Split System Cooling Condensers
Model CTA 7 1/2 to 15 Tons
Models
CTA
090A***A
120A***A
120B***A
180B***A
September 2007
– 60 HZ
– 60 HZ
– 60 HZ
– 60 HZ
“A” and later Design Sequence
PKG-SVX17A-EN
Notice
Overview of Manual
Note: One copy of this document
ships inside each unit and is customer
property. It must be retained by the
unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By
carefully reviewing the information
within this manual and following the
instructions, the risk of improper
operation and/or component damage
will be minimized.
It is important that periodic maintenance be performed to help assure
trouble free operation. A maintenance
schedule is provided at the end of this
manual. Should equipment failure
occur, contact a qualified service
organization with qualified, experienced HVAC technicians to properly
diagnose and repair this equipment.
NOTICE:
Warnings and Cautions appear at
appropriate sections throughout this
manual. Read these carefully.
WARNING– Indicates a
potentially hazardous situation
which, if not avoided, could
result in death or serious injury.
CAUTION – Indicates a
potentially hazardous situation
which, if not avoided, may result
in minor or moderate injury. It
may also be used to alert against
unsafe practices.
CAUTION – Indicates a situa-
tion that may result in equipment
or property-damage-only accidents.
IMPORTANT NOTE: All phases of this
installation must comply with the
NATIONAL, STATE & LOCAL CODES.
In addition to local codes, the installation must conform with National Electric Code -ANSI/NFPA NO. 70 LATEST
REVISION.
Note: Do Not release refrigerant to the atmosphere! If adding or
removing refrigerant is required, the
service technician must comply with
all federal, state, and local laws.
All products are identified by a multiple-character model number that precisely identifies a particular type of
unit. An explanation of the alphanumeric identification code is provided
below. Its use will enable the owner/
operator, installing contractors, and
service engineers to define the opera
tion, specific components, and other
options for any specific unit.
When ordering replacement parts or
requesting service, be sure to refer to
the specific model number, serial
number, and DL number (if applica
ble) stamped on the unit nameplate.
-
Split System Condensing Model Nomenclature
C T A 0 9 0 A 1 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12
Digits 1,2,3 - Product Type
CTA = Remote Air-Cooled Condenser
Digits 4,5,6 - Nominal Gross
-
Cooling Capacity (MBh)
090 = 090 MBh-used with
3 & 5T SCRH
120 = 120 MBh - used with
7.5 & 10T SCRH
180 = 180 MBh - used with
12 & 15T SCRH
Digits 7 - Major Development
Sequence
A = 1 Refrig Cir.(3, 5, 7.5T SCRH)
B = 2 Refrig Cir. (10, 12, 15T SCRH)
Installation procedures should be performed in the sequence that they
appear in this manual. Do not destroy
or remove the manual from the unit.
The manual should remain weatherprotected with the unit until all instal
lation procedures are complete.
Note: It is not the intention of this
manual to cover all possible varia
tions in systems that may occur or to
provide comprehensive information
concerning every possible contin
gency that may be encountered during an installation. If additional
information is required or if specific
problems arise that are not fully dis
cussed in this manual, contact your
local Sales office.
Note: “Warnings” and “Cautions”
appear at appropriate
places in this manual. Your personal
safety and the proper
operation of this machine require that
you follow them carefully. The Company assumes no liability for installations or servicing performed by
unqualified personnel.
Installation Checklist
An “Installation Checklist” is provided
at the end of the installation section of
this manual. Use the checklist to verify
that all necessary installation proce
dures have been completed. Do not
use the checklist as a substitute for
reading the information contained in
the manual. Read the entire manual
before beginning installation proce
dures.
Unit Inspection
Inspect material carefully for any shipping damage. If damaged, it must be
reported to, and claims made against
the transportation company. Compare
the information that
appears on the unit nameplate with
ordering and submittal
data to insure the proper unit was
shipped. Available power supply must
-
-
-
-
-
be compatible with electrical characteristics specified on component
nameplates. Replace damaged parts
with authorized parts only.
-
Inspection Checklist
To protect against loss due to damage
incurred in transit, complete the following checklist upon receipt of the
unit.
[ ] Inspect individual pieces of the
shipment before accepting the unit.
Check for obvious damage to the
unit or packing material.
[ ] Inspect the unit for concealed dam-
age before it is stored and as soon
as possible after delivery. Con
cealed damage must be reported
within 15 days. If concealed damage is discovered, stop unpacking
the shipment. Do not remove damaged material from the receiving
location. Take photos of the dam
age if possible. The owner must
provide reasonable evidence that
the damage did not occur after
delivery.
[ ] Notify the carrier’s terminal of dam-
age immediately by phone and by
mail. Request an immediate joint
inspection of the damage by the
carrier and the consignee.
[ ] Notify the sales representative and
arrange for repair. Do not repair the
unit until the damage is inspected
by the carrier’s representative.
Initial Leak Test
All CTA units are shipped with a hold-
ing charge of nitrogen in each circuit.
Remove the service access panel(s)
shown in Figures 1 to 4. Locate the
discharge or liquid line gauge ports
for each circuit. Install gauges to
determine if the circuits are still pressurized. If not, the charge has
escaped. Repair as required to obtain
a leak-free circuit.
Lifting Recommendations
Before preparing the unit for lifting,
estimate the approximate center of
gravity for lifting safety. Because of
placement of internal components,
the unit weight may be unevenly dis
tributed. Approximate unit weights
are given in Table 2.
Table 2: Unit and corner weights (lbs)
Model
CTA090A 254 210 59633949
CTA120A
CTA120B
CTA180B 532 447 100 105 124 118
-
Heavy Objects!
Do not use cables (chains or
slings) except as shown. Each of
the cables (chains or slings) used
to lift the unit must be capable of
-
supporting the entire weight of
the unit. Lifting cables (chains or
slings) may not be of the same
length. Adjust as necessary for
even unit lift. Other lifting
arrangements may cause equip
ment or property-only damage.
Failure to properly lift unit could
result in death or serious injury.
See details below.
The crated unit can be moved using a
forklift of suitable capacity. For lifting
the unit, attach lifting straps or slings
securely to the lifting holes at each
corner. Use spreader bars to protect
the unit casing from damage. Test lift
the unit to determine proper balance
and stability.
Ship
Max.
Max.
325 281 62855777
WARNING
Corner Weights
Net
#1#2#3#4
-
-
CAUTION
Equipment Damage!
Use spreader bars to prevent lifting straps from damaging the
unit. Install bars between lifting
straps. Failure to properly lift unit
may result in crushing unit cabi
net or damaging unit finish.
-
PKG-SVX17A-EN9
Installation
Clearances
Provide enough space around the unit
to allow unrestricted access to all service points. Refer to Figure 1 through
Figure 4 for unit dimensions and minimum required service and free air
clearances. Observe the following
points to insure proper unit operation.
A. Do not install the unit under a low
overhang. Condenser discharge must
not be restricted. See Notes in Figure
1 through Figure 4.
NOTICE: Do not obstruct condenser
discharge air. This can result in warm
air recirculation through the coil.
B. Do not locate the unit in a position
where runoff water can fall into the
fan discharge openings.
C. Condenser intake air is supplied
from three or four sides of the unit.
Adhere to the minimum required
clearances given in Figure 1 through
Figure 4.
Unit Mounting
Rooftop Mounting: If the unit will be
roof mounted, determine for certain
that the structure is strong enough to
support the unit and any required
accessories. Unit weights are given in
Table 2. The unit should be elevated
on a level, field fabricated four-inch
steel or wood 4" x 4" mounting frame.
Complete the frame and secure it into
position before lifting the unit to the
roof. The mounting frame must sup
port a minimum of three of the unit’s
four sides and should span roof supports to distribute the load on the
roof.
-
Figure 5 Roof Mounted Unit
WARNING
Structural Failure!
Ensure that the roof structure
supports are strong enough to
support the weight of the unit
and any accessories. Failure to do
this could result in death or seri
ous injury due to structural failure and could seriously damage
the unit and the building.
Ground Level Mounting
“For ground level installation, the unit
base should be adequately supported
and hold the unit near level. The
installation must meet the guidelines
set forth in local codes.” The support
should extend two inches beyond the
unit base channels at all points. The
unit and support must be isolated
from any adjacent structure to prevent
possible noise or vibration problems.
Any ground level location must com
ply with required clearances given in
Figure 1 through Figure 4.
-
-
Holes must be made in the structure
to run refrigerant lines. For the major
ity of ground-level installations, the
holes can be made in the header that
rests on top of the foundation. Alter
natively, these holes may also be
made in the foundation itself. On roofmounted units, refrigerant lines
should enter the building as close to
the unit as possible; preferably within
three to four inches of the refrigerant
connection on the unit, plus a six-inch
(long radius) 90 degree "L" entering
the building (See Figure 5).
Refrigerant Piping Guidelines
A. Maximum recommended line
lengths: (per circuit)
Route refrigerant piping for minimum
linear length, minimum number of
bends and fittings (no reducers) and
minimum amount of line exposed to
outdoor ambients.
C. Recommended line sizes:
CTA090, 120A (single circuit)
CTA120B, 180B (dual circuit)
Discharge line - 7/8 inch sealed type L
refrigerant tubing.
Liquid line - 1/2 inch sealed type L
refrigerant tubing.
-
-
10PKG-SVX17A-EN
Installation
Note: Insulate all refrigerant piping
and connections.
Refrigerant Piping Procedures
(Outdoor Units)
Each CTA unit ships with a holding
charge of dry nitrogen. The nitrogen
should be removed and the entire sys
tem evacuated (at the proper time) to
avoid possible contamination.
1. Remove the service access panel.
2. Locate the liquid and discharge
lines. Check that the piping connection stubs on the valves (Figure 6)
line up properly with the holes in
the unit cabinet.
Figure 6
4. Unbraze the tube seal caps to reveal
the line braze connections.
WARNING:
Hazardous Pressures!
Coil has a nitrogen holding
-
charge. Do not remove seal caps
by heating the caps while coil is
under pressure. Depress the
gauge port valve cores to gradu
ally relieve nitrogen holding
charge. Remove valve cores
before removing the tubing seal
caps. Failure to properly relieve
pressure could result in death or
serious injury.
CAUTION:
Equipment Damage!
Do not remove the seal caps from
refrigerant connections until pre
pared to braze refrigerant lines to
the connections. Excessive exposure to atmosphere may allow
moisture or dirt to contaminate
the system, damaging valve seals
and causing ice formation in sys
tem components.
above the maximum recom
mended unit test pressure as
specified in applicable unit literature. Failure to properly regulate
pressure could result in a violent
explosion, which could result in
death or serious injury or equip
ment or property-only-damage.
CAUTION:
-
Equipment Damage!
Wet-wrap all valves and protect
painted surfaces from excessive
heat. Heat can damage system
components and the unit finish.
6. Shut off nitrogen supply.
7. Shut off the manifold valve for the
line that is connected to the dis
charge line gauge port.
Figure 7
-
-
-
-
-
5. Cut, fit and braze tubing, starting at
the outdoor unit and work toward
the indoor unit.
Note: Use long radius bells for all 90
degree bends.
All brazing should be done using a 2
to 3 psig dry nitrogen purge flowing
3. Locate the gauge ports on the discharge and liquid lines. Depress the
valve core to release the nitrogen
from the unit.
through the pipe being brazed (Figure
6).
WARNING:
Note: If nitrogen is not released from
the unit, there is a leak in the system.
Locate the leak and repair before pro
ceeding with the installation.
PKG-SVX17A-EN11
Hazardous Pressures!
When using dry nitrogen cylin-
-
ders for pressurizing units for
leak testing, always provide a
pressure regulator on the cylinder
to prevent excessively high unit
pressures. Never pressurize unit
Refrigerant Piping Procedure
(Indoor Unit)
Once liquid and discharge lines are
complete to the refrigerant connec
tions on the indoor unit, depress the
gauge port valve cores on the suction
and discharge lines to gradually
relieve nitrogen holding charge.
-
Installation
WARNING:
Hazardous Pressures!
Coil has a nitrogen holding
charge. Do not remove seal caps
by heating the caps while coil is
under pressure. Depress the
gauge port valve cores to gradually relieve nitrogen holding
charge. Remove valve cores
before removing the tubing seal
caps. Failure to properly relieve
pressure could result in death or
serious injury.
1. Remove both seal caps from the
indoor unit connection stubs.
CAUTION:
Equipment Damage!
Do not remove the seal caps from
refrigerant connections until pre
pared to braze refrigerant lines to
the connections. Excessive exposure to atmosphere may allow
moisture or dirt to contaminate
the system, damaging valve seals
and causing ice formation in sys
tem components.
2. Turn nitrogen supply on. Nitrogen
enters through liquid line gauge
port.
WARNING:
Hazard of Explosion and Deadly
Gases!
Never solder, braze or weld on
refrigerant lines or any unit com
ponents that are above atmospheric pressure or where
refrigerant may be present.
Always remove refrigerant by fol
lowing the guidelines established by the EPA Federal Clean
Air Act or other state or local
codes as appropriate. After refrig
erant removal, use dry nitrogen to
bring system back to atmospheric
pressure before opening system
for repairs. Mixtures of refrigerants and air under pressure may
become combustible in the presence of an ignition source leading
to an explosion. Excessive heat
from soldering, brazing or welding with refrigerant vapors
present can form highly toxic
gases and extremely corrosive
acids. Failure to follow all proper
safe refrigerant handling prac
tices could result in death or serious injury.
3. Braze the liquid line connections.
4. Open the gauge port on the discharge line and then braze the discharge line to the connection stub.
Nitrogen will bleed out the open
gauge port on the discharge line.
5. Shut off nitrogen supply.
-
Leak Check
After the brazing operation of the outdoor and indoor refrigerant lines is
complete, check the field brazed con
nections for leaks. Pressurize the system through the gauge port with dry
-
nitrogen to 200 psi. Use soap bubbles
or other leak-checking methods to
ensure that all field joints are leak
free. If not, release pressure, repair
and repeat the leak test.
System Evacuation
1. After completion of leak check,
replace suction, liquid and dis
charge valve cores, and evacuate
the system.
2. Attach appropriate hoses from the
-
manifold gauge to suction and discharge line gauge ports.
Note: Unnecessary switching of hoses
can be avoided and complete evacua
-
tion of lines leading to a sealed system can be accomplished with
manifold center hose and connecting
branch hose to cylinder of R-410A and
-
vacuum pump.
3. Attach center hose of manifold
gauges to the vacuum pump.
4. Evacuate the system to hold a 350
micron vacuum.
5. Close off the valve to the vacuum
pump and observe the micron
gauge. If gauge pressure rises
above 500 microns in one (1)
minute, evacuation is incomplete or
the system has a leak.
6. If vacuum gauge does not rise
-
-
-
above 500 microns in one (1)
minute, the evacuation should be
complete.
7. With vacuum pump and micron
gauge blanked off, open the valve
on R-410A cylinder and allow refrigerant pressure to build up to 100
psig.
8. Close valve on the R-410A supply
cylinder. Close valves on the manifold gauge. Set and remove the
refrigerant charging hoses from the
discharge and suction gauge ports.
9. Leak test the entire system. Using
proper procedures and caution,
repair any leaks found and repeat
the leak test.
Refrigerant Charging Procedure
If charging by weight, refer to refrigerant charges that are provided in Table
3. If additional refrigerant is needed
because of length of line, calculate the
requirements using Table 4. Charge
by weight through the gauge port on
the suction line in the indoor unit.
When charging is complete, replace
the cap on the gauge port.
Insulating and Isolating
Refrigerant Lines
Insulate the entire discharge line with
refrigerant piping insulation. Also
-
insulate any portion of the liquid line
exposed to temperature extremes.
Insulate and isolate liquid and dis
charge lines from each other. Isolate
refrigerant lines from the structure
and any ductwork.
Note: To prevent possible noise or
vibration, be certain to isolate refrigerant lines from the building.
-
12PKG-SVX17A-EN
Installation
Table 3: CTA Refrigerant Charge
Model
CTA090A
w/SCRH030
CTA090A
w/SCRH050
CTA120A
w/SCRH075
CTA120B
w/SCRH100
CTA180B
w/SCRH120
CTA180B
w/SCRH150
* Sufficient operating charge for listed unit
and 33 feet of nominally sized refrigerant
piping.
Refrigerant Charge
(R-410A)*
18.1 lbs
19.9 lbs
20.8 lbs
11.9 lbs
(Ckt. #1 & #2)
16.8 lbs. (Ckt. #1)
16.0 lbs. (Ckt. #2)
17.5 lbs. (Ckt. #1)
16.9 lbs. (Ckt. #2)
Table 4: Additional Refrigerant
Tubing SizesAdditional
Discharge Liquid
7/8"1/2"15 ft.1.3 l b s
7/8"1/2"25 ft.2.2 lbs
7/8"1/2"32 ft.2.8 lbs
7/8"1/2"40 ft.3.5 lbs
Note: Amounts shown are based on 0.087
lbs of refrigerant per foot of 7/8" and 1/2"
lines.
Tubing
Length
Additional
Refrig.
Note: For tubing over 40 feet, calculate
the additional refrigerant needed,
based on notes above.
Gaseous Charging
This procedure is accomplished with
the unit operating. Electrical connec
tions must be complete. Do not proceed until the system is ready to
operate.
Procedure
1. Connect R-410A drum with gauge
manifold to the gauge ports (pres
sure taps) on the compressor discharge and suction lines (Figure 7).
Note: On the CTA units, the service
access panel must be installed when
the unit is running and being charged.
WARNING:
Hazardous Energy Sources!
Use extreme caution while servicing the unit when the control box
access panel is removed and
power is applied to the unit. Fail
ure to observe all safety precautions could result in death or
serious injury.
2. Turn on power to the unit. Allow the
system to run for five to ten minutes
to stabilize operating conditions.
3. Measure airflow across the indoor
coil. Compare the measurements
with the fan performance data in the
Data/Submittal.
4. Check suction line superheat and
condenser sub-cooling to ensure
the unit is operating properly.
5. Disconnect all power to the unit.
WARNING:
Hazardous Voltage
w/Capacitors!
Disconnect all electrical power,
including remote disconnects and
discharge all motor start/run ca
pacitors before servicing. Follow
proper lockout/tagout procedures
to ensure the power cannot be in
advertently energized. Verify with
an appropriate voltmeter that all
capacitors have discharged. Fail
ure to diconnect power and discharge capacitors before
servicing could result in death or
serious injury.
Note: For additional information
regarding the safe discharge of
capacitors, see PROD-SVB06A-EN
or PROD-SVB06A-FR.
6. Remove the charging system from
the unit and replace all access pan
els.
-
-
Electrical Wiring
CTA field wiring consists of providing
power supply to the unit, installing the
system indoor thermostat and provid
ing low voltage system interconnecting wiring. Access to electrical
connection locations is shown in Fig
ures 1 through 4.
Unit Power Supply
The installer must provide line voltage
circuit(s) to the unit main power termi
nals as shown by the unit wiring diagrams in Figures 9 and 10 on page 15.
Power supply must include a discon
nect switch in a location convenient to
the unit. Ground the unit according to
local codes and provide flexible conduit if codes require and/or if vibration
transmission may cause noise prob
lems.
CAUTION:
Use Copper Conductors Only!
Unit terminals are not designed to
accept other types of conductors.
Failure to use copper conductors
may result in equipment damage.
CAUTION:
All wiring must comply with applicable local and national NEC
codes. Type and location of dis
connect switches must comply
with all applicable codes.
WARNING:
Ground Wire!
All field-installed wiring must be
completed by qualified personnel.
All field-installed wiring must
comply with NEC and applicable
local codes. Failure to follow this
instruction could result in death
or serious injuries.
WARNING:
Grounding Required!
Follow proper local and state electrical code on requirements for
grounding. Failure to follow code
-
could result in death or serious in
jury
-
-
-
-
-
-
-
PKG-SVX17A-EN13
Figure 8: Typical Field Wiring
Note:
1. Wiring shown with dashed lines is to
be furnished and installed by the cus
tomer. All customer supplied wiring
must be copper only and must conform to NEC and local electrical codes.
Codes may require line of sight between disconnect switch and unit.
Hazardous Voltage w/Capacitors!
Disconnect all electrical power,
including remote disconnects and
discharge all motor start/run ca
pacitors before servicing. Follow
proper lockout/tagout procedures
to ensure the power cannot be in
advertently energized. Verify with
an appropriate voltmeter that all
capacitors have discharged. Fail
ure to diconnect power and discharge capacitors before
servicing could result in death or
serious injury.
Note: For additional information
regarding the safe discharge of
capacitors, see PROD-SVB06A-EN
or PROD-SVB06A-FR.
Determine proper wire sizes and unit
protective fusing requirements by
referring to the unit nameplate. Field
wiring diagrams for accessories
are shipped with the accessory.
-
-
-
14PKG-SVX17A-EN
Field Wiring
PKG-SVX17A-EN15
Wiring
16PKG-SVX17A-EN
Wiring
PKG-SVX17A-EN17
Wiring
18PKG-SVX17A-EN
Wiring
PKG-SVX17A-EN19
Refrigeration
Diagram
Figure 11: Typical Split System Cooling Diagram
20PKG-SVX17A-EN
System
Pre-Start Procedure
Installation Checklist
Complete this checklist once the unit
is installed to verify that all recommended procedures have been
accomplished before starting the system. Do not operate the system until
all items covered by this checklist are
complete.
[ ] Inspect unit location for proper
required service clearances.
[ ] Inspect unit location for proper free
air clearances.
[ ] Inspect unit location for secure,
level mounting position.
Refrigerant Piping
[ ] Performed initial leak test?
[ ] Connected properly sized and con-
structed liquid and discharge lines
to the connection stubs at both the
indoor and outdoor units?
[ ] Insulated the entire discharge line?
[ ] Insulated portions of liquid line
exposed to extremes in tempera
ture?
-
Electrical Wiring
WARNING:
Hazardous Voltage
w/Capacitors!
Disconnect all electrical power,
including remote disconnects and
discharge all motor start/run capacitors before servicing. Follow
proper lockout/tagout procedures
to ensure the power cannot be inadvertently energized. Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure to diconnect power and discharge capacitors before
servicing could result in death or
serious injury.
Note: For additional information
regarding the safe discharge of
capacitors, see PROD-SVB06AEN or PROD-SVB06A-FR.
[ ] Provided unit power wiring (with
disconnect) to proper terminals in
the unit control section?
[ ] Installed system indoor thermo-
stat?
[ ] Evacuated each refrigerant circuit
to 350 microns?
[ ] Charged each circuit with proper
amount of R-410A?
PKG-SVX17A-EN21
[ ] Installed system low voltage inter-
connecting wiring to proper terminals of outdoor unit, indoor unit
and system thermostat?
System
Pre-Start Procedure
Unit Start-Up
Once the unit is properly installed and
pre-start procedures
are complete, start the unit by turning
the System Switch on the indoor thermostat to either HEAT, COOL or AUTO.
The system should operate normally.
Sequence of Operation
General
Operation of the system cooling (and
optional heating) cycles is controlled
by the position of the system switch
on the room thermostat. Once the
system switch is placed in either the
HEAT or COOL position, unit opera
tion is automatic. The optional automatic changeover thermostat, when
in the AUTO position, automatically
changes to heat or cool with sufficient
room temperature change.
Evaporator Fan (Indoor Supply
Air)
The evaporator fan is controlled by an
ON/AUTO switch on the room thermostat. With the switch positioned at
AUTO and the system operating in
the cooling mode, fan operation coin
cides with the cooling run cycles. If
the system is equipped with heat and
is operating in the heating mode
while the fan switch is at AUTO, fan
operation coincides with the heating
run cycles. When the fan switch is
positioned at ON, fan operation is
continuous.
-
Cooling Mode
When the room thermostat system
switch is positioned at COOL and the
fan switch is at AUTO, the condenser
fan relay energizes on a call for cool
ing. When the contacts of the condenser fan relay close, operation of
the condenser fan begins. The evaporator fan contactor also energizes on a
call for cooling and initiates evapora
tor fan operation.
On units with dual circuits, the second
stage of cooling is initiated as a result
of the 2-stage thermostat calling for
additional cooling.
-
-
-
22PKG-SVX17A-EN
Maintenance
WARNING:
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual
could result in exposure to electri
cal, mechanical or other potential
safety hazards. Always refer to
the safety warnings provided
throughout this manual concern
ing these procedures. When possible, disconnect all electrical
power including remote disconnects before servicing. Follow
proper lockout/tagout procedures
to ensure the power can not be in
advertently energized. When necessary to work with live electrical
components, have a qualified licensed electrician or other individual who has been trained in
handling live electrical components perform these tasks. Failure
to follow all of the recommended
safety warnings provided, could
result in death or serious injury.
-
Maintenance
Perform all of the indicated maintenance procedures at the
intervals scheduled. This will prolong
the life of the unit and reduce the possibility of costly equipment failure.
Monthly
Conduct the following maintenance
inspections once per month.
WARNING:
Hazardous Voltage w/Capacitors!
Disconnect all electrical power,
including remote disconnects and
discharge all motor start/run ca-
pacitors before servicing. Follow
proper lockout/tagout procedures
to ensure the power cannot be inadvertently energized. Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure to diconnect power and discharge capacitors before
servicing could result in death or
serious injury.
Note: For additional information
regarding the safe discharge of
capacitors, see PROD-SVB06A-EN
or PROD-SVB06A-FR.
1. Inspect air filters and clean if neces-
sary.
2. Check unit wiring to ensure all con-
nections are tight and that the wiring insulation is intact.
3. Check drain pans and condensate
piping to insure they are free of ob
stacles.
ing mode, check the suction and discharge pressures. Record these
readings on the “Maintenance
Log.”
7. Observe indoor fan operation and
correct any unusual or excessive vi
bration. Clean blower wheels as
needed.
Annually (Cooling Season)
The following maintenance procedures must be performed at the beginning of each cooling season to insure
efficient unit operation.
1. Perform all of the monthly maintenance inspections.
2. With the unit operating, check unit
superheat and record the reading in
the Maintenance Log.
3. Remove any accumulation of dust
and/or dirt from the unit casing.
4. Remove corrosion from any surface
and repaint. Check the gasket
around the control panel door to in
sure it fits correctly and is in good
condition to prevent water leakage.
5. Inspect the evaporator fan belt. If it
is worn or frayed, replace it.
6. Inspect the control panel wiring to
insure that all connections are tight
and that the insulation is intact.
7. Check refrigerant piping and fittings
for leaks.
-
-
-
4. Manually rotate the indoor fan to insure proper operation.
5. Inspect the evaporator and condenser coils for dirt and debris. If the
coils appear dirty, clean them.
Note: Perform each inspection once per month (during cooling season) while unit is operating.
24PKG-SVX17A-EN
Warranty
CTA
Warranty Information
Standard Warranty
The standard split system cooling condenser warranty is Trane’s partsonly warranty, running 12-months from startup, not to exceed 18-
months from shipment.
Extended Warranty
The optional extended warranty is a second through fifth year warranty.
The time starts at the end of standard 1-year coverage through the fifth
year.
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be
ordered prior to start-up.
PKG-SVX17A-EN25
Trane
A business of American Standard Companies
www.trane.com
For more information, contact your local Trane
office or e-mail us at comfort@trane.com
Literature Order Number PKG-SVX17A-EN
DateSeptember 2007
SupersedesSS-SVN11A-EN October 2004
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.