The P0V0 series modular blower is designed for installation
in a closet, utility room, alcove, basement, crawlspace or
attic. These versatile units are applicable to air conditioning
and heat pump applications. Several models are available
to meet the specific requirements of the outdoor
equipment.
SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
November 2021
1188--GGEE2200DD11--11EE--EENN
Page 2
SAFETY SECTION
MODULAR BLOWERS
IImmppoorrttaanntt:: This document contains a wiring diagram,
a parts list, and service information. This is
customer property and is to remain with
this unit. Please return to service
information pack upon completion of work.
IImmppoorrttaanntt:: These instructions do not cover all
variations in systems nor provide for every
possible contingency to be met in
connection with the installation. Should
further information be desired or should
particular problems arise which are not
covered sufficiently for the purchaser’s
purposes, the matter should be referred to
your installing dealer or local distributor.
IImmppoorrttaanntt:: Installation of this unit shall be made in
accordance with the National Electric Code,
NFPA No. 90A and 90B, and any other local
codes or utilities requirements.
NNoottee:: The modular blowers have been evaluated in
accordance with Intertek / ETL UL1995:2011 Ed.4
“SUITABLE FOR MOBILE HOME USE.”
NNoottee:: The manufacturer recommends installing ONLY
A.H.R.I approved, matched indoor and outdoor
systems. Some of the benefits of installing
approved matched indoor and outdoor split
systems are maximum efficiency, optimum
performance, and the best overall system
reliability.
•MULTI-POSITION UPFLOW, DOWNFLOW, HORIZONTAL LEFT
AND HORIZONTAL RIGHT
•PAINTED FINISH ON GALVANIZED STEEL EXTERIOR WITH
FULLY INSULATED CABINET THAT MEETS 4.0 R VALUE.
BLOWER COMPARTMENT INSULATION IS ONLY INSTALLED
IN B, C AND D SIZE PRODUCTS AND HAS A 2.1 R VALUE
•120 VAC OPERATION
•VARIABLE SPEED DIRECT DRIVE BLOWER
•SIDE AND BOTTOM RETURN
•MEETS THE MINIMUM LEAKAGE REQUIREMENTS FOR THE
FLORIDA AND CALIFORNIA BUILDING CODES
BAYFLTR203Horizontal Filter KitB Cabinet modular blowers in Downflow/
BAYFLTR204Horizontal Filter KitC Cabinet modular blowers in Downflow/
BAYFLTR205Horizontal Filter KitD Cabinet modular blowers in Downflow/
(a)
Airflow greater than 1600 CFM requires dual returns
(a)
Filter Access Door Kit (Downflow only)All modular blowers in Downflow orientation
1” SlimFit Box with MERV 4 FilterAll modular blowers
application
B Cabinet modular blowers only when in
bottom return application
Horizontal
Horizontal
Horizontal
18-GE20D1-1E-EN
5
Page 6
Location and Clearances
MODU
LAR BLOW
ER
O
”
21”
O
”
Minimum clearance to combustible materials
6
18-GE20D1-1E-EN
Page 7
Installation Instructions
1. UUnnppaacckkiinngg
Carefully unpack the unit and inspect the contents
for damage. If any damage is found at the time of
delivery, proper notification and claims should be
made with the carrier.
Check the rating plate to assure model number and
voltage match with what you ordered. The
manufacturer should be notified within 5 days of
any discrepancy or parts shortage.
2. LLooccaattiioonn
The modular blower should be centrally located
and may be installed in a closet, alcove, utility
room, basement, crawl space or attic. Minimum
clearances must be met.
When the unit is installed in a closet or utility room,
the room should be large enough, and have an
opening to allow replacement of the unit. All
servicing is done from the front and a clearance of
21" is needed for service unless the closet door
aligns with the front of the modular blower.
If you are installing the unit in an unconditioned
space such as an attic or crawl space, you must
ensure that the area provides sufficient air
circulation to prevent moisture collection on the
cabinet during high dew point conditions.
3. DDuucctt WWoorrkk
The duct work should be installed in accordance
with the NFPA No. 90A "Installation of Air
Conditioning and Ventilating systems" and No. 90B
"Residential Type Warm Air Heating and Air
Conditioning Installation."
The duct work should be insulated in accordance
with the applicable requirements for the particular
installation as required by HUD, FHA, VA the
applicable building code, local utility or other
governing body.
4. BBlloowweerr
This unit is supplied with a variable speed motor
with a direct drive blower wheel which can obtain
various air flows. The unit is shipped with factory
set cooling and heating air flows. Airflow
performance tables are available for additional air
flows. Be sure to check the air flow and the
temperature drop across the evaporator coil to
ensure sufficient air flow.
5. WWiirriinngg
Consult all schematic and pictorial wiring diagrams
of this unit and the outdoor equipment to
determine compatibility of wiring connections and
to determine specific requirements.
All field wiring to the modular blower should be
installed in accordance with the latest edition of the
National Electric Code NFPA No. 70 and any local
codes. Check rating plates on unit for rated volts,
minimum circuit ampacity and maximum over
current protection. Supply circuit power wiring
must be 75 degree C (167 degree F) minimum
copper conductors only. Copper supply wires shall
be sized to the National Electric Code or local code
requirements, whichever is more stringent.
The unit is shipped wired for 120 Volt AC 60 HZ 1
Phase Operation (Ensure unit is properly
grounded). Do Not use GFCI plug.
Class 2 low voltage control wiring should not be run
in conduit with power wiring and must be
separated from power wiring unless class 1 wire
with proper voltage rating is used.
Low voltage control wiring should be 18 AWG,
color coded (105 degree C minimum). For lengths
longer than 100ft., 16 AWG wire should be used.
Make certain that separation of control wiring and
power wiring has been maintained.
6. AAiirr FFiilltteerr
To protect the coil, blower and other internal parts
from excessive dirt and dust an air filter must be
installed before air enters the evaporator coil. A
remote filter must be installed. Consult the filter
manufacturer for proper sizing and maximum
velocity requirements.
7. TThheerrmmoossttaatt
Select a thermostat that is commonly used with HP
or AC two stage or Variable speed Heating/Cooling
outdoor unit. The thermostat will energize the fan
on a demand for heat or cool.
Install the thermostat on an inside wall, away from
drafts, lights or other heat sources in a location that
has sufficient air circulation from other rooms being
controlled by the thermostat.
To obtain proper performance, all units must be
operated and charge adjustments made in
accordance with procedures found in the Service
Facts document of the outdoor unit. After
installation has been completed, it is recommended
that the entire system be checked against the
checkout list located at the back of this document.
See
“Checkout Procedures,” p. 34.
9. MMaaiinntteennaannccee
The system air filter(s) should be inspected, cleaned
or replaced at least monthly. Make certain that the
access panels are replaced and secured properly
before placing the unit back in operation. This
product is designed for dependable service;
however, periodic maintenance should be
scheduled and conducted by trained professional
service personnel. This service should be
conducted at least annually, and should include
testing and inspection of electrical components.
The blower motor is permanently lubricated for
normal operating conditions.
8
18-GE20D1-1E-EN
Page 9
Outline Drawings
Table 3. 14.5” Width Cabinet
18-GE20D1-1E-EN
9
Page 10
OOuuttlliinnee DDrraawwiinnggss
Table 4. 17.5” Width Cabinet
10
18-GE20D1-1E-EN
Page 11
Table 5. 21” Width Cabinet
OOuuttlliinnee DDrraawwiinnggss
18-GE20D1-1E-EN
11
Page 12
OOuuttlliinnee DDrraawwiinnggss
Table 6. 24.5” Width Cabinet
12
18-GE20D1-1E-EN
Page 13
General Installation
Tinnerman clip locations
(if needed)
Shipping bracket
WHEN SUSPENDING THE HORIZONTAL
MODULAR BLOWER, IT SHOULD BE
SUSPENDED BY ATTACHING TO THE
CABINET IN THE PLACES SHOWN.
WHEN SUPPORTING THE
MODULAR BLOWER FROM
BELOW, SUPPORT FRONT
TO BACK (AS SHOWN)
OR SIDE TO SIDE.
The following sections give general instructions for the
installation of the modular blowers.
Panel Removal
Note: For the P0V0, a 1/4" nut driver is required to remove the two
screws at the top of the front panel. The front panel can then be
removed by lifting upwards.
Note: Tinnerman clips are provided in the doc pack if the door panel
flange hole(s) becomes stripped.
Note: Remove shipping bracket before installation.
Horizontal Installation in an Attic
or Crawlspace
The modular blower may be installed in an attic or
crawl space in the horizontal position by placing it on
its left or right side (as viewed from the front in the
vertical position). The horizontal installation in an attic
should be on a service platform large enough to allow
for proper clearances on all sides and service access to
the front of the modular blower. See
Clearances,” p. 6
between lines formed by intersections of the top and
two sides of the modular blower casing and building
joists, studs, or framing.
The modular blower may be placed horizontally in a
crawl space on a pad or other noncombustible
material. Place blocks underneath to support the
modular blower and raise the unit for sufficient
protection from moisture.
18-GE20D1-1E-EN
“Location and
. Line contact is only permissible
The modular blower may be installed hanging in a
hanging position using straps. The modular blower
should be supported at both ends and have an
additional support in the center of the modular blower
in back.
13
Page 14
GGeenneerraall IInnssttaallllaattiioonn
Duct Connections
Table 7. Supply Duct Connections
Upflow Modular Blower with Coil
1. Bend modular blower flanges up.
2. Set the coil on top of the modular blower.
3. Screw through the coil cabinet into the modular blower flange.
Guide holes are located on the coil.
Note: There are no longer guide holes located on the modular blower
flange.
4. Seal per local codes and requirements.
Modular Blower in Horizontal Left with Coil
1. Bend modular blower flanges up.
2. Support the modular blower and coil independently.
3. Screw through the coil cabinet into the modular blower flange.
Guide holes are located on the coil.
Note: There are no longer guide holes located on the modular blower
flange.
4. Seal per local codes and requirements.
14
18-GE20D1-1E-EN
Page 15
Modular Blower in Horizontal Right with “A” Coil
1. Bend modular blower flanges down.
2. Support the modular blower and coil independently.
3. Match the coil up flush to the back of the modular blower.
4. Seal per local codes and requirements.
Note: Flat or dedicated horizontal coils may require flanges to be bent
upward.
GGeenneerraall IInnssttaallllaattiioonn
Downflow Modular Blower with Coil
1. Bend modular blower flanges down.
2. Set the modular blower on top of the coil so that it is flush with the
back of the modular blower.
3. Seal per local codes and requirements.
18-GE20D1-1E-EN
15
Page 16
GGeenneerraall IInnssttaallllaattiioonn
Horizontal Right and Downflow Modular Blower — no Coil
1. Bend modular blower flanges up.
2. Attach ducting.
3. Seal per local codes and requirements.
16
18-GE20D1-1E-EN
Page 17
Table 8. Return Duct Connections
FILTER
Return Ducting General Guidelines
•Back returns are not allowed on any S-Series Modular blowers
•Side returns are not allowed on downflow or horizontal S-Series
Modular blowers
•Mounting flanges must be located on ducting
•Shoot screws through the mount flanges into the modular blower
cabinet
•Always seal per local codes and requirements
•Modular blower, coil, and ducting must be supported separately
•An external overflow drain pan must be installed in all applications
over a finished ceiling to prevent property damage
Upflow Modular Blower with Bottom Return in Closet with
Remote Filter
1. Remove the bottom plate.
2. Set the modular blower on the base inside closet.
3. Install remote filter.
4. Seal per local codes and requirements.
GGeenneerraall IInnssttaallllaattiioonn
Upflow Modular Blower with Bottom Return in Closet with
Filter Box
1. Remove the bottom plate.
2. Set the modular blower on the filter box inside closet.
3. Must have grille present for air.
4. Seal per local codes and requirements.
18-GE20D1-1E-EN
17
Page 18
FILTER
GGeenneerraall IInnssttaallllaattiioonn
Table 8. Return Duct Connections (continued)
Upflow Modular Blower with Bottom Return Mounted on a
Ducted Pedestal
1. Remove the bottom plate.
2. Set the modular blower on the ducted pedestal. The ducted
pedestal will use ducted air from a remote location.
3. Install filter at a remote location.
4. Seal per local codes and requirements.
Upflow Modular Blower with Bottom Return Mounted on a
Ducted Pedestal with Filter Box
1. Remove the bottom plate.
2. Set the modular blower on the filter box. The ducted pedestal will
use ducted air from a remote location.
3. Seal per local codes and requirements.
18
18-GE20D1-1E-EN
Page 19
Table 8. Return Duct Connections (continued)
FILTER
No Cut AreaCutouts
21” Filter Cabinet with BAYLIFT Kit shown
Flush with back
of furnace cabinet
Upflow Modular Blower with Bottom and Side Returns
Mounted on a Ducted Pedestal with Side Return and Filter Box
Important: Make sure the thermostat wiring hole is sealed on the
cabinet side with the side return.
Important: Make sure not to cut the cabinet in the “No Cut” area.
Important: Remove Blower Assembly and Panel Loop before cutting
cabinet to avoid cutting wires.
1. Remove the bottom plate.
2. Create ducting and set the modular blower in place.
Note: Use Optional BAYLIFT kit to lift modular blower. Follow kit
instructions.
Note: The modular blower bottom pedestal must be a minimum of 6”
in height.
3. Match the filter cabinet flush to the back and bottom sides of the
modular blower cabinet and secure in place with screws.
4. Mark the two areas to be cut out for the return air.
5. Cut out the two sections of the cabinet and BAYLIFT kit to be
removed.
6. Attach ducting to the filter box.
7. The ducted pedestal will use ducted air from a remote location.
8. Seal per local codes and requirements.
GGeenneerraall IInnssttaallllaattiioonn
Cabinet cutout when used with BAYLIFT
18-GE20D1-1E-EN
19
Page 20
Use four corner guides
to create cutout
No Cut Area
Use four corner guides
to create cutout
No Cut Area
GGeenneerraall IInnssttaallllaattiioonn
Table 8. Return Duct Connections (continued)
Upflow Modular Blower with Side Return
Important: Make sure the thermostat wiring hole is sealed on the
Important: Make sure not to cut the cabinet in the “No Cut” area.
Important: Remove Blower Assembly and Panel Loop before cutting
1. Using guides, remove the cutout for the side return.
2. Create ducting and set the modular blower in place. Use screws to
Note: If using a filter box, use a transition, if possible, to attach the
3. Seal bottom panel per local codes and requirements.
4. Seal all other panels per local codes and requirements.
cabinet side with the side return.
cabinet to avoid cutting wires.
attach ducting to the modular blower cabinet.
filter box to the modular blower cabinet.
Upflow Modular Blower with Two Side Returns
Important: One of the sides must have a transition to allow the
Important: If a transition is not a viable option, a hole will need to be
Important: Make sure not to cut the cabinet in the “No Cut” area.
Important: Remove Blower Assembly and Panel Loop before cutting
Note: If using one transition, the thermostat wiring will exit on the
1. Using guides, remove the two cutouts for the side returns.
2. Create ducting and set the modular blower in place. Use screws to
Note: If using a filter boxes, use transitions, if possible, to attach the
3. Seal bottom panel per local codes and requirements.
4. Seal all other panels per local codes and requirements.
thermostat wiring to exit the cabinet.
drilled in the side of the cabinet for the thermostat wiring
to exit.
cabinet to avoid cutting wires.
transition side.
attach ducting to the modular blower cabinet.
filter boxes to the modular blower cabinet.
20
18-GE20D1-1E-EN
Page 21
Table 8. Return Duct Connections (continued)
Downflow Modular Blower with Top Return
1. Remove the top plate.
2. Attach the ducting to the top of the modular blower.
3. Install remote filter.
4. Seal per local codes and requirements.
GGeenneerraall IInnssttaallllaattiioonn
Downflow Modular Blower with Top Return and Plenum
1. Remove the top plate.
2. Attach the plenum ducting to the top of the modular blower.
3. Install remote filter.
4. Seal per local codes and requirements.
18-GE20D1-1E-EN
21
Page 22
FILTER
GGeenneerraall IInnssttaallllaattiioonn
Table 8. Return Duct Connections (continued)
Downflow Modular Blower with Top Return and Plenum with
Filter Box
1. Remove the top plate.
2. Attach the filter box to the top of the modular blower.
3. Attach ducting.
4. Seal per local codes and requirements.
22
18-GE20D1-1E-EN
Page 23
Return Air Filters
*
*
*
*
UPFLOW MODULAR BLOWERS ONLY
LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT
* SEE OUTLINE DRAWING
FRONT OF
MODULAR BLOWER
TYPICAL AIR FILTER INSTALLATIONS
Filters are not factory supplied for modular blowers. Filter size needed
will be dependent on type of filter and CFM requirement. Filters must
be installed externally to the unit.
Important: It is recommended to transition return ducting to the
same size as the opening. It is acceptable for return duct
or filter frame to extend forward of the opening but
plastic plugs MUST be installed in any opening that the
duct or filter frame may cover.
Preparation for Upflow Bottom and Side Return Air Filter
Installations
All return air duct systems should provide for installation of return air
filters.
GGeenneerraall IInnssttaallllaattiioonn
Return Air Filters
Modular Blower WidthFilter
Qty and Size
14–1/2”1 — 14” x 25” x 1”
17–1/2”1 — 16” x 25” x 1”
21”1 — 20” x 25” x 1”
24–1/2”1 — 24” x 25” x 1”
Note: For upflow airflow modular blowers where the airflow
requirement exceeds 1600 CFM - modular blowers will
require return air openings and filters on: (1) both sides, or
(2) one side and the bottom, or (3) just on the bottom.
Important: Remove Blower Assembly and Panel Loop before cutting
1. Determine the appropriate position to set the modular blower in
2. For upflow side return installations, remove the insulation around
3. The side panels of the upflow modular blower include locating
4. If a 3/4" flange is to be used for attaching the air inlet duct, add to
5. If flanges are not required, and a filter frame is installed, cut
6. The bottom panel of the upflow modular blower must be removed
cabinet to avoid cutting wires.
order to connect to existing supply and return ductwork.
the opening in the blower compartment.
notches that are used as guides for cutting an opening for return
air, refer to the figure and the upflow modular blower outline
drawing for duct connection dimensions for various modular
blowers.
cut where indicated by dotted lines. Cut corners diagonally and
bend outward to form flange.
between locating notches as in illustration.
for bottom return air.
18-GE20D1-1E-EN
23
Page 24
FILTER
CLOSE COUPLED (LESS THAN 36”)
RETURN (FILTER DIRECTLY BENEATH BOTTOM
SIDE RETURN) NOT RECOMMENDED DUE TO
NOISE CONSIDERATIONS. IF USED, SECURELY
ATTACH 1/2” MESH METAL HARDWARE CLOTH
PROTECTIVE SCREEN TO THE INSIDE BOTTOM
OF THE FILTER GRILLE.
LESS THAN 36”
GGeenneerraall IInnssttaallllaattiioonn
1. When the modular blower is installed in the horizontal right or left
application and a return duct is attached to the top side, do not
install a filter in the return duct directly above the modular blower.
Install the filter in a remote location.
When the modular blower is installed in the horizontal right or left
application and a close coupled (less than 36") return duct is
attached to the bottom side of the modular blower as shown
above, securely attach a 1/2" mesh metal hardware cloth
protective screen to the inside bottom of the filter grille to
prevent personal injury from contacting moving parts
when reaching into the return opening to replace the filter.
Close coupled (less than 36") return (filter directly beneath
bottom side return) is not recommended due to noise
considerations.
2. Connect the duct work to the modular blower. See Outline
Drawing for supply and return duct size and location.
Flexible duct connectors are recommended to connect both
supply and return air ducts to the modular blower.
If only the front of the modular blower is accessible, it is
recommended that both supply and return air plenums are
removable.
3. When replacing an modular blower, old duct work should be
cleaned out. Thin cloths should be placed over the registers and
the modular blower fan should be run for 10 minutes. Don’t forget
to remove the cloths before you start the modular blower.
4. The horizontal installation of the upflow modular blower
requires an external filter section. Filter kits are available
for horizontal applications.
RETURN AIR FILTERS FOR MODULAR BLOWER IN
HORIZONTAL CONFIGURATION
When the modular blower is installed in the horizontal configuration,
the return air filters must be installed exterior to the modular blower
cabinet. Remote filter grilles may be used for homeowner convenience
or the filters may be installed in the duct work upstream of the
modular blower.
24
18-GE20D1-1E-EN
Page 25
O
BK
BK
Y2
Y1Y1
B/CB/C
W2
W1W1
GG
RR
O
Y1
B/C
Two Stage
Thermostat
Modular Blower
Integrated Modular Blower Control
Outdoor Unit
(No Transformer)
SEE
NOTE 2
BK JUMPER
SEE NOTE 1
Y2
W2
Y2
Disabled.
Applying 24VAC to
W1 or W2 will
create error
FIELD WIRING DIAGRAM FOR SINGLE OR TWO STAGE
THERMOSTAT, SINGLE OR TWO STAGE COOLING
NOTES:
1) For PWM (BK) enabled thermostats, cut the BK jumper
on the Integrated Modular Blower Control (IMBC) and
connect wiring.
2) The factory Y1-O jumper must remain in place for proper
LED read out in cooling mode.
3) Y1 and Y2 wiring from the thermostat must connect to
the IMBC for proper airflow and LED readout.
4) Single compressor and two compressor airflow is auto matically set with the IMBC Menu optionsin ODU section.
2-1=2 stage / 1 compressor (1st stage airflow = 80%)
2-2=2 stage / 2 compressors (1st stage airflow = 50%)
INTER-COMPONENT WIRING
24 V FIELD WIRING
24 V FACTORY WIRING
O
BK
BK
Y2
Y1Y1
B/CB/C
W2W2
W1W1
GG
RR
O
Y1
Two Stage
Thermostat
Outdoor Unit
(No Transformer)
SEE
NOTE 2
O
R
X2
Y2
NOTES:
1) For PWM (BK) enabled thermostats, cut the BK jumper
on the IMBC and connect wiring.
2) Remove the factory Y1-O jumper for HP systems
for proper LED read out.
3) Y1 and Y2 wiring from the thermostat must connect to Y1 and
Y2 of the IMBC for proper airflow and LED readout.
4) Single compressor and two compressor airflow is automatically
set with the IMBC Menu options in ODU section.
2-1=2 stage / 1 compressor (1st stage airflow = 80%)
2-2=2 stage / 2 compressors (1st stage airflow = 50%)
INTER-COMPONENT WIRING
24 V FIELD WIRING
24 V FACTORY WIRING
R-BK
JUMPER
SEE NOTE 1
FIELD WIRING DIAGRAM FOR SINGLE OR TWO
STAGE THERMOSTAT, SINGLE OR TWO STAGE HEAT PUMP
Integrated Modular Blower Control
Y2
B/C
Modular Blower
Disabled.
Applying 24VAC to W1 or
W2 will create error
GGeenneerraall IInnssttaallllaattiioonn
Electrical Connections
Make wiring connections to the unit as indicated on enclosed wiring diagram. This modular blower shall be connected into a permanently live
electric circuit. It is recommended that modular blower be provided with a separate "circuit protection device" electric circuit. The modular
blower must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code, ANSI/NFPA
70, if an external electrical source is utilized. The integrated modular blower control is polarity sensitive. The hot leg of the 120V power
supply must be connected to the black power lead as indicated on the wiring diagram.
Refer to the SERVICE FACTS literature and unit wiring diagram attached to modular blower.
Field Wiring
18-GE20D1-1E-EN
25
Page 26
R
W2
G
W1
B/C
O
Y2
Y1
BK
W2
G
W1
O
Y2
Y1
BK
Indoor Unit
Relay Panel
Communicating
Control
HUM
HUM
AUX1
AUX1
AUX2
AUX2
W3
STG2
FAN
STG1
SOV
D
R
B
STG2
STG1
PWM
HUM
HUM
AUX1
AUX1
AUX2
AUX2
STG3
24V
ONLY
24V
ONLY
24V
ONLY
D
R
B
COMMUNICATING CONTROLS WITH NON-COMMUNICATING MODULAR BLOWER
AND COMMUNICATING VS COOLING/HP
D
R
B
Outdoor Unit
NOTES:
1. Cut the BK jumper at the indoor unit - After cutting the jumper, power must
be off or cycled on-off-on for the IMBC to work properly
2. Requires an 850 control with software version 3.0+ or 1050. Not a valid
combination with 950 control
CPC=CFM/Ton cooling. Must be set to 400.
Control Board LED’s will read “
CoF
“ continous fan during cooling and
heat pump operation.
24 V Field Wiring
Disabled.
Applying 24VAC to
W1 or W2 will
create error
GGeenneerraall IInnssttaallllaattiioonn
26
18-GE20D1-1E-EN
Page 27
Integrated Modular Blower Control Menu
CLEARING THE LAST6 FAULTS:
To clear the stored faults, scroll to the last 6 faults
menu, enter the menu by scrolling to the right and
hold the “Opon” key for at least 5 seconds.
Release and a set of 3 dashes will be seen 3 mes.
This confirms the faults have been cleared
SETTING UP YOUR SYSTEM:
To change any factory default value, first remove any “call”
from the modular blower and allow any fan off delays to finish.
(
should be seen on the display)
Scroll to the selected Menu item by momentarily depressing
the “MENU” key and then depress the “OPTION” key to the
desired se"ng. Then momentarily depress the “MENU” key
again to save the change.
CFM per Ton selecons range from 290 – 450
Important:
When applied with zoning or a VSPD outdoor unit,
the CFM/Ton must be set to 400
Model ODT Op!ons [ ]= Default
Upflow
P0V0A 3T[3T], 1.5T, 2T, 2.5T
P0V0B 4T[4T], 2.5T, 3T, 3.5T
P0V0C 5T[5T], 3.5T, 4T, 4.5T
P0V0D 5T[5T], 3.5T, 4T, 4.5T
Designated Maximum 1st Stage Heat Pump Airflow Se#ng
ODU = 2-1 (1st stage airflow is 80% of the total airflow)
ODU = 2-2 (1st stage airflow is 50% of the total airflow)
Total airflow = CPH x Tonnage (400 x 3 = 1200)
Model Number Heang CFM
P0V0A000M30SCA 1000 (Total = 1240)
P0V0B000M40SCA
1200 (Total = 1440)
P0V0C000M50SCA 1400 (Total = 1680)
P0V0D000M50SCA 1400 (Total = 1680)
IdL
STATUS MENU
Err
ACTIVE ERRORS
CL1Arf
Example
1
st
Stage Cooling
Example
800 CFM
L6F
LAST 6 FAULTS
CR1
Control Release#
CR21
Example
So&ware Version #
COd
Cooing Off Delay
000090180EH
Example
seconds
Example
Enhanced Mode
ODT
OD Tonnage
3.0
Example
OD Nominal Tonnage
2.02.53.5
ODU
OD Unit Type
1-12-1
Example
Single Stage
COF
Connuous Fan
050025
Example
50% Cooling Airflow
CPC
Cooliing CFM
per Ton
350390
450
Example
CFM per Ton
000
HOD
Heat Off Delay
000
ISD
Inter-Stage Delay
000
GHC
Gas Heang CFM
P0V0
Control System Menu
2-2
Example
2 stage 1 compressor
Example
2 stage 2 compressor
080
CPH
Heang CFM
per Ton
Example
CFM per Ton
rUn
Run Test Mode
See Run Test Menu
350390
450
18-GE20D1-1E-EN
27
Page 28
P0V0
Examples of System Status
= Idle, no demand for cooling, hea!ng, or fan
= Demand for 1
st
stage cooling
= Demand for 2
nd
stage cooling
= Demand for 1
st
stage heat pump
= Demand for 2
nd
stage heat pump
= Demand for con!nuous fan
= Demand for outdoor unit defrost
/ = Calculated airflow is 800 CFM.
Airflow display is rounded down to the nearest 10 cfm
NOTES:
(1) The menu status displayed is solely dependent on the input of 24VAC
that is applied to the low voltage terminal strip.
(2) The status will alternate between the system mode and the airflow
request every 2 seconds.
(3) If an error occurs, an E*.* will alternately flash with the system mode
and airflow request.
(4) Some units will show demand airflow while others will show calculated airflow.
Calculated airflow will gradually ramp up and may take ~1-2 minutes to stabilize.
using the Menu key, then push the op!on key. The LED will flash three
!mes, then begin the test.
To exit the test mode, momentarily push the Menu key, cycle power to the
call for capacity or fan.
Sequence of Run Test Mode
– Turns the circula!ng blower on 1st stage compressor speed for 30 seconds
– Turns the circula!ng blower on 2nd stage compressor speed for 30 seconds
The above sequence will repeat two more !mes unless the Run Test Mode is exited, see above
Important: The Run Test Mode does not bring the outdoor unit on. It is designed to allow the technician to
observe each mode to ensure the IMBC, circula!ng blower are performing as intended. The run test
for the blower will take approximately 70 seconds to begin.
Note: During run test mode, depressing the option key will allow the user to hold (HLD) that test
sequence if measurements want to be taken. The exception is RU3 (ignitor).
1. To view the last 6 faults, press the “Menu” key until the “Last 6
Faults” (L6F) menu appears.
2. Enter the menu by pressing the “Option” key.
3. The last 6 faults can be viewed.
Clearing the Last 6 Faults
1. To clear the last 6 faults, press the “Menu” key until the “Last 6
Faults” (L6F) menu appears.
2. Enter the menu by pressing the “Option” key.
3. Hold the “Option” key for at least 5 seconds.
4. Release and a set of 3 dashes with be seen 3 times. This confirms
the faults have been cleared.
Resetting Factory Defaults
1. Display must be in Idle Mode.
2. Push the “Menu” and “Option” buttons at the same time for 15
seconds then release.
3. The 7 segment will flash “FD” 3 times. This confirms the unit has
been reset to the factory defaults.
18-GE20D1-1E-EN
31
Page 32
Sequence of Operation
NNoottee:: The seven segment LED readout is based on
thermostat input.
NNoottee:: Some units will show demand airflow while
others will show calculated airflow. Calculated
airflow will gradually ramp up and may take ~1-2
minutes to stabilize.
EEAACC aanndd HHUUMM TTiimmiinngg
•EAC relay closes approximately 2 seconds after the
blower starts.
•EAC relay opens when the blower motor stops.
•HUM relay closes on any heating call (HP)
approximately 1 second after the blower motor
starts.
•HUM relay opens when any heating call (HP) is
removed.
SSiinnggllee SSttaaggee CCoooolliinngg
1. R-Y1-G contacts on the thermostat close sending
24VAC to the Y1 and G low voltage terminals on the
IMBC. Technician should read 24VAC between Y1B/C and between G-B/C.
NNoottee:: Factory supplied Y1-O jumper must remain in
place for proper seven segment LED readout.
If removed, seven segment LED will read
HP1
”.
“
2. 24VAC is sent to the OD unit via thermostat wiring
energizing 1ststage compressor operation.
3. The indoor blower ramps to the 1
airflow. The seven segment LED for example will
alternately read:
CL1 = Cooling, Stage 1
ARF = Airflow
080 = 800 calculated cfm (value shown x 10)
4. When the temperature is lowered enough to satisfy
the thermostat setting, contacts R-Y1-G will open.
The OD unit shuts off and the indoor blower shuts
off, unless a blower off delay has been enabled in
the IMBC setup menu options. The seven segment
LED will read “IDL” = Idle, no thermostat demand.
TTwwoo SSttaaggee CCoooolliinngg
1. See sequence of operation for Single stage cooling
operation above (see steps 1-4).
2. R-Y2 contact on the thermostat closes sending
24VAC to Y2 low voltage terminal on the IMBC.
Technician should read 24VAC between Y2 and B/C.
3. 24VAC is sent to the OD unit via thermostat wiring.
4. The indoor airflow ramps to 2ndstage cooling
airflow. The seven segment LED for example will
read:
st
stage cooling
CL2 = Cooling, Stage 2
ARF = Airflow
160 = 1600 calculated cfm (value shown x 10)
5. When the temperature is lowered enough to satisfy
the thermostat setting, contacts R-Y1-Y2-G will
open.
6. The OD unit shuts off and the indoor blower shuts
off, unless a blower off delay has been enabled in
the IMBC setup menu options. The seven segment
LED will read “IDL” = Idle, no thermostat demand.
SSiinnggllee SSttaaggee HHeeaatt PPuummpp
1. R-Y1-G contacts on the thermostat close sending
24VAC to the Y1 and G low voltage terminals on the
IMBC. Technician should read 24VAC between Y1B/C and between G-B/C.
NNoottee:: Factory supplied Y1-O jumper must be
removed for proper seven segment LED
readout. If left in place, seven segment LED
CL1
will read “
2. 24VAC is sent to the OD unit via thermostat wiring
energizing 1ststage compressor operation.
3. The indoor blower ramps to the 1ststage heat
pump airflow. The seven segment LED for example
will alternately read:
HP1 = Heat Pump heating, Stage 1
ARF = Airflow
080 = 800 calculated cfm (value shown x 10)
4. When the temperature is raised enough to satisfy
the thermostat setting, contacts R-Y1-G will open.
The OD unit shuts off and the indoor blower shuts
off, unless a blower off delay has been enabled in
the IMBC setup menu options. The seven segment
LED will read “IDL” = Idle, no thermostat demand.
TTwwoo SSttaaggee HHeeaatt PPuummpp
1. See sequence of operation for Single stage heat
pump operation above (see steps 1-4).
2. R-Y2 contact on the thermostat closes sending
24VAC to Y2 low voltage terminal on the IMBC.
Technician should read 24VAC between Y2 and B/C.
3. 24VAC is sent to the OD unit via thermostat wiring
energizing 2
4. The indoor blower ramps to the 2ndstage heat
pump airflow. The seven segment LED for example
will alternately read:
HP2 = Heat Pump heating, Stage 2
ARF = Airflow
160 = 1600 calculated cfm (value shown x 10)
nd
”.
stage compressor operation.
32
18-GE20D1-1E-EN
Page 33
SSeeqquueennccee ooff OOppeerraattiioonn
5. When the temperature is raised enough to satisfy
the thermostat setting, contacts R-Y1-Y2-G will
open.
6. The OD unit shuts off and the indoor blower shuts
off. The seven segment LED will read “IDL” = Idle,
no thermostat demand.
18-GE20D1-1E-EN
33
Page 34
Checkout Procedures
The final phase of the installation is the system Checkout Procedures. The following list represents the most common items covered in a
Checkout Procedure. Confirm all requirements in this document have been met.
☐ All wiring connections are tight and properly secured.
☐ Voltage and running current are within limits.
☐ Ductwork is sealed and insulated.
☐ Supply registers and return grilles are open, unobstructed, and air
filter is installed.
☐ Indoor blower and outdoor fan are operating smoothly and
without obstruction.
☐ Indoor blower motor set on correct speed setting to deliver
required CFM. “Blower and fan set screws are tight.”
☐ Cover panels are in place and properly tightened.
☐ System functions safely and properly in all modes.
☐ Owner has been instructed on use of system and given manual.
34
18-GE20D1-1E-EN
Page 35
NNootteess
18-GE20D1-1E-EN
35
Page 36
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For
more information, please visit www.trane.com or www.americanstandardair.com.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to
using environmentally conscious print practices.