7-1 Remote control
7-2 Outline of Air Conditioner Control
7-3 Description of Operation Circuit
7-4Description of Safety and Reliability Prevention Function
7-5One-Touch Operation
7-6Hi POWER Operation
7-7QUIET Operation
7-8ECO Operation
7-9COMFORT SLEEP Operation
7-10 FILTER Check lamp
7-11 Auto Restart Function
7-12 Self-Cleaning Operation
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3 Installation
8-4 Indoor Unit
8-5Outdoor Unit
8-6 Test Operation
FILE NO. SVM-09036
9. TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3 Primary Judgement
9-4 Self-Diagnosis by Remote Control (Check Code)
9-5How To Diagnose Faulty Parts
Troubleshooting for Indoor unit
9-6
9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-8 Troubleshooting for P.C. Board
9-9 Troubleshooting for Remote Control
HOW TO REPLACE THE MAIN PARTS
10.
10-1 Indoor Unit
Outdoor Unit
10-2
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy)
11-2 Indoor Unit
11-3
Outdoor Unit (RAS-18SA-ES, RAS-24SA-ES)
11-4
Outdoor Unit (RAS-18S2AH-ES, RAS-24S2AH-ES)
− 2 −
FILE NO. SVM-09036
1. SPECIFICATIONS
MODEL RAS-18SKP-ESRAS-24SKP-ES
RAS-18SA-ESRAS-24SA-ES
ITEMCoolingCooling
Capacity
kW
Phase
Power source
Hz
Power consumption W
Power factor%
RunningA
CurrentIndoor/Outdoor
Starting currentA
Moisture removallit/h
NoiseIndoor (H/M+/M/L+/L)dB
Outdoor (220-240V)dB
RefrigerantName of refrigerant
Rated amountkg
Refrigerant control
InterconnectionGas side sizemm
pipeConnection type
Liquid side sizemm
Connection type
Maximum lengthm
(One way)
Maximum heightm
difference
INDOOR UNIT
DimensionsHeightmm
Widthmm
Depthmm
Net weightkg
Evaporator type
Indoor fan type
Airflow volumeHigh fan
Medium fan
Low fan
3
m
3
m
3
m
Fan motor outputW
Air filter
OUTDOOR UNIT
DimensionsHeightmm
Widthmm
Depthmm
Net weightkg
Condenser type
Outdoor fan type
Airflow volume
3
m
Fan motor outputW
CompressorModel
OutputW
Safety device
Louver type
Usable outdoor temperature range °C
Note *1 Chargeless pipe
*2 Maximum pipe
220V
5.30
V
1640
9897
0.3/7.30 0.3/6.90 0.50/14.70 0.50/12.90
31
2.0
44/42/39/37/3545/43/41/39/37
5657
1.65
20*
810
RAS-18SKP-ESRAS-24SKP-ES
/h
/h
1000
880
/h
RAS-18SA-ESRAS-24SA-ES
/h
240025502450
PA200X2CS-4KU1
1500
240V220V
5.356.80
1∅
220 - 240
50
16802410
98
5657
R410A
Capillary tube
∅12.7
Flare connection
∅6.35
Flare connection
1
2
15*
320
1050
228
13
Finned tube
Cross flow fan
30
Honeycomb woven filter with PP frame
715
780
290
Finned tube
Propeller fan
42
Fuse , IOL
Automatic louver
15 ~ 43
44
2.7
1.70
2
25*
1100
950
850750
5045
PA270X3CS-4MU2
2000
240V
6.85
2450
93
2600
− 3 −
FILE NO. SVM-09036
MODEL RAS-18SKHP-ESRAS-24SKHP-ES
RAS-18S2AH-ESRAS-24S2AH-ES
ITEMCoolingHeatingCoolingHeating
Capacity
kW
Phase
Power source
Hz
Power consumption W
Power factor%
RunningIndoorA
CurrentOutdoorA
Starting currentA
Moisture removallit/h
NoiseIndoor (H/M+/M/L+/L)dB
Outdoor (220-240V)dB
RefrigerantName of refrigerant
Rated amountkg
Refrigerant control
InterconnectionGas side sizemm
pipeConnection type
Liquid side sizemm
Connection type
Maximum lengthm
(One way)
Maximum heightm
difference
INDOOR UNIT
DimensionsHeightmm
Widthmm
Depthmm
Net weightkg
Evaporator type
Indoor fan type
Airflow volumeHigh fan
Medium fan
Low fan
3
m
3
m
3
m
Fan motor outputW
Air filter
OUTDOOR UNIT
DimensionsHeightmm
Widthmm
Depthmm
Net weightkg
Condenser type
Outdoor fan type
Airflow volume
3
m
Fan motor outputW
CompressorModel
OutputW
Safety device
Louver type
Usable outdoor temperature range°C
Note *1 Chargeless pipe
*2 Maximum pipe
240V220V220V240V220V240V
5.105.12
V
989698
5.455.566.306.35
1∅
220 - 240
50
1470
1530219022501540158020502140
9798939893
0.300.30
6.856.556.556.309.909.809.209.30
31
2.0
44/42/39/37/3545/43/41/39/37
56-5757-58
56-5757-58
R410A
1.53
Capillary tube
∅12.7
Flare connection
∅6.35
Flare connection
1
15*
20*
2
810
RAS-18SKHP-ESRAS-24SKHP-ES
320
1050
228
13
Finned tube
Cross flow fan
/h
/h
/h
10001000
880900
750770
11001100
950950
850850
30
Honeycomb woven filter with PP frame
RAS-18S2AH-ESRAS-24S2AH-ES
715
780780
290290
Finned tube
Propeller fan
240025502400255024002550
/h
42
PA200X2CS-4KU1
PA270X3CS-4MU2
1500
Td sensor , Fuse , IOL
Automatic louver
15 ~ 43-10 ~ 2415 ~ 43-10 ~ 24
220V240V
6.806.90
44
2.5
1.62
2
25*
715
5347
24002550
2000
− 4 −
Note : 1
• Capacity is based on the following temperature conditions.
FILE NO. SVM-09036
Condition
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
• Charge refrigerant according to the table below.
Refrigerant
*1No need to charge
extra refrigerant
*2Need to charge
extra refrigerant
RAS-18SKP-ES / RAS-18SA-ES
RAS-18SKHP-ES / RAS-18S2AH-ES
Over 15 m up to 20 m (20 g/m) Over 15 m up to 25 m (20 g/m)
1 Fan motor (for indoor) ICF-340-30-2B DC 340V, 30W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Switching Transformer (T01) SWT-77 DC7V, 12 V
4 Microcontroller TMP87CM40ANG-6P68
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA
7Diode (DB01)D3SBA604 A, 600 V
8 Capacitor (C03) EKMH451VSN121MQ35S 120 µF, 450 V
9 Fuse (F01) BET 6.3A 6.3 A, 250 V
10 Varistor (R09, R10) SR561K14DL 560 V
11Resistor (R01)RF-5TK1R8
2 TLou
13
v
Relay : (RY03)
P5War1ts name
er motor MP24Z3T Output (Rated) 2 W, 6 poles, 1-2 phas e
2 Fan motor (for outdoor) FG-240-42A Winding resistance (Ω) Red-Black White-Black
(at 20° C) 128 126
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5
Magnetic contactor
CLK-35J
DS451355NPQB AC 450V, 3.5µ F
32332I5606J063 A
B
220 − 240V, 50Hz
C 450V, 60µ F
4-4. Indoor Unit (RAS-18SKHP-ES, RAS-24SKHP-ES)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) ICF-340-30-2B DC 340V, 30W
2 Thermo sensor (TA-sensor) ——— 10 kΩ at 25°C
3 Switching Transformer (T01)SWT-77 DC 7V, 12V
4 Microcontroller TMP87CM40ANG-6P68
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA
7 Diode (DB01) D3SBA60 4 A, 600 V
8 Capacitor (C03) EKMH451VSN121MQ35S 120µF, 450 V
9 Fuse (F01) BET 6.3A 6.3 A, 250 V
All indications, except for the clock time indicator, are displayed by pressing the button.
1.Transmission mark
This transmission mark
remote controller transmits signals to the indoor
unit.
indicates when the
2. Mode indicator
Indicates the current operation mode.
(A : Auto, : Cool,
: Dry, : Heat, : Fan only)
3. Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed.
AUTO or five fan speed levels
LOW , LOW+ , MED , MED+ ,
(
HIGH ) can be shown.
Indicate Auto will be appear with Dry operation
( : Dry) only.
9
1
12
2
13
10
10
5. TIMER and clock time indicator
The time setting for timer operation or the clock
time is indicated.
The current time is always indicated except
during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts.
Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is
pressed during operation.
The
button for more than 3 seconds while the mark is
blinks.
Press another button to turn off the mark.
mark is shown when holding down the
8. ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is
set, “B” appears in the remote controller display.
(When the remote controller setting is “A”, there is
no indication at this position.)
10.Comfort sleep
Indicates when comfort sleep is activaled.
Press comfort sleep button to selectter
11
6
3
8
7
4
5
11.Quiet
Indicates when quiet is activated.
Press quiet button to start and press it again to stop
operation.
12.One-Touch
Indicates when one touch comfort is activated.
Press one-touch button to start the operation.
13.Swing
Indicates when louver is swing.
Press swing button to start the swing operation
and press it again to stop the swing operation.
−20−
7-2. Outline of Air Conditioner Control
y
A
A
y
P
P
A
A
This is a fixed capacity type air conditioner, which uses
a DC motor for an indoor fan. The DC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit.
The outdoor unit receives operation commands
from the indoor unit, and operates the outdoor
fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
Operations according
to the commands
from the indoor unit
FILE NO. SVM-09036
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
• Defrost control in heating operation
(Temperature measurement by the Indoor heat
exchanger, control the four-way valve and
outdoor fan motor control)
7-2-1.
(1)
(2) Swing
7-2-2. Indoor Fan Control
Table (7-2-1) Cooling
Louver contr
V
er
tical air flow louver
ol
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button
is stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [SWING] button is pressed, it stops
swinging.
The operation controls the fan speed at indoor unit
side. The indoor fan (cross flow fan) is operated by
the phase control induction motor. The fan rotates in 5
stages in MANUAL mode, and in 5 stages in AUTO
mode, respectively. (Table 7-2-3)
1) When setting the fan speed to L, L+,M, M+ or H
on the remote controller, the operation is performed
with the constant speed shown in Table 7-2-1 and
Table 7-2-2
Table (7-2-2) Heating
Indication
L
L+
M
M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Indication
L
L+
M
M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
2) When setting the fan speed to AUTO on the remote
controller, revolution of the fan motor is controlled
to the fan speed level show in Table 7-2-3according to the setup temperature, room temperature,
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, (Heat pump model
only) outdoor fan and operation display lamp are
controlled as shown in Fig. 7-3-2.
° C
ONON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
OPERATION
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-3-2
display lamp
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) − (Preset temp.)
Preset
temp.
0
(Preset temp.: 24 °C)
NOTE 1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L*3 : Fan speed = (M + − L) x 1/4 + L
2 : The Hi Power, ECO and COMFORT SLEEP
operation can not be set
(Linear approximation from M+ and L)
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1
*2
*3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*2
*3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
(Linear approximation from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
- 22 -
FILE NO. SVM-09036
7-3-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, (Heat pump model
only) outdoor fan and operation display lamp are
controlled as shown in Fig. 7-3-4.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
OPERATION
display lamp
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-4
7-3-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set
to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-3-6.
° C
Preset
temp.
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
Fig. 7-3-6
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L. *S.L.S.L.L.L.S.L.L.
*Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO, COMFORT SLEEP, QUIET and
Hi POWER operations can not be set.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-7. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) − (Preset temp.)
L
*1
*2
+
M
H
*1 : Fan speed = (M + − L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 3/4 + L
(Calculated with Linear approximation from M+ and L+)
Fig. 7-3-7
- 23 -
FILE NO. SVM-09036
y.
c
e
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-3-8
Fan speed AUTO Fan speed MANUAL
46Tc34
45 33
33 21
32 20
*A+0 *A+0
*A-8 *A-8
Fan speed MANUAL or AUTO in starting
Fan speed AUTO in stability
* No limitation while fan speed MANUAL mode is in stabilit
* A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
Normal AUTO
Line-approximate
H and SL with Tc.
SL (W2)
Stop
L-H (Up to
setting speed)
Line-approximate
H and SL with Tc.
SL (W2)
Stop
[In starting and in stability]
In starting
FAN • Until 12 minutes
AUTO
FAN • Room temp. < Set
Manual
passed after operation
start
• When 12 to 25 minutes
passed after operation
start and room temp.
is 3°C or lower than
set temp.
temp.–4°C
In stability
• When 12 to 25 minutes
passed after opeartion
start and room temp.
is than (set )
between preset
• When 25 minutes or
more passed after
operation start
• Room temp. Set
temp. –3.5°C
3°C
7-3-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-3-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-3-9.
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) − (Preset temp.)
Heat pump model Cooling model
Fig. 7-3-9
Fig. 7-3-8 Cold draft preventing control
(4) In order to prevent cold draft when compressor
during heating operation.Then louver will move
to upper position and fan speed will reduce or
OFF.
- 24 -
7-4. Drescription of Safety and Reliability Prevention Function
FILE NO. SVM-09036
7-4-1. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Heat exchanger
temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 7-4-1
7-4-2 High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-2.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger
temp.
(°C)
62
55
54
7-4-3. Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the
refrigerant evaporation temperature detected by the
outdoor heat exchanger sensor is under the specified
temperature, the outdoor unit starts the defrosting
operation. At this time, the 4-way valve relay and the
outdoor fan motor are turned off. The indoor fan motor
is also turned off by the cold draft preventing control of
the indoor microcomputer. Then, [PRE. DEF.] lamp on
the indoor unit comes on.
The defrosting operation stops and the 4-way valve
relay, outdoor fan motor and the indoor fan motor are
turned on automatically when the refrigerant
evaporation increases to the specified temperature, or
when the defrosting time is over 12 minutes.
7-4-3-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥
start when.
Teo - Te ≥
~ 30 min after operation.
B-Zone : If Te ≤
-18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC ≥
Teo ≥ -10°C defrost will start when
Teo - Te ≤ -3°C at least 20 sec or ~ 60 min
after operation.
7-4-3-2. Defrost finish condition.
1) If Te ≥ 3°C at least 60 sec -->4 way value on.
2) If Te ≥ 8°C --> 4 way value on.
Timing
- 18°C, defrost will
2.5°C at teat 20 sec or
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Fig. 7-4-2
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100
Heating time rate : (Tt - Td) x Tt
Fig. 7-4-3
- 25 -