Through the years, Trane has designed
and developed the most complete line of
Pac kaged Rooftop products available in
the market today. T rane was the first to
introduce the Micro —microelectronic
unit controls— and again moved ahead
with the introduction of the Voyager
Commercial products.
The Voyager Commercial line offers 27½
to 50 ton models; five sizes to meet the
changing demands of the commercial
rooftop market.
Our customers demand that Trane
products provide exceptional reliability,
meet stringent performance
requirements, and to be competitively
priced. T rane delivers with Voyager
Commercial.
V oyager Commercial features cutting
edge technologies like the reliable 3-D
Scroll compressors, Trane engineered
microprocessor controls, computer aided run testing, and Integrated
Comfort™ Systems. S o, whether you’re
the contractor, the engineer , or the
owner you can be certain Voyager
Commercial Products are built to meet
your needs.
Fewer parts than an equal capacity
reciprocating compressor means
significant reliability and efficiency
benefits. The single orbiting scroll
eliminates the need for pistons,
connecting rods, wrist pins and valves.
Fewer parts lead to increased reliability .
Fewer moving parts, less rotating mass
and less internal friction means greater
efficiency than reciprocating
compressors.
The T rane 3-D Scroll pro vides important
reliability and efficiency benefits. The 3-D
Scroll allows the orbiting scrolls to touch
in all three dimensions, forming a
completely enclosed compression
chamber whic h leads to increased
efficiency . In addition, the orbiting scrolls
only touch with enough force to create a
seal; there is no wear between the scroll
plates. The fixed and orbiting scrolls are
made of high strength cast iron which
results in less thermal distortion, less
leakage, and higher efficiencies. The
most outstanding feature of the 3-D
Scroll compressor is that slugging will
not cause failure. In a reciprocating
compressor, however , the liquid or dir t
can cause serious damage.
Low T orque Variation
The 3-D Scroll compressor has a very
smooth compression cycle; torque
variations are only 30 percent of that
produced by a reciprocating compressor.
This means that the scroll compressor
imposes very little stress on the motor
resulting in greater reliability. Low torque
variation reduces noise and vibration.
Suction Gas Cooled Motor
Compressor motor efficiency and
reliability is further optimized with the
latest scroll design. Cool suction gas
keeps the motor cooler for longer life and
better efficiency.
Proven Design Through Testing and
Research
With over twenty years of development
and testing, T rane 3-D Scroll
compressors have undergone more
than 400,000 hours of laboratory testing
and field operation. This work combined
with over 25 patents makes T rane the
worldwide leader in air conditioning
scroll compressor technology .
One of two matched scroll plates —
the distinguishing feature of the scroll
compressor.
Chart illustrates low torque variation of
3-D Scroll compressor vs
reciprocating compressor.
5RT-PRC007-EN
Quality and Reliability
Features and
Benefits
Forced Combustion Blowe r
Negative Pressur e Gas Valve
Hot Surface Ignitor
Drum and Tube Heat Exchanger
Micro Controls
The Micro provides unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.
Quality and Reliability are enhanced
through the use of time-tested microprocessor controls and logic.
The Micro:
• prevents the unit from short cycling,
considerably improving
compressor life.
• ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability
of the commercial compressor.
The Voyager with the Micro reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
Drum and Tube Heat Exchanger
The drum and tube heat exchanger is
designed for increased efficiency and
reliability and has utilized improved
technology incorporated in the large roof
top commercial units for almost
20 years.
The heat exchanger is manufactured
using aluminized steel with stainless
steel components for maximum
durability. The requirement for cycle
testing of heat exchangers is 1 0,000
cycles by ANSI Z21.47. This is the
standard required by both UL and AGA
for cycle test requirements. Trane
requires the design to be tested to 2
times this current standard. The drum
and tube design has been tested and
passed over 150,000 cycles which is over
15 times the current ANSI cycling
requirements.
1
/
2
The negative pressure gas valve will not
allow gas flow unless the combustion
blower is operating. This is one of our
unique safety features.
The forced combustion blower supplies
pre-mixed fuel through a single stainless
steel burner screen into a sealed drum
where ignition takes place. It is more
reliable to operate and maintain than a
multiple burner system.
The hot surface ignitor is a gas ignition
device which doubles as a safety device
utilizing a continuous test to prove the
flame. The design is cycle tested at the
factory for quality and reliability.
All the gas/electric rooftops exceed all
California seasonal efficiency
requirements. They also perform better
than required to meet the California NOx
emission requirements.
RT-PRC007-EN6
Features and
Benefits
FC Fans with Inlet Guide V anes
T rane’s forw ard-curved fans with inlet
guide vanes pre-rotate the air in the
direction of the fan wheel, decreasing
static pressure and horsepower,
essentially unloading the fan wheel. The
unloading characteristics of a Trane FC
fan with inlet guide vanes result in
superior part load performance.
Excellent P art-Load Ef ficiency
The Scroll compressor’s unique design
allows it to be applied in a passive
parallel manifolded piping scheme,
something that a “recip” just doesn’t do
very well.
When the unit begins stage back at part
load it still has the full area and circuitry
of its evaporator and condenser coils
available to transfer heat. In simple
terms this means superior part-load
efficiencies (IPLV) and lower unit
operating costs.
Rigorous T esting
All of Voyager’s designs were rigorously
rain tested at the factory to ensure water
integrity.
Actual shipping tests are performed to
determine packaging requirements.
Units are test shipped around the
country. Factory shake and drop tested
as part of the pac kage design process to
help assure that the unit will arrive at
your job site in top condition.
Rigging tests include lifting a unit into
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.
We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
All parts are inspected at the point of
final assembly. Sub-standard par ts are
identified and rejected immediately.
Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
Ease of Installation
Contractors look for lower installation
(jobsite) costs. Voyager’s conversionless
units provide many time and money
saving features.
Conversionless Units
The dedicated design units (either
downflow or horizontal) require no panel
removal or alteration time to convert in
the field — a major cost savings during
installation.
Improv ed Airflow
U-shaped airflow allows for improved
static capabilities. The need for high static
motor conversion is minimized and time
isn’t spent changing to high static
oversized motors.
Single Point P ow er
A single electrical connection powers the
unit.
Micro™
The function of the Micro replaces the
need for field installed anti-shortcycle
timer and time delay relays. The Micro
ensures that these controls are integral
to the unit. The contractor no longer has
to purchase these controls as options
and pay to install them.
The wiring of the low voltage
connections to the unit and the zone
sensors is as easy as 1-1, 2-2, and 3-3.
This simplified system makes it easier
for the installer to wire.
7RT-PRC007-EN
Features and
Benefits
Easy to Service
Because today’s owners are very costconscious when it comes to service and
maintenance, the Trane Voyager was
designed with direct input from service
contractors. This valuable information
helped to design a product that would
get the serviceman off the job quic ker
and save the owner money. Voyager
does this by offering:
A Simpler Design
The Voyager design uses fewer parts
than previous units. Since it is simpler in
design, it is easier to diagnose.
Micro
The Micro requires no special tools to
run the Voyager unit through its paces.
Simply place a jumper between T est 1
and T est 2 terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps
automatically.
— The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
As long as the unit has power and the
“system on” LED is lit, the Micro is
operational. The light indicates that the
Micro is functioning properly.
The Micro features expanded diagnostic
capabilities when utilized with T rane’s
Integrated Comfort™ Systems.
Some Zone Sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Easy Access Low V oltage T erminal Board
V oyager’s Low Voltage Terminal Board is
external to the electrical control cabinet.
It is extremely easy to locate and attach
the thermostat wire. This is another cost
and time-saving installation feature.
V alue
Low Ambient Cooling
All Voyager Commercial units have
cooling capabilities down to 0 F as
standard.
Pow er Exhaust Option
Provides exhaust of the return air when
using an economizer to maintain proper
building pressurization. Great for
relieving most building
overpressurization problems.
Micro Benefits
The Micro in the Voyager units has builtin anti-short-cycle timer , time delay relay
and minimum “on” time controls. These
controls are functions of the Micro and
are factory tested to assure proper
operation.
The Micro softens electrical “spikes” by
staging on fans, compressors and
heaters.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate
at predetermined temperature setpoint.
Intelligent Anticipation is a standard
feature of the Micro. It functions
constantly as the Micro and zone sensor
work together in harmony to provide
tighter comfort control than conventional
electro-mechanical thermostats.
Horizontal Dischar ge with
Power Exhaust Option
RT-PRC007-EN8
Features and
Benefits
VariTrac
VariTrac
T rane’s c hangeo ver VAV S ystem for light
commercial applications is also
available. Coupled with Voyager
Commercial, it provides the latest in
technological advances for comfort
Downflow and Hor izontal Economiz ers
The economizers come with three
control options dry bulb, enthalpy and
differential enthalpy . (Photo above
shows the three fresh air hoods on the
Horizontal Discharge Configuration).
management systems and can allow
thermostat control in every zone served
by V ariTrac™.
®
Central
Control Panel
Trane Communication Interface (TCI)
Available factory or field installed. This
module when applied with the Micro
easily interfaces with Trane’s Integrated
Comfort™ System.
V ar iable F requency Dr iv es (VFD)
TIME
CLOCK
INPUT/
STATUS
PANEL
EDIT
TERMINAL
V ariable Frequency Drives are factory
installed and tested to provide supply fan
motor speed modulation. VFD’s, as
compared to inlet guide vanes or
discharge dampers, are quieter , more
efficient, and are eligible for utility
rebates. The VFD’s are available with or
without a bypass option. Bypass control
will simply provide full nominal airflow
in the event of drive failure.
Trane factory built roof curbs
Available for all units.
One of Our Finest Assets
T rane Commercial S ales Engineers are a
support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and more
9RT-PRC007-EN
Application
Considerations
Exhaust Air Options
When is it necessary to provide building
exhaust?
Whenever an outdoor air economizer is
used, a building generally requires an
exhaust system. The purpose of the
exhaust system is to exhaust the proper
amount of air to prevent over or under pressurization of the building.
A building may have all or part of its
exhaust system in the rooftop unit. Often,
a building provides exhaust external to
the air conditioning equipment. This
external exhaust must be considered
when selecting the rooftop exhaust
system.
Voyager Commercial roof top units of fer
two types of exhaust systems:
1
Power exhaust fan.
2
Barometric relief dampers.
Application Recommendations
Pow er Exhaust Fan
The exhaust fan option is a dual,
nonmodulating exhaust fan with
approximately half the air -mo ving
capabilities of the supply fan system. The
experience of The Trane Company is that
a non-modulating exhaust fan selected
for 40 to 50 percent of nominal supply
cfm can be applied successfully.
The power exhaust fan generally should
not be selected for more than 40 to 50
percent of design supply airflow. Since it
is an on/off nonmodulating fan, it does
not vary exhaust cfm with the amount of
outside air entering the building.
Therefore, if selected for more than 40 to
50 percent of supply airflow, the building
may become underpressurized when
economizer operation is allowing lesser
amounts of outdoor air into the building.
If, however , building pressure is not of a
critical nature, the non-modulating
exhaust fan may be sized for more than
50 percent of design supply airflow.
Consult T able PD-1 6 for specific exhaust
fan capabilities with Voyager Commercial
units.
Barometric Relief D ampers
Barometric relief dampers consist of
gravity dampers which open with
increased building pressure. As the
building pressure increases, the pressure
in the unit return section also increases,
opening the dampers and relieving air.
Barometric relief may be used to provide
relief for single story buildings with no
return ductwork and exhaust
requirements less than 25 percent.
Altitude Corr ections
The rooftop performance tables and
curves of this catalog are based on
standard air (.075 lbs/ft). If the rooftop
airflow requirements are at other than
standard conditions (sea level), an air
density correction is needed to project
accurate unit performance.
Figure PD-1 shows the air density ratio at
various temperatures and elevations.
T rane roof tops are designed to operate
between 40 and 90 degrees Fahrenheit
leaving air temperature.
The procedure to use when selecting a
supply or exhaust fan on a rooftop for
elevations and temperatures other than
standard is as follows:
1
First, determine the air density ratio
using Figure PD-1 .
2
Divide the static pressure at the
nonstandard condition by the air density
ratio to obtain the corrected static
pressure.
3
Use the actual cfm and the corrected
static pressure to determine the fan rpm
and bhp from the rooftop performance
tables or curves.
4
The fan rpm is correct as selected.
5
Bhp must be multiplied by the air density
ratio to obtain the actual operating bhp.
In order to better illustrate this procedure,
the following example is used:
Consider a 30-ton rooftop unit that is to
deliver 1 1,000 actual cfm at 1.50 inches
total static pressure (tsp), 55 F leaving air
temperature, at an elevation of 5,000 ft.
1
From Figure PD-1, the air density ratio is
0.86.
2
Tsp=1 .50 inc hes/0.86=1.74 inches tsp.
3
From the performance tables: a 30-ton
rooftop will deliver 11,000 cfm at 1 .74
inches tsp at 668 rpm and 6.93 bhp.
4
The rpm is correct as selected — 668
rpm.
5
Bhp = 6.93 x 0.86 = 5.96 .
Compressor MBh, SHR, and kw should
be calculated at standard and then
converted to actual using the correction
factors in T able PD-2. Apply these factors
to the capacities selected at standard cfm
so as to correct for the reduced mass
flow rate across the condenser.
RT-PRC007-EN10
Application
Considerations
Heat selections other than gas heat will
not be affected by altitude. Nominal gas
capacity (output) should be multiplied by
the factors given in Table PD-3 before
calculating the heating supply air
temperature.
Acoustical Considerations
Proper placement of rooftops is critical to
reducing transmitted sound levels to the
building. The ideal time to make
provisions to reduce sound
transmissions is during the design
phase. And the most economical means
of avoiding an acoustical problem is to
place the rooftop(s) away from
acoustically critical areas. If possible,
rooftops should not be located directly
above areas such as: of fices, conference
rooms, executive office areas and
classrooms. Instead, ideal locations
might be over corridors, utility rooms,
toilets or other areas where higher
sound levels directly below the unit(s)
are acceptable.
Several basic guidelines for unit
placement should be followed to
minimize sound transmission through
the building structure:
1
Never cantilever the compressor end of
the unit. A structural cross member must
support this end of the unit.
2
Locate the unit’s center of gravity which
is close to, or over, a column or main
support beam.
3
If the roof structure is very light, roof
joists must be replaced by a structural
shape in the critical areas described
above.
4
If several units are to be placed on one
span, they should be staggered to
reduce deflection over that span.
It is impossible to totally quantify the
effect of building structure on sound
transmission, since this depends on the
response of the roof and building
members to the sound and vibration of
the unit components. However, the
guidelines listed above are experienceproven guidelines which will help reduce
sound transmissions.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency . A reduction in
unit clearance could result in condenser
coil starvation or warm condenser air
recirculation. If the clearances shown are
not possible on a particular job, consider
the following:
Do the clearances available allow for
major service work such as c hanging
compressors or coils?
Do the clearances available allow for
proper outside air intake, exhaust air
removal and condenser airflow?
If screening around the unit is being
used, is there a possibility of air
recirculation from the exhaust to the
outside air intake or from condenser
exhaust to condenser intake?
Actual clearances which appear
inadequate should be reviewed with a
local T rane sales engineer .
When two or more units are to be placed
side by side, the distance between the
units should be increased to 150 percent
of the recommended single unit
clearance. The units should also be
staggered for two reasons:
1
To reduce span deflection if more than
one unit is placed on a single span.
Reducing deflection discourages sound
transmission.
2
To assure proper dif fusion of exhaust air
before contact with the outside air intake
of adjacent unit.
Duct Design
It is important to note that the rated
capacities of the rooftop can be met only
if the rooftop is properly installed in the
field. A well designed duct system is
essential in meeting these capacities.
The satisfactory distribution of air
throughout the system requires that
there be an unrestricted and uniform
airflow from the rooftop discharge duct.
This discharge section should be straight
for at least several duct diameters to
allow the conversion of fan energy from
velocity pressure to static pressure.
However, when job conditions dictate
elbows be installed near the rooftop
outlet, the loss of capacity and static
pressure may be reduced through the
use of guide vanes and proper direction
of the bend in the elbow. The high
velocity side of the rooftop outlet should
be directed at the outside radius of the
elbow rather than the inside.
11RT -PRC007 -EN
Selection
Pr ocedure
Selection of T rane commercial air
conditioners is divided into five basic
areas:
1
Cooling capacity
2
Heating capacity
3
Air delivery
4
Unit electrical requirements
5
Unit designation
Factors Used In Unit Cooling Selection:
1
Summer design conditions — 95 DB/
76 WB, 95 F entering air to condenser.
2
Summer room design conditions —
76DB/66 WB.
3
Total peak cooling load — 321 MBh (27.75
tons).
4
Total peak supply cfm — 12,000 cfm.
5
External static pressure — 1 .0 inc hes.
6
Return air temperatures — 80 DB/66 WB.
7
Return air cfm — 4250 cfm.
8
Outside air ventilation cfm and load —
1200 cfm and 18.23 MBh (1 .52 tons).
9
Unit accessories include:
a
Aluminized heat exchanger — high heat
module.
b
2” Hi-efficiency throwaway filters.
c
Exhaust fan.
d
Economizer cycle.
Step 1 — A summation of the peak
cooling load and the outside air
ventilation load shows: 27.75 tons + 1 .52
tons = 29.27 required unit capacity. F rom
Table 18-2, 30-ton unit capacity at 80 DB/
67 WB, 95 F entering the condenser and
12,000 total peak supply cfm, is 30.0 tons.
Thus, a nominal 30-ton unit is selected.
Step 2 — Having selected a nominal 30ton unit, the supply fan and exhaust fan
motor bhp must be determined.
Supply Air Fan:
Determine unit static pressure at design
supply cfm:
External static pressure1 .20 inc hes
Heat exchanger.14 inc hes
(Table PD-1 4)
High efficiency filter 2”.09 inches
(Table PD-14)
Economizer.076 inches
(Table PD-14)
Unit total static pressure1 .50 inc hes
Using total cfm of 12,000 and total
static pressure of 1.50 inc hes, enter Table
PD-12. T able PD-1 2 shows 7.27 bhp with
652 rpm.
Step 3 — Determine evaporator coil
entering air conditions. Mixed air dry
bulb temperature determination.
Using the minimum percent of OA (1,200
cfm ÷ 12,000 cfm = 10 percent),
determine the mixture dry bulb to the
evaporator. RADB + %O A (OADB - RADB)
= 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5F
Approximate wet bulb mixture
temperature:
RAWB + O A (O A WB - RAWB) = 66 + (0.1 0)
(76-66) = 68 + 1 = 67 F.
A psychrometric c har t can be used to
more accurately determine the mixture
temperature to the evaporator coil.
Step 4 — Determine total required unit
cooling capacity:
Required capacity = total peak load +
O.A. load + supply air fan motor heat.
From Figure SP-1, the supply air fan
motor heat for 7.27 bhp = 20.6 MBh.
Capacity = 321 + 18.23 + 20.6 =
359.8 MBh (30 tons)
Step 5 — Determine unit capacity:
From Table PD-4 unit capacity at 81.5 DB.
67 WB entering the evaporator, 12000
supply air cfm, 95 F entering the
condenser is 361 MBh (30.1 tons) 279
sensible MBh.
Step 6 — Determine leaving air
temperature:
Unit sensible heat capacity, corrected for
supply air fan motor heat 279 - 20.6 =
258.4 MBh.
Supply air dry bulb temperature
difference = 258.4 MBh ÷ (1.085 x 12,000
cfm) = 19.8 F.
Supply air dry bulb: 81 .5 - 1 9.8 = 61.7.
Unit enthalpy difference = 361 ÷ (4.5 x
6.7 Btu/lb = 24.9 Btu/lb.
From Table PD-1, the leaving air wet bulb
temperature corresponding to an
enthalpy of 24.9 Btu/lb = 57.5.
Leaving air temperatures =
61 .7 DB/57.5 WB
RT-PRC007-EN12
Selection
Pr ocedure
Heating capacity selection:
1
Winter outdoor design conditions—5 F.
2
Total return air temperature — 72 F.
3
Winter outside air minimum ventilation
load and cfm — 1,200 cfm and 87.2 MBh.
4
Peak heating load 225 MBh.
Utilizing unit selection in the cooling
capacity procedure.
Mixed air temperature = RADB + %O.A.
(OADB - RADB) = 72
+ (0.10) (0-72) = 64.8 F.
Supply air fan motor heat temperature
rise = 20,600 BTU ÷ (1.085 x 1 2,000) cfm
= 1 .6 F.
Mixed air temperature entering heat
module = 64.8 + 1 .6 = 66.4 F.
Total winter heating load = peak heating
+ ventilation load - total fan motor heat =
225 + 87.2 - 20.6 = 291 .6MBh.
Electric Heating Syst em
Unit operating on 480/60/3 power supply.
From Table PD-9, kw may be selected for
a nominal 30-ton unit operating on 480volt power . The high heat module — 90
KW or 307 MBh will satisfy the winter
heating load of 291 . 6 MBh.
Table PD-9 also shows an air
temperature rise of 23.6 F for 12,000 cfm
through the 90 kw heat module.
Unit supply temperature at design
heating conditions = mixed air
temperature + air temperature rise = 66.4
+ 23.6 = 90 F.
Natural Gas Heating Syst em
Assume natural gas supply — 1 000 Btu/
3
. From T able PD-11, select the high heat
ft
module (486 MBh output) to satisfy 291 .6
at unit cfm.
Table PD-11 also shows air temperature
rise of 37.3 F for 12,000 cfm through
heating module.
Unit supply temperature design heating
conditions = mixed air temperature + air
temperature rise = 66.4 + 37.3 = 103.7 F.
Air Delivery Procedur e
Supply air fan bhp and rpm selection.
Unit supply air fan performance shown
in T able PD-1 2 includes pressure drops
for dampers and casing losses. Static
pressure drops of accessory
components such as heating systems,
and filters if used, must be added to
external unit static pressure for total
static pressure determination.
E = 208/60/3
F = 230/60/3
4 = 460/60/3
5 = 575/60/3
Digit 9 — Heating Capacity (See Note 4)
0 = No Heat (TC only)
L = Low Heat (YC only)
H = High Heat (YC only)
Note: When second digit is “E” for Electric
Heat, the following values apply in the ninth
digit.
A = 36 KW
B = 54 KW
C = 72 KW
D = 90 KW
E = 108 KW
Digit 13 — Supply F an Motor, HP
1 = 7.5 Hp Std. Eff.
2 = 10 Hp Std. Eff.
3 = 15 Hp Std. Eff.
4 = 20 Hp Std. Eff.
5 = 7.5 Hp Hi. Eff.
6 = 10 Hp Hi. Eff.
7 = 15 Hp Hi. Eff.
8 = 20 Hp Hi. Eff.
Digit 14 — Supply Air Fan Dr iv e
Selections (See Note 3)
A = 550 RPMH = 500 RPM
B = 600 RPMJ = 525 RPM
C = 650 RPMK = 575 RPM
D = 700 RPML = 625 RPM
E = 750 RPMM = 675 RPM
F = 790 RPMN = 725 RPM
G = 800 RPM
Digit 15 — Fr esh Air Selection
A = No Fresh Air
B = 0-25% Manual Damper
C = 0-100% Economizer, Dry Bulb Control
D = 0-100% Economizer, Reference
Enthalpy Control
E = 0-100% Economizer, Diff erential
Enthalpy Control
F = “C” Option and Low Leak Fresh
Air Damper
G = “D” Option and Low Leak Fresh
Air Damper
H = “E” Option and Low Leak Fresh
Air Damper
Digit 16 — Sys tem Contr ol
1 = Constant Volume
2 = VAV Supply Air Temperature Control
w/o Inlet Guide Vanes
3 = VAV Supply Air Temperature Control
w/Inlet Guide Vanes
4 = VAV Supply Air Temperature Control
w/Variable Frequency Drive w/o Bypass
5 = VAV Supply Air Temperature Control
w/Variable Frequency Drive and Bypass
Note: Zone sensors are not included with
option and must be ordered as a separate
accessory.
Digit 17 - 29 — Miscellaneous
A = Service Valves (See Note 2)
B = Through the Base Electrical Provision
C = Non-Fused Disconnect Switch with
External Handle
D = Factory-Powered 15A GFI
Convenience Outlet and Non-Fused
Disconnect Switch with
External Handle
E = Field-Powered 15A GFI
Convenience Outlet
F = ICS Control Option — Trane
Communication Interface, Supply Air
Sensing and Clogged Filter Switch
G = Ventilation Override
H = Hinged Service Access
J = Condenser Coil Guards
K = LonTalk Communication Interface
L = Special
M = Stainless Steel Drain Pans
N = Black Epoxy Coated Condenser Coil
Digit 10 Design Sequence
A = First
Digit 1 1 — Exhaust
0 = None
1 = Barometric Relief
(Available w/Economizer only)
2 = Power Exhaust Fan
(Available w/Economizer only)
Digit 12 — Filter
A = Standard 2” Throwaway Filters
B = High Efficiency 2” Throwaway Filters
C = High Efficiency 4” Throwaway Filters
Note:
1. All voltages are across the line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50
ton units only.
4. Electric Heat KW ratings are based upon voltage ratings of 240/480/600 V. Voltage offerings are as follows (see
table PD-9 for additional information):
TonsVoltage36547290108
27½ to 35240xx
480xxxx
600xxx
40 and 50240x
480xxxx
600xxxx
5. The service digit for each model number contains 29 digits; all 29 digits must be referenced.
KW
5
RT-PRC007-EN14
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.