RTAC 140-500 ton units (60 Hz)
RTAC 140-400 ton units (50 Hz)
January 2006RTAC-SVX01F-EN
NOTICE: Warnings and Cautions appear at appropriate sections throughout this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
CAUTION: Indicates a situation that may result in equipment or propertydamage only accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can
affect the earth’s naturally occurring stratospheric ozone layer when
released to the atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants that contain
Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen,
Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing
these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants—including
industry replacements for CFCs such as and HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All
technicians who handle refrigerants must be certified. The Federal Clean
Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some
states or municipalities may have additional requirements that must
also be adhered to for responsible management of refrigerants. Know
the applicable laws and follow them.
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover
refrigerant to relieve pressure before opening the system. See unit
nameplate for refrigerant type. Do not use non-approved refrigerants,
refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved
refrigerants, refrigerant substitutes, or refrigerant additives could result
in death or serious injury or equipment damage.
2RTAC-SVX01F-EN
Table of Contents
General Information ............................................................................................. 7
Literature History.................................................................................................... 7
Unit Identification - Nameplates ............................................................................. 7
Unit Inspection ....................................................................................................... 8
Unit Wiring ......................................................................................................... 165
6RTAC-SVX01F-EN
General Information
Literature History
RTAC-SVX001-EN (December 2000)
New manual.
RTAC-SVX01B-EN (September 2001)
New manual describes installation, operation, and maintenance of RTAC units and the
remote evaporator option.
RTAC-SVX01C-EN (February 2002)
Revised manual includes additional RTAC units to size 500 tons, new installation and
maintenance material, and expanded CH530 diagnostics.
RTAC-SVX01D-EN (July 2003)
Revised manual for new evaporator design for 2 compressor units. Design Sequence
H0 and later.
RTAC-SVX01E-EN (July 2004)
Revised manual for new evaporator design for 3 and 4 compressor units. Design
Sequence J0 and later.
RTAC-SVX01F-EN (January 2006)
Revised manual for new control panel design.
Unit Identification - Nameplates
When the unit arrives, compare all nameplate data with ordering, submittal, and shipping information. A typical unit nameplate is shown in Figure 1.
Figure 1Typical Unit Nameplate
RTAC-SVX01F-EN7
General information
Unit Inspection
When the unit is delivered, verify that it is the correct unit and that it is properly
equipped. Compare the information which appears on the unit nameplate with the
ordering and submittal information.
Inspect all exterior components for visible damage. Report any apparent damage or
material shortage to the carrier and make a “unit damage” notation on the carrier’s
delivery receipt. Specify the extent and type of damage found and notify the appropri
ate Trane Sales Office. Do not proceed with installation of a damaged unit without
sales office approval.
Inspection Checklist
To protect against loss due to damage incurred in transit, complete the following
checklist upon receipt of the unit.
•Inspect the individual pieces of the shipment before accepting the unit. Check for
obvious damage to the unit or packing material.
•Inspect the unit for concealed damage as soon as possible after delivery and
before it is stored. Concealed damage must be reported within 15 days.
•If concealed damage is discovered, stop unpacking the shipment. Do not remove
damaged material from the receiving location. Take photos of the damage, if pos
sible. The owner must provide reasonable evidence that the damage did not
occur after delivery.
•Notify the carrier’s terminal of the damage immediately, by phone and by mail.
Request an immediate, joint inspection of the damage with the carrier and the
consignee.
•Notify the Trane sales representative and arrange for repair. Do not repair the unit,
however, until damage is inspected by the carrier’s representative.
-
-
Loose Parts Inventory
Check all the accessories and loose parts which are shipped with the unit against the
shipping list. Included in these items will be water vessel drain plugs, rigging and
electrical diagrams, and service literature, which are placed inside the control panel
and/or starter panel for shipment.
Unit Description
The 140 - 500 ton Model RTAC units are helical-rotary type, air-cooled liquid chillers
designed for installation outdoors. The compressor circuits are completely assem
bled, hermetic packages that are factory-piped, wired, leak-tested, dehydrated, and
tested for proper control operation before shipment.
NOTE: Packaged units are factory charged with refrigerant and oil.
Figure 2 shows a typical RTAC packaged unit and its components.
Table 1 through Table 5 contain general RTAC mechanical specifications for all unit
sizes.
-
8RTAC-SVX01F-EN
General Information
.
Figure 2Typical RTAC Unit
Chilled water inlet and outlet openings are covered for shipment. Each compressor
has a separate compressor motor starter. The RTAC series features Trane’s exclusive
Adaptive Control ™ logic, which monitors the control variables that govern the opera
tion of the chiller unit. Adaptive Control logic can adjust capacity variables to avoid
chiller shutdown when necessary, and keep producing chilled water. The units feature
two independent refrigerant circuits. Compressor unloaders are solenoid actuated
and oil pressure operated. Each refrigerant circuit is provided with filter, sight glass,
electronic expansion valve, and charging valves. The shell-and-tube type evaporator is
manufactured in accordance with ASME standards or other international codes. Each
evaporator is fully insulated and is equipped with water drain and vent connections.
Packaged units have heat tape protection to - 20°F (-28.9°C) as standard. As an
option, a convenience outlet can be supplied.
RTAC-SVX01F-EN9
-
General information
Table 1General Data — 140-250 Ton 60 Hz Units - Standard Efficiency
Size 140155170185200225250
Type STDSTDSTDSTDSTDSTDSTD
Compressor
Quantity2222222
Nominal
Size
Water Storage (gallons)29323335393842
Min. Flow (gpm)193214202217241217241
Max. Flow (gpm)709785741796883796883
Quantity of Coils4444444
Coil Length (inches)156/156180/156180/180216/180216/216252/216252/252
Coil Height (inches)42424242424242
Fins/Ft192192192192192192192
Number of Rows3333333
Figure 3Unit Dimensions 185-200 Ton Standard Efficiency, 60 Hz and 155, 170 Ton, High Efficiency, 50 and 60 Hz
RTAC-SVX01F-EN15
Figure 4Unit Dimensions 225-250 Ton Standard Efficiency, 60 Hz and 185-200 Ton, High Efficiency, 50 and 60 Hz
16RTAC-SVX01F-EN
Figure 5Unit Dimensions 225-250 Ton High Efficiency, 60 Hz
RTAC-SVX01F-EN17
Figure 6Unit Dimensions 250-275 Ton Standard Efficiency, 50 Hz and 250 Ton High Efficiency, 50 Hz and 275 Ton
Standard Efficiency, 60 Hz
18RTAC-SVX01F-EN
Figure 7Unit Dimensions 275 Ton High Efficiency, 50 and 60 Hz; 300 Ton, Standard Efficiency, 50 and 60 Hz and 350
Ton, Standard Efficiency 60 Hz
RTAC-SVX01F-EN19
Figure 8Unit Dimensions 300 Ton High Efficiency, 50 and 60 Hz
20RTAC-SVX01F-EN
Figure 9Unit Dimensions 350-400 Ton Standard Efficiency, Hz and 400 Ton, Standard Efficiency, 60 Hz and 350 Ton
High Efficiency, 50 and 60Hz
RTAC-SVX01F-EN21
Figure 10Unit Dimensions 450-500 Ton Standard Efficiency, 60 Hz and 375-400 Ton, High Efficiency, 50 Hz and 400 Ton
High Efficiency, 60 Hz
22RTAC-SVX01F-EN
Figure 11Unit Dimensions of Condenser/Compressor Unit for Remote Evaporator Option
RTAC-SVX01F-EN23
Figure 12Unit Dimensions for Remote Evaporator 140-170 Ton Standard Efficiency and 140 Ton High Efficiency
24RTAC-SVX01F-EN
Figure 13Unit Dimensions for Remote Evaporator185-250 Ton Standard Efficiency and 155-200 Ton High Efficiency
RTAC-SVX01F-EN25
Model Number Coding System
The model numbers for the unit and the starter are composed of numbers and letters
that represent features of the equipment. Shown in the following table is a sample of
typical unit model number and the coding system for each.
Each position, or group of positions, in the model number is used to represent a feature. For example, in the first table, position 08 of the unit model number, Unit Voltage, contains the number “4”. A 4 in this position means that the unit voltage is 460/
60/3.
Unit Model Number
An example of a typical unit model number (M/N) is:
RTAC 350A UA0N NAFN N1NX 1TEN NN0N N01N
Model number digits are selected and assigned in accordance with the following defi-
nitions using the model number example shown above.
26RTAC-SVX01F-EN
Digit 1-4
Unit Model
RTAC Air Cooled Series R® chiller
Digit 5-7
Unit Nominal Capacity
140140 Nominal Tons
155155 Nominal Tons
170170 Nominal Tons
185185 Nominal Tons
200200 Nominal Tons
225225 Nom inal Tons
250250 Nom inal Tons
275275 Nom inal Tons
300300 Nominal Tons
350350 Nom inal Tons
375375 Nom inal Tons
400400 Nominal Tons
450450 Nom inal Tons
500500 Nominal Tons
Digit 8
Unit Voltage
A200V/60Hz/3Ph power
K220V/50Hz/3 Ph power
C230V/60Hz/3Ph power
J380V/60Hz/3Ph power
D400V/50Hz/3Ph power
4460V/60Hz/3Ph power
Digit 15
Evaporator Temperature Range &
Application Type
FStandard Temp. with Frz Prot
RRem Evap, Std. Temp, No Frz
Prot
GLow Temp, with Frz Prot
Digit 16
Evaporator Configuration
NStandard pass arrangement,
insulated
Digit 17
Condenser Temperature Range
NStandard ambient range
25-115 deg F
HHigh ambient capability
25-125 deg F
LLow ambient capability
0-115 deg F
WWide ambient capability
0-125 deg F
Digit 18
Condenser Fin Material
1Standard aluminum slit fins
2Copper fins, non-slit fins
4Complete Coat aluminum fins
Digit 19
Condenser Fan/Motor Configuration
NCondenser fans with ODP
motors
WLow Noise fans
TCondenser fans with TEAO
motors
Digit 20
Compressor Motor Starter Type
XAcross-the-line starters
YWye-delta closed transition
starters
Digit 21
Incoming Power Line Connection
1Single point power connection
2Dual point power connection (1/
ckt)
Digit 22
Power Line Connection Type
TTerminals only
DNon-fused disconnect
switch(es)
CCircuit Breaker(s), HACR-rated
Digit 23
Unit Operator Interface
EEasy-View operator interface
DDyna-View operator interface
Digit 24
Remote Interface
NNo remote interface
CTracer Comm 3 interface
LLon Talk Communication interface
(LCI)
Digit 25
Control Input Accessories/Options
NNo remote input
RRemote leaving water temp stpt
CRemote current limit setpoint
BRemote lvg. temp.setpoint and
remote current limit setpoint
Digit 26
COOP26
Control Output Accessories/Options
NNo output options
AAlarm relay
CIcemaking
DIcemaking and alarm relay
Digit 27
Short Circuit Rating
0No short circuit withstand rating
510000A SCR
435000A SCR
665000A SCR
Digit 28
Electrical Accessories and Export
Packing
NNo flow switches
FNEMA-1 flow switch - 150 psi
EVapor Proof FS - 150 psi
Digit 29
Control Panel Accessories
NNo convenience outlet
A15A 115V convenience outlet
(60HZ)
Digit 30
Refrigerant Service Valves
1Suction service valves
Digit 31
Compressor Sound Attenuator
Option
0No sound attenuator
1Factory installed sound attenuator
Digit 32
Appearance Options
NNo appearance options
AArchitectural louvered panels
CHalf Louvers
GAccess guards
BAccess guards and half louvers
PPainted unit
LPainted unit with full louvered
panels
HPainted unit with half louvered
panels
KPainted unit with access guards
WPainted w/access guards and half
louvers
Digit33
Installation Accessories
NNo installation accessories
RNeoprene isolators
FFlanged water connection kit
GNeoprene isolators and flange
wtr conn kit
Digit 34
Factory Test
0No factory run test
PPerformance test
WWitness test
Digit 35
Label, and Literature Language
EEnglish
GChinese
Digit 36
Special Order
XStandard catalog configuration
SUnit has special order feature
Digit 37
Safety Devices
NNone
XStandard
RTAC-SVX01F-EN27
Installation - Mechanical
Installation Responsibilities
Generally, the contractor must do the following when installing an RTAC unit:
•Install unit on a flat foundation, level (within 1/4” [6 mm] across the length and
width of the unit), and strong enough to support unit loading.
•Install unit per the instructions contained in the Installation-Mechanical and
Installation-Electrical sections of this manual.
•Install any optional sensors and make electrical connections at the CH530.
•Where specified, provide and install valves in water piping upstream and
downstream of evaporator water connections to isolate the evaporator for
maintenance, and to balance/trim system.
•Furnish and install flow switch to prove chilled water flow.
•Furnish and install pressure gauges in inlet and outlet piping of the evaporator.
•Furnish and install a drain valve to the bottom of the evaporator waterbox.
•Supply and install a vent cock to the top of the evaporator waterbox.
•Furnish and install strainers ahead of all pumps and automatic modulating valves,
and at inlet of evaporator.
•Provide and install field wiring.
•Install heat tape and insulate the chilled water lines and any other portions of the
system, as required, to prevent sweating under normal operating conditions or
freezing during low ambient temperature conditions.
•Install evaporator drain plug. The plug ships in unit control panel.
•Start unit under supervision of a qualified service technician.
Nameplates
The RTAC outdoor unit nameplates (Figure 1) are applied to the exterior of the Control
Panel. A compressor nameplate is located on each compressor.
Outdoor Unit Nameplate
The outdoor unit nameplate provides the following information:
– Unit model and size description.
– Unit serial number.
– Identifies unit electrical requirements.
– Lists correct operating charges of R-134a and refrigerant oil (Trane OIL00048).
– Lists unit test pressures.
– Identifies installation, operation and maintenance and service data literature
(Pueblo).
– Lists drawing numbers for unit wiring diagrams (Pueblo).
Compressor Nameplate
The compressor nameplate provides following information:
– Compressor model number.
– Compressor serial number.
– Compressor electrical characteristics.
– Utilization range.
– Recommended refrigerant.
28RTAC-SVX01F-EN
Installation - Mechanical
Storage
Extended storage of the outdoor unit prior to installation requires the following precautionary measures:
1.Store the outdoor unit in a secure area.
2. At least every three months (quarterly), check the pressure in the refrigerant circuits to verify that the refrigerant charge is intact. If it is not, contact a qualified
service organization and the appropriate Trane sales office.
3. Close the discharge and liquid line isolation valves.
General
Report any damage incurred during handling or installation to the Trane sales office
immediately.
Location Requirements
Setting the Unit
A base or foundation is not required if the selected unit location is level and strong
enough to support the unit’s operating weight as listed in
the General Information section.
See Table 6 for lifting weights and center of gravity (CG) dimensions.
Tab l e 1 through Tab l e 5 in
1.Lifting chains/cables will not
be the same length. Adjust to keep unit level while lifting.
2.Do not fork lift unit.
3.Weights are typical for units with R-134a charge.
Figure 14Lifting the Unit (Package and Remote) 15-21-foot Base
RTAC-SVX01F-EN29
Installation - Mechanical
1.Lifting chains/cables will not be the same length. Adjust to
keep unit level while lifting.
2.Do not fork lift unit.
3.Weights are typical for units with R-134a charge.
Figure 15Lifting the Unit (Package and Remote) 30-36-foot Base
1.Lifting chains/cables will not be the same length. Adjust to
keep unit level while lifting.
2.Do not fork lift unit.
3. Weights are typical for units with R-134a charge.
Figure 16Lifting the Unit 39-45-foot Base
30RTAC-SVX01F-EN
Loading...
+ 222 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.