Toshiba TCB-TC21LE, TCB-TC21LE2 INSTALLATION MANUAL

INSTALLATION MANUAL
To Personnel Charged in Installation (Electric) Work and Service
Remote sensor MODEL : TCB-TC21LE
Accessory parts
Part Name Q’ty
Remote sensor (200mm-cable
attached) Small screw
M4 x 25
Wood screw
1
2
2
Part Name Q’ty
Spacer
Wire joint
Cable clamper
Installation Manual
Requirement to install the remote sensor
Installation place
• Install the remote sensor at a position with height 1 to
1.5m from the floor, where the average temperature in the room can be felt.
• Do not install the remote sensor at a place behind something or rear side of something, where air flow is poor in the room.
• Do not install the remote controller near the freezing box or refrigerator because water proof or drop-proof is not applied to this remote controller.
• Be sure to set the remote sensor vertically on the wall surface, etc.
How to install the remote sensor
NOTE 1 : Avoid to twist the remote sensor cable with the
NOTE 2 : Install the remote sensor apart from the
NOTE 3 : When noise is induced to the power source of
• In case of using the remote sensor as a concealed type
Remote sensor body
1. Inserting a minus screwdriver, etc. into the groove at
2. Using the attached M4 screws (2 pcs.), fix the rear
power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunction.
generation source of noise.
the indoor unit, some measures such as mounting the noise filter is necessary.
Rear case
Spacer
Small screws M4 x 25 (2 pcs.)
WallWall
the lower side of the remote sensor body, force open the rear case to remove it.
case of the remote sensor. Before installation, press to open the screw hole with a screwdriver, etc.
Fix it with the spacer, but not so strongly. If the remote sensor does not fit closely to the wall, adjust it by cutting off the spacer.
2
3. Connect the remote sensor cable (2 cores) to the terminal numbers of the indoor unit.
2
(Applying AC 220/230/240V breaks the unit.)
4. Install the remote sensor body by matching to hooks on the rear case and putting into the hooks.
1
1
How to perform cab ling of the remote sensor
In case of using the remote sensor as a concealed type
• Connection diagram
Approx. 200mm
Terminal block for remote controller cable in indoor unit
W : White B : Black
A B
Remote sensor cable (Procured locally)
Connecting section
W
B
Cable from remote sensor body
Remote sensor
• Non polarity, 2 core cable is used..
• Use 0.5mm² to 2 mm² cable.
Remote sensor cable
Attached wire joint (White, 2 pcs.)
Cable from remote sensor body
1) Peel the sheath of the cable to be connected by approx. 14mm.
2) Twist two cables and pressure-connect them using a wire joint.
3) When an exclusive pressure-connecting tool is not used or soldering connection is used, apply insulation process with an insulation tape.
Wire joint, CE-1 (Nichiatsu)
Requirement for using the remote sensor
together with the remote controller
• How to install
For the above control, install the remote sensor in the following procedure.
1. Set the remote controller as the master remote controller.
2. Do not change the remote sensor switch in the master remote controller for correct temperature control by remote sensor.
• Basic cabling diagram
1. Connect cables without miswiring. (Miswiring breaks the unit.)
2. In a case to operate an indoor unit from the remote sensors and the remote controller.
Remote sensor
Terminal block for remote controller cable
Remote controller (Master)
Earth
Indoor unit
(Sold separately)
Remote controller cable (Procured locally)
BA