Trane PRC001-EN User Manual

Packaged Gas/Electric Rooftop Units
Voyag er™ 12½ – 25 Tons — 60 Hz
RT-PRC001-ENOctober 2004

Introduction

Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionalize this design concept.
The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.
Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager.
Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer­aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your needs.
It’s Hard To Stop A Trane.
®
© 2004 American Standard Inc. All rights reserved
RT-PRC001-EN
Contents
Introduction Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
Performance Data
Cooling Performance Fan Performance Heat Performance
Controls
Electric Power
Dimension and Weights
2
4
10
11
13
14
21
21 31 43
46
47
58
RT-PRC001-EN
Mechanical Specifications
68
3

Features and Benefits

Factory Installed Options
• Black Epoxy Coated Condenser Coil
• Dehumidification Option
• High Efficiency Motors
• High Pressure Cutout
• Hinged Access Doors
• Novar Unit Controls
• Novar Return Air Sensor
• Powered or Unpowered Convenience Outlet
• Supply and/or Return Air Smoke Detector
• Thermal Expansion Valve/Face-Split Evaporator Coil Option
• Through the Base Electrical with Circuit Breaker
• Through the Base Electrical With Disconnect Switch
• Through the Base Utilities Access
• Two-Inch Pleated Filters
Factory or Field Installed Options
Clogged Filter/Fan Failure Switch
Differential Pressure Switches
Discharge Air Sensing Kit
Downflow – Economizer
Frostat
LonTalk® Communications Interface
Oversized Motors
Reference or Comparative Enthalpy
Tool-less Hail Guards
Trane Communications Interface (TCI)
Field Installed Options
CO
Sensing
2
Digital Display Zone Sensor
Dual Thermistor Remote Zone Sensor
Low Static Drive
High Static Drive
Manual Outside Air Damper
Motorized Outside Air Dampers
Powered Exhaust
Downflow – Roof Curb
Horizontal – Economizer
Remote Potentiometer
Ventilation Override Accessory
Zone Sensors
RT-PRC001-EN4
Features and Benefits
Easy to Install, Service and Maintain
Because today’s owners are very cost­conscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering:
Quality and Reliability
ReliaTel™ Controls (LCI-R)
ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature.
ReliaTel™
Quality and Reliability are enhanced through ReliaTel control and logic:
—prevents the unit from short cycling,
considerably improving compressor life.
—ensures that the compressor will run
for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.
Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them.
The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically. — The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems.
Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation.
ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.
Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.
The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling with Electric Heat, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.
5RT-PRC001-EN
Features and Benefits
Drum and Tube Heat Exchanger
The heat exchanger is manufactured
using aluminized steel with stainless steel components for maximum durability. The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirements. American Standard requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements.
The negative pressure gas valve will
not allow gas flow unless the combustion blower is operating. This is one of our unique safety features.
The forced combustion blower supplies
pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system.
The hot surface ignitor is a gas ignition
device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability.
Our gas/electric rooftops exceed all
California seasonal efficiency requirements and perform even better than the California NOx emission requirements.
Forced Combustion Blower
Negative Pressure Gas Valve
Hot Surface Ignitor
Drum and Tube Heat Exchanger
RT-PRC001-EN6
Features and Benefits
Outstanding Standard and Optional Components
Black Epoxy Coated Condenser Coil
The coil provides corrosion protection to condenser coils for seacoast application.
Cabinet Integrity
For added water integrity, Voyager has a raised 11/8" lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication.
CO
Sensing
2
The CO space occupancy levels within the building by measuring the parts per million of CO As the CO2 levels increase, the outside air damper modulates to meet the CO space ventilation requirements. The CO sensor kit is available as a field installed accessory.
Colored And Numbered Wiring
Save time and money tracing wires and diagnosing the unit.
Compressors
Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models.
Refrigerant Circuits
All Voyager 12½-25 ton units shall have crankcase heaters, low and high pressure controls as standard.
Condenser Coil
Voyager boasts a patent-pending 1+1+1 condenser coil, permanently gapped for easy cleaning.
sensor has the ability to monitor
2
(Carbon Dioxide) in the air.
2
2
2
Dehumidification (Hot Gas Reheat) Option
This option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space. Cooling can operate without a demand for dehumidification. The hot gas reheat coil is designed to deliver maximum reheat temperature.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor should be utilized with ReliaTel™ controls.
Discharge Air Sensing Kit
Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel Options Module.
Downflow And Horizontal Economizers
The economizers come with three control options — dry bulb is standard, enthalpy and differential enthalpy are optional.
Dual Thermistor Remote Zone Sensor
This sensor will reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.
Factory Built Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.
Fresh Air
0 - 25% manual or 0 ­50% motorized outside air hoods are available.
Low Static Drive Accessory
This option shall allow the standard motor to operate at lower static performance. (See Fan Performance tables).
High Static Drive Accessory
Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.
Hinged Access Doors
These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.
LonTalk® Communications Interface
The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls.
Power Exhaust Option
This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Quick-Access Panels
Remove three or fewer screws for access to the standardized internal components and wiring.
Quick-Adjust Idler Arm
With the Quick-Adjust Idler Arm, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.
7RT-PRC001-EN
Features and Benefits
Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.
Sloped Drain Pans
Standard on every unit.
Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager.
Due to standardized components throughout the Voyager line, contractors/ owners can stock fewer parts.
Supply and/or Return Air Smoke Detector
With this option installed, if smoke is
detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used
with certain models.
Tool-less Hail Guards
Tool-less, hail protection quality coil
guards shall be either factory or field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.
VariTra c
When Trane’s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac.
Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.
Zone Sensors
Available in programmable, automatic and manual styles.
Rigorous Testing
The fan and idler arm assembly designs have been tested to over 300,000 cycles each. Our combined cycle testing is now over 7,000,000 cycles.
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity.
Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress.
We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.
Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
Voyager units incorporate either a one piece top or the Trane-Tite-Top (T part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.
3
). Each
Trane Communication Interface (TCI)
Available factory or field installed. This module when applied with the ReliaTel™ easily interfaces with Trane’s Integrated Comfort
TM
System.
VariTrac™
RT-PRC001-EN8
Features and Benefits
Easy to Install and Service
Conversionless Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation.
Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.
Easy Access Low Voltage Terminal Board
Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire. This is another cost and time saving installation feature.
Low Voltage Connections
The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.
Powered or Unpowered Convenience Outlet
This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered. This option is available on all downflow models.
Single Point Power
A single electrical connection powers the unit.
Single Side Service
Single side service is standard on all units.
Through the Base Electrical with Circuit Breaker
This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. This option is available on all downflow models.
Through the Base Electrical with Disconnect Switch
Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. This option is available on all downflow models.
Through the Base Utilities Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.
Factory Installed Options
A wide variety of Factory Installed Options (FIOPs) are available.
Added Efficiency
Airflow
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.
High Efficiency Motors
This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.
U-shaped Airflow
U-shaped airflow allows for improved static capabilities.
Low Ambient Cooling
Cooling capabilities down to 0°F as standard.
Oversized Motors
Factory or field installed oversized motors available for high static applications.
One of our Finest Assets:
Trane Sales Representatives are a Support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and much more
Voyager has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its U-shaped airflow performance is outstanding.
9RT-PRC001-EN

Application Considerations

Application of this product should be within the cataloged airflow and cooling considerations.
Low Ambient Cooling
This Voyager line features, as standard, low ambient cooling down to 0°F. The Voyager™ line features, with ReliaTel™ microprocessor controls, low ambient cooling down to 0°F. The following options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters, thermal expansion valves, frostat. Contact your local Trane Representative for more assistance with low ambient cooling applications.
Barometric Relief
This product offers an optional barometric relief damper included in the downflow economizer accessory. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.
NOTE: THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED. PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZATION.
Heating Operation
The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50% outside air.
Power Exhaust Accessory
The power exhaust accessory is available on all 12½-25 tons downflow units. This accessory can be field installed and will assist in relieving building pressurization.
Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel.
Unit Pitch
These units have sloped condensate drain pans. Units must be installed level; any unit slope must be toward access side of unit.
RT-PRC001-EN10

Selection Procedures

Cooling Capacity
Step 1 — Calculate the building’s total
and sensible cooling loads at design conditions. Use the Trane calculation form or any other standard accepted method.
Example: The following are the building requirements: a. Electrical Characteristics: 460/60/3 b. Summer Design Conditions: Entering
Evaporator Coil: 80° DB/ 67° WB
Outdoor Ambient: 95° DB c. Total Cooling Load: 220 MBh d. Sensible Cooling Load: 140 MBh e. Airflow: 8000 cfm External Static
Pressure: 0.450 in wg f. downflow configuration g. economizer
Step 2 — As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by the nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size.
220 MBh / 12 MBh = 18.333 (approx 20 tons).
Step 3 — Examine gross capacity: Table PD-4 shows that a YC*240B3 has a gross cooling capacity of 246 MBh and 176 MBh sensible capacity at 95 DB ambient and 8000 cfm with 80 DB/ 67 WB air entering the evaporator.
To Find Capacity at Intermiediate Conditions Not in the Table
When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.
Step 4— Verify the unit will have enough capacity to meet the building requirements by determining the net capacity, which includes heat generated by the fan. In order to select the correct unit, the fan motor heat must be deducted from the gross coolingcapacity. The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure.
To determine the total unit static pressure add the external static pressure to the additional static created by the added features:
External Static (duct system) 0.45 wg
Standard Filter 2 in. (from Table PD-36)
0.11 g
Economizer (100% Return Air from Table PD-20) 0.05 wg
Total static pressure 0.61
Note: The Evaporator Fan Performance Table PD-20 has already accounted for the pressure drop for standard filters and wet coils (see note below Table PD-20). Therefore the actual total static pressure is 0.61-0.11 = 0.50 wg.
With 8000 cfm and 0.50 inches external static pressure. Table PD-20 shows 3.96 bhp for this model. At these conditions, the note below the table gives a formula to calculate Fan Motor Heat:
3.15 X bhp = MBh
3.15 X 3.96 = 12.47 MBh.
Subtracting the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity = 246 MBh - 12.47 = 251.53 MBh Net Sensible Cooling Capacity = 176 MBh - 12.47 = 163.53 MBh.
Since the Net Total Cooling Capacity meets the cooling load requirements of 220 MBh, we are satisfied with this selection.
Heating Capacity
Step 1 — Calculate the building heating
load using the Trane calculation form or other standard accepted method.
Step 2 — Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: a. Total heating load of 165 MBh b. 8000 cfm c. Fuel - Natural gas
For the YC*240B3, there are two heating capacities available, 250 MBh and 400 MBh input models shown in Table PD-35. The output capacities of these furnaces are 175 MBh and 300 MBh respectively. The low heat model with 175 MBh best matches the building requirements, indicating a YC*240B3 should be selected.
Air Delivery Selection
External static pressure drop through the air distribution system has been calculated to be 0.50 inches of water. Enter Table PD-20 for a YC*240B3 at 8000 cfm and 0.50 static pressure. The standard motor at high speed will give the desired airflow.
Accessory Selection
Select accessories needed to accommodate the application.
11RT-PRC001-EN
Selection Procedure
Dehumidification Selection
Determine normal unit cooling and heating capacities as previously described in the selection procedures on prior page.
Typical 20 ton YFD241C 6400 cfm Total Supply airflow 2560 cfm Outside Air (40%) 3840 cfm Return Air
1.00” External Static Pressure
OA Conditions
Part load day and raining
68°F db 67°F wb
66.5 dp 95% RH
RA’ conditions 75°F db 63°F wb 52% RH
55.9 dp
Step 1: Determine the mixed/ entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb temperature) + (% return air*return air dry-bulb temperature) MA’ = (0.40*68°F) + (0.60*75°F) MA’ = 72.20°F db
Note: Repeat for wet-bulb temperature (wb).
Plot on psychrometric chart.
MA’
72.2°F db
64.7°F wb
Step 2: Determine the additonal static pressure drop for a reheat unit
Table PD-36 shows a static pressure drop of 0.35” for the reheat coil and an additional .04 for the mandatory 2” pleated filters required when ordering the dehumidification option. Total static pressure =
1.0+0.035+0.04=1.075 (
1.1 for manual calculations)
Do not forget to also add any additional static from other accessories.
Table PD-29 (airflow table for 20 ton dehumidification units) indicates that a standard motor and drive is needed for this airflow and static pressure range.
OA
RA
MA
SA’
SA
Chart C-1
68°F DB, 67°F WB
75°F DB, 52% RH
72°F DB 65°F WB
51.7°F DB,
51.0°F DB
71°F DB, 59°F WB
SA’
SA’
REHEAT
Step 3a: Determine leaving evaporator temperature (SA’)
Leaving Unit Temperature = SA’ Utilizing the manual selection method as previously described and the formula
Temp = gross sensible or latent cooling
capacity in Bth
(cfm)(1.085)
Subtract your sensible temp from the entering db and latent temp from the entering wb or use the TOPSS™ program determine the leaving evaporator temperature (temperature without the addition of fan heat).
51.74 db
51.03 wb
Step 3b: Determine leaving
unit temperature in standard cooling mode
Repeat Step 3a substituting net sensible or latent capacity for gross sensible or latent capacity to find the leaving unit temperature including fan heat or refer to your TOPSS selection.
53.6 db 51 wb 84% RH 49% dp
Step 4: Determine reheat temperature rise
Using the leaving
evaporator temp (SA’), go to PD-37 and determine the reheat temperature rise for that particular cfm:
17.55°F db
Note: Reheat temperature rise is based on supply airflow and leaving evaporator coil temperature.
OAOAOA
MA
MA
RA
RA
SA
SA
Step 5: Determine leaving unit sensible temperature
with reheat
active (SA)
Reheat temperature (obtained in step 4) + (SA’ + fan heat) = SA
(SA’ + fan heat) = leaving unit temperature in standard cooling mode from step 3b.
17.55°F db + 53.6°F = 71.2°F db SA=71.2°F
Since reheat adds only sensible heat, follow the psychrometric chart to find the new wb temperature.
wb
58.7°F
Consider Chart C-1. If the space relative humidity is equal to or above the space relative humidity setpoint, the Dehumidification option will:
• Energize compressor or both compressors (2 stage compressor units).
• Hot gas reheat valve is energized and hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated when space humidity is reduced to 5% below relative humidity setpoint.
At MA’, air enters the RTU. The RTU filters, cools, and dehumidifies the air as it moves through the evaporator coil. Air leaves the evaporator coil saturated at the preset dew point condition (SA’) and is reheated by the hot gas reheat coil to deliver 71°F (SA) supply air to the space.
RT-PRC001-EN12

Model Number Description

Packaged Gas/Electric Unit Typical Model Nomenclature
YC D 150 C 3 L 0 A A
12 3 456 7 8 9 10 11 12
Digits 1, 2 - Product Type
YC = Packaged Gas/Electric YF = With Factory Installed Options
Digit 3 - Airflow Configuration
D = Downflow H = Horizontal
Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh)
150 = 12½ Ton Standard Efficiency 151 = 12½ Ton High Efficiency 180 = 15 Ton Standard Efficiency 181 = 15 Ton High Efficiency 210 = 17½ Ton Standard Efficiency 211 = 17½ Ton High Efficiency 240 = 20 Ton Standard Efficiency 241 = 20 Ton High Efficiency 300 = 25 Ton Standard Efficiency 301 = 25 Ton High Efficiency
Digit 7- Major Development Sequence
Digit 8 - Electrical Characteristics
3 = 208-230/60/3 4 = 460/60/3 W = 575/60/3 K = 380/60/3
Digit 9 - Heating Capacity
L = Low Heat M = Medium Heat H = High Heat
Digit 10 - Factory-Installed Options
0 = Packed Stock, No Options A = Downflow Economizer B = Oversized Motor C = Downflow Economizer and Oversized
Motor F = Trane Communications Interface (TCI) G = Downflow Economizer and TCI H = TXV/Face-Split Evaporator J = Oversized Motor and TXV/Face-Split
Evaporator K = Downflow Economizer, Oversized
Motor, and TXV/Face-Split Evaporator L = Downflow Economizer with TXV/Face-
Split Evaporator M = Reheat Coil N = Downflow Economizer and Reheat Coil P = Oversized Motor and Reheat Coil R = Downflow Economizer, Oversized
Motor and Reheat Coil
Digit 11- Minor Design Sequence
Digit 12- Service Digit
13RT-PRC001-EN
(12½, 15 Ton)

General Data

Standard Efficiency
Table GD-1 — General Data
12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity 150,000 182,000
2
(Downflow/Horizontal) 9.6 9.7
EER
1
Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300 ARI Net Cooling Capacity 142,000 174,000 Integrated Part Load Value System Power (KW) 14.79 17.94
Heating Performance
3
4
Heating Models Low High Low High Heating Input (Btuh) 150,000 250,000 250,000 350,000
1st Stage 100,000 175,000 175,000 250,000
Heating Output (Btuh) 122,000 203,000 203,000 284,000
1st Stage 81,000 142,000 142,000 203,000
5
AFUE (%)
(Downflow/Horizontal) 81.0 80.7/79.9 80.7 / 79.9 80.1 / 79.1 Steady State Efficiency (%) 81.0 81.0 81.0 81.0 No. Burners 1 1 No. Stages 2 2 Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS)
6
Outdoor Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375 Face Area (sq ft) 24.18 27.12 Rows/FPI 2/16 3/16
Indoor Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375 Face Area (sq ft) 17.5 17.50 Rows/FPI 2/15 2/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan - Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 10,600 10,200 No. Motors/HP 2/.50 2/.50 Motor RPM 1,100 1,100
Indoor Fan - Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/15 X 15 1/15 X 15 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized)
9
9
Motor Frame Size (Standard/Oversized)
Filters - Type Furnished Throwaway
(No.) Size Recommended
Downflow (2) 20 X 20 X 2, (4) 20 X 25 X 2 (2) 20 X 20 X 2, (4) 20 X 25 X 2 Horizontal (2) 20 X 20 X 2, (4) 20 X 25 X 2 (2) 20 X 20 X 2, (4) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the unitary large equipment certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.
7
YC*150D3,D4,DWL, DK YC*150D3,D4,DWH, DK YC*180B3,B4,BWL, BK YC*180B3,B4,BWH, BK
10.3 10.0
9.2 9.2
3.0/5.0 3.0/5.0
9
1740/3450 1740/3450 145T/145T 145T/145T
8
Throwaway
8
9.3/9.4/Circuit 17.5/9.5/ Circuit
RT-PRC001-EN14
(17½, 20 Ton)
General Data
Standard Efficiency
Table GD-2 — General Data
17½ Ton Downflow and Horizontal Units 20 Ton Downflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity 210,000 242,000
2
EER
1
Nominal CFM / ARI Rated CFM 7,000/5,80 0 8,000/7,000 ARI Net Cooling Capacity 196,000 232,000 Integrated Part Load Value System Power (KW) 20.41 24.42
Heating Performance
3
4
Heating Models Low High Low High Heating Input (Btuh) 250,000 350,000 250,000 400,000
1st Stage 175,000 250,000 175,000 300,000
Heating Output (Btuh) 203,000 284,000 203,000 324,000
1st Stage 142,000 203,000 142,000 243,000
5
AFUE (%)
Downflow/Horizontal 80.7 / 79.9 80.1 / 79.1 80.2 / 81.0 79.8 / 79.7 Steady State Efficiency (%) 81.0 81.0 81.0 81.0 No. Burners 1 1 No. Stages 2 2 Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS)
6
Outdoor Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375 Face Area (sq ft) 27.12 35.3 Rows/FPI 3/16 3/16
Indoor Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375 Face Area (sq ft) 17.50 26.00 Rows/FPI 4/15 2/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan - Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 13,400 14,600 No. Motors/HP 2/ 1.0 2/1.0 Motor RPM 1,125 1,125
Indoor Fan - Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/15 X 15 1/18 X 18 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) Motor RPM (Standard) Motor Frame Size (Standard/Oversized)
Filters - Type Furnished
8
9
9
(No.) Size Recommended Downflow (2) 20 X 2 0 X 2/(4) 20 X 25 X 2) (4) 20 X 20 X 2/(4) 20 X 25 X 2 Horizontal (2) 20 X 20 X 2/(4) 20 X 25 X 2) (8) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)
7
Downflow 21.0/14.3/Circuit 18.9/21.0/Circuit Horizontal 21.5/14.5/Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.
YC*210C3,C4,CWL, CK YC*210C3,C4,CWH, CK YC*240B3,B4,BWL, BK YC*240B3,B4,BWH, BK
9.6 9.5
9.8 9.8
9.4 9.4
5.0/7.5 5.0/7.5
9
3450/3470 3450/3470 56HZ/184T 145T/184T
Throwaway Throwaway
15RT-PRC001-EN
(25 Ton)
General Data
Standard Efficiency
Table GD-3 — General Data
Cooling Performance
Gross Cooling Capacity 290,000
2
EER
1
YC*300B3,B4,BWL, BK YC*300B3,B4,BWH, BK
Nominal CFM / ARI Rated CFM 10,000 / 8,750 ARI Net Cooling Capacity 272,000 Integrated Part Load Value System Power (KW) 28.05
Heating Performance
3
4
Heating Models Low High Heating Input (Btuh) 250,000 400,000
1st Stage 175,000 300,000
Heating Output (Btuh) 203,000 324,00 0
1st Stage 142,000 243,000
5
AFUE (%)
Downflow/Horizontal 80.2/81.0 79.8/79.7 Steady State Efficiency (%) 81.4/81.0 80.8/81.0 No. Burners 1 No. Stages 2 Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4
Compressor
No./Type 2/Scrolls
Sound Rating (BELS)
6
Outdoor Coil - Type Hi-Performance
Tube Size (in.) OD .375 Face Area (sq ft) 36.43 Rows/FPI 2/16
Indoor Coil - Type Hi-Performance
Tube Size (in.) .375 Face Area (sq ft) 26.00 Rows/FPI 3/15 Refrigerant Control Short Orifice Drain Connection No./Size (in.) 1/1.0 0 NPT
Outdoor Fan - Type Propeller
No. Used/Diameter (in.) 2/28 Drive Type/No. Speeds Direct/1 CFM 16,700 No. Motors/HP 2/1.0 Motor RPM 1,125
Indoor Fan - Type FC Centrifugal
No. Used/Diameter (in.) 1/18 X 18 Drive Type/No. Speeds Belt/1 No. Motors 1 Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized)
Filters - Type Furnished
8
9
9
9
(No.) Size Recommended
Downflow (4) 20 X 20 X 2(4) 20 X 25 X 2 Horizontal (8) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)
Downflow Horizontal 17.0/Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. YC*300B model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.
7
25 Ton Downflow and Horizontal Units
9.7
9.8
9.4
7.5/NA 3470/NA 184T/NA
Throwaway
RT-PRC001-EN16
(12½, 15 Ton)
General Data
High Efficiency
Table GD-4 — General Data
12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity 154,000 189,000
2
EER Nominal CFM / ARI Rated CFM 5,000 / 4400 6,000 / 5,300 ARI Net Cooling Capacity 146,000 180,000 Integrated Part Load Value System Power (KW) 12.92
Heating Performance
Heating Models Low High Low High Heating Input (Btuh) 150,000 250,000 250,000 350,000
1st Stage 100,000 175,000 175,000 250,000
Heating Output (Btuh) 122,000 203,000 203,000 284,000
1st Stage 81,000 142,000 142,000 203,000
5
(Downflow/Horizontal) 81.0 / 81.0 80.7 / 79.9 80.7 / 79.9 80.1 / 79.1
AFUE% Steady State Efficiency (%) No. Burners 1 1 1 1 No. Stages 2 2 2 2 Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS) Outdoor Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) OD 0.375 0.375 Face Area (sq ft) 27.12 35.30 Rows/FPI 3/16 3/16
Indoor Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) 0.375 0.375 Face Area (sq ft) 17.50 26.00 Rows/FPI 3/15 3/15 Refrigerant Control Short Orifice Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT
Outdoor Fan - Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 10,400 11,000 No. Motors/HP 2/.50 2/.50 Motor RPM 1100 1100
Indoor Fan - Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/ 15 x 15 1/18 x 18 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0 Motor RPM (Standard/Oversized) 1740/3450 1740/3450 Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T
1
3
4
5
6
YC*151C3,C4,CW YC*181C3,C4,CW
10
11.30
11.5 13.3
10
81.0 81.0 81.0 81.0
9.2 9.2
10
9
11.50
9
15.65
Short Orifice
9
17RT-PRC001-EN
(12½, 15 Ton)
General Data
High Efficiency
Table GD-4 — Continued
12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units
Filters - Type Furnished
(No.) Size Recommended
Downflow (2)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 Horizontal (2)20 X 20 X 2/(4)20 X 25 X 2 (8)20 X 25 X 2
Optional Hot Gas Reheat Coil - Type Hi-Performance Hi-Performance
Tube Size (in.) OD 0.375 0.375 Face Area (sq. ft.) 17.5 26 Rows/FPI 1/16 1/16
Refrigerant Charge (Lbs of R-22)
Standard 15.0/13.8 Optional Hot Gas Reheat Coil 15.3/14.3 27.8/11.4
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. TXV/Face-Split Option (Downflow Only) YCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/12.0.
10. TXV/Face-Split Option (Downflow Only) YCD151C3,4,W (EER):11.3; (System Power kW): 12.92; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0.
*Indicates both downflow and horizontal units.
8
7
/Circuit
YC*151C3,C4,CW YC*181C3,C4,CW
Throwaway Throwaway
10
25.0/13.0
9
RT-PRC001-EN18
(17½, 20, 25 Ton)
General Data
High Efficiency
Table GD-5 — General Data
Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity 220,000 268,000
2
EER Nominal CFM / ARI Rated CFM 7,000 / 6,20 0 8,000 / 7,0 00 10,000/8,750 ARI Net Cooling Capacity 208,000 250,000 Integrated Part Load Value System Power (KW) 18.91 23.58
Heating Performance
Heating Models Low High Low High Low High Heating Input (Btuh) 250,000 350,000 250,000 400,000 250,000 400,000
1st Stage 175,000 250,000 175,000 300,000 175,000 300,000
Heating Output (Btuh) 203,000 284,000 203,000 324,000 203,000 324,000
1st Stage 142,000 203,000 142,000 243,000 142,000 243,000
5
(Downflow/Horizontal) 80.2 / 81.0 79.3 / 79.7 80.2 / 81.0 79.8 / 79.7 80.2/81.0 79.8/79.7
AFUE% Steady State Efficiency (%) No. Burners 1 1 1 1 1 1 No. Stages 2 2 2 2 2 2 Gas Supply Pressure (in. w.c)
Natural or LP ((minimum/maximum) 2.5/14.0 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls 2/Scrolls
Sound Rating (BELS) Outdoor Coil - Type High-Performance High-Performance High Performance
Tube Size (in.) OD 0.375 0.375 0.375 Face Area (sq ft) 35.30 35.30 Rows/FPI 3/16 3/16 3/16
Indoor Coil - Type High-Performance High-Performance High Performance
Tube Size (in.) 0.375 0.375 0.375 Face Area (sq ft) 26.00 26.00 26.00 Rows/FPI 4/15 4/15 4/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT 1/1.0 NPT
Outdoor Fan - Type Propeller Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM 12,800 13,700 13,700 No. Motors/HP 2/1.0 2/ 1.0 2/1.0 Motor RPM 1125 1125 1125
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/18 x 18 1/18 x 18 1/18x18 Drive Type/No. Speeds BELT/1 BELT/1 BELT/1 No. Motors 1 1 1 Motor HP (Standard/Oversized) 5.0/7.5 5.0/7.5 7.5 Motor RPM (Standard/Oversized) 3450/3470 3450/3470 3470 Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T
1
3
4
5
6
17½ Ton 20 Ton 25 Ton Units
YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW
9
11.0 10.6 10.4
9
12.0 11.2 11.0
81.0 81.0 81.0 81.0 81.0 81.0
9.4 9.4 9.4
9
9
9
300,000
278,000
26.73
35.30
Short Orifice
19RT-PRC001-EN
(17½, 20, 25 Ton)
General Data
High Efficiency
Table GD-5 — Continued
Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units
Filters - Type Furnished
(No.) Size Recommended
Downflow (4)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 Horizontal (8)20 X 25 X 2 (8)20 X 25 X 2 (8)20 X 25 X 2
Optional Hot Gas Reheat Coil - Type Hi-Performance
Tube Size (in.) OD 0.375 — Face Area (sq. ft.) 26 — Rows/FPI 1/16
Refrigerant Charge (Lbs of R-22)
Standard 25.7/12.5 21.8/21.8 Optional Hot Gas Reheat Coil 21.3/21.0
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½-20 tons are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. TXV/Face-Split Option (Downflow Only) YCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kW): 23.02; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2
*Indicates both downflow and horizontal units.
8
7
/Circuit
17½ Ton 20 Ton 25 Ton Units
YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW
Throwaway Throwaway Throwaway
9
24.5/24.5
RT-PRC001-EN20
Performance
(12½ Ton)
Data
Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC*150D3, D4, DW, DK
Enter
CFM Bulb 61 67 73 61 6 7 73 61 67 7 3 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
4500
5000
5500
6000
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Dry Entering Wet Bulb
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5 80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6 85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5 90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6 80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2 85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9 90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0 75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9 80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7 85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0 90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0 80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5 85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8 90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0
85 95 105 115
Ambient Temperature
Standard Efficiency
*Indicates both downflow and horizontal units.
21RT-PRC001-EN
Performance
(15, 17½ Ton)
Data
Standard Efficiency
Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*180B3, B4, BW, BK
Enter.
CFM Bulb 61 67 73 6 1 67 73 61 67 7 3 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
5400
6000
6600
7200
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Dry Entering Wet Bulb
75 168.0 133.0 188.0106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2 80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7 85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0 90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0 75 172.0 140.0 190.0 110.0 199.0 74.3 161.0134.0 184.0106.0 195.0 71.7 151.0129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9 80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9 85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0 90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0 75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1 80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6 85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0 90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0 75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0109.0 191.0 71.0 142.0 142.0 170.0 103.0183.0 67.2 80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4 85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0 90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
85 95 105 115
Ambient Temperature
Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase YC*210C3, C4, CW, CK
Enter
CFM Bulb 61 67 73 6 1 67 73 61 67 7 3 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
6300
7000
7700
8400
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
Dry Entering Wet Bulb
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8 80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0 85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0 90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0 75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4 80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0 85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0 90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0 80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0 85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0 90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5 80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0 85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0 90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0
85 95 105 115
Ambient Temperature
RT-PRC001-EN22
Loading...
+ 50 hidden pages