Innovative technology and an
impressive line-up of features make the
the T rane IntelliPak
number one choice for today and the
future.
T rane’s roof top Unit Control Module
(UCM), an innovative, modular
microprocessor control design,
coordinates the actions of the IntelliPak
rooftop in an efficient manner and allows
for stand-alone operation of the unit.
Access to the unit controls, via a Human
Interface Panel, provides a high degree
of control, superior monitoring
capability, and unmatched diagnostic
information.
®
Rooftop line the
Optionally, for centraliz ed building
control on-site, or from a remote
location, IntelliPak can be configured for
direct communication with a T racer
building management system using a
twisted pair of wires. With Tracer, the
IntelliPak status data and control
adjustment features can be conveniently
monitored from a central location.
• Unit mounted Human Interface Panel
with a 2 line x 40 character English
display and a 16 function key-pad that
includes Custom, Diagnostics, and
Service Test mode menu keys.
• T rane 3-D
(20 to 130 Tons)
• Compressor or circuit lead/lag
depending on unit
• Horizontal disc harge/return duct
connections (SX, SL, SS models)
• CV or VAV control
• Low ambient compressor loc kout
control on units with economizers
• FROSTAT™ coil frost protection on
all units
• Daytime Warm-up (Occupied mode)
on V A V models and Morning Warm-up
operation on all units with heating
options
• Supply air static overpressurization
protection on units with inlet guide
vanes and VFD’s.
• Supply airflow proofing
• Exhaust airflow proofing on units with
exhaust option
• Supply air tempering control
• Supply air heating control on VAV
modulating hot water or steam heat
units
• Emergency stop input
• Liquid and Discharge S ervice Valves
• Mappable sensors and setpoint
sources
• Occupied/Unoccupied switching
• Timed override activation
• Forward-curved supply fans
• Pitched roof over air handler section
• Stainless steel flue stack on gas heat
units
• 14-gauge, single-piece construction
base rails
®
Scroll compressors
• UL and CSA approval on standard
options
• Two-inch spring fan isolation
(90 to 130 tons)
• Meets 672 hours of salt spray testing in
accordance to A STM B117 Standard
• Two inch standard efficiency
throwaw ay filters on 20 to 90 ton units
and two inch high ef ficiency
throwaw ay filters on 105 to 1 30 ton
units.
Optional Featur es
• Trane Communication Interface
Module: ICS interface control module
• Remote Human Interface Panel
(controls up to 4 units)
• Five ventilation override sequences
• Heating options: natural gas, electric,
hot water or steam
• Generic BAS interface
• Choose from three economizer control
options: comparative enthalpy,
reference enthalpy, dry bulb control
• Variable frequency drive control of
supply/exhaust fan motor
• Inlet guide vanes on FC supply fans
(VA V only)
• Outside air CFM compensation on VAV
units with IGV (or VFD) and economiz er
• Hot gas bypass to the evaporator inlet
• Copper evaporator/condenser coils
• Suction service valves
• Replaceable core filter driers
• Phenolic coated evaporator/condenser
coils
• High capacity evaporator coils
(20 to 105 tons)
• Special paint colors
• Extended casing (SX models)
• Double wall access doors
• Double wall construction/perforated
double wall
• Stainless steel drain pan in evaporator
section
• Pitch evaporator drain pan
• Filter rack only (no filters)
• High efficiency throwaway filters
• 90-95 percent bag filters
• 90-95 percent cartridge filters
• Final filters
• Barometric relief
• 50 percent modulating exhaust with
forward-curved fans
• T rane’s air quality (T raq™) sensor
• Modulating Gas Heat
• 10 year limited w arranty on Full
Modulation Gas Heat
• 100 percent modulating exhaust with
forward-curved fans
• 100 percent modulating exhaust with
FC fans and Statitrac™ direct space
sensing building pressurization control
• High duct temperature thermostats
• 0 F low ambient control
• 0-100 percent modulating fresh air
economizer
• Ultra low leak dampers for 0-100
percent modulating fresh air
economizers
• Dual electrical power connection
• T wo-inch spring fan isolation
(20 to 75 tons)
• High efficiency motors
• U-frame motors
• Oversized motors
• Thru the door non-fused disconnect
with external handle
• Electrical convenience outlet
• Power supply monitoring
• Correction capacitors
• Horizontal or Roof disc harge w/g asheat (20-75 tons “F” style units only)
Field Installed A ccessor ies
• Roof curbs
• Programmable sensors with night setback — CV and VAV
• Sensors without night set back — CV
and VA V
• Remote zone sensors — used for
remote sensing with remote panels.
• ICS zone sensors used with T racer®
system for zone control
• Outdoor temperature sensor for units
without economizers
• Remote minimum position control for
economizer
• Field installed module kits available for
field upgrade of controls
RT-PRC010-EN4
Features and
Benefits
Featur es Summary
IntelliPak® roof top features make
installation and servicing easy and
reliable operation a reality.
Installation Ease
• Factory-installed/commissioned
controls
—ease of star t up
—single twisted wire pair
—communication for ICS interface
—full unit points access, no field wir-
ing of required points
• Unit mounted Human Interface Panel
standard
—user friendly keypad — edit
parameters
—thru the access door interface
—start up adjustments
—unit mounted and remote in-
terface panel key pads are
identical
• Unit mounted lifting lugs facilitate
installation and can be used as unit
tiedown points.
Easy to Service
• The microprocessor unit controls
coordinates the operation of the
rooftop with quality , industry-accepted
components for service ease.
• Unit mounted Human Interface Panel
standard
—user friendly keypad — edit pa-
rameters
— thru the access door interface
— start up adjustments
— unit mounted and remote interface
panel key pads are identical
• Modularity of unit control design
—individual replaceable functional
boards
• Advanced diagnostics
Reliability
• Advanced diagnostics
• Microprocessor controls
• Built-in safeties
• Modular control design
• UL approval as standard
• Forward-curved supply and exhaust
fans are T rane designed and factory
balanced.
• Fully insulated and gasketed panels
reduce ambient air infiltration.
• Fixed-speed evaporator fan and
exhaust drive for smooth fan operation
and belt durability.
• 200,000 average life fan bearings
enhance unit durability.
• Gas heater with free-floating stainless
steel heat exchanger relieves the
stresses of expansion and contraction.
Stainless steel provides corrosion
resistance through the entire material
thickness.
• Integral condenser subcooler improves
efficiency while helping avoid liquid
flashing.
• Factory-wired and commissioned
controls assure efficient and reliable
rooftop operation.
• T rane Scroll compressors are used on
20 to 130 ton units. They are designed
for tough industrial operation and
meet demanding operating conditions
both in efficiency and reliability .
• Roll-formed construction enhances
cabinet integrity and assures a
leakproof casing.
• Three-phase, direct-drive condenser
fan motors enhance dependability and
increase rooftop life.
• T rane industrial quality evaporator
and condensing coils help increase
rooftop life.
Application Flexibility
• Modularity in design
• Increased offering of standard options
• Generic BAS interface
• Five factory preset/re-definable in the
field ventilation override sequences
• Superior Tracer® interface for ICS
applications
— factory-installed Trane
Communication Interface
• Unit mounted or Remote Human
Interface panels
— all parameter are editable from the
Human Interface Panel
• Comparative enthalpy, Reference
enthalpy, or Dry bulb control for
economizers
• Statitrac™ direct space building
pressure control
• Compensated outdoor air control —
IAQ
• Factory-installed filter rack includes
two-inch throwaw ay filters.
• CV controls stage both compressors
and heat based on space
requirements.
• Variable F requency Drives (VFD)
Included With or Without Bypass
Control for Supply and Exhaust Fans.
• An array of heating options are
available, including Steam, Hot Water,
Electric and Natural Gas heat. The Gas
Heating option provides a choice of
two-stage gas heat, as well as full and
limited modulating gas heat.
5RT-PRC010-EN
Integrated
Rooftop
Systems:
Pr ofitable,
Simple
Integrat ed Comfor t™
System (ICS)
T rane integrated rooftop systems make
design and installation of rooftop
comfort systems profitable and easy . The
Integrated Comfort™ system (ICS)
improves job profit and increases job
control by combining T rane rooftop units
and a T racer
system. This integrated system provides
total building comfort and control. The
primary motivation for building owners/
managers in making the purchasing
decision of HVA C controls system is no
longer just saving energy; it is having the
ability to automate their facilities and the
convenience of interface to control
systems.
Simplifying The Comfort System
At T rane, we think new tec hnology and
innovation should bring you more
capabilities, more flexibility and at the
same time be able to give you
equipment and systems that are easier
to use, easier to install, commission and
service. The Rooftop Integrated Comfort
system saves you time and money by
simplifying system design and system
installation. When used with Trane’s DDC/
VAV boxes (or VariTrane™), system
balancing almost goes away because
each VA V box is commission and tested
before it leaves the factory. All the status
information and editing data from the
rooftop units, VAV bo xes, lighting,
exhaust and other auxiliary equipment is
available from T racer for control,
monitoring and service support of your
®
building management
Features and
Benefits
facility. Tracer, a family of building
automation products from T rane, is
designed with robust, application
specific software pac kages to minimize
custom programming requirements and
enable system setup and control
through simple editing of parameters in
the standard applications software.
Should you select an Integrated Comfort
system for your facility, the
accountability for equipment,
automation and controls is T rane’s,
T rane’s, and T rane’s!
The IntelliPak
Integrated Comfort system, provides
powerful maintenance monitoring,
control and reporting capabilities. The
T racer places the rooftop in the
appropriate operating mode for
operation for: system on/off, night
setback, demand limiting , setpoint
adjustment based on outside
parameters and much more. Up to 48
different unit diagnostic conditions can
be monitored through T racer to let you
know about things like: sensor failures,
loss of supply airflow, and a compressor
trip out. Further, the addition of Building
Management Network software offers
remote scanning, automatic receipt of
alarms, and easy dial-up access to over
100 various T racer sites across town or
across the country.
T ypical points available through Tracer:
IntelliPak Rooft ops monit or ing points
av ailable through Tracer
• all active Rooftop diagnostics
• history of last 20 unit diagnostics
• all system setpoints
• system sensor inputs
• supply fan mode and status
• inlet guide vane position/VFD speed
• unit heat/cool mode
• exhaust fan status
• exhaust damper position
• economizer position, minimum
position setpoint, economizing
setpoint
• on/off status of eac h compressor
• refrigerant evaporator and saturated
condenser temperatures
• hydronic heat valve position
• electric heat stage status
• ventilation override mode status
®
rooftop, as a par t of an
Tracer control points for IntelliP ak
Rooftops
• cooling and heating setpoints
• zone setpoint offsets for use with
demand limiting
• VAV disc harge air setpoints
• supply air pressure setpoint
• space pressure setpoint
• zone and outdoor temperature values
• cooling and heating enable/disable
• economizer enable/disable
• economizer setpoint
• economizer minimum position
• activation of ventilation override
modes
• diagnostics reset
• unit priority shutdown
IntelliPak Rooft ops set-up and
configuration information through Tracer
• supply fan mode
• configuration of supply air reset
• ventilation override mode
configuration
• default system setpoint values
• sensor calibration offsets
®
RT-PRC010-EN6
Features and
Benefits
Optimum
Building
Comfort Control
The modular control design of the UCM
allows for greater application flexibility.
Customers can order exactly the options
required for the job, instead of one large
control package. Unit features are
distributed among multiple field
replaceable printed circuit boards. The
T rane UCM can be set up to operate
under one of three control applications:
1) stand-alone
2) interface with Trane’s Tracer® building
management system
3) interface with a generic (non-Trane)
building management system. All set-up
parameters are preset from the factory,
requiring less start-up time during
installation.
The unit mounted Human Interface and
the Remote Human Interface Panels’
functions are identical, except for the
Service mode is not available on the
Remote Human Interface Panel. This
common interface feature requires less
time for building maintenance personnel
to learn to interact with the unit. All of the
rooftop’s control parameters are
adjustable and can be set up through the
Remote Human Interface Panel suc h as,
but not limited to: system on/off,
demand limiting type, night setback
setpoints, and many other setpoints. No
potentiometers are required for setpoint
adjustment, all adjustments are done
through the Remote Human Interface
key-pad. Also up to 48 dif ferent roofto p
diagnostic points can be monitored
through the human interfaces such as:
sensor failures, loss of supply airflow,
and compressor trip. No special tools are
required for servicing of the unit. All
diagnostic displays are available in clear
English at the Remote Human Interface
and will be held in memory, so that the
operator/servicer can diagnose the root
cause of failures.
Statitrac™ Direct Space
Building Pressur ization Contr ol
T rane’s Statitrac™ control is a highly
accurate and efficient method of
maintaining building pressure control
with a large rooftop air conditioner.
The efficiency is achieved with a 1 00
percent modulating exhaust system with
two forward-curved fans with
modulating discharge dampers that
operate only when needed, compared to
some systems that operate continually.
And most of the operating hours of the
100 percent modulating exhaust system
are at part load, saving more energy.
T rane’s Statitrac, with the 100 percent
modulating exhaust system, provides
comfort and economy for buildings with
large rooftop air conditioning systems.
Statitrac control is simple! The space
pressure control turns the exhaust fans
on and off as required and modulates
exhaust dampers to maintain space
pressure within the space pressure dead
band. Using the unit mounted Human
Interface Panel you can
1) adjust space pressure setpoint
2) adjust space pressure dead band
3) measure and read building space
pressure. The modulating exhaust
system maintains the desired building
pressure, saving energy while keeping
the building at the right pressure. Proper
building pressurization eliminates
annoying door whistling, doors standing
open, and odors from other zones.
The Statitrac™ direct space building
control sequence will be maintained
when a variable frequency drive is used.
Fans With Inlet Guide V anes
T rane’s forward curved fans (20 through
75 tons) and air foil fans (90 through 130
tons) with inlet guide vanes pre-rotate
the air in the direction of the fan wheel,
decreasing static pressure and
horsepower, essentially unloading the
fan wheel. The unloading characteristics
of a Trane FC fan with inlet guide vanes
result in superior part load performance.
Variable Fr equency Driv es
(VFD)
V ariable Frequency Drives are factory
installed and tested to provide supply/
exhaust fan motor speed modulation.
VFD’s, as compared to inlet guide vanes
or discharge dampers, are quieter , more
efficient, and are eligible for utility
rebates. The VFD’s are available with or
without a bypass option. Bypass control
will simply provide full nominal airflow
in the event of drive failure.
7RT-PRC010-EN
Features and
Benefits
Trane 3-D® Scroll Compr essor
Simple Design with 70% Fewer Par ts
Fewer parts than an equal capacity
reciprocating compressor means
significant reliability and efficiency
benefits. The single orbiting scroll
eliminates the need for pistons,
connecting rods, wrist pins and valves.
Fewer parts lead to increased reliability .
Fewer moving parts, less rotating mass
and less internal friction means greater
efficiency than reciprocating
compressors.
The T rane 3-D Scroll provides impor tant
reliability and efficiency benefits. The 3-D
Scroll allows the orbiting scrolls to touch
in all three dimensions, forming a
completely enclosed compression
chamber whic h leads to increased
efficiency. In addition, the orbiting scrolls
only touch with enough force to create a
seal; there is no wear between the scroll
plates. The fixed and orbiting scrolls are
made of high strength cast iron which
results in less thermal distortion, less
leakage, and higher efficiencies. The
most outstanding feature of the 3-D
Scroll compressor is that slugging will
not cause failure. In a reciprocating
compressor, however , the liquid or dir t
can cause serious damage.
Low T orque V ariation
The 3-D Scroll compressor has a very
smooth compression cycle; torque
variations are only 30 percent of that
produced by a reciprocating compressor.
This means that the scroll compressor
imposes very little stress on the motor
resulting in greater reliability. Low torque
variation reduces noise and vibration.
Suction Gas Cooled Motor
Compressor motor efficiency and
reliability is further optimized with the
latest scroll design. Cool suction gas
keeps the motor cooler for longer life and
better efficiency.
Proven Design Through Testing and
Research
With over twenty years of development
and testing, T rane 3-D Scroll
compressors have undergone more
than 400,000 hours of laboratory testing
and field operation. This work combined
with over 25 patents makes Trane the
worldwide leader in air conditioning
scroll compressor technology .
One of two matched scroll plates — the
distinguishing feature of the scroll
compressor.
Chart illustrates low torque variation of
3-D Scroll compressor vs reciprocating
compressor.
RT-PRC010-EN8
Application
Considerations
EXHAUST AIR OPTIONS
When is it necessary to provide building
exhaust? Whenever an outdoor air
economizer is used, a building generally
requires an exhaust system. The purpose
of the exhaust system is to exhaust the
proper amount of air to prevent over or
underpressurization of the building. The
goal is to exhaust approximately 10
percent less air than the amount of
outside air going into the building. This
maintains a slightly positive building
pressure.
A building may have all or part of its
exhaust system in the rooftop unit. Often,
a building provides exhaust external to
the air conditioning equipment. This
external exhaust must be considered
when selecting the rooftop exhaust
system.
IntelliPak® Roof top units offer four types
of exhaust systems:
1
100 percent modulating exhaust with
Statitrac™ direct space sensing building
pressurization control (with or without
variable frequency drives).
2
100 percent modulating exhaust without
Statitrac.
3
50 percent power exhaust.
4
Barometric relief dampers.
Application Recommendations
1
100 percent modulating exhaust with
Statitrac™ control
For both CV and VAV rooftops, the 100
percent modulating exhaust discharge
dampers (or VFD) are modulated in
response to building pressure. A
differential pressure control system,
called Statitrac™, uses a differential
pressure transducer to compare indoor
building pressure to atmospheric
pressure. The FC exhaust fan is turned on
when required to lower building static
pressure to setpoint. The Statitrac control
system then modulates the discharge
dampers (or VFD) to control the building
pressure to within the adjustable,
specified dead band that is set at the
Human Interface Panel.
Advantages of the Statitrac™
100 percent modulating exhaust
system are:
a
The exhaust fan runs only when needed
to lower building static pressure.
b
Statitrac compensates for pressure
variations within the building from
remote exhaust fans and makeup
air units.
c
The exhaust fan discharges in a single
direction resulting in more efficient fan
operation compared to return fan
systems.
d
Because discharge dampers modulate
the airflow, the exhaust fan may be
running unloaded whenever the
economizer dampers are less than 100
percent open.
With an exhaust fan system, the supply
fan must be sized to pull the return air
back to the unit through the return
system during non-economizer
operation. However, a supply fan can
typically overcome return duct losses
more efficiently than a return air fan
system. Essentially, one large fan by itself
is normally more efficient than two fans
in series because of only one drive loss
not two as with return air systems.
The reason for either a return air fan or
an exhaust fan is to control building
pressure. The Trane 100 percent
modulating exhaust system with
Statitrac does a better job controlling
building pressure than return fans simply
because 100 percent modulating exhaust
discharge dampers (or VFD) are
controlled directly from building
pressure, rather than from an indirect
indicator of building pressure such as
outdoor air damper position.
The 100 percent modulating exhaust
system with Statitrac may be used on
any rooftop application that has an
outdoor air economizer. However, when
most exhaust is handled external to the
rooftop or when building pressure is not
critical, one of the other less expensive
methods of exhaust may be used.
9RT-PRC010-EN
Application
Considerations
2
100 Percent Exhaust S ystem
Competitive rooftops use a return air fan
system for controlling the amount of
exhaust air during economizer
operation. The return fan is in series with
the supply fan and must operate
whenever the supply fan is operating.
During economizer operation, the
economizer outdoor air dampers control
the position of the return and exhaust air
dampers, to exhaust the proper amount
of air. The disadvantage of a return air
fan is that it runs continuously, versus an
exhaust fan system which runs only
when needed to lower or maintain
building static pressure. Also, the return
fan must discharge air in two directions,
through the return air dampers and/or
exhaust air dampers, resulting in less
efficient operation compared to an
exhaust fan.
The IntelliPak® Roof top unit offers
modulating 100 percent exhaust system.
This fan system has performance
capabilities equal to the supply fan. The
FC exhaust fans are started by the
economizer’s outdoor air damper
position and the exhaust dampers track
the economizer outdoor air damper
position. The amount of air exhausted by
this fan is controlled by modulating
discharge dampers at the fan outlet. The
discharge damper position is controlled
by a signal that varies with the position
of the economizer dampers. When the
exhaust fans start, the modulating
discharge dampers are fully closed, and
exhaust airflow is 15 to 20 percent of
total exhaust capabilities.
3
50 Percent Exhaust S ystem
The 50 percent exhaust system is a
single FC exhaust fan with half the air moving capabilities of the supply fan
system. The experience of The T rane
Company is that a non-modulating
exhaust system selected for 40 to 50
percent of nominal supply CFM can be
applied successfully.
The 50 percent exhaust system generally
should not be selected for more than 40
to 50 percent of design supply airflow.
Since it is an on/off nonmodulating
system, it does not vary exhaust CFM
with the amount of outside air entering
the building. Therefore, if selected for
more than 40 to 50 percent of supply
airflow, the building may become under -
pressurized when economizer operation
is allowing lesser amounts of outdoor air
into the building. If, however , building
pressure is not of a critical nature, the
non-modulating exhaust system may be
sized for more than 50 percent of design
supply airflow.
4
Barometr ic Relief D ampers
Barometric relief dampers consist of
gravity dampers which open with
increased building pressure. As the
building pressure increases, the pressure
in the unit return section also increases,
opening the dampers and relieving air.
Barometric relief may be used to provide
relief for single story buildings with no
return ductwork and exhaust
requirements less than 25 percent.
Figure AC-1 — Plan View of Modulating 100 Percent Exhaust Syst em
RT-PRC010-EN10
Application
Considerations
Horizontal Dischar g e
The typical rooftop installation has both
the supply and return air paths routed
through the roof curb and building roof.
However, many roof top installations
require horizontal supply and/or return
from the rooftop because of a building’s
unique design or for acoustic
considerations.
T rane has two ways to accomplish
horizontal supply and/or return. The first
applies to all IntelliPak® Ro oftop units.
Special field supplied curbs are installed
that use the unit’s standard discharge
and return openings. The supply and
return air is routed through the curb to
horizontal openings on the sides of the
curb. The second method available for
20 - 75 tons SXHF, SFHF, SLHF, SSHF, and
90 - 130 tons SXHG, SLHG and SSHG
design units ONLY . With this method the
standard discharge and return openings
are blocked in the field. Access panels
are removed as indicated in Figures AC -1
and AC-2. These openings are used for
the discharge and return. No special
curb is needed.
SXHF, SFHF, SLHF, SSHF Units
Figure AC-1 is a simplified sketch of the
rooftop showing whic h panels can be
used for horizontal supply and/or return.
To supply air horizontally, the panels that
normally house the heat accessory
controls (Panel A) and the gas heat
barometric dampers (Panel B) can be
removed and either of the openings
horizontal supply and return applies to
Figure AC-2 Horizontal Discharge Panel Dimensions — 20 - 75 T ons SXHF, SFHF, SLHF, SSHF Units
Note: Cannot remove Panel A
for horizontal discharge on
SFHF, SLHF, SSHF Units.
used as a unit discharge (see note 1). To
return air horizontally, the exhaust fan
access door (Panel C) can be removed
and used as a return opening. T ables A C1, 2 and 3 show dimensions for those
panels.
Horizontal Disc harge on SXHF, SFHF,
SLHF and SSHF Rooftops (20 t o 75 tons)
The SXHF (extended casing cooling
only), SFHF (gas heat), SSHF (steam
heat) and SLHF (hot water heat) rooftops
can be field modified to supply and
return air horizontally without the use of
a horizontal supply/return curb.
To supply air horizontally on SXHF only,
the panels that normally house the heat
accessory controls (Panel A) and the g as
heat barometric dampers (Panel B) can
be removed and either of the openings
used as a unit discharge. To return air
horizontally, the exhaust fan access door
(Panel C) can be removed and used as a
return opening.
1. For horizontal discharge on SFHF, SLHF and SSHF
units, only the Panel B can be removed. Panel A
cannot be used due to the location of the heating
coils.
2. For horizontal discharge on SFHF (gas heat) models,
the block off under the heater must be removed.
After removal, a support must be added for the drain
tube.
3. Supply and Return Base openings must be covered
when converting to a horizontal configuration.
T able A C-1 — SXHF, SFHF, SSHF, SLHF —
Panel A and B Dimensions
1. Add an extra 0.20-inches pressure drop to the supply external static to account for the extra turn the air is making.
2. The openings all have a 1.25-inch lip around the perimeter to facilitate ductwork attachment.
3. If exhaust fans are being used, provisions should be made for access to the exhaust components, since the access door is now being used as a return.
4. Use the dimensions provided and the supply Cfm to calculate the velocity (ft/min) through the openings to be sure they are acceptable.
T otal Area (H X W)
T able AC-2 — SXHF, SFHF, SSHF, SLHF —
Panel C Dimensions
Figure AC-3 is a simplified sketch
showing which panels can be used for
horizontal supply and/or return. On 90 to
130 ton units, only one side of the
extended casing may be used for
horizontal supply because of the
location of the unit control panel. There
are, however, on SXHF models two
panels (Panels A) on the side opposite
the control box which can be removed
along with the vertical support which
separates the two. Removal of the
vertical support is optional, but will
ensure maximum airflow. On SLHG,
SSHG models only one of the Panel A ’s
may be used for horizontal supply
Figure AC-3 — Hor izontal Disc harg e Panel Dimensions — 90 - 130 Tonss SXHG, SLHG, SSHG Units
because of the location of the heating
coil. Horizontal return is accomplished in
much the same w ay as on S*HFs by
removing the exhaust fan access door
(Panel B). See Tables AC-4 and 5 for
S*HG panel dimensions.
When using an IntelliPak® R ooftop for
horizontal supply and return, an
additional pressure drop must be added
to the supply external static to account
for the 90 degree turn the air is making.
This additional pressure drop depends
on airflow and rooftop size, but a range
of 0.10 inc hes to 0.30 inches can be
expected. The openings on the rooftop
all have a one inch lip around the
perimeter to facilitate ductwork
attac hment. If exhaust fans are being
used on an IntelliPak Roof top unit with
horizontal return, provisions should be
made for access to the exhaust
components, since the access door
opening is now being used as a return.
Perhaps the return ductwork attac hment
to the rooftop can include a section of
removable duct. Use the dimensions
provided and the supply and exhaust
CFM to calculate the velocity (ft/min)
through the openings.
Horiz ontal Dischar g e SXHG, SLHG,
SSHG Rooftops (90 t o 130 tons)
The SXHG, SLHG, SSHG rooftops can be
field modified to supply and return air
horizontally without the use of a
horizontal supply/return curb.
To supply air horizontally, use Panel A
only. The Panel on the opposite side
cannot be used due to the location of the
unit control Panel. SXHG rooftop air
conditioners do not have a panel
configuration like the 20 to 75 ton
rooftops. To achieve maximum airflow,
vertical support can be remo ved af ter the
unit has been placed on the roof curb. It
is secured by four screws. (See Note 1)
For horizontal discharge on SLHG and
SSHG units, only the Panel A next to the
condenser fan section can be removed.
The other Panel A next to the supply fan
cannot be used due to the location of the
heating coils.
To return air horizontally, the exhaust fan
access door (Panel B) can be removed
and used as a return opening.
Note:
1. SXHG units have two Panel A’s that can be removed. Once unit is installed, panel(s) and the 61/2” vertical
support channel in between may be removed.
T able A C-4 — SXHG, SLHG, SSHG —
Panel A and B Dimensions
Panel H (in.)W (in.)(in.2)(ft2)
A72.727.5199913.9
B72.734.5250817 . 4
Notes:
1. Add an extra 0.20-inches pressure drop to the
supply external static to account for the extra turn
the air is making.
2. The openings all have a 1.25-inch lip around the
perimeter to facilitate ductwork attachment.
T otal Area (H X W)
T able AC-5 — SXHG, SLHG, SSHG —
X, Y and Z Dimensions
ModelX (in.)Y (in.)Z (in.)
S*HG 90-13069.077.8244.7
* = X, L, or S
3. If exhaust fans are being used, provisions should
be made for access to the exhaust components,
since the access door is now being used as a
return.
4. Use the dimensions provided and the supply Cfm
to calculate the velocity (ft/min) through the
openings to be sure they are acceptable.
RT-PRC010-EN12
Application
Considerations
High Capacity Evaporator Coil
Rooftops are popular because of their
“pac kaged” nature. Everything needed
is contained in one box; mix-matc hing is
neither necessary nor available. With this
convenience comes some
disadvantages; one is the rooftop’s
cooling capacity may not exactly match
the building load. It is conceivable that a
50 ton rooftop would need to be used on
an application that is 41 tons, simply
because the 40 ton rooftop does not
meet capacity.
In order to avoid suc h occurrences, and
to more closely match the roof top’s
capacity to the building load, a high
capacity evaporator coil option is
available on all IntelliPak® Ro oftops 20 to
105 tons. These high capacity coils have
an increased number of evaporator coil
rows as compared to standard and
enhanced evaporator tube surfaces,
resulting in a higher capacity. Capacity
tables for both standard and high
capacity coils are available in the cooling
data section of this catalog. See T able
PD-43 for the pressure drops associated
with the high capacity coil option. This
pressure drop should be added to the
total static pressure used to size the
supply fan motor.
Low Ambient Operation — Human
Interface Recommendations
Who wants to be on a roof at sub-zero
temperatures? We can understand a
service technician’s reluctance to do this;
that’s why we recommend using a
remote mounted Human Interface Panel.
The service technician can troubleshoot
and diagnose in the comfort of a
mechanical room.
Corr osive Atmospheres
T rane’s IntelliPak® R ooftops are
designed and built to industrial
standards and will perform to those
standards for an extended period
depending on the hours of use, the
quality of maintenance performed, and
the regularity of that maintenance. One
factor that can have an adverse effect on
unit life is its operation in a corrosive
environment.
When rooftops are operated in corrosive
environments, T rane recommends that
copper fins be utilized on the condenser
and/or evaporator coil. Because copper
is more resistant to corrosion than
aluminum, coil life expectancy is greatly
increased. Some industry applications
expose equipment to corrosive agents
that even copper cannot fully resist. For
those special applications, a baked
phenolic resin coating (i.e. Heresite) is
highly desirable. Baked phenolic
coatings or copper fins on the condenser
and/or evaporator coils are available on
T rane’s IntelliPak Rooftops.
V entilation Override Sequences
One of the benefits of using an exhaust
fan rather than a return fan, in addition
to the benefits of lower energy usage
and improved building pressurization
control, is that the rooftop can be used
as part of a ventilation override system.
Several types of sequences can be easily
done when exhaust fans are a part of the
rooftop system.
What would initiate the ventilation
override control sequence? Typically, a
manual switch is used and located near
the fire protection control panel. This
enables the fire department access to the
control for use during or after a fire. It is
also possible to initiate the sequence
from a field-installed automatic smoke
detector. In either case, a contact closure
begins the ventilation override control
sequence. CAUTION!: The ventilation
override system should not be used to
signal the presence of smok e caused by
a fire.
T rane can provide five (5) different
ventilation override sequences on both
CV and V AV IntelliPak® Rooftops. For
your convenience the sequences can be
factory preset or fully field editable from
the Human Interface Panel or T racer®.
Any or all five sequences may be
“loc ked” in by the user at the Human
Interface Panel.
The user can customize up to five (5)
different over ride sequences for
purposes such as smoke control. The
following parameters within the unit can
be defined for each of the five
sequences:
• Supply Fan — on/off
• Inlet Guide Vanes — open/closed/
controlling
• Var iable F r equency Dr iv es — on (60
Hz)/off (0 Hz)/controlling
• Exhaust Fan — on/off
• Exhaust Dampers — open/closed
• Economizer dampers — open/closed
• Heat — off/controlling (output f or) V AVBoxes — open/controlling
Compressors and condenser fans are
shut down for any Ventilation Override
sequence. Factory preset sequences
include unit Off, Exhaust, Purge, Purge
with duct pressure control, and
Pressurization. An y of the user-defined
Ventilation Over ride sequences can be
initiated by closing a field supplied
switch or contacts connected to an input
on the Ventilation Override Module. If
more than one ventilation override
sequence is being requested, the
sequence with the highest priority is
initiated. Refer to the Sequence of
Operation provided in the Control
section of this catalog for more details
on each over ride sequence.
Natural Gas Heating Considerations
The IntelliPak standard, or limited
modulation, gas heat exc hangers are not
recommended for applications with
mixed air conditions entering the heat
exchanger below 50°F. Mixed air
temperatures below 50°F can cause
condensation to form on the heat
13RT-PRC010-EN
Application
Considerations
exchanger , leading to premature failure.
For increased reliability , the
recommendation in these applications is
full modulation gas heat. For airflow
limitations and temperature rise across
the heat exchanger information, see
Table PD-24, 25 and RT-EB-1 04.
Acoustical Considerations
The ideal time to make provisions to
reduce sound transmission to the space
is during the project design phase.
Proper placement of rooftop equipment
is critical to reducing transmitted sound
levels to the building. The most
economical means of avoiding an
acoustical problem is to place any
rooftop equipment away from
acoustically critical area. If possible,
rooftop equipment should not be located
directly above areas such as: of fices,
conference rooms, executive office areas
and classrooms. Ideal locations are
above corridors, utility rooms, toilet
facilities, or other areas where higher
sound levels are acceptable.
Several basic guidelines for unit
placement should be followed to
minimize sound transmission through
the building structure:
1
Never cantilever the condensing section
of the unit. A structural cross member
must support this end of the unit.
2
Locate the unit’s center of gravity close
to or over a column or main support
beam to minimize roof deflection and
vibratory noise.
3
If the roof structure is very light, roof
joists should be replaced by a structural
shape in the critical areas described
above.
4
If several units are to be placed on one
span, they should be staggered to
reduce deflection over that span.
It is impossible to totally quantify the
effect of building structure on sound
transmission, since this depends on the
response of the roof and building
members to the sound and vibration of
the unit components. However, the
guidelines listed above are experience
proven guidelines which will help reduce
sound transmission.
There are several other sources of unit
sound, i.e., supply fan, compressors,
exhaust fans, condenser fans and
aerodynamic noise generated at the duct
fittings. Refer to the ASHRAE
Applications Handbook, Chapter 42, 1991
edition for guidelines for minimizing the
generation of aerodynamic noise
associated with duct fittings.
T rane’s Engineering Bulletin RT-EB-80
describes various duct installation
considerations specifically addressing
indoor sound level concerns. This
bulletin includes sound power data on
T rane’s IntelliPak Rooftops 20 to 1 30 tons.
Ask your local T rane representative for
this informative engineering bulletin.
The V ariTrane® Computeriz ed Duct
Design Program can be used to analyze
the truck duct, run-out duct, VAV control
unit and terminal unit noise attenuation.
This program quantifies the airborne
sound generation that can be expected
in each terminal so that the designer can
identify potential sound problems and
make design alterations before
equipment installation.
The Trane Acoustics Program (TAP)
allows modeling of rooftop installation
parameters. The output of this program
shows the resulting indoor NC level for
the modeled installation. This program is
available from T rane’s Customer Direct
Service Network™ (C.D.S.), ask your
local T rane representative for additional
information on this program.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. A reduction in
unit clearance could result in condenser
coil starvation or warm condenser air
recirculation. If the clearances shown are
not possible on a particular job, consider
the following:
• Do the clearances available allow for
major service work such as c hanging
compressors or coils?
• Do the clearances available allow for
proper outside air intake, exhaust air
removal and condenser airflow?
• If screening around the unit is being
used, is there a possibility of air
recirculation from the exhaust to the
outside air intake or from condenser
exhaust to condenser intake?
Actual clearances which appear
inadequate should be reviewed with a
local T rane sales engineer .
When two or more units are to be placed
side by side, the distance between the
units should be increased to 150 percent
of the recommended single unit
clearance. The units should also be
staggered as shown in Figure AC-4 for
two reasons:
1
To reduce span deflection if more than
one unit is placed on a single span.
Reducing deflection discourages sound
transmission.
2
To assure proper diffusion of exhaust air
before contact with the outside air intake
of adjacent unit.
RT-PRC010-EN14
Application
Considerations
Duct Design
It is important to note that the rated
capacities of the rooftop can be met only
if the rooftop is properly installed in the
field. A well-designed duct system is
essential in meeting these capacities.
The satisfactory distribution of air
throughout the system requires that
there be an unrestricted and uniform
airflow from the rooftop disc harge duct.
This discharge section should be straight
for at least several duct diameters to
allow the conversion of fan energy from
velocity pressure to static pressure.
However, when job conditions dictate
elbows be installed near the rooftop
outlet, the loss of capacity and static
pressure may be reduced through the
use of guide vanes and proper direction
of the bend in the elbow. The high
velocity side of the rooftop outlet should
be directed at the outside radius of the
elbow rather than the inside as
illustrated in Figure AC-5.
Figure AC-4 — Unit Placement
1
2
1. 20-40 ton models have only one outdoor air intake.
50 - 75 ton models have two outdoor air intakes.
2. 90-130 ton models have two outdoor air intakes on
the backside of the unit and one small air intake at
the end of the unit.
Improper
Figure AC-5 — Duct Design
Proper
15RT-PRC010-EN
Selection
Pr ocedure
This section outlines a step-by-step
procedure that may be used to select a
T rane single-zone air conditioner. The
sample selection is based on the
following conditions:
• Return air duct negative static pressure
— 0.65 in wg
Electrical Character istics:
• Voltage/cycle/phase — 460/60/3 Unit
Accessories:
• Gas fired heat exchanger — high heat
module
• Throwaway filters
• Economizer
• Modulating 100 percent exhaust/
return fan
COOLING CAP A CITY SELECTION
Step 1 — Nominal Unit Size Selection
A summation of the peak cooling load
and the outside air ventilation load
shows: 430 MBh + 66.9 MBh = 496.9
MBh required unit capacity. F rom
Table PD-9, a 50 ton unit capacity with
standard capacity evaporator coil at
80 DB/65 WB, 95 F outdoor air
temperature and 17,500 total supply cfm
is 551 MBh total and 422 MBh sensible.
Thus, a nominal 50 ton unit with
standard capacity evaporator coil
is selected.
Step 2 — Evapor ator Coil Ent er ing
Conditions
Mixed air dry bulb temperature
determination:
Using the minimum percent of OA (1,750
cfm ÷ 17,500 cfm = 10 percent),
determine the mixture dry bulb to the
evaporator.
RADB + % OA (O ADB - RADB) = 80 +
(0.10) (95 - 80) = 80 + 1.5 = 81 .5 F
Approximate wet bulb mixture
temperature:
RAWB + % O A (O A WB - RA WB) = 65 +
(0.10) (7 6 - 65) = 65 + 1.1 = 66.1 F
Step 3 — Determine Supply Fan Motor
Heat Gain
Having selected a nominal 50 ton unit,
the supply fan bhp can be calculated. The
supply fan motor heat gain must be
considered in final determination of unit
capacity.
Supply Air Fan
Determine unit total static pressur e at
design supply cfm:
External Static Pressure1.2 inches
Evaporator Coil0.25 inches
(Table PD-43)
Return Duct Negative0.65 inches
Static Pressure
Heat Exchanger0.31 inches
(Table PD-43)
Throwaway Filter0.10 inc hes
(Table PD-43)
Economizer w/Exhaust Fan0.12 inches
(Table PD-43)
T rane Roof Curb0.13 inches
(Table PD-43)
Unit T otal Static P ressure2.7 6 inches
Using total of 17,500 cfm and total
static pressure of 2.76 inches, enter Table
PD-36. T able PD-36 shows 1 5.3 bhp with
924 rpm.
From Chart SP-1 supply fan motor heat
gain = 46.0 MBh.
Step 4 — Determine Total Required
Cooling Capacity
Required capacity = Total peak load + OA
load + supply air fan motor heat.
Required capacity = 430 + 66.9 +
46.0 = 543 MBh (45.2 tons)
Step 5 — Determine Unit Capacity
From Table PD-9, unit capacity at 81.5 DB/
66.1 WB entering the evaporator, 17,500
supply air cfm, 95 F outdoor ambient, is
561 MBh (45.8 tons) with 426 MBh
sensible.
Step 6 — Deter mine Lea ving Air
Temperature
Unit sensible heat capacity corrected for
supply air fan motor heat = 426 MBh - 46
MBh = 380 MBh.
Supply air dry bulb temperature
difference =
Sensible Btu =
1.085 x Supply cfm
380 MBh ÷ (1.085 x 17,500 cfm)
= 20.0 F
Supply air dry bulb = 81.5 DB - 20.0
= 61.5 F
Unit enthalpy difference =
Total Btu =
4.5 x Supply cfm
561 MBh ÷ (4.5 x 17,500 cfm) =
7.12 Btu/lb
Leaving enthalpy = h(ent WB) -
h(diff). From Table 21-1 h(ent WB) =
30.9 Btu/lb
Leaving enthalpy = 30.9 Btu/lb - 7.12
Btu/lb = 23.78 Btu/lb
Supply air wet bulb = 55.9
Leaving air temperature = 61.5
DB/55.9 WB
RT-PRC010-EN16
Selection
Pr ocedure
HEA TING CAPACITY SELECTION
Step 1 — Determine Air Temperatur e
Entering Heating Module
Mixed air temperature = RADB + % OA
(OADB - RADB) = 70 + (0.10) (0 - 70) = 63
F
Supply air fan motor heat temperature
rise = 46,000 Btu ÷ (1 .085 x 1 7,500 cfm) =
2.42 F
Air temperature entering heating
module = 63.0 + 2.42 = 65.4 F
Step 2 — Deter mine Total Winter Heating
Load
Total winter heating load = peak heating
load + ventilation load - supply fan
motor heat = 475 + 133 - 46.0 = 562 MBh
Electric Heating System
Unit operating on 460/60/3 power supply.
From Table PD-30, kw may be selected
for a nominal 50 ton unit operating
460-volt power. The 170 kw heat module
(580.1 MBh) will satisfy the winter
heating load of 563 MBh.
Table PD-28 shows an air temperature
rise of 30.6 F for 17,500 cfm through
the 170 kw heat module.
Unit supply temperature at design
heating conditions = mixed air
temperature + air temperature rise = 65.4
F + 30.6 F = 96.0 F.
Gas Heating System (Natural Gas)
From Table PD-24 select the high heat
module (697 MBh output) to satisfy
winter heating load of 563 MBh at unit
cfm.
Table PD-26 also shows an air
temperature rise of 36.0 F for 17,500 cfm
through the heating module.
Unit supply temperature at design
heating conditions = mixed air
temperature + air temperature rise = 65.4
F + 36.0 F = 10 1.4 F.
Hot Water Heating
Assume a hot water supply temperature
of 190 F. Subtract the mixed air
temperature from the hot water
temperature to determine the ITD (initial
temperature difference).
Chart SP-1 — Fan Motor Heat
120
110
100
90
80
70
60
50
40
FAN MOTOR HEAT - MBH
30
20
10
0
0510152025303540
MOT OR BRAKE HO RSE POW ER
ITD = 190 F - 65.4 F = 125 F. Divide the
winter heating load by ITD = 563 MBh ÷
125 F = 4.50 Q/ITD.
From Table PD-31, select the low heat
module. By interpolation, a Q/ITD of 4.50
can be obtained at a gpm at 25.7.
Water pressure drop at 25.7 gpm is 0.57
ft. of water . Heat module temperature
rise is determined by:
Total Btu = ∆T
1.085 x Supply cfm
563,000 = 29.7 F
(1.085 x 17,500)
Unit supply air temperature = mixed air
temperature + air temperature rise = 65.4
+ 29.7 = 95 F.
Steam Heating System
Assume a 15 psig steam supply .
From Table PD-27, the saturated
temperature steam is 250 F. Subtract
mixed air temperature from the steam
STANDARD MOTOR
HIGH EFF ICIENCY MOTOR
temperature to determine ITD. ITD = 250
F - 65.4 F = 185 F.
Divide winter heating load by ITD =
563 MBh ÷ 185 F = 3.04 Q/ITD.
From Table PD-26, select the high heat
module. The high heat module at 17,500
cfm has a Q/ITD = 5.11.
Heat module capacity, Q = ITD x Q/ITD =
185 F x 5.11 Q/ITD = 945 MBh
Heat module air temperature rise
=
Total Btu
1 .085 x Supply cfm
945 Btu ÷ (1 .085 x 17,500 cfm) = 49.8 F.
Unit supply temperature at design
conditions = mixed air temperature + air
temperature rise = 65.4 F + 49.8 F = 115 F.
17RT-PRC010-EN
Selection
Pr ocedure
AIR DELIVERY PROCEDURE
Supply fan performance tables include
internal resistance of rooftop. For total
static pressure determination, system
external static must be added to
appropriate component static pressure
drop (evaporator coil, filters, optional
economizer , optional exhaust fan,
optional heating system, optional
cooling only extended casing, optional
roof curb).
Supply Fan Motor Sizing
The supply fan motor selected in the
cooling capacity determination was 15.3
bhp and 924 rpm. Thus, a 20 hp supply
fan motor is selected. Enter T able PD-45
to select the proper drive. For a 50 ton
rooftop with 20 hp motor , a drive
number 9 — 900 rpm is selected.
Exhaust Fan Motor Sizing
The exhaust fan is selected based on
total return system negative static
pressure and exhaust fan cfm. Return
system negative static include return
duct static and roof curb static pressure
drop.
Return duct static pressure = 0.65 inches
T rane roof curb (Table PD-43) = 0.12
inches
Total return system negative static
pressure = 0.77 inches
Exhaust fan cfm = 12,000 cfm
From Table PD-47, the required bhp is
3.45 hp at 574 rpm. Thus, the exhaust fan
motor selected is 5 hp.
To select a drive, enter T able PD-49 for a 5
hp motor for a 50 ton unit. Drive
selection number 6 — 600 rpm.
Where altitudes are significantly above
sea level, use T ables PAF-2 and PAF-3 and
Figure P AF-1 for applicable correction
factors.
UNIT ELECTRICAL REQUIREMENTS
Selection procedures for electrical
requirements for wire sizing amps,
maximum fuse sizing, and dual element
fuses are given in the electrical service
section of this catalog.
Altitude Corrections
The rooftop performance tables and
curves of this catalog are based on
standard air (.075 lbs/ft). If the rooftop
airflow requirements are at other than
standard conditions (sea level), an air
density correction is needed to project
accurate unit performance.
Figure P AF-1 shows the air density ratio
at various temperatures and elevations.
T rane rooftops are designed to operate
between 40 and 90 degrees Fahrenheit
leaving air temperature.
The procedure to use when selecting a
supply or exhaust fan on a rooftop for
elevations and temperatures other than
standard is as follows:
1
First, determine the air density ratio
using Figure P AF-1.
2
Divide the static pressure at the
nonstandard condition by the air
density ratio to obtain the corrected
static pressure.
3
Use the actual cfm and the corrected
static pressure to determine the fan rpm
and bhp from the rooftop performance
tables or curves.
4
The fan rpm is correct as selected.
5
Bhp must be multiplied by the air
density ratio to obtain the actual
operating bhp.
RT-PRC010-EN18
Selection
Pr ocedure
In order to better illustrate this
procedure, the following example is
used:
Consider a 60 ton rooftop unit that is to
deliver 18,000 actual cfm at 3-inches total
static pressure (tsp), 55 F leaving air
temperature, at an elevation of 5,000 ft.
1
From Figure PAF-1, the air density ratio is
0.86.
2
Tsp = 3.0-inches / 0.86 = 3.49 inc hes tsp.
3
From the performance tables: a 60 ton
rooftop (without inlet vanes) will deliver
18,000 cfm at 3.49-inches tsp at 906 rpm
and 21 .25 bhp.
4
The rpm is correct as selected - 906 rpm.
5
Bhp = 21 .25 x 0.86 = 18.3 bhp actual.
Compressor MBh, SHR, and kw should
be calculated at standard and then
converted to actual using the correction
factors in Table PAF-2. Apply these factors
to the capacities selected at standard cfm
so as to correct for the reduced mass
flow rate across the condenser.
Heat selections other than gas heat will
not be affected by altitude. Nominal gas
capacity (output) should be multiplied by
the factors given in Table PAF -3 before
calculating the heating supply air
temperature.
HEA TING CAPACITY SELECTION
Step 1 — Determine Air Temperatur e
Entering Heating Module
Mixed air temperature = RADB + % OA
(OADB - RADB) = 70 + (0.10) (0 - 70) = 63
F
Supply air fan motor heat temperature
rise = 46,000 Btu ÷ (1 .085 x 1 7,500 cfm) =
2.42 F
Air temperature entering heating
module = 63.0 + 2.42 = 65.4 F
19RT-PRC010-EN
Model
Number
Description
S F H F C 5 5 F H A 5 5 C 6 9 D 3 0 0 1 0 0 0 0 0 0 0 0 00 0 0 00 0 0 0 0
1 2 3 45 6 7 8 9 10 1112131415161718192021222324252627 28 29 30 31 32 33 34 35 36 37 38
DIGIT 1 — UNIT TYPE
S = Self-Contained (Packaged Rooftop)
DIGIT 2 — UNIT FUNCTION
A = DX Cooling, No Heat
E = DX Cooling, Electric Heat
F = DX Cooling, Natural Gas Heat
L = DX Cooling, Hot Water Heat
S = DX Cooling, Steam Heat
X = DX Cooling, No Heat, Extended Casing
DIGIT 8 — POWER SUPPLY (See Notes)
4 = 460/60/3 XL E = 200/60/3 XL
5 = 575/60/3 XL F = 230/60/3 XL
Note: SEHF units (units with electric heat)
utilizing 208V or 230V require dual power
source.
DIGIT 9 — HEATING CAPACITY
Note: When the second digit calls for “F”
(Gas Heat), the following values apply:
Additionally, please note G and M available
ONLY on 50 Ton models and above.
H = High Heat-2-Stage P = High Heat-Full
L = Low Heat-2-Stage Modulation
0 = No HeatM = Low Heat-Full
J = High Heat-LimitedModulation
Modulation
G = Low Heat-Limited
Modulation
Note: When the second digit calls for “E”
(electric heat), the following values apply:
D = 30 KWR = 130 KW
H = 50 KWU = 150 KW
L = 70 KWV = 170 KW
N = 90 KWW = 190 KW
Q = 110 KW
Note: When the second digit calls for ‘’L’’
(Hot Water) or ‘’S’’(Steam) Heat, one of the
following valve size values must be in Digit
9:
High Heat Coil: 1 = .50”, 2 = .75”, 3 = 1”,
4 = 1.25”, 5 = 1.5”, 6 = 2”.
Low Heat Coil: A = .50”, B = .75”, C = 1”,
D = 1.25”, E = 1.5”, F = 2”.
DIGIT 10 — DESIGN SEQUENCE
A = First (Factory Assigned)
Note: Sequence may be any letter A thru Z,
or any digit 1 thru 9.
DIGIT 11 — EXHA UST OPTION
0 = None
1 = Barometric
2 = 100%, 1.5 HP W/Statitrac
3 = 100%, 3 HP W/Statitrac
4 = 100%, 5 HP W/Statitrac
5 = 100%, 7.5 HP W/Statitrac
6 = 100%, 10 HP W/Statitrac
7 = 100%, 15 HP W/Statitrac
8 = 100%, 20 HP W/Statitrac
A = 50%, 1.5 HP
B = 50%, 3 HP
C = 50%, 5 HP
D = 50%, 7.5 HP
E = 100%, 1.5 HP W/O Statitrac (CV Only)
F = 100%, 3 HP W/O Statitrac (CV Only)
G = 100%, 5 HP W/O Statitrac (CV Only)
H = 100%, 7.5 HP W/O Statitrac (CV Only)
J = 100%, 10 HP W/O Statitrac (CV Only)
K = 100%, 15 HP W/O Statitrac (CV Only)
L = 100%, 20 HP W/O Statitrac (CV Only)
A = Throwaway
B = Cleanable Wire Mesh
C = High-Efficiency Throwaway
D = Bag With Prefilter
E = Cartridge With Prefilter
F = Throwaway Filter Rack Less Filter
Media
G = Bag Filter Rack Less Filter Media
DIGIT 14 — SUPPLY AIR FAN HP
1 = 3 HP4 = 10 HP7 = 25 HP
2 = 5 HP5 = 15 HP8 = 30 HP
3 = 7.5 HP6 = 20 HP9 = 40 HP
376= Factory-Powered 15A GFI
385= VFD Line Reactor
Comparative Enthalpy
Reference Enthalpy
Thermostat
and Exhaust)
tion Bridge
Interface Module
Convenience Outlet
1
RT-PRC010-EN20
Model
Number
Description
SX H G D 1 1 4 O A H 7 C F 9 D 3 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 2 3 4 5678 9 10111213141516171819 2021222324252627 282930313233343536
DIGIT 1 — UNIT TYPE
S = Self-Contained (Packaged Rooftop)
DIGIT 2 — UNIT FUNCTION
E = DX Cooling, Electric Heat
F = DX Cooling, Natural Gas Heat
L = DX Cooling, Hot Water Heat
S = DX Cooling, Steam Heat
X = DX Cooling, No Heat, Extended Casing
DIGIT 3 — UNIT AIRFLOW
H = Single Zone
DIGIT 4 — DEVELOPMENT SEQUENCE
G = Seventh
DIGITS 5,6,7 — NOMINAL CAPACITY
C90 = 90 Tons
D11 = 105 Tons
D12 = 115 T ons
D13 = 130 Tons
DIGIT 8 — POWER SUPPLY
4 = 460/60/3 XL
5 = 575/60/3 XL
E = 200/60/3 XL
F = 230/60/3 XL
DIGIT 9 — HEATING CAPACITY
0 = No Heat
H = High Heat - 2-Stage
J = High Heat - Limited Modulation
P = High Heat - Full Modulation
Note:
When the second digit calls for “E”
(electric heat), the following values apply
in the ninth digit:
W = 190 KW
When the second digit calls for ‘’L’’ or
‘’S’’, one of the following valve size
values must be in Digit 9:
High Heat Coil: 3 = 1.0”, 4 = 1.25”, 5 =
1.50”, 6 = 2.0”, 7 = 2.5”
Low Heat Coil: C = 1.0”, D = 1.25”, E =
1.50”, F = 2.0”, G = 2.5”
DIGIT 10 — DESIGN SEQUENCE
A = First (Factory Assigned)
Note: Sequence may be any letter A thru
Z, or any digit 1 thru 9.
DIGIT 11 — EXHAUST OPTION
0 = None
7 = 100%, 15 HP W/Statitrac
1. EXAMPLE: Model numbers: SFHFC55FHA55C69D3001N describes a unit with the following characteristics: DX
cooling with natural gas heating, 55 ton nominal cooling capacity, 230/60/3 power supply, high heat model. 100
percent exhaust with Statitrac, 7.5 HP exhaust fan motor with drive selection No. 5 (500 RPM), high-efficiency
throwaway filters, 20 HP supply fan motor with drive selection No. 9 (900 RPM), 0-100% economizer, VAV supply air
temperature control with inlet guide vanes, no remote panel, standard ambient control, U.L. agency approval. The
service digit for each model number contains 38 digits; all 38 digits must be referenced.
2. EXAMPLE: Model numbers: SXHGD1140AH7CF8D3001 describes a unit with the following characteristics: DX
cooling with extended casing, no heat, 105 ton nominal cooling capacity, 460/60/3 power supply, no heat, 100
percent exhaust with Statitrac, 30 h.p. exhaust fan motor with drive selection No. 7 — (700 RPM), high-efficiency
throwaway filters, 60 hp supply fan motor with drive selection No. 8 — (900 RPM), economizer, VAV supply air
temperature control with inlet guide vanes, no remote panel, standard ambient, UL agency approval. The service
digit for each model number contains 36 digits; all 36 digits must be referenced.
3. Available as standard 460 volt only for 70 and 75 ton models.
8 = 100%, 20 HP W/Statitrac
9 = 100%, 25 HP W/Statitrac
F = 50%, 15 HP
H = 100%, 30 HP W/Statitrac
J = 100%, 40 HP W/Statitrac
K = 100%, 15 HP W/O Statitrac (CV Only)
L = 100%, 20 HP W/O Statitrac (CV Only)
M = 100%, 25 HP W/O Statitrac (CV Only)
N = 100%, 30 HP W/O Statitrac (CV Only)
P = 100%, 40 HP W/O Statitrac (CV Only)
Interface Module
355= VFD Line Reactor
366= Factory-Powered 15A GFI
Convenience Outlet
2
21RT-PRC010-EN
General Data
Table GD-1— General Data — 20-40 Tons
Compressor Data
Number/Size (Nominal)2/10 Ton1/10 Ton, 1/15 Ton2/15 To n4/10 Ton
ModelScrollScrollScrollScroll
Unit Capacity Steps (%)100/50100/40100/50100/75/50/25
RPM3450345034503450
Evaporator Fans
Number/Size/Type2/15”/FC2/15”/FC2/18”/FC2/20”/FC
Number of Motors1111
Hp Range3-153-155-207
Cfm Range
ESP Range — (In. WG)0.25-4.00.25-4.00.25-4.00.25-4.0
3
1
Exhaust Fans50%100%50%100%50%100%50%100%
Number/Size/Type1/15”/FC2/15”/FC1/15”/FC2/15”/FC1/15”/FC2/15”/FC1/18”/FC2/18”/FC
Hp Range1.5-31.5-31.5-33-53-53-7.55-7.55-10
Cfm Range2000-60004000-100002000-60004000-120002000-70004000-140003000-110007500-16000
ESP Range — (In. WG)0.25-1.40.2-2.00.25-1.40.2-2.00.25-1.40.2-2.00.25-1.40.2-2.0
Condenser Fans
Number/Size/Type2/26”/Prop.3/26”/Prop.3/26”/Prop.4/26”/Prop.
Hp (Each)1.01.01.01.0
Cfm14000183002090028200
Cycle/Phase60/360/360/360/3
Copper Condenser Fins (Optional)3/144/ 3/
Electric Heat
KW Range
Capacity Steps:3333
Natural Gas Heat
Standard Gas Heat
Low Heat Input235235350350
High Heat Input500500500850
Standard Heating Capacity Steps:2222
Modulating Gas Heat (Not Available on 20-40 Ton Models with Low Heat)
High Heat - Limited Modulation
High Heat - Full Modulation
2
4
Heat Exchanger Ty peStandardStandardStandardStandard
Number/Size (Nominal)2/10, 2/15 Ton4/15 Ton4/15 T on4/10, 2/15 Ton4/10, 2/15 Ton 4/10, 2/15 Ton
ModelScrollScrollScrollScrollScroll
Unit Capacity Steps (%)100/80/60/30100/75/50/25100/75/50/25100/72/44/22100/72/44/22
RPM34503450345034503450
Hp Range7
Cfm Range
ESP Range — (In. WG)0.25-4.00.25-4.00.25-4.00.25-4.00.25-4.0
3
1
Exhaust Fans50%100%50%100%50%100%50%100%50%100%
Number/Size/Type1/18”/FC2/18”/FC1/18”/FC2/18”/FC1/20”/FC2/20”/FC1/20”/FC2/20”/FC1/20”/FC2/20”/FC
Hp Range5-7.55-155-7.55-155-7.55-205-7.55-205-7.55-20
Cfm Range3000-11000 9000-20000 3000-11000 10000-21500 4000-13000 12000-27000 4000-13000 12000-27000 4000-13000 12000-27000
ESP Range — (In. WG)0.25-1.40.2-2.00.25-1.40.2-2.00.25-1.40.2-2.00.25-1.40.2-2.00.25-1.40.2-2.0
Condenser Fans
Number/Size/Type6/26”/Prop6/26”/Prop6/26”/Prop6/26”/Prop6/26”/Prop
Hp (Each)1.01.01.01.01.0
Cfm3660036600408004080040800
Cycle/Phase60/360/360/360/360/3
Size (Inches)42x66x2 Row42x66x2 Row42x90x2 Row42x90x2 Row42x90x2 Row
TypeType W, Prima FloType W, Prima FloType W, Prima FloT ype W, Prima FloType W , Prima Flo
High Heat (Fins/Ft)110110110110110
Low Heat (Fins/Ft)8080808080
Number/Size (Nominal)2/10, 4/15 Ton6/15 Ton4/10, 4/15 To n8/15 Ton
ModelScrollScrollScrollScroll
Unit Capacity Steps (%)100/69/38/19100/67/33/17100/70/40/20100/75/50/25
RPM3450345034503450
Evaporator Fans
Number/Size/Type2/28”/AF2/28”/AF2/28”/AF2/28”/AF
Number of Motors2222
Hp Range30-8030-8030-8030-80
Cfm Range
ESP Range — (In. WG)1.0-4.751.0-4.701.0-4.701.0-4.70
Exhaust Fans50%100%50%100%50%100%50%100%
Number/Size/Type1/22”/FC2/22”/FC1/22”/FC2/22”/FC1/22”/FC2/22”/FC1/22”/FC2/22”/FC
Hp Range1515-401515-401515-401515-40
Cfm Range12,000-20,000 28,000-40,000 12,000-20,000 28,000-40,000 12,000-20,000 28,000-40,000 12,000-20,000 28,000-40,000
ESP Range — (In. WG).25-2.5.25-2.5.25-2.5.25-2.5.25-2.5.25-2.5.25-2.5.25-2.5
Condenser Fans
Number/Size/Type8/26”/Prop.10/26”/Prop.10/26”/Prop.12/26”/Prop.
Hp (Each)1.01.01.01.0
Cfm56,40057,00060,00063,200
Cycle/Phase60/360/360/360/3
3
1
Evaporator Coil — Standard
Dimensions122.0 x 70.0122.0 x 71.25122.0 x 71.25122.0 x 71.25