Toshiba TOSVERT VF-FS1 series Function Manual

E6581404
TOSVERT VF-FS1 series
BACnet® option unit
Communication Function Manual
NOTICE
1. Make sure that this function manual is delivered to the end user of BACnet
®
option
unit.
2. Read this manual before installing or operating the BACnet
®
option unit. Keep it in a
safe place for reference.
3. All information contained in this manual are subject to change without notice. Please confirm the latest information on our web site “www.inverter.co.jp”.
E6581404
Introduction
Thank you for purchasing the “BACnet® option unit” for TOSVERT VF-FS1 series Inverter. Before using BACnet® option unit, carefully read this function manual in order to completely and correctly utilize its excellent performance. After reading this function manual, please keep it handy for future reference. For details of its general handling, see an instruction manual attached with the option unit.
TOSVERT VF-FS1 Instruction Manual ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ E6581381 TOSVERT VF-FS1 Communications Function Instruction Manual ・・・・・・・・ E6581393 BCN002Z Instruction Manual ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ E6581402
* BACnet is a registered trademark of ASHRAE.
Handling in general
Danger
Do not connect or disconnect a network cable while the Inverter power is on.
It may lead to electric shocks or fire.
Prohibited
See the instruction manual attached with the option unit for cautions the handling.
Otherwise, it may lead to electric shocks, fire, injuries or damage to product.
Mandatory
Network control
Danger
Do not send the value out of the valid range to network variables.
Otherwise, the motor may suddenly start/stop and that may result in injuries.
Prohibited
Mandatory
Use an additional safety device with your system to prevent a serious accident due to the
network malfunctions. Usage without an additional safety device may cause an accident.
Warning
Set up “Communication error trip function (see below)” to stop the Inverter when the
option unit is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc.
- Communication error trip time, Operation at communication error (f803 ,f892 and f851, see the Inverter instruction manual for details)
Deactivated option unit may cause an accident, if the “Communication error trip function” is not properly set up.
Make sure that the operation signals are STOP before resetting Inverter’s fault. The
motor may suddenly start and that may result in injuries.
Mandatory
Notes on operation
Notes
When the control power is shut off by the instantaneous power failure, communication
will be unavailable for a while.
The Life of EEPROM is approximately 10000 times. Avoid writing a command more than
10000 times to the same parameter of the Inverter and the communication board.
- 1 -
E6581404
Table of Contents
1. Scope ..................................................................................................................................................3
1.1. Overview ....................................................................................................................................3
2. Names and functions of main parts.....................................................................................................3
2.1. Name of main parts....................................................................................................................3
2.2. Use of RS485 communication port........................................................................................... .4
2.3. LED indicator..............................................................................................................................4
2.4. Command & Setpoint selection (Local/Remote)........................................................................5
2.5. Description of terminals .............................................................................................................6
2.6. Network cable connection..........................................................................................................7
2.7. Network configuration ................................................................................................................7
2.8. Wiring of a control terminal ........................................................................................................8
3. Parameters..........................................................................................................................................9
3.1. Communication parameters.......................................................................................................9
3.2. Communication setting between option board.........................................................................10
3.3. Communication error detection between inverter and option board........................................10
3.4. Selection of the communication protocol (f829).................................................................10
3.5. Number of motor poles for communication (f856)..............................................................10
3.6. Network address (f890)......................................................................................................10
3.7. Network baud rate (f891)....................................................................................................10
3.8. Instance Number (f893, f894).......................................................................................10
3.9. MaxMaster (f895) ...............................................................................................................10
3.10. MaxInfoFrames (f896)........................................................................................................10
3.11. Use the communication option.................................................................................................11
4. Functions...........................................................................................................................................12
4.1. Object / Property support Matrix..............................................................................................12
4.2. Drive I/O Objects......................................................................................................................13
4.2.1. Binary Input Object Instance...........................................................................................13
4.2.2. Binary Input Object Instance...........................................................................................13
4.2.3. Analog Output Object Instance .......................................................................................13
4.3. Control objects.........................................................................................................................14
4.3.1. Binary Value Objects Instance........................................................................................14
4.3.2. Analog Value Objects Instance.......................................................................................15
4.4. Device Objects.........................................................................................................................15
4.5. Parameter access....................................................................................................................16
4.6. Option Error..............................................................................................................................16
5. Specifications ....................................................................................................................................17
5.1. BACnet Protocol Implementation Conformance Statement ....................................................18
- 2 -
E6581404
1. Scope
1.1. Overview
Thank you for purchasing a “BACnet communication Option (BCN002Z)” for TOSVERT VF-FS1 inverter. This option can connect with open field network BACnet MS/TP network and data communications with the network through installing this option in the VF-FS1 and using it. BACnet MS/TP supports a maximum of 32 nodes for one segment. By attaching BCN002Z to VF-FS1, the monitor of run/stop and the setting change of the parameter become possible from the network, and it can cope with various application.
This manual is also aimed at the operator using "VF-FS1 BACnet option", so please use it for future maintenance and inspection.
2. Names and functions of main parts
2.1. Name of main parts
Detachable terminal Network communication
Communication condition monitor LED
Input terminal SINK/SOURCE VIB/PTC select SW
Optional RS485 communication port RS485 communication option can be used. However it makes BACnet Communication be disabled.
B A GND SCR
Connector
Termination
resistor SW
Terminal board fixing screw hole
(M3 screw)
- 3 -
E6581404
2.2. Use of RS485 communication port
Serial communication (2-wire RS485) option can be used. However, while it is connected, the internal communication line is switched to RS485 then the communication via BACnet network is disabled and the data can not be refreshed. In this case, communication error trip time (f803) is also active. Use RS485 serial communication option specified by Toshiba.
2.3. LED indicator
The option has two LEDs. Those functions are below table.
COM Green
ERR Red
1s
OFF
2s
OFF
1s 1s
ON
ABC EF
2s
OFF
1s
D
State
LEDs
Comment
A
Green LED : OFF Red LED : Flashing 5 times in 1 second
BACnet board failure
B
Green LED : OFF Red LED :
Flashing 3 times in 2 seconds, Off for 1 second
Communication loss detected. Confirm the network condition and connection of the cable.
C
Green LED : ON Red LED : OFF 0.5s, ON 0.5s
Invalid configuration detected (ADR > max master), or an option is connected to RJ45.
D
Green LED :
Flashing 3 times in 2 seconds, Off for 1 second
Red LED : OFF
Waiting for Auto baudrate detection
E
Green LED : Flashing Intermittent Green Red LED : ---
Valid message received for this node
F
Green LED : --­Red LED : Flashing Intermittent Red
Invalid message received (any node)
- 4 -
E6581404
2.4. Command & Setpoint selection (Local/Remote)
Indication to display Local/Remote mode is on the inverter unit (Refer to the inverter instruction manual for details). BACnet option command and setpoint are activated on Remote mode
*1
. Inverters have some switches to select the command and setpoint location. Following figure shows the diagram. Refer to the inverter instruction manual for the parameter in detail.
*1 Be careful that cmod command and fmod setpoint are activated for a short time just after the
inverter power turned on. Set cmod and fmod to “network” to prevent this problem.
Command
Setpoint
Control T e rminal Operation Pan el
Serial Com.(BACnet)
VI
A
VIB
Operation Pan el
Serial Com.(BACnet)
UP/DOWN
Operation
Panel
Serial Com.
(BACnet)
Operation
Panel
Local/Remote key
cmod
fmod
Logic input = 48 (SC/LC)
Network cancel switch
1 2 3 4 5
0 1 2
1
0
1
0
REM
LOC
Serial Com.
(BACnet)
0
1
0
1
Binary Value #22
REM
LOC
Binary Value #21
- 5 -
E6581404
2.5. Description of terminals
<Control terminals specification>
Terminal
symbol
Function Electrical specifications Internal circuits
B Communication signal (+) A Communication signal (-)
GND Signal common
SCR
BACnet communication signal EIA-485
Shield terminal. Connect to network ground
B A
GND
SCR
47k
47k
4.7k
4.7k
120
SW4
TERM
F
R
Multifunctional programmable contact input.
SINK/SOURCE can be selected with SW.
No voltage contact input 24V
DC
, 5mA or less
N.B. Use contact parts for low
current.
F, R
CC
P24
P24
4.7k
PTC
SOURCESINK
820
VIB
Multifunction programmable analog input. with internal pull-up resistor for PTC
0 to 10V
DC
input Using this terminal as PTC input, set SW2 to PTC side and set the parameters (f645 and f646) to proper value.
VIB
15k
VIB
P10
PTC
15k
3.3k
CC
Control circuit’s equipotential terminal
P24 24 VDC power supply output 24VDC-50mA
P24
P24
PTC
FLA FLB FLC
Multifunctional programmable relay contact outputs
1c contact 30V
DC
-0.5A
250V
AC
-1A (cosφ =1
250V
AC
-0.5A (cosφ =0.4)
FLA FLB
FLC
Ry
Danger
Prohibited
Do not change switches settings while the power is on.
It may lead to electric shocks or damage.
Mandatory
Turn off the motor operation signals before setting the parameter and the switch
(SW), when changing the VIB function. Otherwise, the motor may suddenly start and that may result in injuries.
- 6 -
E6581404
2.6. Network cable connection
Connect the BACnet network cable to communication option as follows.
Title Description
Wire type Shielded twisted cable
Characteristic impedance Between 100 and 130 ohm
Distributed impedance between
conductors
Less than 100pF per meter
Distributed impedance between
conductors and shield
Less than 200pF per meter Foil or braided shields are acceptable.
Length of an MSTP segment 1200 meters with AWG18 (0.8mm2)
Cable sheath should be peeled off by about 7mm. For wiring work, use a flat blade screwdriver with a 0.6mm thick and
3.5mm width blade. Tightening torque for the terminal block is 0.5Nm.
* Fix a cable so that a communication connector may be not taken the weight of wire.
mm
2.7. Network configuration
Make up the network as follows.
- Transmission/reception signals (A, B) Make up the communication path by connecting all transmission/reception data cables.
- Signal common (GND) GND is the signal common.
- Grounding the shield of cable (SCR) Connect the all shield lines of network cable. The shield shall be grounded at one end only prevent currents from being created.
- Termination resistor A termination resistance of 120 ohms plus or minus 5% shall be connected at each of the two ends of the segment medium. This option has a termination resistor, so if use, set up the termination resistor SW. (Refer to
2.1Name of main parts) At least one set, and no more than two sets, of network bias resistors shall exist for each segment. This option has local bias resistors.
Termination
B
A
GND
+5
510
510
Node with network
bias resistors
120
B
A
GND
Node without bias resistors
B
A
GND
+5
47k
Node with local bias resistors
This option board
47k
4.7k
4.7k
Termination
120
SCR
Communication
cable
Communication
cable
SCRSCR
SW4
TERM
N.B.:Do not connect the SCR terminal to the power ground of inverters or other units.
Keep the network cables 20cm or more separate from the power cables to prevent from malfunctioning due to electromagnetic noise.
- 7 -
E6581404
2.8. Wiring of a control terminal
Observe the following when wiring.
- Use 0.3 to 1.5mm2 solid/stranded wire (AWG 22 to 16) for control cables.
- Remove the sheath of a cable about 7mm (6mm for FLA, FLB, FLC and G/E) from the end of cable.
- Use a flat-headed screwdriver with its blade 0.6mm in thickness and 3.5mm in width.
- Screw tightening torque for the terminal block screws should be 0.5 to 0.6Nm.
N.B.: Keep the control signal cables 20cm or more separate from the power cables
to prevent from
malfunctioning due to electromagnetic noise.
N.B.: Provide an inter-lock system stated in below, when using a programmable controller that has the
open collector output. When the programmable controller is turned off with the inverter is on, the difference between each control power potential will cause wrong signals to the inverter as shown in below figure. Provide an inter-lock so that the programmable controller cannot be turned off when the inverter power is alive.
COM
+24V
Inverter internal +24V
External +24V supply
VF-FS1 + BCN002ZProgrammable controller
Input terminal
Fuse blowout detection circuit
Fuse
- 8 -
E6581404
3. Parameters
3.1. Communication parameters
Set up the inverter parameters as follows. To update, reset the power of inverter. If these parameters are set to correct value, this unit can not work normally.
Title Function Description
Shipment
setting
BACnet
cmod Command mode selection
0: Terminal board 1: Operation panel 2: Serial communication
0 2
fmod
Frequency setting mode selection 1
1: VIA 2: VIB 3: Operation panel 4: Serial communication 5: UP/DOWN from external contact
1 4
f800 Communication rate Set “1: 19200bps” (default). 1 1 f801 Parity Set “1: Even” (default). 1 1
f803 Communication error trip time
Set communication time out period. The way of stop is selected by f603.
0 ---
f829 Communication protocol Set “4: BACnet protocol” 0 4
f851
Operation at communication error by disconnection
0: Inverter stop, communication command,
frequency mode open (by cmod,
fmod) 1: None (continued operation) 2: Deceleration stop 3: Coast stop 4: Communication error (err5 trip) or Network error (err8 trip)
4 ---
f856
Number of motor poles for communication
1: 2 poles
5: 10 poles
2: 4 poles 6: 12 poles 3: 6 poles 7: 14 poles 4: 8 poles 8: 16 poles
2 ---
f890 Address Set node address 0 ---
f891 Network baud rate
0: AUTO adaptive 1: 9600 2: 19.2kbps 3: 38.4kbps 4: 76.8kbps Over 5 is AUTO adaptive.
0 ---
f892 Network Time-Out
0: No action Unit 0.1sec, Setting range : 1 to 65535
0 ---
f893 0 --- f894
Instance number Instance No.= f893 x 1000 + f894
0 ---
f895 MaxMaster
Setting range : 0 to 127 Over 127 is limited 127.
0 ---
f896 MaxInfoFrame
Setting range : 0 to 100 Over 100 is limited 100.
0 ---
Warning
Mandatory
Set up “Communication error trip function (f803, see the inverter instruction manual
for details)” to stop the inverter when this option unit is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc. Deactivated option unit may cause an accident, if the “Communication error trip function” is not properly set up.
- 9 -
E6581404
3.2. Communication setting between option board
Do not change communication rate (f800), parity (f801) and communication waiting time (f805) from shipment setting. If change the setting, the option board does not work properly.
3.3. Communication error detection between inverter and option board
Set the communication loss action time to f803 between the inverter and the option board. And the network communication loss action time to f892. The network loss action function starts from receiving the properly frame message. The action of the network communication loss is set by f851. When set the communication loss action time f803 and connect the option to the RJ45 connector, the communication between the inverter and the option is disabled, so the communication loss may be detected.
3.4. Selection of the communication protocol (f829)
Set the communication protocol f829 to “4:BACnet protocol”. The communication protocol of RJ45 is set to MODBUS, so when communicate with PC, use MODBUS protocol.
3.5. Number of motor poles for communication (f856)
Set the motor pole number of using. This parameter is for the calculation of min-1 unit motor speed of BACnet data.
3.6. Network address (f890)
Set the network address of this node. Do not set same address number in the segment, and not set over MaxMaster (f895). If set wrong number, the option board does not work properly.
3.7. Network baud rate (f891)
Set the network baud rate to f891. Set the same baud rate data in the network. If set AUTO baud rate, when the option detect network baud rate, the option sets the baud rate data to f891 automatically.
3.8. Instance Number (f893, f894)
Set BACnet Object Instance number. The instance number should not be duplicate in the network. The instance number is 22bit data length, and set the number of this option board as below.
Instance number = f893 x 1000 + f894
3.9. MaxMaster (f895)
Set the max master number of this segment. The network poles to MaxMaster address to find master node, so set MaxMaster to be small number to be a small response time.
3.10. MaxInfoFrames (f896)
Set the max information frame number to send from this node. Not need to change.
- 10 -
E6581404
3.11. Use the communication option
Serial communication (2-wire RS485) option can be used. However, while it is connected, the internal communication line is switched to RS485 then the communication via BACnet network is disabled. In this case, communication error trip time (f803) is also active. Use RS485 serial communication option specified by Toshiba
- 11 -
E6581404
4. Functions
This option board is based on BACnet “Application Specific Controller” (B-ASC).
4.1. Object / Property support Matrix
This option board supports below table objects and properties.
Object Type
Property
Device
Binary
Input
Binary
Output
Binary
Value
Analog
Input
Analog Output
Analog
Value
Object Identifier
Object Name
Object Type
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Revision
Appl Software Revision
Protocol Version
Protocol Revision
Services Supported
Object Types Supported
Object List
Max APDU Length
Segmentation Support
APDU Timeout
Number APDU Retries
Max Master
Max Info Frames
Device Address Binding
Database Revision
Present Value
Status Flags
Event State
Out-of-Service
Units
Priority Array  *1  *1
Relinquish Default  *1  *1
Polarity
Active Text
Inactive Text
*1: For commandable values only.
- 12 -
E6581404
4.2. Drive I/O Objects
4.2.1. Binary Input Object Instance
The output terminals and the input terminals can be monitored.
Binary Input
Instance ID Object Name VFFS1 Description
Active / Inactive
Access
Binary input #0 RO 1 ACT FL Output terminal monitor ON / OF F R Binary input #1 RO 2 ACT RY Output terminal monitor ON / OF F R Binary input #2 --- --- Reserve --- --­Binary input #3 --- --- Reserve --- --­Binary input #4 --- --- Reserve --- --­Binary input #5 --- --- Reserve --- --­Binary input #6 DI 1 ACT F Input terminal monitor ON / OFF R Binary input #7 DI 2 ACT R Input terminal monitor ON / OFF R
4.2.2. Binary Input Object Instance
The output terminals can be controlled via network. Set the terminal function parameter before control via network.
Binary Output
Instance ID Object Name VFFS1 Description
Active / Inactive
Access
Binary Output #0 RO 1 CMD FL
Output terminal function Set f132 to 38.
ON / OFF C
4.2.3. Analog Output Object Instance
The analog input value can be monitored.
Analog Input
Instance ID Object Name VFFS1 Description Units Access
Analog Input #1 ANALOG INPUT 2 VIB Analog input monitor % R
- 13 -
E6581404
4.3. Control objects
4.3.1. Binary Value Objects Instance
Binary Value Object Instance
Binary
Value ID
Object Name Description
Active/
Inactive Text
Access
#0 RUN/STOP ACT Indicates the drive status RUNS/ READY R #1 FWD/REV ACT Indicates the motor rotation’s direction REV/ FWD R #2 FAULT ACT Indicates the drive’s fault status FAULTED/NONE R #3 --- --- - / - ---
#4
HAND/AUTO
ACT
Indicates if the drive is locally controlled or not
HAND/
AUTO
R
#5 --- --- - / - --- #6 MAINT REQ Commutative operation time alarm status YES / NO R
#7 DRIVE READY The VSD is ready and waits a start command
READY/
NOT READY
R
#8 AT SETPOINT The VSD has reached the target speed
REACHED/
NO
R
#9 --- --- - / - ---
#10
RUN/STOP
CMD
Commands a drive start
START/
STOP
C
#11 FWD/REV CMD Commands a monitor direction’s change
REV/ FWD
C
#12 --- --- - / - --- #13 --- --- - / - ---
#14 FAULT REST Resets faults
RESET/
NO
C
#15 MBOX READ Command to read parameter
WRITE/
RESET
W
#16 MBOX WRITE Command to write parameter
WRITE/
RESET
W
#17 --- --- - / - --- #18 SP1PRESET Preset speed operation frequency 1
SP1/
NONE
C
#19 SP2PRESET Preset speed operation frequency 2
SP2/
NONE
C
#20 SP3PRESET Preset speed operation frequency 3
SP3/
NONE
C
#21 STPSEL Frequency priority selection ENABLED/OFF C #22 CMDSEL Command priority selection ENABLED/OFF C
R = Read-only, W=Writable, C=Commandable. Commandable values support the priority arrays and relinquish defaults.
- 14 -
E6581404
4.3.2. Analog Value Objects Instance
Analog Value Object Instance
Analog
Value ID
Object Name Description Units
Access
#0
OUTPUT
SPEED
Output speed min-1 R
#1 OUTPUT FREQ Output frequency Hz R #2 DC BUS VOLT DC bus voltage *1 V R #3 OUTPUT VOLT Motor voltage V R #4 CURRENT Motor current A R #5 TORQUE Motor Torque % R
#6 POWER
Motor Power 100%=√3×VSD rate voltage×Motor rate current
% R
#7 DRIVE TEMP Drive Thermal State % R #8 KWH (R) Energy counter KWh R #9 --- --- --- ---
#10 PRC PID FBCK PID regulator feedback *1 % R #11 --- --- --- --­#12 --- --- --- --- #13 --- --- --- --- #14 RUN TIME Operating time H R #15 --- --- --- ---
#16 INPUT REF 1
Speed reference from Bus 100%=vl (Base frequency), Setting range=+,- fh / vl x100
% C
#17 --- --- --- --- #18 LAST FLT Error code --- --­#19 PREV FLT 1 Previous fault (occurred before LASTFLT) --- --­#20 PREV FLT 2 Previous fault (occurred before FLT1) --- --­#21 --- --- --- --- #22 --- --- --- --- #23 ACCEL1 TIME Acceleration time s W #24 DECEL1 TIME Deceleration time s W #25 MBOX PARAM Parameter number --- W #26 MBOX DATA Parameter value --- W
R = Read-only, W=Writable, C=Commandable. Commandable values support the priority arrays and relinquish defaults. *1: The value are hold when the inverter trip.
4.4. Device Objects
Object Name “VF-FS1” Object Type “8” (device) Vendor Name “TOSHIBA” Model Name “VFFS1-2007PM” Firmware Revision “V1.02” Application Software Version “V1.08” (VSD software version) Protocol Version “1” Protocol Revision “2”
- 15 -
E6581404
4.5. Parameter access
Using below objects, inverter parameters can be read and written.
Object ID Object Name
Description
Analog value #25
MBOX PARAM
Parameter No. Set the parameter number (hexadecimal) to decimal value number.
Analog value #26
MBOX DATA
Parameter value. The data unit is depend on the parameter specification. Refer to the inverter instruction manual and the communication function manual (E6581393).
Binary value #15
MBOX READ Command to read parameter
Binary value #16
MBOX WRITE Command to write parameter
1) Read Acc. time (Communication number of ACC1 is 0010 ) a) Set “16 (16 dec=0010 hex)” to Analog value #25. b) Set “1” to Binary vale #15. c) Read the data (ACC1) from Analog value #26. The unit is 0.1s.
2) Write Dec. time (Communication number of DEC1 is 0011 ) a) Set “17 (17 dec=0011 hex)” to Analog value #25. b) Set “110 (110=11.0 sec” to Analog value #26. c) Set “1” to Binary value #16.
4.6. Option Error
If the option detects the hardware or software error, the error status is indicated as LEDs on the board. Refer to 2.3 LED indicator.
- 16 -
E6581404
5. Specifications
< Environmental specification >
Item Specification
Service environment Conforms to VF-FS1
Operation temperature Conforms to VF-FS1
Storage temperature
-25 to +65
Relative humidity 20 to 93% (free from condensation and vapor)
Vibration 5.9m/s2 (0.6G) or less (10 to 55 Hz) (To be complied with JIS C0040.)
< BACnet option terminal specification >
Item Specification Note
Communication between
inverter
VF-FS1
Only one board connection is available.
Applicable model Communication method MODBUS-RTU Baud rate 19200bps
Set the inverter parameter (refer to section
3.1)
Parity Even number
Control power supply 5 V Supplied from inverter
DC
2 circuits (F,R)
Logic input terminal Slide switch (SW) enable to select
logical configurations (Source/Sink).
Not isolated
Logic output terminal Nothing
1 circuit (FL): 30V
-0.5A
DC
Relay contact output terminal
250V
-1A (cosφ =1
Isolated
AC
250V
-0.5A (cosφ =0.4)
AC
(R1 circuit (VIB): 10V
DC IN
=
30kohm)
Not isolated Analog input terminals
Analog output terminals Nothing Power supply output 24V -50mA Current limit function
DC
< BACnet option network specification >
Item Specification Data link / Physical layers Master-Slave / Token Passing (MS/TP) Node type Master node Maximum node 32 nodes per segment
9600bps, 19.2kbps, 38.4kbps, 76.8kbps
Communication baud rate
supports auto-baud detection Bias resistor and termination
Local bias resistors are mounted.
Termination resistor (120 ohm) can be select by SW.
Detachable terminal block 4-pole (5.08mm pitch) Terminal block Manufacturer: PHOENIX CONTACT
Type-Form : MSTB 2,5/4-ST-5.08
- 17 -
E6581404
5.1. BACnet Protocol Implementation Conformance Statement
Oct. 2006
Date
Toshiba Schneider Inverter Corporation
Vendor Name
Low Voltage AC Motor Drive
Product Name
VF-FS1
Product Model Number
V1.08 (VSD software version)
Applications Software Version
V1.02
Firmware Revision
2
BACnet Protocol Revision
BACnet Option board is designed for VF-FS1 series.
Product Description
All standard MS/TP baud rates are supported, as well as master mode functionality. Over BACnet, the drive can be fully controlled as a standard adjustable frequency drive.
BACnet Standardized Device Profile
BACnet Operator Workstation (B-OWS)
(Annex L)
BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building
DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-RD-B
Blocks Supported (Annex K) Segmentation Capability
Segmented requests supported. Window Size ____ Segmented responses supported. Window Size ____
Standard Object Types Supported:
An object type is supported if it may be present in the device. For each standard Object Type supported provide the following
1) Whether objects of this type are dynamically creatable using the CreateObject service
2) Whether objects of this type are dynamically detectable using the DeleteObject service
3) List of the optional properties supported 4) List of all properties that are writable where not otherwise required by this standard
5) List of proprietary properties and for each its property identifier, datatype, and meaning
6) List of any property range restrictions
Data Link Layer Options:
BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ___
MS/TP master (Clause 9),
baud rate(s): 9600, 19200, 38400, 76800
MS/TP slave (Clause 9), baud rate(s): ___ Point-To-Point, EIA 232 (Clause 10), baud rate(s): ___ Point-To-Point, modem, (Clause 10), baud rate(s): ___ LonTalk, (Clause 11), medium: __________ Other: __________
Device Address Binding:
Yes
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
No
Networking Options:
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by
Yes
Foreign Devices?
No
- 18 E -
E6581404
- 19 E -
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4 ISO 8859-1 ISO 10646 (UCS-4)
IBM™/Microsoft™ DBCS ISO 10646 (UCS-2) JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:
Loading...