* If required by the custom specifications, the unit will be marked as a CVCF device.
CVCF: C
ninterruptible Power System
onstant Voltage Constant Frequency
(2) Main circuit switches
c MCCB: Molded Case Circuit Breaker
d ACB: A
ir Circuit Breaker
(3) Storage cells
c Individual battery system: A parallel UPS system in which there is a battery for each
UPS in the system.
d Shared battery system: A parallel UPS system in which there is a single battery
for all UPS units in the system.
e HS: Vent type stand-alone lead storage battery
f AHH: Sintered electrode type alkaline storage battery
g MSE: Sealed stand-alone lead storage battery
(4) Display
c Graphic display panel: Includes push buttons, display lamps, and the LCD panel
used to display UPS operating procedures and the UPS state.
d LCD: Liquid Crystal Display. This shows the operational
procedure and the status of the UPS unit.
e LED: Light-Emitting Diode. Individual lamps located on the
graphic display panel indicate th e st atus of the UPS unit.
f Scroll buttons: The △ and ▽ buttons are used to scroll th ro ug h the
LCD screens, from the first screen to the last sc reen and then
back to the first screen (or backward from the last screen to the
first screen and then back to the last screen).
(5) Control system
c Synchronized mode: Indicates that the UPS output phase is synchronized with
1. Be sure to read this manual before use and have a good
2. Unauthorized copying of this manual in part or in its entirety is
3. Every effort has been made to ensure that the information in this
either a Dual clock, a bypass, or a free-running clock.
Notices
understanding of the equipment.
Store it nearby where it can be refe rr ed t o when needed.
strictly prohibited.
manual is correct and accurate in all respects. If you note
inconsistencies or omissions, or if you have any qu estions, please
contact the Toshiba Service Center.
This manual is designed to ensure the safe and correct operation of the TOSNIC-7000S
Uninterruptible Power System (hereafter referred to as "UPS unit"). Please read the "Safety
Precautions" and "Operation" sections of this manual carefully before use and make sure you
have a thorough understanding of the information in these two sections. Keep the manual
handy in a place near the unit so you can refer to it instantly when needed.
Note that this manual was written based on the standard circuits shown in figures 6.2 (page
13). The delivered UPS system may, if desired by the customer, differ from the standard
configuration. Similarly, the displayed markings may differ from those on the standard
system. If this is the case, follow the operating procedures and indications provided in the
development circuit diagrams created individually for the UPS system actually delivered.
Also, while this manual uses the term UPS, the equipment may be marked "CVCF" according
to customer specifications. If this is the case, remember that the term UPS in the manual is
equivalent to CVCF.
2. Safety Precautions
6 F 3 H 1 0 0 1
This manual and the labels on the UPS main unit contain important information designed to
ensure that the UPS unit is used correctly and safely and prevent property loss and injury to
operators and maintenance personnel. Operators and maintenance personnel should follow
all precautions noted in the manual and should have a thorough understanding of the
meaning of the safety signs and safety symbols shown below.
Safety signs
Safety sign Meaning
Indicates that failure to observe proper handling
WARNING
CAUTION
* Here "injury" refers to burns, electrical shock or other injuries that do not
require hospitalization or long-term medical care.
Safety symbols
Safety symbol Meaning
procedures may result in death or serious injury
Indicates that failure to observe proper handling
procedures may result in injury* or property damage
PROHIBITED
The exact nature of what is prohibited is indicated in
pictorial or text form in or near the symbol
MANDATORY
The exact nature of what must be done is indicated in
pictorial or text form near the symbol.
- 2 -
2. Safety Precautions (continued)
Use
Special considerations (*) are required when using equipment that affects the
lives and safety of human beings (**) or has a critical effect on maintaining
public services (***). Be sure to contact Toshiba in such cases. The use of such
equipment without special consideration may result in serious accidents.
* Means holding through consultations with system designers regarding
system operation and management and building a backup system for use in
the event of UPS failure.
** • Operating room equipment
• Life support equipment (artificial dialysis, incubators, etc.)
• Noxious gas or smoke eliminators
• Equipment that must be provided under fire laws, construction standards or
other ordinances
• Equipment equivalent to the above
*** • Equipment used to supervise or control airways, railways, roads, sea
lanes or other transportation routes
6 F 3 H 1 0 0 1
• Equipment used to control nuclear power plants, etc.
• Equipment used to control communications
• Equipment equivalent to the above
Warranty
The warranty on this product may not cover all primary, secondary or tertiary
damage resulting from error or failure of this unit, connected units or software.
Checking Warning Labels
Check to make sure that warning labels are displayed in the appropriate places
(see page 6).
If labels are not present or are smudged and therefore illegible, contact the
Toshiba Service Center .
- 3 -
2. Safety Precautions (continued)
If the unit begins to emit smoke or strange odors, immediately turn off circuit
breakers 52R and 72B.
Continued use may result in fire. Contact the Toshiba Service Center.
WARNING
6 F 3 H 1 0 0 1
MANDATORY
Contact the Toshiba Service Center in the event of malfunction or failure.
This unit should be repaired only by authorized Toshiba
service personnel. Servicing by untrained personnel may
increase the scale of the failure or result in electric shock or
injury.
MANDATORY
Do not attempt to modify or move the unit yourself or to have this done by a
third party.
Electric shock, injury or failure may result if persons other
than specially trained Toshiba technicians attempt to modify
or move the unit.
Be sure to contact Toshiba if you wish modifications to be
made or if you wish to move the unit.
PROHIBITED
Only open the front panel when performing necessary operations.*
Operating parts and high-voltage areas inside the UPS have
been provided with covers as a safety precaution. Still,
touching areas other than those that must be touched to
perform necessary operations may result in electric shock,
burns or other injuries.
* In this case, "necessary operations" means
operating circuit breakers/auxiliary
switches and inserting/removing memory
cards
MANDATORY
- 4 -
2. Safety Precautions (continued)
Do not open the rear door.
The parts inside carry high voltage. Touching them may
result in electric shock, burns or failure.
WARNING
6 F 3 H 1 0 0 1
PROHIBITED
CAUTION
Operators should be qualified* personnel.
Operation of the UPS by unqualified or untrained personnel
may result in electric shock, injury or failure.
* In accordance with customer stipulations
MANDATORY
Make sure the air vents on the front and top of the unit are not blocked.
Blocking the vents will cause the temperature inside the unit
to rise and may result in fire or unit failure.
PROHIBITED
Make sure you understand the meaning of the warning labels on the equipment,
and follow the precautions indicated.
Operating the equipment with an inadequate understanding
of these matters may result in electric shock or burns.
•See Page 6 for the location of these warning labels.
MANDATORY
- 5 -
2. Safety Precautions (continued)
Checking warning labels
(1) The locations of the warning labels on the UPS are shown in Figure 2.1.
Check to make sure that these warning labels are in place.
Note that the placement and content of the warning labels may differ
depending on the capacity of the UPS. Verify the locations by referring to
the warning label placement figure provided with the "Maintenance &
Inspection 6F3H1002" manual.
(2) Read all warning labels and make sure you understand their meaning.
(3) Make sure warning labels are alw ays legible. Do not allow them to become
smudged and do not remove or cover them up.
Locations of the Warning Labels (Example: 300 kVA)
6 F 3 H 1 0 0 1
A
WARNING
Hazardous voltage
can cause injury or death.
Do not touch primary side
of MCCB.
Q
Be always
turn on
H
Do not turn off
in running
T
Check having fixed completely
G
WARNING
Rotating shaft
can cause injury.
Do not touch
rotating section.
F
Hazardous voltage
can cause injury or death.
Do not touch live part
of orange wiring.
WARNING
with the screw of a unit,
when restoring this unit.
* The nameplate B is attached at the ground wire connection points in each section.
** The nameplates E are mounted in t he v i cinity of the main c i rcuit transfor mers and
reactors that can be seen from the back of the panel.
Figure 2.1 Unit Interior Front (with front panel open) and Warning Labels (Example)
B
Hazardous voltage
can shock.
Connect
grounding terminal
to ground
before operating.
C
WARNING
Hazardous voltage
can cause injury or death.
(Discharge takes
approx. 20 minutes)
D
WARNING
Hazardous voltage
can cause injury or death.
Do not open panel
while operating.
E
CAUTION
Hot surface can burn.
Do not touch transformer
or reactor.
- 6 -
3. Handling Precautions
Perform daily and periodic inspections as noted in the maintenance and inspection
plan.
In order to ensure a long service life and optimal performance,
the equipment must be installed in a suitable environment, must
be operated correctly, and must be given the proper daily and
periodic inspections. Maintenance and inspections are
particularly effective in preventing accidents caused by changes
in components that will occur over time. Be sure to have
periodic maintenance work and inspections done by Toshiba
service and maintenance personnel.
For more information on servicing programs and fee options,
contact the Toshiba Service Center.
Operate the unit within the ambient conditions noted in the specifications.
Operating the unit outside these ranges may result in failure.
6 F 3 H 1 0 0 1
During operation, do not turn off the air conditioner for the UPS chamber and the
battery chamber.
This will cause the temperature in these chambers to rise and may result in failure.
PROHIBITED
When starting or stopping the equipment, monitor the operation on the graphic
display panel LCD and follow the procedures described in Chapter 8 "Operation".
Operating the unit in other than the prescribed manner may result in failure.
* The startup and stop procedures presented in this instruction
manual are the operating procedures for independent UPS nits.
For system-wide operating procedures for when other
distribution panels are present, refer to the corresponding
operating procedures manual.
- 7 -
3. Handling Precautions (continued)
Do not turn the circuit breakers ON when control power source switch (8A) is OFF.
This may result in failure.
Certain units also have a control power source switch (8D).
This switch has the same functions as the switch 8A.
6 F 3 H 1 0 0 1
PROHIBITED
Do not turn the control power source switch (8A) to the OFF position when the
circuit breakers are ON.
This may result in failure.
Certain units also have a control power source switch (8D).
This switch has the same functions as the switch 8A.
PROHIBITED
When operating the keys on the graphic display panel, hold down the key for at
least 0.5 second.
The operation may not be performed if the key is held down for
shorter periods of time.
When operating the reset key on the graphic display panel, hold down the key for at
least 5 seconds.
The reset operation may not be performed if the key is held
down for shorter periods of time.
- 8 -
3. Handling Precautions (continued)
When the unit has stopped due to failure, be sure to remove the memory card
before resetting the LCD Failure Error screen on the panel.
Resetting (restarting) the UPS without removing the memory card will
delete the data needed to determine the cause of the failure.
Do not leave the unit for long periods of time (1 week) with control power source
switch (8A) in the OFF position.
This can cause the backup capacitor on the control board to become
discharged and result in incorrect time display and other problems.
Only open the front panel when performing necessary
operations.*
Operating parts and high-voltage areas inside the UPS have
been provided with covers as a safety precaution. Still, touching
areas other than those that must be touched to perform
necessary operations may result in electric shock, burns or other
WARNIN
injuries.
6 F 3 H 1 0 0 1
G
CAUTION
* In this case, "necessary operations" means operating circuit
breakers/auxiliary switches (6CH/8A) and inserting/removing
memory cards
Do not open the rear door.
The parts inside carry high voltage. Touching them may result in
electric shock, burns or failure.
Make sure the air vents on the front and top of the unit are not
blocked.
Blocking the vents will cause the temperature inside the unit to
rise and may result in fire or unit failure.
Example: 300 kVA
Front panel handle (includes a lock)
Graphics display panel
Channel baseFront air vent
Figure 5.1 Unit Exterior (front)
* This is an example of the appearance of a standard configuration unit (300 kVA) UPS.
In some cases, de
ending on system configuration, an additional panel may be
- 11 -
6 F 3 H 1 0 0 1
6. Controls and Circuit Configuration
If the unit begins to emit smoke or strange odors, immediately
WARNIN
G
6.1 Panel Controls
Figure 6.1 and Table 6.1 show the locations and functions of the controls used for the circuit
configurations (see Figures 6.2) on the UPS.
NOTES
turn off circuit breakers 52R and 72B.
Continued use may result in fire. Contact the Toshiba Service
Center .
Do not turn the circuit breakers ON when control power source
switch (8A) is OFF.
This may result in failure.
Do not turn the control power source switch (8A) to the OFF
position when the circuit breakers are ON.
This may result in failure.
* Certain systems are also provided with a control power source
switch (8D).
This switch has the same functions as the switch 8A.
Example: 300 kVA
e52R
f52M
g52L
The figure above is only an example; the layout may be
different depending on capacity and system configu ration.
If an MCCB with auxiliary handles is used as the circuit
breaker, use the auxiliary handles during operation.
c52R
d72B
h8A
i6CH
Figure 6.1 Location of Control (in panel)
- 12 -
6 F 3 H 1 0 0 1
Table 6.1 Control Functions
No. Device Name / Function Normal Status
c
Main circuit AC input circuit breaker
52R
When the AC input is normal, power is
During Operation
ON
supplied to the UPS through this circuit
breaker.
d
Main circui t DC input circuit breaker
72B
When AC input has been cut off, power is
ON
supplied from the battery to the UPS
through this circuit breaker.
e
Bypass AC circuit breaker
52C
When bypass power is supplied, power is
ON
supplied to the load through this circuit
breaker.
f
Maintenance bypass AC circuit breaker
52M
When bypass power is supplied for UPS
OFF
maintenance, power is supplied to the
load through this c i r c u it breaker.
g
AC output circuit breaker
52L
While UPS power or bypass power is
ON
supplied, power is supplied to the load
through this circuit breaker.
h
Control power source switch
8A
When AC input is normal, pressing this
ON
switch supplies power to the control power
source.
i
Precharge circuit button
6CH
Pressing this button supplies power to t h e
ON
circuit that precharges the DC electrolyt ic
capacitor before power is supplied to
circuit breaker 52R.
Remarks
When the circui t br ea k e r
is tripped in manual
mode, reset it by grasping
the handle and pulling it
down or to the right.
Certain systems are
also provided with the
switch 8D.
6.2 Circuit Configuration
UPS
AC INPUT
BYPASS
AC INPUT
52R
52C
~
Figure 6.2 Standard Circuit Configuration
~
72B
52L
AC OUTPUT
BATTERY
52M
- 13 -
AC S
6.3 Panel Controls
When the unit has stopped due to failure, be sure to remove the
memory card before resetting the LCD Failure Error screen on the
panel, so you can give it to the service person.
Resetting (restarting) the UPS without removing the memory card will
NOTES
The locations of the controls on the panel are shown in Figure 6.3.1. For the functions of
each of the controls, see Section 6.3.1 "Panel Key-switch" and Section 6.3.2 "Panel Keys."
delete the data needed to determine the cause of the failure.
Every effort has been made to ensure safety in unit handling.
However, when removing the memory card, do not touch the other
sections of the unit.
Touching the other sections of the unit may result in electric shock.
6 F 3 H 1 0 0 1
i
SCROLL
(**)
c
e
d
h(*)
j
UPS SUPPLY
~
AC INPUT
BATTERIES
~
BYPASS INPUT
OPERATION
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
OPERATION
INHIBITED
WARNING FAULT
~
CONVERTER
UPS
STOP
RUN
~
INVERTER
CHARGE
EQUAL
FLOAT
BYPASS
UPS
AC
SWITCH
BYPASS
WITCHFAULT
UPS
~
AC OUTPUT
RESET
k
g
f
NOTE ***
Figure 6.3.1 Panel Controls
(For individual battery systems. For HS or AHH batteries.)
* This will be the "FLOAT" key for MSE individua l ba ttery systems.
** This will be the "PROTECTION" LED for MSE individual battery
systems.
l(***)
Do not use the keypad on
graphic display panel l.
This keypad is used to
change the internal
settings and should
only be used by
maintenance
personnel.
It is not used during
normal operation.
- 14 -
6.3.1 Panel Key-switch
Table 6.2 shows the function of the key-switch on the graphic display panel.
No. Name Function Remarks
6 F 3 H 1 0 0 1
Table 6.2 Key-switch Function
c
OPERATION
LOCK
Setting this key-switch to the "OPERATION"
side enables operation using the buttons on
the panel; setting it to the "OPERATION
INHIBITED" side prevents operation. When
the switch is set to the "OPERATION
INHIBITED" side, buttons d - h and k in
Table 6.3 are inoperative and pressing them
has no effect upon the operation of the UPS.
LCD scroll buttons i and j are effective
regardless of the position of this switch.
6.3.2 Panel Keys
Table 6.3 shows the functions of the keys on the graphic display panel.
NOTES
When operating the keys on the graphic display panel, hold down the key for
at least 0.5 second.
When operating the reset key on the graphic display panel, hold down the
key for at least 5 seconds.
The operation may not be performed if the key is held down for shorter periods
of time.
Normally setting the
switch to the
OPERATION INHIBITED"
prevents operational
errors. The key can be
removed when it is set to
the "OPERATION
INHIBITED" position; it
cannot be removed when
the switch is set to the
"OPERATION" position.