Toshiba RAS-24SA-ES, RAS-18S2AH-ES, RAS-24SKP-ES, RAS-18SKP-ES, RAS-24S2AH-ES SERVICE MANUAL

...
SERVICE MANUAL
AIR CONDITIONER
RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES
FILE NO. SVM-09036
SPLIT WALL TYPE
RAS-18SKP-ES / RAS-18SA-ES
RAS-24SKP-ES / RAS-24SA-ES
February, 2009
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit
3. WIRING DIAGRAM
3-1 RAS-18SKP-ES / RAS-18SA-ES,
RAS-24SKP-ES / RAS-24SA-ES
3-2 RAS-18SKHP-ES / RAS-18S2AH-ES
RAS-24SKHP-ES / RAS-24S2AH-ES
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-18SKP-ES, RAS-24SKP-ES) 4-2
Outdoor Unit (RAS-18SA-ES) Outdoor Unit (RAS-24SA-ES)
4-3 4-4
Indoor Unit (RAS-18SKHP-ES, RASP-24SKHP-ES) Outdoor Unit (RAS-18S2AH-ES)
4-5
Outdoor Unit (RAS-24S2AH-ES)
4-6
5. REFRIGERATION CYCLE DIAGRAM
5-1
RAS-18SKP-ES / RAS-18SA-ES RAS-24SKP-ES / RAS-24SA-ES
5-2 5-3
RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES
5-4
6. CONTROL BLOCK DIAGRAM
6-1 RAS-18SKP-ES / RAS-18SA-ES,
RAS-24SKP-ES / RAS-24SA-ES
6-2 RAS-18SKHP-ES / RAS-18S2AH-ES
RAS-24SKHP-ES / RAS-24S2AH-ES
1
7. OPERATION DESCRIPTION
7-1 Remote control 7-2 Outline of Air Conditioner Control
7-3 Description of Operation Circuit 7-4 Description of Safety and Reliability Prevention Function 7-5 One-Touch Operation 7-6 Hi POWER Operation 7-7 QUIET Operation 7-8 ECO Operation 7-9 COMFORT SLEEP Operation 7-10 FILTER Check lamp 7-11 Auto Restart Function 7-12 Self-Cleaning Operation
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 Test Operation
FILE NO. SVM-09036
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 How To Diagnose Faulty Parts
Troubleshooting for Indoor unit
9-6 9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire) 9-8 Troubleshooting for P.C. Board 9-9 Troubleshooting for Remote Control
HOW TO REPLACE THE MAIN PARTS
10.
10-1 Indoor Unit
Outdoor Unit
10-2
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy) 11-2 Indoor Unit 11-3
Outdoor Unit (RAS-18SA-ES, RAS-24SA-ES)
11-4
Outdoor Unit (RAS-18S2AH-ES, RAS-24S2AH-ES)
2

1. SPECIFICATIONS

MODEL RAS-18SKP-ES RAS-24SKP-ES
RAS-18SA-ES RAS-24SA-ES
ITEM Cooling Cooling
Capacity
kW
Phase
Power source
Hz Power consumption W Power factor % Running A Current Indoor/Outdoor Starting current A Moisture removal lit/h Noise Indoor (H/M+/M/L+/L) dB
Outdoor (220-240V) dB
Refrigerant Name of refrigerant
Rated amount kg Refrigerant control Interconnection Gas side size mm pipe Connection type
Liquid side size mm
Connection type
Maximum length m
(One way)
Maximum height m
difference
INDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Evaporator type Indoor fan type Airflow volume High fan
Medium fan
Low fan
3
m
3
m
3
m Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume
3
m Fan motor output W Compressor Model
Output W Safety device Louver type Usable outdoor temperature range °C
Note *1 Chargeless pipe
*2 Maximum pipe
220V
5.30
V
1640
98 97
0.3/7.30 0.3/6.90 0.50/14.70 0.50/12.90
31
2.0
44/42/39/37/35 45/43/41/39/37
56 57
1.65
20*
810
RAS-18SKP-ES RAS-24SKP-ES
/h /h
1000
880
/h
RAS-18SA-ES RAS-24SA-ES
/h
2400 2550 2450
PA200X2CS-4KU1
1500
240V 220V
5.35 6.80
1
220 - 240
50
1680 2410
98
56 57
R410A
Capillary tube
12.7
Flare connection
6.35
Flare connection
1
2
15*
320
1050
228
13
Finned tube
Cross flow fan
30
Honeycomb woven filter with PP frame
715 780 290
Finned tube
Propeller fan
42
Fuse , IOL
Automatic louver
15 ~ 43
44
2.7
1.70
2
25*
1100
950 850750
5045
PA270X3CS-4MU2
2000
240V
6.85
2450
93
2600
3
MODEL RAS-18SKHP-ES RAS-24SKHP-ES
RAS-18S2AH-ES RAS-24S2AH-ES
ITEM Cooling Heating Cooling Heating
Capacity
kW
Phase
Power source
Hz Power consumption W Power factor % Running Indoor A Current Outdoor A Starting current A Moisture removal lit/h Noise Indoor (H/M+/M/L+/L) dB
Outdoor (220-240V) dB
Refrigerant Name of refrigerant
Rated amount kg Refrigerant control Interconnection Gas side size mm pipe Connection type
Liquid side size mm
Connection type
Maximum length m
(One way)
Maximum height m
difference
INDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Evaporator type Indoor fan type Airflow volume High fan
Medium fan
Low fan
3
m
3
m
3
m Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume
3
m Fan motor output W Compressor Model
Output W Safety device Louver type Usable outdoor temperature range °C
Note *1 Chargeless pipe
*2 Maximum pipe
240V220V 220V 240V 220V 240V
5.10 5.12
V
98 96 98
5.45 5.56 6.30 6.35
1
220 - 240
50
1470
1530 2190 22501540 1580 2050 2140
97 98 93 98 93
0.30 0.30
6.85 6.55 6.55 6.30 9.90 9.80 9.20 9.30 31
2.0
44/42/39/37/35 45/43/41/39/37
56-57 57-58
56-57 57-58
R410A
1.53 Capillary tube
12.7
Flare connection
6.35
Flare connection
1
15*
20*
2
810
RAS-18SKHP-ES RAS-24SKHP-ES
320
1050
228
13
Finned tube
Cross flow fan
/h /h /h
1000 1000
880 900 750 770
1100 1100
950 950 850 850
30
Honeycomb woven filter with PP frame
RAS-18S2AH-ES RAS-24S2AH-ES
715 780 780 290 290
Finned tube
Propeller fan
2400 2550 2400 2550 2400 2550
/h
42
PA200X2CS-4KU1
PA270X3CS-4MU2
1500
Td sensor , Fuse , IOL
Automatic louver
15 ~ 43 -10 ~ 24 15 ~ 43 -10 ~ 24
220V 240V
6.80 6.90
44
2.5
1.62
2
25*
715
5347
2400 2550
2000
4
Note : 1
Capacity is based on the following temperature conditions.
FILE NO. SVM-09036
Condition
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
Charge refrigerant according to the table below.
Refrigerant
*1 No need to charge
extra refrigerant
*2 Need to charge
extra refrigerant
RAS-18SKP-ES / RAS-18SA-ES
RAS-18SKHP-ES / RAS-18S2AH-ES
Over 15 m up to 20 m (20 g/m) Over 15 m up to 25 m (20 g/m)
(DB) 27°C20°C
(WB) 19°C15°C
(DB) 35°C7°C
(WB) 24°C6°C
15 m or less 15 m or less
JIS C9612
Cooling Heating
RAS-24SKP-ES / RAS-24SA-ES
RAS-24SKHP-ES / RAS-24S2AH-ES
5
2-1. Indoor Unit

2. CONSTRUCTION VIEWS

Grille Inlet
Front Panel
73.57
50
Knock out system
Heat exchanger
320
50
78 72
Air inlet
278 200 222 150
132
1050
Air outlet
200
Air filter
72 78
Knock out system
50
228
73.5
50
7
157
Drain hose (0.5m)
320
40
525
Hanger
Connecting pipe (0.39m)
12.70)
(Flare
85 23
Hanger
6
5
Hanger Hanger
262.5
786
235
215
Center line
Installation plate outline
Connecting pipe (0.49m)
235
215
262.5
Hanger
6.35)(Flare
For stud bold ( For stud bold (
6
5
10947 215.5 153.5
56
Wireless remote controller
63
Remote controller holder
6) 8~
10)
Outline of indoor unit
40
19
125
26
6
2-2. Outdoor Unit
600
50 36
R
15
FILE NO. SVM-09036
A
28
125108
6 hole
320
306
Ø
R
5.5
A Detail Drawing (Back leg)
HANDLE
290
320
Ø
436
Ø
715
86
25 Drain outlet
FAN-GUARD
275
90 600 90 69
2Ø11x14 Hole (For
Ø8-Ø
10 anchor bolt)
B
306
320
Hole
6
Ø
11x14 Hole
Ø
36 50
B Detail Drawing (Front leg)
320 342
R
15
HANDLE
COVER-PV
Z
100 or more
320
100 or more
Z View
600
Air inlet
Air out
let
00 or more
6
Installation dimension
600 or more
4x
54
129
84
11 Long holes(For
Ø
Service port
10 anchor bolt)
Ø8-Ø
Electrical part cover
Liquid side (Flare Ø6.35)
Gas-side (Flare Ø15.88)
7
FILE NO. SVM-09036

3. WIRING DIAGRAM

3-1. RAS-18SKP-ES / RAS-18SA-ES, RAS-24SKP-ES / RAS-24SA-ES
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220 240 V ~ 50 Hz
L
N
BLK
RED
BLK
RED
RED
MAGNETIC CONTACTOR
1
1
BLK BLK
SPARK KILLER
A2 A1
52C
R U
S V
WT
2
2
RED
CAPACITOR
3
3
GRY
CHASSIS
RED
WHI PNK
COMPRESSOR
CAPACITOR
S
R
OUTDOOR
UNIT
BLK
C
WHI RED
FAN MOTOR
BLK
8
FILE NO. SVM-09036
3-2. RAS-18SKHP-ES / RAS-18S2AH-ES, RAS-24SKHP-ES / RAS-24S2AH-ES
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220- 240 V ~ 50 Hz
L
BLK
RED
BLK
RED
WHI PNK
COMPRESSOR
2
1
3
GRN&YEL
2
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
1
S
3
i
CHASSIS
T
A1
52C
BLK
A2
W
RED
WHI RED
FAN MOTOR
U
V
CAPACITOR CAPACITOR
S
C
R
TRANSFORMER
OUTDOOR UNIT
BLK BLK
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU COIL FOR 4 WAY VALVE
MAIN P.C. BOARD (MCC-890)
1
1 2
CN06
3
3
1
1
CN05
3
3
SG01
1
1
F01
3
3
250VAC T6. 3A
5
5
CN01
7
7
9
9
1
CN11
313
11
33
CR11
CN02
CR12
CR13
TNR R74
CN03
1 1
RY07
RY05
3
TNR R73
RY06
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1 2 3
3
BLK
HEAT EXCHANGER SENSOR (TE)
9

4. SPECIFICATION OF ELECTRICAL PARTS

4-1. Indoor Unit (RAS-18SKP-ES, RAS-24SKP-ES)
FILE NO. SVM-09036
No.
1 Fan motor (for indoor) ICF-340-30-2B DC 340V, 30W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Switching Transformer (T01) SWT-77 DC7V, 12 V 4 Microcontroller TMP87CM40ANG-6P68 5 Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C03) EKMH451VSN121MQ35S 120 µF, 450 V 9 Fuse (F01) BET 6.3A 6.3 A, 250 V
10 Varistor (R09, R10) SR561K14DL 560 V
11 Resistor (R01) RF-5TK1R8
2 TLou
13
v
Relay : (RY03)
P5War1ts name
er motor MP24Z3T Output (Rated) 2 W, 6 poles, 1-2 phas e
ype
——— 10 k at 25°C
1.8 ,
DC 12 V
G5NB-1A-CA
Coil DC 12V, 16.7mA, Contact AC 250V, 1A
Specifications
,
4-2. Outdoor Unit (RAS-18SA-ES)
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA200X2CS-4KU1 Winding resistance (Ω) Red-Black White-Black
(at 20°C ) 1.85 2.62
Output (Rated) 42W, 4poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
DS451305NPQB AC 450V, 3
B32332I5606J063 AC 450V, 50µF
CLK-26J
220 240V, 50Hz
.0µF
10
FILE NO. SVM-09036
4-3. Outdoor Unit (RAS-24SA-ES)
No. Parts name Type Specifications
Output (Rated) 2000W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA270X3CS-4MU2 Winding resistance (Ω  ) Red-Black White-Black
(at 20°C) 1.37 2.55 Output (Rated) 42W, 4poles, 1 phase, 220 − 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A Winding resistance (Ω) Red-Black White-Black
(at 20° C) 128 126
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
CLK-35J
DS451355NPQB AC 450V, 3.5µ F
32332I5606J063 A
B
220 240V, 50Hz
C 450V, 60µ F
4-4. Indoor Unit (RAS-18SKHP-ES, RAS-24SKHP-ES)
No. Parts name Type Specifications
1 Fan motor (for indoor) ICF-340-30-2B DC 340V, 30W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Switching Transformer (T01) SWT-77 DC 7V, 12V 4 Microcontroller TMP87CM40ANG-6P68 5 Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C03) EKMH451VSN121MQ35S 120 µF, 450 V 9 Fuse (F01) BET 6.3A 6.3 A, 250 V
10 Varistor (R09, R10) SR561K14DL 560 V
11 Resistor (R01) RF-5TK1R8 1.8, 5W 12 Louver motor MP24Z3T Output (Rated) 2 W, 6 poles, 1-2 phase,
——— 10 k at 25°C
DC 12 V
11
FILE NO. SVM-08037
4-5. Outdoor Unit (RAS-18S2AH-ES)
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA200X2CS-4KU1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.85 2.62 Output (Rated) 42W, 4poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
5
(for 4-way valve)
6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor CLK-26J 220 − 240V, 50Hz 8 Transformer TT-05 220 − 240V
9 Microcomputer TMP47C840N 10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
DS451305NPQB AC 450V, 3.0 µF
B32332I5606J063 AC 450V, 50µF
VHV (STF) AC 220 − 240V
4-6. Outdoor Unit (RAS-24S2AH-ES)
No. Parts name Type Specifications
Output (Rated) 2000W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA270X3CS-4MU2 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.37 2.55 Output (Rated) 42W, 4poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
5
(for 4-way valve) 6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor CLK-35J 220 ~ 240V, 50Hz 8 Transformer TT-05 220 ~ 240V 9 Microcontroller TMP47C840N
10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
DS451305NPQB AC 450V, 3.0µF
B32332I5606J063 AC 450V, 60µF
VHV (STF) AC 220 ~ 240V
12

5. REFRIGERATION CYCLE DIAGRAM

5-1. RAS-18SKP-ES / RAS-18SA-ES
FILE NO. SVM-09036
T
Heat exchanger
(Connecting pipe)
0.39 m 12.7
Cross flow fan
O.D.:12.7 mm O.D.:6.35 mm
Compressor
P
Packed valve
(12.7)
PA200X2CS-4KU1
Heat exchanger
Propeller fan Outdoor unit
Packed valve
(6.35)
Capillary tube
2.0x1100 s
Refrigerant
R410A 1.65 kg
Mark ( ) means check points of Gas Leak
0.49 m (Connecting pipe) 6.35
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.94 10.6 High 27/19 35/24
Cooling High temperature 1.09 15.0 High 32/23 43/26
Low temperature 0.75 4.3 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
13
5-2. RAS-24SKP-ES / RAS-24SA-ES
FILE NO. SVM-09036
Indoor unit
Cooling
0.39 m (Connecting pipe)
12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Compressor
P
Packed valve
(∅12.7 )
Gas container connection (Reinstall etc.)
PA270X3CS-4MU2
Heat exchanger
Cross flow fan
T
0.49 m (Connecting pipe)
6 .35
Packed valve
(∅6.35)
Capillary tube
1000 s
2.0x
Heat exchanger
Refrigerant R410A 1.70 kg
Cooling
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.84 13.0 High 27/19 35/24
Cooling High temperature 1.01 17.0 High 32/23 43/26
Low temperature 0.65 5.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
14
5-3. RAS-18SKHP-ES / RAS-18S2AH-ES
FILE NO. SVM-09036
Indoor unit
Cooling
0.39 m (Connecting pipe)
Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ12.7)
Heating
4-way valve
Cooling
Discharge Muffler
25x160L
Compressor
Accumulator
PA200X2CS-4KU1
Heat exchanger
Cross flow fan
T1
Capillary tube Æ1.7 x 600
Packed valve
(Æ6.35)
Capillary tube
Æ2.0 x 1000
l
0.49 m
(Connecting pipe)
Æ6.35
l
Heat exchanger
Refrigerant R410A : 1.53 kg.
Cooling
Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.53 44.0 High 20/15 7/6
Heating Overload*1 3.30 ~ 3.65 51.0 ~ 55.0 Low 27/- 24/18
Low temperature 1.75 32.0 High 20/
-
-10/-10
Standard 0.54 11.0 High 27/19 35/24
Cooling Overload 1.12 15.0 High 32/23 43/26
Low temperature 0.72 4.2 Low 21/15 21/15
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1 During heating overload operation, a value for the high temperature limit control operation is included.
- 15 -
5-4. RAS-24SKHP-ES / RAS-24S2AH-ES
FILE NO. SVM-09036
Indoor unit
Cooling
0.39 m (Connecting pipe)
Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ12.7)
Heating
4-way valve
Cooling
Discharge Muffler
25x160L
Compressor
Accumulator
PA270X3CS-4MU2
Heat exchanger
Cross flow fan
T1
Capillary tube Æ2.0 x 700
Packed valve
(Æ6.35)
Capillary tube
Æ2.0 x 900
l
0.49 m
(Connecting pipe)
Æ6.35
l
Heat exchanger
Refrigerant R410A 1.62 kg.
Cooling
Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.86 45.6 High 20/15 7/6
Heating Overload*1 3.54 ~ 3.91 53.6 ~ 57.6 Low 27/- 24/18
Low temperature 2.19 33.9 High 20/
-
-10/-10
Standard 0.84 10.0 High 27/19 35/24
Cooling Overload 1.12 16.1 High 32/23 43/26
Low temperature 0.74 2.3 Low 21/15 21/15
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1 During heating overload operation, a value for the high temperature limit control operation is included.
- 16 -
FILE NO. SVM-09036

6. CONTROL BLOCK DIAGRAM

6.1 RAS-18SKP-ES / RAS-18S2A-ES, RAS-24SKP-ES / RAS-24S2A-ES
Indoor Unit Control Panel
M.C.U.
Heat Exchanger Sensor
Functions
Louver Control
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
Remote
Control
From Outdoor Unit
240 V AC 50 Hz
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Outdoor unit
ON/OFF Signal
Relay Driver
Relay RY03
Outdoor Unit
Louver ON/OFF Signal
Louver Driver
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
17
FILE NO. SVM-09036
6.2 RAS-18SKHP-ES / RAS-18S2AH-ES, RAS-24SKHP-ES / RAS-24S2AH-ES
Indoor Unit Control Panel
M.C.U.
Heat Exchanger Sensor
Functions
Louver Control
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
Remote
Control
From Outdoor Unit
240 V AC 50 Hz
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
18

7. OPERATION DESCRIPTION

7-1. Remote control
7-1-1. Function of Push Putton
1
11
Infrared signal emitter
11
2
Start/Stop button
3
Mode select button (MODE)
4
Temperature button (TEMP)
5
Fan speed button (FAN)
6
Swing louver button (SWING)
7
Set louver button (FIX)
8
On timer button (ON) Off timer button (OFF)
9
18
10
Sleep timer button (SLEEP)
19
Timer setup button (SET)
11 12
20
Timer clear button (CLR)
Memory and Preset button (PRESET)
13 14
One Touch button (ONE-TOUCH)
15
High power button (Hi-POWER)
16
Economy button (ECO)
17
Quiet button (QUIET)
18
Comfort sleep button (COMFORT SLEEP)
19
Filter reset button (FILTER)
20
Clock Reset button (CLOCK)
21
Check button (CHK)
FILE NO. SVM-0936
1
13
14
2
17
6
7
8 10 21
19
PRESET
ONE-TOUCH
QUIET
SWING
TIMER
SLEEP
CHK
FAN
TEMP
MODE
COMFORT
SLEEP
FIX Hi-POWER ECO
ON
OFF
FILTER
CLOCK
5
4
3
18
15 16
CLR
SET
12
9
11
20
19
FILE NO. SVM-09036
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the button.
1. Transmission mark
This transmission mark remote controller transmits signals to the indoor unit.
indicates when the
2. Mode indicator
Indicates the current operation mode. (A : Auto, : Cool,
: Dry, : Heat, : Fan only)
3. Temperature indicator
Indicates the temperature setting. (17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed. AUTO or five fan speed levels
LOW , LOW+ , MED , MED+ ,
( HIGH ) can be shown. Indicate Auto will be appear with Dry operation
( : Dry) only.
9
1
12
2
13
10
10
5. TIMER and clock time indicator
The time setting for timer operation or the clock time is indicated.
The current time is always indicated except during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts. Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is pressed during operation.
The button for more than 3 seconds while the mark is
blinks. Press another button to turn off the mark.
mark is shown when holding down the
8. ECO indicator
Indicates when the ECO is in activated. Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is set, “B” appears in the remote controller display. (When the remote controller setting is “A”, there is no indication at this position.)
10. Comfort sleep
Indicates when comfort sleep is activaled. Press comfort sleep button to selectter
11
6
3
8
7
4
5
11. Quiet
Indicates when quiet is activated. Press quiet button to start and press it again to stop operation.
12. One-Touch
Indicates when one touch comfort is activated. Press one-touch button to start the operation.
13. Swing
Indicates when louver is swing. Press swing button to start the swing operation and press it again to stop the swing operation.
20
7-2. Outline of Air Conditioner Control
y
A
A
y
P
P
A
A
This is a fixed capacity type air conditioner, which uses a DC motor for an indoor fan. The DC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit. The outdoor unit receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the
outdoor unit
Receiving of information of the operation status
and judging of the information or indication of error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation commands from the indoor controller and executes them.
Compressor operation
control
Operation control of
outdoor fan motor
Operations according to the commands
from the indoor unit
FILE NO. SVM-09036
Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown command
Defrost control in heating operation
(Temperature measurement by the Indoor heat exchanger, control the four-way valve and
outdoor fan motor control)
7-2-1.
(1)
(2) Swing
7-2-2. Indoor Fan Control
Table (7-2-1) Cooling
Louver contr
V
er
tical air flow louver
ol
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging.
The operation controls the fan speed at indoor unit side. The indoor fan (cross flow fan) is operated by
the phase control induction motor. The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respectively. (Table 7-2-3)
1) When setting the fan speed to L, L+,M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Table 7-2-1 and
Table 7-2-2
Table (7-2-2) Heating
Indication
L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Indication L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level show in Table 7-2-3 according to the setup temperature, room temperature,
Table 7-2-3 Indoor fan and air flow rate
OPERATION
MODE
RAS-18SKP-ES
Model
RAS-24SKP-ES
OPERATION
MODE
RAS-18SKHP-ES
Model
RAS-24SKHP-ES
Cooling Fan only Dr rpm
ir flow volume (m3/h)
rpm
ir flow volume (m3/h)
Cooling Fan only Dr Heat rpm
ir flow volume (m3/h)
rpm
ir flow volume (m3/h)
UH
1100 1000 1200 1100
UH H M+ M L+ L L- UL SL
UH H M+ M L+ L L- UL SL
1100 1000 1200 1100
and heat exchanger temperature.
FAN TA
H M+ M L+ L L- UL SL H M+ M L+ L L-
M+ M L+ L L- UL SL
1050 980 900 850 750 650 550
950 880 800 800 650 550 450 1125 1050 1000 950 850 700 600 1025 950 900 850 750 600 500
FAN TA
H M+ M L+ L L-
M+ M L+ L L- UL SL
1000 1000 940 870 850 850 750 640 550
900 900 840 770 750 750 650 540 450 1050 1050 1050 950 950 950 850 700 600
950 950 950 850 850 850 750 600 500
- 21 -
FILE NO. SVM-09036
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, (Heat pump model
only) outdoor fan and operation display lamp are controlled as shown in Fig. 7-3-2.
° C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
OPERATION
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Fig. 7-3-2
display lamp
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) (Preset temp.)
Preset temp.
0
(Preset temp.: 24 °C)
NOTE 1 : *1 : Fan speed = (M + L) x 3/4 + L
*2 : Fan speed = (M + L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
2 : The Hi Power, ECO and COMFORT SLEEP
operation can not be set
(Linear approximation from M+ and L)
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1
*2
*3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
°C
(Room temp.) (Preset temp.)
Preset temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*2
*3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
(Linear approximation from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
- 22 -
FILE NO. SVM-09036
7-3-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, (Heat pump model
only) outdoor fan and operation display lamp are controlled as shown in Fig. 7-3-4.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
OPERATION
display lamp
(Room temp.) (Preset temp.)
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-4
7-3-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-3-6.
° C
Preset temp.
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
Fig. 7-3-6
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L. *S.L. S.L.L. L. S.L. L.
*Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO, COMFORT SLEEP, QUIET and
Hi POWER operations can not be set.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-7. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
Preset temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L
*1 *2
+
M
H
*1 : Fan speed = (M + L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 3/4 + L
(Calculated with Linear approximation from M+ and L+)
Fig. 7-3-7
- 23 -
FILE NO. SVM-09036
y.
c
e
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-3-8
Fan speed AUTO Fan speed MANUAL
46Tc34 45 33
33 21 32 20
*A+0 *A+0
*A-8 *A-8
Fan speed MANUAL or AUTO in starting Fan speed AUTO in stability
* No limitation while fan speed MANUAL mode is in stabilit * A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
Normal AUTO
Line-approximate H and SL with Tc.
SL (W2)
Stop
L-H (Up to setting speed)
Line-approximate H and SL with Tc.
SL (W2)
Stop
[In starting and in stability]
In starting
FAN • Until 12 minutes
AUTO
FAN Room temp. < Set
Manual
passed after operation start
When 12 to 25 minutes
passed after operation start and room temp. is 3°C or lower than set temp.
temp.–4°C
In stability
When 12 to 25 minutes
passed after opeartion start and room temp. is than (set ) between preset
When 25 minutes or
more passed after operation start
Room temp. Set
temp. –3.5°C
3°C
7-3-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-3-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-3-9.
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) (Preset temp.)
Heat pump model Cooling model
Fig. 7-3-9
Fig. 7-3-8 Cold draft preventing control
(4) In order to prevent cold draft when compressor
during heating operation.Then louver will move to upper position and fan speed will reduce or OFF.
- 24 -
7-4. Drescription of Safety and Reliability Prevention Function
FILE NO. SVM-09036
7-4-1. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Heat exchanger temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 7-4-1
7-4-2 High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-2.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger temp.
(°C) 62
55 54
7-4-3. Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the refrigerant evaporation temperature detected by the outdoor heat exchanger sensor is under the specified temperature, the outdoor unit starts the defrosting operation. At this time, the 4-way valve relay and the outdoor fan motor are turned off. The indoor fan motor is also turned off by the cold draft preventing control of the indoor microcomputer. Then, [PRE. DEF.] lamp on the indoor unit comes on. The defrosting operation stops and the 4-way valve relay, outdoor fan motor and the indoor fan motor are turned on automatically when the refrigerant evaporation increases to the specified temperature, or when the defrosting time is over 12 minutes.
7-4-3-1. Defrost starting condition
A-Zone : If -10°C > Teo
start when. Teo - Te
~ 30 min after operation.
B-Zone : If Te
-18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC
Teo ≥ -10°C defrost will start when
Teo - Te -3°C at least 20 sec or ~ 60 min after operation.
7-4-3-2. Defrost finish condition.
1) If Te 3°C at least 60 sec -->4 way value on.
2) If Te 8°C --> 4 way value on.
Timing
- 18°C, defrost will
2.5°C at teat 20 sec or
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Fig. 7-4-2
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100 Heating time rate : (Tt - Td) x Tt
Fig. 7-4-3
- 25 -