Toshiba TC218, DA264 User Manual

UM-TS02∗∗∗-E026
PROGRAMMABLE CONTROLLER
PROSEC
T2-series
ANALOG I/O MODULES
AD268 / DA264 / TC218
TOSHIBA CORPORATION
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Important Information
Misuse of this equipment can result in property damage or human injury. Because controlled system applications vary widely, you should satisfy yourself as to the acceptability of this equipment for your intended purpose. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential dam age or injur y that may result from the use of this equipment.
No patent liability is assumed by Toshiba Corporation with respect to use of information, illustrations, circuits, equipment or ex amples of application in this publication.
Toshiba Corporation reserves the right to make changes and improvements to this publication and/or related products at any time without notice. No obligation shall be incurred other than as noted in this publication.
This publication is copyrighted and contains proprietary material. No part of this book may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means elect r ical, mechanical, photocopying, recordi ng, or otherwise without obtaining prior written permission from Toshiba Corp oration.
© TOSHIBA Corpor ation 2001, A ll rights reserved
Publication number: UM-TS02∗∗∗-E026 1st edition December 2001, 2nd edition September 2002
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
1
Safety Precautions
The AD268, DA264, and TC218 are the analog input/output modules for Toshiba’s Programmable Controller PROSEC T2-series (T2/T2E/T2N). Read this manual thoroughly before using this module. Also, keep this manual and related manuals so that you can read them anytime while this module is in operation.
Safety Sy m bols
The following safety symbols are used on the product and/or in the related manuals. Pay attention to the information preceded by the following symbols for safety.
!
WARNING
!
CAUTION
Safety Pr ecau tion s
!
CAUTION
Turn off power to the PLC (T2, T2E or T2N) and to this module (AD268, DA264 or TC218) before removing or mounting this module. Failure to do so can cause electrical shock or damage to this product.
Read the Safety Precautions described in the T2, T2E or T2N User’s Manual before using this module.
Follow the instructions described in this manual and in the T2, T2E or T2N User’s Manual when installing and wiring this module.
This module has been designed for the T2/T2E/T2N. Use your AD268/DA264/TC218 only on the T2-series PLC rack.
These modules consume the internal 5 Vdc power as shown below.
AD268 ... 300 mA DA264 ... 230 mA
TC218 ... 300 mA Confirm that the total 5 Vdc consumed current per one power supply module is within the limit (2.5 A). If it exceeds the limit, the T2/T2E/T2N cannot operate properly and this may cause unsafe situation.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe p ractices.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2
Analog I/O Modules (AD268 / DA264 / TC218)
About This Manual
About This Manual
This manual describes the specification and the operations of Toshiba's analog I/O modules (AD268, DA264 and TC218) for PROSEC T2 series programmable controllers. Read this manual carefully for your correct operation of these modules.
This manual consists in three parts.
Part 1 ... 8 channel analog input module AD268 Part 2 ... 4 channel analog output module DA264 Part 3 ... 8 channel thermocouple input module TC218
Related Manual
The following related manuals are available for your reference.
T2E User's Manual (UM-TS02E∗∗
∗∗∗∗
∗∗-E001)
This manual describes the configuration, specification, installation, wiring, and maintenance of the basic hardware of the programmable controller T2E. The functions of the T2E and how to use them, and the information necessary for creating user program are also described.
T2N User's Manual (UM-TS02N∗∗
∗∗∗∗
∗∗-E001)
This manual describes the configuration, specification, installation, wiring, and maintenance of the basic hardware of the programmable controller T2N. The functions of the T2N and how to use them, and the information necessary for creating user program are also described.
T-series Inst r uction Set (UM-TS03∗∗∗
∗∗∗∗∗∗
∗∗∗-E004)
This manual describes the detailed specifications of instructions for Toshiba's T-series programmable controllers.
Note: In this manual, the T2 series programmable controllers (T2, T2E, and T2N) are called as
T2 for ease of explanation.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
3
Table of Contents
Table of Contents
Safety Precautions ............................................................................................................ 1
About This Manual ............................................................................................................ 2
Part 1 8 Channel Analog Input Module AD268
1. Introduction …………….……………………………………………………………….… 8
1.1 AD268 functions ............………………..…………………….………………………… 8
1.2 External features …......…………………………………………………………………. 9
2. Specifications ….………………………………………………………………………... 10
2.1 Specif ication s .................…………….……………………………………………….. 10
2.2 Internal block diagram ………….......………………………………………………… 11
3. Input Type Setting ….........……………………………………………………………... 12
3.1 Jumper plug setting ........…………….……………………………………………….. 12
3.2 Parameter setting by software ….....………...……………………………………… 13
4. Wiring ………………..…………………………………………………………………… 14
4.1 Terminal arrangement …….......…………..…………………………………………. 14
4.2 Signal wiring …..………………………………………………………………………. 15
4.3 Wiring precautions ………...…………………………………………………………. 16
5. I/O Allocation and Programming …………………………………………………… 17
5.1 Allocatio n to the T2 registers ……………..…………………………………………. 17
5.2 A/D conversion data …….......................……………………………………………. 18
5.3 Programming ……................................……………………………………………. 23
6. Parameters ……..................…......…………………………………………………… 24
6.1 Memory map …...........………………………………………………………………… 24
6.2 Parameter setting procedure ….........……..………………………………………… 30
6.3 S ample program for settin g the parameters …..………………………………..… 31
7. Troubleshooting ….…....……………………………………………………………… 32
7.1 RAS information ……...............…........……………………………………………… 32
7.2 Troubleshooting ................................................................................................. 33
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
4
Analog I/O Modules (AD268 / DA264 / TC218)
Table of Contents
Part 2 4 Channel Analog Output Module DA264
1. Introduction …………….……………………………………………………………….… 36
1.1 DA264 functions............………………..…………………….………………………… 36
1.2 External features…......…………………………………………………………………. 37
2. Specifications ….………………………………………………………………………... 38
2.1 Specif ication s .................…………….……………………………………………….. 38
2.2 Internal block diagram ………….......………………………………………………… 39
3. Output Type Setting ….........……………………………………………………………... 4 0
3.1 Parameter setting by software ….....………...……………………………………… 40
4. Wiring ………………..…………………………………………………………………… 41
4.1 Terminal arrangement …….......…………..…………………………………………. 41
4.2 Signal wiring …..………………………………………………………………………. 42
4.3 Wiring precautions ………...…………………………………………………………. 43
5. I/O Allocation and Programming …………………………………………………… 44
5.1 Allocatio n to the T2 registers ……………..…………………………………………. 44
5.2 D/A conversion data …….......................……………………………………………. 45
5.3 Programming ……................................……………………………………………. 50
6. Parameters …..................….…......…………………………………………………… 51
6.1 Memory map …...........………………………………………………………………… 51
6.2 Sample program to access the parameters …..……..…………………………..… 55
7. Troubleshooting ….…....……………………………………………………………… 56
7.1 RAS information ……...............…........……………………………………………… 56
7.2 Troubleshooting ................................................................................................. 56
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
5
Table of Contents
Part 3 8 Channel Thermocouple Input Module TC218
1. Introduction …………….……………………………………………………………….… 60
1.1 TC218 functions............………………..…………………….………………………… 60
1.2 External features…......…………………………………………………………………. 61
2. Specifications ….………………………………………………………………………... 62
2.1 Specif ication s .................…………….……………………………………………….. 62
2.2 Internal block diagram ………….......………………………………………………… 63
3. Input Type Setting ….........……………………………………………………………... 64
3.1 Jumper plug setting ........…………….……………………………………………….. 64
3.2 Parameter setting by software ….....………...……………………………………… 65
4. Wiring ………………..…………………………………………………………………… 66
4.1 Terminal arrangement …….......…………..…………………………………………. 66
4.2 Signal wiring …..………………………………………………………………………. 67
4.3 Wiring precautions ………...…………………………………………………………. 68
5. I/O Allocation and Programming …………………………………………………… 69
5.1 Allocatio n to the T2 registers ……………..…………………………………………. 69
5.2 A/D conversion data …….......................……………………………………………. 70
5.3 Programming ……................................……………………………………………. 74
6. Parameters …..................….…......…………………………………………………… 75
6.1 Memory map …...........………………………………………………………………… 75
6.2 Parameter setting procedure ….........……..………………………………………… 81
6.3 S ample program for settin g the parameters …..………………………………..… 82
7. Troubleshooting ….…....……………………………………………………………… 83
7.1 RAS information ……...............…........……………………………………………… 83
7.2 Troubleshooting ................................................................................................. 84
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6
Analog I/O Modules (AD268 / DA264 / TC218)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
7
Part 1
8 Channel Analog Input Module
AD268
1. Introduction, 8
2. Specifications, 10
3. Input Type Setting, 12
4. Wiring, 14
5. I/O Allocation and Programming, 17
6. Parameters, 24
7. Troubleshooting, 32
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8
Analog I/O Modules (AD268 / DA264 / TC218)
1. Introduction
PART 1 AD268
1. Introduction
The AD268 is an 8 channel analog input module for the T2 series programmable controllers. The AD268 converts external analog signals (voltage or current) into digital values cyclically so that the T2 can process the analog signals.
1.1 AD268 Functions
The AD268 has the following functions.
1) 8 channels input per module
2) Selectable input type
• ±5V
• ±10V
0 to 5V
0 to 10V
1 to 5V
0 to 20mA
4 to 20mA
3) 16-bit high-resolution A/D conversion
4) High-speed (1ms/channel) conversion cycle
5) Gain and offset calibration function
6) Input data averaging function
7) Unused channel skip function
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
9
PART 1 AD268
1. Introduction
1.2 External features
Model type AD268 Status indication LED
Analog input terminal
External power supply connection terminal Line ground and Frame ground terminal
Terminal block fixing scr ew 2-points
Removable terminal block
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
10
Analog I/O Modules (AD268 / DA264 / TC218)
2. Specifications
PART 1 AD268
2. Specifications
This section describes the AD268 specifications. The general specification for the AD268 conforms to the specification for the T2 PLC.
2.1 Specifications
Item AD268
Input type Voltage input Current input
-5 to 5V
Bipolar
-10 to 10V 0 to 5V 0 to 20mA 0 to 10V
Input range
Unipolar
1 to 5V 4 to 20mA
Input impedance
1M or more 250 Number of input channels 8 channels I/O allocation type X 8W (8 input registers XW are assigned) Resolution 16-bit
Overall accuracy
±0.2% FS (at 25°C)
±0.5% FS (0 to 55°C) (FS: ±10V)
Temperature drift
±100ppm/°C or less Conversion cycle Approx. 1ms/channel (Approx. 8m s/8 channels) Insulation resistance
10M or more
Withstand voltage
1500Vac - 1 minute (between logic and analog circuits)
500Vac - 1 minute (betw een analog circuit and external 24V)
1500Vac - 1 minute (betw een analog circuit and FG/LG)
Status indication 1 green LED (On when normal)
Special function
Gain and offset calibration function
Input data averaging function
Unused channel skip function
External 24Vdc power voltage drop detection External power supply
24Vdc ±10% - 120mA Internal 5Vdc current consumption
300mA or less External connection 20-pin removable terminal block
Weight Approx. 300g
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
11
PART 1 AD268
2. Specifications
2.2 Internal block diagram
The AD268 performs the following operations. The external analog signals come to th e buffer am plifier through the filter. The multiplexer sequentially selects CH1 to CH8 to convert the input analog signals into digital data via the A/D converter. The convert ed digital data reaches to the internal control circuit through optical isolator. Every time when the T2 CPU requests to read the converted data, the internal control circuit sends the data to the T2 CPU. The AD268's parameters are stored in the EEPROM.
Filter
Buffer
Multiplexer
1
3
2
Jumper
Filter
Buffer
1
3
2
Jumper
A/D conversion
Optical isolat ion
CH1
P
N
Internal control ci r cui t
CH8
P
N
Filter
DC/DC
converter
Voltage
check
circuit
Regulator
+5V +15V
-15V
AG
P24
COM
LG
FG
EEPROM
LED
T2 CPU
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
12
Analog I/O Modules (AD268 / DA264 / TC218)
3. Input Type Setting
PART 1 AD268
3. Input Type Setting
The AD268 supports multiple input ranges, ±5V, ±10V, 0 to 5V, 0 to 10V, 1 to 5V, 0 to 20mA, or 4 to 20mA. The input range is selected by jumper plug setting and the parameter writing by the T2 program .
The general flow for setting the input type is as follows. (1) Set the jumper plugs to select voltage input or current input.
(2) Mount the AD268 onto the T2 rack. (3) Turn on power to the T2 system. (4) Execute I/O alloc ati on. (5) Program the "input type setting program". (see t he next page) (6) Turn the T2 to RUN mode.
3.1 Jumper plug setting
8 jumper plugs are provided on the AD268 board. The jumper plug setting is for selecting either voltage input or current input.
JP1 is for channel 1, JP2 is for channel 2, ... JP8 is for channel 8.
Jumper plugs (JP1 to JP8)
1
3
Set the jumper plugs for each channel.
Side 1: Voltage input Side 3: Current input
The fa ctory setting is voltage input (side 1).
Use a pair of tweezers to set the jumper plug.
Pay attention not to touch the components on
the board other than the jumper plug.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
13
PART 1 AD268
3. Input Type Setting
3.2 Parameter setting by software
The input range of the AD268 is specified by writing the following parameter data into the AD268's buffer memory. To access the buffer memory, T2 user program (READ and WRITE instructions) is required. When the parameter is set to the AD268, it is saved in the AD268's built-in EEPROM. Therefore, once the input type parameter is set, there is no need to execute the input type setting operation.
T2 CPU AD268
Input type parameter data:
Input typeParameter
data
Voltage input Current input 0 0 to 5V 0 to 20mA 1 0 to 10V 2 1 to 5V 4 to 20mA 4
±5V
5
±10V
AD268 buffer memory address:
H8018 Input type for channel 1 H8019 Input type for channel 2 H801A Input type for channel 3
H801B Input type for channel 4 H801C Input type for channel 5 H801D Input type for channel 6 H801E Input type for channel 7 H801F Input type for channel 8
The fact o ry se tting is
±10V range.
For details of the procedure to set the input type parameter, refer to section 6.
Buffer memory
User program
WRITE
READ
EEPROM
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
14
Analog I/O Modules (AD268 / DA264 / TC218)
4. Wiring
PART 1 AD268
4. Wiring
4.1 Terminal arrangement
AD268 terminal block
11P
1N 2
32P
2N 4
53P
3N 6
74P
4N 8
95P
5N 10
11 6P
6N 12
13 7P
7N 14
15 8P
8N 16
17 P24
COM 18
19 LG
FG 20
Terminal
No.
Signal
name
Function
11P 21N
Channel 1 input
32P 42N
Channel 2 input
53P 63N
Channel 3 input
74P 84N
Channel 4 input
95P
10 5N
Channel 5 input
11 6P 12 6N
Channel 6 input
13 7P 14 7N
Channel 7 input
15 8P 16 8N
Channel 8 input
17 P24 External 24Vdc power (+) 18 COM External 24Vdc power (-) 19 LG Line filter ground 20 FG Frame ground
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User’s Manual
15
PART 1 AD268
4. Wiring
4.2 Signal wiring
Voltage input
Current input
External 24Vdc power supply
+15V
AG -15V
nP
nN
Internal circuit
Shielded twisted-pair cable
n : Channe l number (1 to 8) AG : Analog ground FG : Frame ground
AG
250
+
-
V
Set the jumper
plug to Side 1
1 2
3
Voltage source
AD268
+15V
AG -15V
nP
nN
Internal circuit
Shielded twisted-pair cable
n : Channe l number (1 to 8) AG : Analog ground FG : Frame ground
AG
250
+
-
↑↑↑↑
Set the jumper
plug to Side 3
1 2
3
Current source
AD268
P24
COM
Internal circuit
Normally connect LG and FG, then connect to ground. (a) However, depending on the condition, connect groundi ng individually by opening LG and FG. (b)
AD268
LG
FG
+
-
24Vdc ±10%
(b) (a)
DC/DC
converter
+15V
-15V
AG
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
16
Analog I/O Modules (AD268 / DA264 / TC218)
4. Wiring
PART 1 AD268
4.3 Wiring precautions
(1) Use shielded twisted-pair cables for analog input signal lines and wire them in shortest
distance. Connect the cable shield to ground in shortest distance for EMC conformity. Normally the grounding method (a) is recommended. However, depending on the condition, method (b) or (c) may be useful for stable operation.
(2) Separate the analog signal cable from other cables to prevent noise interference. (200mm
or more)
(3) This module requires 24Vdc power. Apply the 24Vdc power before (or at the same time)
applying T2s main power. Otherwise, this module detects the external 24Vdc error.
(4) If the external 24Vdc power for this module is not stable, the converted data will not be
stable. In this case, use a dedicated 24Vdc power supply for this module.
(5) It is recommended to short the unused channels. Because if it is open for voltage input,
meaningless A/D conversion data will appear.
(6) If the converted data is not stable owing to electrical noise, it is recommended to use the
input averaging function to reduce the noise interference. For the averaging function, refer to section 6.
Analog input
module
FG
(a)
Analog input
module
FG
(b)
Analog input
module
FG
(c)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Users Manual
17
PART 1 AD268
5. I/O Allocation and Programming
5. I/O Allocation and Programming
5.1 Allocation to the T2 registers
The I/O type of the AD268 is "X 8W". When the automatic I/O allocation operation is performed with a AD268 mounted on the rack, the AD268 is allocated as "X 8W". The AD268 occupies the 8 consecutive input (XW) registers of the T2. In this manual, these assigned I/O registers are expressed as XW(n), XW(n+1), ... XW(n+7).
The following figure shows an example of I/O allocation window of the T-PDS programming software. In this case, the AD268 is mounted in the slot 0 of base unit BU218.
In the above example, the AD268 is allocated on the unit-0, slot-0. And 8 I/O registers, XW000 to XW007 are assigned to the AD268.
PS261
PU234E
No slot
DI32
Vacant
DO32
AD268
Vacant
Vacant
Vacant
Vacant
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
18
Analog I/O Modules (AD268 / DA264 / TC218)
5. I/O Allocation and Programming
PART 1 AD268
5.2 A/D conversion data
The analog signals received by the AD268 are converted into the digital data in this module. These con verted digital data are read by T2 CPU in the batch I/O processing and stored in the assigned input registers as follows.
XW(n) ........ A/D conversion data for channel 1
XW(n+1) .... A/D conversion data for channel 2
XW(n+2) .... A/D conversion data for channel 3
XW(n+3) .... A/D conversion data for channel 4
XW(n+4) .... A/D conversion data for channel 5
XW(n+5) .... A/D conversion data for channel 6
XW(n+6) .... A/D conversion data for channel 7
XW(n+7) .... A/D conversion data for channel 8
The conversion data stored in the XW register is dependent on the input type as follows.
±±±±10V range:
A/D conversion data
Input voltage
Hexadecimal Integer
Resolution
Upper limit +10. 2 V H7F80 32640
:: :
Full scale (positive) +1 0 V H7D00 32000
:: :
+0.3125 mV H0001 1
0 0 V H0000 0
-0.3125 mV HFFFF -1 :: :
Full scale (negative) - 10 V H8300 -32000
:: :
Lower limit -1 0 . 2 V H8080 -32640
0.3125 mV / bit
+10.2V
HC000
-16384
0
H3FFF
16383
+10V
H7D00 32000
+5.1196V-5.12V-10.2V
-10V
H8300
-32000
Digital value
Analog input
D = 3200 × A
D: Digital dat a A: Analog signal (V)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Users Manual
19
PART 1 AD268
5. I/O Allocation and Programming
±±±±5V ra nge :
A/D conversion data
Input voltage
Hexadecimal Integer
Resolution
Upper limit +5 .1196 V H3FFF 16383
:: :
Full scale (positive) +5 V H3E80 16000
:: :
+0.3125 mV H0001 1
0 0 V H0000 0
-0.3125 mV HFFFF -1 :: :
Full scale (negative) -5 V HC180 -16000
:: :
Lower limit -5 . 1 2 V HC000 -16384
0.3125 mV / bit
HC000
-16384
0
H3FFF
16383
+5V
H3E80 16000
+5.1196V-5.12V
-5V
HC180
-16000
Digital value
+10.2V-10.2V
Analog input
Upper limit
Lower limit
D = 3200 × A
D: Digital dat a A: Analog signal (V)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
20
Analog I/O Modules (AD268 / DA264 / TC218)
5. I/O Allocation and Programming
PART 1 AD268
0 to 10V range:
A/D conversion data
Input voltage
Hexadecimal Integer
Resolution
Upper limit +10. 2 V H7F80 32640
:: :
Full scale (positive) +1 0 V H7D00 32000
:: :
+0.3125 mV H0001 1
0 0 V H0000 0
0.3125 mV / bit
D = 3200 × A
D: Digital dat a A: Analog signal (V)
0
H3FFF
16383
Analog input
+5.1196V
Digital value
+10.2V
H7D00
32000
-10.2V
+10
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Users Manual
21
PART 1 AD268
5. I/O Allocation and Programming
0 to 5V / 0 to 20mA range:
Input voltage/current A/D conversion data
0 t o 5 V 0 t o 2 0 mA Hexadecimal Integer
Resolution
Upper limit +5.1196 V +20.479 mA H3FFF 16383
:: : :
Full scale (positive) +5 V +2 0 mA H3E80 16000
:: : :
+0.3125 mV +0.00125 mA H0001 1
0 0 V 0 mA H0000 0
0.3125 mV / bit
1.25 µA / bit
0 to 20mA range:
D = 800 × A
D: Digital dat a A: Analog signal (mA)
0
H3FFF
16383
Analog input
+5.1196V
20.479mA
Digital value
+10.2V
H3E80
16000
-10.2V
Upper limit
Lower limit
+5V
20mA
0 to 5V range:
D = 3200 × A
D: Digital data A: Analog signal (V)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
22
Analog I/O Modules (AD268 / DA264 / TC218)
5. I/O Allocation and Programming
PART 1 AD268
1 to 5V / 4 to 20mA range:
Input voltage/current A/D conversion data
1 t o 5 V 4 t o 2 0 mA Hexadecimal Integer
Resolution
Upper limit +5.1196 V +20.479 mA H337F 13183
:: : :
Full scale (positive) +5 V +2 0 mA H3200 12800
:: : :
+1.0003125 V +4.00125 mA H0001 1
Lower limit 1 V 4 mA H0000 0
0.3125 mV / bit
1.25 µA / bit
4 to 20mA range:
D = 800 × A - 3200
D: Digital dat a A: Analog signal (mA)
1 to 5V range:
D = 3200 × A - 3200
D: Digital dat a A: Analog signal (V)
0
Analog input value
+5.1196V
20.479mA
Digital value
+10.2V-10.2V
Upper limit
Lower limit
+5V
20mA
H3200
12800
H337F
13183
1V
4mA
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Users Manual
23
PART 1 AD268
5. I/O Allocation and Programming
5.3 Programming
To read the A/D conversion data, there is no need to use special instruction. The A/D conversion data are automatically stored in the assigned input registers (XW registers).
For example, when the AD268 is allocated to XW000 to XW007, the A/D conversion data of each channel is stored as follows.
XW000 : Channel 1 A/D conversion data XW001 : Channel 2 A/D conversion data XW002 : Channel 3 A/D conversion data XW003 : Channel 4 A/D conversion data XW004 : Channel 5 A/D conversion data XW005 : Channel 6 A/D conversion data XW006 : Channel 7 A/D conversion data XW007 : Channel 8 A/D conversion data
Therefore, in the us er program, you can use these XW registers directly for the analog data processing.
The program shown below is an example of simple comparison with the channel 1 analog data. (±10V setting)
Line 1: When XW000 is greater than 25600 (channel 1 analog input is more than 8V), R0100
is set to ON.
Line 2: When XW000 is in the range of -9600 to 9600 (channel 1 analog input is in the range
of -3V to 3V), R0101 is set to ON.
Line 3: When XW000 is less than -16000 (channel 1 analog input is less than -5V), R0102 is
set to ON.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
24
Analog I/O Modules (AD268 / DA264 / TC218)
6. Parame ters
PART 1 AD268
6. Parameters
The AD268 has the memory that stores the control parameters, input type designation, module status information, etc. This memory is called the buffer memory. To access (read/write) this memory from the T2 program, READ and WRITE instructions are used.
6.1 Memory map
The contents of the AD268's buffer memory are as fo llows.
Address Contents
F0
H8000 Gain calibration value for channel 1 H8001 Gain calibration value for channel 2 H8002 Gain calibration value for channel 3 H8003 Gain calibration value for channel 4 H8004 Gain calibration value for channel 5 H8005 Gain calibration value for channel 6 H8006 Gain calibration value for channel 7 H8007 Gain calibration value for channel 8 H8008 Offset calibration value for channel 1
H8009 Offset calibration value for channel 2 H800A Offset calibration value for channel 3 H800B Offset calibration value for channel 4 H800C Offset calibration value for channel 5 H800D Offset calibration value for channel 6 H800E Offset calibration value for channel 7 H800F Offset calibration value for channel 8
H8010 Averaging times for channel 1
H8011 Averaging times for channel 2
H8012 Averaging times for channel 3
H8013 Averaging times for channel 4
H8014 Averaging times for channel 5
H8015 Averaging times for channel 6
H8016 Averaging times for channel 7
H8017 Averaging times for channel 8
H8018 Input type setting for channel 1
H8019 Input type setting for channel 2 H801A Input type setting for channel 3 H801B Input type setting for channel 4 H801C Input type setting for channel 5 H801D Input type setting for channel 6 H801E Input type setting for channel 7 H801F Input type setting for channel 8
H8020 Command register
H8021 Response register
H8022
:
H8027
No use
Use WRITE instruction to write data into these addresses.
Use READ instruction to read data from this address.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net