Trane PRGD series Installation, Operation And Maintenance Manual

Page 1
Installation, Operation, and Maintenance
PRGD
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
July 2017
X39641072060
SSAAFFEETTYY WWAARRNNIINNGG
PPRRGGDD--SSVVXX0011FF--EENN
Page 2
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess..
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg)).. AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee MMaatteerriiaall SSaaffeettyy DDaattaa SShheeeettss ((MMSSDDSS))//SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE..
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee MMSSDDSS//SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss..
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt.. NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG.. EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE..
©2017 Ingersoll Rand
PRGD-SVX01F-EN
Page 3
IInnttrroodduuccttiioonn
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
•• AAllll IInnggeerrssoollll RRaanndd ppeerrssoonnnneell mmuusstt ffoollllooww IInnggeerrssoollll RRaanndd EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy ((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,, lloocckkoouutt//ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc.. AAllll ppoolliicciieess ccaann bbee ffoouunndd oonn tthhee BBOOSS ssiittee.. WWhheerree llooccaall rreegguullaattiioonnss aarree mmoorree ssttrriinnggeenntt tthhaann tthheessee ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee ppoolliicciieess..
•• NNoonn--IInnggeerrssoollll RRaanndd ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww llooccaall rreegguullaattiioonnss..
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt aaddddiittiivveess..
IImmppoorrttaanntt:: The PRGD purge uses R-404A refrigerant
and is used with chillers using R-123 and OIL00022. Verify proper refrigerant and oil for the PRGD purge and chiller before proceeding!
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Running edits
PRGD-SVX01F-EN
3
Page 4
Table of Contents
EarthWise Purge System Nameplate . . . . . . . 5
EarthWise Purge System Model
Number . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . . . . . . . 6
Purge System Overview . . . . .. . . . . . .. . . . . . . . 7
General Information . . . . . . . . . . . . . . . . . . . . . . 7
Reference Sources. . . . . . . . . . . . . . . . . . . . . . . . 7
How a Purge System Works . . . . . . . . . . . . . . . 7
Refrigeration Circuit Subsystem. . . . . . . . 8
Purge Tank Subsystem . . . . . . . . . . . . . . . 11
Pump-out Subsystem . . . . . . . . . . . . . . . . 11
Carbon Tank and Regeneration
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Tracer AdaptiView Control
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sequence of Operations . . . .. . . . . . . .. . . . . . . 13
Purge Operating Modes . . . . . . . . . . . . . . . . . . 13
Adaptive Mode . . . . . . . . . . . . . . . . . . . . . . 13
Adaptive Mode Process—Chiller
Compressor On . . . . . . . . . . . . . . . . . . . . . . 13
Adaptive Mode Procedure—Chiller
Compressor Off. . . . . . . . . . . . . . . . . . . . . . 14
Typical Purge Refrigeration Circuit
Operating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Pump-out Operating Sequence . . . . . . . . . . . 18
Non-condensable Pump-out
Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Non-condensable Pump-out
cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Establishing a Daily Pump-out Limit. . . . . . . 20
Carbon Tank and Regeneration
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Carbon Regeneration Algorithm. . . . . . . 21
Carbon Tank Regeneration
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Purge Settings . . . . . . . . . . . . . . . . . . . . . . . 24
Manual Control Settings. . . . . . . . . . . . . . 24
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Maintenance . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . 25
Weekly Maintenance. . . . . . . . . . . . . . . . . . . . . 25
Semi-Annual Maintenance . . . . . . . . . . . . . . . 25
Annual Maintenance . . . . . . . . . . . . . . . . . . . . . 25
Replacing the Filter-Drier Assembly . . . . . . . 25
Inspecting the Moisture Indicator . . . . . . . . . 26
Maintaining the Moisture-Indicating
Sight Glass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Removing Air After Servicing the
Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Troubleshooting. . . . . . . . . . . . . .. . . . . . . . . . . . . 28
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Carbon Regeneration Temperature
Diagnostic Procedure . . . . . . . . . . . . . . . . . . . . 30
Purge Refrigeration Circuit Diagnostic
Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Taking Surface Temperature
Measurements. . . . . . . . . . . . . . . . . . . . . . . 30
Determining the Refrigerant Charge
Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Determining Proper Expansion Valve
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Determining Correct Vapor Pick-up and Liquid Return Line Connection
Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Using the Service Functions . . . . . . . . . . 31
Purge Regen Cycle . . . . . . . . . . . . . . . . . . . 31
Purge Exhaust Circuit Test . . . . . . . . . . . . 31
Exhaust Circuit Pressure Check. . . . . . . . 32
Exhaust Circuit Vacuum Check . . . . . . . . 32
Specifications . . .. . . . . . . .. . . . . . .. . . . . . . .. . . 33
Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . 23
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Purge Operating Modes . . . . . . . . . . . . . . 23
Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4
Schematic Wiring Diagram . . . . . .. . . . . . . . . . 34
EarthWise Purge System with Tracer
AdaptiView Controls . . . . . . . . . . . . . . . . . . . . . 34
PRGD-SVX01F-EN
Page 5
EarthWise Purge System Nameplate
Each Trane EarthWise™ purge system is assigned a alphanumeric model number that identifies the operating components and option for that specific unit (see “EarthWise Purge System Model Number,” p. 6
Figure 1. Example of a typical nameplate
for detailed information). The model number is also printed on the unit nameplate. It is important to refer to the model number when ordering parts or requesting technical assistance.
PRGD-SVX01F-EN
5
Page 6
EarthWise Purge System Model Number
Digit 1, 2, 3 — Unit Type
PRG = Purge
Digit 4 — Development Sequence
A = First Generation B = Second Generation C = Third Generation D = Fourth Generation
Digit 5 — Enclosure Type
A = Standard B = NEMA 4 C = NEMA 4 with Hersite Condensing Unit S = Special
Digit 6 — Control Options
0 = Without Power Supply 1 = With Power Supply 2 = Standard Condenser Pressure Cutout 3 = ASME Condenser Pressure Cutout
Digit 7 — Control Interface
0 = Chiller Interface 1 = Purge Interface
Digit 8 — Frequency
1 = 60 Hz 2 = 50 Hz
Digit 9 — Vacuum Pump
A = Standard Vacuum Pump B = High Vacuum Pump C = Industrial Vacuum Pump
Digit 10, 11 — Design Sequence
A0 = Original
Digit 12 — Special Options
0 = None S = Special
6
PRGD-SVX01F-EN
Page 7
Purge System Overview
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt aaddddiittiivveess..
IImmppoorrttaanntt:: The PRGD purge uses R-404A refrigerant
and is used with chillers using R-123 and OIL00022. Verify proper refrigerant and oil for the PRGD purge and chiller before proceeding!
This guide describes the operation and maintenance of a Trane® EarthWise™ purge system with Tracer® AdaptiView™ controls. Tracer® AdaptiView™ controls include the Tracer® UC800 controller and the Tracer® AdaptiView™ display.
General Information
Centrifugal chillers that use low-pressure refrigerants, such as R-123, operate with areas of the chiller at less than atmospheric pressure. Non-condensables in the air, such as water and nitrogen vapor, may leak into these low-pressure areas and accumulate in the condenser. If these non-condensables are not removed, the condenser loses its ability to condense refrigerant efficiently and the pressure of the condenser increases. Increased condenser pressure lowers the chiller’s efficiency and capacity.
A purge system is required on low-pressure centrifugal chillers. It is a device that is externally mounted on the chiller. Its purpose is to remove non-condensable materials that have leaked into the machine.
NNoottee:: For convenience, the term “air” is often used in
describing non-condensables removed by the purge system, although any other non­condensable materials that may exist in the chiller are also removed by the purge system.
Reference Sources
The following reference documents may be helpful resources for EarthWise™ purge system operation and maintenance:
Installation, Operation, and Maintenance Guide:
CDHF and CDHG Water-cooled CenTraVac Chillers with Tracer AdaptiView Control (CDHF-SVX01*-EN)
Installation, Operation, and Maintenance Guide: CVHE, CVHF, CVHG Water-cooled CenTraVac
Chillers with Tracer AdaptiView Control (CVHE-
SVX02*-EN)
Installation, Operation, and Maintenance Guide:
CVHL Water-cooled CenTraVac Chillers with Tracer AdaptiView Control (CVHL-SVX01*-EN)
Installation, Operation, and Maintenance Guide: Series S CVHS Water-cooled CenTraVac Chillers with Tracer AdaptiView Control and AdaptiSpeed Technology (CVHS-SVX01*-EN)
Diagnostics Manual: Diagnostic Descriptions, Troubleshooting Tables, and Control Component Overview for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control (CTV-SVD03*-EN)
Programming Guide: Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer AdaptiView Control (CTV-SVP02*-EN)
Operations Guide: Tracer AdaptiView Display for Water-cooled CenTraVac Chillers (CTV-SVU01*-EN)
Getting Started Guide: Tracer TU Service Tool (TTU-SVN01*-EN)
How a Purge System Works
From a functional standpoint, the purge system can be divided into subsystems of components. This section identifies and describes the function of these subsystems.
The following list identifies these subsystems and their components; the following figures illustrate them:
Refrigeration circuit subsystem
Purge tankPurge evaporator coil (inside purge tank)1/4 hp air-cooled condensing unit (compressor,
fan, condensing coil)
Automatic expansion valveChiller refrigerant supply lineChiller refrigerant return line (includes filter-
drier and moisture-indicating sight glass)
Purge tank subsystem
Purge tankPurge evaporator coil (inside purge tank)Pressure-relief device (fusible plug)Liquid level sensor (float switch)Supply and return lines to the chiller condenser
Pump-out subsystem
Pump-out compressorPump-out solenoid valve
Carbon tank and regeneration subsystem
Carbon tankCarbon tank heaterRegeneration solenoid valve
PRGD-SVX01F-EN
7
Page 8
PPuurrggee SSyysstteemm OOvveerrvviieeww
Exhaust solenoid valvePressure-relief valveTemperature sensor
Purge control subsystem
Tracer® UC800 controllerTracer® AdaptiView™ display
Detailed descriptions of the various purge subsystems are included after the figures.
Refrigeration Circuit Subsystem
The purge evaporator of the refrigeration circuit is located in the purge tank. The purge tank is connected to the chiller condenser by supply and return lines through which chiller refrigerant can freely flow.
The purge evaporator coil presents a cold condensing surface to the chiller refrigerant entering the purge
tank. When the purge refrigeration system is running, refrigerant from the chiller condenser is attracted to the cold surface of the purge evaporator. When the gaseous refrigerant contacts the surface of the purge evaporator coil, it condenses into a liquid, leaving a partial vacuum behind. More refrigerant vapor from the chiller condenser migrates to the purge tank to fill the vacuum.
The liquid refrigerant that has condensed in the purge tank returns to the chiller condenser through the liquid return line. The return line includes a filter-drier and a moisture-indicating sight glass.
The condensing unit is air-cooled and is operable whether the chiller is running or not. No additional cooling source is required.
8
PRGD-SVX01F-EN
Page 9
Figure 2. Components of a Trane EarthWise purge system (front view)
PPuurrggee SSyysstteemm OOvveerrvviieeww
1. Purge tank
2. Condensing unit (includes compressor, condenser coil, and fan)
3. Pressure-relief device (fusible plug)
4. Pump-out solenoid valve
5. Automatic expansion valve
6. Carbon tank
7. Carbon tank temperature sensor
8. Carbon tank heater
9. Exhaust solenoid valve
10. Pump-out compressor
11. Float switch
12. Compressor suction temperature sensor
13. Chiller refrigerant return line
14. Filter-drier canister
PRGD-SVX01F-EN
9
Page 10
PPuurrggee SSyysstteemm OOvveerrvviieeww
Figure 3. Components of a Trane EarthWise purge system (back view)
1. Regeneration solenoid valve
2. Pressure-relief valve
3. Exhaust solenoid valve
4. Pump-out compressor
5. Carbon tank heater
6. Automatic expansion valve
7. Pump-out solenoid valve
8. Pressure-relief device (fusible plug)
9. Carbon tank
10. Purge tank
11. Condensing unit
12. Chiller refrigerant supply line
10
PRGD-SVX01F-EN
Page 11
PPuurrggee SSyysstteemm OOvveerrvviieeww
Purge Tank Subsystem
Any non-condensables that have accumulated from the refrigerant vapor are left behind to collect in the purge tank. As the quantity of non-condensables increases, the heat transfer efficiency of the purge evaporator coil is reduced, causing the purge compressor suction temperature to decrease.
A float switch, mounted in the bottom of the purge tank, indicates if there is excessive accumulation of liquid refrigerant in the tank. A liquid level sensor, which resides in the purge control panel, monitors the status of the float switch.
If the normally closed float switch is open for more than 20 minutes, the purge controls will turn off the refrigeration system and generate a non-latching diagnostic—Purge Liquid Level Too High Warning. If the float switch has re-closed after 20 minutes, the purge controls will restart the refrigeration system.
If the float switch remains open for more than 20 minutes, or if the float switch/liquid level restart cycle has occurred more than four times in four hours, a latching diagnostic—Purge Liquid Level Too High Continuously—will be generated. The purge system will not restart until it is reset.
If a Purge Liquid Level Too High Continuously diagnostic occurs, check the purge lines for any type of restriction (trapped liquid, closed valves, etc.) and ensure that the filter-drier on the liquid return line is in good condition.
A UL-required pressure-relief device (fusible plug), which protects against over-pressurization of the purge tank, is mounted on the purge tank. The plug material will fuse at 210°F (98.9°C), which equates to approximately 98 psig (675.7 kPaG) for refrigerant R-
123.
Pump-out Subsystem
When the purge control subsystem detects the presence of non-condensables in the purge tank, the pump-out solenoid and exhaust solenoid valves open, and the pump-out compressor turns on. The valves and the compressor cycle on and off as needed to achieve an efficient and fast removal of non-condensables.
NNoottee:: A High Vacuum Pump option is available for
applications that require purge operation at low condensing temperatures and pressures. This option provides a two-stage pump-out compressor. The High Vacuum Pump option allows the purge system to operate to saturation temperatures as low as 34°F (1.1°C). Typical applications that may require the High Vacuum Pump option include free-cooling installations, series chiller installations, ice systems having brine flowing through idle chillers, chillers installed outdoors or in unconditioned spaces, or any application that may cause very low condenser water temperatures.
Carbon Tank and Regeneration Subsystem
The discharge from the pump-out compressor is piped through the carbon tank. The special carbon in the tank effectively scrubs and collects refrigerant molecules from the non-condensable gas before the gas passes through the exhaust solenoid valve to the chiller vent line.
A 175 W resistive heater is mounted inside the carbon tank and is used to periodically “regenerate” the carbon bed and drive any collected refrigerant vapor back into the chiller. A UL-required pressure-relief valve, rated at 150 psig (1034.2 kPaG), is mounted on the line leaving the carbon tank. The valve protects against over-pressurization of the carbon tank.
A temperature sensor is installed through the top of the carbon tank shell so that the controls can monitor the carbon bed temperature. The temperature sensor controls the regeneration cycle and protect against overheating. If the limit temperature is reached, the system shuts down and a Purge Carbon Regen Temperature Limit Exceeded diagnostic is generated.
Tracer AdaptiView Control Subsystem
Tracer UC800 controller
Control of the EarthWise™ purge system is provided by the Tracer® UC800 controller. The controller is mounted in the chiller control panel and is used to interface with the purge system as well as the chiller.
Tracer AdaptiView display
The operator interface for control of the chiller, including the purge system, is the Tracer® AdaptiView™ display. For detailed information on the display, refer to Operations Guide: Tracer AdaptiView Display for Water-Cooled CenTraVac Chillers (CTV­SVU01*-EN).
Much of the purge setup, operation, and troubleshooting can be accomplished using the Tracer® AdaptiView™ display. However, more advanced functions require the use of the laptop-based Tracer® TU service tool. For more information, refer to Getting Started Guide: Tracer TU Service Tool (TTU­SVN01*-EN).
Sensors
The following sensors are used to enable control communication between the Tracer® UC800 controller and the EarthWise™ purge system. The sensors use low-level intelligence devices (LLIDs) to communicate with the Tracer® UC800 controller.
CCoommpprreessssoorr ssuuccttiioonn tteemmppeerraattuurree sseennssoorr.. This sensor is mounted on the purge condensing unit suction line. The controller uses the value of this temperature sensor to decide whether or not to purge non-condensables from the purge tank. When the temperature drops to a specified point,
PRGD-SVX01F-EN
11
Page 12
PPuurrggee SSyysstteemm OOvveerrvviieeww
the controller activates the pump-out cycle to remove the accumulated non-condensables from the purge tank. When enough non-condensables have been removed and the purge compressor suction temperature increases in response, the controller terminates the pump-out cycle.
SSaattuurraatteedd ccoonnddeennsseerr tteemmppeerraattuurree sseennssoorr.. This sensor is mounted on the chiller. If the chiller is running, the controller uses the value of this temperature sensor to adjust the purge pump-out initiate/terminate setpoints. It may be used to prohibit pump-out if system conditions are too cool.
SSaattuurraatteedd eevvaappoorraattoorr tteemmppeerraattuurree sseennssoorr.. This sensor is mounted on the chiller. If the chiller is off, the controller uses the value of this temperature sensor to adjust the purge pump-out initiate/ terminate setpoints. It may be used to prohibit pump-out if system conditions are too cool.
CCaarrbboonn ttaannkk tteemmppeerraattuurree sseennssoorr.. This sensor is mounted in the carbon tank of the purge system. It provides feedback to the carbon regeneration algorithm. The sensor and the controller function much the same as a thermostat to control the carbon tank heater.
LLiiqquuiidd lleevveell sseennssoorr.. This sensor resides in the purge control panel. It monitors the status of the normally closed float switch, which is mounted in the bottom of the purge tank. If an adequate amount of liquid fails to drain from the purge tank, the float switch and sensor detect the condition and prevent further purge operation.
CCoonnddeennssiinngg uunniitt LLLLIIDD.. This LLID resides in the purge control panel. It uses a high-capacity relay to control the operation of the purge condensing unit.
QQuuaadd rreellaayy LLLLIIDD.. This LLID resides in the purge control panel. It has four relay outputs that are used to control the pump-out compressor, the carbon tank heater, the regeneration solenoid valve, and an alarm output.
DDuuaall ttrriiaacc LLLLIIDD.. This LLID resides in the purge control panel. It has two triac-type outputs that are used to control the pump-out solenoid valve and the exhaust solenoid valve. The purge system draws its control power from the power supplies of the chiller control panel.
12
PRGD-SVX01F-EN
Page 13
Sequence of Operations
A Tracer® UC800 controller that is configured to control a purge system uses the operational sequences described in this section.
Purge Operating Modes
Purge operating mode options are as follows:
SSttoopp.. The purge condensing unit does not run in this mode.
OOnn.. The purge condensing unit runs continuously in this mode, regardless of the chiller’s operational status.
AAuuttoo.. The purge condensing unit runs in this mode if the main compressor of the chiller is operating.
AAddaappttiivvee.. The purge condensing unit operation depends on past purge activity.
Adaptive Mode
The objectives of operating the unit in the Adaptive mode are to:
Enable purge system operation.
Enable the refrigeration circuit to effectively accumulate non-condensables whether or not the chiller is running.
Provide information to an operator regarding whether leakage is on the high-pressure or low­pressure side of the chiller.
Decrease energy usage by running the purge refrigeration circuit only when needed to remove non-condensables, rather than running it continuously.
The Adaptive mode requires historical operating data so that the controller can make optimal decisions regarding how to run the purge refrigeration circuit in the future. On initial start-up of a chiller that is in Adaptive mode, the purge refrigeration circuit runs continuously for 168 hours (7 days). The chiller compressor may or may not be running during this period.
Following the initial data collection period, the Adaptive mode customizes the purge refrigeration circuit operation during two distinct chiller operating conditions:
Chiller compressor On
Chiller compressor Off
Adaptive Mode Process—Chiller Compressor On
The following figure illustrates the process described in this subsection.
When the chiller compressor starts, the purge refrigeration circuit starts. The purge refrigeration circuit continues to run until 60 consecutive minutes of running occur without any pump-out of non­condensables. The Pumpout Time is the greater of the following two values that the controller has been tracking:
The pump-out time with the chiller On, over the last 24 hours
The average daily pump-out time with the chiller On, over the last 7 days
PRGD-SVX01F-EN
13
Page 14
SSeeqquueennccee ooff OOppeerraattiioonnss
Figure 4. Adaptive chiller ON flow chart
The purge then shuts down for a corresponding period of time, as shown in the following table:
Pumpout Time with chiller On (over the last 24 hours or daily average over the last 7 days, whichever is greater)
Pumpout Time ≤ 1 minute
1 minute < Pumpout Time ≤ 3 minutes
3 minutes < Pumpout Time ≤ 5 minutes
5 minutes < Pumpout Time ≤ 8 minutes
Pumpout Time > 8 minutes No Off cycle
14
Purge Off cycle duration
4 hours
3 hours
2 hours
1 hour
During the purge refrigeration circuit Off cycle, the time remaining is displayed as Time Until Next Purge Run in the Log Sheet that you can view from the Tracer® AdaptiView™ display (refer to “Log Sheet,” p. 23).
If the compressor is turned Off during the purge refrigeration circuit Off cycle, the purge transfers to Adaptive Mode Procedure—Chiller Compressor Off.
Figure 5, p. 15 illustrates this process.
Adaptive Mode Procedure—Chiller Compressor Off
Refer to the following figure for an illustration of the process described in this subsection.
PRGD-SVX01F-EN
Page 15
SSeeqquueennccee ooff OOppeerraattiioonnss
If the chiller compressor is turned Off, the purge refrigeration circuit Off cycle is determined by the purge control. The purge Off-cycle duration is determined by the pump-out time, which is the greater of the following two values:
Daily Pumpout—24 hours (the pump-out time over the last 24 hours whether the chiller is On or Off)
Figure 5. Adaptive chiller OFF flow chart
Average Daily Pumpout—7 days (the pump-out time with the chiller On over the last 7 days)
NNoottee:: These two values can be seen on the Tracer
AdaptiView™display.
®
The purge will be shut down for a corresponding period of time, as shown in the following table:
PRGD-SVX01F-EN
Pumpout Time with chiller On or Off (over the last 24 hours or daily average over the last 7 days, whichever is greater)
Pumpout Time ≤ 1 minute 3 days
1 minute < Pumpout Time ≤ 3 minutes 2 days
3 minutes < Pumpout Time ≤ 5 minutes 1 day
Pumpout Time > 5 minutes
Purge Off cycle duration
6 hours
15
Page 16
SSeeqquueennccee ooff OOppeerraattiioonnss
During the purge refrigeration circuit Off cycle, the time remaining is displayed as the Time Until Next Purge Run in the purge report of the Tracer® AdaptiView™ display.
If the controls determine it is necessary to run the purge while the chiller compressor is Off, the purge will be started and run until 60 consecutive minutes have passed without any pump-out of non-condensables.
If the chiller compressor starts before the purge Off cycle has elapsed, the purge starts and transfers to Adaptive Mode Procedure—Chiller Compressor On.
Figure 4, p. 14, illustrates this process.
Figure 6. Purge refrigeration circuit showing temperatures at various locations in operating cycle
Typical Purge Refrigeration Circuit Operating Cycle
At typical operating temperatures of 70°F (21.1°C) ambient and 100°F (37.8°C) condensing, the purge refrigeration cycle should have the temperatures shown in the following figure for Locations 1–5.
NNoottee:: To troubleshoot the system by taking these
temperatures, refer to “Taking Surface
Temperature Measurements,” p. 30.
Temperatures at numbered locations:
1. After expansion device: -16°F (-26.7°C)
2. Compressor suction line temperature: greater than 60°F (15.5°C) when few non-condensables are present
3. Compressor discharge temperature: 150°F (65.5°C)
4. Condensing temperature: 85°F (29.4°C)
5. Liquid line temperature: 75°F (23.9°C)
The purge condensing-unit compressor suction temperature (Location 2 in the preceding figure) varies
16
with the amount of non-condensables collected in the purge tank. If the amount of non-condensables
PRGD-SVX01F-EN
Page 17
SSeeqquueennccee ooff OOppeerraattiioonnss
collected in the purge tank limits the available condensing surface in the tank, the condensing-unit compressor suction temperature begins to fall.
The purge controller initiates a pump-out cycle when the suction temperature reaches the pump-out initiate value that is calculated within the purge control. During the pump-out cycle, the small pump-out compressor pulls any non-condensables from the purge tank and discharges them through the carbon tank. As the non-
Figure 7. Purge operating limits
condensables are removed from the purge tank, the condensing-unit compressor suction temperature increases. The purge controller monitors the compressor suction temperature and cycles or stops the pump-out, depending on the temperature that is present.
The 1/4 hp air-cooled condensing unit of the refrigeration system operates effectively when it is in the operating range shown in the following figure.
Air Removal
If no air is in the purge tank, the refrigerant returning to the purge condensing unit compressor suction has a high superheat (heat added past the point of evaporation), because of the heat removed from the condensing chiller refrigerant vapor in the purge tank. As air accumulates in the purge tank, it displaces the chiller refrigerant vapor and decreases the amount of coil surface that is exposed to the vapor. Less heat is removed from the vapor, and the available superheat at the purge condensing unit compressor suction consequently falls. When the purge refrigerant
compressor suction temperature falls far enough to reach the pump-out initiate value, the purge control activates the solenoids and the pump-out compressor to remove the accumulated air. The following figure illustrates this process.
As air is removed from the purge tank, the inside coil is once again exposed to chiller refrigerant vapor. As more chiller refrigerant vapor condenses on the coil, more heat is removed from the vapor, and the purge refrigerant compressor suction temperature rises. The purge control cycles or stops the pump-out process in response to the compressor suction temperature.
PRGD-SVX01F-EN
17
Page 18
SSeeqquueennccee ooff OOppeerraattiioonnss
Figure 8. Air removal cycle
Pump-out Operating Sequence
As the purge control system detects the presence of non-condensables in the purge tank, it initiates a pump-out cycle. The pump-out solenoid valve, the exhaust solenoid valve, and the pump-out compressor cycle On and Off as needed to remove the non­condensables.
Non-condensable Pump-out Algorithm
The controller uses the non-condensable pump-out algorithm to determine when to initiate, control, and terminate a pump-out cycle to remove air from the purge tank. The purge refrigerant compressor suction temperature sensor serves as the feedback to this control algorithm. The compressor suction temperature pump-out initiate and pump-out terminate values are calculated by the purge control and are a function of the purge liquid temperature.
The refrigerant used in the purge refrigeration circuit, R-404A, is metered into the purge tank coil by a constant-pressure regulating expansion valve. The valve automatically controls the purge suction pressure at a constant value of 34 psia (234.4 kPaA). Therefore,
18
refrigerant is metered into the coil as a two-phase refrigerant mixture at a constant saturation temperature of approximately -16°F (-8.9°C).
The cold coil creates a low vapor pressure near its outside surface, which draws refrigerant from the chiller condenser into the purge tank and to the coil surface. When the refrigerant gets close enough to the coil surface, it condenses into a liquid. Since liquid refrigerant requires less volume than it does in a gaseous form, additional refrigerant enters the purge tank to fill the void and, in turn, condenses. This mechanism is known as a thermal siphon.
As the chiller refrigerant condenses, heat is transferred into the purge coil through the latent heat of condensation. The compressor suction temperature sensor monitors this heat transfer.
Air and other gases carried with the chiller refrigerant vapor do not condense on the coil. Instead, they accumulate in the purge tank, effectively acting to insulate and inhibit the flow of refrigerant to the cold coil surface. The thermal siphon rate is reduced and, consequently, so is the amount of heat transfer. A corresponding reduction occurs in the temperature of
PRGD-SVX01F-EN
Page 19
SSeeqquueennccee ooff OOppeerraattiioonnss
the purge refrigerant exiting the coil. The compressor suction temperature sensor monitors this temperature.
When sufficient non-condensables have accumulated in the purge tank to decrease the compressor suction temperature below the pump-out initiate value, a pump-out cycle begins. The cycle is terminated when the compressor suction temperature sensor increases above the pump-out terminate value. The calculations for the pump-out values are:
Pump-out initiate:
(°F) = Purge liquid temperature (°F) – 50°F or 0°F (whichever is higher)
(°C) = Purge liquid temperature (°C) – 10.0°C or
-17.8°C (whichever is higher)
Pump-out terminate:
(°F) = Purge liquid temperature (°F) – 40°F or 5°F (whichever is higher)
(°C) = Purge liquid temperature (°C) – 4.4°C or -
15.0°C (whichever is higher)
For factory installed purges or those retrofit purges that communicate with the chiller control system, the purge liquid temperature value comes from the chiller’s saturated condenser temperature sensor when the chiller is running, or the chiller’s saturated evaporator temperature sensor when the chiller is off.
For a field installed retrofit purge that does not communicate with the chiller control system, a purge liquid temperature sensor is mounted on the purge liquid drain line and the resulting temperature from this sensor is used in the above equations.
Non-condensable Pump-out cycle
A non-condensable pump-out cycle may be initiated as described below only if the following two conditions are met:
a carbon regeneration cycle is NOT in process, and
the refrigeration circuit is on.
If at any time, except as described above, the purge refrigerant compressor suction temperature drops below the pump-out initiate value, the following sequence is initiated by the controls.
The controller starts the pump-out compressor and opens the exhaust solenoid valve. After 5 seconds, the pump-out solenoid valve opens and pulses at a rate of 20 seconds On and 20 seconds Off. If after two cycles, the purge refrigerant compressor suction temperature has not exceeded the pump-out terminate value, the pump-out solenoid valve stays continuously open. If the pump-out compressor runs for more than 10 consecutive minutes, the controller recalculates the pump-out initiate and pump-out terminate values as described.
The purge controls continue to operate the pump-out solenoid valve and calculate values as described above until the purge refrigerant compressor suction temperature rises above the pump-out terminate value. At this point, the controller will close the pump-out solenoid valve and turn off the pump-out compressor and exhaust solenoid valve.
Typical pump-out cycles are shown in the following figures.
NNoottee:: For purge systems equipped with standard
pump-out compressors, operation at low chiller condenser saturation temperatures may result in a system vacuum greater than the pump-out compressor can overcome. If the chiller experiences low condensing temperatures, then
®
the Tracer programmed to inhibit the operation of the purge pump-out compressor.
UC800 controller can be
PRGD-SVX01F-EN
19
Page 20
SSeeqquueennccee ooff OOppeerraattiioonnss
Figure 9. Non-condensable pump-out cycle, large quantity of air
Figure 10. Non-condensable pump-out cycle, small quantity of air
Establishing a Daily Pump-out Limit
The average pump-out time for a CenTraVac™ chiller purge system is approximately 7 minutes per day for a one-week period. This value, however, varies widely depending on chiller size, operating conditions, and operating schedule.
Carefully monitor the purge pump-out activity for each chiller for an appropriate period of time (one week or more) in order to establish a baseline value for a Purge Daily Pumpout Limit that is appropriate for that specific installation. Set the Purge Daily Pumpout Limit high enough to avoid nuisance trips, but low enough to trigger an alarm diagnostic, should the pump-out rate suddenly increase. Carefully review
“Troubleshooting,” p. 28 and the chiller purge history
20
PRGD-SVX01F-EN
Page 21
SSeeqquueennccee ooff OOppeerraattiioonnss
before making a decision to shut down the chiller for leak testing and repair.
Carbon Tank and Regeneration Subsystem
The function of the carbon tank is to absorb refrigerant molecules that may be entrained in the discharge of non-condensables. In order to maintain effectiveness, the carbon tank periodically regenerates.
Carbon Regeneration Algorithm
The controller uses the carbon regeneration algorithm to determine when to initiate, control, and terminate a carbon regeneration cycle. The carbon bed temperature sensor serves as the feedback to this algorithm. In addition, the controller uses a pump-out accumulation timer to indicate the remaining carbon capacity in the carbon tank. The carbon capacity is the capacity of the carbon to adsorb refrigerant while maintaining acceptable levels of refrigerant emission through the chiller vent line. A capacity of 100 percent means the carbon bed has the capacity to adsorb refrigerant and maintain acceptable emission levels. A capacity of 0 percent means the carbon bed has inadequate capacity to adsorb refrigerant and still maintain acceptable emission levels.
The main objectives of the carbon regeneration algorithm are to:
Minimize the amount of refrigerant contained in the carbon by performing a periodic regeneration.
Regenerate to maintain low emissions levels.
Minimize the regeneration time.
Regenerate only when the chiller is at a minimum level of purging activity.
Allow regeneration to occur with the chiller On or Off. Regeneration is preferable when the chiller is On to ensure low carbon tank pressure, but regeneration is also acceptable when the chiller is Off.
The remaining amount of adsorption capacity within the carbon tank is directly proportional to the number of purge pump-out minutes that have accumulated, and is also a function of the chiller refrigerant type. The purge carbon tank on an R-123-equipped chiller is considered to be fully saturated after the purge has accumulated 500 minutes of pump-out time. Because the relationship between pump-out capacity and pump-out minutes is directly proportional, it can be described by the following equation within the regeneration algorithm:
Remaining carbon capacity% =
100 - (pump-out minutes since last regen/pump-out minutes at 100% capacity)*100
For example, an R-123-equipped chiller that has accumulated 80 minutes of purge pump-out time since the last carbon tank regeneration would be estimated to have 84 percent carbon tank capacity remaining:
100 – (80/500)*100 = 84%
The purge controls may initiate a carbon tank regeneration cycle when the remaining carbon tank capacity is calculated to be less than 80 percent. However, the continued stable operation of the chiller is always more important than the regeneration of the carbon tank. Therefore, the following rules apply:
1. If the Daily Pump-out Limit is disabled, a regeneration cycle may not be initiated, regardless of the value of the remaining carbon capacity.
Also, if the Daily Pump-out Limit is disabled during a regeneration cycle, the regeneration cycle must be terminated.
2. When the remaining carbon capacity is less than 80 percent, a regeneration cycle will be initiated at the next opportunity when the chiller is running (after the chiller has started and no pump-out minutes have accumulated for the previous 60 minutes).
3. If there is no opportunity to purge as indicated by Rules 1 and 2 and the remaining carbon capacity is less than 50 percent, a regeneration cycle will be initiated at the best opportunity when the chiller is shut down (and no pump-out minutes have accumulated for the previous 60 minutes).
4. If there is no opportunity to regenerate as indicated by Rules 1, 2, and 3 and the carbon capacity drops below 0 percent, then a regeneration cycle is initiated.
5. Note that, if at any time during the regeneration cycle the chiller is running and shuts down or if the chiller is off and starts up, then the regeneration cycle is continued.
Carbon Tank Regeneration Sequence
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
If the purge controller determine that carbon tank regeneration is desired and is allowed, the purge controls:
1. Disable the purge refrigeration circuit and the pump-out solenoid valve.
PRGD-SVX01F-EN
21
Page 22
SSeeqquueennccee ooff OOppeerraattiioonnss
2. Open the regeneration solenoid valve and turn on the carbon tank heater.
3. Monitor the carbon temperature until it reaches the regeneration temperature value of 240°F (115.6°C), and control within a ±10°F (5.5°C) dead band for 15 minutes (this step should take approximately 3 hours).
If the carbon tank temperature exceeds 120 percent of the regeneration temperature setpoint, the controller issues a latching diagnostic, Purge Carbon Regeneration Temperature Limit Exceeded. The purpose of this diagnostic is to identify a failed heater relay or temperature sensor. It disables the purge and opens the exhaust solenoid valve.
If the carbon tank temperature does not increase more than 25°F (13.9°C) in the first two hours, the controller generates a non-latching diagnostic, Carbon Regeneration Temperature Too Low. The purpose of this diagnostic is to identify a failed heater or temperature sensor. It prevents automatic regeneration from occurring, but a service technician can initiate a manual regeneration for testing purposes. All other purge algorithms continue to function.
If the carbon tank temperature does not reach the minimum regeneration temperature setpoint within four hours, the controller generates a non-latching diagnostic, Purge Carbon Regen Temperature Not Satisfied. The purpose of this diagnostic is to identify a failing insulation system.
Consult “Carbon Regeneration Temperature Diagnostic
Procedure,” p. 30, if a Carbon Regeneration
Temperature Setpoint Not Satisfied diagnostic or a Carbon Regeneration Temperature Limit Exceeded diagnostic is generated.
The complete regeneration cycle can take as long as seven hours to accomplish but an average chiller does not have to regenerate very often. A typical regeneration cycle is depicted in the following figure.
Figure 11. Typical carbon regeneration cycle
22
PRGD-SVX01F-EN
Page 23
Operator Interface
The Tracer® AdaptiView™ display, which is mounted on the side of the chiller, allows you to monitor chiller status and make changes to its operation, including the purge system. Refer to Operations Guide: Tracer
AdaptiView Display for Water-Cooled CenTraVac Chillers (CTV-SVU01*-EN) for a complete description of
this display.
This section provides more detail about the purge­related information that you can access through the display.
Reports
From the Reports screen menu, you can access basic operating data for the purge system by selecting one of the following buttons:
Log Sheet
ASHRAE Chiller Log
Purge Operating Modes
Log Sheet
The following status points appear on the Log Sheet:
NNoottee:: The status points also appear on the purge
component screen of the Tracer display. The purge component screen is accessible from the purge touch target on the home screen of the display (refer to CTV­SVU01*-EN).
TTiimmee UUnnttiill NNeexxtt PPuurrggee RRuunn.. Displayed if the purge is in Adaptive mode and is idle. It indicates the amount of time left on the adaptive cycle timer.
DDaaiillyy PPuummppoouutt——2244 HHoouurrss.. Indicates the daily pumpout time for the last 24 hours (a moving 24­hour window). It indicates how the hermetic integrity of the chiller compares to historic pump­out times for the same chiller. It also allows a check against factory-recommended values.
AAvveerraaggee DDaaiillyy PPuummppoouutt——77 DDaayyss.. Indicates the average daily pump-out time for the last 168 hours (a moving 168-hour window). It enables a comparison of present pump-out times to past averages, and can be another indication of the hermetic integrity of the chiller.
DDaaiillyy PPuummppoouutt LLiimmiitt//AAllaarrmm.. Indicates the limit value that an operator has set in the SSeettttiinnggss menu. When the daily pumpout rate exceeds this value, purge operation stops and a diagnostic is generated.
CChhiilllleerr OOnn——77 DDaayyss.. Indicates the percentage of time during the past seven days (floating 168-hour window) that the chiller was operating. You can use it to help determine if a leak is present on the high side or the low side of the chiller.
®
AdaptiView
PPuummppoouutt CChhiilllleerr OOnn——77 DDaayyss.. Indicates the percentage of the total purge pump-out time during the past seven days that occurred while the chiller was operating. You can use it to help determine if a leak is present on the high side or the low side of the chiller.
PPuummppoouutt CChhiilllleerr OOffff——77 DDaayyss.. Indicates the percentage of the total purge pump-out time during the past seven days that occurred when the chiller was not operating. You can use it to help determine if a leak is present on the high side or the low side of the chiller.
PPuummppoouutt——LLiiffee.. Indicates the total purge pump-out time that has accumulated over the life of the purge.
PPuurrggee RRffggtt CCpprrssrr SSuuccttiioonn TTeemmpp.. Indicates the purge refrigerant compressor suction temperature. It is useful for diagnosing purge system problems.
PPuurrggee LLiiqquuiidd TTeemmpp.. Indicates the temperature sensed by the controller and used to inhibit purge operation. The purge liquid temperature sensor, when the chiller is operating, is the chiller saturated condenser temperature sensor; when the chiller is Off, it is the chiller saturated evaporator temperature sensor. If this temperature is below the Pumpout Inhibit Temperature that is defined in the SSeettttiinnggss menu, pump-out is not allowed. This value is used to prevent inefficient operation of the purge under certain conditions.
CCaarrbboonn TTaannkk TTeemmpp.. Indicates the carbon bed temperature and is useful for monitoring regeneration and for diagnosing regeneration system problems.
Purge Operating Modes
The Purge Operating Mode screen displays the current mode and up to six submodes of operation for the purge system. Only one mode can be active at a time, while several submodes can be active simultaneously. For more information on this subject, refer to “Purge
Operating Modes,” p. 13.
Modes
The four available modes of purge operation are:
SSttoopp
OOnn
AAuuttoo
AAddaappttiivvee
Submodes
You can view submodes from the Purge Settings screen. The available purge submodes are:
PRGD-SVX01F-EN
23
Page 24
OOppeerraattoorr IInntteerrffaaccee
RReeffrriiggeerraattiioonn CCiirrccuuiitt OOnn.. Appears if the purge condensing unit/compressor is operating.
RReeffrriiggeerraattiioonn CCiirrccuuiitt IIddllee.. Appears if the purge condensing unit/compressor is not operating.
PPuummppiinngg OOuutt.. Appears if the purge refrigeration circuit is On and pump-out has been initiated by the purge unit controls.
EExxhhaauusstt CCiirrccuuiitt CChheecckk.. Appears if a pump-out has been initiated by an operator.
PPuummppoouutt IInnhhiibbiitteedd.. Appears if the purge refrigeration circuit is On but pump-out has been inhibited by a low condenser saturation temperature.
DDaaiillyy PPuummppoouutt LLiimmiitt DDiissaabblleedd.. Appears if the purge refrigeration circuit is On but the daily pump­out limit has been disabled.
RReeggeenneerraattiinngg.. Appears if the purge carbon system is in its regeneration mode. Pump-out is not allowed in this submode.
AAllaarrmm––CChheecckk DDiiaaggnnoossttiiccss.. Appears if a new diagnostic occurs.
PPuurrggee DDiiaagg SShhuuttddoowwnn.. Appears if the purge system has shut down in response to a latching diagnostic.
RReeggeenn DDiissaabblleedd.. Appears if carbon regeneration is not allowed.
Settings
The Tracer® AdaptiView™ display enables you to manually select operating modes and setpoints that are appropriate for a specific chiller application. The Settings screen menu contains two buttons that provide access to purge-related settings:
Purge Settings
Manual Control Settings
Purge Settings
The following purge settings are available:
PPuurrggee MMooddee.. Use it to set the purge operating mode.
DDaaiillyy PPuummppoouutt LLiimmiitt.. Use it to set the allowable amount of daily pump-out time. The range is from 1 to 50 minutes; the factory default is 10 minutes.
DDiissaabbllee DDaaiillyy PPuummppoouutt LLiimmiitt.. Use it to disable alarms for a specified time that are associated with exceeding the daily pumpout limit. This is useful when large amounts of purging are needed following chiller servicing or operator error. The range is from 0 to 72 hours, the factory default is 0 hours. Any setting greater than 0 hours will effectively disable the Daily Pumpout Limit for the amount of time selected.
PPuurrggee LLiiqquuiidd TTeemmpp IInnhhiibbiitt.. Use it to enable or disable the inhibit feature that prevents purge pump-out if the sensed purge liquid temperature is less than the pump-out inhibit value.
PPuurrggee LLiiqquuiidd TTeemmppeerraattuurree LLiimmiitt.. Use it to define the setpoint for the Purge Liquid Temp Inhibit feature. If the sensed chiller refrigerant temperature is below this value, pump-out will not be allowed. The allowable range is 32°F (0.0°C) to 50°F (10.0°C). Factory default is 40°F (4.4°C).
Manual Control Settings
The manual control settings that affect purge operation are as follows:
PPuurrggee EExxhhaauusstt CCiirrccuuiitt TTeesstt.. On/Off, Auto/On. Factory default is Off. If set to On, the system initiates a 30-second non-condensable pumpout cycle. This setting can be used to check exhaust circuit components.
PPuurrggee RReeggeenn CCyyccllee.. On/Off, Auto/On. Factory default is Off. Use this setting to manually start a carbon regeneration cycle.
NNoottee:: This setting is also accessible from the purge
component screen of the Tracer display; refer to Operations Guide: Tracer
AdaptiView Display for Water-Cooled CenTraVac Chillers (CTV-SVU01*-EN).
®
AdaptiView
Alarms
You can view and reset diagnostics from the Alarms screen of the Tracer® AdaptiView™ display. For more information about the display, refer to CTV-SVU01*­EN. For information about troubleshooting using purge diagnostics, see “Troubleshooting,” p. 28.
24
PRGD-SVX01F-EN
Page 25
Maintenance
Maintenance requirements for an EarthWise™ purge system with Tracer® AdaptiView™ control are described in this section. To ensure efficient and reliable purge operation, perform all inspections and procedures at the prescribed intervals. Keep records of inspection results to establish proper service intervals. Document changes that occur in purge activity that could provide information about chiller performance.
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt aaddddiittiivveess..
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
WWAARRNNIINNGG
HHoott SSuurrffaaccee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn sseevveerree bbuurrnnss.. SSuurrffaaccee tteemmppeerraattuurreess mmaayy eexxcceeeedd 330000°°FF ((115500°°CC)).. TToo aavvooiidd ppoossssiibbllee sskkiinn bbuurrnnss,, ssttaayy cclleeaarr ooff tthheessee ssuurrffaacceess.. IIff ppoossssiibbllee,, aallllooww ssuurrffaacceess ttoo ccooooll bbeeffoorree sseerrvviicciinngg.. IIff sseerrvviicciinngg iiss nneecceessssaarryy wwhhiillee ssuurrffaaccee tteemmppeerraattuurreess aarree ssttiillll eelleevvaatteedd,, yyoouu MMUUSSTT ppuutt oonn aallll PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE))..
Weekly Maintenance
Perform the following maintenance procedure on a weekly basis:
1. With the purge unit operating, check the purge tank condensing activity by observing the liquid refrigerant flow in the moisture-indicating sight glass located in the liquid drain line immediately after the filter drier canister. A lack of visible refrigerant flow in the sight glass indicates one of the following:
a. A pump-out cycle is necessary.
b. A problem exists with the purge heat transfer
circuit (such as the condensing unit, expansion device, or purge evaporator coil).
c. A problem exists in the purge control
subsystem.
d. Refrigerant vapor from the chiller condenser is
blocked or restricted.
2. Check the moisture-indicator sight glass. Replace the filter-drier core if moisture is indicated.
NNoottee:: The need for frequent changes of the filter
drier could be an indication of significant chiller air or tube leaks.
Semi-Annual Maintenance
Perform the following maintenance procedure on a semi-annual basis:
1. Inspect the air-cooled condenser coil and clean as needed. Clean the coil from the fan side using compressed air or coil cleaner. A dirty coil will reduce purge efficiency and capacity.
2. Inspect the purge tank and carbon tank insulation for any damage or degradation. Make any needed repairs to the insulation.
Annual Maintenance
Perform the following maintenance procedure on an annual basis:
1. Semi-annual maintenance procedures described in
“Semi-Annual Maintenance,” p. 25.
2. Purge system control checks described in
“Troubleshooting,” p. 28.
3. Open the purge control panel and check all internal components for such problems as corrosion, terminal tightness, or signs of overheating.
4. Change the filter-drier assembly.
Replacing the Filter-Drier Assembly
Following are maintenance instructions for filter-drier assembly replacement; refer to Figure 2, p. 9, for the location of this component.
1. At the Tracer® AdaptiView™ display, touch the SSeettttiinnggss button to display the Settings screen. Touch the PPuurrggee SSeettttiinnggss button to display the Purge Settings screen. Touch PPuurrggee MMooddee to display Purge Mode screen. From this screen, set the mode to Stop.
2. Isolate the purge unit from the chiller. Close the isolation valves on the purge vapor inlet and the liquid return lines.
PRGD-SVX01F-EN
25
Page 26
MMaaiinntteennaannccee
3. Drain the filter-drier of liquid refrigerant prior to opening. Use available pressure differential whenever possible. Connect a refrigeration hose to the 1/4-inch Schrader drain fitting located on the drain line isolator valve and also to a service valve on the chiller evaporator. Open the chiller valve and drain the filter-drier.
4. Remove the refrigerant vapor from inside the filter­drier by connecting the suction side of a vacuum pump to the Schrader drain fitting and the discharge side to the chiller. Pull a vacuum for approximately 30 minutes.
NNootteess::
Due to the slow out-gassing of refrigerant from the filter-drier, it will not be possible to pull and hold a deep vacuum.
The replacement filter-drier absorbs water vapor from the ambient air, so it is shipped with sealing caps on each end. Do not remove these caps until immediately before installation.
5. Remove the screws connecting the filter-drier to the purge base. Loosen the nuts at each end of the
Figure 12. Filter-drier assembly
filter-drier and slide it out from the adjacent tubing.
6. Immediately cap the two ends with the caps from the replacement filter-drier.
7. Dispose of the old filter-drier in accordance with local regulations.
8. Install the new filter-drier using new O-rings supplied with the assembly (see the following figure).
9. Pressurize the purge with dry air or nitrogen to 10 psig (68.9 kPaG) through the Shrader drain valve. Then check for leaks.
10. Release the pressure, remove hoses, and replace all valve caps.
11. Set the purge operating mode to “On” and wait for the purge pump-out compressor to start.
12. Open the isolation valves on the vapor inlet lines and the liquid return line.
13. After purge pump-out stops, or after several minutes, return the purge operating mode to Auto or Adaptive (recommended) using the Tracer® AdaptiView™ display.
Inspecting the Moisture Indicator
Monitor the quality of the liquid refrigerant in the chiller by periodically inspecting the moisture indicator. The indicator will show “wet” whenever the chiller moisture exceeds the levels shown in the following table. Notice that the indicator becomes more sensitive as the temperature decreases. (The moisture indicator normally operates at equipment room ambient temperatures.)
A “wet” indication for more than 72 hours typically indicates that the filter-drier is saturated and should be replaced. In some cases in which a substantial amount of moisture has accumulated, such as when the chiller has been serviced, several filter-drier assembly changes may be required before a satisfactory moisture level is achieved. A reoccurring or persistent
26
“wet” indication is a sign of possible chiller air or water infiltration.
Inspect the moisture indicator only under the following conditions:
The chiller is operating.
The purge unit is operating and has been allowed sufficient time to properly remove system moisture (allow a minimum of 72 hours after replacing filter­drier).
PRGD-SVX01F-EN
Page 27
MMaaiinntteennaannccee
Table 1. R-123 refrigerant moisture content as
determined by moisture indicator
Refrigerant moisture level
Dry
Caution 20–50 30–80 35–100
Wet Above 50 Above 80 Above 100
NNoottee:: Refrigerant moisture content given in parts per million (ppm).
75°F
(23.9°C)
Below 20 Below 30 Below 35
100°F
(37.8°C)
125°F
(51.7°C)
Maintaining the Moisture­Indicating Sight Glass
In normal operating conditions, the moisture-indicating sight glass should not require maintenance beyond keeping the sight glass clean. However, the sight glass should be replaced after any major repair to the unit has taken place, or if it is on a unit in which severe moisture contamination is known to have occurred.
Be aware that it is normal for the sight glass to indicate the presence of moisture for a period of least 72 hours after it is installed and after it has been exposed to atmosphere. Allow a minimum of 72 hours after sight glass installation or filter-drier service before using the sight glass to determine the system moisture content.
Removing Air After Servicing the Chiller
Air that leaks into a chiller during servicing needs to be removed so that the chiller can operate normally. The purge pump-out system, which performs this function, may operate for a long time to remove the air before cycling off for the first time. This is due to the large amount of non-condensables and the relatively small amount of refrigerant being drawn into the purge tank.
IImmppoorrttaanntt:: Do NOT bypass or remove the pump-out
restrictor of the EarthWise
purge system. Doing so could reduce the efficiency of the purge system. The purge system has a faster air exhaust rate than previous purge systems, which makes bypassing or removing the restrictor unnecessary.
The Daily Pumpout Limit determines how long the purge pump-out compressor can operate continuously without generating a Purge Daily Pumpout Exceeded diagnostic, which will shut off the purge system. You can disable the Daily Pumpout Limit to allow the purge to pump out for an extended period of time.
Disable the Daily Pumpout Limit by using the Tracer® AdaptiView™ display as follows:
1. Touch the SSeettttiinnggss button to access the SSeettttiinnggss menu screen.
2. Touch the PPuurrggee SSeettttiinnggss button to access the PPuurrggee SSeettttiinnggss screen.
3. Touch the PPuurrggee DDiissaabbllee DDaaiillyy PPuummppoouutt LLiimmiitt button. A screen with the current value and a keypad appears. Use the keypad to enter a new value. Any setting greater than 0 hours will effectively disable the Daily Pumpout Limit for the amount of time selected. The range of available settings is from 1 to 72 hours in one-hour increments. Typically, 24 hours is sufficient. After the selected time has expired, the Disable Daily Pumpout Limit automatically de-energizes and returns the purge system to normal operation.
After the level of non-condensables present in the chiller falls to a point in which an increasing amount of refrigerant enters the purge tank, the pump-out compressor begins to cycle on and off. As the refrigerant in the system becomes less contaminated with non-condensables, purge pump-out is activated less frequently.
NNoottee:: If large amounts of non-condensables are
present in the chiller, the air removal rate can be enhanced by operating the chiller at part-load conditions.
PRGD-SVX01F-EN
27
Page 28
Troubleshooting
Use this section to assist you in diagnosing operational problems with the purge system.
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt aaddddiittiivveess..
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
WWAARRNNIINNGG
HHoott SSuurrffaaccee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn sseevveerree bbuurrnnss.. SSuurrffaaccee tteemmppeerraattuurreess mmaayy eexxcceeeedd 330000°°FF ((115500°°CC)).. TToo aavvooiidd ppoossssiibbllee sskkiinn bbuurrnnss,, ssttaayy cclleeaarr ooff tthheessee ssuurrffaacceess.. IIff ppoossssiibbllee,, aallllooww ssuurrffaacceess ttoo ccooooll bbeeffoorree sseerrvviicciinngg.. IIff sseerrvviicciinngg iiss nneecceessssaarryy wwhhiillee ssuurrffaaccee tteemmppeerraattuurreess aarree ssttiillll eelleevvaatteedd,, yyoouu MMUUSSTT ppuutt oonn aallll PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE))..
Diagnostics
The chiller controller generates diagnostics to alert the operator to abnormal conditions. There are two kinds of diagnostics:
Non-latching diagnostics: Operation continues. Alarms resolve themselves and the alarm disappears. They are informational only.
Latching diagnostics: Operation stops until the condition is corrected and the diagnostic has been manually reset from the Tracer® AdaptiView™ display or from the Tracer® TU service tool.
The following table describes the causes of diagnostics and operating problems that can occur with purge systems, and suggests solutions to resolving them.
Table 2. Troubleshooting a purge system
Diagnostic or Problem
Purge Cprsr Suction Temp Sensor (latching diagnostic)
Purge Liquid Temp Sensor (latching diagnostic)
Purge Carbon Tank Temp Sensor (latching diagnostic)
Purge Liquid Level Too High (non­latching diagnostic)
Purge Liquid Level Too High Continuously (latching diagnostic)
Purge Carbon Regen Temp Too Low (non-latching diagnostic)
Carbon Regeneration Temperature Setpoint Not Satisfied (non­latching diagnostic)
Cause Solution
Bad Sensor or LLID.
Bad Sensor or LLID.
Bad Sensor or LLID.
High liquid level in purge tank or bad level switch. The level switch was open for at least 20 minutes.
High liquid level in purge tank or bad level switch. The level switch was open for more than 20 minutes, or the liquid level/ refrigeration circuit restart cycle has occurred more than four times in 4 hours.
The carbon tank temperature did not increase more than 25°F (-3.9°C) in the first 2 hours after energizing the carbon tank heater.
The carbon tank temperature sensor did not reach the minimum regeneration temperature setpoint within 4 hours after energizing the heater.
The purge refrigerant compressor suction temperature sensor has failed. The connection has been broken or a short has occurred in the wiring, or the LLID is not programmed or functioning correctly. Replace or repair as required. The purge liquid temp sensor has failed. The connection has been broken or a short has occurred in the wiring, or the LLID is not programmed or functioning correctly. Replace as required. The purge carbon tank temp sensor has failed. The connection has been broken or a short has occurred in the wiring, or the LLID is not programmed or functioning correctly. Replace as required. Check for restrictions in the in the vapor pick-up line and in the liquid return line. Ensure the vapor line is sloped correctly and has no liquid traps. Change filter drier if required. Ensure the line shutoff valves are open.
Check for restrictions in the in the vapor pick-up line and in the liquid return line. Ensure the vapor line is sloped correctly and has no liquid traps. Change filter drier if required. Ensure the line shutoff valves are open.
This diagnostic is intended to identify a failed heater or sensor. Check carbon tank heater and heater wiring. Check the carbon tank temperature sensor and its wiring. Check the carbon tank insulation and the surrounding ambient temperature. Check the purge unit controls and settings.
This is intended to identify a failing insulation system. Check carbon tank insulation for integrity. Check ambient conditions. Check heater operation.
28
PRGD-SVX01F-EN
Page 29
Table 2. Troubleshooting a purge system (continued)
Diagnostic or Problem
Carbon Regeneration Temperature Limit Exceeded (latching diagnostic)
Purge Daily Pump-out Limit Exceeded (latching diagnostic)
Comm Loss: xxxx (latching diagnostic)
Purge unit does not run or pump­out system does not run.
Purge continues to operate when chiller is Off. Pump-out compressor operates continuously. Purge refrigerant compressor suction temperature is greater than the pump-out initiate setpoint.
Purge fails to pump-out non­condensables. Chiller observations indicate air is actually present in the chiller; that is, measured condenser pressure is greater than measured condenser temperature converted to pressure, and/ or chiller surges at start-up.
Pump-out compressor operates continuously. Purge refrigerant compressor suction temperature is less than the pump-out initiate value.
Cause Solution
The carbon tank temperature exceeded 120% of the regeneration temperature setpoint. The carbon tank temperature did not decrease more than 25°F (-3.9°C) in the first hour after the heater is turned off.
The pump-out time recorded over the past 24 hours has exceeded the daily pump-out limit setpoint.
A loss of communication of more than 30 continuous seconds has occurred between the controller and the identified component (LLID).
Control circuit problem.
Purge is set to On or to Adaptive operating mode. Purge refrigerant compressor suction temperature sensor has failed.
The control system has failed. Check the controller by using diagnostic tools.
Depending on the chiller type and the operating conditions, air may accumulate in the chiller condenser away from the purge vapor pick-up location (retrofit purge).
Pump-out restrictor plugged.
Purge condensing unit is overcharged or undercharged.
Purge expansion valve has failed.
Pump-out circuit fault. Run diagnostic of purge control circuit. Refer to control circuit test.
Purge condensing unit fan has failed.
Purge condensing unit condenser coil is fouled.
Condensing unit compressor motor winding temperature sensor opened (line break thermostat).
Pump-out compressor fault—does not run Pump-out compressor fault— pump motor runs
Purge refrigerant compressor suction temperature sensor
Purge is set to Auto mode and the chiller run signal has failed.
Excessive air in chiller.
Leakage in purge or purge pump­out tubing.
Failed or restricted solenoid.
Pump-out restrictor plugged.
Gas pick-up connection of the purge is below the liquid level of the condenser.
Gas pick-up or return line restricted.
TTrroouubblleesshhoooottiinngg
Check carbon tank heater relay and heater wiring. Check the carbon tank temperature sensor and its wiring. Check the purge unit controls and settings.
Air infiltration rate into chiller may be too high, leak check chiller and repair leaks. The daily pump-out limit setpoint may be set too low. Check and adjust to proper value. The chiller refrigerant temperature may be too low. Do not operate purge at condensing temps of 40°F (4.4°C) or lower. High vacuum pump-outs may be operated down to 32°F (0.0°C). Set pump-out inhibit to Enable and set appropriate limit.
Check the LLID and the interconnecting Machine bus. Check the LLID configuration and function using the Tracer TU service tool.
Run diagnostics of purge control system. Refer to the control circuit test. Check the purge control for active diagnostics. Check the purge control system using the Tracer TU service tool. Check operating mode. The On mode should be used only for specific service procedures; Adaptive is the normal operating mode.
Check sensor, LLID, and machine bus.
Operate the purge with the chiller Off. Any air in the chiller will be removed if the purge is functioning correctly. If a large amount of air is removed, leak test the chiller and repair leaks. Consider using the Adaptive mode to run the purge as required when the chiller is Off. If non-condensable removal is required during chiller operation, relocate the vapor/liquid connections to a more effective location. Clean out restrictor orifice with compressed air (preferred) or a small wire.
Refer to the “Determining the Refrigerant Charge Level,” p. 30 to evaluate the purge charge level. Refer to the “Determining Proper Expansion Valve Operation,” p. 31 to evaluate the purge expansion valve performance.
Test and replace fan as needed.
Clean condenser coil as required.
Check condensing fan and coil. Check purge condensing unit charge level. Check purge condensing unit compressor. Check purge power supply. Replace line break protector if needed. Replace compressor if needed.
Low voltage, no voltage, failed pump motor, failed controls.
Failed pump diaphragm, failed pump reed valves, fitting leaks, line restrictions, high-pressure drop across the pump. Not installed correctly or the thermal conductive paste has degraded. Correct orientation of installed sensor and install thermal conductive paste.
Check the chiller run signal (retrofit purge). Check the controller system.
Trace air source and repair any leak paths. Allow purge to remove accumulated air.
Check all connections on purge and between the purge tank and the pump-out compressor. Check all solenoid and other valves for possible leakage.
Failure of the pump-out solenoid to open, or a failure of the exhaust solenoid to open. Check for dirt or contamination, failed or misaligned armature, or an incorrect control command from the controller.
Refer to the installation instructions of a retrofit purge. Check overall unit operation.
Ensure shut-off valves are fully open and remove any restrictions.
PRGD-SVX01F-EN
29
Page 30
TTrroouubblleesshhoooottiinngg
Table 2. Troubleshooting a purge system (continued)
Diagnostic or Problem
Cause Solution
Restriction in exhaust lines.
Check carbon tank for restriction, check solenoid valves for restriction, check outlet tubing from the carbon tank to the chiller vent line.
Carbon Regeneration Temperature Diagnostic Procedure
If a Carbon Regeneration Temperature Setpoint Not Satisfied diagnostic is generated, follow this procedure:
1. Close the regeneration solenoid valve and turn off the heater.
2. Reset the calculated carbon capacity to 100 percent.
3. Turn the purge refrigeration circuit on and allow the carbon tank to cool for 4 hours or until the carbon temperature reaches 100°F (37.8°C), whichever comes first.
If the carbon tank temperature does not decrease more than 25°F (13.8°C) in the first hour after this procedure, the controller initiates a latching diagnostic, Carbon Regeneration Temperature Limit Exceeded. The purpose of this diagnostic is to identify a failed heater relay or temperature sensor. This diagnostic disables the purge system and opens the exhaust solenoid valve.
If a Carbon Regeneration Temperature Limit Exceeded diagnostic is generated, follow this procedure:
1. Open the exhaust solenoid for 5 minutes and then close it.
2. Run the refrigeration circuit for 15 minutes. Operating the refrigeration circuit during the carbon cool-down cycle allows time for any gas that may have remained in the carbon tank to accumulate in the purge tank.
3. While the refrigeration circuit is running, enable pump-outs. If enough gas has accumulated in the purge tank, a pump-out cycle is activated following completion of the cool-down cycle.
Purge Refrigeration Circuit Diagnostic Procedures
You can troubleshoot the refrigeration circuit by taking surface temperature measurements and using them to diagnose specific problems, as explained in this section.
Taking Surface Temperature Measurements
While the purge condensing unit is running, take temperature readings with an accurate (±1°F [±0.55°C]) surface-mounted thermocouple-type temperature probe that has a range of -40°F (-40.0°C) to 200°F (93.3°
C). The locations to be measured are shown in Figure
6, p. 16. The temperatures that you should expect to
find under typical operating conditions are given in the same figure.
1. To ensure accurate measurements, remove any ice that may exist on measuring surfaces before attaching the probe.
2. Fasten the sensor of the probe tightly against the tubing surface and insulate around the sensor for accurate results.
3. To measure the temperature at Location 1, move aside a small portion of the insulation covering the tubing between the expansion valve and the purge tank.
4. To read the purge refrigerant compressor suction temperature, view the purge component screen of the Tracer® AdaptiView™ display. Then confirm that reading by measuring the temperature with a surface-mounted thermocouple at Location 2.
5. To measure the compressor discharge temperature, mount the probe on the surface at Location 3.
6. To measure the condenser temperature (Location 4), remove the sheet metal cover from the side of the condenser and measure the surface temperature of the second or third from the top condenser tubing U-bend on the side of the coil opposite the discharge gas inlet.
7. To measure the liquid line temperature, measure the tubing between the purge condenser and the expansion valve (Location 5).
Determining the Refrigerant Charge Level
To operate correctly, the purge refrigeration system must have a proper charge level of R-404A. The charge level should be determined before any other refrigeration circuit components are evaluated.
1. Take the surface temperature measurements for Locations 1–5 as described in “Taking Surface
Temperature Measurements,” p. 30.
2. Calculate the difference between Locations 4 and 5.
3. The difference is the sub-cooling value. If the system is properly charged with R-404A, the sub­cooling value should be between 8°F (4.4°C) and 15° F (8.3°C).
a. A sub-cooling of less than 5°F (2.8°C) indicates a
possible refrigerant undercharge and a possible leak.
b. A sub-cooling value greater than 20°F (11.0°C)
30
PRGD-SVX01F-EN
Page 31
TTrroouubblleesshhoooottiinngg
indicates a refrigerant overcharge.
properly located on the chiller condenser, and are properly sloped, as described:
Determining Proper Expansion Valve Operation
The purpose of the expansion valve is to regulate refrigerant flow so that a constant pressure is maintained within the purge tank coil. A constant pressure results in a constant temperature of the refrigerant that is entering the purge tank.
To determine if the expansion valve is operating properly, measure the temperature at Location 1, as described in “Taking Surface Temperature
Measurements,” p. 30. An optimum constant
temperature of -16°F (-26.6°C) is ideal. However, an acceptable range, to allow for errors or operating conditions, is between -20°F (-28.9°C) and -10°F (-23.3° C).
Determining Correct Vapor Pick-up and Liquid Return Line Connection Locations
To ensure correct purge operation, make sure that the vapor pick-up and liquid return connections are
During chiller operation, non-condensables accumulate in the coolest, calmest spot in the condenser above the liquid level. On a Trane® chiller this location is typically just under half-way up the condenser shell above the condenser sump. An internal baffle has been installed to enhance this process during chiller operation. During chiller Off cycles, non-condensables may rise to higher elevations within the chiller. However, during purge system operation, a continuous thermal siphon develops that effectively draws the non­condensables into the purge tank.
Vapor pick-up and liquid return lines must be sloped a minimum of 2 inches per foot off horizontal or vertical to ensure that no liquid or vapor traps exist.
Using the Service Functions
Service functions allow you to take manual control to test the operation of specific functions. Refer to the following table as you test the functions in this section.
Table 3. Purge component status
Displayed purge status
Refrigerant Circuit On
Refrigerant Circuit Idle
Pumping Out
Regenerating
Exhaust Circuit Check o o
Pumpout Inhibited
Daily Pumpout Limit Disabled
Purge Diag Shutdown
Notes:
1. o = Off or de-energized
2. • = On or energized
3. X = Cycling on internal algorithm
Condensing
unit
o o o o o
o o o o o o
X o o
X o o o X X
o o o o o
X X X o o
o o o o o o
Pump-out
compressor
Pump-out
solenoid
Exhaust
solenoid
Regeneration
solenoid
Carbon tank
heater
Purge Regen Cycle
The Purge Regen Cycle is a manual control setting that allows you to manually initiate a carbon tank regeneration cycle.
NNoottee:: This test can be initiated from either the Tracer
AdaptiView™display or the Tracer®TU service tool.
Run this cycle to:
Observe the purge condensing unit stopping
Observe the pumpout solenoid closing (if open)
Observe the regeneration solenoid opening
Observe the carbon tank heater energizing
Verify that regeneration setpoints are achieved
Verify that timing functions are correct
PRGD-SVX01F-EN
For more information regarding this feature, see
“Carbon Regeneration Temperature Diagnostic Procedure,” p. 30.
Purge Exhaust Circuit Test
®
The Purge Exhaust Circuit Test is a manual control setting that you can use to check that the components activate in the right sequence and at the right time when commanded to do so by the controls.
NNoottee:: This test can be initiated from either the Tracer
AdaptiView™display or the Tracer®TU service tool.
This feature, when enabled, overrides the pump-out algorithm and executes a pump-out sequence, regardless of the actual purge refrigerant compressor suction temperature. Once activated, the pump-out sequence continues for 30 seconds. During this time,
®
31
Page 32
TTrroouubblleesshhoooottiinngg
you can observe and confirm that the pump-out compressor starts and the exhaust solenoid opens. After 5 seconds, you should also be able to observe the pump-out solenoid opening.
Exhaust Circuit Pressure Check
The Exhaust Circuit Pressure Check enables the servicing technician to check the exhaust circuit components and lines for leakage by pressurizing the exhaust circuit.
NNoottee:: This test can be initiated from only the Tracer
TU service tool.
To perform this test, follow this procedure:
1. Install a pressure gauge, isolation valve, pressure regulator, and a source of dry compressed air or nitrogen to the line downstream of the exhaust solenoid valve. When this check is enabled, the exhaust solenoid opens.
2. Pressurize the exhaust circuit to no more than 10 psi (68.9 kPa) using dry air or nitrogen.
3. After the target pressure is achieved, isolate the pressure source and monitor the pressure gauge for decay. A loss of pressure indicates leakage from the exhaust system.
4. Test the exhaust components and line connections for leaks by using a soap solution.
5. Relieve the testing pressure from the exhaust circuit before disabling this test. When the test is disabled
®
the exhaust solenoid valve re-closes.
Exhaust Circuit Vacuum Check
The Exhaust Circuit Vacuum Check enables the servicing technician to check the exhaust circuit components and lines for leakage by placing a vacuum on the exhaust circuit.
NNoottee:: This test can be initiated from only the Tracer
TU service tool.
To perform this test, the servicing technician should follow this procedure:
1. Install a vacuum gauge, isolation valve, and a vacuum source to the line downstream of the exhaust solenoid valve. When this check is enabled, the exhaust solenoid opens.
2. Turn on the vacuum source and pull the exhaust circuit to as deep a vacuum as can be achieved.
3. After a vacuum is achieved, isolate the vacuum source and monitor the vacuum gauge for decay. A rise in pressure indicates leakage into the exhaust system.
NNoottee:: Out-gassing of refrigerant from the carbon
tank may give a false indication of a pressure rise.
4. Relieve the vacuum from the exhaust circuit before disabling this test. When the test is disabled the exhaust solenoid valve re-closes.
®
32
PRGD-SVX01F-EN
Page 33
Specifications
An EarthWise™ purge system has the specifications shown in the following table:
115 Vac, 60 Hz, 1-phase, 10.3 A
Electrical power requirements
Purge compressor motor rated-load ampacity
Total unit ampacity
Minimum circuit ampacity
Carbon tank heater wattage
Alarm relay output rating 120 Vac, 1/3 hp, 7.2 FLA
Operating temperature range 34°F to 110°F (1.1°C to 43.3°C)
Storage temperature range -40°F to 150°F (-40.0°C to 65.5°C)
Storage and operating humidity range 5% to 95% relative humidity, non-condensing
Mounting Direct-mounted on condenser shell above the liquid level of highest condenser
Dimensions (approximate)
Weight 140 lb (63.5 kg) with filter-drier
Condensing unit refrigerant charge 0.60 lb (0.27 kg) of R-404A
110 Vac, 50 Hz, 1-phase, 10.3 A Voltage range is +10%, -15%
8 RLA
10.3 A
12.3 A
175 W
25-3/4 in. (65.4 cm) high x 27-1/2 in. (69.9 cm) wide x 21-3/4 in. (55.2 cm) deep, with filter-drier
PRGD-SVX01F-EN
33
Page 34
Schematic Wiring Diagram
EarthWise Purge System with Tracer AdaptiView Controls
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
NNOOTTIICCEE
UUssee CCooppppeerr CCoonndduuccttoorrss OOnnllyy!!
FFaaiilluurree ttoo uussee ccooppppeerr ccoonndduuccttoorrss ccoouulldd rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee aass tthhee eeqquuiippmmeenntt wwaass nnoott ddeessiiggnneedd oorr qquuaalliiffiieedd ttoo aacccceepptt ootthheerr ttyyppeess ooff ccoonndduuccttoorrss..
34
PRGD-SVX01F-EN
Page 35
SScchheemmaattiicc WWiirriinngg DDiiaaggrraamm
PRGD-SVX01F-EN
35
Page 36
SScchheemmaattiicc WWiirriinngg DDiiaaggrraamm
36
PRGD-SVX01F-EN
Page 37
NNootteess
PRGD-SVX01F-EN
37
Page 38
NNootteess
38
PRGD-SVX01F-EN
Page 39
NNootteess
PRGD-SVX01F-EN
39
Page 40
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands — including Club Car
®
Trane
— work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
PRGD-SVX01F-EN 20 Jul 2017
Supersedes PRGD-SVX01E-EN (November 2016) ©2017 Ingersoll Rand
®
, Ingersoll Rand®, Thermo King®and
ingersollrand.com
Loading...