 3 BK130 / 324 1VP44 / 105 BX75 / 1905 6,05 2,4 2,9 400 500 200 3 BK160 / 400 1VL40 / 95 BX90 / 2286 6,96 2,4 2,9 400 500 250 4,6 BK190 / 476 1VP50 / 121 BX96 / 2438 6,91 2,4 2,9 400 500 125 3 BK130 / 324 1VP44 / 105 BX75 / 1905 5,85 2,4 2,9 400 500 155 3 BK140 / 349 1VP44 / 105 BX77 / 1955 6,17 2,4 2,9 400 500 175 4,6 BK140 / 349 1VP56 / 136 BX75 / 1905 5,45 2,4 2,9 400 500 200 4,6 BK190 / 476 1VP56 / 136 BX96 / 2438 6,87 2,4 2,9 400 500 250 4,6 BK190 / 476 1VP56 / 136 BX96 / 2438 6,32 2,4 2,9 400 500
Installation
17RT-SVX19A-E4
Component air pressure drops
Table 7 - YKD/YKH Pressure drop through accessories
Filter Filter Economizer Economizer
Airflow EU2/G2 EU4/G4
100%
outside air
100%
return air
YKD/YKH 155
6800 13 27 8 6
7650 16 30 10 7 8500 19 34 12 8 9350 22 37 14 9
10200 26 40 16 10
YKD/YKH 175
7870 17 30 10 7 8860 21 34 12 8 9850 25 38 15 9
10840 30 43 17 11 11830 35 47 20 12
YKD 200
8970 12 26 29 6
10090 15 30 37 8 112 10 19 33 45 9 12330 23 37 55 11 13450 27 41 65 13
YKH 200
8970 11 23 33 6
10090 14 26 41 8 112 10 17 29 51 9 12330 20 33 61 11 13450 23 36 72 13
YKD 250
11280 18 32 46 10 12690 24 36 58 12 14100 29 41 71 14 15510 36 46 86 17 16920 43 51 102 19
YKH 250
11280 17 30 52 10 12690 21 34 65 12 14100 26 38 80 14 15510 31 43 96 17 16920 36 47 11 4 19
Installation
RT-SVX19A-E418
Table 8 - TKD/TKH Pressure drop through accessories
Filter Filter Economizer Economizer Electric Hot water coil
Airflow EU2/G2 EU4/G4
100%
outside air
100%
return air
heater Downflow only
TKD/TKH 155
6800 13 27 8 6 7 33 7650 16 30 10 7 9 40 8500 19 34 12 8 11 48 9350 22 37 14 9 13 56
10200 26 40 16 10 16 65
TKD/TKH 175
7870 17 30 10 7 10 42 8860 21 34 12 8 13 51
9850 25 38 15 9 16 61 10840 30 43 17 11 19 72 11830 35 47 20 12 23 83
TKD 200
8970 12 26 29 6 13 33 10090 15 30 37 8 17 40
112 10 19 33 45 9 21 48 12330 23 37 55 11 25 56 13450 27 41 65 13 30 65
TKH 200
8970 11 23 33 6 13 -
10090 14 26 41 8 17 -
112 10 17 29 51 9 21 ­12330 20 33 61 11 25 ­13450 23 36 72 13 30 -
TKD 250
11280 18 32 46 10 20 49 12690 24 36 58 12 25 59 14100 29 41 71 14 32 71 15510 36 46 86 17 38 82 16920 43 51 10 2 19 46 95
TKH 250
11280 17 30 52 10 19 ­12690 21 34 65 12 24 ­14100 26 38 80 14 29 ­15510 31 43 96 17 35 ­16920 36 47 114 19 42 -
Installation
19RT-SVX19A-E4RT-SVX19A-E4
Table 9 - WKD/WKH Pressure drop through accessories
Airflow
Filter
EU2/G2
Filter
EU4/G4
Economizer
100%
outside air
Economizer
100%
return air
Electric
heater
Hot water coil
Downflow only
WKD/WKH 125
5720 9 21 6 5 4 37 6430 11 24 7 6 6 45 7140 14 27 9 6 7 53 7850 17 30 10 7 9 62 8560 20 33 12 8 12 72
WKD/WKH 155
6800 13 27 8 6 7 33 7650 16 30 10 7 9 40 8500 19 34 12 8 11 48 9350 22 37 14 9 13 56
10200 26 40 16 10 16 65
WKD 200
8970 12 26 29 6 13 33
10090 15 30 37 8 17 40
112 10 19 33 45 9 21 48 12330 23 37 55 11 25 56 13450 27 41 65 13 30 65
WKH 200
8970 11 23 33 6 13 -
10090 14 26 41 8 17 -
112 10 17 29 51 9 21 ­12330 20 33 61 11 25 ­13450 23 36 72 13 30 -
Installation
RT-SVX19A-E420
Supply fan performances
Table 10 - YK 155 External static pressure
Standard drive Oversized drive
External Static Pressure (Pa)
275 300 325 350 375 400 425 450 475 500
m3/h RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
6800 699 1. 4 7 719 1. 5 5 739 1. 6 3 758 1. 7 1 777 1. 7 9 795 1. 8 6 813 1. 9 4 830 2.01 847 2.09 863 2.16 7650 729 1. 8 2 74 9 1. 9 2 76 8 2.01 787 2.1 806 2.19 824 2.28 841 2.37 858 2.46 875 2.55 8500 764 2.25 782 2.35 800 2.45 818 2.55 9350 10200
External Static Pressure (Pa)
25 50 75 100 125 150 175 200 225 250
m3/h RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
6800 564 1 587 1. 0 7 610 1. 15 633 1. 2 3 655 1. 3 1 677 1. 3 9 7650 560 1. 1 4 583 1. 2 3 605 1. 3 1 627 1. 3 9 648 1. 4 8 669 1. 5 6 690 1. 6 5 710 1. 74 8500 559 1. 3 1 584 1. 4 1 606 1. 5 628 1. 6 649 1. 6 9 669 1. 7 8 689 1. 8 7 708 1. 9 7 727 2.06 74 6 2.16 9350 610 1. 7 2 633 1. 8 3 654 1. 9 4 675 2.04 694 2.14 713 2.24 732 2.34 750 2.45 767 2.55 785 2.65 10200 661 2.21 683 2.33 703 2.45 722 2.56
Loading...
+ 44 hidden pages