Power peak-cut control board
(1) Be sure to turn off the power switch before installing.
(2) Place this P.C. board by using the support on the upper side of the electric component
box. There are four installation holes to place the support on the upper side of the electric
component box.
(3) Install the P.C.board to the supports.
Be careful the terminal block direction
as the interior side.
(4) Connect the P.C.board (TCB-PCDM2E)PJ17
and outdoor unit interface CN513
withconnection cable.
(5) Bind the remaining connection cable with the
attached banding band.
Wiring
SN:EH99839001
INSTALLATION MANUAL
MODEL:
TCB-PCDM2E
Feature
The upper limit capacity of the outdoor unit is restricted based on the
demand request signal from outside
Dimension
No.
1
2
3
4
5
6
Q’ty
1
4
2
1
1
2
Parts name
Connection cable
Support to fix the board
Earth screw
Wire-clamp
Screw for wire-clamp
Banding band
Terminal(Screw M3)
Terminal(Screw M4)
4-φ4 hole
2
2
Accesory parts
Placing position
Power peak-cut
control board
Outdoor unit
interface PC board
[ Outdoor unit ] [ Electric component box ]
Terminal
block
Correct
direction
Incorrect
direction
Safety Precautions
WARNING
CAUTION
This symbol is used to identify action which, if carried out in an incorrect ignoring this indication,
could lead to serious personal injury or even death.
Installation of accessory parts should be performed either by personnel from this dealer
where it was purchased or by specialist installation technicians.
Reassembling, repair, or modification of this accessory parts is strictry forbidden.
Do not install a location where flammable gasses may be present.
Repair of the accessory parts must also carried out by personnel from dealer where it was purcased.
Use the specified wires for wiring connect the terminals securely fix. To prevent external
forces applied to the terminals from affecting the terminals.
This symbol is used to identify action which, if carried out in an incorrect ignoring this indication,
could lead to serious human injury or property damage.
l Please read this section carefully before installation work to install the accessory parts in the
prescribed manner. The precaution given here deal with serious safety issues. It is, therefore,
of the utmost importance that they are observed in full.
l
The meanings of safety-related symbol are as follows:
l
After installation work has been completed, perform a trial operation of the equipment in order
to ensure that it is operating normally, and then hand over to the customer and ask to keep
this Safety Precautions and Installation Instruction.
l
Incorrect installation by unqualified personnel can result in electric shock, fire or abnormal operation.
l
Fire may break out should flammable gas leak into the vicinity of the parts.
l
Fire may break out should flammable gas leak into the vicinity of the parts.
l
Failure to follow these directions can result in inflammation, earth leakage or abnormal operation
causing electric shock or injury.
WARNING
Size(mm):H20 x L85 x W71
Weight(g): 65
Length
Shield wire
Shield wire
TypeSize
*
In conformity with design 60245 IEC 57
Input wiring
Output wiring
Up to 500m
Up to 200m
Up to 400m
2-core or 3-core, 0.75mm
2
2-core, 0.75mm2
*
2-core, 1.5mm2
*
(1) Refer to the "Electric wiring diagram" when wiring.
(2) Be sure to use the shield wire to prevent noise trouble, and perform the grounding at both
sides of shield wires.
(3) Fix the output wiring with the wire clamp and banding band.
(3)-1.
Let the output wiring into the banding band and band it together with the other wiring.
(3)-2. Fix the wire-clamp using the screw hole on the "B" position.
[ Electric component box ]
Banding band
Wire-clamp
Output wiring
(Local supply)
Function / Electric wiring diagram
Two type control can be selected by setting SW07(Bit2)on the interface P.C. board of the header unit.
[ Standard function ]
I/F P.C. Board
*
*
Place this option P.C. Board to header unit.
Connection
Cable
Local Supply
: Display lamp suring power
peak-cut control.
TCB-PCDM2E SW07-Bit2 OFF
Power Supply
OPERATION
COM
COM
OFF
OFF
ON
ON
PJ17CN513
L1
L1
SW1
SW1
SW2
SW2
Display
Relay
SW07
Bit2 OFF
Input
SW1
OFF
ON
SW2
ON
OFF
OFF
ON
Bit1 OFF
100%(Normal)
0%(Stop)
Bit1 ON
100%(Normal)
Up to 60%
SW07-Bit1 Display Relay
(L1)
CAUTION)
・Be sure to prepare a non-voltage point for each terminal.
・Display Relay capacity of "OPERATION"
Below AC240V 0.5A (COSφ=100%)
When connecting load such as relay coil to "L1" load, insert the noise surge absorber.
Below DC24V 1A (Non-inductive load)
When connecting load such as relay coil to "L1" load, insert the the bypass circuit.
・Supplementary Insulation must be added to user touchable part of switches.
In case of pulse signal
Be sure to prepare the point of contact for each terminal.
The time of the pulse signal is more than 100msec.
Don’t switch on both SW1 and SW2
terminal simultaneously.
PJ17
I/F P.C. Board
*
*
Place this option P.C. Board to header unit.
Local Supply
: Display lamp suring power
peak-cut control.
TCB-PCDM2E
SW07-Bit2 ON
Power Supply
OPERATION
COM
COM
OFF
OFF
ON
ON
CN513
L1
L1
SW1
SW2
Display
Relay
SW07
Bit2 ON
Input
SW1
OFF
ON
OFF
ON
SW2
OFF
OFF
ON
ON
OFF
ON
ON
ON
Bit1 OFF
100%(Normal)
Up to 80%
Up to 60%
0%(Stop)
Bit1 ON
100%(Normal)
Up to 85%
Up to 75%
Up to 60%
SW07-Bit1 Display Relay
(L1)
CAUTION)
・Be sure to prepare non voltage continuous point of contact for each terminal.
・Display Relay capacity of "OPERATION"
Below AC240V 0.5A (COSφ=100%)
When connecting load such as relay coil to "L1" load, insert the noise surge absorber.
Below DC24V 1A (Non-inductive load)
When connecting load such as relay coil to "L1" load, insert the bypass circuit.
・Supplementary Insulation must be added to user touchable part of switches.
Connection
Cable
[ Expansion function ]
Install this P.C. board to the upper side of the
electric component box on outdoor unit.
<Switch position>
<Connector position>
CCoonnnneeccttoorr aanndd SSwwiittcchh ppoossiittiioonn oonn iinntteerrffaaccee PPCC bbooaarrdd