No.
1
2
3
4
Q’ty
1
4
2
1
Parts name
Connection cable
Support to fix the board
Earth screw
Banding band
4-φ4 hole
Terminal(Screw M3)
2
2
Length
Shield wire
TypeSize
Wiring Up to 500m
2-core or 3-core, 0.75mm
2
Correct
direction
Terminal
block
Incorrect
direction
CN508
RED
CN509
BLACK
CN510
WHITE
CN512
BLUE
CN508
CN509
CN510
CN512
Night operation control
Snowfall fan control
Operation mode selection control
External master ON/OFF control
TCB-PCMO2E
Outdoor unit
interface P.C. board
Operation mode selection control
● Feature
This control can be operated with the operation mode which is permitted by SMC or SMH.
● Function
SMC :Cooling mode
designated input switch
SMH
:Heating mode
designated input switch
I/F P.C. Board*
*Place this option P.C.board to header outdoor unit.
Connection
Cable
Local SupplyTCB-PCMO2E
SMC
COM
COOL
HEAT
PJ17CN510
SMH
Selected operation mode
Note
*1
Note
Only cooling mode permitted
Only heating mode permitted
Normal operation
*1
*1
Terminal
ON
OFF
OFF
OFF
ON
OFF
COOL
(SMC)
HEAT
(SMH)
When the operation select button of remote controller is pushed,
"
(mode select control )" mark is indicated on the remote controller display.
Snowfall fan control
● Feature
Outdoor fan is operated with the snowfall signal from outside.
● Function
SMC :Snowfall detection switch
I/F P.C. Board*
*Place this option P.C.board to header outdoor unit.
Connection
Cable
Local SupplyTCB-PCMO2E
SMC
COM
PJ17CN509
COOL
HEAT
Terminal Operation
Snowfall fan control
(Operates outdoor fan.)
Normal operation
Input signal
ON
OFF
ON
OFF
COOL
(SMC)
External master ON/OFF control
● Feature
The outdoor unit starts or stops the system.
● Function
SMC
:Input
signaal for start
SMH
:Input signal for stop
I/F P.C. Board*
*Place this option P.C.board to header outdoor unit.
Connection
Cable
Local SupplyTCB-PCMO2E
SMC
COM
COOL
HEAT
PJ17CN512
SMH
Terminal Operation
All indoor units are started
on previous operating.
Stops all indoor units.
Input signal
ON
OFF
ON
OFF
COOL
(SMC)
HEAT
(SMH)
Night operation (Sound reduction) control
● Feature
Sound level can be reduced with connecting outdoor interface P.C.Board by restricting commpressor and fan speed
.
● Function
SMC :Input signal for night operation
I/F P.C. Board*
*Place this option P.C.board to header outdoor unit.
Connection
Cable
Local SupplyTCB-PCMO2E
SMC
COM
PJ17CN508
COOL
HEAT
Terminal Operation
Night operation control
Normal operation
Input signal
ON
OFF
ON
OFF
COOL
(SMC)
CAUTION)
・
Be sure to prepare non voltage pulse point of contact for each terminal.
・
This control is conducted when input signal stand up or fall down.
(Standing and falling status should be held for 100 msec. or more.)
・Supplementary Insulation must be added to user touchable part of switches.
External master ON/OFF control board
INSTALLATION MANUAL
MODEL:
TCB-PCMO2E
Feature
"TCB-PCMO2E" is used for the following external master controls
Safety Precautions
WARNING
CAUTION
This symbol is used to identify action which, if carried out in an incorrect ignoring this indication,
could lead to serious personal injury or even death.
Installation of accessory parts should be performed either by personnel from this dealer
where it was purchased or by specialist installation technicians.
Reassembling, repair, or modification of this accessory parts is strictry forbidden.
Do not install a location where flammable gasses may be present.
Repair of the accessory parts must also carried out by personnel from dealer where it was purcased.
Use the specified wires for wiring connect the terminals securely fix. To prevent external
forces applied to the terminals from affecting the terminals.
This symbol is used to identify action which, if carried out in an incorrect ignoring this indication,
could lead to serious human injury or property damage.
l Please read this section carefully before installation work to install the accessory parts in the
prescribed manner. The precaution given here deal with serious safety issues. It is, therefore,
of the utmost importance that they are observed in full.
l
The meanings of safety-related symbol are as follows:
l
After installation work has been completed, perform a trial operation of the equipment in order
to ensure that it is operating normally, and then hand over to the customer and ask to keep
this Safety Precautions and Installation Instruction.
l
Incorrect installation by unqualified personnel can result in electric shock, fire or abnormal operation.
l
Fire may break out should flammable gas leak into the vicinity of the parts.
l
Fire may break out should flammable gas leak into the vicinity of the parts.
l
Failure to follow these directions can result in inflammation, earth leakage or abnormal operation
causing electric shock or injury.
WARNING
1. Night operation control 3. Operation mode selection control
2. Snowfall fan control 4. External master ON/OFF controll
Refer to the "Function/Electric wirong diagram" for feature of the each controls, and connecting way is
different according to the control.
Dimension
Accesory parts
Size(mm):H18 x L55.5 x W60
Weight(g): 20
Wiring
(1) Refer to the "Electric wiring diagram" when wiring.
(2)
Be sure to use the shield wire to prevent noise trouble, and perform the grounding at both sides of shield wires.
Placing position
[ Outdoor unit ] [ Electric component box ]
Install this P.C. board to the upper side of the electric component box on outdoor unit.
Up to 4"TCB-PCMO2E" can be installed simultaneously in one electric component box.
(1) Be sure to turn off the power switch before installing.
(2) Place this P.C. board by using 4 pcs the support to fix the board.
There are four installation holes to place the support on the upper
side of the electric component box.
(3) Install the P.C.board to the supports.
Be careful the terminal block direction as the interior side.
(4) Connect the P.C.board (TCB-PCMO2E)PJ17 and
outdoor unit interface CN508 to CN512 with connection cable.
Connecter on interface P.C. board is different according to the
purpose.
(5) Bind the remaining connection cable with the
attached banding band.
[ Outdoor unit interface PC board ]
How to install
Function / Electric wiring diagram
CAUTION
)
・Be sure to prepare non voltage continuous point of contact for each terminal.
・Supplementary Insulation must be added to user touchable part of switches.
CAUTION
)
・Be sure to prepare non voltage continuous point of contact for each terminal.
・Supplementary Insulation must be added to user touchable part of switches.
CAUTION
)
・Be sure to prepare non voltage continuous point of contact for each terminal.
・Supplementary Insulation must be added to user touchable part of switches.