Note: For specific dimensional and weight information, refer to the unit s ubmittals. The
dimensions and weights in this ma nual are appro ximate. Trane has a policy of continuous
product and product data improvement and reserves the right to change design and
specifications without notice.
1. Size the air-handling unit based on airflow through the cooling coil (see Table 1). The unique
fin design of T rane coils enables cooling coil selections at velocities in excess of 625 fpm with
no moisture carryover. The coil moisture carryover curves from tested data are built into the
T rane Official Product Selection System (the T OPSS™ program). Use this system to select coils.
2. Choose the coil section (see Table 2). Unit size, coil type, and coil rows determine the minimum
coil section size required.
3. Select a filter type and check face velocities (see Table 3). The maximum recommended face
velocity for pleated media, permanent, bag, and 12-inch cartridge filters is 625 fpm; for
throwaway and HE PA filters, it is 500 fpm.
Note: If selecting an outdoor unit with an inlet hood, verify airflow limitations using Table 4.
4. Design the basic air-handling system.
5. Estimate system static pressure requirements and select a fan (see Table 5 and Table 6).
6. Total the overall air-handling unit dimensions and weights using Table 7 and Table 8.
Note: If selecting an outdoor unit, include external piping cabinet weight and dimensions. S ee
Table 7 and Table 8.
7. Select a control system. Factory-mounted, -wired, and -tested end devices, starters, VFDs, and
direct-digital, interoperable controllers are available to minimize construction cycles and jobsite coordination.
8. Contact your local Trane sales office to order an air-handling system or to ask questions.
Table 1. Size the air handler based on airflow thro ugh the cooling coil
Coil Type Unit Size3468101214
1/2-inch
unit
5/8-inch
unit
1-inch unit
1/2-inch
modified
5/8-inch
modified
1-inch
modified
2
Area (ft
Area (ft2)2.504.005.337.319.1911.8113.13
Area (ft
Area (ft2)1.742.782.784.956.389.3810.42
Area (ft
Area (ft2)1.672.672.674.886.139.0010.00
)2.924.516.117.999.9812.3013.65
Qty-Size1-20 x 211-20 x 32.501-26.25 x 33.50 1-28.75 x 401-28.75 x 50 1-32.50 x 54.50 1-32.5 x 60.50
Qty-Size1-18 x 201-18 x 321-24 x 321-27 x 391-27 x 491-31.50 x 541-31.50 x 60
Back inlet hood1 side inlet hood2 side inlet hoodsSingle inlet hood
6 CLCH-PRC016-EN
Table 5. Select a fan for unit sizes 3-30
Nominal Airflow
Airflow @ 625 fpm
Unit Size3468101214172122252630
Fan size/type9-in FC 10-in FC 12-in FC 12-in FC 15-in FC 18-in FC 18-in FC 20-in FC 22-in FC 22-in FC 22-in FC 22-in FC 25-in FC
Fan name9FA10FA12FA12FA15FA18FA18FA20FA22FA22FA22FA22FA25FA
Max TSP/rpm4/2250 4.5/2100 5/1900 5/1900 5/1600 4/1215 4/1215 4/1050 3.5/950 3.5/950 3.5/950 3.5/9504/850
Motor hp (ODP) 0.75-30.75-50.75-51-51-7.51-7.51-7.51.5-202-202-203-203-203-20
Outlet area (ft
Fan size/type9-6-in FC 9-in FC 10-in FC 10-in FC 12-in FC 15-in FC 15-in FC 18-in FC 20-in FC 20-in FC 20-in FC 20-in FC 22-in FC
Fan name5FA9FA10FA10FA12FA15FA15FA18FA20FA20FA20FA20FA22FA
Max TSP/rpm4.5/2250 4/2250 4.5/2100 4.5/2100 5/1900 5/1600 5/1600 4/1215 4/1050 4/1050 4/1050 4/1050 3.5/950
Motor hp (ODP) 0.75-30.75-30.75-51-51-51-7.51-7.51.5-7.52-202-203-203-203-20
Outlet area (ft2) 0.600.841.031.031.462.052.052.884.384.384.384.385.54
Low Pressure
Fan size/type9-4-in FC 9-6-in FC 9-in FC 9-in FC 10-in FC 12-in FC 12-in FC 15-in FC 18-in FC 18-in FC 18-in FC 18-in FC 20-in FC
Fan name4FA5FA9FA9FA10FA12FA12FA15FA18FA18FA18FA18FA20FA
Max TSP/rpm4.5/2250 4.5/2250 4/2250 4/2250 4.5/2100 5/1900 5/1900 5/1600 4/1215 4/1215 4/1215 4/1215 4/1050
Motor hp (ODP) 0.75-30.75-30.75-31-31-51-51-51.5-7.52-7.52-7.53-7.53-7.53-20
Outlet area (ft
Fan size/type9-in FC 10-in FC 12-in FC 12-in FC 15-in FC 18-in FC 18-in FC 20-in FC 22-in FC 22-in FC 22-in FC 22-in FC 25-in FC
Fan name9FB10FB12FB12FB15FB18FB18FB20FB22FB22FB22FB22FB25FB
FC Housed Fan
Max TSP/rpm5/2900 6/2525 6/2115 6/2115 6/1720 6/1500 6/1500 6/1330 5.5/1200 6/1200 6/1200 6/1200 6/1025
Motor hp (ODP) 0.75-30.75-5 0.75-7.5 1-7.51-101-151-151.5-202-202-203-253-253-30
Outlet area (ft2) 0.851.041.461.462.052.882.884.385.545.545.545.546.94
Fan size/type9-6-in FC 9-in FC 10-in FC 10-in FC 12-in FC 15-in FC 15-in FC 18-in FC 20-in FC 20-in FC 20-in FC 20-in FC 22-in FC
Fan name5FB9FB10FB10FB12FB15FB15FB18FB20FB20FB20FB20FB22FB
Max TSP/rpm6.5/2900 6/2900 6.5/2525 6.5/2525 6/2115 6/1720 6/1720 6/1500 6/1330 6/1330 6/1330 6/1330 6/1200
Motor hp (ODP) 0.75-30.75-5 0.75-7.5 1-7.51-101-101-101.5-152-202-203-253-253-30
Outlet area (ft
High Pressure
Fan size/type9-4-in FC 9-6-in FC 9-in FC 9-in FC 10-in FC 12-in FC 12-in FC 15-in FC 18-in FC 18-in FC 18-in FC 18-in FC 20-in FC
Fan name4FB5FB9FB9FB10FB12FB12FB15FB18FB18FB18FB18FB20FB
Max TSP/rpm7/2900 6.5/2900 6/2900 6/2900 6.5/2525 6/2115 6/2115 6/1720 6/1500 6/1500 6/1500 6/1500 6/1330
Motor hp (ODP) 0.75-30.75-50.75-51-51-7.51-101-101.5-102-152-153-153-153-25
Outlet area (ft2) 0.500.600.840.841.031.461.462.052.882.882.882.884.38
1
Note:
Nominal airflow is based on 500 fpm through a nominal coil (i.e. 500xunit size 8=4000 cfm). 2Airflow@625 fpm through the flat filter (maximum
Fan size/type9-in BC 10-in BC 12-in AF 12-in AF 15-in AF 18-in AF 18-in AF 20-in AF 22-in AF 22-in AF 22-in AF 22-in AF 25-in AF
Fan name9BA10BA12AA12AA15AA18AA18AA20AA22AA22AA22AA22AA25AA
Max TSP/rpm6.5/4375 5/4070 8/3700 8/3700 7/2900 6.5/2450 6.5/2450 7/2300 6/1900 6/1900 6/1900 6/1900 6/1650
Motor hp (ODP) 0.75-30.75-3 0.75-7.5 1-7.51-101-101-101.5-152-152-153-153-153-20
Outlet area (ft
Fan size/type9-in BC 10-in BC 10-in BC 12-in AF 15-in AF 15-in AF 18-in AF 20-in AF 20-in AF 20-in AF 20-in AF 22-in AF
Fan name9BA10BA10BA12AA15AA15AA18AA20AA20AA20AA20AA22AA
Max TSP/rpm6/4375 5.5/4070 5.5/4070 8/3700 7/2900 7/2900 6.5/2450 6.5/2300 6.5/2300 6.5/2300 6.5/2300 6/1900
Motor hp (ODP)0.75-30.75-31-31-7.51-101-101.5-102-152-153-153-153-15
Outlet area (ft2)0.851.031.031.462.052.052.884.384.384.384.385.54
Low Pressure
Fan size/type9-in BC 9-in BC 10-in BC 12-in AF 12-in AF 15-in AF 18-in AF 18-in AF 18-in AF 18-in AF 20-in AF
Fan name9BA9BA10BA12AA12AA15AA18AA18AA18AA18AA20AA
Max TSP/rpm6.5/4375 6.5/4375 5.5/4070 8/3700 8/3700 7/2900 6.5/2450 6.5/2450 6.5/2450 6.5/2450 6.5/2300
Motor hp (ODP)0.75-31-31-31-7.51-7.51.5-102-102-103-103-103-15
Outlet area (ft
Fan size/type9-in BC 10-in BC 12-in AF 12-in AF 15-in AF 18-in AF 18-in AF 20-in AF 22-in AF 22-in AF 22-in AF 22-in AF 25-in AF
Fan name9BB10BB12AB12AB15AB18AB18AB20AB22AB22AB22AB22AB25AB
AF Housed Fan
Max TSP/rpm8/5000 8/4650 8/4350 8/4350 9/3500 7.5/3100 7.5/3100 7.5/2750 8/2500 8/2500 9/2500 9/2500 9/2200
Motor hp (ODP) 0.75-50.75-5 0.75-7.51-101-151-151-151.5-202-252-253-303-303-40
Outlet area (ft2) 0.851.031.461.462.052.882.884.385.545.545.545.546.94
Fan size/type9-in BC 10-in BC 10-in BC 12-in AF 15-in AF 15-in AF 18-in AF 20-in AF 20-in AF 20-in AF 20-in AF 22-in AF
Fan name9BB10BB10BB12AB15AB15AB18AB20AB20AB20AB20AB22AB
Max TSP/rpm8/5000 7.5/4650 7.5/4650 9/4350 9/3500 9/3500 9/3100 9.5/2750 9.5/2750 10/2750 10/2750 9/2500
Motor hp (ODP)0.75-50.75-51-51-101-151-151.5-202-252-253-303-303-30
Outlet area (ft
High Pressure
Fan size/type9-in BC 9-in BC 10-in BC 12-in AF 12-in AF 15-in AF 18-in AF 18-in AF 18-in AF 18-in AF 20-in AF
Fan name9BB9BB10BB12AB12AB15AB18AB18AB18AB18AB20AB
Max TSP/rpm8/5000 8/5000 7.5/4650 9/4350 9/4350 9/3500 9.5/3100 9.5/3100 9.5/3100 9.5/3100 10/2750
Motor hp (ODP)0.75-51-51-51-101-101.5-152-202-203-203-203-30
Outlet area (ft2)0.840.841.031.461.462.052.882.882.882.884.38