EarthWise™™ Purge System with Tracer®®
AdaptiView™™ Control for Water-Cooled CenTraVac™™
Chillers with R-123 Refrigerant
PRGD
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
July 2017
X39641072060
SSAAFFEETTYY WWAARRNNIINNGG
PPRRGGDD--SSVVXX0011FF--EENN
Page 2
Introduction
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs). Not all refrigerants
containing these compounds have the same potential
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs and HCFCs such as
saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices
are important to the environment, our customers, and
the air conditioning industry. All technicians who
handle refrigerants must be certified according to local
rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.
IImmppoorrttaanntt:: The PRGD purge uses R-404A refrigerant
and is used with chillers using R-123 and
OIL00022. Verify proper refrigerant and oil
for the PRGD purge and chiller before
proceeding!
Copyright
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Each Trane EarthWise™ purge system is assigned a
alphanumeric model number that identifies the
operating components and option for that specific unit
(see “EarthWise Purge System Model Number,” p. 6
Figure 1. Example of a typical nameplate
for detailed information). The model number is also
printed on the unit nameplate. It is important to refer to
the model number when ordering parts or requesting
technical assistance.
PRGD-SVX01F-EN
5
Page 6
EarthWise Purge System Model Number
Digit 1, 2, 3 — Unit Type
PRG = Purge
Digit 4 — Development Sequence
A = First Generation
B = Second Generation
C = Third Generation
D = Fourth Generation
Digit 5 — Enclosure Type
A = Standard
B = NEMA 4
C = NEMA 4 with Hersite Condensing Unit
S = Special
Digit 6 — Control Options
0 = Without Power Supply
1 = With Power Supply
2 = Standard Condenser Pressure Cutout
3 = ASME Condenser Pressure Cutout
Digit 7 — Control Interface
0 = Chiller Interface
1 = Purge Interface
Digit 8 — Frequency
1 = 60 Hz
2 = 50 Hz
Digit 9 — Vacuum Pump
A = Standard Vacuum Pump
B = High Vacuum Pump
C = Industrial Vacuum Pump
IImmppoorrttaanntt:: The PRGD purge uses R-404A refrigerant
and is used with chillers using R-123 and
OIL00022. Verify proper refrigerant and oil
for the PRGD purge and chiller before
proceeding!
This guide describes the operation and maintenance of
a Trane® EarthWise™ purge system with Tracer®
AdaptiView™ controls. Tracer® AdaptiView™ controls
include the Tracer® UC800 controller and the Tracer®
AdaptiView™ display.
General Information
Centrifugal chillers that use low-pressure refrigerants,
such as R-123, operate with areas of the chiller at less
than atmospheric pressure. Non-condensables in the
air, such as water and nitrogen vapor, may leak into
these low-pressure areas and accumulate in the
condenser. If these non-condensables are not
removed, the condenser loses its ability to condense
refrigerant efficiently and the pressure of the
condenser increases. Increased condenser pressure
lowers the chiller’s efficiency and capacity.
A purge system is required on low-pressure centrifugal
chillers. It is a device that is externally mounted on the
chiller. Its purpose is to remove non-condensable
materials that have leaked into the machine.
NNoottee:: For convenience, the term “air” is often used in
describing non-condensables removed by the
purge system, although any other noncondensable materials that may exist in the
chiller are also removed by the purge system.
Reference Sources
The following reference documents may be helpful
resources for EarthWise™ purge system operation and
maintenance:
•Installation, Operation, and Maintenance Guide:
CDHF and CDHG Water-cooled CenTraVac Chillers
with Tracer AdaptiView Control (CDHF-SVX01*-EN)
•Installation, Operation, and Maintenance Guide:
CVHE, CVHF, CVHG Water-cooled CenTraVac
Chillers with Tracer AdaptiView Control (CVHE-
SVX02*-EN)
•Installation, Operation, and Maintenance Guide:
CVHL Water-cooled CenTraVac Chillers with Tracer
AdaptiView Control (CVHL-SVX01*-EN)
•Installation, Operation, and Maintenance Guide:
Series S CVHS Water-cooled CenTraVac Chillers
with Tracer AdaptiView Control and AdaptiSpeed
Technology (CVHS-SVX01*-EN)
•Diagnostics Manual: Diagnostic Descriptions,
Troubleshooting Tables, and Control Component
Overview for Water-cooled CenTraVac Chillers with
Tracer AdaptiView Control (CTV-SVD03*-EN)
•Programming Guide: Tracer TU Service Tool for
Water-cooled CenTraVac Chillers with Tracer
AdaptiView Control (CTV-SVP02*-EN)
•Operations Guide: Tracer AdaptiView Display for
Water-cooled CenTraVac Chillers (CTV-SVU01*-EN)
•Getting Started Guide: Tracer TU Service Tool
(TTU-SVN01*-EN)
How a Purge System Works
From a functional standpoint, the purge system can be
divided into subsystems of components. This section
identifies and describes the function of these
subsystems.
The following list identifies these subsystems and their
components; the following figures illustrate them:
•Refrigeration circuit subsystem
– Purge tank
– Purge evaporator coil (inside purge tank)
– 1/4 hp air-cooled condensing unit (compressor,
fan, condensing coil)
– Automatic expansion valve
– Chiller refrigerant supply line
– Chiller refrigerant return line (includes filter-
drier and moisture-indicating sight glass)
•Purge tank subsystem
– Purge tank
– Purge evaporator coil (inside purge tank)
– Pressure-relief device (fusible plug)
– Liquid level sensor (float switch)
– Supply and return lines to the chiller condenser
•Pump-out subsystem
– Pump-out compressor
– Pump-out solenoid valve
•Carbon tank and regeneration subsystem
– Carbon tank
– Carbon tank heater
– Regeneration solenoid valve
PRGD-SVX01F-EN
7
Page 8
PPuurrggee SSyysstteemm OOvveerrvviieeww
– Exhaust solenoid valve
– Pressure-relief valve
– Temperature sensor
Detailed descriptions of the various purge subsystems
are included after the figures.
Refrigeration Circuit Subsystem
The purge evaporator of the refrigeration circuit is
located in the purge tank. The purge tank is connected
to the chiller condenser by supply and return lines
through which chiller refrigerant can freely flow.
The purge evaporator coil presents a cold condensing
surface to the chiller refrigerant entering the purge
tank. When the purge refrigeration system is running,
refrigerant from the chiller condenser is attracted to the
cold surface of the purge evaporator. When the
gaseous refrigerant contacts the surface of the purge
evaporator coil, it condenses into a liquid, leaving a
partial vacuum behind. More refrigerant vapor from the
chiller condenser migrates to the purge tank to fill the
vacuum.
The liquid refrigerant that has condensed in the purge
tank returns to the chiller condenser through the liquid
return line. The return line includes a filter-drier and a
moisture-indicating sight glass.
The condensing unit is air-cooled and is operable
whether the chiller is running or not. No additional
cooling source is required.
8
PRGD-SVX01F-EN
Page 9
Figure 2. Components of a Trane EarthWise purge system (front view)
PPuurrggee SSyysstteemm OOvveerrvviieeww
1. Purge tank
2. Condensing unit (includes compressor, condenser coil, and fan)
3. Pressure-relief device (fusible plug)
4. Pump-out solenoid valve
5. Automatic expansion valve
6. Carbon tank
7. Carbon tank temperature sensor
8. Carbon tank heater
9. Exhaust solenoid valve
10. Pump-out compressor
11. Float switch
12. Compressor suction temperature sensor
13. Chiller refrigerant return line
14. Filter-drier canister
PRGD-SVX01F-EN
9
Page 10
PPuurrggee SSyysstteemm OOvveerrvviieeww
Figure 3. Components of a Trane EarthWise purge system (back view)
1. Regeneration solenoid valve
2. Pressure-relief valve
3. Exhaust solenoid valve
4. Pump-out compressor
5. Carbon tank heater
6. Automatic expansion valve
7. Pump-out solenoid valve
8. Pressure-relief device (fusible plug)
9. Carbon tank
10. Purge tank
11. Condensing unit
12. Chiller refrigerant supply line
10
PRGD-SVX01F-EN
Page 11
PPuurrggee SSyysstteemm OOvveerrvviieeww
Purge Tank Subsystem
Any non-condensables that have accumulated from the
refrigerant vapor are left behind to collect in the purge
tank. As the quantity of non-condensables increases,
the heat transfer efficiency of the purge evaporator coil
is reduced, causing the purge compressor suction
temperature to decrease.
A float switch, mounted in the bottom of the purge
tank, indicates if there is excessive accumulation of
liquid refrigerant in the tank. A liquid level sensor,
which resides in the purge control panel, monitors the
status of the float switch.
If the normally closed float switch is open for more
than 20 minutes, the purge controls will turn off the
refrigeration system and generate a non-latching
diagnostic—Purge Liquid Level Too High Warning. If
the float switch has re-closed after 20 minutes, the
purge controls will restart the refrigeration system.
If the float switch remains open for more than
20 minutes, or if the float switch/liquid level restart
cycle has occurred more than four times in four hours,
a latching diagnostic—Purge Liquid Level Too High
Continuously—will be generated. The purge system
will not restart until it is reset.
If a Purge Liquid Level Too High Continuously
diagnostic occurs, check the purge lines for any type of
restriction (trapped liquid, closed valves, etc.) and
ensure that the filter-drier on the liquid return line is in
good condition.
A UL-required pressure-relief device (fusible plug),
which protects against over-pressurization of the purge
tank, is mounted on the purge tank. The plug material
will fuse at 210°F (98.9°C), which equates to
approximately 98 psig (675.7 kPaG) for refrigerant R-
123.
Pump-out Subsystem
When the purge control subsystem detects the
presence of non-condensables in the purge tank, the
pump-out solenoid and exhaust solenoid valves open,
and the pump-out compressor turns on. The valves and
the compressor cycle on and off as needed to achieve
an efficient and fast removal of non-condensables.
NNoottee:: A High Vacuum Pump option is available for
applications that require purge operation at low
condensing temperatures and pressures. This
option provides a two-stage pump-out
compressor. The High Vacuum Pump option
allows the purge system to operate to saturation
temperatures as low as 34°F (1.1°C). Typical
applications that may require the High Vacuum
Pump option include free-cooling installations,
series chiller installations, ice systems having
brine flowing through idle chillers, chillers
installed outdoors or in unconditioned spaces, or
any application that may cause very low
condenser water temperatures.
Carbon Tank and Regeneration
Subsystem
The discharge from the pump-out compressor is piped
through the carbon tank. The special carbon in the tank
effectively scrubs and collects refrigerant molecules
from the non-condensable gas before the gas passes
through the exhaust solenoid valve to the chiller vent
line.
A 175 W resistive heater is mounted inside the carbon
tank and is used to periodically “regenerate” the
carbon bed and drive any collected refrigerant vapor
back into the chiller. A UL-required pressure-relief
valve, rated at 150 psig (1034.2 kPaG), is mounted on
the line leaving the carbon tank. The valve protects
against over-pressurization of the carbon tank.
A temperature sensor is installed through the top of the
carbon tank shell so that the controls can monitor the
carbon bed temperature. The temperature sensor
controls the regeneration cycle and protect against
overheating. If the limit temperature is reached, the
system shuts down and a Purge Carbon Regen
Temperature Limit Exceeded diagnostic is generated.
Tracer AdaptiView Control Subsystem
Tracer UC800 controller
Control of the EarthWise™ purge system is provided
by the Tracer® UC800 controller. The controller is
mounted in the chiller control panel and is used to
interface with the purge system as well as the chiller.
Tracer AdaptiView display
The operator interface for control of the chiller,
including the purge system, is the Tracer®
AdaptiView™ display. For detailed information on the
display, refer to Operations Guide: Tracer AdaptiViewDisplay for Water-Cooled CenTraVac Chillers (CTVSVU01*-EN).
Much of the purge setup, operation, and
troubleshooting can be accomplished using the
Tracer® AdaptiView™ display. However, more
advanced functions require the use of the laptop-based
Tracer® TU service tool. For more information, refer to
Getting Started Guide: Tracer TU Service Tool (TTUSVN01*-EN).
Sensors
The following sensors are used to enable control
communication between the Tracer® UC800 controller
and the EarthWise™ purge system. The sensors use
low-level intelligence devices (LLIDs) to communicate
with the Tracer® UC800 controller.
•CCoommpprreessssoorr ssuuccttiioonn tteemmppeerraattuurree sseennssoorr.. This
sensor is mounted on the purge condensing unit
suction line. The controller uses the value of this
temperature sensor to decide whether or not to
purge non-condensables from the purge tank.
When the temperature drops to a specified point,
PRGD-SVX01F-EN
11
Page 12
PPuurrggee SSyysstteemm OOvveerrvviieeww
the controller activates the pump-out cycle to
remove the accumulated non-condensables from
the purge tank. When enough non-condensables
have been removed and the purge compressor
suction temperature increases in response, the
controller terminates the pump-out cycle.
•SSaattuurraatteedd ccoonnddeennsseerr tteemmppeerraattuurree sseennssoorr.. This
sensor is mounted on the chiller. If the chiller is
running, the controller uses the value of this
temperature sensor to adjust the purge pump-out
initiate/terminate setpoints. It may be used to
prohibit pump-out if system conditions are too cool.
•SSaattuurraatteedd eevvaappoorraattoorr tteemmppeerraattuurree sseennssoorr.. This
sensor is mounted on the chiller. If the chiller is off,
the controller uses the value of this temperature
sensor to adjust the purge pump-out initiate/
terminate setpoints. It may be used to prohibit
pump-out if system conditions are too cool.
•CCaarrbboonn ttaannkk tteemmppeerraattuurree sseennssoorr.. This sensor is
mounted in the carbon tank of the purge system. It
provides feedback to the carbon regeneration
algorithm. The sensor and the controller function
much the same as a thermostat to control the
carbon tank heater.
•LLiiqquuiidd lleevveell sseennssoorr.. This sensor resides in the
purge control panel. It monitors the status of the
normally closed float switch, which is mounted in
the bottom of the purge tank. If an adequate
amount of liquid fails to drain from the purge tank,
the float switch and sensor detect the condition and
prevent further purge operation.
•CCoonnddeennssiinngg uunniitt LLLLIIDD.. This LLID resides in the
purge control panel. It uses a high-capacity relay to
control the operation of the purge condensing unit.
•QQuuaadd rreellaayy LLLLIIDD.. This LLID resides in the purge
control panel. It has four relay outputs that are used
to control the pump-out compressor, the carbon
tank heater, the regeneration solenoid valve, and an
alarm output.
•DDuuaall ttrriiaacc LLLLIIDD.. This LLID resides in the purge
control panel. It has two triac-type outputs that are
used to control the pump-out solenoid valve and
the exhaust solenoid valve. The purge system
draws its control power from the power supplies of
the chiller control panel.
12
PRGD-SVX01F-EN
Page 13
Sequence of Operations
A Tracer® UC800 controller that is configured to
control a purge system uses the operational sequences
described in this section.
Purge Operating Modes
Purge operating mode options are as follows:
•SSttoopp.. The purge condensing unit does not run in
this mode.
•OOnn.. The purge condensing unit runs continuously
in this mode, regardless of the chiller’s operational
status.
•AAuuttoo.. The purge condensing unit runs in this mode
if the main compressor of the chiller is operating.
•AAddaappttiivvee.. The purge condensing unit operation
depends on past purge activity.
Adaptive Mode
The objectives of operating the unit in the Adaptive
mode are to:
•Enable purge system operation.
•Enable the refrigeration circuit to effectively
accumulate non-condensables whether or not the
chiller is running.
•Provide information to an operator regarding
whether leakage is on the high-pressure or lowpressure side of the chiller.
•Decrease energy usage by running the purge
refrigeration circuit only when needed to remove
non-condensables, rather than running it
continuously.
The Adaptive mode requires historical operating data
so that the controller can make optimal decisions
regarding how to run the purge refrigeration circuit in
the future. On initial start-up of a chiller that is in
Adaptive mode, the purge refrigeration circuit runs
continuously for 168 hours (7 days). The chiller
compressor may or may not be running during this
period.
Following the initial data collection period, the
Adaptive mode customizes the purge refrigeration
circuit operation during two distinct chiller operating
conditions:
•Chiller compressor On
•Chiller compressor Off
Adaptive Mode Process—Chiller
Compressor On
The following figure illustrates the process described in
this subsection.
When the chiller compressor starts, the purge
refrigeration circuit starts. The purge refrigeration
circuit continues to run until 60 consecutive minutes of
running occur without any pump-out of noncondensables. The Pumpout Time is the greater of the
following two values that the controller has been
tracking:
•The pump-out time with the chiller On, over the last
24 hours
•The average daily pump-out time with the chiller
On, over the last 7 days
PRGD-SVX01F-EN
13
Page 14
SSeeqquueennccee ooff OOppeerraattiioonnss
Figure 4. Adaptive chiller ON flow chart
The purge then shuts down for a corresponding period
of time, as shown in the following table:
Pumpout Time with chiller
On (over the last 24 hours
or daily average over the
last 7 days, whichever is
greater)
Pumpout Time ≤ 1 minute
1 minute < Pumpout Time ≤ 3
minutes
3 minutes < Pumpout Time ≤ 5
minutes
5 minutes < Pumpout Time ≤ 8
minutes
Pumpout Time > 8 minutesNo Off cycle
14
Purge Off cycle duration
4 hours
3 hours
2 hours
1 hour
During the purge refrigeration circuit Off cycle, the time
remaining is displayed as Time Until Next Purge Run in
the Log Sheet that you can view from the Tracer®
AdaptiView™ display (refer to “Log Sheet,” p. 23).
If the compressor is turned Off during the purge
refrigeration circuit Off cycle, the purge transfers to
Adaptive Mode Procedure—Chiller Compressor Off.
Figure 5, p. 15 illustrates this process.
Adaptive Mode Procedure—Chiller
Compressor Off
Refer to the following figure for an illustration of the
process described in this subsection.
PRGD-SVX01F-EN
Page 15
SSeeqquueennccee ooff OOppeerraattiioonnss
If the chiller compressor is turned Off, the purge
refrigeration circuit Off cycle is determined by the
purge control. The purge Off-cycle duration is
determined by the pump-out time, which is the greater
of the following two values:
•Daily Pumpout—24 hours (the pump-out time over
the last 24 hours whether the chiller is On or Off)
Figure 5. Adaptive chiller OFF flow chart
•Average Daily Pumpout—7 days (the pump-out
time with the chiller On over the last 7 days)
NNoottee:: These two values can be seen on the Tracer
AdaptiView™display.
®
The purge will be shut down for a corresponding
period of time, as shown in the following table:
PRGD-SVX01F-EN
Pumpout Time with chiller On or Off
(over the last 24 hours or daily average
over the last 7 days, whichever is
greater)
Pumpout Time ≤ 1 minute3 days
1 minute < Pumpout Time ≤ 3 minutes2 days
3 minutes < Pumpout Time ≤ 5 minutes1 day
Pumpout Time > 5 minutes
Purge Off
cycle
duration
6 hours
15
Page 16
SSeeqquueennccee ooff OOppeerraattiioonnss
During the purge refrigeration circuit Off cycle, the time
remaining is displayed as the Time Until Next Purge
Run in the purge report of the Tracer® AdaptiView™
display.
If the controls determine it is necessary to run the
purge while the chiller compressor is Off, the purge will
be started and run until 60 consecutive minutes have
passed without any pump-out of non-condensables.
If the chiller compressor starts before the purge Off
cycle has elapsed, the purge starts and transfers to
Adaptive Mode Procedure—Chiller Compressor On.
Figure 4, p. 14, illustrates this process.
Figure 6. Purge refrigeration circuit showing temperatures at various locations in operating cycle
At typical operating temperatures of 70°F (21.1°C)
ambient and 100°F (37.8°C) condensing, the purge
refrigeration cycle should have the temperatures
shown in the following figure for Locations 1–5.
NNoottee:: To troubleshoot the system by taking these
temperatures, refer to “Taking Surface
Temperature Measurements,” p. 30.
Temperatures at numbered locations:
1. After expansion device: -16°F (-26.7°C)
2. Compressor suction line temperature: greater than 60°F (15.5°C) when few non-condensables are present
The purge condensing-unit compressor suction
temperature (Location 2 in the preceding figure) varies
16
with the amount of non-condensables collected in the
purge tank. If the amount of non-condensables
PRGD-SVX01F-EN
Page 17
SSeeqquueennccee ooff OOppeerraattiioonnss
collected in the purge tank limits the available
condensing surface in the tank, the condensing-unit
compressor suction temperature begins to fall.
The purge controller initiates a pump-out cycle when
the suction temperature reaches the pump-out initiate
value that is calculated within the purge control. During
the pump-out cycle, the small pump-out compressor
pulls any non-condensables from the purge tank and
discharges them through the carbon tank. As the non-
Figure 7. Purge operating limits
condensables are removed from the purge tank, the
condensing-unit compressor suction temperature
increases. The purge controller monitors the
compressor suction temperature and cycles or stops
the pump-out, depending on the temperature that is
present.
The 1/4 hp air-cooled condensing unit of the
refrigeration system operates effectively when it is in
the operating range shown in the following figure.
Air Removal
If no air is in the purge tank, the refrigerant returning to
the purge condensing unit compressor suction has a
high superheat (heat added past the point of
evaporation), because of the heat removed from the
condensing chiller refrigerant vapor in the purge tank.
As air accumulates in the purge tank, it displaces the
chiller refrigerant vapor and decreases the amount of
coil surface that is exposed to the vapor. Less heat is
removed from the vapor, and the available superheat
at the purge condensing unit compressor suction
consequently falls. When the purge refrigerant
compressor suction temperature falls far enough to
reach the pump-out initiate value, the purge control
activates the solenoids and the pump-out compressor
to remove the accumulated air. The following figure
illustrates this process.
As air is removed from the purge tank, the inside coil is
once again exposed to chiller refrigerant vapor. As
more chiller refrigerant vapor condenses on the coil,
more heat is removed from the vapor, and the purge
refrigerant compressor suction temperature rises. The
purge control cycles or stops the pump-out process in
response to the compressor suction temperature.
PRGD-SVX01F-EN
17
Page 18
SSeeqquueennccee ooff OOppeerraattiioonnss
Figure 8. Air removal cycle
Pump-out Operating Sequence
As the purge control system detects the presence of
non-condensables in the purge tank, it initiates a
pump-out cycle. The pump-out solenoid valve, the
exhaust solenoid valve, and the pump-out compressor
cycle On and Off as needed to remove the noncondensables.
Non-condensable Pump-out Algorithm
The controller uses the non-condensable pump-out
algorithm to determine when to initiate, control, and
terminate a pump-out cycle to remove air from the
purge tank. The purge refrigerant compressor suction
temperature sensor serves as the feedback to this
control algorithm. The compressor suction
temperature pump-out initiate and pump-out terminate
values are calculated by the purge control and are a
function of the purge liquid temperature.
The refrigerant used in the purge refrigeration circuit,
R-404A, is metered into the purge tank coil by a
constant-pressure regulating expansion valve. The
valve automatically controls the purge suction pressure
at a constant value of 34 psia (234.4 kPaA). Therefore,
18
refrigerant is metered into the coil as a two-phase
refrigerant mixture at a constant saturation
temperature of approximately -16°F (-8.9°C).
The cold coil creates a low vapor pressure near its
outside surface, which draws refrigerant from the
chiller condenser into the purge tank and to the coil
surface. When the refrigerant gets close enough to the
coil surface, it condenses into a liquid. Since liquid
refrigerant requires less volume than it does in a
gaseous form, additional refrigerant enters the purge
tank to fill the void and, in turn, condenses. This
mechanism is known as a thermal siphon.
As the chiller refrigerant condenses, heat is transferred
into the purge coil through the latent heat of
condensation. The compressor suction temperature
sensor monitors this heat transfer.
Air and other gases carried with the chiller refrigerant
vapor do not condense on the coil. Instead, they
accumulate in the purge tank, effectively acting to
insulate and inhibit the flow of refrigerant to the cold
coil surface. The thermal siphon rate is reduced and,
consequently, so is the amount of heat transfer. A
corresponding reduction occurs in the temperature of
PRGD-SVX01F-EN
Page 19
SSeeqquueennccee ooff OOppeerraattiioonnss
the purge refrigerant exiting the coil. The compressor
suction temperature sensor monitors this temperature.
When sufficient non-condensables have accumulated
in the purge tank to decrease the compressor suction
temperature below the pump-out initiate value, a
pump-out cycle begins. The cycle is terminated when
the compressor suction temperature sensor increases
above the pump-out terminate value. The calculations
for the pump-out values are:
Pump-out initiate:
•(°F) = Purge liquid temperature (°F) – 50°F or 0°F
(whichever is higher)
•(°C) = Purge liquid temperature (°C) – 10.0°C or
-17.8°C (whichever is higher)
Pump-out terminate:
•(°F) = Purge liquid temperature (°F) – 40°F or 5°F
(whichever is higher)
•(°C) = Purge liquid temperature (°C) – 4.4°C or -
15.0°C (whichever is higher)
For factory installed purges or those retrofit purges that
communicate with the chiller control system, the purge
liquid temperature value comes from the chiller’s
saturated condenser temperature sensor when the
chiller is running, or the chiller’s saturated evaporator
temperature sensor when the chiller is off.
For a field installed retrofit purge that does not
communicate with the chiller control system, a purge
liquid temperature sensor is mounted on the purge
liquid drain line and the resulting temperature from
this sensor is used in the above equations.
Non-condensable Pump-out cycle
A non-condensable pump-out cycle may be initiated as
described below only if the following two conditions
are met:
•a carbon regeneration cycle is NOT in process, and
•the refrigeration circuit is on.
If at any time, except as described above, the purge
refrigerant compressor suction temperature drops
below the pump-out initiate value, the following
sequence is initiated by the controls.
The controller starts the pump-out compressor and
opens the exhaust solenoid valve. After 5 seconds, the
pump-out solenoid valve opens and pulses at a rate of
20 seconds On and 20 seconds Off. If after two cycles,
the purge refrigerant compressor suction temperature
has not exceeded the pump-out terminate value, the
pump-out solenoid valve stays continuously open. If
the pump-out compressor runs for more than
10 consecutive minutes, the controller recalculates the
pump-out initiate and pump-out terminate values as
described.
The purge controls continue to operate the pump-out
solenoid valve and calculate values as described above
until the purge refrigerant compressor suction
temperature rises above the pump-out terminate value.
At this point, the controller will close the pump-out
solenoid valve and turn off the pump-out compressor
and exhaust solenoid valve.
Typical pump-out cycles are shown in the following
figures.
NNoottee:: For purge systems equipped with standard
pump-out compressors, operation at low chiller
condenser saturation temperatures may result in
a system vacuum greater than the pump-out
compressor can overcome. If the chiller
experiences low condensing temperatures, then
®
the Tracer
programmed to inhibit the operation of the
purge pump-out compressor.
UC800 controller can be
PRGD-SVX01F-EN
19
Page 20
SSeeqquueennccee ooff OOppeerraattiioonnss
Figure 9. Non-condensable pump-out cycle, large quantity of air
Figure 10. Non-condensable pump-out cycle, small quantity of air
Establishing a Daily Pump-out
Limit
The average pump-out time for a CenTraVac™ chiller
purge system is approximately 7 minutes per day for a
one-week period. This value, however, varies widely
depending on chiller size, operating conditions, and
operating schedule.
Carefully monitor the purge pump-out activity for each
chiller for an appropriate period of time (one week or
more) in order to establish a baseline value for a Purge
Daily Pumpout Limit that is appropriate for that specific
installation. Set the Purge Daily Pumpout Limit high
enough to avoid nuisance trips, but low enough to
trigger an alarm diagnostic, should the pump-out rate
suddenly increase. Carefully review
“Troubleshooting,” p. 28 and the chiller purge history
20
PRGD-SVX01F-EN
Page 21
SSeeqquueennccee ooff OOppeerraattiioonnss
before making a decision to shut down the chiller for
leak testing and repair.
Carbon Tank and Regeneration
Subsystem
The function of the carbon tank is to absorb refrigerant
molecules that may be entrained in the discharge of
non-condensables. In order to maintain effectiveness,
the carbon tank periodically regenerates.
Carbon Regeneration Algorithm
The controller uses the carbon regeneration algorithm
to determine when to initiate, control, and terminate a
carbon regeneration cycle. The carbon bed
temperature sensor serves as the feedback to this
algorithm. In addition, the controller uses a pump-out
accumulation timer to indicate the remaining carbon
capacity in the carbon tank. The carbon capacity is the
capacity of the carbon to adsorb refrigerant while
maintaining acceptable levels of refrigerant emission
through the chiller vent line. A capacity of 100 percent
means the carbon bed has the capacity to adsorb
refrigerant and maintain acceptable emission levels. A
capacity of 0 percent means the carbon bed has
inadequate capacity to adsorb refrigerant and still
maintain acceptable emission levels.
The main objectives of the carbon regeneration
algorithm are to:
•Minimize the amount of refrigerant contained in the
carbon by performing a periodic regeneration.
•Regenerate to maintain low emissions levels.
•Minimize the regeneration time.
•Regenerate only when the chiller is at a minimum
level of purging activity.
•Allow regeneration to occur with the chiller On or
Off. Regeneration is preferable when the chiller is
On to ensure low carbon tank pressure, but
regeneration is also acceptable when the chiller is
Off.
The remaining amount of adsorption capacity within
the carbon tank is directly proportional to the number
of purge pump-out minutes that have accumulated,
and is also a function of the chiller refrigerant type. The
purge carbon tank on an R-123-equipped chiller is
considered to be fully saturated after the purge has
accumulated 500 minutes of pump-out time. Because
the relationship between pump-out capacity and
pump-out minutes is directly proportional, it can be
described by the following equation within the
regeneration algorithm:
Remaining carbon capacity% =
100 - (pump-out minutes since last regen/pump-out
minutes at 100% capacity)*100
For example, an R-123-equipped chiller that has
accumulated 80 minutes of purge pump-out time since
the last carbon tank regeneration would be estimated
to have 84 percent carbon tank capacity remaining:
100 – (80/500)*100 = 84%
The purge controls may initiate a carbon tank
regeneration cycle when the remaining carbon tank
capacity is calculated to be less than 80 percent.
However, the continued stable operation of the chiller
is always more important than the regeneration of the
carbon tank. Therefore, the following rules apply:
1. If the Daily Pump-out Limit is disabled, a
regeneration cycle may not be initiated, regardless
of the value of the remaining carbon capacity.
Also, if the Daily Pump-out Limit is disabled during
a regeneration cycle, the regeneration cycle must
be terminated.
2. When the remaining carbon capacity is less than
80 percent, a regeneration cycle will be initiated at
the next opportunity when the chiller is running
(after the chiller has started and no pump-out
minutes have accumulated for the previous
60 minutes).
3. If there is no opportunity to purge as indicated by
Rules 1 and 2 and the remaining carbon capacity is
less than 50 percent, a regeneration cycle will be
initiated at the best opportunity when the chiller is
shut down (and no pump-out minutes have
accumulated for the previous 60 minutes).
4. If there is no opportunity to regenerate as indicated
by Rules 1, 2, and 3 and the carbon capacity drops
below 0 percent, then a regeneration cycle is
initiated.
5. Note that, if at any time during the regeneration
cycle the chiller is running and shuts down or if the
chiller is off and starts up, then the regeneration
cycle is continued.
If the purge controller determine that carbon tank
regeneration is desired and is allowed, the purge
controls:
1. Disable the purge refrigeration circuit and the
pump-out solenoid valve.
PRGD-SVX01F-EN
21
Page 22
SSeeqquueennccee ooff OOppeerraattiioonnss
2. Open the regeneration solenoid valve and turn on
the carbon tank heater.
3. Monitor the carbon temperature until it reaches the
regeneration temperature value of 240°F (115.6°C),
and control within a ±10°F (5.5°C) dead band for
15 minutes (this step should take approximately
3 hours).
If the carbon tank temperature exceeds 120 percent of
the regeneration temperature setpoint, the controller
issues a latching diagnostic, Purge Carbon
Regeneration Temperature Limit Exceeded. The
purpose of this diagnostic is to identify a failed heater
relay or temperature sensor. It disables the purge and
opens the exhaust solenoid valve.
If the carbon tank temperature does not increase more
than 25°F (13.9°C) in the first two hours, the controller
generates a non-latching diagnostic, Carbon
Regeneration Temperature Too Low. The purpose of
this diagnostic is to identify a failed heater or
temperature sensor. It prevents automatic regeneration
from occurring, but a service technician can initiate a
manual regeneration for testing purposes. All other
purge algorithms continue to function.
If the carbon tank temperature does not reach the
minimum regeneration temperature setpoint within
four hours, the controller generates a non-latching
diagnostic, Purge Carbon Regen Temperature Not
Satisfied. The purpose of this diagnostic is to identify a
failing insulation system.
Consult “Carbon Regeneration Temperature Diagnostic
Procedure,” p. 30, if a Carbon Regeneration
Temperature Setpoint Not Satisfied diagnostic or a
Carbon Regeneration Temperature Limit Exceeded
diagnostic is generated.
The complete regeneration cycle can take as long as
seven hours to accomplish but an average chiller does
not have to regenerate very often. A typical
regeneration cycle is depicted in the following figure.
Figure 11. Typical carbon regeneration cycle
22
PRGD-SVX01F-EN
Page 23
Operator Interface
The Tracer® AdaptiView™ display, which is mounted
on the side of the chiller, allows you to monitor chiller
status and make changes to its operation, including the
purge system. Refer to Operations Guide: Tracer
AdaptiView Display for Water-Cooled CenTraVac
Chillers (CTV-SVU01*-EN) for a complete description of
this display.
This section provides more detail about the purgerelated information that you can access through the
display.
Reports
From the Reports screen menu, you can access basic
operating data for the purge system by selecting one of
the following buttons:
•Log Sheet
•ASHRAE Chiller Log
•Purge Operating Modes
Log Sheet
The following status points appear on the Log Sheet:
NNoottee:: The status points also appear on the purge
component screen of the Tracer
display. The purge component screen is
accessible from the purge touch target on the
home screen of the display (refer to CTVSVU01*-EN).
•TTiimmee UUnnttiill NNeexxtt PPuurrggee RRuunn.. Displayed if the purge
is in Adaptive mode and is idle. It indicates the
amount of time left on the adaptive cycle timer.
•DDaaiillyy PPuummppoouutt——2244 HHoouurrss.. Indicates the daily
pumpout time for the last 24 hours (a moving 24hour window). It indicates how the hermetic
integrity of the chiller compares to historic pumpout times for the same chiller. It also allows a check
against factory-recommended values.
•AAvveerraaggee DDaaiillyy PPuummppoouutt——77 DDaayyss.. Indicates the
average daily pump-out time for the last 168 hours
(a moving 168-hour window). It enables a
comparison of present pump-out times to past
averages, and can be another indication of the
hermetic integrity of the chiller.
•DDaaiillyy PPuummppoouutt LLiimmiitt//AAllaarrmm.. Indicates the limit
value that an operator has set in the SSeettttiinnggss
menu. When the daily pumpout rate exceeds this
value, purge operation stops and a diagnostic is
generated.
•CChhiilllleerr OOnn——77 DDaayyss.. Indicates the percentage of
time during the past seven days (floating 168-hour
window) that the chiller was operating. You can use
it to help determine if a leak is present on the high
side or the low side of the chiller.
®
AdaptiView
™
•PPuummppoouutt CChhiilllleerr OOnn——77 DDaayyss.. Indicates the
percentage of the total purge pump-out time during
the past seven days that occurred while the chiller
was operating. You can use it to help determine if a
leak is present on the high side or the low side of
the chiller.
•PPuummppoouutt CChhiilllleerr OOffff——77 DDaayyss.. Indicates the
percentage of the total purge pump-out time during
the past seven days that occurred when the chiller
was not operating. You can use it to help determine
if a leak is present on the high side or the low side
of the chiller.
•PPuummppoouutt——LLiiffee.. Indicates the total purge pump-out
time that has accumulated over the life of the
purge.
•PPuurrggee RRffggtt CCpprrssrr SSuuccttiioonn TTeemmpp.. Indicates the
purge refrigerant compressor suction temperature.
It is useful for diagnosing purge system problems.
•PPuurrggee LLiiqquuiidd TTeemmpp.. Indicates the temperature
sensed by the controller and used to inhibit purge
operation. The purge liquid temperature sensor,
when the chiller is operating, is the chiller saturated
condenser temperature sensor; when the chiller is
Off, it is the chiller saturated evaporator
temperature sensor. If this temperature is below the
Pumpout Inhibit Temperature that is defined in the
SSeettttiinnggss menu, pump-out is not allowed. This
value is used to prevent inefficient operation of the
purge under certain conditions.
•CCaarrbboonn TTaannkk TTeemmpp.. Indicates the carbon bed
temperature and is useful for monitoring
regeneration and for diagnosing regeneration
system problems.
Purge Operating Modes
The Purge Operating Mode screen displays the current
mode and up to six submodes of operation for the
purge system. Only one mode can be active at a time,
while several submodes can be active simultaneously.
For more information on this subject, refer to “Purge
Operating Modes,” p. 13.
Modes
The four available modes of purge operation are:
•SSttoopp
•OOnn
•AAuuttoo
•AAddaappttiivvee
Submodes
You can view submodes from the Purge Settings
screen. The available purge submodes are:
PRGD-SVX01F-EN
23
Page 24
OOppeerraattoorr IInntteerrffaaccee
•RReeffrriiggeerraattiioonn CCiirrccuuiitt OOnn.. Appears if the purge
condensing unit/compressor is operating.
•RReeffrriiggeerraattiioonn CCiirrccuuiitt IIddllee.. Appears if the purge
condensing unit/compressor is not operating.
•PPuummppiinngg OOuutt.. Appears if the purge refrigeration
circuit is On and pump-out has been initiated by the
purge unit controls.
•EExxhhaauusstt CCiirrccuuiitt CChheecckk.. Appears if a pump-out has
been initiated by an operator.
•PPuummppoouutt IInnhhiibbiitteedd.. Appears if the purge
refrigeration circuit is On but pump-out has been
inhibited by a low condenser saturation
temperature.
•DDaaiillyy PPuummppoouutt LLiimmiitt DDiissaabblleedd.. Appears if the
purge refrigeration circuit is On but the daily pumpout limit has been disabled.
•RReeggeenneerraattiinngg.. Appears if the purge carbon system
is in its regeneration mode. Pump-out is not
allowed in this submode.
•AAllaarrmm––CChheecckk DDiiaaggnnoossttiiccss.. Appears if a new
diagnostic occurs.
•PPuurrggee DDiiaagg SShhuuttddoowwnn.. Appears if the purge
system has shut down in response to a latching
diagnostic.
•RReeggeenn DDiissaabblleedd.. Appears if carbon regeneration is
not allowed.
Settings
The Tracer® AdaptiView™ display enables you to
manually select operating modes and setpoints that are
appropriate for a specific chiller application. The
Settings screen menu contains two buttons that
provide access to purge-related settings:
•Purge Settings
•Manual Control Settings
Purge Settings
The following purge settings are available:
•PPuurrggee MMooddee.. Use it to set the purge operating
mode.
•DDaaiillyy PPuummppoouutt LLiimmiitt.. Use it to set the allowable
amount of daily pump-out time. The range is from 1
to 50 minutes; the factory default is 10 minutes.
•DDiissaabbllee DDaaiillyy PPuummppoouutt LLiimmiitt.. Use it to disable
alarms for a specified time that are associated with
exceeding the daily pumpout limit. This is useful
when large amounts of purging are needed
following chiller servicing or operator error. The
range is from 0 to 72 hours, the factory default is
0 hours. Any setting greater than 0 hours will
effectively disable the Daily Pumpout Limit for the
amount of time selected.
•PPuurrggee LLiiqquuiidd TTeemmpp IInnhhiibbiitt.. Use it to enable or
disable the inhibit feature that prevents purge
pump-out if the sensed purge liquid temperature is
less than the pump-out inhibit value.
•PPuurrggee LLiiqquuiidd TTeemmppeerraattuurree LLiimmiitt.. Use it to define
the setpoint for the Purge Liquid Temp Inhibit
feature. If the sensed chiller refrigerant temperature
is below this value, pump-out will not be allowed.
The allowable range is 32°F (0.0°C) to 50°F (10.0°C).
Factory default is 40°F (4.4°C).
Manual Control Settings
The manual control settings that affect purge operation
are as follows:
•PPuurrggee EExxhhaauusstt CCiirrccuuiitt TTeesstt.. On/Off, Auto/On.
Factory default is Off. If set to On, the system
initiates a 30-second non-condensable pumpout
cycle. This setting can be used to check exhaust
circuit components.
•PPuurrggee RReeggeenn CCyyccllee.. On/Off, Auto/On. Factory
default is Off. Use this setting to manually start a
carbon regeneration cycle.
NNoottee:: This setting is also accessible from the purge
component screen of the Tracer
display; refer to Operations Guide: Tracer
AdaptiView Display for Water-Cooled CenTraVac
Chillers (CTV-SVU01*-EN).
®
AdaptiView
™
Alarms
You can view and reset diagnostics from the Alarms
screen of the Tracer® AdaptiView™ display. For more
information about the display, refer to CTV-SVU01*EN. For information about troubleshooting using purge
diagnostics, see “Troubleshooting,” p. 28.
24
PRGD-SVX01F-EN
Page 25
Maintenance
Maintenance requirements for an EarthWise™ purge
system with Tracer® AdaptiView™ control are
described in this section. To ensure efficient and
reliable purge operation, perform all inspections and
procedures at the prescribed intervals. Keep records of
inspection results to establish proper service intervals.
Document changes that occur in purge activity that
could provide information about chiller performance.
Perform the following maintenance procedure on a
weekly basis:
1. With the purge unit operating, check the purge tank
condensing activity by observing the liquid
refrigerant flow in the moisture-indicating sight
glass located in the liquid drain line immediately
after the filter drier canister. A lack of visible
refrigerant flow in the sight glass indicates one of
the following:
a. A pump-out cycle is necessary.
b. A problem exists with the purge heat transfer
circuit (such as the condensing unit, expansion
device, or purge evaporator coil).
c. A problem exists in the purge control
subsystem.
d. Refrigerant vapor from the chiller condenser is
blocked or restricted.
2. Check the moisture-indicator sight glass. Replace
the filter-drier core if moisture is indicated.
NNoottee:: The need for frequent changes of the filter
drier could be an indication of significant
chiller air or tube leaks.
Semi-Annual Maintenance
Perform the following maintenance procedure on a
semi-annual basis:
1. Inspect the air-cooled condenser coil and clean as
needed. Clean the coil from the fan side using
compressed air or coil cleaner. A dirty coil will
reduce purge efficiency and capacity.
2. Inspect the purge tank and carbon tank insulation
for any damage or degradation. Make any needed
repairs to the insulation.
Annual Maintenance
Perform the following maintenance procedure on an
annual basis:
1. Semi-annual maintenance procedures described in
“Semi-Annual Maintenance,” p. 25.
2. Purge system control checks described in
“Troubleshooting,” p. 28.
3. Open the purge control panel and check all internal
components for such problems as corrosion,
terminal tightness, or signs of overheating.
4. Change the filter-drier assembly.
Replacing the Filter-Drier
Assembly
Following are maintenance instructions for filter-drier
assembly replacement; refer to Figure 2, p. 9, for the
location of this component.
1. At the Tracer® AdaptiView™ display, touch the
SSeettttiinnggss button to display the Settings screen.
Touch the PPuurrggee SSeettttiinnggss button to display the
Purge Settings screen. Touch PPuurrggee MMooddee to
display Purge Mode screen. From this screen, set
the mode to Stop.
2. Isolate the purge unit from the chiller. Close the
isolation valves on the purge vapor inlet and the
liquid return lines.
PRGD-SVX01F-EN
25
Page 26
MMaaiinntteennaannccee
3. Drain the filter-drier of liquid refrigerant prior to
opening. Use available pressure differential
whenever possible. Connect a refrigeration hose to
the 1/4-inch Schrader drain fitting located on the
drain line isolator valve and also to a service valve
on the chiller evaporator. Open the chiller valve and
drain the filter-drier.
4. Remove the refrigerant vapor from inside the filterdrier by connecting the suction side of a vacuum
pump to the Schrader drain fitting and the
discharge side to the chiller. Pull a vacuum for
approximately 30 minutes.
NNootteess::
•Due to the slow out-gassing of refrigerant
from the filter-drier, it will not be possible
to pull and hold a deep vacuum.
•The replacement filter-drier absorbs water
vapor from the ambient air, so it is
shipped with sealing caps on each end.
Do not remove these caps until
immediately before installation.
5. Remove the screws connecting the filter-drier to the
purge base. Loosen the nuts at each end of the
Figure 12. Filter-drier assembly
filter-drier and slide it out from the adjacent tubing.
6. Immediately cap the two ends with the caps from
the replacement filter-drier.
7. Dispose of the old filter-drier in accordance with
local regulations.
8. Install the new filter-drier using new O-rings
supplied with the assembly (see the following
figure).
9. Pressurize the purge with dry air or nitrogen to
10 psig (68.9 kPaG) through the Shrader drain
valve. Then check for leaks.
10. Release the pressure, remove hoses, and replace all
valve caps.
11. Set the purge operating mode to “On” and wait for
the purge pump-out compressor to start.
12. Open the isolation valves on the vapor inlet lines
and the liquid return line.
13. After purge pump-out stops, or after several
minutes, return the purge operating mode to Auto
or Adaptive (recommended) using the Tracer®
AdaptiView™ display.
Inspecting the Moisture
Indicator
Monitor the quality of the liquid refrigerant in the
chiller by periodically inspecting the moisture
indicator. The indicator will show “wet” whenever the
chiller moisture exceeds the levels shown in the
following table. Notice that the indicator becomes
more sensitive as the temperature decreases. (The
moisture indicator normally operates at equipment
room ambient temperatures.)
A “wet” indication for more than 72 hours typically
indicates that the filter-drier is saturated and should be
replaced. In some cases in which a substantial amount
of moisture has accumulated, such as when the chiller
has been serviced, several filter-drier assembly
changes may be required before a satisfactory
moisture level is achieved. A reoccurring or persistent
26
“wet” indication is a sign of possible chiller air or water
infiltration.
Inspect the moisture indicator only under the following
conditions:
•The chiller is operating.
•The purge unit is operating and has been allowed
sufficient time to properly remove system moisture
(allow a minimum of 72 hours after replacing filterdrier).
PRGD-SVX01F-EN
Page 27
MMaaiinntteennaannccee
Table 1. R-123 refrigerant moisture content as
determined by moisture indicator
Refrigerant
moisture level
Dry
Caution20–5030–8035–100
WetAbove 50Above 80Above 100
NNoottee:: Refrigerant moisture content given in parts per million (ppm).
75°F
(23.9°C)
Below 20Below 30Below 35
100°F
(37.8°C)
125°F
(51.7°C)
Maintaining the MoistureIndicating Sight Glass
In normal operating conditions, the moisture-indicating
sight glass should not require maintenance beyond
keeping the sight glass clean. However, the sight glass
should be replaced after any major repair to the unit
has taken place, or if it is on a unit in which severe
moisture contamination is known to have occurred.
Be aware that it is normal for the sight glass to indicate
the presence of moisture for a period of least 72 hours
after it is installed and after it has been exposed to
atmosphere. Allow a minimum of 72 hours after sight
glass installation or filter-drier service before using the
sight glass to determine the system moisture content.
Removing Air After Servicing the
Chiller
Air that leaks into a chiller during servicing needs to be
removed so that the chiller can operate normally. The
purge pump-out system, which performs this function,
may operate for a long time to remove the air before
cycling off for the first time. This is due to the large
amount of non-condensables and the relatively small
amount of refrigerant being drawn into the purge tank.
IImmppoorrttaanntt:: Do NOT bypass or remove the pump-out
™
restrictor of the EarthWise
purge system.
Doing so could reduce the efficiency of the
purge system. The purge system has a
faster air exhaust rate than previous purge
systems, which makes bypassing or
removing the restrictor unnecessary.
The Daily Pumpout Limit determines how long the
purge pump-out compressor can operate continuously
without generating a Purge Daily Pumpout Exceeded
diagnostic, which will shut off the purge system. You
can disable the Daily Pumpout Limit to allow the purge
to pump out for an extended period of time.
Disable the Daily Pumpout Limit by using the Tracer®
AdaptiView™ display as follows:
1. Touch the SSeettttiinnggss button to access the SSeettttiinnggss
menu screen.
2. Touch the PPuurrggee SSeettttiinnggss button to access the
PPuurrggee SSeettttiinnggss screen.
3. Touch the PPuurrggee DDiissaabbllee DDaaiillyy PPuummppoouutt LLiimmiitt
button. A screen with the current value and a
keypad appears. Use the keypad to enter a new
value. Any setting greater than 0 hours will
effectively disable the Daily Pumpout Limit for the
amount of time selected. The range of available
settings is from 1 to 72 hours in one-hour
increments. Typically, 24 hours is sufficient. After
the selected time has expired, the Disable Daily
Pumpout Limit automatically de-energizes and
returns the purge system to normal operation.
After the level of non-condensables present in the
chiller falls to a point in which an increasing amount of
refrigerant enters the purge tank, the pump-out
compressor begins to cycle on and off. As the
refrigerant in the system becomes less contaminated
with non-condensables, purge pump-out is activated
less frequently.
NNoottee:: If large amounts of non-condensables are
present in the chiller, the air removal rate can be
enhanced by operating the chiller at part-load
conditions.
PRGD-SVX01F-EN
27
Page 28
Troubleshooting
Use this section to assist you in diagnosing operational
problems with the purge system.
The chiller controller generates diagnostics to alert the
operator to abnormal conditions. There are two kinds
of diagnostics:
•Non-latching diagnostics: Operation continues.
Alarms resolve themselves and the alarm
disappears. They are informational only.
•Latching diagnostics: Operation stops until the
condition is corrected and the diagnostic has been
manually reset from the Tracer® AdaptiView™
display or from the Tracer® TU service tool.
The following table describes the causes of diagnostics
and operating problems that can occur with purge
systems, and suggests solutions to resolving them.
Purge Carbon Tank Temp Sensor
(latching diagnostic)
Purge Liquid Level Too High (nonlatching diagnostic)
Purge Liquid Level Too High
Continuously (latching diagnostic)
Purge Carbon Regen Temp Too
Low (non-latching diagnostic)
Carbon Regeneration Temperature
Setpoint Not Satisfied (nonlatching diagnostic)
CauseSolution
Bad Sensor or LLID.
Bad Sensor or LLID.
Bad Sensor or LLID.
High liquid level in purge tank or
bad level switch. The level switch
was open for at least 20 minutes.
High liquid level in purge tank or
bad level switch. The level switch
was open for more than
20 minutes, or the liquid level/
refrigeration circuit restart cycle
has occurred more than four times
in 4 hours.
The carbon tank temperature did
not increase more than 25°F
(-3.9°C) in the first 2 hours after
energizing the carbon tank heater.
The carbon tank temperature
sensor did not reach the minimum
regeneration temperature setpoint
within 4 hours after energizing the
heater.
The purge refrigerant compressor suction temperature sensor has failed.
The connection has been broken or a short has occurred in the wiring, or
the LLID is not programmed or functioning correctly. Replace or repair as
required.
The purge liquid temp sensor has failed. The connection has been broken
or a short has occurred in the wiring, or the LLID is not programmed or
functioning correctly. Replace as required.
The purge carbon tank temp sensor has failed. The connection has been
broken or a short has occurred in the wiring, or the LLID is not
programmed or functioning correctly. Replace as required.
Check for restrictions in the in the vapor pick-up line and in the liquid
return line. Ensure the vapor line is sloped correctly and has no liquid
traps. Change filter drier if required. Ensure the line shutoff valves are
open.
Check for restrictions in the in the vapor pick-up line and in the liquid
return line. Ensure the vapor line is sloped correctly and has no liquid
traps. Change filter drier if required. Ensure the line shutoff valves are
open.
This diagnostic is intended to identify a failed heater or sensor. Check
carbon tank heater and heater wiring. Check the carbon tank
temperature sensor and its wiring. Check the carbon tank insulation and
the surrounding ambient temperature. Check the purge unit controls and
settings.
This is intended to identify a failing insulation system. Check carbon tank
insulation for integrity. Check ambient conditions. Check heater
operation.
28
PRGD-SVX01F-EN
Page 29
Table 2. Troubleshooting a purge system (continued)
Diagnostic or Problem
Carbon Regeneration Temperature
Limit Exceeded (latching
diagnostic)
Purge unit does not run or pumpout system does not run.
Purge continues to operate when
chiller is Off.
Pump-out compressor operates
continuously.
Purge refrigerant compressor
suction temperature is greater
than the pump-out initiate
setpoint.
Purge fails to pump-out noncondensables. Chiller observations
indicate air is actually present in
the chiller; that is, measured
condenser pressure is greater
than measured condenser
temperature converted to
pressure, and/ or chiller surges at
start-up.
Pump-out compressor operates
continuously.
Purge refrigerant compressor
suction temperature is less than
the pump-out initiate value.
CauseSolution
The carbon tank temperature
exceeded 120% of the
regeneration temperature
setpoint.
The carbon tank temperature did
not decrease more than 25°F
(-3.9°C) in the first hour after the
heater is turned off.
The pump-out time recorded over
the past 24 hours has exceeded
the daily pump-out limit setpoint.
A loss of communication of more
than 30 continuous seconds has
occurred between the controller
and the identified component
(LLID).
Control circuit problem.
Purge is set to On or to Adaptive
operating mode.
Purge refrigerant compressor
suction temperature sensor has
failed.
The control system has failed.Check the controller by using diagnostic tools.
Depending on the chiller type and
the operating conditions, air may
accumulate in the chiller
condenser away from the purge
vapor pick-up location (retrofit
purge).
Pump-out restrictor plugged.
Purge condensing unit is
overcharged or undercharged.
Purge expansion valve has failed.
Pump-out circuit fault.Run diagnostic of purge control circuit. Refer to control circuit test.
Purge condensing unit fan has
failed.
Purge condensing unit condenser
coil is fouled.
Condensing unit compressor
motor winding temperature sensor
opened (line break thermostat).
Pump-out compressor fault—does
not run
Pump-out compressor fault—
pump motor runs
Purge refrigerant compressor
suction temperature sensor
Purge is set to Auto mode and the
chiller run signal has failed.
Excessive air in chiller.
Leakage in purge or purge pumpout tubing.
Failed or restricted solenoid.
Pump-out restrictor plugged.
Gas pick-up connection of the
purge is below the liquid level of
the condenser.
Gas pick-up or return line
restricted.
TTrroouubblleesshhoooottiinngg
Check carbon tank heater relay and heater wiring. Check the carbon tank
temperature sensor and its wiring.
Check the purge unit controls and settings.
Air infiltration rate into chiller may be too high, leak check chiller and
repair leaks. The daily pump-out limit setpoint may be set too low. Check
and adjust to proper value. The chiller refrigerant temperature may be
too low. Do not operate purge at condensing temps of 40°F (4.4°C) or
lower. High vacuum pump-outs may be operated down to 32°F (0.0°C).
Set pump-out inhibit to Enable and set appropriate limit.
Check the LLID and the interconnecting Machine bus. Check the LLID
configuration and function using the Tracer TU service tool.
Run diagnostics of purge control system. Refer to the control circuit test.
Check the purge control for active diagnostics. Check the purge control
system using the Tracer TU service tool.
Check operating mode. The On mode should be used only for specific
service procedures; Adaptive is the normal operating mode.
Check sensor, LLID, and machine bus.
Operate the purge with the chiller Off. Any air in the chiller will be
removed if the purge is functioning correctly. If a large amount of air is
removed, leak test the chiller and repair leaks. Consider using the
Adaptive mode to run the purge as required when the chiller is Off. If
non-condensable removal is required during chiller operation, relocate
the vapor/liquid connections to a more effective location.
Clean out restrictor orifice with compressed air (preferred) or a small
wire.
Refer to the “Determining the Refrigerant Charge Level,” p. 30 to
evaluate the purge charge level.
Refer to the “Determining Proper Expansion Valve Operation,” p. 31 to
evaluate the purge expansion valve performance.
Test and replace fan as needed.
Clean condenser coil as required.
Check condensing fan and coil. Check purge condensing unit charge
level. Check purge condensing unit compressor.
Check purge power supply. Replace line break protector if needed.
Replace compressor if needed.
Low voltage, no voltage, failed pump motor, failed controls.
Failed pump diaphragm, failed pump reed valves, fitting leaks, line
restrictions, high-pressure drop across the pump.
Not installed correctly or the thermal conductive paste has degraded.
Correct orientation of installed sensor and install thermal conductive
paste.
Check the chiller run signal (retrofit purge). Check the controller system.
Trace air source and repair any leak paths. Allow purge to remove
accumulated air.
Check all connections on purge and between the purge tank and the
pump-out compressor. Check all solenoid and other valves for possible
leakage.
Failure of the pump-out solenoid to open, or a failure of the exhaust
solenoid to open. Check for dirt or contamination, failed or misaligned
armature, or an incorrect control command from the controller.
Refer to the installation instructions of a retrofit purge. Check overall unit
operation.
Ensure shut-off valves are fully open and remove any restrictions.
PRGD-SVX01F-EN
29
Page 30
TTrroouubblleesshhoooottiinngg
Table 2. Troubleshooting a purge system (continued)
Diagnostic or Problem
CauseSolution
Restriction in exhaust lines.
Check carbon tank for restriction, check solenoid valves for restriction,
check outlet tubing from the carbon tank to the chiller vent line.
Carbon Regeneration
Temperature Diagnostic
Procedure
If a Carbon Regeneration Temperature Setpoint Not
Satisfied diagnostic is generated, follow this
procedure:
1. Close the regeneration solenoid valve and turn off
the heater.
2. Reset the calculated carbon capacity to 100 percent.
3. Turn the purge refrigeration circuit on and allow the
carbon tank to cool for 4 hours or until the carbon
temperature reaches 100°F (37.8°C), whichever
comes first.
If the carbon tank temperature does not decrease more
than 25°F (13.8°C) in the first hour after this procedure,
the controller initiates a latching diagnostic, Carbon
Regeneration Temperature Limit Exceeded. The
purpose of this diagnostic is to identify a failed heater
relay or temperature sensor. This diagnostic disables
the purge system and opens the exhaust solenoid
valve.
If a Carbon Regeneration Temperature Limit Exceeded
diagnostic is generated, follow this procedure:
1. Open the exhaust solenoid for 5 minutes and then
close it.
2. Run the refrigeration circuit for 15 minutes.
Operating the refrigeration circuit during the carbon
cool-down cycle allows time for any gas that may
have remained in the carbon tank to accumulate in
the purge tank.
3. While the refrigeration circuit is running, enable
pump-outs. If enough gas has accumulated in the
purge tank, a pump-out cycle is activated following
completion of the cool-down cycle.
Purge Refrigeration Circuit
Diagnostic Procedures
You can troubleshoot the refrigeration circuit by taking
surface temperature measurements and using them to
diagnose specific problems, as explained in this
section.
Taking Surface Temperature
Measurements
While the purge condensing unit is running, take
temperature readings with an accurate (±1°F [±0.55°C])
surface-mounted thermocouple-type temperature
probe that has a range of -40°F (-40.0°C) to 200°F (93.3°
C). The locations to be measured are shown in Figure
6, p. 16. The temperatures that you should expect to
find under typical operating conditions are given in the
same figure.
1. To ensure accurate measurements, remove any ice
that may exist on measuring surfaces before
attaching the probe.
2. Fasten the sensor of the probe tightly against the
tubing surface and insulate around the sensor for
accurate results.
3. To measure the temperature at Location 1, move
aside a small portion of the insulation covering the
tubing between the expansion valve and the purge
tank.
4. To read the purge refrigerant compressor suction
temperature, view the purge component screen of
the Tracer® AdaptiView™ display. Then confirm
that reading by measuring the temperature with a
surface-mounted thermocouple at Location 2.
5. To measure the compressor discharge temperature,
mount the probe on the surface at Location 3.
6. To measure the condenser temperature
(Location 4), remove the sheet metal cover from the
side of the condenser and measure the surface
temperature of the second or third from the top
condenser tubing U-bend on the side of the coil
opposite the discharge gas inlet.
7. To measure the liquid line temperature, measure
the tubing between the purge condenser and the
expansion valve (Location 5).
Determining the Refrigerant
Charge Level
To operate correctly, the purge refrigeration system
must have a proper charge level of R-404A. The charge
level should be determined before any other
refrigeration circuit components are evaluated.
1. Take the surface temperature measurements for
Locations 1–5 as described in “Taking Surface
Temperature Measurements,” p. 30.
2. Calculate the difference between Locations 4 and 5.
3. The difference is the sub-cooling value. If the
system is properly charged with R-404A, the subcooling value should be between 8°F (4.4°C) and 15°
F (8.3°C).
a. A sub-cooling of less than 5°F (2.8°C) indicates a
possible refrigerant undercharge and a possible
leak.
b. A sub-cooling value greater than 20°F (11.0°C)
30
PRGD-SVX01F-EN
Page 31
TTrroouubblleesshhoooottiinngg
indicates a refrigerant overcharge.
properly located on the chiller condenser, and are
properly sloped, as described:
Determining Proper Expansion Valve
Operation
The purpose of the expansion valve is to regulate
refrigerant flow so that a constant pressure is
maintained within the purge tank coil. A constant
pressure results in a constant temperature of the
refrigerant that is entering the purge tank.
To determine if the expansion valve is operating
properly, measure the temperature at Location 1, as
described in “Taking Surface Temperature
Measurements,” p. 30. An optimum constant
temperature of -16°F (-26.6°C) is ideal. However, an
acceptable range, to allow for errors or operating
conditions, is between -20°F (-28.9°C) and -10°F (-23.3°
C).
Determining Correct Vapor Pick-up and
Liquid Return Line Connection Locations
To ensure correct purge operation, make sure that the
vapor pick-up and liquid return connections are
•During chiller operation, non-condensables
accumulate in the coolest, calmest spot in the
condenser above the liquid level. On a Trane®
chiller this location is typically just under half-way
up the condenser shell above the condenser sump.
An internal baffle has been installed to enhance this
process during chiller operation. During chiller Off
cycles, non-condensables may rise to higher
elevations within the chiller. However, during purge
system operation, a continuous thermal siphon
develops that effectively draws the noncondensables into the purge tank.
•Vapor pick-up and liquid return lines must be
sloped a minimum of 2 inches per foot off
horizontal or vertical to ensure that no liquid or
vapor traps exist.
Using the Service Functions
Service functions allow you to take manual control to
test the operation of specific functions. Refer to the
following table as you test the functions in this section.
Table 3. Purge component status
Displayed purge status
Refrigerant Circuit On
Refrigerant Circuit Idle
Pumping Out
Regenerating
Exhaust Circuit Check••••oo
Pumpout Inhibited
Daily Pumpout Limit Disabled
Purge Diag Shutdown
Notes:
1. o = Off or de-energized
2. • = On or energized
3. X = Cycling on internal algorithm
Condensing
unit
•ooooo
oooooo
••X•oo
XoooXX
•ooooo
•XXXoo
oooooo
Pump-out
compressor
Pump-out
solenoid
Exhaust
solenoid
Regeneration
solenoid
Carbon tank
heater
Purge Regen Cycle
The Purge Regen Cycle is a manual control setting that
allows you to manually initiate a carbon tank
regeneration cycle.
NNoottee:: This test can be initiated from either the Tracer
AdaptiView™display or the Tracer®TU service
tool.
Run this cycle to:
•Observe the purge condensing unit stopping
•Observe the pumpout solenoid closing (if open)
•Observe the regeneration solenoid opening
•Observe the carbon tank heater energizing
•Verify that regeneration setpoints are achieved
•Verify that timing functions are correct
PRGD-SVX01F-EN
For more information regarding this feature, see
“Carbon Regeneration Temperature Diagnostic
Procedure,” p. 30.
Purge Exhaust Circuit Test
®
The Purge Exhaust Circuit Test is a manual control
setting that you can use to check that the components
activate in the right sequence and at the right time
when commanded to do so by the controls.
NNoottee:: This test can be initiated from either the Tracer
AdaptiView™display or the Tracer®TU service
tool.
This feature, when enabled, overrides the pump-out
algorithm and executes a pump-out sequence,
regardless of the actual purge refrigerant compressor
suction temperature. Once activated, the pump-out
sequence continues for 30 seconds. During this time,
®
31
Page 32
TTrroouubblleesshhoooottiinngg
you can observe and confirm that the pump-out
compressor starts and the exhaust solenoid opens.
After 5 seconds, you should also be able to observe the
pump-out solenoid opening.
Exhaust Circuit Pressure Check
The Exhaust Circuit Pressure Check enables the
servicing technician to check the exhaust circuit
components and lines for leakage by pressurizing the
exhaust circuit.
NNoottee:: This test can be initiated from only the Tracer
TU service tool.
To perform this test, follow this procedure:
1. Install a pressure gauge, isolation valve, pressure
regulator, and a source of dry compressed air or
nitrogen to the line downstream of the exhaust
solenoid valve. When this check is enabled, the
exhaust solenoid opens.
2. Pressurize the exhaust circuit to no more than
10 psi (68.9 kPa) using dry air or nitrogen.
3. After the target pressure is achieved, isolate the
pressure source and monitor the pressure gauge
for decay. A loss of pressure indicates leakage from
the exhaust system.
4. Test the exhaust components and line connections
for leaks by using a soap solution.
5. Relieve the testing pressure from the exhaust circuit
before disabling this test. When the test is disabled
®
the exhaust solenoid valve re-closes.
Exhaust Circuit Vacuum Check
The Exhaust Circuit Vacuum Check enables the
servicing technician to check the exhaust circuit
components and lines for leakage by placing a vacuum
on the exhaust circuit.
NNoottee:: This test can be initiated from only the Tracer
TU service tool.
To perform this test, the servicing technician should
follow this procedure:
1. Install a vacuum gauge, isolation valve, and a
vacuum source to the line downstream of the
exhaust solenoid valve. When this check is enabled,
the exhaust solenoid opens.
2. Turn on the vacuum source and pull the exhaust
circuit to as deep a vacuum as can be achieved.
3. After a vacuum is achieved, isolate the vacuum
source and monitor the vacuum gauge for decay. A
rise in pressure indicates leakage into the exhaust
system.
NNoottee:: Out-gassing of refrigerant from the carbon
tank may give a false indication of a pressure
rise.
4. Relieve the vacuum from the exhaust circuit before
disabling this test. When the test is disabled the
exhaust solenoid valve re-closes.
®
32
PRGD-SVX01F-EN
Page 33
Specifications
An EarthWise™ purge system has the specifications
shown in the following table:
115 Vac, 60 Hz, 1-phase, 10.3 A
Electrical power requirements
Purge compressor motor rated-load ampacity
Total unit ampacity
Minimum circuit ampacity
Carbon tank heater wattage
Alarm relay output rating120 Vac, 1/3 hp, 7.2 FLA
Operating temperature range34°F to 110°F (1.1°C to 43.3°C)
Storage temperature range-40°F to 150°F (-40.0°C to 65.5°C)
Storage and operating humidity range5% to 95% relative humidity, non-condensing
MountingDirect-mounted on condenser shell above the liquid level of highest condenser
Dimensions (approximate)
Weight140 lb (63.5 kg) with filter-drier
Condensing unit refrigerant charge0.60 lb (0.27 kg) of R-404A
110 Vac, 50 Hz, 1-phase, 10.3 A
Voltage range is +10%, -15%
8 RLA
10.3 A
12.3 A
175 W
25-3/4 in. (65.4 cm) high x 27-1/2 in. (69.9 cm) wide x 21-3/4 in. (55.2 cm) deep,
with filter-drier
PRGD-SVX01F-EN
33
Page 34
Schematic Wiring Diagram
EarthWise Purge System with
Tracer AdaptiView Controls
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands — including Club Car
®
Trane
— work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.