11.HO W TO DIAGNOSE THE TROUBLE...................................................... 87
12.HOW TO REPLACE THE MAIN PARTS................................................. 107
13.EXPLODED VIEWS AND PARTS LIST................................................. 123
– 2 –
Revised
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm² (H07RN-F or 245IEC66) polychloroprene
sheathed flexible cord.
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because
the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the
adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during
installation work, be sure that water , dust, former refrigerant, or refrigeration machine oil does not enter into
the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging
port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units . For connecting pipes, use new
and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does
not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings
and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact
separation of at least 3 mm.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated.
Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCORRECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND
INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
– 3 –
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE
TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE
THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT
RESISTORS , FURNACE, STOVES , ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CAREFUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY
OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS
MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL
BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PERSONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE
WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE
REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY
RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or b ypass any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property
damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source such as a cooking range, noxious gas
may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external
forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture bef ore installation may result in an electrical short.
Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously perf ormed for a long time under the condition that the outdoor
temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner.
For details, contact the dealer.
– 4 –
2. SPECIFICATIONS
The indoor and outdoor units that can be used in combination are shown in the tables below.
Combinations of indoor unit models that can be connected
Refer to page 17 to 22
Refer to page 8 to 13
Refer to page 14 to 16
Indoor unit
NOTES
A 1-room connection is not an option for the indoor units (you cannot connect only one indoor unit).
Be sure to connect indoor units in two rooms or more.
The contents noted in this service manual limit the indoor units to the RAS-B10GKVP-E, RAS-B13GKVP-E,
RAS-B16GKVP-E, RAS-M10GKCVP-E, RAS-M13GKCVP-E and RAS-M16GKCVP-E.
For other indoor units that can also be used in combination, see the service manual of each indoor unit.
Net weight(kg)999
Fan motor output(W)303030
Air flow rate (Cooling/Heating)(m³/h)550/610560/640640/660
Unit model
Net weight(kg)6564
Compressor
Fan motor output(W)60
Air flow r ate(m³/h)High : 3000, Medium : 2800
TypeFlare connection
Indoor unit
Outdoor unit
Maximum length (per unit)(m)2525
Maximum length (total)(m)7050
Maximum chargeless length(m)7050
Maximum height difference(m)1515
Name of refrigerantR410A
Weight(k
Power supply3 Wires : includes earth
Interconnection4 Wires : includes earth
Indoor(Cooling/Heating)(°C)21 to 32/0 to 28
Outdoor(Coolin
Unit model
Installation plate111
Wireless remote controller111
Batteries222
Remote controller holder111
Running current(A)0.150.150.15
Power consumption(W)303030
Power factor(%)91/87/8391/87/8391/87/83
Unit model
Operati on mode
Running current(A)
Power consumption(W)2500225022502550
Power factor(%)98989898
Starting current(A)11.60/11.09/10.6311.83/11. 31/ 10.84
Unit model
High(dB•A)42/4343/4445/45
Medium(dB•A)33/3434/3536/36
Low(dB•A)27/2727/2729/29
Unit model
Full indoor units operatin
Motor output(W)2000
TypeTwin rotary type with DC-inverter variable speed control
ModelDA220A2F-20L
Unit model
Liquid side/Gas sideØ6.35/ Ø9.52Ø6.35/ Ø9.52Ø6.35/ Ø12.7
Unit model
A unit liquid side/Gas sideØ6.35/ Ø12.7Ø6.35/ Ø12.7
B unit liquid side/Gas sideØ6.35/ Ø9.52Ø6.35/ Ø9.52
C unit liquid side/Gas sideØ6.35/ Ø9.52Ø6.35/ Ø9.52
D unit liquid side/Gas sideØ6.35/ Ø9.52—
Net weight(kg)999
Fan motor output(W)303030
Air flow r ate(m³/h)550560640
Unit model
Net weight(kg)63
Fan motor output(W)60
Air flow r ate(m³/h)High : 3000, Medium : 2800
TypeFlare connection
Indoor unit
Outdoor unit
Maximum length (per unit)(m)25
Maximum length (total)(m)70
Maximum chargeless length(m)70
Maximum height difference(m)15
Name of refrigerantR410A
Weight(kg)2.2
Indoor unit
Outdoor unit
Running current(A)0.150.150.15
Power consumption(W)303030
Power factor(%)91/87/8391/87/8391/87/83
Unit model
Running current(A)11.60/11.09/10.63
Power consumption(W)2500
Power factor(%)98
Starting current(A)11.60/11.09/10.63
Unit model
High(dB•A)424345
Medium(dB•A)333436
Low(dB•A)272729
Unit model
Full indoor units operating(dB•A)48
Motor output(W)2000
TypeTwin rotary type with DC-inverter variable speed controlCompressor
ModelDA220A2F-20L
Unit model
Liquid side/Gas sideØ6.35/ Ø9.52Ø6.35/ Ø9.52Ø6.35/ Ø12.7
Unit model
A unit liquid side/Gas sideØ6.35/ Ø12.7
B unit liquid side/Gas sideØ6.35/ Ø9.52
C unit liquid side/Gas sideØ6.35/ Ø9.52
D unit liquid side/Gas sideØ6.35/ Ø9.52
Power supply3 Wires : includes earth
Interconnection4 Wires : includes earth
Indoor(°C )21 to 32
Outdoor(°C)10 to 43
Unit model
Installation plate111
Wireless remote controller111
Batteries222
Remote controller holder111
Zeolite-plus filter111
Plasma pure filter111
Remote controller holder mounting screw2 (Ø3.1 × 16L)2 (Ø3.1 × 16L)2 (Ø3.1 × 16L)
Owner’s manual111
Mounting screw6 (Ø4 × 25L)6 (Ø4 × 25L)6 (Ø4 × 25L)
Installation manual111
Unit model
Installation manual1
Specifications1
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E
RAS-4M27GACV - E
RAS-M10GKCVP-ERAS-M13GKCVP-ERAS-M16GKCVP-E
RAS-4M27GACV - E
RAS-M10GKCVP-ERAS-M13GKCVP-ERAS-M16GKCVP-E
RAS-4M27GACV - E
RAS-M10GKCVP-ERAS-M13GKCVP-ERAS-M16GKCVP-E
RAS-4M27GACV - E
RAS-M10GKCVP-ERAS-M13GKCVP-ERAS-M16GKCVP-E
RAS-4M27GACV - E
RAS-M10GKCVP-ERAS-M13GKCVP-ERAS-M16GKCVP-E
RAS-4M27GACV - E
• For performance when each indoor unit is combined with other unit, refer to the separate table.
• The specifications may be subject to change without notice for purpose of improvement.
– 7 –
2-2. Specifications of Performance When Each Indoor Unit is Combined with Other Unit
pply
p
g
p
Outdoor Unit : RAS-4M27GAV-E
<Cooling/220V>
O
su
(V)
2201 unit10–––2.70–––
eratin
status
2 units1010––2.702.70––
3 units101010–2.532.532.53–
4 units101010101.981.981.981.98
Indoor unitUnit capacity (kW)Power
ABCD A B C D
13–––3.70–––
16–––4.50–––
1310––3.412.49––
1610––3.942.36––
1313––3.153.15––
1613––3.733.07––
1616––3.603.60––
131010–3.132.282.28–
161010–3.502.102.10–
131310–2.822.822.06–
161310–3.222.651.93–
131313–2.602.602.60–
161610–3.043.041.82–
161313–2.992.462.46–
161613–2.802.802.30–
161616–2.672.672.67–
131010102.481.811.811.81
161010102.861.711.711.71
131310102.312.311.691.69
161310102.652.181.591.59
131313102.142.142.141.57
161313102.472.032.031.48
131313132.002.002.002.00
161610102.502.501.501.50
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.6
(3.8 to 8.2)
7.7
(3.9 to 8.3)
7.7
(4.0 to 8.5)
7.7
(4.0 to 8.5)
7.8
(4.1 to 8.6)
7.8
(4.1 to 8.6)
7.9
(4.1 to 8.7)
7.9
(4.1 to 8.7)
7.9
(4.2 to 8.9)
8.0
(4.3 to 9.0)
7.9
(4.0 to 8.7)
7.9
(4.1 to 8.8)
8.0
(4.1 to 9.0)
8.0
(4.1 to 9.0)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(960 to 2740)
(960 to 2790)
(960 to 2790)
(970 to 2810)
(970 to 2810)
(970 to 2830)
(970 to 2830)
(970 to 2880)
(980 to 2900)
(930 to 2800)
(940 to 2820)
(940 to 2860)
(940 to 2860)
(950 to 2880)
(950 to 2880)
(950 to 2900)
(950 to 2900)
(950 to 2900)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2400
2410
2410
2410
2430
2430
2440
2440
2440
2450
2450
2450
2500
2500
2500
2500
2500
2500
2500
Operating
current
(A)
3.87
(3.68 to 4.64 )
5.74
(3.68 to 7.20 )
7.81
(3.68 to 9.28 )
7.10
(3.64 to 9.46 )
8.40
(3.75 to 10.30)
9.46
(3.81 to 11.13)
9.46
(3.81 to 11.13)
10.76
(3.92 to 11.92)
11.83
(3.98 to 12.76)
11.13
(4.80 to 12.62)
11.18
(4.85 to 12.71)
11.18
(4.85 to 12.94)
11.18
(4.85 to 12.94)
11.27
(4.90 to 13.03)
11.27
(4.90 to 13.03)
11.32
(4.90 to 13.13)
11.32
(4.90 to 13.13)
11.32
(4.90 to 13.36)
11.36
(4.95 to 13.45)
11.36
(4.70 to 12.99)
11.36
(4.75 to 13.08)
11.60
(4.75 to 13.27)
11.60
(4.75 to 13.27)
11.60
(4.80 to 13.36)
11.60
(4.80 to 13.36)
11.60
(4.80 to 13.45)
11.60
(4.80 to 13.45)
11.60
(4.80 to 13.45)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 8 –
Outdoor Unit : RAS-4M27GAV-E
pply
p
g
p
<Cooling/230V>
O
su
(V)
2301 unit10–––2.7–––
eratin
status
2 units1010––2.702.70––
3 units101010–2.532.532.53–
4 units101010101.981.981.981.98
Indoor unitUnit capa ci t y (kW )Power
ABCD A B C D
13–––3.7–––
16–––4.5–––
1310––3.412.49––
1610––3.942.36––
1313––3.153.15––
1613––3.733.07––
1616––3.603.60––
131010–3.132.282.28–
161010–3.502.102.10–
131310–2.822.822.06–
161310–3.222.651.93–
131313–2.602.602.60–
161610–3.043.041.82–
161313–2.992.462.46–
161613–2.802.802.30–
161616–2.672.672.67–
131010102.481.811.811.81
161010102.861.711.711.71
131310102.312.311.691.69
161310102.652.181.591.59
131313102.142.142.141.57
161313102.472.032.031.48
131313132.002.002.002.00
161610102.502.501.501.50
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.6
(3.8 to 8.2)
7.7
(3.9 to 8.3)
7.7
(4.0 to 8.5)
7.7
(4.0 to 8.5)
7.8
(4.1 to 8.6)
7.8
(4.1 to 8.6)
7.9
(4.1 to 8.7)
7.9
(4.1 to 8.7)
7.9
(4.2 to 8.9)
8.0
(4.3 to 9.0)
7.9
(4.0 to 8.7)
7.9
(4.1 to 8.8)
8.0
(4.1 to 9.0)
8.0
(4.1 to 9.0)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(960 to 2740)
(960 to 2790)
(960 to 2790)
(970 to 2810)
(970 to 2810)
(970 to 2830)
(970 to 2830)
(970 to 2880)
(980 to 2900)
(930 to 2800)
(940 to 2820)
(940 to 2860)
(940 to 2860)
(950 to 2880)
(950 to 2880)
(950 to 2900)
(950 to 2900)
(950 to 2900)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2400
2410
2410
2410
2430
2430
2440
2440
2440
2450
2450
2450
2500
2500
2500
2500
2500
2500
2500
Operating
current
(A)
3.71
(3.52 to 4.44 )
5.49
(3.52 to 6.88 )
7.47
(3.52 to 8.87 )
6.79
(3.48 to 9.05 )
8.03
(3.59 to 9.85 )
9.05
(3.64 to 10.65)
9.05
(3.64 to 10.65)
10.29
(3.75 to 11.40)
11.31
(3.80 to 12.20)
10.65
(4.59 to 12.07)
10.69
(4.64 to 12.16)
10.69
(4.64 to 12.38)
10.69
(4.64 to 12.38)
10.78
(4.69 to 12.47)
10.78
(4.69 to 12.47)
10.83
(4.69 to 12.56)
10.83
(4.69 to 12.56)
10.83
(4.69 to 12.78)
10.87
(4.73 to 12.87)
10.87
(4.49 to 12.42)
10.87
(4.54 to 12.51)
11.09
(4.54 to 12.69)
11.09
(4.54 to 12.69)
11.09
(4.59 to 12.78)
11.09
(4.59 to 12.78)
11.09
(4.59 to 12.87)
11.09
(4.59 to 12.87)
11.09
(4.59 to 12.87)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 9 –
Outdoor Unit : RAS-4M27GAV-E
pply
p
g
p
<Cooling/240V>
O
su
(V)
2401 unit10–––2.7–––
eratin
status
2 units1010––2.702.70––
3 units101010–2.532.532.53–
4 units101010101.981.981.981.98
Indoor unitUnit capa ci t y (kW )Power
ABCD A B C D
13–––3.7–––
16–––4.5–––
1310––3.412.49––
1610––3.942.36––
1313––3.153.15––
1613––3.733.07––
1616––3.603.60––
131010–3.132.282.28–
161010–3.502.102.10–
131310–2.822.822.06–
161310–3.222.651.93–
131313–2.602.602.60–
161610–3.043.041.82–
161313–2.992.462.46–
161613–2.802.802.30–
161616–2.672.672.67–
131010102.481.811.811.81
161010102.861.711.711.71
131310102.312.311.691.69
161310102.652.181.591.59
131313102.142.142.141.57
161313102.472.032.031.48
131313132.002.002.002.00
161610102.502.501.501.50
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.6
(3.8 to 8.2)
7.7
(3.9 to 8.3)
7.7
(4.0 to 8.5)
7.7
(4.0 to 8.5)
7.8
(4.1 to 8.6)
7.8
(4.1 to 8.6)
7.9
(4.1 to 8.7)
7.9
(4.1 to 8.7)
7.9
(4.2 to 8.9)
8.0
(4.3 to 9.0)
7.9
(4.0 to 8.7)
7.9
(4.1 to 8.8)
8.0
(4.1 to 9.0)
8.0
(4.1 to 9.0)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(960 to 2740)
(960 to 2790)
(960 to 2790)
(970 to 2810)
(970 to 2810)
(970 to 2830)
(970 to 2830)
(970 to 2880)
(980 to 2900)
(930 to 2800)
(940 to 2820)
(940 to 2860)
(940 to 2860)
(950 to 2880)
(950 to 2880)
(950 to 2900)
(950 to 2900)
(950 to 2900)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2400
2410
2410
2410
2430
2430
2440
2440
2440
2450
2450
2450
2500
2500
2500
2500
2500
2500
2500
Operating
current
(A)
3.55
(3.38 to 4.26 )
5.26
(3.38 to 6.60 )
7.16
(3.38 to 8.50 )
6.51
(3.33 to 8.67 )
7.70
(3.44 to 9.44 )
8.67
(3.49 to 10.20)
8.67
(3.49 to 10.20)
9.86
(3.59 to 10.93)
10.84
(3.65 to 11.69)
10.20
(4.40 to 11.56)
10.25
(4.44 to 11.65)
10.25
(4.44 to 11.86)
10.25
(4.44 to 11.86)
10.33
(4.49 to 11.95)
10.33
(4.49 to 11.95)
10.37
(4.49 to 12.03)
10.37
(4.49 to 12.03)
10.37
(4.49 to 12.24)
10.42
(4.54 to 12.33)
10.42
(4.31 to 11.90)
10.42
(4.35 to 11.99)
10.63
(4.35 to 12.16)
10.63
(4.35 to 12.16)
10.63
(4.40 to 12.24)
10.63
(4.40 to 12.24)
10.63
(4.40 to 12.33)
10.63
(4.40 to 12.33)
10.63
(4.40 to 12.33)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 10 –
Outdoor Unit : RAS-4M27GAV-E
pply
p
g
p
<Heating/220V>
O
su
(V)
2201 unit10–––4.0–––
eratin
status
2 units1010––3.603.60––
3 units101010–2.872.872.87–
4 units101010102.232.232.232.23
Indoor unitUnit capacity (kW)Power
ABCD A B C D
13–––5.0–––
16–––5.5–––
1310––4.223.38––
1610––4.573.33––
1313––3.953.95––
1613––4.353.95––
1616––4.304.30––
131010–3.352.682.68–
161010–3.542.582.58–
131310–3.113.112.49–
161310–3.343.032.43–
131313–2.932.932.93–
161610–3.263.262.37–
161313–3.162.872.87–
161613–3.063.062.78–
161616–3.003.003.00–
131010102.622.092.092.09
161010102.832.062.062.06
131310102.502.502.002.00
161310102.682.431.951.95
131313102.372.372.371.89
161313102.542.312.311.85
131313132.252.252.252.25
161610102.612.611.891.89
Heating
capacity
(kW)
4.0
(0.8 to 5.2)
5.0
(0.8 to 6.5)
5.5
(0.8 to 6.9)
7.2
(1.5 to 10.0)
7.6
(1.5 to 10.1)
7.9
(1.5 to 10.1)
7.9
(1.5 to 10.1)
8.3
(1.5 to 10.2)
8.6
(1.5 to 10.2)
8.6
(2.0 to 10.4)
8.7
(2.0 to 10.5)
8.7
(2.0 to 10.5)
8.7
(2.0 to 10.5)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
9.0
(2.0 to 10.8)
8.9
(2.2 to 10.8)
8.9
(2.2 to 10.9)
9.0
(2.2 to 10.9)
9.0
(2.2 to 10.9)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
Power
consum
(300 to 1980)
(310 to 2750)
(310 to 3000)
(320 to 3200)
(320 to 3210)
(320 to 3230)
(320 to 3230)
(320 to 3240)
(320 to 3250)
(380 to 2750)
(380 to 2760)
(380 to 2760)
(380 to 2760)
(380 to 2780)
(380 to 2780)
(380 to 2790)
(380 to 2790)
(380 to 2790)
(380 to 2800)
(450 to 2810)
(460 to 2830)
(460 to 2830)
(470 to 2830)
(480 to 2850)
(480 to 2850)
(490 to 2850)
(490 to 2850)
(500 to 2850)
(W)
1450
2050
2400
2100
2320
2480
2480
2700
2860
2300
2350
2350
2350
2400
2400
2450
2450
2450
2500
2100
2100
2250
2250
2250
2250
2250
2250
2250
tion
Operating
current
(A)
6.73
(1.87 to 9.18 )
9.51
(1.93 to 12.76)
11.13
(1.93 to 13.91)
9.74
(1.94 to 14.84)
10.76
(1.94 to 14.89)
11.50
(1.94 to 14.98)
11.50
(1.94 to 14.98)
12.52
(1.94 to 15.03)
13.27
(1.94 to 15.07)
10.67
(2.16 to 12.76)
10.90
(2.16 to 12.80)
10.90
(2.16 to 12.80)
10.90
(2.16 to 12.80)
11.13
(2.16 to 12.89)
11.13
(2.16 to 12.89)
11.36
(2.16 to 12.94)
11.36
(2.16 to 12.94)
11.36
(2.16 to 12.94)
11.60
(2.16 to 12.99)
9.74
(2.56 to 13.03)
9.74
(2.61 to 13.13)
10.44
(2.61 to 13.13)
10.44
(2.67 to 13.13)
10.44
(2.73 to 13.22)
10.44
(2.73 to 13.22)
10.44
(2.78 to 13.22)
10.44
(2.78 to 13.22)
10.44
(2.84 to 13.22)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/
WB=7/6°C.
– 11 –
Outdoor Unit : RAS-4M27GAV-E
pply
p
g
p
<Heating/230V>
O
su
(V)
2301 unit10–––4.0–––
eratin
status
2 units1010––3.603.60––
3 units101010–2.872.872.87–
4 units101010102.232.232.232.23
Indoor unitUnit capa ci t y (kW )Power
ABCD A B C D
13–––5.0–––
16–––5.5–––
1310––4.223.38––
1610––4.573.33––
1313––3.953.95––
1613––4.353.95––
1616––4.304.30––
131010–3.352.682.68–
161010–3.542.582.58–
131310–3.113.112.49–
161310–3.343.032.43–
131313–2.932.932.93–
161610–3.263.262.37–
161313–3.162.872.87–
161613–3.063.062.78–
161616–3.003.003.00–
131010102.622.092.092.09
161010102.832.062.062.06
131310102.502.502.002.00
161310102.682.431.951.95
131313102.372.372.371.89
161313102.542.312.311.85
131313132.252.252.252.25
161610102.612.611.891.89
Heating
capacity
(kW)
4.0
(0.8 to 5.2)
5.0
(0.8 to 6.5)
5.5
(0.8 to 6.9)
7.2
(1.5 to 10.0)
7.6
(1.5 to 10.1)
7.9
(1.5 to 10.1)
7.9
(1.5 to 10.1)
8.3
(1.5 to 10.2)
8.6
(1.5 to 10.2)
8.6
(2.0 to 10.4)
8.7
(2.0 to 10.5)
8.7
(2.0 to 10.5)
8.7
(2.0 to 10.5)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
9.0
(2.0 to 10.8)
8.9
(2.2 to 10.8)
8.9
(2.2 to 10.9)
9.0
(2.2 to 10.9)
9.0
(2.2 to 10.9)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
Power
consum
(300 to 1980)
(310 to 2750)
(310 to 3000)
(320 to 3200)
(320 to 3210)
(320 to 3230)
(320 to 3230)
(320 to 3240)
(320 to 3250)
(380 to 2750)
(380 to 2760)
(380 to 2760)
(380 to 2760)
(380 to 2780)
(380 to 2780)
(380 to 2790)
(380 to 2790)
(380 to 2790)
(380 to 2800)
(450 to 2810)
(460 to 2830)
(460 to 2830)
(470 to 2830)
(480 to 2850)
(480 to 2850)
(490 to 2850)
(490 to 2850)
(500 to 2850)
(W)
1450
2050
2400
2100
2320
2480
2480
2700
2860
2300
2350
2350
2350
2400
2400
2450
2450
2450
2500
2100
2100
2250
2250
2250
2250
2250
2250
2250
tion
Operating
current
(A)
6.43
(1.79 to 8.78 )
9.09
(1.85 to 12.20)
10.65
(1.85 to 13.31)
9.32
(1.86 to 14.20)
10.29
(1.86 to 14.24)
11.00
(1.86 to 14.33)
11.00
(1.86 to 14.33)
11.98
(1.86 to 14.37)
12.69
(1.86 to 14.42)
10.20
(2.07 to 12.20)
10.43
(2.07 to 12.24)
10.43
(2.07 to 12.24)
10.43
(2.07 to 12.24)
10.65
(2.07 to 12.33)
10.65
(2.07 to 12.33)
10.87
(2.07 to 12.38)
10.87
(2.07 to 12.38)
10.87
(2.07 to 12.38)
11.09
(2.07 to 12.42)
9.32
(2.45 to 12.47)
9.32
(2.50 to 12.56)
9.98
(2.50 to 12.56)
9.98
(2.55 to 12.56)
9.98
(2.61 to 12.64)
9.98
(2.61 to 12.64)
9.98
(2.66 to 12.64)
9.98
(2.66 to 12.64)
9.98
(2.72 to 12.64)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/
WB=7/6°C.
– 12 –
Outdoor Unit : RAS-4M27GAV-E
pply
p
g
p
<Heating/240V>
O
su
(V)
2401 unit10–––4.0–––
eratin
status
2 units1010––3.603.60––
3 units101010–2.872.872.87–
4 units101010102.232.232.232.23
Indoor unitUnit capa ci t y (kW )Power
ABCD A B C D
13–––5.0–––
16–––5.5–––
1310––4.223.38––
1610––4.573.33––
1313––3.953.95––
1613––4.353.95––
1616––4.304.30––
131010–3.352.682.68–
161010–3.542.582.58–
131310–3.113.112.49–
161310–3.343.032.43–
131313–2.932.932.93–
161610–3.263.262.37–
161313–3.162.872.87–
161613–3.063.062.78–
161616–3.003.003.00–
131010102.622.092.092.09
161010102.832.062.062.06
131310102.502.502.002.00
161310102.682.431.951.95
131313102.372.372.371.89
161313102.542.312.311.85
131313132.252.252.252.25
161610102.612.611.891.89
Heating
capacity
(kW)
4.0
(0.8 to 5.2)
5.0
(0.8 to 6.5)
5.5
(0.8 to 6.9)
7.2
(1.5 to 10.0)
7.6
(1.5 to 10.1)
7.9
(1.5 to 10.1)
7.9
(1.5 to 10.1)
8.3
(1.5 to 10.2)
8.6
(1.5 to 10.2)
8.6
(2.0 to 10.4)
8.7
(2.0 to 10.5)
8.7
(2.0 to 10.5)
8.7
(2.0 to 10.5)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
9.0
(2.0 to 10.8)
8.9
(2.2 to 10.8)
8.9
(2.2 to 10.9)
9.0
(2.2 to 10.9)
9.0
(2.2 to 10.9)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
9.0
(2.2 to 11.0)
Power
consum
(300 to 1980)
(310 to 2750)
(310 to 3000)
(320 to 3200)
(320 to 3210)
(320 to 3230)
(320 to 3230)
(320 to 3240)
(320 to 3250)
(380 to 2750)
(380 to 2760)
(380 to 2760)
(380 to 2760)
(380 to 2780)
(380 to 2780)
(380 to 2790)
(380 to 2790)
(380 to 2790)
(380 to 2800)
(450 to 2810)
(460 to 2830)
(460 to 2830)
(470 to 2830)
(480 to 2850)
(480 to 2850)
(490 to 2850)
(490 to 2850)
(500 to 2850)
(W)
1450
2050
2400
2100
2320
2480
2480
2700
2860
2300
2350
2350
2350
2400
2400
2450
2450
2450
2500
2100
2100
2250
2250
2250
2250
2250
2250
2250
tion
Operating
current
(A)
6.16
(1.71 to 8.42 )
8.72
(1.77 to 11.69)
10.20
(1.77 to 12.76)
8.93
(1.78 to 13.61)
9.86
(1.78 to 13.65)
10.54
(1.78 to 13.73)
10.54
(1.78 to 13.73)
11.48
(1.78 to 13.78)
12.16
(1.78 to 13.82)
9.78
(1.98 to 11.69)
9.99
(1.98 to 11.73)
9.99
(1.98 to 11.73)
9.99
(1.98 to 11.73)
10.20
(1.98 to 11.82)
10.20
(1.98 to 11.82)
10.42
(1.98 to 11.86)
10.42
(1.98 to 11.86)
10.42
(1.98 to 11.86)
10.63
(1.98 to 11.90)
8.93
(2.34 to 11.95)
8.93
(2.40 to 12.03)
9.57
(2.40 to 12.03)
9.57
(2.45 to 12.03)
9.57
(2.50 to 12.12)
9.57
(2.50 to 12.12)
9.57
(2.55 to 12.12)
9.57
(2.55 to 12.12)
9.57
(2.60 to 12.12)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/
WB=7/6°C.
– 13 –
Outdoor Unit : RAS-4M27GACV-E
pply
p
g
p
<Cooling/220V>
O
su
(V)
2201 unit10–––2.7–––
eratin
status
2 units1010––2.702.70––
3 units101010–2.532.532.53–
4 units101010101.981.981.981.98
Indoor unitUnit capacity (kW)Power
ABCD A B C D
13–––3.7–––
16–––4.5–––
1310––3.412.49––
1610––3.942.36––
1313––3.153.15––
1613––3.733.07––
1616––3.603.60––
131010–3.132.282.28–
161010–3.502.102.10–
131310–2.822.822.06–
161310–3.222.651.93–
131313–2.602.602.60–
161610–3.043.041.82–
161313–2.992.462.46–
161613–2.802.802.30–
161616–2.672.672.67–
131010102.481.811.811.81
161010102.861.711.711.71
131310102.312.311.691.69
161310102.652.181.591.59
131313102.142.142.141.57
161313102.472.032.031.48
131313132.002.002.002.00
161610102.502.501.501.50
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.6
(3.8 to 8.2)
7.7
(3.9 to 8.3)
7.7
(4.0 to 8.5)
7.7
(4.0 to 8.5)
7.8
(4.1 to 8.6)
7.8
(4.1 to 8.6)
7.9
(4.1 to 8.7)
7.9
(4.1 to 8.7)
7.9
(4.2 to 8.9)
8.0
(4.3 to 9.0)
7.9
(4.0 to 8.7)
7.9
(4.1 to 8.8)
8.0
(4.1 to 9.0)
8.0
(4.1 to 9.0)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(960 to 2740)
(960 to 2790)
(960 to 2790)
(970 to 2810)
(970 to 2810)
(970 to 2830)
(970 to 2830)
(970 to 2880)
(980 to 2900)
(930 to 2800)
(940 to 2820)
(940 to 2860)
(940 to 2860)
(950 to 2880)
(950 to 2880)
(950 to 2900)
(950 to 2900)
(950 to 2900)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2400
2410
2410
2410
2430
2430
2440
2440
2440
2450
2450
2450
2500
2500
2500
2500
2500
2500
2500
Operating
current
(A)
3.87
(3.68 to 4.64 )
5.74
(3.68 to 7.20 )
7.81
(3.68 to 9.28 )
7.10
(3.64 to 9.46 )
8.40
(3.75 to 10.30)
9.46
(3.81 to 11.13)
9.46
(3.81 to 11.13)
10.76
(3.92 to 11.92)
11.83
(3.98 to 12.76)
11.13
(4.80 to 12.62)
11.18
(4.85 to 12.71)
11.18
(4.85 to 12.94)
11.18
(4.85 to 12.94)
11.27
(4.90 to 13.03)
11.27
(4.90 to 13.03)
11.32
(4.90 to 13.13)
11.32
(4.90 to 13.13)
11.32
(4.90 to 13.36)
11.36
(4.95 to 13.45)
11.36
(4.70 to 12.99)
11.36
(4.75 to 13.08)
11.60
(4.75 to 13.27)
11.60
(4.75 to 13.27)
11.60
(4.80 to 13.36)
11.60
(4.80 to 13.36)
11.60
(4.80 to 13.45)
11.60
(4.80 to 13.45)
11.60
(4.80 to 13.45)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 14 –
Outdoor Unit : RAS-4M27GACV-E
pply
p
g
p
<Cooling/230V>
O
su
(V)
2301 unit10–––2.7–––
eratin
status
2 units1010––2.702.70––
3 units101010–2.532.532.53–
4 units101010101.981.981.981.98
Indoor unitUnit capa ci t y (kW )Power
ABCD A B C D
13–––3.7–––
16–––4.5–––
1310––3.412.49––
1610––3.942.36––
1313––3.153.15––
1613––3.733.07––
1616––3.603.60––
131010–3.132.282.28–
161010–3.502.102.10–
131310–2.822.822.06–
161310–3.222.651.93–
131313–2.602.602.60–
161610–3.043.041.82–
161313–2.992.462.46–
161613–2.802.802.30–
161616–2.672.672.67–
131010102.481.811.811.81
161010102.861.711.711.71
131310102.312.311.691.69
161310102.652.181.591.59
131313102.142.142.141.57
161313102.472.032.031.48
131313132.002.002.002.00
161610102.502.501.501.50
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.6
(3.8 to 8.2)
7.7
(3.9 to 8.3)
7.7
(4.0 to 8.5)
7.7
(4.0 to 8.5)
7.8
(4.1 to 8.6)
7.8
(4.1 to 8.6)
7.9
(4.1 to 8.7)
7.9
(4.1 to 8.7)
7.9
(4.2 to 8.9)
8.0
(4.3 to 9.0)
7.9
(4.0 to 8.7)
7.9
(4.1 to 8.8)
8.0
(4.1 to 9.0)
8.0
(4.1 to 9.0)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(960 to 2740)
(960 to 2790)
(960 to 2790)
(970 to 2810)
(970 to 2810)
(970 to 2830)
(970 to 2830)
(970 to 2880)
(980 to 2900)
(930 to 2800)
(940 to 2820)
(940 to 2860)
(940 to 2860)
(950 to 2880)
(950 to 2880)
(950 to 2900)
(950 to 2900)
(950 to 2900)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2400
2410
2410
2410
2430
2430
2440
2440
2440
2450
2450
2450
2500
2500
2500
2500
2500
2500
2500
Operating
current
(A)
3.71
(3.52 to 4.44 )
5.49
(3.52 to 6.88 )
7.47
(3.52 to 8.87 )
6.79
(3.48 to 9.05 )
8.03
(3.59 to 9.85 )
9.05
(3.64 to 10.65)
9.05
(3.64 to 10.65)
10.29
(3.75 to 11.40)
11.31
(3.80 to 12.20)
10.65
(4.59 to 12.07)
10.69
(4.64 to 12.16)
10.69
(4.64 to 12.38)
10.69
(4.64 to 12.38)
10.78
(4.69 to 12.47)
10.78
(4.69 to 12.47)
10.83
(4.69 to 12.56)
10.83
(4.69 to 12.56)
10.83
(4.69 to 12.78)
10.87
(4.73 to 12.87)
10.87
(4.49 to 12.42)
10.87
(4.54 to 12.51)
11.09
(4.54 to 12.69)
11.09
(4.54 to 12.69)
11.09
(4.59 to 12.78)
11.09
(4.59 to 12.78)
11.09
(4.59 to 12.87)
11.09
(4.59 to 12.87)
11.09
(4.59 to 12.87)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 15 –
Outdoor Unit : RAS-4M27GACV-E
pply
p
g
p
<Cooling/240V>
O
su
(V)
2401 unit10–––2.7–––
eratin
status
2 units1010––2.702.70––
3 units101010–2.532.532.53–
4 units101010101.981.981.981.98
Indoor unitUnit capa ci t y (kW )Power
ABCD A B C D
13–––3.7–––
16–––4.5–––
1310––3.412.49––
1610––3.942.36––
1313––3.153.15––
1613––3.733.07––
1616––3.603.60––
131010–3.132.282.28–
161010–3.502.102.10–
131310–2.822.822.06–
161310–3.222.651.93–
131313–2.602.602.60–
161610–3.043.041.82–
161313–2.992.462.46–
161613–2.802.802.30–
161616–2.672.672.67–
131010102.481.811.811.81
161010102.861.711.711.71
131310102.312.311.691.69
161310102.652.181.591.59
131313102.142.142.141.57
161313102.472.032.031.48
131313132.002.002.002.00
161610102.502.501.501.50
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.6
(3.8 to 8.2)
7.7
(3.9 to 8.3)
7.7
(4.0 to 8.5)
7.7
(4.0 to 8.5)
7.8
(4.1 to 8.6)
7.8
(4.1 to 8.6)
7.9
(4.1 to 8.7)
7.9
(4.1 to 8.7)
7.9
(4.2 to 8.9)
8.0
(4.3 to 9.0)
7.9
(4.0 to 8.7)
7.9
(4.1 to 8.8)
8.0
(4.1 to 9.0)
8.0
(4.1 to 9.0)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.1)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
8.0
(4.2 to 9.2)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(960 to 2740)
(960 to 2790)
(960 to 2790)
(970 to 2810)
(970 to 2810)
(970 to 2830)
(970 to 2830)
(970 to 2880)
(980 to 2900)
(930 to 2800)
(940 to 2820)
(940 to 2860)
(940 to 2860)
(950 to 2880)
(950 to 2880)
(950 to 2900)
(950 to 2900)
(950 to 2900)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2400
2410
2410
2410
2430
2430
2440
2440
2440
2450
2450
2450
2500
2500
2500
2500
2500
2500
2500
Operating
current
(A)
3.55
(3.38 to 4.26 )
5.26
(3.38 to 6.60 )
7.16
(3.38 to 8.50 )
6.51
(3.33 to 8.67 )
7.70
(3.44 to 9.44 )
8.67
(3.49 to 10.20)
8.67
(3.49 to 10.20)
9.86
(3.59 to 10.93)
10.84
(3.65 to 11.69)
10.20
(4.40 to 11.56)
10.25
(4.44 to 11.65)
10.25
(4.44 to 11.86)
10.25
(4.44 to 11.86)
10.33
(4.49 to 11.95)
10.33
(4.49 to 11.95)
10.37
(4.49 to 12.03)
10.37
(4.49 to 12.03)
10.37
(4.49 to 12.24)
10.42
(4.54 to 12.33)
10.42
(4.31 to 11.90)
10.42
(4.35 to 11.99)
10.63
(4.35 to 12.16)
10.63
(4.35 to 12.16)
10.63
(4.40 to 12.24)
10.63
(4.40 to 12.24)
10.63
(4.40 to 12.33)
10.63
(4.40 to 12.33)
10.63
(4.40 to 12.33)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 16 –
Outdoor Unit : RAS-3M26GAV-E
y
p
g
p
<Cooling/220V>
Power
suppl
O
eratin
(V)
2201 unit10––2.7––
status
2 units1010–2.702.70–
3 units1010102.472.472. 47
Indoor unitUnit capacity (kW)
ABCABC
13––3.7––
16––4.5––
1310–3.412.49–
1610–3.942.36–
1313–3.153.15–
1613–3.733.07–
1616–3.603.60–
1310103.012.202.20
1610103.362.022.02
1313102.712.711.98
1613103.102.551.86
1313132.502.502.50
1616102.882.881.73
1613132.842.332.33
1616132.662.662.19
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.4
(3.8 to 8.2)
7.4
(3.9 to 8.3)
7.4
(4.0 to 8.5)
7.4
(4.0 to 8.5)
7.5
(4.0 to 8.6)
7.5
(4.0 to 8.6)
7.5
(4.1 to 8.8)
7.5
(4.1 to 8.8)
7.5
(4.2 to 8.9)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(950 to 2750)
(950 to 2820)
(950 to 2820)
(980 to 2850)
(980 to 2850)
(980 to 2920)
(980 to 2920)
(980 to 2950)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2230
2230
2230
2230
2250
2250
2250
2250
2250
Operating
current
(A)
3.87
(3.68 to 4.64 )
5.74
(3.68 to 7.20 )
7.81
(3.68 to 9.28 )
7.10
(3.64 to 9.46 )
8.40
(3.75 to 10.30)
9.46
(3.81 to 11.13)
9.46
(3.81 to 11.13)
10.76
(3.92 to 11.92)
11.83
(3.98 to 12.76)
10.34
(4.80 to 12.62)
10.34
(4.80 to 12.76)
10.34
(4.80 to 13.08)
10.34
(4.80 to 13.08)
10.44
(4.95 to 13.22)
10.44
(4.95 to 13.22)
10.44
(4.95 to 13.54)
10.44
(4.95 to 13.54)
10.44
(4.95 to 13.68)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 17 –
Outdoor Unit : RAS-3M26GAV-E
y
p
g
p
<Cooling/230V>
Power
suppl
O
eratin
(V)
2301 unit10––2.7––
status
2 units1010–2.702.70–
3 units1010102.472.472.47
Indoor unitUnit capacity (kW)
ABCABC
13––3.7––
16––4.5––
1310–3.412.49–
1610–3.942.36–
1313–3.153.15–
1613–3.733.07–
1616–3.603.60–
1310103.012.202.20
1610103.362.022.02
1313102.712.711.98
1613103.102.551.86
1313132.502.502.50
1616102.882.881.73
1613132.842.332.33
1616132.662.662.19
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.4
(3.8 to 8.2)
7.4
(3.9 to 8.3)
7.4
(4.0 to 8.5)
7.4
(4.0 to 8.5)
7.5
(4.0 to 8.6)
7.5
(4.0 to 8.6)
7.5
(4.1 to 8.8)
7.5
(4.1 to 8.8)
7.5
(4.2 to 8.9)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(950 to 2750)
(950 to 2820)
(950 to 2820)
(980 to 2850)
(980 to 2850)
(980 to 2920)
(980 to 2920)
(980 to 2950)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2230
2230
2230
2230
2250
2250
2250
2250
2250
Operating
current
(A)
3.71
(3.52 to 4.44 )
5.49
(3.52 to 6.88 )
7.47
(3.52 to 8.87 )
6.79
(3.48 to 9.05 )
8.03
(3.59 to 9.85 )
9.05
(3.64 to 10.65)
9.05
(3.64 to 10.65)
10.29
(3.75 to 11.40)
11.31
(3.80 to 12.20)
9.89
(4.59 to 12.07)
9.89
(4.59 to 12.20)
9.89
(4.59 to 12.51)
9.89
(4.59 to 12.51)
9.98
(4.73 to 12.64)
9.98
(4.73 to 12.64)
9.98
(4.73 to 12.95)
9.98
(4.73 to 12.95)
9.98
(4.73 to 13.09)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 18 –
Outdoor Unit : RAS-3M26GAV-E
y
p
g
p
<Cooling/240V>
Power
suppl
O
eratin
(V)
2401 unit10––2.7––
status
2 units1010–2.702.70–
3 units1010102.472.472.47
Indoor unitUnit capacity (kW)
ABCABC
13––3.7––
16––4.5––
1310–3.412.49–
1610–3.942.36–
1313–3.153.15–
1613–3.733.07–
1616–3.603.60–
1310103.012.202.20
1610103.362.022.02
1313102.712.711.98
1613103.102.551.86
1313132.502.502.50
1616102.882.881.73
1613132.842.332.33
1616132.662.662.19
Cooling
capacity
(kW)
2.7
(1.4 to 3.2)
3.7
(1.4 to 4.4)
4.5
(1.4 to 5.0)
5.4
(2.5 to 6.3)
5.9
(2.7 to 6.6)
6.3
(2.9 to 6.9)
6.3
(2.9 to 6.9)
6.8
(3.0 to 7.2)
7.2
(3.2 to 7.5)
7.4
(3.8 to 8.2)
7.4
(3.9 to 8.3)
7.4
(4.0 to 8.5)
7.4
(4.0 to 8.5)
7.5
(4.0 to 8.6)
7.5
(4.0 to 8.6)
7.5
(4.1 to 8.8)
7.5
(4.1 to 8.8)
7.5
(4.2 to 8.9)
Power
consum
(640 to 1520)
(640 to 2000)
(640 to 2040)
(660 to 2220)
(670 to 2400)
(670 to 2400)
(690 to 2570)
(700 to 2750)
(950 to 2720)
(950 to 2750)
(950 to 2820)
(950 to 2820)
(980 to 2850)
(980 to 2850)
(980 to 2920)
(980 to 2920)
(980 to 2950)
tion
(W)
750
(640 to 950)
1200
1650
1530
1810
2040
2040
2320
2550
2230
2230
2230
2230
2250
2250
2250
2250
2250
Operating
current
(A)
3.55
(338 to 4.26)
5.26
(3.38 to 6.60 )
7.16
(3.38 to 8.50 )
6.51
(3.33 to 8.67 )
7.70
(3.44 to 9.44 )
8.67
(3.49 to 10.20)
8.67
(3.49 to 10.20)
9.86
(3.59 to 10.93)
10.84
(3.65 to 11.69)
9.48
(4.40 to 11.56)
9.48
(4.40 to 11.69)
9.48
(4.40 to 11.99)
9.48
(4.40 to 11.99)
9.57
(4.54 to 12.12)
9.57
(4.54 to 12.12)
9.57
(4.54 to 12.41)
9.57
(4.54 to 12.41)
9.57
(4.54 to 12.54)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor
DB/WB=35/–°C.
– 19 –
Outdoor Unit : RAS-3M26GAV-E
y
p
g
p
<Heating/220V>
Power
suppl
O
eratin
(V)
2201 unit10––4.0––
status
2 units1010–3.603.60–
3 units1010102.872.872.87
Indoor unitUnit capacity (kW)
ABCABC
13––5.0––
16––5.5––
1310–4.223.38–
1610–4.573.33–
1313–3.953.95–
1613–4.353.95–
1616–4.304.30–
1310103.352.682.68
1610103.592.612.61
1313103.143.142.51
1613103.343.032.43
1313132.932.932.93
1616103.263.262.37
1613133.162.872.87
1616133.093.092.81
Heating
capacity
(kW)
4.0
(0.8 to 5.2)
5.0
(0.8 to 6.5)
5.5
(0.8 to 6.9)
7.2
(1.5 to 10.0)
7.6
(1.5 to 10.1)
7.9
(1.5 to 10.1)
7.9
(1.5 to 10.1)
8.3
(1.5 to 10.2)
8.6
(1.5 to 10.2)
8.6
(2.0 to 10.4)
8.7
(2.0 to 10.5)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
9.0
(2.0 to 10.8)
Power
consum
(300 to 1980)
(310 to 2750)
(310 to 3000)
(320 to 3200)
(320 to 3210)
(320 to 3230)
(320 to 3230)
(320 to 3240)
(320 to 3250)
(380 to 2750)
(380 to 2760)
(380 to 2780)
(380 to 2780)
(380 to 2780)
(380 to 2780)
(380 to 2790)
(380 to 2790)
(380 to 2800)
(W)
1500
2050
2400
2050
2240
2380
2380
2560
2700
2300
2360
2430
2430
2430
2430
2490
2490
2550
tion
Operating
current
(A)
6.96
(1.87 to 9.18 )
9.51
(1.93 to 12.76)
11.13
(1.93 to 13.91)
9.51
(1.94 to 14.84)
10.39
(1.94 to 14.89)
11.04
(1.94 to 14.98)
11.04
(1.94 to 14.98)
11.87
(1.94 to 15.03)
12.52
(1.94 to 15.07)
10.67
(2.16 to 12.76)
10.95
(2.16 to 12.80)
11.27
(2.16 to 12.89)
11.27
(2.16 to 12.89)
11.27
(2.16 to 12.89)
11.27
(2.16 to 12.89)
11.55
(2.16 to 12.94)
11.55
(2.16 to 12.94)
11.83
(2.16 to 12.99)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/
WB=7/6°C.
– 20 –
Outdoor Unit : RAS-3M26GAV-E
y
p
g
p
<Heating/230V>
Power
suppl
O
eratin
(V)
2301 unit10––4.0––
status
2 units1010–3.603.60–
3 units1010102.872.872.87
Indoor unitUnit capacity (kW)
ABCABC
13––5.0––
16––5.5––
1310–4.223.38–
1610–4.573.33–
1313–3.953.95–
1613–4.353.95–
1616–4.304.30–
1310103.352.682.68
1610103.592.612.61
1313103.143.142.51
1613103.343.032.43
1313132.932.932.93
1616103.263.262.37
1613133.162.872.87
1616133.093.092.81
Heating
capacity
(kW)
4.0
(0.8 to 5.2)
5.0
(0.8 to 6.5)
5.5
(0.8 to 6.9)
7.2
(1.5 to 10.0)
7.6
(1.5 to 10.1)
7.9
(1.5 to 10.1)
7.9
(1.5 to 10.1)
8.3
(1.5 to 10.2)
8.6
(1.5 to 10.2)
8.6
(2.0 to 10.4)
8.7
(2.0 to 10.5)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
9.0
(2.0 to 10.8)
Power
consum
(300 to 1980)
(310 to 2750)
(310 to 3000)
(320 to 3200)
(320 to 3210)
(320 to 3230)
(320 to 3230)
(320 to 3240)
(320 to 3250)
(380 to 2750)
(380 to 2760)
(380 to 2780)
(380 to 2780)
(380 to 2780)
(380 to 2780)
(380 to 2790)
(380 to 2790)
(380 to 2800)
(W)
1500
2050
2400
2050
2240
2380
2380
2560
2700
2300
2360
2430
2430
2430
2430
2490
2490
2550
tion
Operating
current
(A)
6.65
(1.79 to 8.78 )
9.09
(1.85 to 12.20)
10.65
(1.85 to 13.31)
9.09
(1.86 to 14.20)
9.94
(1.86 to 14.24)
10.56
(1.86 to 14.33)
10.56
(1.86 to 14.33)
11.36
(1.86 to 14.37)
11.98
(1.86 to 14.42)
10.20
(2.07 to 12.20)
10.47
(2.07 to 12.24)
10.78
(2.07 to 12.33)
10.78
(2.07 to 12.33)
10.78
(2.07 to 12.33)
10.78
(2.07 to 12.33)
11.05
(2.07 to 12.38)
11.05
(2.07 to 12.38)
11.31
(2.07 to 12.42)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/
WB=7/6°C.
– 21 –
Outdoor Unit : RAS-3M26GAV-E
y
p
g
<Heating/240V>
Power
suppl
O
eratin
(V)
2401 unit10––4.0––
status
2 units1010–3.603.60–
3 units1010102.872.872.87
Indoor unitUnit capacity (kW)
ABCABC
13––5.0––
16––5.5––
1310–4.223.38–
1610–4.573.33–
1313–3.953.95–
1613–4.353.95–
1616–4.304.30–
1310103.352.682.68
1610103.592.612.61
1313103.143.142.51
1613103.343.032.43
1313132.932.932.93
1616103.263.262.37
1613133.162.872.87
1616133.093.092.81
Heating
capacity
(kW)
4.0
(0.8 to 5.2)
5.0
(0.8 to 6.5)
5.5
(0.8 to 6.9)
7.2
(1.5 to 10.0)
7.6
(1.5 to 10.1)
7.9
(1.5 to 10.1)
7.9
(1.5 to 10.1)
8.3
(1.5 to 10.2)
8.6
(1.5 to 10.2)
8.6
(2.0 to 10.4)
8.7
(2.0 to 10.5)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.8
(2.0 to 10.6)
8.9
(2.0 to 10.7)
8.9
(2.0 to 10.7)
9.0
(2.0 to 10.8)
Power
consumption
(W)
1500
(300 to 1980)
2050
(310 to 2750)
2400
(310 to 3000)
2050
(320 to 3200)
2240
(320 to 3210)
2380
(320 to 3230)
2380
(320 to 3230)
2560
(320 to 3240)
2700
(320 to 3250)
2300
(380 to 2750)
2360
(380 to 2760)
2430
(380 to 2780)
2430
(380 to 2780)
2430
(380 to 2780)
2430
(380 to 2780)
2490
(380 to 2790)
2490
(380 to 2790)
2550
(380 to 2800)
Operating
current
(A)
6.38
(1.71 to 8.42 )
8.72
(1.77 to 11.69)
10.20
(1.77 to 12.76)
8.72
(1.78 to 13.61)
9.52
(1.78 to 13.65)
10.12
(1.78 to 13.73)
10.12
(1.78 to 13.73)
10.88
(1.78 to 13.78)
11.48
(1.78 to 13.82)
9.78
(1.98 to 11.69)
10.03
(1.98 to 11.73)
10.33
(1.98 to 11.82)
10.33
(1.98 to 11.82)
10.33
(1.98 to 11.82)
10.33
(1.98 to 11.82)
10.59
(1.98 to 11.86)
10.59
(1.98 to 11.86)
10.84
(1.98 to 11.90)
Outdoor
noise
(dB)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/
WB=7/6°C.
– 22 –
2-2-1. Operation Characteristic Curve
<Cooling><Heating>
16
• Conditions
14
Indoor: DB27˚C/WB19˚C
Outdoor: DB35˚C
Air flow: High
12
Pipe length: 5m x 4
4 units operating
10
8
6
Current (A)
4
2
0
0
1020304050607080
Inverter output frequency (rps)
220V
240V
230V
14
• Conditions
Indoor: DB20˚C
12
Outdoor: DB7˚C / WB6˚C
Air flow: High
10
Pipe length: 5m x 4
4 units operating
8
6
Current (A)
4
2
0
101002030405060708090
0
Inverter output frequency (rps)
2-2-2. Capacity Variation Ratio According to Outdoor Temperature
<Cooling><Heating>
110
100
90
Current limited start
110
• Conditions
Indoor: DB20˚C
100
Air flow: High
Pipe length: 5m x 4
4 units operating
90
220V
240V
230V
80
70
• Conditions
Indoor: DB27˚C/WB19˚C
Indoor air flow : High
60
Cooling capacity ratio (%)
Pipe length: 5m x 4
4 units operating
50
33 34 35 36 37 38 39 40 41 4243 44
32
Outdoor temp. (˚C)
80
70
60
Heating capacity ratio (%)
50
10
-9-8-7-6-5-4-3-2-1012345678910
-
2-2-3. Capacity Variation Ratio According to Pipe Length
<Cooling><Heating>
110
105
100
95
• Conditions
90
Indoor: DB27˚C/WB19˚C
Outdoor: DB35˚C
85
Indoor air flow: High
Coolimg capacity ratio (%)
4 units operating
80
0
Standard pipe length 20m
1020304050607080
Total pipe length (m)
110
105
100
95
• Conditions
90
Indoor: DB20˚C
Outdoor: DB7˚C/WB6˚C
Heating capacity ratio (%)
85
Indoor air flow: High
4 units operating
80
0
Outdoor temp. (˚C)
Standard pipe length 20m
1020304050607080
Total pipe length (m)
– 23 –
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water , dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
1. Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure
in the refrigeration cycle becomes abnormally
high, and it may cause personal injury, etc. by a
rupture.
2. Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
3. If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
4. When installing or removing an air conditioner, do
not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so
that a rupture or personal injury may be caused.
5. After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentr ation
does not exceed the marginal le vel.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal le vel, an
oxygen starvation accident ma y result.
7. Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair may result in water leakage,
electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant m ust be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants .
1. Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored
portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary
to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 3-2-1. Never use copper
pipes thinner than 0.8 mm even when it is
available on the market.
– 24 –
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410AR22
0.800.80
0.800.80
0.800.80
1.001.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds
20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose
diameter is larger than 20 mm.
Thicknesses of sock et joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not
enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used,
and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils
whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any
other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur.
Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 25 –
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimen-
sion A” by using a gauge for size adjustment.
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Fig. 3-2-1 Flare pr ocessing dimensions
Flare tool for R410A
clutch type
ØD
A
A (mm)
Conventional flare tool
Clutch type Wing nut type
1/4
3/8
1/2
5/8
Nominal
diameter
1/4
3/8
1/2
5/8
6.35
9.52
12.70
15.88
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Table 3-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
1.0 to 1.51.5 to 2.0
1.0 to 1.51.5 to 2.0
1.0 to 1.52.0 to 2.5
1.0 to 1.52.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.01.0 to 1.5
0.5 to 1.01.0 to 1.5
0.5 to 1.01.5 to 2.0
0.5 to 1.01.5 to 2.0
Nominal
diameter
1/4
3/8
1/2
5/8
Table 3-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.19.26.513
13.213.59.720
16.616.012.923
19.719.016.025
– 26 –
Flare nut width
(mm)
17
22
26
29
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4
3/8
1/2
5/8
3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
45˚ to 46
˚
BA
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Dimension (mm)
ABCD
9.09.26.513
13.013.59.720
16.216.012.920
19.719.016.023
23.324.019.234
D
C
43˚ to 45
˚
Flare nut width
(mm)
17
22
24
27
36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis .
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removab le. When choosing the tighten-
ing torque, comply with values designated by man ufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
N•m (kgf•cm)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4
3/8
1/2
5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
– 27 –
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is
changed to prev ent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing
dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are
lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the follo wing three types .
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conv entional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
air-water heat pump installation
No.
1
2
3
4
5
6
7
8
9
10
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
(Note 2) Charging cylinder for R410A is being currently developed.
Whether new equipment
can be used with
conventional refrigerant
¡
*(Note 1)
×
×
¡
¡
×
¡
×
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also f or R22 are necessary
as the general tools.
1. Vacuum pump
Use vacuum pump by attaching
vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench
(Opposite side 4mm)
11 . Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
– 28 –
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps .
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
Connect the charge hose to the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
(For refrigerant charging, see the figure below.)
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(Water heat
exchanger unit)
Opened
(Outdoor unit)
Refrigerant cylinder
(with siphon)
Check valve
Opened
Open/close
valve for charging
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
Opened
Closed
Service port
– 29 –
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an allo y mainly composed
of silver and copper. It is used to join iron, copper
or copper alloy, and is relatively expensive though
it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
Electronic
balance
Siphon
Fig. 3-4-2
1. Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage. Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.
2. When performing brazing again at time of
servicing, use the same type of brazing filler.
3-5-2. Flux
3. Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
1. Reason why flux is necessary
• By removing the o xide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler .
• In the brazing process, it prevents the metal
surface from being oxidized.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 30 –