Through the years, Trane has designed
and developed the most complete line of
Pac kaged Rooftop products available in
the market today. T rane was the first to
introduce the Micro —microelectronic
unit controls— and again moved ahead
with the introduction of the Voyager
Commercial products.
The Voyager Commercial line offers 27½
to 50 ton models; five sizes to meet the
changing demands of the commercial
rooftop market.
Our customers demand that Trane
products provide exceptional reliability,
meet stringent performance
requirements, and to be competitively
priced. T rane delivers with Voyager
Commercial.
V oyager Commercial features cutting
edge technologies like the reliable 3-D
Scroll compressors, Trane engineered
microprocessor controls, computer aided run testing, and Integrated
Comfort™ Systems. S o, whether you’re
the contractor, the engineer , or the
owner you can be certain Voyager
Commercial Products are built to meet
your needs.
Fewer parts than an equal capacity
reciprocating compressor means
significant reliability and efficiency
benefits. The single orbiting scroll
eliminates the need for pistons,
connecting rods, wrist pins and valves.
Fewer parts lead to increased reliability .
Fewer moving parts, less rotating mass
and less internal friction means greater
efficiency than reciprocating
compressors.
The T rane 3-D Scroll pro vides important
reliability and efficiency benefits. The 3-D
Scroll allows the orbiting scrolls to touch
in all three dimensions, forming a
completely enclosed compression
chamber whic h leads to increased
efficiency . In addition, the orbiting scrolls
only touch with enough force to create a
seal; there is no wear between the scroll
plates. The fixed and orbiting scrolls are
made of high strength cast iron which
results in less thermal distortion, less
leakage, and higher efficiencies. The
most outstanding feature of the 3-D
Scroll compressor is that slugging will
not cause failure. In a reciprocating
compressor, however , the liquid or dir t
can cause serious damage.
Low T orque Variation
The 3-D Scroll compressor has a very
smooth compression cycle; torque
variations are only 30 percent of that
produced by a reciprocating compressor.
This means that the scroll compressor
imposes very little stress on the motor
resulting in greater reliability. Low torque
variation reduces noise and vibration.
Suction Gas Cooled Motor
Compressor motor efficiency and
reliability is further optimized with the
latest scroll design. Cool suction gas
keeps the motor cooler for longer life and
better efficiency.
Proven Design Through Testing and
Research
With over twenty years of development
and testing, T rane 3-D Scroll
compressors have undergone more
than 400,000 hours of laboratory testing
and field operation. This work combined
with over 25 patents makes T rane the
worldwide leader in air conditioning
scroll compressor technology .
One of two matched scroll plates —
the distinguishing feature of the scroll
compressor.
Chart illustrates low torque variation of
3-D Scroll compressor vs
reciprocating compressor.
5RT-PRC007-EN
Quality and Reliability
Features and
Benefits
Forced Combustion Blowe r
Negative Pressur e Gas Valve
Hot Surface Ignitor
Drum and Tube Heat Exchanger
Micro Controls
The Micro provides unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.
Quality and Reliability are enhanced
through the use of time-tested microprocessor controls and logic.
The Micro:
• prevents the unit from short cycling,
considerably improving
compressor life.
• ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability
of the commercial compressor.
The Voyager with the Micro reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
Drum and Tube Heat Exchanger
The drum and tube heat exchanger is
designed for increased efficiency and
reliability and has utilized improved
technology incorporated in the large roof
top commercial units for almost
20 years.
The heat exchanger is manufactured
using aluminized steel with stainless
steel components for maximum
durability. The requirement for cycle
testing of heat exchangers is 1 0,000
cycles by ANSI Z21.47. This is the
standard required by both UL and AGA
for cycle test requirements. Trane
requires the design to be tested to 2
times this current standard. The drum
and tube design has been tested and
passed over 150,000 cycles which is over
15 times the current ANSI cycling
requirements.
1
/
2
The negative pressure gas valve will not
allow gas flow unless the combustion
blower is operating. This is one of our
unique safety features.
The forced combustion blower supplies
pre-mixed fuel through a single stainless
steel burner screen into a sealed drum
where ignition takes place. It is more
reliable to operate and maintain than a
multiple burner system.
The hot surface ignitor is a gas ignition
device which doubles as a safety device
utilizing a continuous test to prove the
flame. The design is cycle tested at the
factory for quality and reliability.
All the gas/electric rooftops exceed all
California seasonal efficiency
requirements. They also perform better
than required to meet the California NOx
emission requirements.
RT-PRC007-EN6
Features and
Benefits
FC Fans with Inlet Guide V anes
T rane’s forw ard-curved fans with inlet
guide vanes pre-rotate the air in the
direction of the fan wheel, decreasing
static pressure and horsepower,
essentially unloading the fan wheel. The
unloading characteristics of a Trane FC
fan with inlet guide vanes result in
superior part load performance.
Excellent P art-Load Ef ficiency
The Scroll compressor’s unique design
allows it to be applied in a passive
parallel manifolded piping scheme,
something that a “recip” just doesn’t do
very well.
When the unit begins stage back at part
load it still has the full area and circuitry
of its evaporator and condenser coils
available to transfer heat. In simple
terms this means superior part-load
efficiencies (IPLV) and lower unit
operating costs.
Rigorous T esting
All of Voyager’s designs were rigorously
rain tested at the factory to ensure water
integrity.
Actual shipping tests are performed to
determine packaging requirements.
Units are test shipped around the
country. Factory shake and drop tested
as part of the pac kage design process to
help assure that the unit will arrive at
your job site in top condition.
Rigging tests include lifting a unit into
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.
We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
All parts are inspected at the point of
final assembly. Sub-standard par ts are
identified and rejected immediately.
Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
Ease of Installation
Contractors look for lower installation
(jobsite) costs. Voyager’s conversionless
units provide many time and money
saving features.
Conversionless Units
The dedicated design units (either
downflow or horizontal) require no panel
removal or alteration time to convert in
the field — a major cost savings during
installation.
Improv ed Airflow
U-shaped airflow allows for improved
static capabilities. The need for high static
motor conversion is minimized and time
isn’t spent changing to high static
oversized motors.
Single Point P ow er
A single electrical connection powers the
unit.
Micro™
The function of the Micro replaces the
need for field installed anti-shortcycle
timer and time delay relays. The Micro
ensures that these controls are integral
to the unit. The contractor no longer has
to purchase these controls as options
and pay to install them.
The wiring of the low voltage
connections to the unit and the zone
sensors is as easy as 1-1, 2-2, and 3-3.
This simplified system makes it easier
for the installer to wire.
7RT-PRC007-EN
Features and
Benefits
Easy to Service
Because today’s owners are very costconscious when it comes to service and
maintenance, the Trane Voyager was
designed with direct input from service
contractors. This valuable information
helped to design a product that would
get the serviceman off the job quic ker
and save the owner money. Voyager
does this by offering:
A Simpler Design
The Voyager design uses fewer parts
than previous units. Since it is simpler in
design, it is easier to diagnose.
Micro
The Micro requires no special tools to
run the Voyager unit through its paces.
Simply place a jumper between T est 1
and T est 2 terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps
automatically.
— The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
As long as the unit has power and the
“system on” LED is lit, the Micro is
operational. The light indicates that the
Micro is functioning properly.
The Micro features expanded diagnostic
capabilities when utilized with T rane’s
Integrated Comfort™ Systems.
Some Zone Sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Easy Access Low V oltage T erminal Board
V oyager’s Low Voltage Terminal Board is
external to the electrical control cabinet.
It is extremely easy to locate and attach
the thermostat wire. This is another cost
and time-saving installation feature.
V alue
Low Ambient Cooling
All Voyager Commercial units have
cooling capabilities down to 0 F as
standard.
Pow er Exhaust Option
Provides exhaust of the return air when
using an economizer to maintain proper
building pressurization. Great for
relieving most building
overpressurization problems.
Micro Benefits
The Micro in the Voyager units has builtin anti-short-cycle timer , time delay relay
and minimum “on” time controls. These
controls are functions of the Micro and
are factory tested to assure proper
operation.
The Micro softens electrical “spikes” by
staging on fans, compressors and
heaters.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate
at predetermined temperature setpoint.
Intelligent Anticipation is a standard
feature of the Micro. It functions
constantly as the Micro and zone sensor
work together in harmony to provide
tighter comfort control than conventional
electro-mechanical thermostats.
Horizontal Dischar ge with
Power Exhaust Option
RT-PRC007-EN8
Features and
Benefits
VariTrac
VariTrac
T rane’s c hangeo ver VAV S ystem for light
commercial applications is also
available. Coupled with Voyager
Commercial, it provides the latest in
technological advances for comfort
Downflow and Hor izontal Economiz ers
The economizers come with three
control options dry bulb, enthalpy and
differential enthalpy . (Photo above
shows the three fresh air hoods on the
Horizontal Discharge Configuration).
management systems and can allow
thermostat control in every zone served
by V ariTrac™.
®
Central
Control Panel
Trane Communication Interface (TCI)
Available factory or field installed. This
module when applied with the Micro
easily interfaces with Trane’s Integrated
Comfort™ System.
V ar iable F requency Dr iv es (VFD)
TIME
CLOCK
INPUT/
STATUS
PANEL
EDIT
TERMINAL
V ariable Frequency Drives are factory
installed and tested to provide supply fan
motor speed modulation. VFD’s, as
compared to inlet guide vanes or
discharge dampers, are quieter , more
efficient, and are eligible for utility
rebates. The VFD’s are available with or
without a bypass option. Bypass control
will simply provide full nominal airflow
in the event of drive failure.
Trane factory built roof curbs
Available for all units.
One of Our Finest Assets
T rane Commercial S ales Engineers are a
support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and more
9RT-PRC007-EN
Application
Considerations
Exhaust Air Options
When is it necessary to provide building
exhaust?
Whenever an outdoor air economizer is
used, a building generally requires an
exhaust system. The purpose of the
exhaust system is to exhaust the proper
amount of air to prevent over or under pressurization of the building.
A building may have all or part of its
exhaust system in the rooftop unit. Often,
a building provides exhaust external to
the air conditioning equipment. This
external exhaust must be considered
when selecting the rooftop exhaust
system.
Voyager Commercial roof top units of fer
two types of exhaust systems:
1
Power exhaust fan.
2
Barometric relief dampers.
Application Recommendations
Pow er Exhaust Fan
The exhaust fan option is a dual,
nonmodulating exhaust fan with
approximately half the air -mo ving
capabilities of the supply fan system. The
experience of The Trane Company is that
a non-modulating exhaust fan selected
for 40 to 50 percent of nominal supply
cfm can be applied successfully.
The power exhaust fan generally should
not be selected for more than 40 to 50
percent of design supply airflow. Since it
is an on/off nonmodulating fan, it does
not vary exhaust cfm with the amount of
outside air entering the building.
Therefore, if selected for more than 40 to
50 percent of supply airflow, the building
may become underpressurized when
economizer operation is allowing lesser
amounts of outdoor air into the building.
If, however , building pressure is not of a
critical nature, the non-modulating
exhaust fan may be sized for more than
50 percent of design supply airflow.
Consult T able PD-1 6 for specific exhaust
fan capabilities with Voyager Commercial
units.
Barometric Relief D ampers
Barometric relief dampers consist of
gravity dampers which open with
increased building pressure. As the
building pressure increases, the pressure
in the unit return section also increases,
opening the dampers and relieving air.
Barometric relief may be used to provide
relief for single story buildings with no
return ductwork and exhaust
requirements less than 25 percent.
Altitude Corr ections
The rooftop performance tables and
curves of this catalog are based on
standard air (.075 lbs/ft). If the rooftop
airflow requirements are at other than
standard conditions (sea level), an air
density correction is needed to project
accurate unit performance.
Figure PD-1 shows the air density ratio at
various temperatures and elevations.
T rane roof tops are designed to operate
between 40 and 90 degrees Fahrenheit
leaving air temperature.
The procedure to use when selecting a
supply or exhaust fan on a rooftop for
elevations and temperatures other than
standard is as follows:
1
First, determine the air density ratio
using Figure PD-1 .
2
Divide the static pressure at the
nonstandard condition by the air density
ratio to obtain the corrected static
pressure.
3
Use the actual cfm and the corrected
static pressure to determine the fan rpm
and bhp from the rooftop performance
tables or curves.
4
The fan rpm is correct as selected.
5
Bhp must be multiplied by the air density
ratio to obtain the actual operating bhp.
In order to better illustrate this procedure,
the following example is used:
Consider a 30-ton rooftop unit that is to
deliver 1 1,000 actual cfm at 1.50 inches
total static pressure (tsp), 55 F leaving air
temperature, at an elevation of 5,000 ft.
1
From Figure PD-1, the air density ratio is
0.86.
2
Tsp=1 .50 inc hes/0.86=1.74 inches tsp.
3
From the performance tables: a 30-ton
rooftop will deliver 11,000 cfm at 1 .74
inches tsp at 668 rpm and 6.93 bhp.
4
The rpm is correct as selected — 668
rpm.
5
Bhp = 6.93 x 0.86 = 5.96 .
Compressor MBh, SHR, and kw should
be calculated at standard and then
converted to actual using the correction
factors in T able PD-2. Apply these factors
to the capacities selected at standard cfm
so as to correct for the reduced mass
flow rate across the condenser.
RT-PRC007-EN10
Application
Considerations
Heat selections other than gas heat will
not be affected by altitude. Nominal gas
capacity (output) should be multiplied by
the factors given in Table PD-3 before
calculating the heating supply air
temperature.
Acoustical Considerations
Proper placement of rooftops is critical to
reducing transmitted sound levels to the
building. The ideal time to make
provisions to reduce sound
transmissions is during the design
phase. And the most economical means
of avoiding an acoustical problem is to
place the rooftop(s) away from
acoustically critical areas. If possible,
rooftops should not be located directly
above areas such as: of fices, conference
rooms, executive office areas and
classrooms. Instead, ideal locations
might be over corridors, utility rooms,
toilets or other areas where higher
sound levels directly below the unit(s)
are acceptable.
Several basic guidelines for unit
placement should be followed to
minimize sound transmission through
the building structure:
1
Never cantilever the compressor end of
the unit. A structural cross member must
support this end of the unit.
2
Locate the unit’s center of gravity which
is close to, or over, a column or main
support beam.
3
If the roof structure is very light, roof
joists must be replaced by a structural
shape in the critical areas described
above.
4
If several units are to be placed on one
span, they should be staggered to
reduce deflection over that span.
It is impossible to totally quantify the
effect of building structure on sound
transmission, since this depends on the
response of the roof and building
members to the sound and vibration of
the unit components. However, the
guidelines listed above are experienceproven guidelines which will help reduce
sound transmissions.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency . A reduction in
unit clearance could result in condenser
coil starvation or warm condenser air
recirculation. If the clearances shown are
not possible on a particular job, consider
the following:
Do the clearances available allow for
major service work such as c hanging
compressors or coils?
Do the clearances available allow for
proper outside air intake, exhaust air
removal and condenser airflow?
If screening around the unit is being
used, is there a possibility of air
recirculation from the exhaust to the
outside air intake or from condenser
exhaust to condenser intake?
Actual clearances which appear
inadequate should be reviewed with a
local T rane sales engineer .
When two or more units are to be placed
side by side, the distance between the
units should be increased to 150 percent
of the recommended single unit
clearance. The units should also be
staggered for two reasons:
1
To reduce span deflection if more than
one unit is placed on a single span.
Reducing deflection discourages sound
transmission.
2
To assure proper dif fusion of exhaust air
before contact with the outside air intake
of adjacent unit.
Duct Design
It is important to note that the rated
capacities of the rooftop can be met only
if the rooftop is properly installed in the
field. A well designed duct system is
essential in meeting these capacities.
The satisfactory distribution of air
throughout the system requires that
there be an unrestricted and uniform
airflow from the rooftop discharge duct.
This discharge section should be straight
for at least several duct diameters to
allow the conversion of fan energy from
velocity pressure to static pressure.
However, when job conditions dictate
elbows be installed near the rooftop
outlet, the loss of capacity and static
pressure may be reduced through the
use of guide vanes and proper direction
of the bend in the elbow. The high
velocity side of the rooftop outlet should
be directed at the outside radius of the
elbow rather than the inside.
11RT -PRC007 -EN
Selection
Pr ocedure
Selection of T rane commercial air
conditioners is divided into five basic
areas:
1
Cooling capacity
2
Heating capacity
3
Air delivery
4
Unit electrical requirements
5
Unit designation
Factors Used In Unit Cooling Selection:
1
Summer design conditions — 95 DB/
76 WB, 95 F entering air to condenser.
2
Summer room design conditions —
76DB/66 WB.
3
Total peak cooling load — 321 MBh (27.75
tons).
4
Total peak supply cfm — 12,000 cfm.
5
External static pressure — 1 .0 inc hes.
6
Return air temperatures — 80 DB/66 WB.
7
Return air cfm — 4250 cfm.
8
Outside air ventilation cfm and load —
1200 cfm and 18.23 MBh (1 .52 tons).
9
Unit accessories include:
a
Aluminized heat exchanger — high heat
module.
b
2” Hi-efficiency throwaway filters.
c
Exhaust fan.
d
Economizer cycle.
Step 1 — A summation of the peak
cooling load and the outside air
ventilation load shows: 27.75 tons + 1 .52
tons = 29.27 required unit capacity. F rom
Table 18-2, 30-ton unit capacity at 80 DB/
67 WB, 95 F entering the condenser and
12,000 total peak supply cfm, is 30.0 tons.
Thus, a nominal 30-ton unit is selected.
Step 2 — Having selected a nominal 30ton unit, the supply fan and exhaust fan
motor bhp must be determined.
Supply Air Fan:
Determine unit static pressure at design
supply cfm:
External static pressure1 .20 inc hes
Heat exchanger.14 inc hes
(Table PD-1 4)
High efficiency filter 2”.09 inches
(Table PD-14)
Economizer.076 inches
(Table PD-14)
Unit total static pressure1 .50 inc hes
Using total cfm of 12,000 and total
static pressure of 1.50 inc hes, enter Table
PD-12. T able PD-1 2 shows 7.27 bhp with
652 rpm.
Step 3 — Determine evaporator coil
entering air conditions. Mixed air dry
bulb temperature determination.
Using the minimum percent of OA (1,200
cfm ÷ 12,000 cfm = 10 percent),
determine the mixture dry bulb to the
evaporator. RADB + %O A (OADB - RADB)
= 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5F
Approximate wet bulb mixture
temperature:
RAWB + O A (O A WB - RAWB) = 66 + (0.1 0)
(76-66) = 68 + 1 = 67 F.
A psychrometric c har t can be used to
more accurately determine the mixture
temperature to the evaporator coil.
Step 4 — Determine total required unit
cooling capacity:
Required capacity = total peak load +
O.A. load + supply air fan motor heat.
From Figure SP-1, the supply air fan
motor heat for 7.27 bhp = 20.6 MBh.
Capacity = 321 + 18.23 + 20.6 =
359.8 MBh (30 tons)
Step 5 — Determine unit capacity:
From Table PD-4 unit capacity at 81.5 DB.
67 WB entering the evaporator, 12000
supply air cfm, 95 F entering the
condenser is 361 MBh (30.1 tons) 279
sensible MBh.
Step 6 — Determine leaving air
temperature:
Unit sensible heat capacity, corrected for
supply air fan motor heat 279 - 20.6 =
258.4 MBh.
Supply air dry bulb temperature
difference = 258.4 MBh ÷ (1.085 x 12,000
cfm) = 19.8 F.
Supply air dry bulb: 81 .5 - 1 9.8 = 61.7.
Unit enthalpy difference = 361 ÷ (4.5 x
6.7 Btu/lb = 24.9 Btu/lb.
From Table PD-1, the leaving air wet bulb
temperature corresponding to an
enthalpy of 24.9 Btu/lb = 57.5.
Leaving air temperatures =
61 .7 DB/57.5 WB
RT-PRC007-EN12
Selection
Pr ocedure
Heating capacity selection:
1
Winter outdoor design conditions—5 F.
2
Total return air temperature — 72 F.
3
Winter outside air minimum ventilation
load and cfm — 1,200 cfm and 87.2 MBh.
4
Peak heating load 225 MBh.
Utilizing unit selection in the cooling
capacity procedure.
Mixed air temperature = RADB + %O.A.
(OADB - RADB) = 72
+ (0.10) (0-72) = 64.8 F.
Supply air fan motor heat temperature
rise = 20,600 BTU ÷ (1.085 x 1 2,000) cfm
= 1 .6 F.
Mixed air temperature entering heat
module = 64.8 + 1 .6 = 66.4 F.
Total winter heating load = peak heating
+ ventilation load - total fan motor heat =
225 + 87.2 - 20.6 = 291 .6MBh.
Electric Heating Syst em
Unit operating on 480/60/3 power supply.
From Table PD-9, kw may be selected for
a nominal 30-ton unit operating on 480volt power . The high heat module — 90
KW or 307 MBh will satisfy the winter
heating load of 291 . 6 MBh.
Table PD-9 also shows an air
temperature rise of 23.6 F for 12,000 cfm
through the 90 kw heat module.
Unit supply temperature at design
heating conditions = mixed air
temperature + air temperature rise = 66.4
+ 23.6 = 90 F.
Natural Gas Heating Syst em
Assume natural gas supply — 1 000 Btu/
3
. From T able PD-11, select the high heat
ft
module (486 MBh output) to satisfy 291 .6
at unit cfm.
Table PD-11 also shows air temperature
rise of 37.3 F for 12,000 cfm through
heating module.
Unit supply temperature design heating
conditions = mixed air temperature + air
temperature rise = 66.4 + 37.3 = 103.7 F.
Air Delivery Procedur e
Supply air fan bhp and rpm selection.
Unit supply air fan performance shown
in T able PD-1 2 includes pressure drops
for dampers and casing losses. Static
pressure drops of accessory
components such as heating systems,
and filters if used, must be added to
external unit static pressure for total
static pressure determination.
E = 208/60/3
F = 230/60/3
4 = 460/60/3
5 = 575/60/3
Digit 9 — Heating Capacity (See Note 4)
0 = No Heat (TC only)
L = Low Heat (YC only)
H = High Heat (YC only)
Note: When second digit is “E” for Electric
Heat, the following values apply in the ninth
digit.
A = 36 KW
B = 54 KW
C = 72 KW
D = 90 KW
E = 108 KW
Digit 13 — Supply F an Motor, HP
1 = 7.5 Hp Std. Eff.
2 = 10 Hp Std. Eff.
3 = 15 Hp Std. Eff.
4 = 20 Hp Std. Eff.
5 = 7.5 Hp Hi. Eff.
6 = 10 Hp Hi. Eff.
7 = 15 Hp Hi. Eff.
8 = 20 Hp Hi. Eff.
Digit 14 — Supply Air Fan Dr iv e
Selections (See Note 3)
A = 550 RPMH = 500 RPM
B = 600 RPMJ = 525 RPM
C = 650 RPMK = 575 RPM
D = 700 RPML = 625 RPM
E = 750 RPMM = 675 RPM
F = 790 RPMN = 725 RPM
G = 800 RPM
Digit 15 — Fr esh Air Selection
A = No Fresh Air
B = 0-25% Manual Damper
C = 0-100% Economizer, Dry Bulb Control
D = 0-100% Economizer, Reference
Enthalpy Control
E = 0-100% Economizer, Diff erential
Enthalpy Control
F = “C” Option and Low Leak Fresh
Air Damper
G = “D” Option and Low Leak Fresh
Air Damper
H = “E” Option and Low Leak Fresh
Air Damper
Digit 16 — Sys tem Contr ol
1 = Constant Volume
2 = VAV Supply Air Temperature Control
w/o Inlet Guide Vanes
3 = VAV Supply Air Temperature Control
w/Inlet Guide Vanes
4 = VAV Supply Air Temperature Control
w/Variable Frequency Drive w/o Bypass
5 = VAV Supply Air Temperature Control
w/Variable Frequency Drive and Bypass
Note: Zone sensors are not included with
option and must be ordered as a separate
accessory.
Digit 17 - 29 — Miscellaneous
A = Service Valves (See Note 2)
B = Through the Base Electrical Provision
C = Non-Fused Disconnect Switch with
External Handle
D = Factory-Powered 15A GFI
Convenience Outlet and Non-Fused
Disconnect Switch with
External Handle
E = Field-Powered 15A GFI
Convenience Outlet
F = ICS Control Option — Trane
Communication Interface, Supply Air
Sensing and Clogged Filter Switch
G = Ventilation Override
H = Hinged Service Access
J = Condenser Coil Guards
K = LonTalk Communication Interface
L = Special
M = Stainless Steel Drain Pans
N = Black Epoxy Coated Condenser Coil
Digit 10 Design Sequence
A = First
Digit 1 1 — Exhaust
0 = None
1 = Barometric Relief
(Available w/Economizer only)
2 = Power Exhaust Fan
(Available w/Economizer only)
Digit 12 — Filter
A = Standard 2” Throwaway Filters
B = High Efficiency 2” Throwaway Filters
C = High Efficiency 4” Throwaway Filters
Note:
1. All voltages are across the line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50
ton units only.
4. Electric Heat KW ratings are based upon voltage ratings of 240/480/600 V. Voltage offerings are as follows (see
table PD-9 for additional information):
TonsVoltage36547290108
27½ to 35240xx
480xxxx
600xxx
40 and 50240x
480xxxx
600xxxx
5. The service digit for each model number contains 29 digits; all 29 digits must be referenced.
KW
5
RT-PRC007-EN14
General Data
Table GD-1 — General Data — 27 1/2 - 30 Tons
Cooling Performance
Nominal Gross Capacity329,000363,000
Natural Gas Heat
1
2
LowHighLowHigh
Heating Input (BTUH)350,000600,000350,000600,000
First Stage250,000425,000250,000425,000
Heating Output (BTUH)283,500486,000283,500486,000
First Stage202,500344,500202,500344,500
Steady State Efficiency (%)
Number/T ype2/Scroll2/Scroll
Size (Nominal)10/1515
Unit Capacity Steps (%)100/40100/50
Motor RPM34503450
Outdoor Coil — TypeLancedLanced
T ube Siz e (in.) OD
Face Area (sq. f t.)51.3351.33
Rows/Fins Per Inch2/162/16
Indoor Coil — TypeHi-PerformanceHi-Performance
T ube Siz e (in.) OD
Face Area (sq. f t.)31.6731.67
Rows/Fins Per Foot2/1802/180
Refrigerant ControlTXVTXV
No. of Circuits11
Drain Connection No./Size (in)1/1.251/1.25
T ypePVCPVC
Outdoor Fan TypePropellerPropeller
No. Used/Diameter3/28.003/28.00
Drive T ype/No. SpeedsDirect/1Direct/1
CFM24,80024,800
No. Motors/HP/RPM3/1.1 0/11253/1 .10/1125
Indoor Fan TypeFCFC
No. Used11
Diameter/Width (in)22.38/22.0022.38/22.00
Drive Type/No. SpeedsBelt/1Belt/1
No. Motors/HP1/7.50/10.001/7.50/10.00
Motor RPM17601760
Motor Frame Size213/215T213/215T
Exhaust Fan TypePropellerPropeller
No. Used/Diameter (in)2/26.002/26.00
Drive Type/No. Speeds/MotorsDirect/2/2Direct/2/2
Motor HP/RPM1 .0/1 0751.0/1 075
Motor Frame Size4848
Filters — Type FurnishedThrowawayThrowaway
No./ Recommended Size (in)
Refrigerant Charge (Lbs of R-22)
Minimum Outside Air Temperature
For Mechanical Cooling0 F0 F
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in
accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
6
4
27 1/2 Ton30 Ton
1
3
/
4
27-9027-90
3
/
8
1
/
2
16/16 x 20 x 216/16 x 20 x 2
46.0046.60
1
3
8
/
1
/
2
15RT -PRC007 -EN
General Data
Table GD-2— General Data — 35-40 T on
Cooling Performance
Nominal Gross Capacity417,000513,000
Natural Gas Heat
1
2
LowHighLowHigh
Heating Input (BTUH)350,000600,000400,000800,000
First Stage250,000425,000300,000600,000
Heating Output (BTUH)283,500486,000324,000648,000
First Stage202,500344,500243,000486,000
Steady State Efficiency (%)
Number/T ype2/Scroll3/Scroll
Size (nominal)1515/15/10
Unit Capacity Steps (%)100/50100/60/40
Motor RPM34503450
Outdoor Coil — TypeLancedLanced
T ube Siz e (in.) OD
Face Area51.3369.79
Rows/Fins Per Inch2/162/16
Indoor Coil — TypeHi-PerformanceHi-Performance
T ube Siz e (in.) OD
Face Area (sq. f t.)31.6737.50
Rows/Fins Per Foot3/1803/180
Refrigerant ControlTXVTXV
No. of Circuits12
Drain Connection No./Size (in)1/1.251/1.25
T ypePVCPVC
Outdoor Fan TypePropellerPropeller
No. Used/Diameter3/28.004/28.00
Drive T ype/No. SpeedsDirect/1Direct/1
CFM24,80031,700
No. Motors/HP/RPM3/1.1 0/11254/1.10/1125
Indoor Fan TypeFCFC
No. Used11
Diameter/Width (in)22.38/22.0025.00/25.00
Drive Type/No. SpeedsBelt/1Belt/1
No. Motors/HP1/7.50/10.00/15.001/10.00/15.00
Motor RPM17601760
Motor Frame Size213/215/254T215/254T
Exhaust Fan TypePropellerPropeller
No. Used/Diameter (in)2/26.002/26.00
Drive Type/No. Speeds/MotorsDirect/2/2Direct/2/2
Motor HP/RPM1 .0/1 0751.0/1 075
Motor Frame Size4848
Filters — Type FurnishedThrowawayThrowaway
No./Recommended Size (in)
Refrigerant Charge (Lbs of R-22)
6
4
Minimum Outside Air Temperature
For Mechanical Cooling0 F0 F
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested
in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
35 T on40 Ton
1
3
/
4
27-9041-108
3
/
8
1
/
2
16/16 x 20 x 217/16 x 20 x 2
51.5026.00/47 .10 per circuit
1
3
/
8
1
/
2
RT-PRC007-EN16
General Data
Table GD-3— General Data — 50 T on
Cooling Performance
Nominal Gross Capacity616,000
Natural Gas Heat
1
2
LowHigh
Heating Input (BTUH)400,000800,000
First Stage300,000600,000
Heating Output (BTUH)324,000648,000
First Stage243,000486,000
Steady State Efficiency (%)
3
81.0081.00
No. Burners12
No. Stages22
Gas Connection Pipe Size (in.)
Electric Heat
KW Range
5
3
/
4
Capacity Steps:2
Compressor
Number/Type3/Scroll
Size (nominal)14
Unit Capacity Steps (%)100/67/33
Motor RPM3450
Outdoor Coil — TypeLanced
T ube Siz e (in.) OD
Face Area (sq. f t.)69.79
Rows/Fins Per Inch2/16
Indoor Coil — TypeHi-Performance
T ube Siz e (in.) OD
Face Area (sq. f t.)37.50
Rows/Fins Per Foot4/164
Refrigerant ControlTXV
No. of Circuits2
Drain Connection No./Size (in)1/1 .25
T ypePVC
Outdoor Fan TypePropeller
No. Used/Diameter4/28.00
Drive Type/No. SpeedsDirect/1
CFM31,700
No. Motors/HP/RPM4/1.10/1125
Indoor Fan TypeFC
No. Used1
Diameter/Width (in)25.00/25.00
Drive Type/No. SpeedsBelt/1
No. Motors/HP1/10.00/15.00/20.00
Motor RPM1760
Motor Frame Size215/254/256T
Exhaust Fan TypePropeller
No. Used/Diameter (in)2/26.00
Drive Type/No. Speeds/MotorsDirect/2/2
Motor HP/RPM1 .0/1 075
Motor Frame Size48
Filters — Type FurnishedThrowaway
No./Recommended Size (in)
Refrigerant Charge (Lbs of R-22)
6
4
Minimum Outside Air Temperature
For Mechanical Cooling0 F
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. Rated and tested in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation,
Maintenance Guide.
50 Ton
41-108
3
/
8
1
/
2
17/16 x 20 x 2
25.70/54.30 per circuit
1
Table GD-4 — Economizer Outdoor Air
Damper Leakage (Of Rat ed Airflow)
∆P Across Dampers (In. WC)
Standard1 .5 %2.5 %
Optional “Low Leak”0.5 %1.0 %
Note: Above data based on tests completed in
accordance with AMCA Standard 575.
0.5 (In.)1 .0 (In.)
17RT -PRC007 -EN
P erformance
Adjustment
Factors
Table PD-1— Enthalpy of Saturated AIR
Wet Bulb TemperatureBtu Per Lb.
4015.23
4115.70
4216.17
4316.66
4417.15
4517.65
4618.16
4718.68
4819.21
4919.75
5020.30
5120.86
5221.44
5322.02
5422.62
5523.22
5623.84
5724.48
5825.12
5925.78
6026.46
6127.15
6227.85
6328.57
6429.31
6530.06
6630.83
6731.62
6832.42
6933.25
7034.09
7134.95
7235.83
7336.74
7437 .66
7538.61
Figure PD-1 — Air Density Ratios
Altitude/Temperature Correction
Air Density
Ratio (Density
at New
Air Density)
Condition/Std.
Rooftop Leaving Air Temperature (degrees F)
Table PD-2 — Cooling Capacity Altitude Cor r ection F act ors
1. Fan performance table includes internal resistances of cabinet, and 2” standard filters. For other components refer to component static pressure drop table. Add the
pressure drops from any additional components to the duct (external) static pressure, enter the table, and select motor bhp.
2. The pressure drop from the supply fan to the space cannot exceed 2.25”.
3. Maximum air flow for 27½ ton — 12,100 cfm, 30 ton — 13,200 cfm, 35 ton — 14,400 cfm.
4. Maximum motor horsepower for 27½ ton — 10 hp, 30 ton — 10 hp, 35 ton — 15 hp.
1. Fan performance table includes internal resistances of cabinet, and 2” standard filters. For other components refer to component static pressure drop table. Add the
pressure drops from any additional components to the duct (external) static pressure, enter the table, and select motor bhp.
2. The pressure drop from the supply fan to the space cannot exceed 2.50”.
3. Maximum air flow for 40 ton — 17,600 cfm, 50 ton — 20,000 cfm.
4. Maximum motor horsepower for 40 ton — 15 hp, 50 ton — 20 hp.
1. Performance in table is with both motors operating.
2. High speed = both motors on high speed. Medium speed is one motor on high speed and one on low speed.
3. Power Exhaust option is not to be applied on systems that have more return air static pressure drop than the
120000.005——
Low speed is both motors on low speed.
maximum shown in the table for each motor speed tap.
27RT -PRC007 -EN
Controls
V AV Units Only
Sequence of Operation
1
Supply Air Pressure Control
Inlet Guide Vane Control
Inlet guide vanes are driven by a
modulating 2-10 vdc signal from the VAV
Module. A pressure transducer
measures duct static pressure, and the
inlet guide vanes are modulated to
maintain the supply air static pressure
within an adjustable user -defined range.
The range is determined by the supply
air pressure setpoint and supply air
pressure deadband, which are set
through a unit mounted potentiometer.
Inlet guide vane assemblies installed on
the supply fan inlets regulate fan
capacity and limit horsepower at lower
system air requirements. When in an y
position other than full open, the vanes
pre-spin intake air in the same direction
as supply fan rotation. As the vanes
approach the full-closed position, the
amount of “spin” induced by the vanes
increases at the same time that intake
airflow and fan horsepower diminish.
The inlet guide vanes will close when the
supply fan is shut down.
Supply Air Static Pressur e Limit
The opening of the inlet guide vanes and
VAV boxes are coordinated, with respect
to time, during unit start up and
transition to/from Occupied/Unoccupied
modes to prevent overpressurization of
the supply air ductwork. However, if for
any reason the supply air pressure
exceeds the fixed supply air static
pressure limit of 3.5” W .C., the supply
fan is shut down and the inlet guide
vanes are closed. The unit is then
allowed to restart four times. If the
overpressurization condition occurs on
the fifth time, the unit is shut down and a
manual reset diagnostic is set and
displayed at any of the remote panels
with LED status lights or communicated
to the Integrated Comfort system.
V ar iable F requency Dr iv es (VFD) Contr ol
V ariable frequency drives are driven by a
modulating 0-10 vdc signal from the VAV
module. A pressure transducer
measures duct static pressure, and the
VFD is modulated to maintain the supply
air static pressure within an adjustable
user -defined range. The range is
determined by the supply air pressure
setpoint and supply air pressure
deadband, which are set through a unit
mounted potentiometer. Variable
frequency drives provide supply fan
motor speed modulation. The drive will
accelerate or decelerate as required to
maintain the supply static pressure
setpoint. When subjected to high
ambient return conditions the VFD shall
reduce its output frequency to maintain
operation. Bypass control is offered to
provide full nominal airflow in the event
of drive failure.
2
Supply Air Temperatur e Controls
Cooling/Economizer
During occupied cooling mode of
operation, the economizer (if available)
and primary cooling are used to control
the supply air temperature. The supply
air temperature setpoint is user -defined
at the unit mounted VAV Setpoint Panel
or at the remote panel. If the enthalpy of
the outside air is appropriate to use “free
cooling,” the economizer will be used
first to attempt to satisfy the supply
setpoint.
On units with economizer , a call for
cooling will modulate the fresh air
dampers open. The rate of economizer
modulation is based on deviation of the
discharge temperature from setpoint,
i.e., the further away from setpoint, the
faster the fresh air damper will open.
Note that the economizer is only allowed
to function freely if ambient conditions
are below the enthalpy control setting or
below the return air enthalpy if unit has
comparative enthalpy installed. If outside
air is not suitable for “economizing,” the
fresh air dampers drive to the minimum
open position. A field adjustable
potentiometer on the Unitary
Economizer Module, T racer®, or a
remote potentiometer can provide the
input to establish the minimum damper
position.
At outdoor air conditions above the
enthalpy control setting, primary cooling
only is used and the fresh air dampers
remain at minimum position.
If the unit does not include an
economizer , primary cooling only is used
to satisfy cooling requirements.
Supply Air Setpoint Reset
Supply air reset can be used to adjust
the supply air temperature setpoint on
the basis of a zone temperature, return
air temperature, or on outdoor air
temperature. Supply air reset adjustment
is available on the unit mounted VAV
Setpoint Panel for supply air cooling
control.
a
Reset Based on Outdoor Air Temperature
Outdoor air cooling reset is sometimes
used in applications where the outdoor
temperature has a large effect on
building load. When the outside air
temperature is low and the building
cooling load is low, the supply air
setpoint can be raised, thereby
preventing subcooling of critical zones.
This reset can lower usage of primary
cooling and result in a reduction in
primary cooling energy usage.
There are two user -defined parameters
that are adjustable through the VA V
Setpoint Panel: reset temperature
setpoint and reset amount. The amount
of reset applied is dependent upon how
far the outdoor air temperature is below
the supply air reset setpoint. The amount
is zero where they are equal and
increases linearly toward the value set at
the reset amount input. The maximum
value is 20 F. If the outdoor air
temperature is more than 20 F below the
RT-PRC007-EN28
Controls
reset temperature setpoint the amount
of reset is equal to the reset amount
setpoint.
b
Reset Based On Zone Or Return
Temperature
Zone or return reset is applied to the
zone(s) in a building that tend to
overcool or overheat. The supply air
temperature setpoint is adjusted based
on the temperature of the critical zone(s)
or the return air temperature. This can
have the effect of improving comfort
and/or lowering energy usage. The userdefined parameters are the same as for
outdoor air reset.
Logic for zone or return reset control is
the same except that the origins of the
temperature inputs are the zone sensor
or return sensor respectively. The
amount of reset applied is dependent
upon how far the zone or return air
temperature is below the supply air reset
setpoint. The amount is zero where they
are equal and increases linearly toward
the value set at the reset amount
potentiometer on the VAV Setpoint
panel. The maximum value is 3 F. If the
return or zone temperature is more than
3 F below the reset temperature setpoint
the amount of reset is equal to the reset
amount setpoint.
3
Zone T emperature Control
Unoccupied Zone Heating and Cooling
During Unoccupied mode, the unit is
operated as a CV unit. Inlet guide vanes
and VAV boxes are driven full open. The
unit controls zone temperature to the
Unoccupied zone cooling and heating
(heating units only) setpoints.
Daytime W arm-up
During occupied mode, if the zone
temperature falls to a temperature three
degrees below the Morning Warm-up
setpoint, Daytime W arm-up is initiated.
The system changes to CV heating (full
unit airflow), the VAV boxes are fully
opened and the CV heating algorithm is
in control until the Morning Warm-up
setpoint is reached. The unit is then
returned to V AV cooling mode. The
Morning Warm-up setpoint is set at the
unit mounted VAV Setpoint panel or at a
remote panel.
Morning Warm-up (MWU)
Morning warm-up control (MWU) is
activated whenever the unit switches
from unoccupied to occupied and the
zone temperature is at least 1.5 F below
the MWU setpoint. When MWU is
activated the V AV box output will be
energized for at least 6 minutes to drive
all boxes open, the inlet guide vanes are
driven full open, and all stages of heat
(gas or electric) are energized. When
MWU is activated the economizer
damper is driven fully closed. When the
zone temperature meets or exceeds the
MWU setpoint minus 1 .5 F, the heat will
be staged down. When the z one
temperature meets or exceeds the MWU
setpoint then MWU will be terminated
and the unit will switch over to VA V
cooling.
CV Units Only
Sequence of Operation
1
Occupied Zone T emper at ure Contr ol
Cooling/Economizer
During occupied cooling mode, the
economizer (if provided) and primary
cooling are used to control zone
temperature. If the enthalpy of outside
air is appropriate to use “free cooling”,
the economizer will be used first to
attempt to satisfy the cooling zone
temperature setpoint; then primary
cooling will be staged up as necessary.
On units with economizer , a call for
cooling will modulate the fresh air
dampers open. The rate of economizer
modulation is based on deviation of the
zone temperature from setpoint, i.e., the
further away from setpoint, the faster the
fresh air damper will open. First stage of
cooling will be allowed to start after the
economizer reac hes full open.
Note that the economizer is allowed to
function freely only if ambient conditions
are below the enthalpy control setting or
below the return air enthalpy if unit has
comparative enthalpy. If outside air is
not suitable for “economizing,” the fresh
air dampers drive to the minimum open
position. A field adjustable
potentiometer on the Unitary
Economizer Module (UEM), Tracer or a
remote potentiometer can provide the
input to establish the minimum damper
position.
At outdoor air temperatures above the
enthalpy control setting, primary cooling
only is used and the outdoor air
dampers remain at minimum position.
If the unit does not include an
economizer , primary cooling only is used
to satisfy cooling requirements.
Heating
Gas Heating
When heating is required the UCP
initiates the heating cycle by energizing
the K5 relay, heating relay(s), and the
ignition control module(s). The K5 relay
brings on the combustion fan motor. The
ignition control module(s) begin the
ignition process by preheating the hot
surface ignitor(s). After the hot surface
ignitor is preheated the gas valve is
opened to ignite first stage. If ignition
does not take place the ignition control
module(s) will attempt to ignite 2 more
times before locking out. When ignition
does occur the hot surface ignitor is
deenergized and then functions as a
flame sensor. The UCP will energize the
supply fan contactor 45 seconds after the
initiation of the heat cycle. If more
capacity is needed to satisfy the heating
setpoint, the UCP will call for the second
stage of heat by driving the combustion
blower motor to high speed.
When the space temperature rises above
the heating setpoint, the UCP
deenergizes the K5 relay , the heating
relays, and the ignition control module,
terminating the heat cycle.
Electric Heating
When heat is required, the UCP initiates
first stage heating by energizing the first
stage electric heat contactor. The first
stage electric heater bank(s) will be
energized if the appropriate limits are
closed. The UCP will cycle first stage heat
on and off as required to maintain zone
temperature. If first stage cannot satisfy
29RT -PRC007 -EN
Controls
the requirement, the UCP will energize
the second stage electric heat
contactor(s) if the appropriate limits are
closed. The UCP will cycle second stage
on and off as required while keeping
stage one energized.
The supply fan is energized
approximately 1 second before the
electric heat contactors. When the space
temperature rises above the heating
setpoint, the UCP deenergizes the supply
fan and all electric heat contactors.
Supply Air Tempering
This feature is available only with
TRACER® or with systems using
programmable zone sensors (CV only
with economizer). For gas and electric
heat units in the Heat mode but not
actively heating, if the supply air
temperature drops to 10 F below the
occupied zone heating temperature
setpoint, one stage of heat will be
brought on to maintain a minimum
supply air temperature. The heat stage is
dropped if the supply air temperature
rises to 10 F above the occupied z one
heating temperature setpoint.
Aut o Changeo v er
When the System Mode is “Auto,” the
mode will change to cooling or heating
as necessary to satisfy the zone cooling
and heating setpoints. The zone cooling
and heating setpoints can be as close as
2 F apart.
Unoccupied Zone T emper atur e Contr ol
Cooling and Heating
Both cooling or heating modes can be
selected to maintain Unoccupied zone
temperature setpoints. For Unoccupied
periods, heating or primary cooling
operation can be selectively locked out at
the remote panels or TRACER.
Conventional Thermostat Interface
An interface is required to use a
conventional thermostat instead of a
zone sensor module with the UCP. The
Conventional Thermostat Interface (CTI)
is connected between conventional
thermostat and the UCP and will allow
only two steps of heating or cooling. The
CTI provides zone temperature control
only and is mutually exclusive of the
T rane Communications Interface.
Control Sequences of
Operation Common to Both
V AV and CV Units
V entilation ov er r ide (V OM)
V entilation over ride allows an external
system to assume control of the unit for
the purpose of exhaust or pressurization.
There are two inputs associated with
ventilation override, the initiate input and
the select input. When the UCP senses a
continuous closed condition on the
initiate input at the low voltage terminal
board the unit will begin ventilation
override depending on the condition of
the select input. The default condition of
the select input is exhaust (input open).
A closed select input will yield
pressurization. The component state
matrix for ventilation override is
as follows:
System Component ExhaustPressurization
Heat/Cooloffoff
IGVclosedopen
Supply Fanoffon
Exhaust Fanonoff
Outside Air Damperclosedopen
Return Air Damperopenclosed
VA V Boxesn/aopen
RT-PRC007-EN30
Controls
Coil Freeze Pr ot ection FROS TAT™
The FROST AT system eliminates the
need for hot gas bypass and adds a
suction line surface temperature sensor
to determine if the coil is in a condition
of impending frost. If impending frost is
detected primary cooling capacity is
shed as necessary to prevent icing. All
compressors are turned off after they
have met their minimum 3 minute on
times. The supply fan is forced on until
the FROST AT device no longer senses a
frosting condition or for 60 seconds after
the last compressor is shut off,
whichever is longer .
Occupied/Unoccupied Switching
There are 3 ways to switch Occupied/
Unoccupied:
1
NSB Panel
2
Electronic time clock or field-supplied
contact closure
3
TRACER
Night Setback Sensors
T rane’s night setbac k sensors are
programmable with a time clock function
that provides communication to the
rooftop unit through a 2-wire
communications link. The desired
transition times are programmed at
the night setback sensor and
communicated to the unit.
Night setback (unoccupied mode) is
operated through the time clock
provided in the sensors with night
setback. When the time clock switches to
night setback operation, the outdoor air
dampers close and heating/cooling can
be enabled or disabled. As the building
load changes, the night setbac k sensor
communicates the need for the rooftop
heating/cooling (if enabled) function and
the evaporator fan. The rooftop unit will
cycle through the evening as heating/
cooling (if enabled) is required in the
space. When the time clock switches
from night setback to occupied mode, all
heating/cooling functions begin normal
operation.
When using the night setback options
with a VAV heating/cooling rooftop,
airflow must be maintained through the
rooftop unit. This can be accomplished
by electrically tying the V AV boxes to the
VAV heat relay contacts on the Low
voltage terminal board or by using
changeover thermostats. Either of these
methods will assure adequate airflow
through the unit and satisfactory
temperature control of the building.
Timed over r ide Activation—ICS
When this function is initiated by
pushing the override button on the ICS
sensor, TRA CER will switc h the unit to
the occupied mode. Unit operation
(occupied mode) during timed override
is terminated by a signal from TRACER.
Timed over r ide Activation—Non-lCS
When this function is initiated by the
push of an override button on the
programmable zone sensor , the unit will
switch to the occupied mode. Automatic
Cancellation of the Timed override Mode
occurs after three hours of operation.
Comparative Enthalpy Contr ol of
Economizer
The Unitary Economizer Module (UEM)
receives inputs from optional return air
humidity and temperature sensors and
determines whether or not it is feasible
to economize. If the outdoor air enthalpy
is greater than the return air enthalpy
then it is not feasible to economize and
the economizer damper will not open
past its minimum position.
Fan F ailur e S witch
The fan failure switch will disable all unit
functions and “flash” the Service LED on
the zone sensor .
Emergency St op Input
A binary input is provided on the UCP for
installation of field provided switch or
contacts for immediate shutdown of all
unit functions. The binary input is
brought out to Low Voltage Terminal
Board One (L TB1).
31RT -PRC007 -EN
Electrical
Data
Electrical Service Sizing
To correctly siz e electrical service
wiring for your unit, find the
appropriate calculations listed below.
Each type of unit has its own set of
calculations for MCA (Minimum Circuit
Ampacity), MOP (Maximum
Overcurrent Protection), and RDE
(Recommended Dual Element fuse
size). Read the load definitions that
follow and then find the appropriate
set of calculations based on your unit
type.
Set 1 is for cooling only and cooling
with gas heat units, and set 2 is for
cooling with electric heat units.
Load Definitions: (To determine load
values, see the Electrical Service Sizing
Data Tables.)
LO AD1 = CURREN T OF THE LARGEST
MOTOR (COMPRESSOR OR F AN
MOTOR)
LO AD2 = SUM OF THE CURRENTS OF
ALL REMAINING MOTORS
LO AD3 = CURREN T OF ELECTRIC
HEATERS
LO AD4 = ANY O THER L OAD RATED AT
1 AMP OR MORE
Set 1. Cooling Only Roof t op Units and
Cooling with Gas Heat Rooftop Units
MCA = (1 .25 x L OAD1) + L O AD2 +
LOAD4
MOP = (2.25 x LO AD1) + L O AD2 +
LOAD4
Select a fuse rating equal to the MOP
value. If the MOP value does not equal
a standard fuse size as listed in NEC
240-6, select the next lower standard
fuse rating. NOTE: If selected MOP is
less than the MCA, then reselect the
lowest standard maximum fuse size
which is equal to or larger than the
MCA, provided the reselected fuse size
does not exceed 800 amps.
RDE = (1 .5 x L OAD1) + L O AD2 + L OAD4
Select a fuse rating equal to the RDE
value. If the RDE value does not equal
a standard fuse size as listed in NEC
240-6, select the next higher standard
fuse rating. NOTE: If the selected RDE
is greater than the selected MOP value,
then reselect the RDE value to equal
the MOP value.
DSS = 1 .15 x (LOAD1 + LO AD2 + L O AD4)
Select a disconnect switch siz e equal to
or larger than the DSS value calculated.
Set 2. Rooft op units with Electr ic Heat
To arrive at the correct MCA, MOP, and
RDE values for these units, you must
perform two sets of calculations. First
calculate the MCA, MOP, and RDE values
as if the unit was in cooling mode (use
the equations given in Set 1). Then
calculate the MCA, MOP, and RDE values
as if the unit were in the heating mode as
follows.
(Keep in mind when determining L O ADS
that the compressors and condenser
fans don’t run while the unit is in the
heating mode).
For units using heaters less than 50 kw.
MCA = 1 .25 x (LO AD1 + L O AD2 + LO AD4)
+ (1 .25 x L O AD3)
For units using heaters equal to or
greater than 50 kw.
MCA = 1 .25 x (LO AD1 + L O AD2 + LO AD4)
+ LO AD3
The nameplate MCA value will be the
larger of the cooling mode MCA value or
the heating mode MCA value calculated
above.
MOP = (2.25 x LO AD1) + L O AD2 + LOAD3
+ LO AD4
The selection MOP value will be the
larger of the cooling mode MOP value or
the heating mode MOP value calculated
above.
Table ED-1 — Ton Electrical Service Sizing Data — Electr ic Heat Module (Electr ic Heat Only)
Models: TED/TEH 330 thru 600
NominalNominal
Unit SizeUnitKW Heater
(T ons)Voltage36547290108
27½20874.91 12.4———
30.023086.6129.9———
35.046043.365.086.6108.3—
40.0208—112.4———
50.0230—129.9———
Notes:
1. All FLA in this table are based on heater operating at 208, 240, 480, and 600 volts.
575—52.069.386.6—
460—65.086.6108.31 29.9
575—52.069.386.6103.9
Electric Heat FLA
FLAFLAFLAFLAFLA
Select a fuse rating equal to the MOP
value. If the MOP value does not equal a
standard fuse size as listed in NEC 240-6,
select the next lower standard fuse
rating. NOTE: If selected MOP is less
than the MCA, then reselect the lowest
standard maximum fuse size which is
equal to or larger than the MCA,
provided the reselected fuse size does
not exceed 800 amps.
RDE = (1 .5 x L OAD1) + L O AD2 + L OAD3 +
LOAD4
The selection RDE value will be the
larger of the cooling mode RDE value or
the heating mode RDE value calculated
above.
Select a fuse rating equal to the RDE
value. If the RDE value does not equal a
standard fuse size as listed in NEC 240-6,
select the next higher standard fuse
rating. NOTE: If the selected RDE is
greater than the selected MOP value,
then reselect the RDE value to equal the
MOP value.
DSS = 1 .1 5 x (L O AD1 + L OAD2 + L O AD3 +
LO AD4)
NOTE: Keep in mind when determining
LO ADS that the compressors and
condenser fans don’t run while the unit
is in the heating mode.
The selection DSS value will be the
larger of the cooling mode DSS or the
heating mode DSS calculated above.
Select a disconnect switch siz e equal to
or larger than the DSS value calculated.
RT-PRC007-EN32
Electrical
Data
Table ED-2 — 27½-50 Ton Electr ical Service Sizing Data
Figure DD-1 — 27 1/2 - 35 Tons (TC, TE, Y C Low Heat)
1/16
NOTES:
1. ALL DIMENSIONS INCHES.
2. THRU-BASE ELECTRICAL LOCATIONS
ARE PRESENT ONLY WHEN OPTION
IS ORDERED.
NOTE: The Two Horizontal Power
Exhaust Hoods and the three
Horizontal Fresh Air Hoods are
located side by side. The Fresh
Air Hoods (not shown) extend only
23 15/16” from the end of the unit.
RT-PRC007-EN34
Dimensional
Data
Figure DD-2 — 27 1/2 - 35 Tons (YC High Heat)
1/16
NOTES:
1. ALL DIMENSIONS INCHES.
2. THRU-BASE ELECTRICAL LOCATIONS
ARE PRESENT ONLY WHEN OPTION
IS ORDERED.
3”
NOTE: The Two Horizontal Power
Exhaust Hoods and the three
Horizontal Fresh Air Hoods are
located side by side. The Fresh
Air Hoods (not shown) only extend
23 15/16” from the end of the unit.
2. THRU-BASE ELECTRICAL LOCATIONS
ARE PRESENT ONLY WHEN OPTION
IS ORDERED.
4”
NOTE: The Two Horizontal Power
Exhaust Hoods and the three
Horizontal Fresh Air Hoods are
located side by side. The Fresh
Air Hoods (not shown) only extend
23 15/16” from the end of the unit.
RT-PRC007-EN36
Dimensional
(Variable Air
Data
Field Installed Sensors
SINGLE SETPOINT SENSOR WITH S Y S TEM FUNCTION LIGHTS (BAYSENS021*)
Volume VAV)
PROGRAMMABLE NIGHT-SETBACK SENSOR (BAY SENS020*)
Note:
1. Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
37RT -PRC007 -EN
Dimensional
(Constant
Data
V olume CV)
Field Installed Sensors
PROGRAMMABLE NIGHT-SETBACK SENSOR (BA YSENS019*)
Note:
1. Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
DUAL SETPOINT, MANUAL/AUT OMATIC
CHANGEOVER SENSOR WITH SYS TEM
FUNCTION LIGHTS (BAYSENS01 0*)
WITHOUT LED STATUS INDICATORS
(BAY SENS008*)
SINGLE SETPOINT WITHOUT
LED ST ATUS INDICA T ORS (BAYSENS006*)
RT-PRC007-EN38
Dimensional(CV and VAV)
Data
Integrat ed Comfort™ Syst em Sensors
ZONE TEMPERATURE SENSOR W/TIMED OVERRIDE BUTTON
AND LOCAL SETPOINT ADJUSTMENT (BAY SENS0 14)
1
ZONE TEMPERATURE SENSOR W/TIMED OVERRIDE BUTTONS
(BAYSENS013*) ALSO AVAILABLE SENSOR ONLY (BA YSENS0 1 7*)
REMOTE MINIMUM POSITION POTENTIOMETER CONTROL (BAYSTAT023*)
TEMPERA TURE SENSOR (BAYSENS0 16*)
Note:
1. Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
1. Point Loading is identified with corner A being the corner with the
compressors. As you move clockwise around the unit as viewed
from the top, mid-point B, corner C, corner D, mid-point E and
corner F.
1
2
Basic Unit Weights
1
DEF
COMPRS
CBA
TOP VIEW
OF UNIT
T able W-3 — Component Weights
Hi-Static/
Weights of Optional Components
Hi-Eff 0-25%Inlet
Unit Barometric Power Supply Fan ManualGuide
ModelReliefExhaust Motors (2) Damper Econo Vanes W/O Bypass With Bypass Valves ElectricSwitchSwitchLo Hi
Drives (VFD's)Service Base Disconnect DisconnectWeights
T able W-4 — Minimum Operating Clearances for Unit Installation
2
Service Side
RT-PRC007-EN40
Single Unit
Multiple Unit
Notes:
1. Horizontal and Downflow Units, all sizes.
2. Condenser coil is located at the end and side of the unit.
3. Clearances on multiple unit installations are distances between units.
1
1,3
Econo/Exhaust EndEnd / SideAccess
6 Feet8 F eet / 4 F eet4 Feet
12 F eet16 Feet / 8 Feet8 F eet
Condenser Coil
Mec hanical
Specifications
General
The units shall be dedicated downflow
or horizontal airflow. The operating range
shall be between 115 F and 0 F in cooling
as standard from the factory for all units.
Cooling performance shall be rated in
accordance with ARI testing procedures.
All units shall be factory assembled,
internally wired, fully charged with
HCFC-22 and 100% run tested to check
cooling operation, fan and blower
rotation and control sequence before
leaving the factory. Wiring internal to the
unit shall be numbered for simplified
identification. Units shall be UL listed
and labeled, classified in accordance to
UL 1995/CAN/CS A No. 236-M90 for
Central Cooling Air Conditioners.
Canadian units shall be CSA Certified.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
All components shall be mounted in a
weather resistant steel cabinet with a
painted exterior. Where top cover seams
exist, they shall be double hemmed and
gasket sealed to prevent water leakage.
Cabinet construction shall allow for all
maintenance on one side of the unit.
Service panels shall have handles and
shall be removable while providing a
water and air tight seal. Control box
access shall be hinged. The indoor air
section shall be completely insulated
with fire resistant, permanent, odorless
glass fiber material. The base of the unit
shall have provisions for crane lifting.
Filters
T wo inc h, throw aw ay filters shall be
standard on all size units. T wo inc h “high
efficiency”, and four inc h “high
efficiency” filters shall be optional.
Compressors
®
T rane 3-D
simple mechanical design with only
three major moving parts. Scroll type
compression provides inherently low
vibration. The 3-D Scroll provides a
completely enclosed compression
Scroll compressors have a
chamber whic h leads to increased
efficiency . Exhaustive testing on the 3-D
Scroll, including start up with the shell
full of liquid, has proven that slugging
does not fail involutes. Direct-drive, 3600
rpm, suction gas-cooled hermetic motor .
T rane 3-D S croll compressor includes
centrifugal oil pump, oil level sightglass
and oil charging valve. Eac h compressor
shall have crankcase heaters installed,
properly sized to minimize the amount of
liquid refrigerant present in the oil sump
during off cycles.
Refriger ant Circuits
Each refrigerant circuit shall have
independent thermostatic expansion
devices, service pressure ports and
refrigerant line filter driers factoryinstalled as standard. An area shall be
provided for replacement suction line
driers.
Evaporat or and Condenser Coils
3
Condenser coils shall have
tubes mechanically bonded to lanced
aluminum plate fins. Evaporator coils
shall be
tubes mechanically bonded to high
performance aluminum plate fins. All
coils shall be leak tested at the factory to
ensure pressure integrity. All coils shall
be leak tested to 200 psig and pressure
tested to 450 psig. All dual circuit
evaporator coils shall be of intermingled
configuration. Sloped condensate drain
pans are standard.
Outdoor Fans
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw through in the vertical disc harge
position. The fan motor(s) shall be
permanently lubricated and have built-in
thermal overload protection.
Indoor Fan
Units shall have belt driven, FC,
centrifugal fans with fixed motor
sheaves. All motors shall be circuit
breaker protected. All indoor fan motors
meet the U.S. Energy Policy Act of 1992
(EP A CT).
1
/2” internally finned copper
/8” copper
Electric Heaters
Electric heat shall be available for factory
installation within basic unit. Electric
heater elements shall be constructed of
heavy-duty nickel c hromium elements
internally delta connected for 240 volt,
wye connected for 480 and 600 volt.
Staging shall be achieved through the
unitary control processor (UCP). Each
heater package shall have automatically
reset high limit control operating
through heating element contactors. All
heaters shall be individually fused from
factory, where required, and meet all
NEC and CEC requirements. Power
assemblies shall provide single-point
connection. Electric heat shall be UL
listed or CSA certified.
Gas Heating Section
The heating section shall have a drum
and tube heat exchanger(s) design using
corrosion resistant steel components. A
forced combustion blower shall supply
premixed fuel to a single burner ignited
by a pilotless hot surface ignition
system. In order to provide reliable
operation, a negative pressure gas valve
shall be used that requires blower
operation to initiate gas flow. On an
initial call for heat, the combustion
blower shall purge the heat exchanger(s)
45 seconds before ignition. After three
unsuccessful ignition attempts, the entire
heating system shall be locked out until
manually reset at the thermostat. Units
shall be suitable for use with natural gas
or propane (field installed kit) and also
comply with California requirements for
low NOx emissions. All units shall have
two stage heating.
Controls
Unit shall be completely factory wired
with necessary controls and terminal
block for power wiring. Units shall
provide an external location for
mounting fused disconnect device.
Microprocessor controls shall be
provided for all 24 volt control functions.
The resident control algorithms shall
41RT -PRC007 -EN
Mec hanical
Specifications
make all heating, cooling and/or
ventilating decisions in response to
electronic signals from sensors
measuring indoor and outdoor
temperatures. The control algorithm
maintains accurate temperature control,
minimizes drift from set point and
provides better building comfort. A
centralized microprocessor shall provide
anti-short cycle timing and time delay
between compressors to provide a
higher level of machine protection.
Control Options
Inlet Guide Vanes shall be installed on
each fan inlet to regulate capacity and
limit horsepower at lower system
requirements. When in any position
other than full open they shall pre-spin
intake air in the same direction as fan
rotation. The inlet guide vanes shall close
when supply fan is off, except in night
setback.
The inlet guide vane actuator motor shall
be driven by a modulating dc signal
from the unit microprocessor. A pressure
transducer shall measure duct static
pressure and modulate the inlet guide
vanes to maintain the required supply air
static pressure within a predetermined
range.
V ar iable Fr equency Dr iv es (VFDs)
VFDs shall be factory installed and tested
to provide supply fan motor speed
modulation. The VFD shall receive a 210 VDC signal from the unit
microprocessor based upon supply
static pressure and shall cause the drive
to accelerate or decelerate as required to
maintain the supply static pressure
setpoint. When subjected to high
ambient return conditions the VFD shall
reduce its output frequency to maintain
operation. Bypass control to provide full
nominal air flow in the event of drive
failure shall be optional.
V entilation Over r ide
Ventilation Over ride shall allow a binary
input from the fire/life safety panel to
cause the unit to override standard
operation and assume one of two
factory preset ventilation sequences,
exhaust or pressurization. The two
sequences shall be selectable based
open a binary select input.
Outside Air
Manual Outside Air
A manually controllable outside air
damper shall be adjustable for up to 25
percent outside air. Manual damper is
set at desired position at unit start up.
Economizer
Economizer shall be factory installed. The
assembly includes: fully modulating 0100 percent motor and dampers,
minimum position setting, preset
linkage, wiring harness, and fixed dry
bulb control. Solid state enthalpy and
differential enthalpy control shall be a
factory or field installed option.
Exhaust Air
Barometric Relief
The barometric relief damper shall be
optional with the economizer. Option
shall provide a pressure operated
damper for the purpose of space
pressure equalization and be gravity
closing to prohibit entrance of outside air
during the equipment “off” cycle.
Pow er Exhaust F an
Power exhaust shall be available on all
units and shall be factory installed. It
shall assist the barometric relief damper
in maintaining building pressurization.
Unit Options
Service V alves
Service valves shall be provided factory
installed and include suction, liquid, and
discharge 3-way shutof f valves.
Through-The-Base Electrical Provision
An electrical service entrance shall be
provided which allows access to route all
high and low voltage electrical wiring
inside the curb, through the bottom of
the outdoor section of the unit and into
the control box area.
Non-Fused Disconnect Switch
A factory installed non-fused disconnect
switch with external handle shall be
provided and shall satisfy NEC
requirements for a service disconnect.
The non-fused disconnect shall be
mounted inside the unit control box.
GFI Convenience Outlet (F actory
Pow er ed)
A 15A, 115V Ground Fault Interrupter
convenience outlet shall be factory
installed. It shall be wired and powered
from a factory mounted transformer.
Unit mounted non-fused disconnect with
external handle shall be furnished with
factory powered outlet.
GFI Convenience Outlet (Field Po w ered)
A 15A, 115V Ground Fault Interrupter
convenience outlet shall be factory
installed and shall be powered by
customer provided 115V circuit.
Hinged Service A ccess
Filter access panel and supply fan access
panel shall be hinged for ease of unit
service.
Condenser Coil Guards
Factory installed condenser vinyl coated
wire mesh coil guards shall be available
to provide full area protection against
debris and vandalism.
LonTalk Communication Interface
Available either field or factory-installed
for constant volume units. When
installed on a constant volume unit, this
LonTalk board will allow the unit to
communicate as a Trane Comm5 device
or directly with generic LonTalk Network
Building Automation System Controls.
Stainless Steel Drain P ans
Sloped stainless steel evaporator coil
drain pans are durable, long-lasting and
highly corrosion resistant.
Black Epoxy Coated Condenser Coil
The coil provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory applied
thermoset vinyl coating, bonded to
normal aluminum fin stock. The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B1 17.
RT-PRC007-EN42
Mec hanical
Specifications
Accessor ies
Roof Curb
The roof curb shall be designed to mate
with the unit and provide support and a
water tight installation when installed
properly. The roof curb design shall allow
field-fabricated rectangular supply/return
ductwork to be connected directly to the
curb when used with downflow units.
Curb design shall comply with NRCA
requirements. Curb shall ship knocked
down for field assembly and include
wood nailer strips.
Trane Communication Interface (TCI)
Shall be provided to interface with the
T rane Integrated Comfor t™ S ystem and
shall be available factory installed. The
TCI shall allow control and monitoring of
the rooftop unit via a two-wire
communication link.
The following alarm and diagnostic
information shall be available:
UCP Originated D ata
• Unit operating mode
• Unit failure status
Cooling failure
Heating failure
Emergency service stop indication
Supply fan proving
Timed override activation
High temperature thermostat status
• Zone temperature
• Supply air temperature
• Cooling status (all stages)
• Stage activated or not
• Stage locked out by UCP
• HPC status for that stage
• Compressor disable inputs
• Heating status
• Number of stages activated
• High temperature limit status
• Economizer status
• Enthalpy favorability status
• Requested minimum position
• Damper position
• Dry bulb/enthalpy input status
• Outside air temperature
• Outside relative humidity
• Sensor Failure
Humidity sensor
OAT sensor
SA T sensor
RA T sensor
Zone temperature sensor
Mode input
Cooling/heating setpoints from
sensors
Static pressure transducer
Unit mounted potentiometer
SA T from potentiometer
Air reset setpoint from potentiometer
• Unit Configuration data
Gas or electric heat
Economizer present
Shall be provided to interface with the
Micro unit controls and shall be available
in either manual, automatic
programmable with night setback, with
system malfunction lights or remote
sensor options.
Conventional Thermostat Interface (CTI)
This field installed circuit board shall
provide interface with electromechanical
thermostats or automation systems. Not
available with V AV system control.
Differ ential Pressur e S witches
This field installed option allows dirty
filter indication. The dirty filter switch will
light the Service LED on the zone sensor
and will allow continued unit operation.
Remote Potentiomet er
A remote potentiometer shall be
available to remotely adjust the unit
economizer minimum position.
High T emperature Thermostats
Field installed, manually resettable high
temperature thermostats shall provide
input to the unit controls to shut down
the system if the temperature sensed at
the return is 135 F or at the discharge
240 F.
Reference Enthalp y Kit
Field installed enthalpy kit shall provide
inputs for economizer control based
upon comparison of the outside air
stream to a definable enthalpy reference
point. May also be factory installed.
Comparative Enthalpy Kit
Field installed enthalpy kit shall provide
inputs for economizer control based
upon comparison of the enthalpies of
the return and outdoor air streams. Also
available factory installed.
43RT -PRC007 -EN
Mec hanical
Specifications
LP Conversion Kit
Field installed conversion kit shall
provide orifice(s) for simplified
conversion to liquefied propane gas. No
change of g as valve shall be required.
BAY SENS006* — Zone S ensor has one
temperature setpoint lever, heat, off or
cool system switch, fan auto or fan on
switch. Manual c hangeover. These
sensors are for CV units only.
BAY SENS008* — Zone S ensor has two
temperature setpoint levers, heat, auto,
off, or cool system switc h, fan auto or fan
on switch. Auto changeover . These
sensors are used with CV units.
BAY SENS0 10* — Zone Sensor has two
temperature set point levers, heat, auto,
off, or cool system switc h, fan auto or fan
on switch. Status indication LED lights,
System on, Heat, Cool, and Service are
provided. These sensors are used with
CV units.
BAY SENS0 13* — Zone temperature
sensor with timed override buttons used
with Tracer® Integrated Comfor t system.
BAY SENS0 14* — Zone temperature
sensor with local temperature
adjustment control and timed override
buttons used with T racer Integrated
Comfort system. May also be used for
Morning Warm-up setpoint and sensor .
BAY SENS0 16* — Temperature Sensor is
a bullet or pencil type sensor that could
be used for temperature input such as
return air duct temperature.
BAYSENS017* — Remote Sensor can be
used for remote zone temperature
sensing capabilities when zone sensors
are used as remote panels or as a
morning warm-up sensor for use with
VAV units or as a zone sensor with Tracer
Integrated Comfort system.
BAYSENS01 9* & BAYSENS020* —
Electronic programmable sensors with
auto or manual changeover with seven
day programming. Keyboard selection of
heat, cool, auto fan or on. All
programmable sensors have System on,
Heat, Cool, Service LED/LCD indicators
as standard. Night setback sensors have
two occupied, and two unoccupied
programs per day. Sensors are available
for CV zone temperature control and VAV
zone temperature control.
BAYSENS021* — Zone Sensor with
supply air single temperature setpoint
and A UT O/OFF system switc h. Status
indication LED lights, System ON, Heat,
Cool, and Service are provided. Sensors
are available to be used with VAV units.
BAYST AT023* — Remote Minimum
Position Potentiometer is used to
remotely specify the minimum
economizer position.
RT-PRC007-EN44
(20-60Ton)
45RT-PRC007-EN
The Trane Company
An American Standard Compan y
www.trane.com
For more information contact your
local district office, or e-mail us at
comfort@trane.com
Literature Order NumberRT-PRC007-EN
File NumberPL-RT-TC/TE/YC-27½ - 50-TONS-PRC0007-EN-10-2001
SupersedesRT-PRC007-EN 02/01
Stocking LocationInland-LaCrosse
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the
right to change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.