Toshiba TCB-FC281BE INSTALLATION MANUAL

1. Combination of air conditioner indoor unit and High Efficiency Filter
FILTER CHAMBER Model:TCB-FC281BE, FC501BE, FC801BE, FC1401BE
INSTALLATION MANUAL
Note: Install the Filter Chamber before hanging the indoor unit main body.
2. Parts list
3. Installation procedure
filter frame from the back of the indoor unit main body. Since the removed screws are reused later, be careful not to lose them.
TCB-FC281BE
Filter Chamber model name
Collecting Efficiency
65%*
*NBS Calorimetric method
Collecting Efficiency
90%*
High Efficiency Filter model name
Airconditioner
model name
MMD-AP0071BH
~AP0121BH
TCB-UFM11BFCE
TCB-UFH51BFCE
TCB-UFM21BFCE
TCB-UFH61BFCE
TCB-UFM11BFCE
TCB-UFH51BFCE
2pcs
2pcs
TCB-UFM21BFCE
TCB-UFH61BFCE
2pcs
2pcs
MMD-AP0151BH
~AP0181BH
MMD-AP0241BH
~AP0301BH
MMD-AP0361BH
~AP0561BH
TCB-FC501BE TCB-FC801BE TCB-FC1401BE
RAV-SM561BT-E RAV-SM801BT-E RAV-SM562BT-E RAV-SM802BT-E
RAV-SM1101BT-E
~SM1401BT-E
RAV-SM1102BT-E
~SM1402BT-E
TCB-FC281BE
Filter Chamber model name
Filter Chamber
Fixing screws
TCB-FC501BE TCB-FC801BE TCB-FC1401BE 1111 8999
High Efficiency Filter eject port*
*Set the crevice between indoor unit and the circumference to 350mm or more in order to secure the crevice for extraction of filter.
Standard filter frame
High Efficiency Filter Chamber
(sold separately parts)
Fixing screws
Inlet port
(backside of the indoor unit)
Indoor unit main body
(2) Install the High Efficiency Filter Chamber to the back of the indoor unit main body with fixing screws.
Install it in the direction the filter chamber's filter eject port (door) is positioned to the piping connection port side.
(3) Fix the standard filter frame, which you have previously removed, to the High Efficiency Filter Chamber with the
stored screws.
(4)
Insert the Standard Filter (ordinary) and sold separately High Efficiency Filter into the chamber before test operation. When installing the sold separatelyl High Efficiency Filter, be careful of the installation direction. Confirm the airflow mark and insert it in the correct direction. Insert it in such a way that the black and white portions of the tape fastener will face each other (If the white por­tion faces the white portion or the black portion faces the black portion, the filter cannot be removed).
4. Installation of High Efficiency Filter
Insert the high efficiency filter to the filter chamber.
(1)
Insert the filter into the section (A) of the filter chamber.
(2)
A label indicating the wind direction is attached to the filter main body. Be careful to insert the filter in the correct direction.
(3)
A tape fastener is attached to the filter for when removing the filter. Insert the filter so that the black and white portions of the tape fastener will face each other.
NOTE
•The high efficiency filter can be used by itself. However, we recommend that you use it together with the super long life filter (optional).
•The high efficiency filter cannot be cleaned and reused. Since the high efficiency filter has resistance of about 30Pa, the resistance (outside static pressure) of the connected duct must be 40Pa.
Indoor unit
filter chamber
Wind direction (
Air inlet
)
(A)
Wind direction
Air inlet port
Tape fastener (black)
Tape fastener (white)
Filter chamber
CH58286101-(1)