Trane PTAC-SVX01C-EN User Manual

Installation, Operation, and Maintenance

Packaged Terminal Air Conditioner

PTEE070/PTHE070 (7,000 Btuh) PTEE090/PTHE 090 (9,000 Btuh) PTEE120/PTHE120 (12,000 Btuh) PTEE150/PTHE150 (15,000 Btuh)
September 2006 PTAC-SVX01C-EN

Table of Contents

Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . 3
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Ta b le 1 . Minimum interior and exterior projections . . . . . . . . 6
Table 2. Minimum clearances and projections . . . . . . . . . . .7
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Energy Management System . . . . . . . . . . . . . . . . . . . . . . 19
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigeration System Service . . . . . . . . . . . . . . . . . . . . . . 31
Brazing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Cooling Performance Test . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ground Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 27. Thermistor indoor coil resistance . . . . . . . . . . . . 38
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 28. Diagnostic codes . . . . . . . . . . . . . . . . . . . . . . . 41
Table 29. Latching diagnostics, reset required . . . . . . . . . 41
Table 30. Automatically resetting diagnostics . . . . . . . . . . 41
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Full 1st Year Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Full 2nd - 5th Sealed System Warranty . . . . . . . . . . . . . . . 50
Limited 2nd through 5th Year Functional Parts Warranty 50
2 PTAC-SVX01C-EN

Model Number Description

Each Packaged Terminal Air Conditioner/Heat Pump is assigned a multiple-character alphanumeric model number that precisely identifies each unit.
An explanation of the identification code that appears on the unit nameplate is shown below.
The model number helps owner/ operator, installing contractors, and service technicians to define the operation, components and options for a specific unit.
P T E E 0 9 0 1 * A A 1 2 3 4 5 6 7 8 9 10 11
Digits 1, 2—Packaged Terminal Air Conditioner
Digit 3—Product Type
E = Air Conditioner with auxiliary heat
H= Heat Pump
Digit 4—Development Sequence
E = Fifth Development Series
Digit 5, 6, 7—Unit Cooling Capacity
070 = 7,000 Btu
090 = 9,000 Btu
120 = 12,000 Btu
150 = 15,000 Btu
Refer to the model number printed on the equipment nameplate when ordering replacement parts or requesting service.
Digit 8—Main Power Supply
1 = 230-208V/60Hz/1phase
2 = 265V/60Hz/1phase
4 = 115V/60Hz/1phase (Hydronic Only)
Digit 9 —Electric Heat Capacity*
U = Universal Heater (Heater kW determined by
power cord, see Accessories Section)
W = Hydronic (ships with no front cover & no
electric heater)
Digit 10 — Unit Features
A = Standard
C = Corrosion Resistant
D = Internal Condensate Pump
Digit 11—Minor Design Sequence
Front and discharge grille
Electric heater
Indoor coil
*All heat pump units must have electric heat.
Wall sleeve
Outdoor grille
Outdoor fan
Indoor Fan
Display Module
Outdoor coil
Rotary compressor
Power cord
Control box
Power cord coverplate (not shown)
PTAC-SVX01C-EN 3

General Information

General Information
NOTICE:
Warnings and Cautions appear in appropriate sections throughout this manual. Read these carefully.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment or property-damage­only accidents.

Overview of Manual

Note: One copy of this document
ships with each unit and is customer property. It must be retained by the customer.
This booklet describes proper installation, operation, and maintenance procedures for PTACs. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere.
In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact to the environment.
The manufacturer advocates the responsible handling of all refrigerants—including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
The manufacturer believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry.
All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, recovering, recycling and reclaiming of certain refrigerants and the equipment that is used in these service procedures.
In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNIN G Hazardous Voltage with Capacitators!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
© 2005 American Standard Inc. All rights reserved PTAC-SVX01C-EN
General Information

Refrigerant Handling Procedures

WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.

Environmental Accountability Policy

The manufacturer urges that all HVAC servicers make every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC, and HFC refrigerants to the atmosphere. Always act in a responsible manner to conserve refrigerants for continued usage even when acceptable alternatives are available.

Recover and Recycle Refrigerants

Never release refrigerant to the atmosphere!
Always recover and/or recycle refrigerant for reuse, reprocessing (reclaimed), or properly dispose if removing from equipment.
Always determine the recycle or reclaim requirements of the refrigerant before beginning the recovery procedure.
Obtain a chemical analysis of the refrigerant if necessary.
Questions about recovered refrigerant and acceptable refrigerant quality standards are addressed in ARI Standard 700.

Refrigerant Handling and Safety

Consult the manufacturer’s material safety data sheet (MSDS) for information on refrigerant handling to fully understand health, safety, storage, handling, and disposal requirements.
Use only approved containment vessels and refer to appropriate safety standards. Comply with all applicable transportation standards when shipping refrigerant containers.

Service Equipment and Procedures

To minimize refrigerant emissions while recovering refrigerant, use the manufacturer’s recommended recycling equipment per the MSDS.
Use equipment and methods which will pull the lowest possible system vacuum while recovering and condensing refrigerant. Equipment capable of pulling a vacuum of less than 1,000 microns (1.0 mm) of mercury is recommended.
Do not open the unit to the atmosphere for service work until refrigerant is fully removed/ recovered.
When leak-testing with trace refrigerant and nitrogen, use HCFC­22 (R-22) rather than CFC-12 (R-12) or any other fully-halogenated refrigerant.
Be aware of any new leak test methods which may eliminate refrigerants as a trace gas.
Perform evacuation prior to charging with a vacuum pump capable of pulling a vacuum of 1,000 microns (1.0 mm) of mercury or less. Let the unit stand for 12 hours and with the vacuum not rising above 2,500 microns (2.6 mm) of mercury.
A rise above 2,500 microns (2.5 mm) of mercury indicates a leak test is required to locate and repair any leaks. A leak test is required on any repaired area.
Charge refrigerant into the equipment only after equipment does not leak or contain moisture.
Refer to proper refrigerant charge requirements in the maintenance section of this manual to ensure efficient machine operation.
When charging is complete, purge or drain charging lines into an approved refrigerant container.
Seal all used refrigerant containers with approved closure devices to prevent unused refrigerant from escaping to the atmosphere.
Take extra care to properly maintain all service equipment directly supporting refrigerant service work such as gauges, hoses, vacuum pumps, and recycling equipment.
When cleaning system components or parts, avoid using CFC-11 (R-11) or CFC-113 (R-113). Use only cleaning­solvents that do not have ozone depletion factors.
Properly dispose of used materials. Refrigeration system cleanup methods using filters and driers are preferred.
Check for leaks when excessive purge operation is observed.
Keep abreast of unit enhancements, conversion refrigerants, compatible parts, and manufacturer’s recommendations that will reduce refrigerant emissions and increase equipment operating efficiencies.
PTAC-SVX01C-EN 5

Pre-Installation

Pre-Installation

Pre-Installation Considerations

Before beginning installation, make the following considerations:
1. Verify the wall opening is in the correct location and the correct size.
2. Drill mounting holes on both sides of the wall sleeve, if equipment requires any of the following options: subbase, leveling legs, or hydronic heat kit.
If dimension A in Figure 2 is at or near the minimum specified in
Ta b l e 2, p . 7 , accessory options
should be mounted to the sleeve prior to installing the sleeve in the wall. Otherwise, there may not be enough access room for the tools used to mount the accessories to the wall sleeve.
3. If additional wall sleeve support is required, the leveling leg accessory kit or a subbase kit that includes leveling legs can be used to provide extra support.
4. If installing in a concrete or masonry wall, you must provide a lintel in the wall opening for support. Do not use the wall sleeve as a lintel.
See Figure 1 for a typical lintel construction.
Figure 1. Typical Installation
framing with lintel
5. When installing in walls that are deeper than 13 1/2 inches, use an extended wall sleeve. A sleeve without the proper depth will require special care to prevent problems with rain water, condensate drainage, and intake/ discharge air.
Under these circumstances, careful jobsite analysis and cautions are required. Consult your local HVAC representative before attempting such installations.

Checklist

The following checklist provides an overview of the factory­recommended pre-installation considerations. Follow the procedures in this section to ensure the installation is complete and adequate for proper unit operation. Verify this checklist is complete before beginning unit installation.
If unit arrives shipped on its side, do not accept.
Verify the unit size and tagging with the unit nameplate to ensure the correct unit is received.
Inspect the unit for possible shipping damage and make any necessary claims with the freight delivery company immediately.
Verify the installation location is free of airflow obstructions, such as curtains, furniture, trees, or other objects that may block airflow to and from the unit.
WARNIN G
Fire Hazard!
Do not use extension cords. Using extension cords could cause a fire.
Make provisions for correct supply power and that the electrical receptacle is within 52 inches of the lower right corner of the equipment.
Ensure the unit wall opening is level.
Ensure adequate sealing and insulation is around the wall sleeve.
Figure 2. Minimum unit clearance
Table 1. Minimum interior and exterior
projections
42 1/2” min.
Finished Floor
Figure 3. Minimum wall opening
dimensions
16 1/4” min.
Dimension B
6 PTAC-SVX01C-EN
Pre-Installation
Table 2. Minimum clearances and
projections
Option In. Mm In. Mm In. Mm
Minimum clearances Minimum projection
AB C
Wall sleeve only 3 75 0 0 0 0
Subbase kit 3 75 3 1/4 85 2 3/4 70
Leveling legs kit 3 75 3 75 2 50
Hydronic heat kit
Drain kit 3 75 0
Hardwire kit 3 75 3 75 0 0
(1)
Max height is based on skirt options available.
(2)
This dimension can be from 2-6", but if this dimension exceeds 6" an extended standard kick plate is necessary.
(3)
This dimension can be from 50-150mm, but if this dimension exceeds 150mm an extended standard kick plate is necessary.
(4)
To achieve a flush fit between the hydronic front and the finished wall, dimension "C" must be between 3" and 3-1/8". If this dimension is more than 3-1/8" there will be a gap between the front and the wall. This gap could permit occupant access to hydronic lines or other dangerous parts.
(5)
To achieve a flush fit between the hydronic front and the finished wall, dimension "C" must be between 76-80mm. If this dimension is more than 80mm there will be a gap between the front and the wall. This gap could permit occupant access to hydronic lines or other dangerous parts.
(6)
If inside mounted then B = 1-1/2 inches
(7)
If inside mounted then B = 40 mm
(1)
9 230 2-6”
(6)
(2)
50 -150
(7)
1
(3)
(4)
3-3 1/
76-80
8
00
(5)

Receiving and Handling

Shipping Package

The chassis and the cabinet front ship in one carton. Accessories ship separate.

Receiving Checklist

Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage.
Verify that the unit nameplate data corresponds to the sales order and bill of lading (including electrical data).
Visually inspect the unit exterior for physical signs of shipping damage or material shortages.
If a unit appears damaged, inspect it immediately before accepting the shipment. Remove access panels and check for interior component damage. Make specific notations concerning the damage on the freight bill. Do not accept delivery.
Report concealed damage to the freight line within the allotted time after delivery. Verify with the carrier what their allotted time is to submit a claim.
Note: Failure to follow these
procedures may result in no reimbursement for damages from the freight company.
Do not move damaged material from the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the shipment if it appears damaged. Retain all packaging. Take photos of damaged material if possible.
Notify the carrier’s terminal of the damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.
Notify your HVAC representative of the damage and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.
PTAC-SVX01C-EN 7

Unit Dimensions

Unit Dimensions
Figure 4. Unit with wall sleeve and subbase accessory
Figure 5. Wall Sleeve
8 PTAC-SVX01C-EN
Unit Dimensions
PTAC Wall Sleeve
Air discharge
Figure 6. Top view of the hydronic kit
Hotwater or steam inlet and outlet connection (left hand coil connection)
1“
1-1/20”
20-1/4”
16-1/5”
Air inlet
Figure 7. Hydronic kit front view
Steam/water coil position
Front View
Unit controls compartment
Steam inlet and outlet connection (right hand coil connection)
53-2/3”
PTAC
Hydronic front
Toe plate 0 to 3.0” long
Top of wall sleeve
Bottom of wall sleeve
1-3/8” - 1-1/2”
5.00”
12.62
Figure 8. Hydronic kit side view
PTAC-SVX01C-EN 9
WARNIN G
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
WARNING
Fire Hazard!
Do not use an extension cord with this unit. Doing so may cause a fire.
Installation

Installation

CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.

Electrical Requirements

The PTAC can be powered by a power cord connected to a receptacle in the wall or in a subbase. It can also be connected directly to the building supply wires with a hard wire kit.
For U.S. approval, 265V units must have a permanent wiring connection. This requirement can be met either by supplying a subbase for concealed cord connection or by direct wiring with the hard wire kit.
The power cord measures 60 inches, with 56 inches usable from the point where the cord exits the unit cabinet and the attached plug.
10 PTAC-SVX01C-EN
Installation
Table 3. Electric heat capacity and electrical data, models PTEE and PTHE
(i)
Nominal heating Building circuit requirement
Electric
Voltage
Size (kW)
heater
(ii)
230/208 2.0/1.6 1 6,800/
230/208 3.0/2.4 1 10,200/
230/208 5.0/4.0 1 17,100/
# of stages
Btu/h at 230/208V
5,500
8,200
13,700
Btu/h at 265V
- 2000/
- 3000/
- 5000/
Total watts
1600
2400
4000
Unit
(iii)
total amps
Minimum ampacity
(iv)
Maximum protection
(v)
8.9/7.9 11.4 15 6 - 15 P
13.4/11.8 17 20 6 - 20 P
22.2/19.7 28 30 6 - 30 P
Plug
265 2.0 1 - 6,800 2000 7.7 9.8 15 7 - 20 P
265 3.0 1 - 10,200 3000 11.6 14.7 15 7 - 20 P
265 5.0 1 - 17,100 5000 19.3 24.4 25 7 - 30 P
(i)
All heat pumps have electric heat.
(ii)
Minimum voltage on 230/208 volt models is 187 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 239 volts; max­imum is 292 volts.
(iii)
Total watts for 7,000 and 9,000 Btu models; add 70 watts for 12,000 and 15,000 Btu models.
(iv)
Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
(v)
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge­style time delay fuses.
Table 4. Power receptacle configurations
Unit Voltage Rating
Unit plug
230/ 208
230/ 208
230/ 208 265 265
Plug amp rating
NEMA designation
Receptacle
Receptacle amp rating
NEMA designation
15 20 30 15/20 30
6-15P 6-20P 6-30P 7-15P/7-20P 7-30P
20 20 30 20 30
6-20R 6-20R 6-30R 7-20R 7-30R
PTAC-SVX01C-EN 11
Installation
Figure 9. Panel wall installation

Installation Procedure

WARNIN G Hazardous Voltage w/ Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.Install components in this order.
1. Remove rear closure panel from
wall sleeve.
2. Install drain kit (optional).
3. Install outdoor air grille in wall
sleeve.
12 PTAC-SVX01C-EN
4. Install wall sleeve in wall opening.
5. Install unit chassis in wall sleeve.
6. Install unit power supply.
•Power cord
•Hard wire kit
Subbase kit
Electrical receptacle
Power switch
Cicuit breaker
7. Install unit controls.
Display module
Remote wall thermostat
8. Configure display module settings.
9. Progammable settings.

Step 1. Remove rear closure panel from wall sleeve.

1. Remove the zigzag folded cardboard sleeve stiffener. See
Figure 10. Remove the rear
closure panel by folding the four flaps as indicated in Figure 11
Figure 10. Wall sleeve stiffener
Figure 11. Sleeve rear closure
panel
Installation
2. Grasping the top and bottom flanges of the rear closure panel as shown in Figure 12, the entire panel is pulled out diagonally from one side.
Figure 12. Pull rear closure panel
out of wall sleeve

Step 2. Install drain kit in wall sleeve.

Drain kits are available for indoor or outdoor installation to help condensate drain from either the right or left side of the wall sleeve externally, or from the bottom of the sleeve internally.
Note: For installation procedures,
please refer to the Installation Guide that accompanied the accessory.
If you do not use the drain kit, condensate will drain out of the rear of the wall sleeve. The drain kit must be installed before the outdoor grille is installed.
Step 3. Install outdoor air

Step 4. Install wall sleeve in wall opening.

For condensate to drain properly inside the unit, the sleeve must be installed properly:
level from right to left
with a slight downward pitch from the indoor side to the outdoor side
Note: If equipment is 230/208 volt,
verify the electrical receptacle is located within 52 inches of the sleeve’s right hand corner. Do not use an extension cord.
Note: For installation procedures,
please refer to the Installation Guide that accompanied the accessory.
5. Install unit chassis in wall
sleeve.
WARNING
Fire Hazard!
Do not use an extension cord with this unit. Doing so may cause a fire.
1. Attach the insulation strip to the upper rear of the wall sleeve. See
Ta bl e 1 3 . If using an extended
wall sleeve, attach the insulation strip between the two baffles, touching the baffle surface facing towards the front.
4. Slide the chassis into the wall sleeve until the chassis flanges contact the front edge of the wall sleeve. See Figure 14.
5. Secure the chassis to the wall sleeve using three screws on each side of the chassis to ensure a proper seal between the chassis and the wall sleeve . The screws are supplied in a plastic bag which is attached to the power cord. See Figure 15.
6. Verify the indoor and outdoor grilles are free of airflow obstructions.
7. Make the power supply connections as detailed in the next step.
Figure 14. Slide unit chassis into
the wall sleeve
grille in wall sleeve.
An outdoor air grille directs airflow for proper unit operation and to protect the outdoor coil. Install the grille before installing the chassis.
Outdoor air grille options are either a stamped grille or an architectural grille. When replacing an old chassis with an existing grille, please check with your HVAC representative to determine if the new chassis can be used with the old outdoor grille.
Using the wrong type outdoor grille can decrease cooling or heating capacity, increase energy usage, or shorten compressor life.
Note: For installation procedures,
please refer to the Installation Guide that accompanied the accessory.
PTAC-SVX01C-EN 13
Front
Bottom
Figure 13. Insulation strip location
2. Remove the cabinet front from the chassis by pulling the bottom of the cabinet front away from the chassis until the retaining clips disengage.
3. If using a subbase, be sure the right-hand subbase cover is removed before installing the chassis in the wall sleeve.
11”
Rear
Figure 15. Secure chassis to wall
sleeve

Step 6. Install unit power supply.

Note: For installation procedures,
please refer to the Installation Guide that accompanied the accessory.
Installation
Table 5. Unit power supply
Voltage Options Accessory Accessory part number
115V
Option 1.
Option 2.
Option 3. Required: Hard Wire Kit BAYHWRK001
265 V
Option 1. Required: Universal Subbase BAYSUB001
Option 2. Required: Hard Wire Kit BAYHWRK001
230/ 208 V
Option 1. Required: Universal Power Cord
Option 2. Required: Universal Subbase BAYSUB001
Option 3. Required: Hard Wire Kit BAYHWRK001
1. All units required either a power cord or hard wire kit to power the unit
2. The Hydronic chassis "W" ships with no electric heat
3. All Hydronic Chassis "W" units required a power cord
4. All 265volt Hydronic chassis "W" required subbase, fuses and socket.
Required: Universal Power Cord 15
Required: Universal Power Cord 15
Optional Power Switch BAYPSW002
Optional Power Switch if 30 Amp BAYPSW002
Optional Power Switch BAYPSW002
Optional Circuit Breaker 15, 20 or
Optional Power Switch BAYPSW002
Amp
A field supplied 115 volt 15 amp receptacle is mounted in the building floor or wall. A Trane 115 volt 15 amp power cord BAYPCRD007 is connected to the PTAC and plugged into the receptacle.
Amp
Universal Subbase BAYSUB001
A Trane subbase BAYSUB001 is attached to the wall sleeve. A field supplied 115 volt 15 amp receptacle is mounted into the subbase. A Trane 115 volt 15 amp power cord BAYPCRD007 is connected to the PTAC and plugged into the receptacle
Connector for Hardwire Kit for 15 Amp
A Trane hardwire kit BAYHRK001 is direct wired to the building power supply and attached to the PTAC. A Trane connector kit BAYCNHK031 is connected to the PTAC and connected to the hard wire kit in the unit mounted junction box
Socket for subbase 20 or 30 Amp
Universal Power Cord 15,20 or 30 Amp
Fuses 15, 20 or 30 Amp BAYFUSE001, BAYFUSE002,
Connector for Hardwire Kit for 15, 20 or 30 Amp
15,20 or 30 Amp
Socket for subbase 20 or 30 Amp
Universal Power Cord 15,20 or 30 Amp
30 Amp
Power Switch BAYPSW002
Connector for Hardwire Kit for 15, 20 or 30 Amp
BAYPCRD007
BAYPCRD007
BAYCNHK031
BAYSCKT003, BAYSCKT004
BAYPCRD004, BAYPCRD005, BAYPCRD006
BAYFUSE003
BAYCNHK021, BAYCNHK022 , BAYCNHK023
BAYPCRD001, BAYPCRD002, BAYPCRD003
BAYSCKT001, BAYSCKT002
BAYPCRD001, BAYPCRD002, BAYPCRD003
BAYCBKR001, BAYCBKR002, BAYCBKR003
BAYCNHK011, BAYCNHK012, BAYCNHK013

Step 7. Install the unit controls.

The PTAC controller’s normal operation can be operated by using either
Display module - can be wall­mounted or unit mounted.
Remote Class 2 thermostat -
For Remote Class 2 Thermostat Installation, read installation, operation, and maintenance booklet carefully.
Look in Wiring Diagram section for information on wiring.
If a remote thermostat is connected, the unit's display will not be present and the controller's normal space temperature control functionality is overridden by the remote device.
When the controller is being directed by a remote thermostat, the following inputs/functions are disabled or not present:
1. User display inputs (setpoint/ mode/fan)
2. Dehumidification
3. Configuration setup (indoor fan, setpoint limits, EMS offset, display units)
4. Energy management system
5. Manual Test
Unit functions that remain under direct supervision of the controller are:
1. Random Restart
2. Heat Pump OAT switchover
3. Tubing burst protection
4. Room freeze protection
5. Indoor coil freeze protection
6. Defrost control
When connected to a remote thermostat, the controller interprets the combination of thermostat inputs as its operating mode and behaves accordingly.
It is recommended to use a small screwdriver to gently pryt the removable treminal block "TB2" up and off for easy connection.
14 PTAC-SVX01C-EN
Installation
Note: If using a third party
thermostat to control the unit, the thermostat must have a clearly marked OFF state or position.
Note: It is important to make sure
that the control board’s fuse is functioning. The specs for the control board fuse are: 5x20mm, 250V, 315mA, fast acting. For more inormation on a blown fuse on the control board, check the Troubleshooting section of this document.
Table 6. Maximum wire length for front
External Interface
Thermostat
Energy mgmt system #20 900 ft.
Remote fan #20 60 ft.
Display module #20 100 ft.
desk switch and remote control connections
Wire
Specification
Size Length
#22 100 ft.
#20 200 ft
#18 300 ft.
#18 1500 ft.
#18 66 ft.
#18 120 ft.
Table 7. Wiring Voltage
Unit Mode
High Heat Pump 24 0 0 24 0 Heat
High Auxiliary Heat 24 0 24 0 X Heat
Low Auxiliary Heat 0 24 24 0 X Heat
PTEE Air Conditioner (Auxiliary is Electric, Hot Water, or Steam
Notes: In the event that none of the combinations listed in the table above is present, the input will be deemed invalid and all heating, cooling, and fan operation will be disabled.
High Cooling 24 0 0 24 X Cool
Low Cooling 0 24 0 24 X Cool
High Fan 24 0 0 0 X Fan Only
Low Fan 0 24 0 0 X Fan Only
Off 0 0 0 0 X Off – no capacity
Voltage at terminal Corresponding
Normal
OperationGH GL W Y O
Table 7. Wiring Voltage
Unit Mode
PTHE Heat Pump Auxiliary is Electric only
Voltage at terminal Corresponding
High Heat Pump 24 0 0 24 0 Heat
Low Heat Pump 0 24 0 24 0 Heat
High Emgcy Heat 24 0 24 0 0 Heat
24 0 24 24 0 Electric Heat Only
Low Emgcy Heat 0 24 24 0 0 Heat
0 24 24 24 0 Electric Heat Only
High Cooling 24 0 0 24 24 Cool
Low Cooling 0 24 0 24 24 Cool
High Fan 24 0 0 0 0 Fan Only
Low Fan 0 24 0 0 0 Fan Only
Off 0 0 0 0 0 Off – no capacity
Normal
OperationGH GL W Y O
PTAC-SVX01C-EN 15
Installation
Table 8. Output settings
ID
User Mode / Model
High Heat Pump (PTHE only)
Low Heat Pump (PTHE only)
High Emergency/ Auxiliary Heat
Low Emergency/ Auxiliary Heat
High Cooling ON OFF OFF ON ON ON EN EN EN
Low Cooling OFF ON OFF ON ON ON EN EN EN
High Fan ON OFF OFF OFF N/C OFF EN EN EN
Low Fan OFF ON OFF OFF N/C OFF EN EN EN
Off OFF OFF OFF OFF N/C OFF OFF EN OFF
Notes: EN = Enabled - operations based on other logic Notes: N/C = No change from prior state
Fan High
ON OFF OFF ON OF ON EN EN EN
OFF ON OFF ON OFF ON EN EN EN
ON OFF ON OFF N/C OFF EN EN EN
OFF ON ON OFF N/C OFF EN EN EN
ID Fan Low
Aux Heat Comp
Rev Valve (PTHE)
OD Fan
Rmt Fan
Cond Pump (PTHE)
Vent Door /Fan

Step 8. Configure the display module settings

Indoor Temperature setpoint
The indoor temperature setpoint buttons tell the unit how warm or cool the occupant wants the room.
The setpoint is set by pressinging the up/down buttons on the interface module. These buttons do not scroll (i.e. holding the button will not continue to adjust the setpoint value) because each adjustment of the setpoint value requires its own unique button press.
Default setpoint on first power up: 72°F (22.0°C – closest approximation)
Setpoint resolution: ± 1°F (± 0.5°C)
User Mode Selection
Pressing the MODE button on the unit tells the unit which mode the occupant prefers. There are four modes to choose from.
1. C OO L
2. HEAT
3. FAN (fan only)
4. OFF (default for first power up)
Figure 16. Digital display module
Fan Speed Selection
Pressing the FAN button on the interface module determines fan speed. There are two fan speeds to choose from.
1. LOW (default for first power up)
2. HIGH

Field commissioning support

Manual Test Mode
A manual test mode is provided to allow a field technician to verify proper output and end device operation through a predetermined, timed sequence.
Fan
Mode
The sequence will automatically advance through all outputs and exit when the sequence has completed; it is left to the technician to monitor the status of the end devices during the test to verify that each operates properly.
Manual test is initiated by combining the following conditions:
User Mode = OFF
Press and hold MODE & SETPOINT DOWN for 5 seconds
During the test process, the word "STEP" and the corresponding step number will be lighted on the display. After the final step has been executed, the controller will exit Manual test and force the controller to into a reset.
Manual test mode may be cancelled by pressing any button on the display.
Manual test is not available if there is no interface module, as is in Class 2 control applications.
The test sequence attempts to clear unit diagnostics and restore normal unit operation prior to testing the outputs. If the diagnostics remain after an attempt to clear them, manual test may be affected or disallowed.
Dehumidification
The PTAC controller does not directly measure room humidity.
The PTAC provides dehumidfication by combining the following actions in a predefined sequence.
1. The PTAC subcools the room to a preset state, a dehumidification offset below the cooling setpoint.
2. The unit will automatically adjust the fan speed.
3. When incorporating the vent door option, the controller will automatically adjust its position.
16 PTAC-SVX01C-EN
Loading...
+ 36 hidden pages