Not e: This accessory is n ot for use on un its w ith Single Zone VAV or True VAV sup ply fan types (Digit 15 = 2,3,4,5).
SAFETY WARNING
Only qualified personnel should install and service the equipment . The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When w orking on the equipment, observe all precautions in the literature and on the tags, stickers, and labels t hat are
attached to the equipment.
August 2022
ACC-SVN231A-EN
Page 2
Introduction
Read th is manual th oro ughly before op erati ng o r
servici ng this unit.
Warnings, Cautions, and Notices
Safety ad visories appear through out this m anual as
req uir ed. Your p ersonal saf ety and t he pr oper oper ation o f
this m achine depend upon the st rict ob servance of these
precautions.
The thr ee types of advi sories are defined as f ollow s:
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirement s
for field wiring installation and grounding as described
in NEC and your local/ state/ nat ional electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a pot entially hazard ous
situation w hich, if n ot avoided, could
result in death or serious injury .
Indicates a pot entially hazard ous
si
tuation w hich, if no t avoided, cou ld
result in m i nor or m oder ate inju ry. It
could also be used to alert against
unsafe practices.
Ind icates a si tuat ion that coul d resul t in
equipm en t or pr operty -dam age only
accident s.
Important Environmental Concerns
Scienti fic research has shown that certain m an-m ade
chem i cals can affect th e eart h’s natu rally occurring
strato spheric ozone lay er w hen released to the
atm osph ere. In particular, several of the identified
chem icals that m ay affect the ozone layer are refrigerants
that contain Chlor ine, Fluor ine and Carb on (CFCs) and
those cont aining Hydrogen, Chlor ine, Fluorine and
Carbon (HCFCs). No t all refrigeran ts containi ng these
com pounds have th e sam e potenti al im pact to th e
envir onm ent. Trane advocates the resp onsible handling
of all refr iger ants-includi ng ind ustry replacem ents for
CFCs and HCFCs such as saturated or unsaturated HFCs
and HCFCs.
Important Responsible Refrigerant
Practices
Trane believes t hat respo nsible refrigerant practices are
im portant t o the env ironm ent, our custom ers, and the air
conditioning industry. All technicians w ho handle
refri gerants must be certified according to local r ules. For
the USA , the Federal Clean Air Act (Section 608) set s forth
th e requir emen ts for h andl ing, recl aimin g, recover ing and
recycling of certain refrigerant s and the eq uipm ent that is
used in these service p rocedur es. In addit ion, some states
or m uni cipalities m ay hav e additio nal requirement s that
must also be adhered to for resp onsible m anagem en t of
refri gerants. Know the applicable law s and follow them .
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken
could result in death or serious injury. Technicians, in
order to protect them selves from potential electrical,
mechanical, and chemical hazards, MUST follow
precautions in this manual and on the tags, stickers,
and labels, as w ell as the instructions below :
•Before installing/ servicing this unit, technicians
MU
ST put on all PPE required for t he w ork being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/ bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Safety Data Sheets
(SDS) and OSHA guidelines for proper PPE.
•When w orking with or around hazardous chemicals,
WAYS refer t o the appropriate SDS and OSHA/
AL
GHS (Global Harmonized System of Classificat ion
and Labeling of Chemicals) guidelines for
information on allowable personal exposure levels,
proper respiratory protection and handling
instructions.
•If there is a risk of energized electrical contact, arc,
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirement s for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTIN G, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions below could result in
death or serious injury.
•All Trane personnel must follow the company’s
E
nvironmental, Health and Safety (EHS) policies
when performing work such as hot w ork, electrical,
fall protection, lockout/ tagout, refrigerant handling,
etc. Where local regulations are more stringent than
these policies, those regulations supersede these
policies.
•Non-Trane personnel should alw ays follow local
lations.
regu
Copyright
Thi s docu men t and t he in for mat ion in i t are t he pr oper ty o f
Trane, and m ay not be used or rep rod uced i n who le or in
part w ithout w ritt en perm ission. Trane reser ves the right
to revise th is publ icati on at any tim e, and to m ake chang es
to it s content w ith out obligati on to n otify any perso n of
such rev ision or chan ge.
Introduction
Trademarks
All t radem arks refer enced in this docum ent are the
tradem arks of t heir respectiv e owners.
This instru ction co vers installation of FIADM PR102* for 6
to 12.5 to ns, T/YS* 072-150.
Inspection
1. Unpack all com pon ents of the kit.
2. Check careful ly for shippi ng damage. If any dam age is
found, report i t im m ediately, and file a claim again st
the tr ansport ation co m pany .
3. Visually in spect the com pon ents for shipping damage
as soon as possible after del ivery, before it is stored.
Concealed d am age m ust b e repo rted w ithin 15 days.
4. If co ncealed dam age is di scovered, st op unp acking th e
shi pm ent.
5. Do not rem ove dam aged m aterial from the receiv ing
location. Take photos of the d am age, if possible. The
ow n er must provi de reasonab le evidence that th e
dam age did not occu r aft er del ivery.
6. No tif y th e carri er’s ter mi nal o f dam age im m ediat ely b y
phone and b y mail. Requ est an im m ediate joi nt
inspection of th e damage by t he carrier and the
consig nee.
Not e: Do n ot attem pt to repair an y dam aged parts un til
the par ts are insp ected by t he carrier’s
representative.
Parts List
•One (1) M o torized OA Dam per A ssem bly
•12 Screw s
•One (1) Blockoff ; Bottom
•One (1) Actuato r Control Har ness
ACC-SVN231A-EN5
Page 6
Installation – FIADMPR102*
Align (3) tabs on bracket
with (3) slots in panel.
Pivot into place and
secure with three screws
engaged into damper
side panel.
Align (3) slots in panel
with (3) tabs on damper
side panel. Pivot panel
into place.
Uncrat e the damper and locat e all part s show n in Figu re 1.
Each dam per ship s wi th i tem s 1, 2 and 3 at tache
screw s completely fr om it em s 1 and 2. Remove i tem 3 by
loosenin g the three screw s but do not remov e them . See
figure below .
Figure 1.Damper
components
d. Rem ove
1
2
3
Do not
remove screws
Figure 2.Damper panel
5. Remove the filter access panel. Position the adapter
backing plate in side the f ilter sect ion. The adapter
backing plate w ill slip over the three screw s t hat w ere
lo osened in
le in t he adapter backing plate, w ith the screw
ho
clearance h ole in eco nom i zer side panel and secure
low er right si de of dam p er wit h screw four. Refer to
Figure 2, p. 6.
6. Install the bottom blockoff and secure
screw s. Refer to
Figure 1, p. 6. A lig n t he screw eng agem ent
wit h three
Figure 3, p. 6.
WARNING
Hazardous Voltage w / Capacitors!
Failure to follow instructions below could result in
death or serious injury.
Power dow n the outdoor unit
with t he inverter circuit board. Follow proper lockout/
tagout procedures to ensure the pow er cannot be
inadvertently energized.Wait for at least 15 minutes to
allow the unit to fully discharge high DC voltage.
Confirm the unit is fully discharged using a CAT III or IV
voltmeter rated per N FPA 70E.
1. Remove unit end panel , retain the screw s rem o ved
fro
m the top of panel and the scr ew s rem oved fr om
bott om of panel fo r use later
2. To install the dam per, lif t into po s
upper left hand corner ar oun d the chan nel in the
cabinet post. Then pivot the dam per into the opening
in th e cabinet. Refer to
3. Once the d am per is in place, lift th e damper and panel
assemb
th e top by inserti ng tw o screw s, top left 1 then top ri ght
2. Refer t o
4. Pull ou t on th e bottom of the
bott om lef t 3. Refer to
ly to align the u pper tw o screw ho les. Secure
Figure 2, p. 6.
before making contact
Figure 2, p. 6.
Figure 3, p. 6.
ition by fi tting the
dam p er and secur e
Figure 3.Bottom blockoff
1
3
Adapter
2
Backing Plate Panel
4
Bottom Blockoff
6 ACC-SVN231A-EN
Page 7
Installation – FIADMPR102*
Remove screw to
remove bottom
blockoff from
shipping location.
Bottom Blockoff
Factory Installed Damper Set-Up
Downflow Configuration
To p osit ion dam per for dow nflo w o perat ion , compl ete th e
foll owing steps:
WARNING
Hazardous Voltage!
Failure to disconnect pow er before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the pow er can not be
inadvertently energized. Verify that no pow er is
present with a voltmeter.
1. Remove filt er access pan el.
2. Remove bottom blocko ff from
See
Figure 4, p. 7.
Figure 4.Remove bott om blockoff
its shipp ing locati on.
Figure 5.Damper assembly operating position
Bottom Blockoff
Screws used to
secure economizer
3. Remove the bo ttom three screws fr om the dam per
panel.
4. Pull th e damper assem bly out into operati ng position
as shown in
5. Secure the dam per assem b ly w i th tw o screw s at the
bott om of the
6. Install bottom blo ckoff and secure w
Figure 5, p. 7.
corner posts.
ith three screw s.
ACC-SVN231A-EN7
Page 8
General Information – FIADMPR103*
This in struction covers installatio n of FIADM PR103* for
12.5 to 25 to ns, T/YS* 180-300, W/D/GS* 150-300.
Inspection
1. Unpack all com pon ents of the kit.
2. Check careful ly for shippi ng damage. If any dam age is
found, report i t im m ediately, and file a claim again st
the tr ansport ation co m pany .
3. Visually in spect the com pon ents for shipping damage
as soon as possible after del ivery, before it is stored.
Concealed d am age m ust b e repo rted w ithin 15 days.
4. If co ncealed dam age is di scovered, st op unp acking th e
shi pm ent.
5. Do not rem ove dam aged m aterial from the receiv ing
location. Take photos of the d am age, if possible. The
ow n er must provi de reasonab le evidence that th e
dam age did not occu r aft er del ivery.
6. No tif y th e carri er’s ter mi nal o f dam age im m ediat ely b y
phone and b y mail. Requ est an im m ediate joi nt
inspection of th e damage by t he carrier and the
consig nee.
Not e: Do n ot attem pt to repair an y dam aged parts un til
the par ts are insp ected by t he carrier’s
representative.
Parts List
•One (1) M o torized OA Dam per A ssem bly
•Ten (10) Screw s
•One (1) Blockoff ; Bottom
8 ACC-SVN231A-EN
Page 9
Installation – FIADMPR103*
1
2
2
1
Field Installed Damper
1. Uncrate the d am per and locate all parts show n in
Figure 1, p. 9.
Figure 1.Damper content s
WARNING
Hazardous Voltage w / Capacitors!
Failure to disconnect pow er and discharge capacit ors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start / run
capacit ors before servicing. Follow proper lockout/
tagout procedures to ensure the pow er cannot be
inadvertently energized. Verify with a CAT III or IV
voltmeter rated per N FPA 70E that all capacit ors have
discharged.
3. Attach blockoff (2) t o u
Figure 3.Install blockoff
4. Secure econom izer assem bly
screw s.
Figure 4.Install economizer assembly
nit by using four scr ew s.
(1) to unit using ten
2. Remove unit end panel , retain the screw s for later use.
Figure 2.Remove end panel
5. Attach end panel back to u nit using the screw s
emov ed in Step 2 and seal indicat ed areas in
r
wit h field supp lie
p. 10
therm ostat sel ector sw itch to the OFF po sition .
ACC-SVN231A-EN9
d sili cone sealant.Place the
Figure 5,
Page 10
Installation – FIADMPR103*
Remove screws and lay blockoff
angle aside. Do not discard.
Blockoff Angle
Figure 5.Reinst all end panel
Factory Installed Damper (Field
Set-Up)
Downflow Configuration
To p osit ion dam per for dow nflo w o perat ion , compl ete th e
foll owing steps:
WARNING
Hazardous Voltage!
Failure to disconnect pow er before servicing could
result in death or serious injury.
Disconnect all electric powe
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the pow er can not be
inadvertently energized. Verify that no pow er is
present with a voltmeter.
1. Remove filt er access pan el.
2. Remove the lo w er screws in the end panel. See
Figure 6, p. 10. Lay blockoff angle aside for l ater
stallation.
in
r, including remote
Figure 6.Remove low er screws
3. Do not rem ove the screws in th e upper row of the end
panel.
4. Grasp th e botto m of t he end pan el and pu ll the
conomizer assem bly outw ard into the operating
e
posit ion. See
5. Remove approx imately 3-inches of gasket m aterial
from the
holes u sed to att ach the econ omizer assem bly to t he
unit . See
6. With the screws provided, secure
econ om izer assem bly by inser tin g a screw thr oug h th e
clear ance ho le in the b otto m o f th e cor ner p ost an d in to
the eng agement hole in th e econom izer assem bly.
Refer to
Figure 7.Remove gasket material
Figure 6, p. 10.
bott om of each corner post to expose the
Figure 7, p. 10.
each side o f the
Figure 7, p. 10.
10 ACC-SVN231A-EN
Page 11
7. Install the blockoff angle un derneath the econo m izer.
The blockoff angle is design ed to clo se the opening
created, betw een the econ omizer and the base, when
the economizer assem b ly is in its oper ating position.
a. Holding the blo ckoff angle w ith
bott om and th e bottom angle outw ard, tilt the top
forw ard and insert it into the opening b etween the
econ omizer and th e unit base.
b. Press the bottom of the bl
unit and line up the holes. Usi ng the provided
screw s, secu re it in to p lace.
Figure 8.Blockoff installation
the ho les at the
ockoff angle against the
Installation – FIADMPR103*
8. Proceed to m i nim um p osition sett ing.
ACC-SVN231A-EN11
Page 12
Minimum Position Setting – FIADMPR102* / 103*
To adju st the m inim um position setting and check ou t the
economizer, t he pow er m ust be con nected.
1. Close t he un it disco nnect and p lace t he zone sen sor f an
selector in the fan ON position and the heat/cool
select or in the OFF posi tion. Th is wil l place th e damper
in the m i nim um v enti lation posi tio n.
2. To adjust t he minim um positio n setting for the
requi red vent ilation air, use the Sym bio service and
instal lation m obile ap p or Sym bio™ 700 on-boar d UI
to adj ust the eco nom i zer m inim um position setpoint
BAS in t he fresh/r eturn air settin gs menu. The damper
wil l open t o this set ting each ti m e the blow er circuit is
energi zed.
When adjusting m inim um position, the dam per may
mov e to the n ew setting in sev eral sm all steps. Once
the damper has rem ained in position fo r 10 - 15
secon ds w ithou t m ovem ent, it can be assum ed it is at
th e new position.
3. Replace the f ilter access panel.
The dam per w ill close when the blo w er cir cui t is
de-energized.
FRESH AIR OPTIONS MODULE ONLY PRESENT ON CERTAIN UNIT CONFIGURATIONS. SEE INSET A FOR
UNITS WITHOUT FRESH AIR OPTIONS MODULE.
1
BK R BL O
BK R BL O
White
BK R BL O
1
234
1
23
4
White
BK R BL O
1
234
TO IOM-P4
SHEET 5
1
23
4
TO AIRFI
1
INSET A
BK R
BK R
XFR
2
1
White
BK R BL O
1
234
TO AIRFI
3
4
2
RETURN AIR TEMP SENSOR PRESENT ON UNITS WITH DIFFERENTIAL DRY BULB, REFERENCE ENTHALPY,
AND COMPARATIVE ENTHALPY CONTROL
RETURN AIR HUMIDITY SENSOR PRESENT ON UNITS WITH REFERENC E ENTHALPY AND COMPARATIVE
ENTHALPY CONTROL
RETURN AIR HUMIDITY SENSOR PRESENT ON UNITS WITH COMPARATIVE ENTHALPY CONTROL
PPF62
PPF63
PPF64
PPF87PPM87
PPF88PPM88
PPF86
PPM86
BK
2
1
TO LINE 320
Sheet 6
J11-1
TO LINE 322
Sheet 6
J8-1
3
1
2
ECA
24 V? IN
DAMPER POSITION IN
DAMPER POSITION OUT
Common
4
BK
R
BL
O
3
1
2
4
OpƟonal Horizontal Low Leak
OpƟonal Economizer
OpƟonal Economizer
OpƟonal Return Air Smoke Detector
OpƟonal Power Exhaust
1. Using the suppli ed harness co nnect PPF87 to the
actuator co nnector.
2. Route harness t o fresh air options m odule l ocated in
the ret urn s
ection and co nnect to FAOM -J11.
Figure 9.Fresh air options module
3. After installati on is complete, Sy m bio ™ 700 UC unit
figu ration w ill need to be updat ed to reflected
con
installed option.
ACC-SVN231A-EN13
Page 14
Notes
14 ACC-SVN231A-EN
Page 15
Notes
ACC-SVN231A-EN15
Page 16
Tran e and A m erican Stand ard cr eate com fortable, energy effi cient indoor enviro nments for
com m ercial and resi dential applicat ions. For m ore informati on, please v isit tr ane.com or