Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improper ly installed, adjusted or alt er ed equipment b y an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
October 2012
CLCH-SVX07C-EN
X-39641152010
Warnings, Cautions and Notices
Warnings, Cautions and Notices.
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provide to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situ ations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.
ATTENTION:
appropriate sections throughout this literature. Read
these carefully:
WARNING
CAUTION
NOTICE:
Warnings, Cautions and Notices appear at
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
s
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
Note that warnings,
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the oz one layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment. T rane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow r equirements f or
field wiring installat i on a nd grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servi cing this unit, technicians
MUST put on all P ersonal Protectiv e Equipment (PPE)
recommended for the work being undertaken.
AL WAYS r efer to appropr iate MSDS sheets and OSHA
guidelines for proper PPE.
•When work ing with or ar ound hazar dous c hemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of arc or flash, tec hnicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failur e to f ollow r ecommendations could resul t in death
or serious injury.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
The United States Environmental Protection Agency (EPA)
believes that molds and bacteria inside buildings have the
potential to cause health problems in sensitive
individuals. If specified, Trane provides ultraviolet lights
(UV-C) as a factory-engineered and installed option in
select commercial air handling products for the purpose of
reducing microbiological growth (mold and bacteria)
within the equipment. When factory provided, polymer
materials that are susceptible to deterioration by the UV-C
light will be substituted or shielded from direct expo sure
to the light. In addition, UV-C radiation can damage human
tissue, namely eyes and skin. To reduce the potential for
inadvertent exposure to the lights by operating and
maintenance personnel, electrical interlocks that
automatically disconnect power to the lights are provided
at all unit entry points to equipment where lights are
located.
Warnings, Cautions and Notices
WARNING
Equipment Damage F rom Ultra violet (UV)
Lights!
Trane does not recommend field installa tion of
ultraviolet lights in its air handling equipment for the
intended purpose of improving indoor air quality. High
intensity C-band ultra v io let light is known to severely
damage polymer (plastic) materials and poses a
personal safety risk to anyone exposed to the light
without proper personal protective equipment (could
cause damage to eyes and skin). Polymer materials
commonly found in HVAC equipment that may be
susceptible include insulation on electrical wiring, fan
belts, thermal insulation, various fasteners and
bushings. Degradation of these materials can result in
serious damage to the equipment.
Trane accepts no responsibility for the performance or
operation of our air handling equipment in which
ultraviolet devices were installed outside of the Trane
factory.
Connecting the operator display
Setting up the operator display
Calibrating the operator display
Adjusting brightness and contrast
External communications port
Use this manual to install, star tup, operate, and maintain
the Performance Climate Changer™ air handler. Carefully
review the procedures discussed in this manual to
minimize installation and startup difficulties.
Nameplate
Each Performance air handler section includes one or
more nameplate/label (see Figure 1), which i dentifies the
Figure 1. Performance air handler section nameplate
type of section and functional components, customer
tagging information, the unit serial number, the unit order
number, the build-section position for installation, and the
unit model number.
Note: The unit serial number and order number is
required when ordering parts or requesting service
for a Trane air handler.
6 CLCH-SVX07C-EN
General Information
General Information
Operating Environment
The Performance Climate Changer™ air handler is a
central station air handler for indoor and outdoor
applications. When considering the placement of the air
handler, it is important to consider the operating
environment. The acceptable ambient temperature range
for unit operation is -40ºF to 140ºF (-40ºC to 60ºC).
For heating applications, a special motor may be required
to withstand the higher temperatures. Motors with Class B
insulation are acceptable for ambient temperatures up to
104º F, while motors with Class F insulation can withstand
ambient temperatures to +140º F (60º C).
Note: Units with UL approval have a maximum ambient
temperature requirement of 104ºF. The customer
should provide adequate freeze protection for the
coils. See “Routi ne Maintenanc e” on page 121 for
more information.
Unit Description
The Performance Climate Changer air handler is designed
for a variety of controlled-air applications. The basic unit
consists of a fan, heating and/or coolin g coils, filters, and
dampers.
Trane air handlers ship as complete assemblies or in subassemblies if shipping splits are required. Some assembly
is required when the unit ships in subassemblies.
A wide variety of components is available for Trane air
handlers, including numerous fan, coil, and filter options,
access sections, diffusers, discharge plenums, face-andbypass sections, UL-approved electric heat sections,
humidifiers, mixing boxes, moisture eliminator sections,
exhaust dampers, controls, blenders and airflo w
monitoring stations.
For more information, refer to the following documents,
available from your local Trane sales engineer:
•CLCH-PRC015-EN, P erformance Climate Changer™ Air
Handler catalog
•CLCH-PRC016-EN, P erformance Climate Changer™ Air
Handler quick select
•CLCH-SVN05A-EN, Roof Curbs for Performance
Climate Changer™ Air Handlers installation
instructions
•CLCH-PRG003-EN, Performance Climate Changer™
Air handler guide specifications
•CLCH-SLB017 -EN, Performance Climate Changer™ Air
Handler sales brochure
•CLCH-SVX08A-EN, Gas Heat in Performance Climate
Changer™ Air Handlers installation, operation, and
maintenance guide
Factory-Mounted Controls
Trane air handlers are available with a wide selection of
factory-mounted controls, including controllers, motor
starters, and variable frequency drives (VFD).
Most control components are mounted inside the unit.
Depending on the system configuration, this may include
damper actuators, dirty filter switches, averaging
temperature sensors, and low limit switches. VFDs,
starters, controllers, control transformers, static pressure
transducers, DC power supplies, and customer interface
relays will be in enclosures m ou nte d on the inside of the
unit.
Small items that cannot be factory-mounted, such as
space temperature sensors, outside air temperature
sensors, and humidity sensors, will ship inside the control
enclosures, or packaged and shipped inside the fan or
mixing box section. Larger items are shipped inside the
fan section.
Note: All control valves ship directly to the “ship-to
address” from the vendor unless another address
is given on the Trane sales order.
All factory-mounted control systems (controls that are
factory-wired to a unit controller or termination strip)
ordered without starters or variable-frequency drives
(VFDs) are provided with 120 to 24 Vac control
transformers mounted and wired in the auxiliary control
panel. The customer must provide 1 20 Vac control power ,
50/60 Hz, typically 3 amps for unit sizes 3 to 57 and 5 amps
for unit sizes 66 to 100. A dedicated 15-amp circuit is
recommended.
Factory-mounted control systems ordered with factorymounted starters or VFDs are supplied wit h line to 24 Vac
control transformers. No additional power wiring is
required.
Pre-Packaged Solutions for Controls
If the air handler has been selected using one of Trane’s
pre-packaged solutions options for controls, there are a
number of resources available to aid in commissioning
and start-up of the unit. These resources include
commissioning sheets, graphics and tec hnical application
notes. The tec hnical applic ation notes i nclude the contro l
sequencing, T rane Graphic Programming (TGP) and Rover
set-up files for the specific unit selected. These resources
are available through your local Trane sales office.
CLCH-SVX07C-EN7
General Information
For a more in-depth understanding of controls, refer to the
following manuals:
•For programmable MP580 controllers
– CNT-SVP01A-EN
•For hardware installation
– CNT-SVN01A-EN
•For Trane TR200 Drives
– BAS-SVX19A-EN
Wiring
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follo w requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Entrances are generally provided for field-installation of
high and low voltage wiring through a pipe/nipple
connection in the unit depending on unit configuration
with or without factory-mounted controls. Before
installation, consider overall unit serviceability and
accessibility before mounting, running wires (power),
making penetrations, or mounting any components to the
cabinet.
Wiring to the air handler must be provided by the installer
and must comply with all national and local codes. The fan
motor nameplate includes a wiring diagram. If there are
any questions concerning the wiring of the motor, write
down the information on the motor nameplate and contact
your local Trane sales office.
8 CLCH-SVX07C-EN
Pre-Installation Requirements
Based on customer requirements, Trane air handlers can
ship as complete units or as individual sections to be field
assembled. Unit sizes 3-120 have an integral base frame
designed with the necessary number of lif t points for safe
installation. Indoor air handlers sizes 3-30 are also shipped
with a shipping skid designed for forklift transport.
Unless otherwise specified, Performance indoor air
handlers ship in subassemblies if the total length of the
units exceeds 98 inches or if the total weight exceeds the
limits shown in Table 1. If either the maximum weight or
maximum length is exceeded, the unit will ship in multiple
pieces. See Table 2 for limits for outdoor air handlers.
Note: These limits are based on a four-point lift.
Table 1.Shipping length and weight limitations for
Table 2.Shipping length and weight limitations for
outdoor air handlers
Unit Size
3–3124.50360.008,000
35-5824.5096.00
66-12024.5096.00
Notes:1Some specialty sections can be attached to the adjacent section
even if this causes length to be greater than 96 inches, up to
118.44 inches.
Minimum
Length (in.)
Maximum
Length (in.)
1
1
Maximum
Weight (lb.)
12,000
12,000
Receiving Checklist
Upon receipt of the air handler(s), a thorough inspection
should be performed to note any shipping damage that
may have occurred and that the shipment is complete. All
factory shipping protection should be removed
immediately to allow complete access for the inspection.
The shipping protection provided by the factory is for
transit protection only and shou ld not be used as a jobsite
storage cover.
Note: Delivery cannot be refused. Trane is not
responsible for shipping damage.
•Check all access doors to confirm that the latc hes and
hinges are not damaged.
•Inspect the interior of each section for any internal
damage.
Note: Concealed damage must be reported within
15 days of receipt.
•Inspect the coils for damage to the fin surface and/or
coil connections.
•If the unit was ordered with factory-mounted controls,
locate all sensors.
Note: Items that cannot be factory- mounted should s hip
inside the control enclosures or should be
packaged inside the fan or mixing box section.
•Check all control devices attached to the unit exterior
and confirm that they are not damaged.
•Manually rotate the fan wheel to ensure free
movement of the shaft, bearings, and drive.
•Inspect the fan housing for any foreign obj e cts.
•If the unit is shipped in subassemblies, locate the
assembly hardware, which should be packaged and
shipped inside the fan or mixing box section.
•Inspect and test all piping for possible shipping
damage. Nipples may be installed on coils at the
factory but should always be tightened and tested
before any connections are made. Rough handling
during shipping, in addition to other factors can cause
pipe connections to become loose.
Note: T rane will not be responsible for any leak at the field
connections. Coils have been factory pressure
tested before shipping.
Assembly Hardware
Trane air handlers ship with all necessary assembly
hardware and gasket material. This hardware is packaged
in either a clear plastic envelope or cardboard box and can
be found inside the fan, mixing box, or access section. If
there is not enough space inside the section, a crate or
pallet will be loaded onto the bed of the truck. Check the
Parts List on the Field Assembly drawing against the
contents of the crate. Do not proceed with unit assembly
until verification that all materials are present. Sometimes
it is necessary to use more than one section to ship
hardware. Please check all sections thoroughly before
contacting your local Trane sales engineer to report
missing hardware.
Resolving Shipping Damag e
Trane air handlers ship freight-on-board (FOB), meaning
that the unit belongs to the customer the moment the
delivery truck leaves the factory. If damage has occurred to
the unit during shipment, follow these instructions:
Note: Trane is not responsible for shipping damage.
1 . Make specific notation, describing the damage, on the
freight bill. Take photos of the damaged material if
possible.
2. R eport all claims of shipping damage to the delivering
carrier immediately and coordinate carrier inspection
if necessary.
Note: Do not attempt to repair the unit without consulting
the delivering carrier.
CLCH-SVX07C-EN9
Pre-Installation Requirements
3. Notify your Trane sales representative of the damage
and arrange for repair.
Note: Do not attempt to repair the unit without consulting
the Trane sales representative.
4. Keep the damaged material in the same location as it
was received.
Note: It is the receiver's responsibility to provide
reasonable evidence that concealed damage was
not incurred after delivery.
Storage Recommendations
NOTICE:
Corrosion!
Use only canvas tarps to cover air handlers. Plastic
tarps can cause condensation to form in and on the
equipment, which could result in corrosion damage or
wet storag e stains.
Note: All factory shipping protection shou ld be removed.
This wrapping is for transit protection only and
should not be used for jobsite storage.
Indoor air handlers and/or field-installed accessories that
must be stored for a period of time before installation must
be protected from the elements. A controlled indoor
environment is recommended for proper storage.
Outdoor air handlers require no special protection for
storage before installation. K e ep the equipment in the
original container for protection and ea se of handling.
Note: The warranty does not cover damage to the unit or
controls due to negligence during storage.
General Storage
The unit controller and all other electrical/electronic
components should be stored in conditions of
-20ºF to 120°F and 5 to 95 percent relative humidity, non-
condensing. Electrical components are not moisturetolerant. Factory protective coverings should be removed
prior to storage.
Long-Term St orage
For longer periods of storage, allow proper clearance
around the unit to perform periodic inspection and
maintenance of the equipment.
While the unit is in storage:
•Every two weeks, rotate the fan and motor shaft 30
revolutions by hand. Check for free rotation.
•Every six months, check fan shaf t bearings and grease
lines. Add grease using a manual grease gun following
the lubrications recommendations in “Fan Bearing
Lubrication” on page 124.
•Check the motor lubrication; remove and clean grease
plugs and check for the presence of moisture in the
grease. If moisture is present, remove the motor and
send it to an authorized repair shop for bearing
inspection/replacement. If no moisture if present, refer
to the motor manufacturer’s lubrication
recommendation for proper lubrication.
Outdoor Storage Considerations
Outdoor storage is not recommended for units that will be
installed indoors. However, when outdoor storage is
necessary, several things must be done to prevent
damage:
Note: Keep the equipment on the or iginal wooden blocks/
skid for protection and ease of handling.
•Select a well-drained area, preferably a concrete pad or
blacktop surface.
•Place the unit on a dry surface or ra ised off the ground
to assure adequate air circulation beneath the unit and
to assure no portion of the unit will contact standing
water at any time.
•Loosen the belt tension on the drive belts.
•Cover the unit securely with a canvas tarp.
•Do not stack units.
•Do not pile other material on the unit.
Preparing the Unit Site
•Ensure the installation site can support the total weight
of the unit (see “Unit Dimensions and Weights” on
page 12 for approximate section weights; refer to the
unit submittals for actual weights).
•Allow sufficient space for adequate free air and
necessary service access (see “Service Clearances”
on page 12). Refer to submittals for specific
minimums.
•Allow room for supply and return piping, ductwork,
electrical connections, and coil removal.
•Ensure there is adequate height for condensate drain
requirements. See “Drain Pan Trapping” on page 86.
Note: If unit is installed in a mechanical room on a pad,
inadequate height may necessitate core-drilling
the floor to attain proper trap height. Insufficient
height could inhibit condensate drainage and
result in flooding the unit a nd/or eq uipment r oom.
10 CLCH-SVX07C-EN
Pre-Installation Requirements
Screw securing roof
felt to rigid insulation
or 2 x 10
Flashing
(field-supplied)
Roofing felt
(field-supplied)
4 x 4 cant
(field-supplied)
Roof deckSupport channels
NOTICE:
Microbial Growth!
The floor or foundation must be level and the
condensate drain at the proper height for proper coil
drainage and condensate flow. Standing water and wet
surfaces inside the equipment can become an
amplification site for microbial growth (mold), which
could cause odors and damage to the equipment and
building materials.
•Confirm the roof curb or foundation of the mounting
platform is level and large enough to accommodate
the unit. Refer to the unit submittals for specific
dimensions.
•Provide adequate lighting for maintenance personnel
to perform maintenance duties.
•Provide permanent power outlets in close proximity to
the unit for installation and maintenance.
•Depending upon job requirements, the customer may
need to provide 120 Vac power to the unit controller.
Refer to submittals for more information. A dedicated
15-amp circuit is recommended.
•Wiring for the air handler must be provided by the
installer and must comply with all national and local
electrical codes.
•If the unit integral base frame ceiling suspension
provisions are not used, the installer/contractor must
provide a ceiling-suspended mou nti ng frame
designed to support the length, width, and weight of
the entire air -handling unit. See “Ceiling Suspension”
on page 26 for more information.
•Rooftop curb-mounted units must be sealed tightly to
the curb. Use proper sealants and roof-to-curb sealing
techniques to prevent water and air leakage. Refer to
CLCH-SVN05A-EN Roof Curbs for Performance
Climate Changer™ Air Handlers Installation
Instructions.
Note: Preparation of the roof curb or pier mount and roof
openings should be completed prior to lifting the
unit to the roof.
Roof Curb Installation Checklist
Figure 2.Cross section of typical curb installation on
new construction
1. Verify that the roof structure can adequately support
the combined weight of the unit and curb assembly.
2. Ensure that the selected installation location provides
sufficient service and operational clearances.
3. Remove any twist within the curb due to roof supports
and square the curb.
4. Level the curb.
5. Secure the curb to the roof support members.
6. Install 2-inc h thick boards or rigid insulation around the
curb.
7. Install cant strips around the curb.
8. Bring field supplied roofing felt up to the top of the curb
nailing strips. Nail felt into place.
9. Install field supplied flashing und er the lip of the curb
flanges and over the felt.
10. Apply sealant to the fou r corners.
11. Caulk all joints between the curb and the roof.
Attach the gasket material to the curb’ s top flanges (entire
perimeter) and to the supply and return air duct opening
panel flanges.
See CLCH-SVN05A-EN Roof Curbs for P erformance
Climate Changer™ Air Handlers Installation Instructions
for information on installing roof curbs.
It is recommended that the curb be installed directly on the
support members and fastened to the supports using tac k
welds or other equivalent methods. Properly supported
decking sh ould be ins talle d inside the ai r handl er section
of the curb when this method is used. See Figure 2.
CLCH-SVX07C-EN11
Unit Dimensions and Weights
Filter mixing box
Coil
Fan
Gas heat
Access
door
UV
lights
VFD
F
E
D
C
B
A
Note: For specific dimensional and weight information, refer to the unit submittals. The dimensions and weights in this
manual are approximate. T r ane has a policy of continuous product and product data improvement and reserves
the right to change design and specifications without notice.
Service Clearances
A minimum clearance of the section width plus 1 2 inc hes
on the access door side of the gas heat section is
recommended for routine maintenance. This clearance
Figure 3. Service Clearance
provides enough room to replace the heat exchanger in
the event of failure. The section side panels must be
removed to access the heat exchanger. Refer to Table 3 for
service clearance recommendations for the air handler.
C (Catalytic Air
Cleaner)
D (external starter
or VFD)
D (internal starter
or VFD)
E (fan)484848485154586160516651665866607060776677669393101101
F (gas heat - Ext
Vestibule)
F (gas heat - Int
Vestibule)
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors , coil, piping connections, motor locations, hoods, pipe cabinets, etc. Sufficient clear an ce
must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs,
or other high-voltage devices must be provided per NEC requir ements.
Note: For specific dimensional and weight information, refer to the unit submittals. The dimensions and weights in this manual are approximate. Tr ane has
a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Note:1Nominal airflow is based on 500 fpm through a no minal coil (i .e. 500xunit size 8=4000 cfm ). 2Airflow@625 fpm through th e flat filter (maximum filt er velocit y).
3
Height includes standard 2.5-inch base frame for sizes 3-57 and 6-inch base frame for sizes 66-120. 4Height includes 6-inch base frame for sizes 3-120.5Variable
lengths available from 14-96 inches. 6Fan section weights include the heaviest fan with the largest ODP motor available. 7Nominal length and height shown for
discharge plenums. Variable plenum height and length is available from 0.5 to 1.5 of nominal. 8Access section required with humidifiers for dispersion distance.
Prior to unit placement, remove the shipping tiedowns. See Figure 4.
Figure 4.Isolator tie-down rem oval
•Shipping tie-downs are located at each corner of the
isolation base. See Figure 5, Figure 6, Figure 7, and
Figure 8.
Figure 5.Isolator tie-down for unit sizes 3-8Figure 6.Isolator tie-down for unit sizes 10-30
Required
clearance
Tiedown
Figure 7.Isolator tie-down removal for unit sizes 66-120 Figure 8.Belt-drive plenum fan tie down
CLCH-SVX07C-EN21
Installation - Mechanical
Remove plug panel plate
Remove
tie-down
•Access for removal of shipping tie-downs for unit sizes
3-30 is available through the fan section access door or
opposite drive-side plug panel. See Figure 9.
Figure 9.Plug panel plate
•Access for removal of shipping tie-downs for unit sizes
3-30 is available through the fan section access door or
opposite drive-side plug panel. See Figure 9.
•Remove the bolt. This will release the isolator and
make it possible to remove the pipe or spacer.
•Replace plug panel if applica ble.
Note: For outdoor air handlers, after isolator tie-down is
removed, remove the paper backing from the butyl
tape around plug panel perimeter prior to replacing
plug panel.
General Lifting Considerations
WARNING
Risk of Unit Dropping!
Always place, assemble, and suspend modules/
subassemblies one at a time. Placing, assembling, and/
or suspending more than one module/subassembly at
a time could result in module/subassemblies dropping
and crushing technicians which could result in death,
serious injury, or equipment damage.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in unit dropping and
possibly crushi ng ope rator/technician which could
result in death or serious injury and possible equipment
or property-only damage.
:
NOTICE:
Equipment Damage!
Keep skid in place until unit is ready to set. Do not
move the unit or subassembly without the skid in
place as shipped from the factory. Premature skid
removal could result in equipment damage.
Before preparing the unit for lifting, estimate the
approximate center of gravity for lifting safety. Because of
placement of internal componen ts, the unit weight may be
unevenly distributed, with more weight in the coil a nd fan
areas. Approximate unit weights are provided in “Unit
Dimensions and Weights” on page 12. Refer to the unit
submittals for actual section weight s. Test the unit for
proper balance before liftin g.
For outdoor air handlers, preparation of the roof curb or
pier mount and roof openings must be comple ted before
lifting to the roof. See CLCH-SVN04A-EN Roof Curbs for
Performance Climate Changer Air Handlers installation
instructions for details.
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. A djust as necessary fo r ev en
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.
Always rig subassemblies or sections as they ship from
the factory. Never bolt sections together before rigging.
•Make the loop of the sling parallel to the direction of
airflow, if possible.
•When hoisting the unit into position, use the proper
rigging method, suc h as straps, slings, spreader bars,
or lifting lugs for protection and safety.
•Use all lifting lugs provided. See Figure 10 and Table 8
for lug hole sizes and location.
22 CLCH-SVX07C-EN
Installation - Mechanical
Unit lug
Pipe cabinet
or hood lug
Diameter
Width
Height
Rigging and spreader
bars furnished
by others
Figure 10. Lug holes
Table 8.Lug hole sizes
SectionLocationUnit SizeWidthHeight
Indoor3-21, 25, 300.881.38
Unit Lug
Hole Size
Pipe Cabinet Outdoor3-1202.5-in. diameter
HoodOutdoor3-1201-in. diameter
Indoor
Indoor66-1201.252.75
Outdoor3-301.252.75
22, 26, 31,
35-58
1.381.25
•For unit sizes 3 to 120 with integral base frame, use
field-provided spreader bars and slings to rig units and
subassemblies as shown in Figure 11. The air handler
is not designed to be lifted or rigged from the top of the
unit.
Figure 11.Lifting detail for unit sizes 3 to 120
•For outdoor units, never stack the pipe cabinet or inlet
hood on the unit as it is being lifted.
•Do not attach the intake/exhaust hood or pipe cabinet
to the unit prior to lifting the unit. Doing so may
damage the equipment. Attach the hoods to the unit
only after all sections are in place.
•For outdoor air handlers, all shipping suppo rts and
crating on the face of the sections must be removed to
permit proper fit-up and sealing of the surfaces.
Dispose of properly.
CLCH-SVX07C-EN23
Installation - Mechanical
48 in.
Wooden toe
cleat or metal
cross beam
Unfasten external bracket
to remove wooden toe cleat.
Lifting Hoods and Pipe Cabinets
WARNING
Risk of Unit Dropping!
Always place, ass emble, and suspen d modules/subassemb lies one at a time . Placing, assemb ling, and/or suspend ing
more than one module/subassembly at a time could result in module/subassemblies dropping and crushing
technicians which could result in death, serious injury, or equipment damage.
Do not use a fork lift on air handlers or subassemblie s
larger than size 30. Improper use of fork lifts on units
larger than size 30 could result in equipment damage.
Trane is not responsible for equipment damage
resulting from improper fork lifting practices.
Note: Do not use a forklift on outdoor air handlers or
indoor air handlers/subassemblies larg er than size
30.
For unit sizes 3-30, a forklift may be used to lift a single
section or small subassembly, pro vided the forks extend
under both ends of the base frame, or a s indicated in
Figure 14. The forks should not contact the bott om of the
air handler. Units should only be lifted from the proper end
identified by the lifting label on the u nit. A lif ting crane or
other means should be used for larger units where forks
cannot extend under both base rails.
Figure 14. Fork lift points with base rail
24 CLCH-SVX07C-EN
Installation - Mechanical
Piers
Unit Placement and Assembly
If the air handler ships in subassemblies or in individual
sections, some assembly is required, including:
•Ceiling-suspended indoor unit assembly; see See
“Ceiling Suspension” on page 26.
•Section-to-section assembly; see “Section-to-Section
Assembly” on page 27.
WARNING
Toxic Fumes!
Keep open flame away from unit exterior or interior. Do
not weld or use cutting torch on the exterior or interior
of the unit. The unit contains polyurethane insulatio n.
Flame could produce toxic gas which could result in
death or serious injury.
:
NOTICE:
Equipment Damage!
The internal sections of this unit containing electrical
components must not exceed 104
temperature. Internal sections of the unit which do not
contain electrical components must not exceed 200o F
temperature. Failure to comply with temperature
requirements could result in equipment damage.
o
F operating
Refer to the unit submittals and unit tagging for correct
placement of all sections. If there are any discrepancies
between the submittals and the unit tagging, contact you r
local Trane representative before proceeding.
Following the order of the sections on the unit submittals
and tagging, individually place e ach unassemb led section
or subassembly in the appropriat e installation location.
Note: Prior to placing fan section in the approp ri ate
installation location, verify shipping tie-downs
have been removed.
For outdoor units, the pipe cabinet must also be m ounted
as an individual section. Refer to “P ipe Cabinet
Installation” on page 32 for specific instructions.
When mounting the unit on a roof curb, make sure the
gasketing between the roof curb and unit base provides an
airtight seal.
When mounting the unit on a pier mount, locate one pier
at each corner as a minimum, directly unde r neath any
shipping split (ensure full support under each side) and
then every four feet at equally spaced intervals around the
perimeter of the unit. Both the unit and the pipe cabinet
should be supported by their base around the entire
perimeter. See Figure15 and Figure 16.
Figure 15. Piers located in each corner and spaced evenly
every four feet
Unit Placement
WARNING
Risk of Unit Dropping!
Always place, assemble, and suspend modules/
subassemblies one at a time. Placing, assembling, and/
or suspending more than one module/subassembly at
a time could result in module/subassemblies dropping
and crushing technicians which could result in death,
serious injury, or equipment damage.
NOTICE:
Microbial Growth!
The floor or foundation must be level and the
condensate drain at the proper height for proper coil
drainage and condensate flow. Standing water and wet
surfaces inside the equipment can become an
amplification site for microbial growth (mold), which
could cause odors and damage to the equipment and
building materials.
If a unit arrives in sections, then each section must be
individually hoisted, set on the housekeeping pad, roof
curb, or pier mount and then assembled.
Note: Piers beneath shipping splits must be structurally
sound to support the weight of the unit.
CLCH-SVX07C-EN25
Installation - Mechanical
4 ft
Figure 16. Side view with two shipping splits - locate
one pier directly under each shipping split
ceiling-suspended mounting frame designed to support
the length, width, and weight of the entire air-handling
unit. See “Unit Dimensions and Weights” on page 12 for
approximate weights.
Note: It is the building engineer’ s responsibility to size the
structural channels and to provide the appropriate
hangers.
Structural channels in a field-provided frame can be
mounted parallel to airflow or perpendicular to airflow:
•For parallel-to-airflow channels, size channels based
on a four-point load distribution (see Figure17.
Note: Piers beneath shipping splits must be structurally
sound to support the weight of the unit.
For proper operation, the unit must be installed level (zero
tolerance) in both horizontal axes. For vertical discharge
units, allow space under the unit for supply air ductwork
connections.
Unit Assembly
Note: Air handlers often include optional factory-
provided casing penetration entry points for fieldprovided wiring. Consider overall unit
serviceability and accessibility before mounting,
running wires (power), making cabinet
penetrations, or mounting any components to the
cabinet.
See “Component Install ation Re quirements” on page 45
for special assembly/installation consid erations.
Removing the Shipping Skid
Remove the wooden shipping blocks, wooden toe cleat if
there is one, and end cleats prior to lowering unit into final
position or installing the unit to the roof curb.
•For perpendicular-to-airflow channels, size channels
based on the load distribution of the individual
sections and install the channels so that both ends of every section are supported (see Figure 18).
Do not use mounting legs for ceiling suspension,
external isolation, or unit support during module
placement. Mounting legs are designed only to secure
the unit to the floor, housekeeping pad, or platform.
Improper use of the mounting legs as described above
could result in unit dropping and crushing technicians
which could result in death or serious injury, and
equipment damage.
Note: Ceiling suspension is not recommended for units
larger than size 57 unless using a field-provided
mounting frame.
Using a Field-Provided Mounting Frame
If a field-provided mounting frame is used for ceiling
suspension, the installer/contractor must provide a
26 CLCH-SVX07C-EN
Installation - Mechanical
Hole diameter
is 0.625 inches
Using Integral Base Frame
Figure 19. Ceiling suspension for unit sizes 3-57
•Suspend the unit (on both sides of the unit) at each
shipping split lug as well as the four corners of the unit
(see Figure 19). See Figure 10 and Table 8 on page 23
for lug hole sizes.
•Bolt shipping splits together.
The hanger rods must extend through the bottom of the
base lug. It is the building engineer’s responsibility to
provide the appropriate hangers.
Shipping Gussets
Prior to pulling the shipping splits together, the shipping
gussets (see Figure 20) should be removed to simplify
panel removal (except for units requ ir e d OSHPD
certification). If there is enough access after joining the
shipping splits, the gussets can be removed after they are
joined. The exception to this rule is for size 35-50 stacked
units. For these sizes, the gusse t should be left in place for
the lower level unit unless they are installed in a shipping
split that contains a coil.
Do not mistake the coil structural gusset (see Figure 21)
If using the factory-provided integral base frame for ceiling
suspension, individual sections and/or subassemblies will
have base frame shipping splits and base frame lifting
lugs. When using the base frame for ceiling suspension:
used on unit sizes 66-120 with the shipping gussets.
Section-to-Section Assembly
Air handlers ship with all necessary assembly hardware
and gasket material. The hardware should be packaged in
either a clear plastic envelope or cardboard box inside the
fan section, access section, or mixing box.
The number of sections to be assembled often makes it
necessary to use more than one section to ship the
assembly material; therefore, check all sections
thoroughly before contacting your Trane sales
representative to report missing items.
Sections are joined with gasketing applied to one of the
mating surfaces and hardware to bolt the sections
CLCH-SVX07C-EN27
together. The gasketing for section-to-section joints is a
closed cell foam with adhesive backing.
To assemble the unit:
1. Locate the mounting hardware and gasket material.
2. All shipping supports and crating on the face of the
sections must be removed and discarded to permit
proper fit-up and sealing of the surfaces. Remove any
shipping bolts located on the mo unting surfaces of the
sections (see Figure 22).
3. Apply the gasketing to one of the mating surfaces; see
Figure 22, Figure 23, and Figure 24.
Installation - Mechanical
Indoor units - Gasket
0.375 in. T x 0.750 in. W (3-30)
1.0 in. T x 1.0 in. W (35-120)
Outdoor units - Butyl tape
0.375 in. T x 0.375 in W (3-120)
Butyl Tape
0.375 in. T x 0.375 in. W
Gasket
0.375 in. T x 0.750 in. W
Gasket
X23010544010
1.00 inches T
x
4.00 inches W
Use 2 x 4 inch wood to protect
hands from accidental pinching
Figure 22. Section-to-section installation
Figure 24. Stacked unit assembly (shown for sizes 3-50)
Figure 23. Coil-section-to-downstream-section bolt up
with splash guard
Note: Reference the appropriate controller manual for
more details on the installation of units with
factory-mounted controls.
4. If the unit is equipped with factory-mounted controls,
move adjacent subassembly within six inches and
fasten quick connects where the sections bolt together
(see Figure 25).
28 CLCH-SVX07C-EN
5. Use a bar clamp to pull adjacent sh ipping section lifting
lugs together.
6. For indoor units sizes 66-120 and for outdoor units size
10-120, a wedge bloc k is provided to aid in pulling and
aligning the units together. At tach the wedge bloc ks to
both sides of the units being pulled together, matching
the correct wedge block with the cor rect hole pat tern.
See Figure 29, p. 30.
7. V erify that the subassembly with the overhang profile
on the roof is higher than the mating subassembly . If it
is not, raise one end of the subassembly and brin g the
unit together. See Figure 26.
8. Due to unlevel floor and platforms, the roof may be
misaligned as shown in Figure 26. A common solution
Installation - Mechanical
Loosen screws along
width of unit for roof
height adjustment.
Loosen screws along
width of unit for roof
height adjustment.
is to raise one end of the shipping section to clear the
hemming before pulling the units together.
Figure 26. Roof alignment (indoor unit only)
Figure 27. Adjust height of roof by adjusting vertical channels
9. In addition, an adjustment can also be made to the
height of the roof of either subassembly.
At the center
(width-wise) of the unit, measure the height of each
adjacent subassembly and verify that the
subassembly with the overlap sheet metal is higher
than the mating subassembly roof. If it is not, adjust
the height of either subassembly by loosening the
screws in the vertical channels or component
structure and adjust the height of the roof. See
Figure 27
and Figure 28).
Figure 28. Adjust height of roof by loosening screws
Hex machine bolt fully
threaded zinc plated
Size 3-30 - 5/16 x 6 in.
Size 66-120 - 0.500-13 x 10 in.
Washer
Size 3-30 - 0.375 ID x 0.875 OD
Size 66-120 - 0.656 ID x 0.312 OD
Lifting lugs
Threaded rod
0.500-13 x 10.50
Nut
0.500-13 hex machine
Washer
0.656 ID x 1.312 OD
Wedge block for
indoor unit size 66-120
outdorr unit size 10-120
Leached self-driller screw
0.250-14 x 0.75
10. For unit sizes 3-30, bolt the unit base frames together
using 5/16-inch bolts (see Figure 29).
1 1 . For unit sizes 35-120, bolt the unit base frames together
using ½-threaded rod (see Figure 29).
12. For sizes 66-120 only, bolt through the wedge blocks
using a ½-threaded rod (see Figure 29). Alternate
Figure 29. Base frame split assembly
between tightening on the liftin g lug bolts and wedge
block bolts until the shipping section comes together.
13. Use straps and come-alongs to compress the
gasketing and pull the sections together along the
height of the unit.
30 CLCH-SVX07C-EN
Installation - Mechanical
Seam cap
Butyl tape
Detail A
See
Detail A
See
Detail B
Detail B
Roof overhang
Butyl tape
14. Install the section-to-section screws inserting the
appropriate screws through the overlapping flanges
using a powered impact gun and taking care not to
strip the screws. Outdoor air ha ndlers will ship wi th a
seam cap that is to be installed over the section-to-
Figure 30. Section-to-section seam cap installation
section seams. Factory-supplied butyl tape must be
applied over the seam prior to seam cap being applied.
See Figure 30.
15. For outdoor air handlers, attach roof overhang angle
with number 10 screws. Join outdoor roof panels
together at the seams in the direction perpendicular to
airflow and secure them in place with 5/16-inch x 3/4inch bolts and 5/16 l oc k nuts. Inst all the roof joint strip
to cover the seam between two outdoor roof panels in
the perpendicular to airflow direction of. Use 3/8-inch
butyl tape to cover the seam between two outdoor roof
panels overhang at the side the unit. Bend joint strip
over roof panel and use two number 10 sheet metal
screws (one in each roof panel) to secure joint strip.
Trim the roof joint strip to insure that it does not
protrude more than 1/16-inch beyond outdoor roof
overhang (see Figure 31).
CLCH-SVX07C-EN31
Installation - Mechanical
See
Detail A
Detail A
Butyl tape
Figure 31. Join outdoor roof panels at the seams
Pipe Cabinet Installation
1. After air handler is completely installed and checked
for accuracy of level and square, pipe cabinet install
can begin.
2. Remove pipe cabinet base cross member by removing
the four bolts and nuts.
3. Check to ensure that the structure the pipe cabinet is to
be installed on is square and level.
Figure 32. Pipe cabinet installation
4. Install 3/8-inch x 3/8-inch white butyl tape to flanged
side of pipe cabinet wall and remove paper backing
from tape. See Figure 32.
5. Lift cabinet into place on to pipe cabinet curb.
6. Slide pipe cabinet tight up against the sidewall of the
air handler.
7. Check pipe cabinet side walls to ensure they are plumb.
8. Apply a bead of caulk along the corner between the
pipe cabinet and air handler wall prior to installing
connecting angle.
Butyl tape
32 CLCH-SVX07C-EN
Installation - Mechanical
A
See Detail B
AHU
Pipe cabinet
Ribbed
Butyl tape
Screw:
10-16 x .750
self-driller
Pipe cabinet
outer roof
Slots provided to allow
final adjustment
of outer roof
AHU
outdoor roof
Inside corner cap
Ribbed Butyl tape
Ribbed Butyl tape
(see note)
Inside
corner cap
Pipe cabinet
wall
Detail B
Detail A
Top view
Roof and base parts
rmoved for clarity
Note: Seam to be sealed prior to
attaching inside corner cap with
10-16 x .750 self-driller screws
Ribbed Butyl tape
(see note)
9. Install inside corner cap. SeeFigure 33 Detail A and B.
10. Install 3/8-inch x 3/8-inch white butyl tape to unit wall
where pipe cabinet roof connects.
Figure 33. Pipe cabinet installation details
11. Lift pipe cabinet roof into place and at tac h to unit w all
with screws. See Figure33.
CLCH-SVX07C-EN33
Installation - Mechanical
AHU outdoor roof
Butyl caulk tape
1.00 W x .125T.
Hood
Nut-Hex .31-18
Detail A
Screw self-driller
10-16 x .750
Butyl caulk tape
1.00 W x .125T.
Nut-Hex .31-18
Bolt .313-18 x .750 Hex
Bracket Support
Angle Hood Support
(when required)
Bolt .313-18 x .750 Hex
Outdoor Unit Weather Hoods
1. Per the unit drawing determine mounting location of
the unit weather hoods.
2. Using the factory provided screws mount the weather
hoods to the unit.
3. On larger units, weather hoods may be large enough to
require angled down supports. In those cases, the
angles are shipped attached to the hood but will need
Figure 34. Hood installation
to be connected to the air handler by the installing
contractor. See Figure 34.
Note: It is required that the hoods be sealed to the unit
using factory-provided butyl/caulk tape.
Stacked Outdoor Units
Assembly hardware
Table 9.Parts list for outdoor stacked units
ItemDescriptionItemDescription
1Gasket: 1.00T x 4.00W
2Bracket: Stacked unit10Guard: Energy recovery end cover
3Screw: 0.313-18 x 0.875 sheet metal11Guard: Energy recovery end cover
4Screw: 10-16 x 0.750 self driller12Guard: Direction of airflow flashing
5Tape: Butyl 0.38T13Guard: Flashing seam cover
6Tape: Ribbed Butyl14Adhesive/sealant: Flex polyurethane
7Plate: Vertical seam cap15Bracket: Hood support
8Tape: 0.12T x 1.00W, gray Butyl16Angle: Hood support
9Guard: perpendicular to airflow flashing17Screw: 0.250-14 x 0.750 self driller
34 CLCH-SVX07C-EN
Installation - Mechanical
(1) Gasket:
1.00T x 4.00W
(2) Bracket:
stacked unit
(5) Tape:
Butyl 0.38T
(5) Tape:
Butyl 0.38T
(3) Screw:
0.313-18 x 0.875
sheetmetal
Part# X25240049010
(4) Screw:
10-16 x 0.750
self-driller
Part# X25020634020
(1) Gasket:
1.00T x 4.00W
See Detail A
Detail A
Remove lugs from upper
baserail prior to installing
stacked unit bracket
(2) Bracket:
stacked unit
(2) Bracket:
stacked unit
(2)Bracket:
stacked unit
Part# 4953-0203
Unit assembly
1. See Figure 35. Apply gasket (Item 1) on top of lower
unit. Compress gasketing to ensure a good air seal
between upper and lower sections.
2. Place upper unit on lower unit.
3. Remove lifting lugs from top unit and attach stacking
brackets (Item 2) to top and bot tom units using screws
(Item 3 and Item 4). See Detail A in Figure 35. Stacking
Figure 35. Stacked unit assembly
brackets (Item 2) are to be used on the right and left
sides at each shipping split section end and also on
front and back of the unit.
4. Apply Butyl tape (Item 5) to one side of the shipping
split section.
5. Slide shipping split sections together, pulling tight
using lifting lugs and threaded rod on bottom and
straps or pipe clamps on top.
CLCH-SVX07C-EN35
Installation - Mechanical
(7) Plate:
Vertical
seam cap
(6) Tape:
Ribbed Butyl
(7) Plate:
Vertical
seam cap
(4) Screw:
10-16 x 0.750
self driller
(6) Tape:
Ribbed Butyl
(7) Plate: Vertical
seam cap
(6) Tape:
Ribbed Butyl
Detail A
Shipping split seams
Detail B
Ribbed Butyl tape and
seam cap flush with
bottom of wall panel
First level ribbed
Butyl tape 1/2 inch
below second level
wall panel
First level seam cap
starts at bottom of
hem on roof panel
First level
Ribbed Butyl tape and seam
cap extend beyond the bottom
of wall panel onto base rail at
least one inch
First level
Second level
Detail C
Vertical Seam Cap Installation
1. See Figure 36. Apply ribbed Butyl tape (Item 6) over all
vertical shipping split seams (see Detail A). First level
ribbed Butyl tape (Item 6) starts 1/2 inch below second
level wall panel (see Detail B), and extends down
beyond the bottom of the first level wall panel onto the
base rail at least one inch (see Detail C). Second level
ribbed Butyl tape (Item 6) starts at bottom of wall panel
on second level (see Detail B) and runs up to the top of
the second level wall panel.
Figure 36. Vertical seam cap installation
2. Secure vertical seam cap (Item 7) over ribbed Butyl
tape (Item 6) with screws (Item 4) (see Detail A). First
level vertical seam cap (Item 7) starts at bottom of hem
on roof panels (see Detail B) and extends down onto
the base rail at least one inch (see Detail D in Figure 41).
Vertical seam cap (Item 7) on second level starts at
bottom of wall panel and extends up (see Detail B).
Second level vertical seam cap (Item 7) may extend
onto the roof panel.
36 CLCH-SVX07C-EN
Installation - Mechanical
(9) Guard:
Perpendicular-toairflow flashing
(8) Tape:
0.12T x 1.00W
gray Butyl
(12) Guard:
Direction-ofairflow flashing
(10) Guard:
Energy recovery
end cover
(11) Guard:
Energy recovery
end cover
(12) Guard:
Direction-ofairflow flashing
(8) Tape:
0.12T x 1.00W
gray Butyl
(9) Guard:
Perpendicular-toairflow flashing
Flashing Installation
For additional information, see “Flashing Installation
Notes” on page 40.
For hood installations, see “Install flash ing and hood” on
page 41.
1. See Figure 37. Apply Butyl tape (Item 8) to
perpendicular-to-airflow flashing (Item 9) and secure
to base rail with screws (Item 4) on front and back of
unit (see Detail A in Figure 41).
2. For energy wheel/CDQ wheel, preassemble end covers
(Item 10 and Item 11) to direction-of-airflow flashing
Figure 37.Flashing installation
(Item 12) with screws (Item 4). Apply caulk (Item 14) to
create water tight seal (see Detail B in Figure 39).
3. Apply Butyl tape (Item 8) to direction-of-airflow
flashing (Item 12) and secure to base rails with screws
(Item 4). Start at corners to ensure tight corner seams.
Apply caulk (Item 14) to create water-tight seal (see
Detail A and Detail C in Figure 40).
4. Install seam covers (Item 13) to all flashing seams (see
Detail D in Figure 41).
CLCH-SVX07C-EN37
Installation - Mechanical
Detail A
Base rail
.060 gap between
bottom of panel and
top of flashing
Lower panel
Upper panel
(4) Screw:
10-16 x 0.750
self-driller
(9) Guard: Perpendicularto-airflow flashing
or
(12) Guard: Directionof-airflow flashing
Figure 39. Flashing end cover installation applied to energy wheels and CDQ sections
38 CLCH-SVX07C-EN
Figure 40. Flashing for corner seams
Assembled view
Detail C
Apply caulk
(14) Adhesive/sealant:
Flex polyurethane
(12) Guard:
Direction-ofairflow flashing
(4) Screw:
10-16 x 0.750
self-driller
(9) Guard:
Perpendicular-toairflow flashing
(8) Tape:
0.12T x 1.00W
gray Butyl
Detail D
(4) Screw:
10-16 x 0.750
self-driller
(13) Guard:
Flashing seam cover
Note: Install flashing seam
cover on all flashing seams
(4) Screw:
10-16 x 0.750
self-driller
(13) Guard:
Flashing seam cover
Installation - Mechanical
Figure 41. Flashing seam cover installation
CLCH-SVX07C-EN39
Installation - Mechanical
Flashing
Plug panel
Detail A
without full height doors
.406 from plug
panel flange
Vertical
seam cap
Flashing
Door
Flashing flush
with vertical
seam cap
Detail A
with full height doors
Assembled view
See Detail A
Flashing Installation Notes
•Side flashing will have locating features :
– Right side front and back pieces will have two
diamonds and a tab. Intermediate right side pieces
(if present) will have two diamonds and length of
part will matc h the ship group length and mo unting
holes will match hole pattern on the unit.
– Left side front and back pieces will have one
diamond and a tab. Intermediate lef t side pieces (i f
present) will have one diamond a nd l en gth of part
will match the ship group length and mounting
holes will match hole pattern on the unit.
Figure 42. Side flashing installation
•Flashing runs full length on right/left sides of unit
except on access side when an energy recovery
section is present. For energy recovery section without
full height doors, flashing will extend to removable
plug panel. For energy recovery section with full height
doors, flashing will be flush with edge o f vertical seam
caps (see Detail A in Figure 42).
•Flashing runs full length on front/back of unit. Front/
back flashing will not have any locating features and
will always have mitre (o ne piece will have two mitres,
two pieces will have one mitre).
1. See Figure 43. Secure two hood support brackets (Item
15) to base rail with screws (Item 17).
2. Apply Butyl tape (Item 8) to flashing (Item 9) and place
over hood support brackets (Item 15) using cut in
flashing and secure to base rails with screws (Item 4).
3. See “Outdoor Un it Weather Hoods” on page 34 for
hood installation instructions.
Figure 43. Stacked unit assembly
4. Secure hood suppor t angles (Item 1 6) to hood suppor t
brackets (Item 15) and to the hood side panels with
screws (Item 17).
5. Apply caulk (Item 14) around hood support bracket
(Item 15), hood support angle (Item 16), and cutout in
perpendicular-to-airflow flashing (Item 9) to ensure
water-tight seal.
CLCH-SVX07C-EN41
Installation - Mechanical
Gasket
X23010544010
1.0 inches T x
4.0 inches W
Airflow
Unit support
brackets
Center of units
Secondary
unit
Gasket
Primary
unit
Indoor Dual-Path SDU/Winterizer
Assembly
WARNING
Heavy Objects!
Do not stack air handlers unless factory-designed and
factor y-approved. When stacking units, facto r ydesigned unit support brackets must be used. Stacking
units without factory-approval and without factoryprovided support brackets could result in the base unit
collapsing under the weight of the top unit which could
result in death or serious injury and property damage.
A dual-path, Split Dehumidification Unit (SDU)/winterizer
air handler consists of two units that are stacked together
in a draw-thru arrangement that share one supply fan. The
unit on the first level (primary unit) is designed to handle
the return air and is larger than the unit on the second level
(secondary unit), which is designed to handle outside air.
Factory-designed unit support brac kets are provided with
all factory-appro v ed , dual-path SDUs or winterizer air
handlers.
•A horizontal SDU/winterizer dual-path air handler
incorporates a horizontal supply fan on the first level
with a top opening in the primary unit that aligns with
a bottom opening in the secondary unit.
•A vertical SDU/winterizer dual-path air handler
incorporates a vertical supply fan on the second level
with a back opening that aligns with a front opening in
the secondary unit.
To assemble air handlers utilizing factory-approved and
factory-provided dissimilar unit sizes for horizontal SDU or
winterizer applications, join all similar size shipping
sections per “Section-to-Secti on Asse mbly” on page 27.
Figure 44. Apply gasket in direction of airflow
3. If there is an opening in the roof of the primary unit,
apply gasket perpendicular to airflow on the roof next
to the opening (air entering side only).
4. Lift the secondary unit, following instructions in
“General Lifting Considerations” on page 22 (see
Figure 11), and place on the blac k unit support brac kets
(see Figure 45). The secondary unit must be centered
on the primary unit between the black unit support
brackets.
Figure 45. Place secondary unit on black unit support
brackets.
Horizontal SDU/Winterizer Air Handler
Assembly
To assemble dissimilar unit sizes for an indoor horizontal
SDU/winterizer configuration:
1. Locate the mounting hardware and gasket material.
Note: Black unit support brackets ship pre-installed on
the primary (larger) unit section.
2. Apply gasket in direction of airflow between the black
unit support brackets to the roof of the primary unit.
See Figure 44. The gasket needs to be placed such that
it will be directly under the integral base frame of the
secondary (smaller) unit to be stacked on top. The
secondary unit will be centere d along the width on the
primary unit.
42 CLCH-SVX07C-EN
5. Install screws as shown in Figure 46 inserting the
Airflow
X25240049010
Screw: 0.313-18 x 0.875 in.
Sheet metal hex head
Airflow
Gasket
1.0 inches T x 1.0 inches W
Gasket
1-inch T x
2 1/2 inch W
Airflow
Airflow
appropriate screws using a powered impact gun and
taking care not to strip the screws.
6. Remove the secondary un it lifting lugs one at a time
and reinstall screws after sections are set in final
position.
Figure 46. Install screws using powered impact gun.
Vertical SDU/Winterizer Air Handler
Assembly
To assemble dissimilar unit s izes for an indoor vertical
SDU/winterizer configuration:
1 . Apply gasketing to the mating surface of the secondary
unit (see Figure 47).
Installation - Mechanical
Figure 48. Apply gasketing to the mating surface of the
primary unit.
3. Lift the secondary unit, follow instructions in “General
Lifting Consideratio ns” on page 22 (see Figure 11), and
place on the blac k unit support brac kets (see Figure 45,
p. 42. The secondary unit must be centered on the
primary unit between the black unit support brackets.
4. Install trim angles as shown in Figure 49 inserting the
10-16 x 3/4-inch self-drilling screws using a powered
impact gun and taking care not to strip the screws.
Figure 49. Install trim angles
Figure 47. Apply gasketing to mating surface of
secondary unit
Vertical and horizontal
trim angles
2. Apply gasketing to the mating surface of the primary
unit at the bottom of the opening (see Figure 48.
CLCH-SVX07C-EN43
Installation - Mechanical
Cut zip-ties
Step 1
Match connector
numbers (LV side)
Match connector
colors (HV side)
High-voltage (HV)
stacked harness
Low-voltage (LV)
stacked harness
Step 2
Verify if conduit is
1-inch or 2-inch for
stacked harness
Use for 1-inch stacked
raceway conduit
Use for 2-inch stacked
raceway conduit (requires
removal of knockout)
Cover
Conduit
Step 3
Wrap around
conduit when
attaching cover
Screw; 10-16 x 0.75
self-driller
Enclosure;
stacked raceway
Step 4
Tie; 0.25 wire screw type
Screw;
.250-14 x 0.75
self-driller
Space tie downs
no greater than
10 inches. Also
locate cut-screw
behind conduit
Step 5
External Raceway Assembly
For air handling units with fa ctory -installe d power wiri ng
extending from the first level to the second level, wiring
must be connected and assembled in a raceway.
1. Remove protective foam cover from connectors.
2. Attach stac ked raceway harness connectors, matching
connector colors on the high voltage side and
connector numbers on the low voltage side.
The components in the air handler may have installation
requirements that could affect the unit’s performance.
Diffuser Section
Diffuser sections are usually placed between a fan and a
downstream coil or filter. Because placement is critical to
unit performance, verify the correct placement of the
diffuser section before a ssembling the unit (see Figure 51).
Figure 51. Diffuser placement sizes 3 to 120
Filter Section
Bag and cartridge filter sections can be used as a pre-filter
section, a final filter section, or both. This use is
determined by the filter’s placement in relation to the fan.
•A final filter is placed after the fan.
•A pre-filter is placed before the fan.
Note: Cartridge and bag fil t ers provided by Tr ane are
fitted with a 7/8-inch header that fits in the filter
track. If using filters supplied by another
manufacturer, filters should be purc hased with a 7/
8-inch h eader. In some cases it may be necessary to
gasket other manufacturers’ filters to ensure a
good air seal.
Filters should be installed when the unit is set. This will
protect internal components, such as the heating and
cooling coils.
Trane recommends the use of disposable pre-filters with
high-efficiency filters. Disposable pre-filters slide into the
mounting tracks just ahead of the bag/cartridge filters.
Filter Installation
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
To install filters:
1. Disconnect the power to the unit.
2. Open the filter section access door.
3. Slide the filters into the tracks.
Note: Bag filters must be installed with the pleats in the
vertical plane.
4. The block-of f is permanently installed and will c reate a
seal when the access door is closed.
5. Close the access door slowly to allow any gasketing to
compress.
Figure 52. Filter block-off placement
Final Filter Section
A final filter section should not be bolted directly to the
face of a fan section. One or more intermediate sections
must be placed between the fan discharge and the filter
section.
Pre-Filter Section
A pre-filter section has no special installation
requirements unless placed directly upstream of a plenum
fan. In these configurations, ensure a blank section is
placed between the fan inlet and the filter section.
CLCH-SVX07C-EN45
Component Installation Requirements
Size 3
20
25
2.5
Size 4
20
2020
2020
Size 6
25
2420
Size 8
24
2.5
Size 10
20
20
1.25
25
16
Size 12
16
16
20
20
20 2.5
Size 14
20
3
16
16
2025
Size 17
20
20
24
2420
16
25
25
25
25
1
16
202020
Size 21
25
25
7.5
Size 22
16
20
20
20
2016
1.5
24
20
20
12
16
24244
202020
Size 25
Size 26
1.5
20
25
25
25
2016
12
24
17.5
20
20
242416 1.5
Size 30
25
20
Size 31
25
25
161616
Size 35
24
20
25252520 1
20
16
242424
Size 36
20
252025251
16
20
20
202016
Size 40
20
16
20
20
202025 3.520
Size 41
20
20
242424 4
12
20
20
20
202016
Size 50
16
25
20
25
25
25252520
2020202020 1.5
3.47 ft ²5.56 ft ²
6.94 ft ²
7.33 ft ²
9.72 ft ²
13.33 ft ²
14.44 ft ²
18.89 ft ²
21.53 ft ²
21.11 ft ²
27.11 ft ²
29.17 ft ²
30.44 ft ²
35.42 ft ²
37.22 ft ²
40.00 ft ²
40.83 ft ²
48.22 ft ²
55.00 ft ²
Filter Placement
Figure 53. 2-inch and 4-inch flat filter placement for unit sizes 3-50 - side loading
46 CLCH-SVX07C-EN
Component Installation Requirements
Size 51
12
24
17.5
20
242416 1.5
20
20
20
Size 57
20
25
16
20
20
25252520 1.5
Size 58
20
24
20
20
20
20
242416 1.5
Size 66
20
24
20
20
20
2424242416 .5
Size 80
20
16.5
242424242416 .5
12
20
20
20
Size 100
20
25
20
20
20
20
2525252525 .5
Size 120
25
20
25
25
25
2020202020202016 2
54.89 ft²
63.33 ft ²
61.11 ft²
75.56 ft²
85.56 ft²
104.17 ft²
122.22 ft²
Figure 54. 2-inch and 4-inch flat filter placement for unit sizes 51-120 - side loading
CLCH-SVX07C-EN47
Component Installation Requirements
Size 3
20
25
2.5
Size 4
20
2020
2020
Size 6
25
2420
Size 8
24
2.5
Size 10
20
20
1.25
25
16
Size 12
16
16
20
20
20 2.5
Size 14
20
3
16
16
2025
Size 17
20
20
24
2420
16
25
25
25
25
1
16
202020
Size 21
25
25
7.5
Size 22
16
20
20
20
2016
1.5
24
20
20
12
16
24244
202020
Size 25
Size 26
1.5
20
25
25
25
2016
12
24
17.5
20
20
242416 1.5
Size 30
25
20
Size 31
25
25
1616 16
Size 35
24
20
25252520 1
20
16
242424
Size 36
20
25202525 1
16
20
20
202016
Size 40
20
16
20
20
202025 3.520
Size 41
20
20
242424 4
12
20
20
20
202016
Size 50
16
25
20
25
25
25252520
2020202020 1.5
3.47 ft ²5.56 ft ²
6.94 ft ²
7.33 ft ²
9.72 ft ²
13.33 ft ²
14.44 ft ²
18.89 ft ²
21.53 ft ²
21.11 ft ²
27.11 ft ²
29.17 ft ²
30.44 ft ²
35.42 ft ²
37.22 ft ²
40.00 ft ²
40.83 ft ²
48.22 ft ²
55.00 ft ²
Figure 55. 2-inch/4-inch combination flat filter placement for unit sizes 3-50 - side loading
48 CLCH-SVX07C-EN
Component Installation Requirements
Size 51
12
24
17.5
20
242416 1.5
20
20
20
Size 57
20
25
16
20
20
25252520 1.5
Size 58
20
24
20
20
20
20
242416 1.5
Size 66
20
24
20
20
20
2424242416 .5
Size 80
20
16.5
242424242416 .5
12
20
20
20
Size 100
20
25
20
20
20
20
2525252525 .5
Size 120
25
20
25
25
25
2020202020202016 2
54.89 ft²
63.33 ft ²
61.11 ft²
75.56 ft²
85.56 ft²
104.17 ft²
122.22 ft²
Figure 56. 2-inch/4-inch combination flat filter placement for unit sizes 51-120 - side loading
CLCH-SVX07C-EN49
Component Installation Requirements
Size 3
16
25
2.5
Size 4
16
2020
Size 6
2020
Size 8
20
6.5
Size 10
25
25
7.25
20
Size 12
20
20
20
20
20 2.5
16
16
16
2020
16
20
20
Size 14
20
3
20
20
2025
Size 17
16
16
20
2025
16
25
25
25
1
Size 21
25
25
7.5
Size 22
16
16
16
3
16
16
16
16
16
16
16
16
251625251
Size 25
Size 26
7.5
25
16
25
16
20
Size 30
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
202025 4.5
16
20
Size 31
Size 35
25252520 1
16
Size 36
2525251
20
16
16
16
16
16
16
16
16
20253
16
16
16
16
16
20
20
20
20
20
Size 40
2016202025 3.520
Size 41
16
Size 50
20
202020202020 1.5
16
16
16
16
16
16
16
16
16
16
16
16
2525251
20
20
20
20
20
5.56 ft ²
8.89 ft ²8.89 ft ²
18.06 ft ²
28.89 ft ²
11.11 ft ²
13.89 ft ²
16.67 ft ²
33.33 ft ²
33.33 ft ²
50.00 ft ²
44.44 ft ²
57.78 ft ²
63.33 ft ²
56.67 ft ²
62.50 ft ²
70.00 ft ²
66.67 ft ²
100.00 ft ²
Figure 57. 2-inch and 4-inch angled filter placement for unit sizes 3-50 - side loading
50 CLCH-SVX07C-EN
Component Installation Requirements
Size 51
20
Size 57
20
20 1.5
Size 58
20
25 1
Size 66
20
16 .5
Size 80
16 .5
20
Size 100
20
252525252525 .5
Size 120
20
25 3
20
20
20
20
20
20
20
20202025 4.5
20
20
20
20
20
2020202020
20
20
20
20
20
20
20
16161616
20
20
20
20
20
202020202020
20
20
20
20
20
20
20
202020202020
20
20
20
20
20
20
20
20
20
20
20
20
20
20
252525252525
94.44 ft ²
100.00 ft ²
98.89 ft ²
113.33 ft ²
151.11 ft ²
166.67 ft ²
194.44 ft ²
Figure 58. 2-inch and 4-inch angled filter placement for unit sizes 51-120 - side loading
CLCH-SVX07C-EN51
Component Installation Requirements
Size 3
20
24
3.9
Size 4
20
20.8
2020
Size 6
24
1212
Size 8
24
.1
Size 10
20
20
6.45
24
12
Size 12
12
20
20
20
20 3.7
Size 14
24
1.2
12
20
2420
Size 17
20
20
24
2420
20
24
5.2
242424
Size 21
Size 22
202420 12
6.7
24
20
20
12
2424 5.2
Size 25
Size 26
6.7
20
24
24
24
20 12
12
20
18.7
20
20
11.1
Size 30
24
24
Size 31
24
24
2420 1.2
Size 35
24
20
20
12
242424
Size 36
24
24
5.2
Size 40
24
24
24
2.5
Size 41
242424 5.2
24
Size 50
12
24
24
24
3.5
.8
242415.3
20.82424
20
12 12
1.2
24
242424
202020
1.6
24
24
2424
24242412
24
24
24
24242424
3.33 ft ²
5.56 ft ²
6.67 ft ²
8.00 ft ²
8.67 ft ²
12.33 ft ²
13.44 ft ²
18.89 ft ²
22.00 ft ²
17.33 ft ²
26.00 ft ²
26.00 ft ²
28.22 ft ²
34.00 ft ²
34.67 ft ²
36.00 ft ²
36.00 ft ²
48.00 ft ²
50.00 ft ²
Figure 59. Long bag filter placement for unit sizes 3-50 - side loading
52 CLCH-SVX07C-EN
Figure 60. Long bag filter placement for unit sizes 57-120 - side loading
Size 51
24
24
242412 7.1
24
24
24
Size 57
24
24
24
24
3.5
Size 58
12
24
24
24
24
24
242412 7.1
Size 66
20
24
20
20
20
2424242418.5
Size 80
24
246.9
Size 100
12
20
24
1.7
Size 120
24
241.2
24242424
18.7
24
24
24
2424242412
24
24
24
2424242424248.9
202020202020 12
12
24
24
24
24242424242412
12.8
56.00 ft ²
60.00 ft ²
62.00 ft ²
66.67 ft ²
88.00 ft ²
111.33 ft ²
134.00 ft ²
Component Installation Requirements
CLCH-SVX07C-EN53
Component Installation Requirements
Size 3
20
24
3.9
Size 4
20
20.8
2020
Size 6
24
1212
Size 8
24
.1
Size 10
20
20
6.45
24
12
Size 12
12
20
20
20
20 3.7
Size 14
24
1.2
12
20
2420
Size 17
20
20
24
2420
20
24
5.2
242424
Size 21
Size 22
202420 12
6.7
24
20
20
12
2424 5.2
Size 25
Size 26
6.7
20
24
24
24
20 12
12
20
18.7
20
20
11.1
Size 30
24
24
Size 31
24
24
2420 1.2
Size 35
24
20
20
12
242424
Size 36
24
24
5.2
Size 40
24
24
24
2.5
Size 41
242424 5.2
24
Size 50
12
24
24
24
3.5
.8
242415.3
20.82424
20
12 12
1.2
24
242424
202020
1.6
24
24
2424
24242412
24
24
24
24242424
3.33 ft ²
5.56 ft ²
6.67 ft ²
8.00 ft ²
8.67 ft ²
12.33 ft ²
13.44 ft ²
18.89 ft ²
22.00 ft ²
17.33 ft ²
26.00 ft ²
26.00 ft ²
28.22 ft ²
34.00 ft ²
34.67 ft ²
36.00 ft ²
36.00 ft ²
48.00 ft ²
50.00 ft ²
Figure 61. Short bag filter placement for unit sizes 3-50 - side loading
54 CLCH-SVX07C-EN
Figure 62. Short bag filter placement for unit sizes 57-120 - side loading
Size 51
24
24
242412 7.1
24
24
24
Size 57
24
24
24
24
3.5
Size 58
12
24
24
24
24
24
242412 7.1
Size 66
20
24
20
20
20
2424242418.5
Size 80
24
246.9
Size 100
12
20
24
1.7
Size 120
24
241.2
24242424
18.7
24
24
24
2424242412
24
24
24
2424242424248.9
202020202020 12
12
24
24
24
24242424242412
12.8
56.00 ft ²
60.00 ft ²
62.00 ft ²
66.67 ft ²
88.00 ft ²
111.33 ft ²
134.00 ft ²
Component Installation Requirements
CLCH-SVX07C-EN55
Component Installation Requirements
Size 3
20
24
3.9
Size 4
20
20.8
2020
Size 6
24
1212
Size 8
24
.1
Size 10
20
20
6.45
24
12
Size 12
12
20
20
20
20 3.7
Size 14
24
1.2
12
20
2420
Size 17
20
20
24
2420
20
24
5.2
242424
Size 21
Size 22
202420 12
6.7
24
20
20
12
2424 5.2
Size 25
Size 26
6.7
20
24
24
24
20 12
12
20
18.7
20
20
11.1
Size 30
24
24
Size 31
24
24
2420 1.2
Size 35
24
20
20
12
242424
Size 36
24
24
5.2
Size 40
24
24
24
2.5
Size 41
242424 5.2
24
Size 50
12
24
24
24
3.5
.8
242415.3
20.82424
20
12 12
1.2
24
242424
202020
1.6
24
24
2424
24242412
24
24
24
24242424
3.33 ft ²
5.56 ft ²
6.67 ft ²
8.00 ft ²
8.67 ft ²
12.33 ft ²
13.44 ft ²
18.89 ft ²
22.00 ft ²
17.33 ft ²
26.00 ft ²
26.00 ft ²
28.22 ft ²
34.00 ft ²
34.67 ft ²
36.00 ft ²
36.00 ft ²
48.00 ft ²
50.00 ft ²
Figure 63. Cartridge filter placement for unit sizes 3-50 - side loading
56 CLCH-SVX07C-EN
Figure 64. Cartridge filter placement for unit sizes 57-120 - side loading
Size 51
24
24
242412 7.1
24
24
24
Size 57
24
24
24
24
3.5
Size 58
12
24
24
24
24
24
242412 7.1
Size 66
20
24
20
20
20
2424242418.5
Size 80
24
246.9
Size 100
12
20
24
1.7
Size 120
24
241.2
24242424
18.7
24
24
24
2424242412
24
24
24
2424242424248.9
202020202020 12
12
24
24
24
24242424242412
12.8
56.00 ft ²
60.00 ft ²
62.00 ft ²
66.67 ft ²
88.00 ft ²
111.33 ft ²
134.00 ft ²
Component Installation Requirements
CLCH-SVX07C-EN57
Component Installation Requirements
Size 3
12
24
3.38
Size 4
12
24 15.88
2412
Size 6
24
24
Size 8
24
10.25
Size 10
24
24
9.25
24
Size 12
10.88
24
24
24
12 2.13
Size 14
24
7.63
24
2412
Size 17
12
24
24
2412
12
24
3.625
242424
Size 21
Size 22
242424
12
9.25
24
24
24
6.75
24243.63
Size 25
Size 26
9.25
24
24
24
24
24
6.75
24
24
24
5
Size 30
24
24
Size 31
24
24
24
12
7.63
Size 35
24
24
24
12
242412
Size 36
24
24
3.63
Size 40
24
24
Size 41
2424243.63
24
Size 50
12
24
24
24
.88
3.75
7.63
24
242412
11.5
24
24
2424
24
24
24
24242424
12
12
24242424
12
2.00 ft ²
2.00 ft ²
6.00 ft ²
6.00 ft ² 8.00 ft ²
10.00 ft ²
10.00 ft ²
14.00 ft ²
18.00 ft ²
18.00 ft ²
24.00 ft ²
24.00 ft ²
28.00 ft ²
30.00 ft ²
34.00 ft ²
36.00 ft ²
46.00 ft ²
50.00 ft ²
10.38
10.38
4.63
7.13
7.13
10.88
6.25
10
.38
6.63
6.63
.38
6.63
.38
1
8.88
38.00 ft ²
Figure 65. Front-load bag and cartridge filter placement for unit size 3-50
58 CLCH-SVX07C-EN
Component Installation Requirements
Size 51
24
242412 5
24
24
24
Size 57
24
24
24
24
.88
Size 58
12
12
24
24
24
24
24
24
24
5
Size 66
10.13
24
24
24
24
2424243.75
Size 80
24
243.75
Size 100
12
24
Size 120
24
249.13
24242424
24
24
24
2424242412
24
24
24
245.75
12
24
24
24
2412
2424242424
242424242424
54.00 ft ²
60.00 ft ²
62.00 ft ²
66.00 ft ²
24
1
6.63
1.13
1
1.13
1.13
106.00 ft ²
124.00 ft ²
86.00 ft ²
Figure 66. Front-loading bag and cartridge filter placement for unit size 57-120
CLCH-SVX07C-EN59
Component Installation Requirements
Size 3
12
24
2.88
Size 4
12
2415.38
2412
Size 6
24
30
Size 8
24
3.25
Size 10
24
24
8.25
30
Size 12
30
24
24
13.25
Size 14
24
18.75
30
24
Size 17
12
24
30
12
30
2.13
242424
Size 21
Size 22
30
30
24
2.25
30
24
24
3012 2.13
Size 25
Size 26
2.25
30
24
24
24
24
30
24
24
3.63
Size 30
24
30
Size 31
24
24
306.75
Size 35
30
30
24
3030
Size 36
24
24
2.13
Size 40
24
30
24
6
Size 41
242424 2.13
Size 50
12
30
24
24
5.0
2.75
6.75
24
3024
4.13
24
24
2424
30
30
30
303024
12
9
303012
242424
30
4.0
2.00 ft ²
2.00 ft ²
6.00 ft ²7.00 ft ²
10.00 ft ²
10.00 ft ²
10.00 ft ²
14.00 ft ²
21.00 ft ²
19.00 ft ²
24.00 ft ²
27.00 ft ²
28.00 ft ²
30.00 ft ²
30.00 ft ²
36.00 ft ²
37.00 ft ²
45.00 ft ²
46.00 ft ²
24 624
2424
6
242424
242424249
30
6
9
9
Figure 67. HEPA filter placement for unit size 3-50 - front loading
60 CLCH-SVX07C-EN
Size 51
30
12
3024 3.625
24
24
24
Size 57
24
30
24
24
5.0
Size 58
30
24
24
24
24
3024 3.625
Size 66
30
24
24
24
30301.375
Size 80
12
301.375
Size 100
12
Size 120
245.625
303024
24
24
24
30303012
30
30
30
242.75
12
30
30
30
3012
2424242424
48.00 ft ²
57.00 ft ²
56.00 ft ²
66.00 ft ²
76.00 ft ²
102.00 ft ²
119.00 ft ²
2424246
24242424246
242424242424
6
6
Figure 68. HEP A filter placement for unit size 57-120 - front loading
Component Installation Requirements
CLCH-SVX07C-EN61
Component Installation Requirements
Required
clearance
Tiedown
Required
clearance
Tiedown
Fan Section
The fan section can be configured as either draw-thru or
blow-thru. Review the submittals and unit tagging
information prior to assembly to determin e pl ace ment.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this manual could result in exposure
to electrical, mechanical or other potential safety
hazards. Always refer to the safety warnings provided
throughout this manual concerning these procedures.
Unless specified otherwise, disconnect all electrical
power including remote disconnect and disc ha rge all
energy storing devices such as capacitors before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licen sed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Fa ilure to
follow all of the recommended safety warnings
provided, could result in death or serious injury.
Fan Isolation
The fan-and-motor assembly is internally isolated. The fan
and motor bases are bolted to a minimum of four spr ing
isolators. The isolators are secured to the fan section
support base.
Shipping tie-down bolts are bolted adjacent to the
isolators between the fan isolation base and the isolator
support frame. The shipping tie-downs secure the
isolation base to the support assembly to prevent any
damage to the fan section during shipment.
Note: Remove the tie-downs only if the factory-pro vided
isolation is to be used.
Adjusting the Isolators
Once the shipping tie-downs are removed and the internal
isolation is released, it may be necessary to adjust the
isolators to achieve the proper operation height of the fan
and motor isolation base.
Minimum required clearances are listed in Table 10. To
determine the isolator clearances on all unit sizes,
measure between the top of the cabinet channel and the
bottom of the isolation base channel. See Figure 69,
Figure 70, Figure 71, and Figure 72.
Table 10. Minimum isolator clearances (inches)
Unit SizeFan Type
3–8FC, BC, Plenum1.0
10–31FC, AF, Plenum0.5
35-58FC, AF, Plenum0.5
66-120FC, AF, Plenum1.0
Required
Clearance
Figure 69. Isolator adjustment for unit sizes 10-30Figure 70. Isolator adjustment for unit sizes 10-30
Tiedown
Figure 71. Isolator adjustment for unit sizes 66-120
Require d
clearance
Figure 72. Belt-drive plenum fan isolator adjustment size
3-8
Required
clearance
62 CLCH-SVX07C-EN
Component Installation Requirements
Section
Base rail
Staggered anchor bolt patterns
Shipping split joint
Lifting
lugs
Anchor bolt
to floor curb
AHU Plan View
AHU Elevation View
Shipping split 1
Shipping split 2
Lifting lugs
Shipping split 1
Shipping split 2
Seismic Application
Requirements
Air handling equipment manufactured by Trane is capable
of structurally and operationally withstanding the seismic
response criteria as required by the International Building
Codes (IBC) 2000,2003, 2006, 2009. Trane has third-party
certification for IBC compliance for seismic applications
for unit sizes 3-30. Certification for larger sizes is in
process.
Note: If seismic isolation has been specified, the
following requirements must be adhered to for
installation. Failure to follow these instruction
would void the warranty.
Anchor Requirements
Single Level Design Break - Size 3-120
Grade to Roof Mounted (0<=Sds<=1.85) NonIsolated
4000 psi concrete
•3/8-inch diameter Hilti Kwik Bolt TZ carbon steel
concrete anchors attached to unit base rails.
•Install clips at shipping split corners
•Install clips at shipping splits containing fa ns or coils at
48 inches maximum on-center spacing.
•2-inch minimum anchor embedment
•4-3/8-inch minimum distance to the nearest edge
•4-inch minimum concrete slab thickness
Steel dunnage/steel curb
3/8-inch diameter ASTM A325 or SAE grade 5 bolts
attach ed to unit base located as noted above or 1-inc h long
3/16-inch welds at unit base located as noted above.
Steel dunnage/steel curb
1/2-inch diameter ASTM A325 or SAE Grade 5 bolts
attac hed to unit base located as noted above or 1-inch long
3/16-inch welds at unit bases located as noted above.
Anchor Pattern
Lifting lugs should be used to anchor the unit at the ends
of each shipping split. Per the anchor requirements,
additional anc horing may be needed. If so, anc hors will be
provided and installed on the unit. An example of a seismic
anchor is shown in Figure 73.
Anchor selection meets or exceeds IBC 2000, 2003, 2006
and 2009 compliance requirements.
Special Inspection per IBC Section 1 704 is requ ired on all
installations. All anchors listed above must be installed to
meet compliance.
•1/2-inch diameter Hilti Kwik Bolt TZ carbon steel
concrete anchors attached to unit base rails
•Install clips at all ship split corners.
•Install clips at ship splits with a stacked section at 36
inches maximum on-center spacing.
•Install clips at single level ship splits containing fans or
coils at 48 inches maximum on-center spacing.
•3 1/4-inch minimum anchor embedment
•7 1/2-inch minimum distance to the nearest edge
•6-inch minimum concrete slab thickness
CLCH-SVX07C-EN63
Component Installation Requirements
See Detail C
for hood support
installation
See Detail B
Install fastener to
substrate through only one
lug at this location
See Detail A
Hurricane Application
Requirements
Miami/Dade County Hurricane-Certified
Air Handlers
Performance Climate Changer air handlers size 3-30 are
approved and have has been designed to comply with the
High Velocity Hur ricane Zone of the Florida Building Code.
Notice of compliance and additional product construction
details can be found at the Miami-Dade County, Building
Code Compliance Office Web site.
Figure 75. Method for anchoring unit to substrate and roof curb
The Florida licensed engineer or arc hitect-of-record for the
project shall be responsible for the design, sizing, and
structural adequacy of the product framework as well as
curbing and attachment to the roof, or as accepted by the
corresponding buildin g de pa rtments.
Approved Method for Anchoring Unit
The method shown in Figure 75 through Figure 85 is what
is approved and recommended for anchoring the unit to
substrate and roof curb. Any deviation to this may require
the approval of the local building code enforcement
agency.
64 CLCH-SVX07C-EN
Hurricane Unit Anchorage
Detail A
First level base rail
First level lifting lug
Install fastener
one per lug, either hole
Substrate
Min embedment
Min edge
distance
Detail B
First level base rails
3-in.x3-in.x6-in. long
x 1/4-in. thick min. L-angle
clip, galv steel 36 ksi min.
Qty 5 screws per angle
Installation fastener
one per angle, centered
Substrate
Min embedment
Min edge
distance
Unit base panel
1/4-in. sheet
metal fasteners
Factory-supplied
drip lip
6-in. max O.C. for 0.119-in.
min roof curb thickness.
2-in. max O.C. for 0.047-in.
min roof curb thickness
Roof curb
by others
Figure 76. Typical direct anchorage to substrate at
lifting lugs (also see Table 11 )
Component Installation Requirements
Table 11. Installation anchor information
Minimum
1/2-inch powers chem-standard
Anchor/substrate
threaded rod installed with chemstandard adhesive capsule in 3.2 ksi
minimum concrete substrate
1/4-inch Elco dril-flex hex head schre
installed in 36 ksi minimum steel 1/8inch think minimum Ufull thread
engagement)
Minimum
embedment
1 1/2 inches6 inches
1/8 inch1/2 inch
Figure 78. Typical installation of unit baserail to curb
edge
distance
Figure 77.Typical direct anchorage to substrate using
L-clip in addition to lifting lugs (also see
Tab l e 11)
Note: Anchor spacing to be 24 inches maximum typical long side of unit.
CLCH-SVX07C-EN65
Component Installation Requirements
ItemDescription
1
2
3
Support bracket
L angle
1/4-14 x .75 sheet metal screw
3
1
2
3
Fasten bracket to bottom of
hood L angle (for hoods that
are lower to ground, may need
to flip the bracket (1) so the
short flange is pointing down
to the ground.
Detail C
Front and Back Hoods Only
Fasten ship-with angle
to support bracket
These brackets
are attached to
the unit baserail.
Attach the gas heat flue duct
to the L angles on both sides
Gas heat flue
See note
L bracket
Right side view
Note: When installing flue, leave enough clearance to avoid roof’s edge and anything above the roof.
#10 x 3/4-in. self-drilling
sheet metal screws
Figure 79. Installation of front and back hoods
Gas Heat Installation
Figure 80. Attach the gas heat flue duct to the L angles on both sides
66 CLCH-SVX07C-EN
Component Installation Requirements
ItemDescription
1
2
3
Nested U Channel
L angle
5/16-18 x .875 screw
3
1
2
Detail B
See Detail B
See Detail A
Step 1
Step 2
Step 3
Detail A
Pipe Cabinet Installation
Nested U Channels and L angle have to be removed to
install the pipe cabinet to the unit and reinstall per
1. Remove the fasteners from the top of the nested U
2. Remove the U c ha nnel from the unit base L angle and
hurricane certification guidelines. See Figure 81.
3. Remove the corner fasteners from the pipe cabinet
Figure 81. Instructions for pipe cabinet with nested U channels
channel.
the pipe cabinet base L angle.
base and the unit base L angle. These fasteners are not
required to be put back.
CLCH-SVX07C-EN67
Component Installation Requirements
Pipe cabinet wall
removed for clarity
Step 5
Step 4
Step 6
L angle attached
to unit baserail
Nested U channel
attached to L angle
Unsupported span
Size 3-50 - 52 in. max
Size 57-120 - 34 in. max
Air handler
Step 7
3
4. Attach the unit base L angle from the pipe cabinet to the
unit base rail. See Step 4 in Figure 82
5. Attach a U c hannel to the unit base L angle. Make sure
to clear any coil piping. Make sure to attach enough
nested U ch annels to comply to the unsuppor ted span.
See Step 5 in Figure 82.
Figure 82. Attaching L angles in pipe cabinet
6. Locate the pipe cabinet in place, and reinstall the U
channel to the pipe base L angle and reinstall the top U
channel to the nest (see Step 1, Figure 81).
7. When the L angle interferes with the unit base rail
lifting lugs or splice plate , mark and cut L angle section
to clear the component. If excess L angle is not needed
for nested U channel, leave it off. See Figure 82.
68 CLCH-SVX07C-EN
Pipe Cabinet Hurricane Anchorage
6-in. max O.C. for 0.119-in.
min roof curb thickness.
2-in. max O.C. for 0.047-in.
min roof curb thickness
Roof curb
by others
1/4-in. sheet
metal screws
3-in.x3-in.x6-in. long
x 1/4-in. thick min.
L-angle clip, galv steel
36 ksi min.
Qty 5 screws per angle
Installation fastener
one per angle, centered
Substrate
Min embedment
Min edge
distance
Baserail
3-in. min
panel left
or right
2-in. max
3-in. min
panel top
or bottom
Field-drilled hole detail
Figure 83. Typical installation of pipe cabinet baserail to
curb
Figure 84. Typical direct anchorage pipe cabinet
baserail to substrate with L clip
Component Installation Requirements
Figure 85. Pipe-cabinet approved field penetrations
Damper Sectio n
Dampers are factory-installed and adjusted and can be
found in mixing box/economizer sections. There are two
damper blade configurations available: parallel-blade and
opposed-blade.
Traq™ dampers ar e ano t her type of damper available in
mixing box sections. Traq dampers have only one blade
configuration - opposed. They have two control
applications available - standard Traq dampers and lowflow T raq dampers. Low-flow Traq dampers are always not
linked and consist of two damper sets - one set for
minimum outside air measurement and one set for
economizing. Each will have its own VCM.
The air handler is available with fac tory-mounted contro ls
or end devices. If the unit is not ordered with controls or
end devices, it is the installer’s responsibility to provide
and install the damper actuators. Size the actuators
according to Table 12.
Mixing section and economizer dampers are designed for
the damper actuators to be direct coupled and installed in
the air stream. If other provisions are required,
modifications to the section will be the responsibility of
the installing contractor.
CLCH-SVX07C-EN69
Component Installation Requirements
Damper Torque Requirements
Table 12. Mixing box damper torque requirements (inch pound) at 1-inch w.g. air pressure drop
Opposed-blade and parallel-blade airfoil dampers in unit
sizes 3-120, as well as internal and external face-andbypass sections, have centered dampers with an internal
jack-shaft (see Figure 86, Figure 87 and Figure 88). A 95-
degree actuator rotation gives a 90-degree blade travel.
Note: Damper blades should be checked for proper
operation from full open to full closed position
before unit start up. Damper blade positioning may
have chan ge d due to shipping and handling
vibrations.
Actuator
Qty
Figure 86. Typical mixing box configurations for unit sizes 3 to 120
78 CLCH-SVX07C-EN
Figure 87. Typical internal
Open
Close
Close
Damper blades
Damper
linkage bar
Damper
lever
Bearing
bracket assembly
BRK1756
Drive rod
SHF1709
Clip
CL0312
Complete Kit DMP0670
face-and-bypass
configuration
Figure 88. Typi cal external
face-and-bypass
configuration
Component Installation Requirements
5. Repeat steps 3 and 4 for the remaining zones.
6. Attach the damper operator drive rod to one blade axle
in each zone with the two-deck damper.
7. Use the self-drilling screws provided to mount the
bearing bracket assembly (see Figure 89).
Note: The drive rod kits ship in a separate box, found in
the fan module or the cold deck of the multizone
module.
Figure 89. Setting the zone damper rods an d da mper
linkage
Multizone Modules
Under certain operating conditions, condensation may
form on the cold deck portion of the multizone damper
section. T o prevent this, insulate around the damper rods.
Be sure the insulation does not affect damper operation.
Zone Damper Operators
Zone damper operators are available factory-mounted
with factory-mounted controls or as a stand-alone end
device. If not factory-provided, the contractor is
responsible for providing these operators. In all cases, the
damper operator should be connected to the drive rod.
Adjusting Zone Dampers
Zone dampers should be installed and adjusted prior to
making duct connections, assuring proper setup of the
damper zones:
1. Check the damper blades to confirm they are not
binding. The blade should rotate 90 degrees.
2. Determine the number of zones required. The zone
damper is fitted with a linkage bar that connects all
damper zones.
3. Select the number of damper segments required for
the first zone.
4. Cut a section out of the damper linkage bar just after
the last lever in that zone.
Note: It may be necessary to remove the damper linkage
bar to cut it. To remove the linkage bar pry the “ e ”
rings from the blade axles and remov e the bar.
Duct Connections
All duct connections to the air handlers should be installed
in accordance with the standards of the National Fire
Protection Association (NFPA):
•NFP A 90A for installing air conditioning and ventilating
systems other than residence type.
•NFP A 90B for resid ence-type wa rm air heating and airconditioning systems.
See unit submittal docum e nta tion for additional duct
mounting information.
Fan Discharge Connections
To ensure the highest fan efficiency, duct turns and
transitions must be made carefully , minimizing air friction
losses and turbulence. Proper ductwork installation, as
outlined by such organizations as Sheet Metal and Air
Conditioning Contractors National Association, Inc.
(SMACNA), should be followed closely.
Fan sections with rectangular and round openings have a
one-inch flange on the discharge that can be used to attach
the duct. When using lined ducts, the insulati on should not
obstruct the discharge opening. For plenum fan sections
with bell mouth fittings, see “Bell Mouth Discharge
Connections” on page 82.
CLCH-SVX07C-EN79
Component Installation Requirements
Splitters or
turning vanes
Vane turns in same
direction as fan rotation
3 fan
diameter
minimum
Unit
Section
Flat Connection
Uninsulated Duct
Airflow
Connections made directly to the discharge opening of a
housed fan should have a minimum of three fan diameters
of straight duct before any turns or transitions. The
ductwork should be the same size as the fan discharge
opening. The first turn of the connection should be in the
same direction as the fan rotation as shown in Figure 90.
The air that the fan discharges into the duct is extremely
turbulent and requires some length of duct to stabilize.
Abrupt change s in ductwork directly o ff the fa n disc harge
may adversely affect fan performance and acoustics.
Figure 90. Typical discharge ductwork
recommendations
Figure 91. Typical section with duct flat/flange
connection- uninsulated or externally
insulated
Damper Connections
Standard damper sections include mixing sections, filter
mixing sections, face dampers sections, internal face-andbypass sections, and economizer sections. There ar e two
damper blade configurations available - parallel-blade and
opposed-blade. Traq™ dampers are another type of
damper available in mixing box sections.
Ductwork attached to the standard damper sections
should be sized to fit the opening of the damper. Duct
opening dimensions are provide d in the submittals. When
using lined duct, ensure that the insulation does not
obstruct the damper opening (see Figure 91 and
Figure 92).
Note: Damper blades should be checked for pr oper
operation from full-open to full-closed position
before unit start up. Damper blade positioning may
have changed due to shipping and handling
vibrations.
Figure 92. Typical section with duct flat/flange
connection- internally insulated
Insulated Duct
Unit
Section
Airflow
Flat Connection
80 CLCH-SVX07C-EN
Component Installation Requirements
Bottom supply/
return airflow
Trane AHU
base (typical)
Field-supplied
rigid duct
Trane AHU
base (typical)
Field-supplied
rigid duct
Field-supplied
duct
Gasket
Supply opening
in floor
Roof Curb
Unit
wall
Unit floor
Building roofing
and structure
may vary per job
Unit base
3-50-14 ga
57-120-10 ga
3-120-10 ga
6 inches
1 in. flange
3-120-16 ga
Bottom Opening Duct Installation
3. Bottom of unit base elevation is flus h with duct
opening in bottom of unit (see Figure 94 and
1. Install gasket to duct flange to ensure air tight seal.
Figure 95).
2. Install duct into place underneath framed opening in
unit base per Figure 93. Refer to factory curb layout
provided with unit submittals for duct size and
location.
Figure 93. Field-supplied duct connection to AHU bottom supply/ret u rn air opening
Figure 94. Field-supplied duct connection details - curb mou nt
CLCH-SVX07C-EN81
Component Installation Requirements
Gasket
Supply opening
in floor
Unit
wall
Unit
floor
Building roofing
and structure
may vary per job
Unit base
3-57-3 inches
66-120-4 inches
1 in. flange
Field-supplied
duct
Figure 95. Field-supplied duct connection detai ls - pier mount
Discharge Plenum Connections
Discharge plenum sections are available with or without
openings. Sections with rectangular and round openings
have a framed opening that can be used to secure the duct
to the frames. If the duct is lined, it is important the
insulation does not obstruct the opening of the section.
For a discharge plenum with field-cut openings, attac h the
duct to the side panel.
Bell Mouth Discharge Connections
Round duct connections to be fastened to plenum fan and
discharge plenum sections with bell mouth discharge
openings should be sized to attach to the casing or directly
to the bell mouth fitting. Attac hment to the casing requires
the round duct diameter to be sized two inches larger than
the nominal bell mouth outlet. An angle ring with a flat
flange should be affixed to the round duct to secure the
duct to the casing (see Figure 96). Attachment to the bell
mouth fitting requires the duct and fitting to be insulated
by the installing contractor up to the bell mouth radius to
prevent condensation (see Figure 97). The bell mouth
fitting extends through the casing by one inch.
82 CLCH-SVX07C-EN
Component Installation Requirements
1 inch
Bell mouth
outlet nominal
diameter
1 inch
Round duct
Angle ring
Airflow
1 inch
Bell mouth
outlet nominal
diameter
Round
duct
1 inch
External
insulation
Airflow
Traq damper
mixing box
Inlet duct
Traq damper
mixing box
Radius elbow
(sweep)
Mitered
corner
W
d
H
d = 1 hydraulic duct diameter = 2 x W x H
W + H
Figure 96. Securing round duct to casing over bell
mouth outlet
Traq Damper Connections
Size the duct connections to attac h to the specified portion
on the face of the mixing box that the duct connection
completely covers all of the Traq damper.
Figure 97. Securing round duct to bel l mo uth outlet
For a mitered corner, provide one hydraulic duct diameter
between the entering face of the Traq dampers and the
duct turn. For a radius elbow, or sweep, place the elbow
directly against the face of the Traq dampers (see
Figure 98).
Figure 98. Traq damper duct connections
CLCH-SVX07C-EN83
Component Installation Requirements
Duct
Fan
External
face-and-bypass
Coil
Fan
Coil
Coil
External
face-and-bypass
Duct
Access
External Face-and-Bypass Connections
The external face-and-bypass damper sections will
require a field-fabricated duct to direct the bypass air into
the appropriate section. Duct sizing recommendations are
listed in Table 29.
When bypassing into an access section, remove a panel. It
is not necessary to cut an opening.
Figure 99. External face-and-bypass with duct
configuration designed to bypass air into a
vertical fan section
When attaching a bypass duct to a downstream fan section
or access section, the section will have a factory-provided
opening. (see Figure 99, Figure 100, and Figure 101.)
Figure 100. External face-and-bypass with duct configuration designed to bypass air around one coil
84 CLCH-SVX07C-EN
Component Installation Requirements
Fan
CoilCoil
External
face-and-bypass
Duct
Unit Section
End of unit
2-inch panel
Thermal
break
Uninsulated Duct
2-inch panel
Thermal
break
Airflow
Unit Section
End of unit
2-inch panel
Thermal
break
Internally insulated Duct
2-inch panel
Thermal
break
Airflow
Figure 101. External face-and-bypass with duct configuration designed to bypass air into a horizontal fan section
Other Connections
Access, filter, and other sections may have open inlets
with a 2-inch (sizes 3-1 20) panel frame for connecting the
ductwork. If the duct is lined, it is important the insulation
does not obstruct the opening of the section.
Figure 103. Typical duct flat/flan ge end of unit
connection - insulated
Figure 102. Typical duct flat/flange end of unit
connection - uninsulated
CLCH-SVX07C-EN85
Coil Piping and Connections
NOTICE:
Connection Leaks!
Use a backup wrench when attaching piping to coils
with copper headers to prevent damage to the coil
header. Do not use brass connectors because they
distort easily and could cause connection leaks.
NOTICE:
Over Tightening!
Do not use Teflon-based products for any field
connections because their high lubricity could allow
connections to be over-tightened, resulting in damage
to the coil header.
•Use pipe sealer on all thread connections.
•After completing the pipi ng conne ction s, seal aroun d
pipe from inner panel to outer panel.
Drain Pan Trapping
WARNING
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on
the drain pan could cause the supporting metal to
collapse, resulting in the operator/technician to fall.
Failure to follow this recommendation could result in
death or serious injury.
NOTICE:
NOTICE:
Leakage!
Properly seal all penetrations in unit casing. Failure to
seal penetrations from inner panel to outer panel could
result in unconditioned air entering the module, and
water infiltrating the insulation, resulting in equipment
damage.
General Recommendations
Proper installation, piping, and tr ap ping is necessary to
ensure satisfactory coil operation and to prevent
operational damage:
•Support all piping independently of the coils.
•Provide swing joints or flexible fittings on all
connections that are adjacent to heating coils to
absorb thermal expansion and contraction strains.
•If the coil was ordered with factory-mounte d controls,
install the control valves. The valves ship separately.
Note: The contractor is responsible for supplying the
installation hardware.
•For best results, use a short pipe nipple on the coil
headers prior to making any welded flange or welded
elbow type connections.
•Extended drain and vent connections are provided as
standard on D1 and D2 coils only. If extended drains
and vents are required on other water coils, they must
be field-installed or ordered as specials from the
factory.
•Pipe coils counterflow to airflow.
•When attaching the piping to the coil header , make the
connection only tight enough to prevent leaks.
Maximum recommended torque is 200 foot-pounds.
Water Damage!
When more than one module has a drain pain, trap
each module individually. Connecting all drains to a
common line with only one trap can result in
condensate retention and possible water damage to
the air handler or adjoining space.
Threaded condensate drain connections are provided on
only one side of the coil section. Pitch the connection lines
horizontal or downward toward an open drain. Trane
recommends installing a plug to facilitate cleaning of the
trap. The drain connection sizes are:
Unit size
NPT (national pipe thread) external
3-311-inch
35-581 1/4 inch
66-1201 1/2 inch
Figure 30 illustrates the proper trapping, piping, and
operation of the trap. Use the formula under the figure to
determine the correct minimu m depth for the condensate
trap. If a section has a drain pan for cleaning purposes
only, it does not need a trap; however, a cap or shutoff
valve should be installed on the drain connection. Only
sections handling condensate, such as a cooling coil
section or moisture eliminator section, require a trap.
connection
86 CLCH-SVX07C-EN
Table 30. Drain pan trapping for negative and positive pressure applications
H
J
L
Drain pan trapping for section
under negative pressure
L = H + J + pipe diameter where:
H = 1 inch for each inch of negative
pressure plus 1 inch
J = 1/2 H
Drain pan trapping for section
under positive pressure
L = H + J + pipe diameter where:
H = 1/2 inch (minimum)
J = 1/2 inch plus the unit positive static
pressure at coil discharge
(loaded filters)
Full size of
coil connection
ST
GV
MV
Steam main
Pitch down
VB
GV
Airflow
12 in. min.
FT
ST
12 in. min.
Full
size
of
main
VB
GV
ST
FT
Return main
Full size of
steam trap
connection
ST
FT
Coil Piping and Connections
Steam Coil Piping
Air handlers fitted with steam coils have labeled holes for
piping penetrations. Figure 104 illustrates a typical steam
coil piping configuration. See Table 31 for the codes of
system components in these figures.
The coil condensate return line must be piped full size of
the condensate trap connection, except for a short nipple
screwed directly into the coil header’s condensate return
tapping. Do not bush or reduce the coil return trapping
size.
Table 31. Code of system components for piping figures
CodeSystem component
FTFloat and thermostatic steam trap
GVGate valve
OVAutomatic two-position (ON-OFF) control valve
VBVacuum breaker
STStrainer
AVAutomatic or manual air vent
MVModulating control valve
Figure 104. Typical piping for Type NS steam coils and
horizontal tubes for horizontal airflow
CLCH-SVX07C-EN87
Coil Piping and Connections
NOTICE:
Breaker Cracking Pressure!
The 1/2-inch NPT, 15 degree swing check valve vacuum
breaker is recommended because oth er vacuum
breakers, such as spring-loaded ball-check breakers,
have cracking pressures as high as 1.25 inches Hg (17
inches of water). Vacuum breakers with fitting sizes
smaller than 1/2 inch NPT are too small to relieve
vacuum quick enough to ensure complete condensate
drainage. Other types of swing check valve vacuum
breakers ar e acceptable if the fittings siz e is not smaller
than 1/2-inch NPT and the cracking pressure is not
larger than 0.25 inches HG (3.5 inches of w ater). Failure
to follo w th ese in structions could result in equipment
damage.
To prevent coil damage, complete the following
recommendations:
•Install a 1/2-inch NPT, 15 degree swing check valve
vacuum breaker with cracking pressure of 0.25 inches
Hg (3.4 inches water) or lower at the top of the coil. This
vacuum breaker should be installed as close to the coil
as possible.
•For coil type NS, install the vacuum breaker in the
unused condensate return tapping at the top of the
coil.
•Vent the vacuum breaker line to atmosphere or
connect it into the return main a t the disc harge side of
the steam trap
Note: V acuum breaker relief is mandatory when the coil
is controlled by a modulating st eam supply or
automatic two position (ON-OFF) steam supply
valve. Vacuum breaker relief is also recommended
when face-and-bypass control is used.
NOTICE:
Coil Condensate!
Condensate must flow freely from the coil at all times
to prevent coil damage from water hammer, unequal
thermal stresses, freeze-up and/or corrosion. In all
steam coil installations, the condensate return
connections must be at the low point of the coil. Failure
to follo w th ese in structions could result in equipment
damage.
Proper steam trap installation is necessary for satisfactory
coil performance and service life. For steam trap
installation:
1. Install the steam trap discharge 12 inches below the
condensate return connection. Twelve inc hes provides
sufficient hydro static head pressure to overcome trap
losses and ensures complete condensate removal.
a. Use float and thermostatic traps with atmospheric
pressure gravity condensate return, with automatic
controls, or where the possibility of low-pressure
supply steam exists. (Float and thermostatic traps
are recommended because of gravity dr a in and
continuous discharge operation.)
b. Use bucket traps only when the supply steam is not
modulated and is 25 psig or higher .
Note: Trane steam coils require a minimum of 2 psi of
pressure to assure even heat distribution.
2. Trap each coil separately to prevent holding up
condensate in one or more of the coils.
3. Install strainers as close as possible to the inlet side of
the trap.
4. If installing coils in series airflow, control each coil
bank independently with an automatic steam-control
valve. Size the traps for each coil using the capacity of
the first coil in direction of airflow.
5. Use a modulating valve that has linear flow
characteristics to obtain gradual modulation of the coil
steam supply.
Note: Do not modulate systems with overhead or
pressurized returns unless the condensate is
drained by gravity into a receiver, vented to
atmosphere, and returned to the condensate
pump.
6. Pitch all supply and return steam piping down 1 inch
for every 10 feet in the direction of the steam or
condensate flow.
Note: Do not drain the steam mains or take-offs through
the coils. Drain the mains ahead of the coils
through a steam trap to the return line.
7. Ensure overhead returns have 1 psig of pressure at the
steam trap discharge for every 2 feet of elevation for
continuous condensate removal.
88 CLCH-SVX07C-EN
Coil Piping and Connections
GV
GV
GV
AV
AV
Water supply
main
Water
return main
Drain
Level
Air flow
AV
AV
AV
GV
Water supply
main
Water
return main
Drain
Air flow
Pitch down
Water Coil Piping
Figure 1 0 5 , and Figure 106 illustrate typical water coil
piping configurations.
T ype 5A, 5W , D1, W, UW , TT, P,2, P4, and P8 water coils are
self-venting only if the water velocity exceeds 1. 5 feet per
second (fps) in the coil tubes. Type D2, UA, UU, and WD
water coils are self-venting only if the water velocity
exceeds 2.5 fps in the coil tubes. See the unit submittals for
coil water velocity. If the water velocity is below these
minimums, vent the coil by one of the following methods:
Figure 105. Typical piping for type 5W one-row water coil
1. Install an air vent in the top pipe plug tapping of the
return header.
2. When the return line rises above the top of the coil,
vent from the top of the return header horizontally to
the return piping.
Note: TT coils are designed with larger than normal end
tube sheet holes to allow for maximum expansion.
Air leakage around tubes should be expected and
handled by capping over coil ends or by sealing
around tubes with a pliable sealant such as
silicone.
Figure 106. Typical piping for type 5A, 5W two-row, W 3- to 12-row, WD, D1, and D2 water coils
CLCH-SVX07C-EN89
Coil Piping and Connections
Pitch down
AV
AV
AV
Water
supply main
Water
return main
GV
Drain
Airflow
GV
MV
Figure 107. Typical piping for stacked water coils
Refrigerant Coil Piping
Note: Refer to for information on handling refrigerants.
Figure 1 08. Example of placement for split-system components
Discharge
line
Manual
angle valves
Compressors
Solenoid
valve
Access
port
Kit with sensor - X13790452010 SEN-01212
Kit with switch - X13100429010 THT 02442
sbucooler coil
Condenser and
Condensing unit
Evaporator coil
Check/relief
Expansion
valves
Distriburtor
valve
Moistureindicating
sight glass
Use Figure 108 to determine the proper, relative sequence
of the components in the refrigerant lines that connect the
condensing unit to an evaporator coil. Refer to “,” p . 9 3 for
more detailed schematics of evaporator piping.
Access
Manual
ball valve
Access
Manual
ball valve
port
Access
port
Liquid line
Manual ball valve
port
Manual
ball valve
Filter drier
with access
port
Suction lineFrostat™ control
Filter
90 CLCH-SVX07C-EN
Coil Piping and Connections
Cut here
for piping
Perforated plate
(packed elbow)
Panel
Venturi type
distributor
Coil
Liquid Lines
Line Sizing
Properly sizing the liquid line is critical to a successful splitsystem application. The selected tube diameter must
provide at least 5°F [2.7°C] of subcooling at the expansion
valve throughout the operating envelope. Increasing the
size of the liquid line will not increase the available
subcooling.
Routing. Install the liquid line with a slight slope in the
direction of flow so that it can be routed with the suction
line. Minimize tube bends and reducers because these
items tend to increase pressure drop and to reduce
subcooling at the expansion valve. Liquid line receivers,
other than those that are factory-installed, are not
recommended.
Insulation
The liquid line is generally warmer than the surrounding
air, so it does not require insulation. In fact, heat loss from
the liquid line improves system capacity because it
provides additional subcooling.
Components
Liquid-line refrigerant components necessary for a
successful job include a filter drier, access port, solenoid
valve, moisture-indicating sight glass, expansion valve(s),
and ball shutoff valves. Figure 108 illustrates the proper
sequence for positioning them in the liquid line. Position
the components as close to the evaporator as possible.
•Filter drier. There is no substitute for cleanliness during
system installation. The filter drier prevents residual
contaminants, introduced during installation, from
entering the expansion valve and solenoid valve.
•Access port. The access port allows the unit to be
charged with liquid refrigerant and is used to
determine subcooling. This port is usually a
Schraeder
•Solenoid valve. In split systems, solenoid valves
isolate the refrigerant from the evaporator during off
cycles; under certain conditions, they may also trim the
amount of active evaporator as compressor s unloa d.
Generally, the “trim” solenoid valve is unnecessary for
variable-air -volume comfort-cooling applications, and
is only required for constant-volume applications
when dehumidification is a concern.
•Moisture-indicating sight glass. Be sure to in stall one
moisture-indicating sight glass in the ma in liquid line.
The only value of the sight glass is its moisture
indication ability. Use actual measurements of
temperature and pressure—not the sight glass—to
determine subcooling and whether the system is
properly charged. The moisture indicator/sight glass
must be sized to matc h the si ze of the l iquid line at the
thermal expansion valve.
®
valve with a core.
•Thermal expansion valve. The expansion valve is the
throttling device that meters the refrigerant into the
evaporator coil. Metering too much refrigerant floods
the compressor; metering too little elevates the
compressor temperature. Choosing the correct size
and type of expansion valve is critical to assure it will
correctly meter refrigerant into the evaporator coil
throughout the entire operating envelope of the
system. Correct refrigerant distribution into the coil
requires an expansion valve for each distributor.
NOTICE:
Valve Damage!
Disassemble the thermal expansion valve before
completing the brazing connections. If necessary, wrap
the valve in a cool, wet cloth while brazing. Failure to
protect the valve from high temperatures could result
in damage to internal components.
The thermal expansion valve must be selected for proper
size and capacity. The size of the expansion valve should
cover the full range of loadings. Check that the valve will
successfully operate at the lightest load condition. For
improved modulation, choose expansion valves with
balanced port construction and external equalization.
Cut the process tube and cap assembly from the liquid
connection as shown in Figure 109 and install the
expansion valve directly to the liquid connections.
Figure 109. Type F refrigerant coil with packed elbow
CLCH-SVX07C-EN91
Coil Piping and Connections
Suction Lines
Line sizing
Proper suction-line sizing is required to guarantee the oil
returns to the compressor throughout the system’s
operating envelope. At the same time, the line must be
sized so that the pressure drop does not excessively affect
capacity or efficiency. To accomplish both objectives, it
may be necessary to use two different line diameters: one
for the horizontal run and for vertical drops, and another
for the vertical lifts.
Routing
To prevent residual or condensed refrigerant from “freeflowing” toward the compressor , install the suction line so
it slopes slightly—that is, by ¼ inch to 1 inch per 10 feet of
run—toward the evaporator. When the application
includes a suction riser, oil must be forced to travel the
height of the riser. Riser traps and double risers are
unnecessary in the suction line when the refrigerant coil is
used with Trane condensing units.
Avoid putting refrigerant lines undergro und. Refrigerant
condensation or installation debris inside the line, service
access, and abrasion/corrosion can quickly impair
reliability.
Insulation
Any heat that transfers from the surrounding air to the
cooler suction lines increases the load on the condenser
(reducing the system’s air-conditioning capacity) and
promotes condensate formation (adversely affecting
indoor air quality). After operating the system and testing
all fittings and joints to verify the system is leak-free,
insulate the suction lines all the way to inner side panel to
prevent heat gain and unwanted condensation.
Components
Installing the suction line requires field installation of
these components: a filter, access port, and a Frostat™
control when the refrigerant coil is used with Trane
condensing units. Position them as close to the
compressor as possible.
Note: Placement of the Frostat control is illustrated in
Figure 108 on page 90.
•Filter. The suction filter prevents contaminants,
introduced during installation, from entering the
compressor. For this reason, the suction filter should
be the replaceable-core type, and a clean core should
be installed after the system is cleaned up.
•Access port. The access port is used to determine
suction pressure. This port is usually a Schraeder valve
with a core.
•Frostat™ coil frost protection. The Fr ostat control is the
preferred method for protecting evaporator coils from
freezing when the refrigerant coil is used with Trane
condensing units. It senses the suction-line
temperature and temporarily disables mechanical
cooling if it detects frost conditions. The control is
mechanically attac hed to the outside of the refrigerant
line, near the evaporator, and wired to the unit control
panel.
•Ball shutoff valve. Adding manual, ball-type shutoff
valves upstream and downstream of the filter
simplifies replacement of the filter core.
92 CLCH-SVX07C-EN
Field-Installed Evaporator Piping Examples
Figure 110. Single-circuit condensing unit: evaporator coil with one distributor
Coil Piping and Connections
1. Pitch the liquid line slightly—1inch/10 feet —so that
the refrigerant drains toward the evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction header
toward the suction riser—that is, 1 inch/10feet in the
direction of flow. Use the tube diameter that matches
the suction-header connection.
4. For the vertical riser, use the tube diameter
recommended by the condensing unit manufacturer.
Assure the top of the riser is higher than the evaporator
coil.
5. Arrange the suction line so the refrigerant gas leaving
the coil flows downward, past the lowest suctionheader outlet, before turning upward.
6. Pitch the suction line slightly—1 inch/10 feet —so the
refrigerant drains toward the evaporator.
7. Insulate the suction line.
CLCH-SVX07C-EN93
Coil Piping and Connections
Suction line
7, 8
Liquid
line
Evaporator coil
with horizontal-split
(standard) circuiting
Evaporator coil with
intertwined circuiting
Liquid
line
‘Trim’
solenoid valve
‘Pump-down’
solenoid valve
Sight
glass
1
Filter drier
Filter drier
Solenoid
valve
Thermal
expansion
valve (TXV)
9
2
2
1
9
7, 8
3
4
4
5
5
6
6
3
3
Distributor
Thermal
expansion
valve (TXV)
Sight
glass
Distributor
S
S
S
Figure 111. Single-circuit condensing unit: evaporator coil with two distributors
1 . Pitch the liquid line slightly—1 inch/1 0feet —so
the refrigerant drains toward the evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction
header toward the suction riser—that is, 1 inch/
10 feet in the direction of flow. Use the tube
diameter that matches the suction-header
connection.
4. Arrange the suction line so the refrigerant gas
leaving the coil flows downw ard, past the lowest
suction-header outlet, before turning upward.
Use a double-elbow configuration to isolate the
thermal expansion valve bulb from other
suction headers.
5. For horizontal tubing, use the tube diameter
recommended by the condensing unit
manufacturer.
6. For the vertical riser, use the tube diameter
recommended by the condensing unit
manufacturer. Assure the top of the riser is
higher than the evaporator coil.
7. Pitch the suction line slightly—1 inch/10feet —
so the refrigerant drains toward the evaporator.
8. Insulate the suction line.
9. Only use a “trim” solenoid valve for constantvolume, humidity-sensitive applications. F or all
other applications, install a single solenoid valve
(the “pumpdown” solenoid valve) between the
liquid-line filter drier and the sight glass.
94 CLCH-SVX07C-EN
Figure 112. Single-Circuit Condensing Unit: Evaporator Coil with Four Distributors
1 . Pitch the liquid line slightly—1 inch/10 feet —so
the refrigerant drains toward the evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction
header toward the suction riser—that is, 1 inch/
10 feet in the direction of flow. Use the tube
diameter that matches the suction-header
connection.
4. Arrange the suction line so the refrigerant gas
leaving the coil flows downward, past the lowest
suction-header outlet, before turning upward.
Use a double-elbow configuration to isolate the
thermal expansion valve bulb from other
suction headers.
5. For horizontal tubing, use the tube diameter
recommended by the condensing unit
manufacturer.
6. For the vertical riser, use the tube diameter
recommended by the condensing unit
manufacturer. Assure the top of the riser is
higher than the evaporator coil.
7. Pitch the suction line slightly—1 inch/10feet —
so the refrigerant drains toward the evaporator.
8. Insulate the suction line.
Only use a “trim” solenoid valve for constantvolume, humidity-sensitive applications. For all
other applications, install a single solenoid valve
(the “pumpdown” solenoid valve) between the
liquid-line filter drier and the sight glass.
Coil Piping and Connections
CLCH-SVX07C-EN95
Coil Piping and Connections
Figure 113. Dual-circuit condensing unit: evaporator coil with two distributors
1. Pitch the liquid lines slightly—1inch/10feet —so the
refrigerant drains toward the evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction header
toward the suction riser—that is, 1 inch/10feet in the
direction of flow. Use the tube diameter that matches
the suction-header connection.
4. The top of the Circuit 1 suction riser must be higher
than the bottom evaporator coil. Use the tube diameter
recommended by the condensing unit manufacturer
for the riser.
5. Arrange the suction line so the refrigerant gas leaving
the coil flows downward, past the lowest suctionheader outlet, before turning upward.
6. The top of the Circuit 2 suction riser must be higher
than the top evaporator coil. Use the tube diameter
recommended by the condensing unit manufacturer
for the riser.
7. Pitch the suctio n lines slightly—1 inch/10 feet —so the
refrigerant drains toward the evaporator.
8. Insulate the suction lines.
96 CLCH-SVX07C-EN
Figure 114. Dual-circuit condensing unit: evaporator coil with four distributors
1 . Pitch the liquid line slightly—1 inch/10 feet —so
the refrigerant drains toward the evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction
header toward the suction riser—that is, 1 inch/
10 feet in the direction of flow. Use the tube
diameter that matches the suction-header
connection.
4. Arrange the suction line so the refrigerant gas
leaving the coil flows downw ard, past the lowest
suction-header outlet, before turning upward.
Use a double-elbow configuration to isol ate the
thermal expansion valve bulb from other
suction headers.
5. For horizontal tubing, use the tube diameter
recommended by the condensing unit
manufacturer.
6. For the vertical riser, use the tube diameter
recommended by the condensing unit
manufacturer. Assure the top of the riser is
higher than the evaporator coil.
7. Pitch the suction line slightly—1 inch/10 feet —
so the refrigerant drains toward the evaporator.
8. Insulate the suction line.
9. The top of the Circuit 1 suction riser must be
higher than the bottom evaporator coil. Use the
tube diameter recommended by the condensing
unit manufacturer for the riser.
10. The top of the Circuit 2 suction riser must be
higher than the top evaporator coil. Use the tube
diameter recommended by the condensing unit
manufacturer for the riser.
Coil Piping and Connections
CLCH-SVX07C-EN97
Coil Piping and Connections
Figure 115.Dual-circuit condensing unit: evaporator coil with eight distributors
1 . Pitch the liquid line slightly—1 inch/10 feet —so
the refrigerant drains toward the evaporator.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction
header toward the suction ris er—th at is, 1 inch/
10 feet in the direction of flow. Use the tube
diameter that matches the suction-header
connection.
4. Arrange the suction line so the refrigerant gas
leaving the coil flows downward, past the
lowest suction-header outlet, before turning
upward. Use a double-elbow configuration to
isolate the TXV bulb from other suction headers.
5. For horizontal tubing, use the tube diameter
recommended by the condensing unit
manufacturer.
6. For the vertical riser, use the tube diameter
recommended by the condensing unit
manufacturer. Assure the top of the riser is
higher than the evaporator coil.
7. Pitch the sucti on line slightly—1 inch/10 feet —
so the refrigerant drains toward the evaporator.
8. Insulate the suction line.
9. The top of the Circuit 1 suction riser must be
higher than the bottom evaporator coil. Use the
tube diameter recommended by the
condensing unit manufacturer for the riser.
10. The top of the Circuit 2 suction riser must be
higher than the top evaporator coil. Use the tube
diameter recommended by the condensing unit
manufacturer for the riser.
11. Only use a “trim” solenoid valve for cons tan tvolume, humidity-sensitive applications. For all
other applications, install a single solenoid
valve (the “pumpdown” solenoid valve)
between the liquid-line filter drier and the sight
glass.
98 CLCH-SVX07C-EN
Installation - Electrical
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriat e v oltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.
Units intended for indoor use are available with starters or
variable-frequency drives (VFDs) that are externally
mounted in an enclosure or internally mounted in a
recessed cabinet. Units intended for outdoor use are only
available with internally mounted starters or VFDs. A
typical internally mounted VFD is shown in Figure 116. A
typical externally mounted VFD is shown in Figure 117.
T ypical wiring schematics for VFDs and starters are shown
in Figure 123 and Figure 124, respectively. Unit specific
wiring schematics are shipped with each unit.
All units with starters or VFDs that have direct-digital
controllers (DDCs) are provided with line voltage to 24 V ac
power transformers as shown in Figure 118. When
provided, the line voltage to 24 Vac transformers are
factory wired to the supply fan power feed. All units with
factory-mounted controll ers, and no starters or VFDs, are
provided with 120 Vac to 24 Vac control transformers, as
shown in Figure 120, and require a separ ate 120V field
connection. As with starters or VFDs, units intended for
indoor use are available with DDCs mounted internally
(see Figure 118) or externally (see Figure 119 and
Figure 120), while units intended for outdoor use are only
available with internally mounted DDCs.
In units with 24Vac LED marine lights, the lights are wired
together to a single switc h located in the controls interface
module. Figure 119 shows a typical mounting of the
controls interface module with an externally mounted
controller. When DDCs are provided, the lighting circuit is
powered from the DDC power feed and does not require a
separate power source. When marine lights are provided
without DDCs, the lighting circuit requires a separate 120V
field connection that powers the lights through a 120V to
24Vac power transformer.
A mounted GFCI receptacle is provided for all units that
have DDCs or marine lights. The receptacle is mounted in
the controls interface module (see Figure 119) with the unit
light switch. The receptacle requires a separate 120V
power feed.
Figure 116. Internally
mounted VFD
CLCH-SVX07C-EN99
Figure 117. Externally
mounted VFD
Installation - Electrical
Figure 118. Internal controller
Field installed DDC control devices:
•Install outside-air sensor and space sensor, if ordered.
•Connect control valves, if ordered, to the valve jack
provided as part of the unit wiring harness. The valve
jack is typically located at the air-leaving side of the coil
connection inside the casing panel. F or valve junction
box mounting and wiring detail, see Figure 121.
Figure 121.
Junction box for valv e wiring
Figure 119. External mounted
controller
Figure 120. External controller
#10 self-drilling
screws (2)
Bushing
(2 required
for units with
double-wall)
Doublewall panel
End panel
2 x 4 junction box
Cover
Conduit
assembly
Airflow
Valve
connection
100 CLCH-SVX07C-EN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.