Trane PKGP-PRC001-EN User Manual

Packaged Heat Pumps
Voyager™ 12½ to 20 Tons — 60 Hz
September 2004
PKGP-PRC001-EN

Introduction

Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionalize this design concept.
The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.
Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager.
Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer­aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your needs.
It’s Hard To Stop A Trane.
®
PKGP-PRC0 01-EN© 2004 American Standard Inc. All rights reserved
Contents
Introduction
Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
Performance Data
Cooling Performance Fan Performance Heating Performance
Controls
Electric Power
Dimension and Weights
2
4
9
10
11
12
14
14 17
22
26
27
38
PKGP-PRC0 01-EN
Mechanical Specifications
48
3

Features and Benefits

Factory Installed Options
• Black Epoxy Pre-Coated Coils
• High Efficiency Motors
• High Pressure Cutout
• Hinged Access Doors
• Powered or Unpowered Convenience Outlet
• Supply and/or Return Air Smoke Detector
• Through the Base Electrical with Circuit Breaker
• Through the Base Electrical With Disconnect Switch
• Through the Base Utilities Access
• Two-Inch Pleated Filters
Factory or Field Installed Options
Clogged Filter/Fan Failure Switch
Differential Pressure Switches
Discharge Air Sensing Kit
Downflow – Economizer
Electric Heaters
Frostat
LonTalk® Communications Interface
Oversized Motors
Reference or Comparative Enthalpy
Tool-less Hail Guards
Trane Communications Interface (TCI)
Field Installed Options
CO
Sensing
2
Digital Display Zone Sensor
Dual Thermistor Remote Zone Sensor
High Static Drive
Manual Outside Air Damper
Motorized Outside Air Dampers
Powered Exhaust
Downflow – Roof Curb
Horizontal – Economizer
Remote Potentiometer
Ventilation Override Accessory
Zone Sensors
4
PKGP-PRC0 01-EN
Features and Benefits
Easy to Install, Service and Maintain
Because today’s owners are very cost­conscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering:
Quality and Reliability
ReliaTel™ Controls (LCI-R)
ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature.
ReliaTel™
Quality and Reliability are enhanced through ReliaTel control and logic:
—prevents the unit from short cycling,
considerably improving compressor life.
—ensures that the compressor will run
for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.
Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them.
The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically. — The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems.
Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation.
ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.
Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.
The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling with Electric Heat, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.
PKGP-PRC0 01-EN
5
Features and Benefits
Outstanding Standard and Optional Components
Black Epoxy Pre-Coated Coils
The pre-coated coils are an economical option for protection in mildly corrosive environments.
Cabinet Integrity
For added water integrity, Voyager has a raised 1 return of the downflow units to prevent water from blowing into the ductwork.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication.
CO
The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO As the CO damper modulates to meet the CO space ventilation requirements. The CO sensor kit is available as a field installed accessory.
Colored And Numbered Wiring
Save time and money tracing wires and diagnosing the unit.
Compressors
Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models.
1
/8" lip around the supply and
Sensing
2
(Carbon Dioxide) in the air.
2
levels increase, the outside air
2
2
2
Condenser Coil
Voyager boasts a patent-pending 1+1+1 condenser coil, permanently gapped for easy cleaning.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor should be utilized with ReliaTel™ controls.
Discharge Air Sensing Kit
Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel Options Module.
Downflow And Horizontal Economizers
The economizers come with three control options — dry bulb is standard, enthalpy and differential enthalpy are optional.
Dual Thermistor Remote Zone Sensor
This sensor will reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.
Factory Built Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.
Fresh Air
0 - 25% manual or 0 - 50% motorized outside air hoods are available.
High Static Drive Accessory
Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.
Hinged Access Doors
These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.
LonTalk® Communications Interface
The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls.
Power Exhaust Option
This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Quick-Access Panels
Remove three or fewer screws for access to the standardized internal components and wiring.
Quick-Adjust Idler Arm
With the Quick-Adjust Idler Arm, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.
6
PKGP-PRC0 01-EN
Features and Benefits
Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.
Sloped Drain Pans
Standard on every unit.
Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager.
Due to standardized components throughout the Voyager line, contractors/ owners can stock fewer parts.
Supply and/or Return Air Smoke Detector
With this option installed, if smoke is
detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used
with certain models.
Tool-less Hail Guards
Tool-less, hail protection quality coil
guards shall be either factory or field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.
Va riTra c
When Trane’s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac.
Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.
Zone Sensors
Available in programmable, automatic and manual styles.
Rigorous Testing
The fan and idler arm assembly designs have been tested to over 300,000 cycles each. Our combined cycle testing is now over 7,000,000 cycles.
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity.
Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress.
We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.
Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
Voyager units incorporate either a one piece top or the Trane-Tite-Top (T part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.
3
). Each
Trane Communication Interface (TCI)
Available factory or field installed. This module when applied with the ReliaTel™ easily interfaces with Trane’s Integrated Comfort
TM
System.
PKGP-PRC0 01-EN
VariTrac™
7
Features and Benefits
Easy to Install and Service
Conversionless Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation.
Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.
Easy Access Low Voltage Terminal Board
Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire. This is another cost and time saving installation feature.
Low Voltage Connections
The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.
Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.
Powered or Unpowered Convenience Outlet
This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered. This option is available on all downflow models.
Single Point Power
A single electrical connection powers the unit.
Single Side Service
Single side service is standard on all units.
Through the Base Electrical with Circuit Breaker
This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. This option is available on all downflow models.
Through the Base Electrical with Disconnect Switch
Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. This option is available on all downflow models.
Through the Base Utilities Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.
Factory Installed Options
A wide variety of Factory Installed Options (FIOPs) are available.
Added Efficiency
Airflow
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.
High Efficiency Motors
This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.
U-shaped Airflow
U-shaped airflow allows for improved static capabilities.
Low Ambient Cooling
Cooling capabilities down to 0°F as standard.
Oversized Motors
Factory or field installed oversized motors available for high static applications.
One of our Finest Assets:
Trane Sales Representatives are a Support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and much more
Voyager has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its U-shaped airflow performance is outstanding.
8
PKGP-PRC0 01-EN

Application Considerations

Application of this product should be within the cataloged airflow and cooling considerations.
Low Ambient Cooling
This Voyager line features, as standard, low ambient cooling down to 0°F. Contact your local Trane Representative for more assistance with low ambient cooling applications.
Barometric Relief
This product line offers an optional barometric relief damper included in the downflow economizer accessory. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.
NOTE: THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED.
PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZATION.
Power Exhaust Accessory
The power exhaust accessory is available on all downflow units. This accessory can be field installed and will assist in relieving building pressurization.
Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel.
Unit Pitch
These units have sloped condensate drain pans. Units must be installed level, any unit slope must be toward access side of unit.
PKGP-PRC0 01-EN
9

Selection Procedures

Cooling Capacity
Step 1
Calculate the building’s total and sensible cooling loads at design conditions. Use the Tranecalculation form or any other standard accepted method.
Step 2
Given the following building requirements:
A
Electrical Characteristics: 460/60/3
B
Summer Design Conditions: Entering Evaporator Coil: 80 DB/ 67 WB Outdoor Ambient: 95 DB
C
Total Cooling Load: 172 MBh
D
Sensible Cooling Load: 122 MBh
E
Airflow: 6000 cfm
F
External Static Pressure: .50 in. w.g.
G
Rooftop - downflow configuration.
H
Accessories Economizer Supplementary Electric Heat
I
Heating Capacity 88 MBh 460 volt/3 phase Electric Supplemental Heat - at 6000 cfm
Size the equipment using Table PD-3. As a starting point, a rough determination of the size of the unit must be made. This selection will then be confirmed after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size. 172 MBh/12 MBh = 14.33 (approx. 15 tons.)
Step 3
Table PD-3 shows that a WCD180B4 has a gross cooling capacity of 183.0 MBh and 129.0 MBh sensible capacity at 95 degree ambient and 6000 cfm with 80 DB/67 WB air entering the evaporator.
To Find Capacity at Intermediate Conditions
When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.
Step 4
Verify that there will be enough capacity by determining net capacity. In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor cfm and static pressure. To determine the total unit static pressure, add the following:
External Static: 0.50 in.
Standard Filter 1 in: 0.11 in. (from table PD-13)
Economizer Return Air: 0.04 in. (from table PD-13)
Electric Heater Size 18 kW: .06 in.
Total Static Pressure: .71 in.
Note: The Evaporator Fan Performance Table PD-7 has already accounted for the pressure drop for standard filters and wet coils.
Therefore, the actual Total Static Pressure is .71 - .11 = .60. With 6000 cfm and .60 inches, Table PD-7 shows 2.66 Bhp.
The note below Table PD-7 gives a formula to calculate Fan Motor Heat:
3.15 x bhp = MBh
3.15 x 2.66 = 8.38 MBh
Now subtracting the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity =
183-8.38=170.62
Net Sensible Cooling Capacity=
129-8.38=120.62
Step 5
If the performance will not meet the required load of the building, try a selection at the next higher size unit.
Heating Capacity
Step 1
Calculate the building heating load using the Trane calculation form or other standard accepted method.
Step 2
Size the equipment using Table PD-16 to match the heating loads at design conditions.
A
Total Heating Load: 88 MBh
B
Outdoor Ambient (Winter) 17 DB
C
Indoor Return Temperature: 70 DB
D
Airflow: 6000 Cfm
Use the integrated portion of Table PD-16 for the WCD180B4 to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 45 MBh.
Step 3
Because 45 MBh is less than the building’s required heating capacity at winter design conditions, a supplementary heater must be selected.
88 MBh - 45 MBh = 43 MBh
From Table PD-20, at 480 volts, the 18 kW Heater will be adequate to do the job.
18 kW 61 MBh
From Table ED-3 select heater AYDHTRK418A (18 kW 460/60/3).
10
PKGP-PRC0 01-EN

Model Number Description

Packaged Heat Pump Unit Model Nomenclature
W C D 150 C 3 0 0 B A
12 3 456 7 8 9 10 11 12
Digits 1,2 Product Type
WC = Heat Pump, Packaged WF = With Factory Installed Options
Digit 3 - Airflow Configuration
D = Downflow H = Horizontal
Digits 4, 5, 6 - Nominal Gross Cooling Capacity (MBh)
150 = 12½ ton 180 = 15 ton 240 = 20 ton
Digit 7- Major Development Sequence
Digit 8 - Electrical Characteristics
3 = 208-230/60/3 4 = 460/60/3 W = 575/60/3
Digits 9, 10 - Factory Installed Options
00 = Packed Stock, No Options 0A= Factory Installed Downflow
Economizer 0B = Oversize Motor 0C = Downflow Economizer and Oversize
Motor 0F = Trane Communications Interface (TCI) 0G = Downflow Economizer and TCI
Digit 11- Minor Design Sequence
Digit 12- Service Digit
PKGP-PRC0 01-EN
11

General Data

(12½ Ton)
Table GD-1 — General Data
12½ Ton Downflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity 152,00 152,000
2
EER Nominal CFM / ARI Rated CFM 4,400 / 4,400 4,400 / 4,400 ARI Net Cooling Capacity 144,000 144,000 Integrated Part Load Value System Power KW 15.16 15.16
Heating Performance
High Temp. Btuh Rating 135,000 132,000
System Power KW/COP 12.76/3.10 12.48/3.10
Low Temp. Btuh Rating 78,000 72,000
System Power KW/COP 10.88/2.1 10.55/2.0
HSPF (Btu/Watts-hr)
Compressor
No./Type 2/Scroll 2/Scroll
ARI Sound Rating (BELS)
Outdoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375 Face Area (sq ft) 23.96 23.96 Rows/FPI 2/16 2/16 Refrigerant Control Expansion Valve Expansion Valve
Indoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375 Face Area (sq ft) 15.83 17.50 Rows/FPI 2/15 2/15 Refrigerant Control Capillary Tube Capillary Tube Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan — Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 Drive Type/No. Speeds Direct/1 Direct/1 CFM 10,800 10,800 No. Motors/HP 2/.50 2/.50 Motor RPM 1,110 1,110
Indoor Fan — Type FC Centrifugal FC Centrifugal
No. Used 1 1 Diameter x Width (in.) 15 x 15 15 x 15 Drive Type/No. Speeds Belt/1 Belt/1 No. Motors 1 1 Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0 Motor RPM (Standard/Oversized) 1,740/3,450 1,740/3,450 Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T
Filters — Type Furnished
(No.) Size Recommended (in.) (2) 20 x 20 x 2 (2) 20 x 20 x 2
Refrigerant Charge (Lbs of R-22)
Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.
1
3
1
4
6
5
WCD150B3, B4, BW WCH150B3, B4, BW
9.5 9.5
9.9 9.9
9.2 9.2
Throwaway Throwaway
(4) 20 x 25 x 2 (4) 20 x 25 x 2
11.1/11.4 Circuit 11.5/11.8 Circuit
*Indicates both downflow and horizontal units.
12
PKGP-PRC0 01-EN
General Data
(15, 20 Ton)
Table GD-2 — General Data
15 Ton Downflow and Horizontal Units 20 Ton Downflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity 180,000 233,000 237,000
2
EER Nominal CFM / ARI Rated CFM 6,000 / 5,300 8,000 / 8,000 8,000/7,000 ARI Net Cooling Capacity 168,000 222,000 224,000 Integrated Part Load Value System Power KW 17.50 22.2 21.3
Heating Performance
High Temp. Btuh Rating 166,000 208,000 204,000
System Power KW/COP 15.69/3.10 19.65/3.10 19.29/3.10
Low Temp. Btuh Rating 88,000 118,000 118,000
System Power KW/COP 13.12/2.1 18.75/2.0 17.29/2.00
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll
Sound Rating (BELS)
Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375 .375 Face Area (sq ft) 27.12 35.3 35.3 Rows/FPI 3/16 3/16 3/16 Refrigerant Control Expansion Valve Expansion Valve Expansion Valve
Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance
Tube Size (in.) .375 .375 .375 Face Area (sq ft) 17.50 26.00 26.00 Rows/FPI 3/15 3/15 3/15 Refrigerant Control Short Orifice Capillary Tube Capillary Tube Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT
Outdoor Fan — Type Propeller Propeller Propeller
No. Used/Diameter (in.) 2/26 2/28 2/28 Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM 10,200 13,800 13,800 No. Motors/HP 2/.50 2/1.0 2/1.0 Motor RPM 1,100 1,125 1,125
Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 11 Diameter x Width (in.) 15 x 15 18 x 18 18 x 18 Drive Type/No. Speeds Belt/1 Belt/1 Belt/1 No. Motors 1 1 1 Motor HP (Standard/Oversized) 3.0/5.0 5.0/7.5 5.0/7.5 Motor RPM (Standard/Oversized) 1,740/3,450 3,450/3,450 3,450/3,450 Motor Frame Size (Standard/Oversized) 145T/145T 184T/184T 184T/184T
Filters — Type Furnished
(No.) Size Recommended (in.) (2) 20 x 20 x 2 (4) 20 x 20 x 2 (8) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)
Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.
1
3
1
4
6
5
WC*180B3, B4, BW WCD240B3, B4, BW WCH240B3, B4, BW
9.6 9.8 10.5
10.0 9.7 10.3
9.2 9.4 9.4
Throwaway Throwaway Throwaway
(4) 20 x 25 x 2 (4) 20 x 25 x 2
19.9/9.9 Circuit 22.0/21.0 Circuit 22.0/21.0 Circut
*Indicates both downflow and horizontal units.
PKGP-PRC0 01-EN
13

Performance Data

(12½ Ton)
Table PD-1 — Gross Cooling Capacities (MBh) 12½ Ton Downflow Three Phase WCD150B
Enter.
CFM Bulb 61 67 73 6 1 67 73 61 6 7 73 6 1 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
4500 80 141.0 134.0 154.0 105.0 159.0 78.3 130.0 128.0 149.0 104.0 161.0 77.4 119.0 119.0 138.0 98.3 157.0 74.3 109.0 109.0 125.0 91.8 148.0 69.6
5000 80 145.0 141.0 156.0 108.0 160.0 79.2 134.0 134.0 152.0 109.0 162.0 79.5 124.0 124.0 141.0 104.0 160.0 77.2 114.0 114.0 128.0 97.5 151.0 72.9
5500 80 147.0 147.0 157.0 111.0 162.0 80.5 139.0 139.0 154.0 113.0 163.0 80.9 129.0 129.0 144.0 110.0 161.0 79.9 118.0 118.0 131.0 103.0 154.0 75.9
6000 80 150.0 150.0 158.0 113.0 162.0 81.2 144.0 144.0 156.0 117.0 164.0 82.1 133.0 133.0 147.0 115.0 162.0 82.1 122.0 122.0 133.0 108.0 156.0 78.7
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Dry Entering Wet Bulb (F)
75 140.0 113.0 153.0 90.8 158.0 57.9 128.0 106.0 149.0 83.3 160.0 56.3 116.0 99.8 137.0 83.3 157.0 53.5 104.0 93.3 124.0 77.1 148.0 48.9
85 146.0 146.0 155.0 124.0 160.0 94.3 139.0 139.0 150.0 125.0 162.0 95.8 129.0 129.0 138.0 119.0 158.0 94.9 119.0 119.0 125.0 113.0 148.0 90.2 90 153.0 153.0 156.0 143.0 162.0 111.0 148.0 148.0 151.0 145.0 163.0 114.0 140.0 140.0 139.0 139.0 158.0 114.0 130.0 130.0 129.0 129.0 148.0 111.0 75 143.0 119.0 154.0 93.5 159.0 59.0 132.0 113.0 152.0 87.2 161.0 57.4 119.0 106.0 141.0 88.6 159.0 54.8 107.0 99.5 127.0 82.3 151.0 50.9
85 150.0 150.0 157.0 128.0 162.0 97.0 145.0 145.0 153.0 131.0 164.0 98.4 135.0 135.0 142.0 127.0 160.0 98.9 125.0 125.0 129.0 120.0 152.0 95.3 90 156.0 156.0 158.0 148.0 164.0 112.0 153.0 153.0 155.0 153.0 165.0 118.0 146.0 146.0 146.0 146.0 161.0 120.0 136.0 136.0 136.0 136.0 152.0 118.0 75 145.0 124.0 155.0 96.1 160.0 60.0 135.0 119.0 153.0 90.7 162.0 58.5 122.0 112.0 144.0 93.8 160.0 55.7 110.0 105.0 130.0 87.4 154.0 52.4
85 153.0 153.0 158.0 132.0 164.0 97.4 149.0 149.0 155.0 137.0 165.0 101.0 140.0 140.0 145.0 134.0 162.0 102.0 130.0 130.0 132.0 128.0 154.0 100.0 90 159.0 159.0 160.0 152.0 166.0 115.0 157.0 157.0 157.0 157.0 166.0 121.0 151.0 151.0 151.0 151.0 163.0 125.0 141.0 141.0 141.0 141.0 154.0 124.0 75 147.0 128.0 156.0 98.4 160.0 60.0 138.0 125.0 155.0 92.7 163.0 59.5 125.0 118.0 147.0 88.6 161.0 57.2 112.0 111.0 132.0 92.4 155.0 52.5
85 156.0 156.0 159.0 135.0 164.0 98.4 153.0 153.0 157.0 142.0 166.0 103.0 145.0 145.0 148.0 141.0 163.0 106.0 134.0 134.0 134.0 134.0 156.0 104.0 90 160.0 160.0 161.0 156.0 166.0 116.0 160.0 160.0 160.0 160.0 167.0 123.0 155.0 155.0 155.0 155.0 165.0 129.0 146.0 146.0 146.0 146.0 157.0 130.0
85 95 105 115
Ambient Temperature (F)
Table PD-2 — Gross Cooling Capacities (MBh) 12½ Ton Horizontal Three Phase WCH150B
Enter.
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
4500 80 141.0 134.0 154.0 105.0 160.0 78.3 130.0 128.0 149.0 104.0 161.0 77.5 119.0 119.0 138.0 98.4 157.0 74.3 109.0 109.0 124.0 91.9 148.0 69.6
5000 80 145.0 142.0 156.0 109.0 162.0 79.9 134.0 134.0 152.0 109.0 162.0 79.6 124.0 124.0 141.0 104.0 159.0 77.3 114.0 114.0 128.0 97.7 151.0 72.9
5500 80 147.0 147.0 157.0 111.0 162.0 80.8 139.0 139.0 154.0 114.0 163.0 81.0 129.0 129.0 144.0 110.0 161.0 80.1 118.0 118.0 130.0 103.0 154.0 76.0
6000 80 150.0 150.0 158.0 114.0 163.0 81.5 144.0 144.0 156.0 118.0 164.0 82.1 133.0 133.0 147.0 115.0 162.0 82.3 122.0 122.0 133.0 109.0 155.0 78.8
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Dry Entering Wet Bulb (F)
75 140.0 113.0 153.0 91.1 159.0 58.0 128.0 106.0 149.0 83.3 160.0 56.2 116.0 100.0 137.0 82.9 157.0 53.5 104.0 93.5 124.0 76.7 147.0 48.9
85 146.0 146.0 155.0 124.0 161.0 94.3 139.0 139.0 149.0 125.0 162.0 96.0 129.0 129.0 138.0 119.0 158.0 95.0 119.0 119.0 125.0 113.0 148.0 90.2 90 153.0 153.0 156.0 143.0 163.0 110.0 148.0 148.0 151.0 145.0 163.0 114.0 140.0 140.0 139.0 139.0 158.0 115.0 130.0 130.0 129.0 129.0 148.0 111.0 75 143.0 119.0 154.0 93.3 160.0 59.0 132.0 113.0 151.0 86.8 161.0 57.4 119.0 106.0 141.0 88.2 159.0 54.7 107.0 99.8 127.0 81.8 151.0 50.8
85 150.0 150.0 157.0 129.0 164.0 96.6 145.0 145.0 152.0 131.0 164.0 98.7 135.0 135.0 142.0 127.0 160.0 99.1 125.0 125.0 129.0 121.0 151.0 95.5 90 156.0 156.0 158.0 149.0 164.0 112.0 153.0 153.0 153.0 153.0 165.0 118.0 146.0 146.0 146.0 146.0 161.0 120.0 136.0 136.0 136.0 136.0 151.0 118.0 75 145.0 124.0 156.0 95.9 160.0 60.1 135.0 119.0 153.0 90.8 162.0 58.5 122.0 112.0 144.0 93.2 160.0 55.8 110.0 106.0 130.0 86.9 153.0 52.3
85 154.0 154.0 158.0 133.0 164.0 97.9 149.0 149.0 155.0 137.0 165.0 101.0 140.0 140.0 145.0 135.0 162.0 103.0 130.0 130.0 132.0 128.0 154.0 100.0 90 159.0 159.0 160.0 153.0 166.0 115.0 157.0 157.0 157.0 157.0 167.0 121.0 151.0 151.0 151.0 151.0 163.0 125.0 141.0 141.0 141.0 141.0 154.0 124.0 75 147.0 129.0 157.0 98.2 161.0 60.6 138.0 125.0 155.0 92.9 163.0 59.5 125.0 118.0 146.0 88.7 161.0 57.1 111.0 111.0 132.0 91.8 155.0 52.5
85 156.0 156.0 160.0 136.0 165.0 99.1 153.0 153.0 157.0 143.0 166.0 103.0 145.0 145.0 148.0 142.0 163.0 106.0 134.0 134.0 134.0 134.0 156.0 105.0 90 161.0 161.0 162.0 157.0 167.0 117.0 160.0 160.0 160.0 160.0 168.0 124.0 155.0 155.0 155.0 155.0 164.0 130.0 146.0 146.0 146.0 146.0 156.0 130.0
85 95 105 115
Ambient Temperature (F)
14
PKGP-PRC0 01-EN
Performance Data
(15 Ton)
Table PD-3 — Gross Cooling Capacities (MBh) 15 Ton Downflow and Horizontal Three Phase WC*180B
CFM Dry Entering Wet Bulb (F)
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
5400
6000
6600
7200
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Enter.
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
75 162.3 130.3 184.5 103.3 194.1 71.1 150.5 124.1 176.5 99.0 190.3 68.4 137.5 117.3 163.6 93.0 185.5 65.5 124.8 110.8 149.4 94.8 176.1 61.2 80 163.8 154.2 185.1 126.5 195.7 95.8 152.7 148.2 176.7 122.2 191.5 92.1 139.3 139.3 163.8 116.2 186.0 88.8 129.4 129.4 150.0 109.7 176.4 84.3 85 170.5 170.5 185.5 148.7 197.4 115.8 161.6 161.6 177.1 145.3 192.1 113.7 151.3 151.3 164.3 139.4 186.7 111.8 141.5 141.5 151.0 133.1 176.7 107.3 90 181.0 181.0 186.7 170.9 201.0 136.9 173.5 173.5 178.5 168.4 194.9 135.7 163.7 163.7 166.9 163.2 187.1 133.8 153.8 153.8 153.7 153.7 177.0 130.2 75 167.0 137.5 187.0 106.7 195.3 71.7 154.8 131.2 179.7 102.8 191.7 69.1 141.4 124.3 167.8 97.3 187.5 66.4 128.5 117.7 153.8 90.9 178.8 62.4 80 169.2 163.7 187.6 131.0 197.2 98.1 156.0 156.0 180.0 128.0 193.2 95.1 145.5 145.5 168.0 122.6 188.3 91.8 135.3 135.3 154.1 116.1 179.2 87.6 85 177.5 177.5 188.5 154.8 199.6 118.6 168.9 168.9 180.6 152.9 194.1 116.7 158.3 158.3 168.8 147.9 188.7 116.2 148.1 148.1 155.5 141.6 179.6 112.5 90 186.6 186.6 190.1 178.4 202.6 140.1 180.0 180.0 182.7 177.5 197.3 140.3 171.1 171.1 171.0 171.0 189.9 139.5 161.1 161.1 161.2 161.2 180.0 136.8 75 170.8 144.2 188.9 110.1 196.2 72.6 158.6 137.9 182.2 106.4 192.7 70.2 144.9 131.0 171.3 101.3 188.8 67.3 131.8 124.4 157.2 95.0 180.7 63.4 80 173.6 172.6 189.7 134.9 198.3 99.3 162.1 162.1 182.7 133.3 194.4 97.9 151.1 151.1 171.5 128.5 190.0 94.7 140.6 140.6 157.6 122.2 181.2 90.5 85 182.5 182.5 191.0 160.1 200.5 120.2 175.0 175.0 183.6 159.7 195.9 119.6 164.6 164.6 172.7 155.9 190.8 119.7 154.0 154.0 159.6 149.9 181.6 117.1 90 190.6 190.6 192.9 184.7 202.3 140.8 184.9 184.9 186.2 185.4 199.1 144.1 177.1 177.1 177.0 177.0 192.1 144.4 167.4 167.4 167.3 167.3 182.6 142.8 75 174.0 150.5 190.0 112.2 196.9 73.6 162.1 144.4 184.2 109.7 193.5 71.2 148.1 137.4 174.0 105.0 189.9 68.2 134.8 130.7 160.2 98.8 182.1 64.2 80 176.7 176.7 191.4 138.3 199.1 100.2 167.6 167.6 184.8 137.8 195.7 99.2 156.3 156.3 174.3 134.1 190.7 97.2 145.4 145.4 160.6 128.0 182.9 93.4 85 186.4 186.4 192.9 164.7 201.5 121.7 179.6 179.6 186.0 165.5 197.7 122.4 170.1 170.1 175.9 163.3 192.4 122.8 159.4 159.4 163.2 157.7 183.5 121.0 90 193.8 193.8 195.1 190.1 203.3 143.0 188.6 188.6 188.5 188.5 200.6 147.4 181.9 181.9 181.7 181.7 193.9 148.7 172.6 172.6 172.5 172.5 184.6 148.2
85 95 105 115
Ambient Temperature ( F)
*Indicates both downflow and horizontal units.
PKGP-PRC0 01-EN
15
Performance Data
(20 Ton)
Table PD-4 — Gross Cooling Capacities (MBh) 20 Ton Downflow Three Phase WCD240B
CFM Dry Entering Wet Bulb (F)
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
7200 85 229.0 229.0 236.0 197.0 249.0 148.0 220.0 220.0 231.0 202.0 249.0 153.0 205.0 205.0 215.0 196.0 242.0 153.0 189.0 189.0 194.0 186.0 226.0 146.0
8000 85 234.0 234.0 241.0 207.0 250.0 150.0 228.0 228.0 235.0 213.0 252.0 158.0 215.0 215.0 221.0 210.0 244.0 159.0 197.0 197.0 197.0 197.0 230.0 155.0
8800 85 238.0 238.0 244.0 212.0 252.0 152.0 234.0 234.0 239.0 223.0 253.0 161.0 222.0 222.0 226.0 223.0 247.0 165.0 205.0 205.0 205.0 205.0 233.0 164.0
9600 85 241.0 241.0 245.0 222.0 253.0 155.0 239.0 239.0 242.0 231.0 255.0 165.0 229.0 229.0 229.0 229.0 249.0 170.0 212.0 212.0 212.0 212.0 236.0 171.0
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Enter.
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
75 212.0 177.0 233.0 137.0 243.0 89.7 198.0 173.0 228.0 133.0 244.0 87.3 179.0 164.0 211.0 130.0 239.0 83.1 160.0 154.0 189.0 115.0 225.0 76.8 80 219.0 218.0 234.0 165.0 246.0 122.0 204.0 204.0 229.0 168.0 247.0 123.0 188.0 188.0 212.0 160.0 240.0 118.0 172.0 172.0 190.0 150.0 225.0 112.0
90 238.0 238.0 238.0 227.0 252.0 174.0 234.0 234.0 233.0 233.0 252.0 183.0 222.0 222.0 222.0 222.0 242.0 186.0 206.0 206.0 206.0 206.0 227.0 181.0 75 218.0 193.0 237.0 144.0 244.0 91.2 204.0 185.0 232.0 139.0 246.0 89.1 184.0 175.0 216.0 131.0 242.0 85.0 162.0 162.0 193.0 128.0 229.0 78.8 80 224.0 224.0 239.0 173.0 247.0 123.0 213.0 213.0 233.0 176.0 249.0 126.0 196.0 196.0 217.0 170.0 243.0 124.0 180.0 180.0 195.0 160.0 230.0 117.0
90 242.0 242.0 245.0 238.0 253.0 178.0 240.0 240.0 240.0 240.0 254.0 190.0 231.0 231.0 231.0 231.0 246.0 195.0 216.0 216.0 216.0 216.0 232.0 193.0 75 223.0 201.0 238.0 148.0 245.0 93.4 209.0 196.0 235.0 145.0 248.0 90.6 189.0 186.0 220.0 138.0 244.0 86.8 168.0 168.0 196.0 136.0 232.0 80.6 80 229.0 229.0 241.0 177.0 248.0 139.0 220.0 220.0 236.0 184.0 250.0 128.0 204.0 204.0 221.0 180.0 246.0 129.0 186.0 186.0 199.0 170.0 233.0 122.0
90 245.0 245.0 247.0 245.0 255.0 181.0 245.0 245.0 245.0 245.0 256.0 195.0 238.0 238.0 238.0 238.0 249.0 203.0 224.0 224.0 224.0 224.0 236.0 205.0 75 226.0 208.0 241.0 151.0 246.0 94.2 214.0 206.0 236.0 148.0 249.0 91.4 191.0 191.0 223.0 144.0 245.0 88.6 174.0 174.0 199.0 143.0 235.0 82.4 80 232.0 232.0 243.0 185.0 250.0 126.0 226.0 226.0 238.0 190.0 251.0 115.0 211.0 211.0 225.0 189.0 247.0 123.0 193.0 193.0 203.0 179.0 235.0 127.0
90 248.0 248.0 247.0 247.0 256.0 184.0 248.0 248.0 248.0 248.0 258.0 200.0 243.0 243.0 243.0 243.0 252.0 210.0 231.0 231.0 231.0 231.0 239.0 215.0
85 95 105 115
Ambient Temperature (F)
Table PD-5 — Gross Cooling Capacities (MBh) 20 Ton Horizontal Three Phase WCD240B
CFM Dry Entering Wet Bulb (F)
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
7200
8000
8800
9600
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Enter.
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
75 217.0 181.0 238.0 140.0 248.0 91.4 202.0 177.0 233.0 136.0 249.0 88.9 183.0 167.0 215.0 132.0 244.0 84.7 163.0 157.0 192.0 117.0 229.0 78.3 80 224.0 223.0 239.0 168.0 250.0 124.0 208.0 208.0 233.0 171.0 251.0 126.0 192.0 192.0 216.0 163.0 245.0 121.0 175.0 175.0 194.0 153.0 229.0 114.0 85 233.0 233.0 241.0 201.0 253.0 151.0 224.0 224.0 235.0 206.0 254.0 156.0 209.0 209.0 219.0 200.0 246.0 156.0 192.0 192.0 198.0 190.0 230.0 149.0 90 242.0 242.0 242.0 230.0 256.0 177.0 238.0 238.0 238.0 238.0 257.0 186.0 226.0 226.0 226.0 226.0 247.0 189.0210.0 210.0210.0 210.0 231.0 185.0
75 223.0 197.0 241.0 147.0 249.0 93.5 208.0 188.0 236.0 142.0 251.0 90.8 188.0 178.0 220.0 134.0 247.0 86.6 165.0 165.0 196.0 130.0 233.0 80.3 80 228.0 228.0 244.0 176.0 252.0 126.0 217.0 217.0 237.0 180.0 254.0 128.0 200.0 200.0 221.0 174.0 248.0 126.0 183.0 183.0 199.0 163.0 234.0 119.0 85 238.0 238.0 246.0 211.0 255.0 153.0 233.0 233.0 240.0 217.0 256.0 161.0 219.0 219.0 225.0 214.0 249.0 163.0 201.0 201.0 201.0 201.0 234.0 158.0 90 246.0 246.0 250.0 243.0 258.0 181.0 245.0245.0 245.0 245.0 259.0194.0 235.0235.0 235.0 235.0251.0 199.0 220.0220.0220.0 220.0 236.0 197.0 75 228.0 205.0 243.0 151.0 250.0 95.2 213.0 200.0 239.0 147.0 252.0 92.3 193.0 189.0 224.0 140.0 249.0 88.5 172.0 172.0 200.0 138.0 237.0 82.1 80 233.0 233.0 245.0 181.0 253.0 142.0 224.0 224.0 240.0 187.0 255.0 131.0 208.0 208.0 225.0 183.0 250.0 131.0 190.0 190.0 203.0 173.0 237.0 124.0 85 242.0 242.0 248.0 216.0 256.0 155.0 239.0 239.0 243.0 227.0 258.0 165.0 227.0 227.0 230.0 227.0 252.0 169.0 209.0 209.0 209.0 209.0 238.0 167.0 90 249.0 249.0 252.0 250.0 260.0 184.0 249.0249.0 249.0 249.0 261.0 199.0242.0242.0 242.0 242.0 254.0 207.0 228.0 228.0 228.0 228.0 240.0 208.0
75 231.0 212.0 245.0 153.0 251.0 96.0 218.0 210.0 241.0 151.0 253.0 93.1 195.0 195.0 227.0 146.0 250.0 90.3 177.0 177.0 203.0 146.0 239.0 84.0 80 237.0 237.0 247.0 188.0 254.0 128.0 230.0 230.0 243.0 194.0 256.0 117.0 215.0 215.0 229.0 193.0 251.0 125.0 196.0 196.0 207.0 183.0 240.0 130.0 85 245.0 245.0 249.0 226.0 258.0 158.0 243.0 243.0 246.0 236.0 260.0 168.0 233.0 233.0 233.0 233.0 253.0 173.0 216.0 216.0 216.0 216.0 241.0 175.0 90 253.0 253.0 252.0 252.0 261.0 187.0 253.0253.0 253.0253.0 263.0 204.0 247.0 247.0 247.0 247.0 256.0214.0 235.0 235.0 235.0 235.0 244.0 219.0
85 95 105 115
Ambient Temperature (F)
16
PKGP-PRC0 01-EN
Loading...
+ 36 hidden pages