Toshiba MMY-MAP1202FT8, MMY-MAP1002FT8, MMY-MAP0802FT DATA BOOK

Super-HRM
Engineering
(2 series)
Super Heat Recovery Multi System
Data Book
1
Foreword
The engineering data book details all specific data, charts
from the Toshiba Super Heat Recovery Multi System (2 Se-
ries) for the various different applications.
The information is aimed to assist you with greater detail of
the system and the wider applications that the system will
Foreword
1
cover.
It is recommended the use of the data book is used in accor-
dance with the following as references.
Design manual : File No.A04-017
Installation manual : File No.A05-018
1
2
Contents
Foreword
2
1 Forward
2 Contents
3 Introduction
4 System overview
5 Capacity compensation chart
6 Piping requirements
7 Refrigerant cycle diagram
8 Sensible capacity table
9 Part load performance
10 Wiring guideline
11 Wiring diagram
....................................................................
.....................................................................
.................................................................
.........................................................
..................................................
..........................................
..............................................
...............................................
........................................................
..........................................................
.....................................
1
2
3
7
17
25
31
43
69
81
89
12 Controls
13 Fan characteristics
14 Sound characteristics (NC curve)
15 Dimensional drawing
1. Indoor units
2. Outdoor units
3. FS units
4. Branch header/Branch joint
16 Specifications
..................................................................
..................................................
...............................................
..........................................................
Appendix
High Wall Type (2 series)
.............................
107
129
139
155
191
1-Way Air Discharge Cassette Type (2 series)
Slim Duct Type
2
3
Introduction
3
4
3
Introduction
Foreword
The World's Best Technology for Energy Saving, Heat Recovery VRF
Toshiba is proud to introduce the Super HRM system, 3pipe heat recovery VRF operating on R410A. Incorporating advanced technology in all aspects of efficiency, durability, flexibility and comfort. Super HRM will meet various different site applications.
3
System Outline
Outdoor unit
Indoor unit
(Heating)
Suction gas
Discharge gas
Liquid
(Discharge gas / Suction gas / Liquid)
Energy saving
No.1 COP in heat recovery VRF industry. DC twin rotary compressors are most congenial with R410A and are used within the outdoor units. All compressors are driven by a High-speed Calculation Vector Control Inverter.
3 pipe
FS unit
(Flow Selector unit)
Indoor unit
(Cooling)
Outdoor unit
High-speed Calculation Vector Control Inverter
Average COP
8HP System 10HP System
Super-HRM(R410A)
3.83
3.45
DC Twin Rotary Compressor
Simultaneous Operation
By control of the FS unit, Super HRM enables simultaneous operation of cooling and heating. Super HRM also improves the energy efficiency by the recycling of exhaust heat.
Ex. Mainly Cooling, Partly Heating Operation
FS unit
Indoor unit
Heating
Cooling Cooling Cooling
Main Heat Exchanger Sub-Heat
Exchanger
Outdoor unit
Compressor
5
Design Flexibility
3
Piping flexibility
Equivalent piping length Up to 125m
50m (from 1st branching)
35m (elevation between FCU)
50m (Elevation between CDU and FCU)
Elevation between indoor units = 35m(No.1!) Furthest piping length from 1st branch = 50m(No.1!)
Flexibile Joint Combination
Y Branch after header branch
(Toshiba unique technology)
Header branch after Y joint
Header after header branch
(Toshiba unique technology)
FS Unit Design
The compact and light weight design of the FS unit(Flow Selector Unit)allows it to be easily installed within a limited space.
190H x 250W x 160D
5kg
Easy of hanging (Only 2 hangers)
Easy maintenance (Valve coil and P.C. board are on the same side)
Centralized Control System
By using the central control devices, individual control of indoor units is possible throughout multiple systems. Centralized control systems with Super MMS can also be integrated with Build­ing Management System (BMS).
Super MMS Super HRM
Central remote controller
6
4
System overview
7
8
4
System overview
Foreword
1. OUTLINE OF TOSHIBA SUPER HRM (Super Heat Recovery Multi System)
Shortest route design by free branching
The Combination of line and header branching is highly flexible. This follows for the shortest design route possible, thereby saving on installation time and cost. Line/header branching after the header branching is only available with TOSHIBA Super HRM.
Line branching
Outdoor unit
4
Branching joint
FS unit
Indoor unit
Header branching
Outdoor unit
Branching
header
FS unit
Indoor unit
Line + Header branching
Outdoor unit
Branching joint
Indoor unit
Header
Line branching after header branching
Outdoor unit
8F
7F
2F
FS unit
1F
Branching joint
Super HRM
MMS Only
Only
Indoor unit
Header
Header branching after header branching
Outdoor unit
Header
Super HRM
Only
Header
FS unit
Indoor unit
FS unit
9
4
Non-polarized control wiring between outdoor and indoor units
8F
7F
Outdoor unit
Indoor unit
FS unit
Indoor
unit
Heating Cooling Cooling Cooling
Simultaneous operation
U1 U2
U1 U2 U1 U2 U1 U2
main heat exchanger
Sub heat exchanger
Outdoor unit
Compressor
10
2F
1F
Outdoor unit
Height difference between indoor
Height difference between indoor
unit and indoor unit : 35m
unit and outdoor unit : 50m
From 1st branching to the furthest indoor unit : 50m
Allowable pipe length : 150m equivalent length
1st branching section
Energy saving
No.1 COP in heat recovery VRF industry.Compared with the conventional chiller fan coil system, a large energy saving can be achieved.
Advanced bus communication system
Wiring between indoor and outdoor units is a simple 2 core wire system. Communication of addresses is also automatically configured. A default test mode operation is available.
Self diagnostics system
Comprehensive troubleshooting codes allows for a timely identification of possible problems arising.
High lift and flexible piping design
Equivalent pipe length of 150m and vertical lift of 50m is possible with TOSHIBA Super HRM. Vertical lift between indoor units of 35m is the highest in the industry. Also the maximum piping length from the 1st branch is 50m. This allows for greater flexibility within the building design of the system.
Simultaneous operation
By controlling the FS unit, Super HRM enables simultaneous operation of cooling and heating. This operation meets the various requirements of modern buildings that are highly airtight or have an increasing heat load due to the use of computers. Super HRM also improves energy efficiency by recycling of the exhaust heat.
Extended outdoor temperature operating range
By use of sophisticated system control with inverter driven compressors, the operating range in cooling has been increased from -5
to -10 .
4
Compact FS unit design
The compact and light weight design of the FS unit (Flow selector unit) allows it to be easily installed with in a limited space.
Group control by one FS unit
Up to 8 indoor units can be group controlled by the use of only one FS unit, this gives greater flexibility for various different types and sizes of rooms.
Intelligent control
TOSHIBA Super HRM intelligent controls and modulating valves deliver the required capacity according to the load variation from 50% to 100%. The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so humidity and temperature are kept within the comfort zone.
Conforms to building control law
IAQ (Indoor Air Quality) is also achieved by combining various accessories required by the Building Control Law.
Wide control applications
Artificial Intelligence Network system. Central control and monitoring system available. Weekly schedule operation through weekly timer.
Integration with Building Management System (BMS) is available.
11
4
2. SUMMARY OF SYSTEM EQUIPMENTS
Equipment
1. Outdoor units
Corresponding HP
Model name MMY-
Cooling capacity (kW)
Heating capacity (kW)
8HP
MAP0802FT8
22.4
25.0
2. Outdoor units (Combination of outdoor units)
Corresponding HP
Combined model
Cooling capacity (kW) Heating capacity (kW)
Combined outdoor units
No. of connectable indoor units
MMY-
8HP 10HP
MAP0802FT8
22.4 25
8HP
13
Inverter unit
10HP
MAP1002FT8
28.0
31.5
MAP1002FT8
28
31.5
10HP
16
MAP1202FT8
12HP
MAP1202FT8
33.5
35.5
12HP
16
12HP
33.5
35.5
16HP
AP1602FT8
45
50 8HP 8HP
27
Appearance
18HP
AP1802FT8
50.4
56.5
10HP
8HP
30
Corresponding HP
Combined model
Cooling capacity (kW) Heating capacity (kW)
Combined outdoor units
No. of connectable indoor units
MMY-
20HP 24HP
AP2002FT8
56
63 10HP 10HP
33
AP2402FT8
68
76.5 8HP 8HP 8HP
40
26HP
AP2602FT8
73
81.5
10HP
8HP 8HP
43
3. FS units (Flow selector units)
Model name
RBM-Y1122FE
RBM-Y1802FE
RBM-Y2802FE
Total capacity for indoor unit : Below 11.2 kw
Total capacity for indoor unit : 11.2 to below 18.0 kw
Total capacity for indoor unit : 18.0 to 28.0 kw or less
*Accessory part (Sold separately): Connection cable kit (RBC-CBK15FE) up to 15m.
Usage Appearance
4. Branching joints and headers
Model name Usage
Y-shape branching joint (*3)
4-branching header (*4) (*5)
8-branching header (*4) (*5)
T-shape branching joint (For connection of outdoor units)
RBM-BY53FE RBM-BY103FE RBM-BY203FE RBM-BY303FE
RBM-BY53E RBM-BY103E RBM-BY203E RBM-BY303E
RBM-HY1043FE RBM-HY2043FE
RBM-HY1043E
RBM-HY2043E RBM-HY1083FE RBM-HY2083FE
RBM-HY1083E
RBM-HY2083E
RBM-BT13FE
Indoor unit capacity code (*1) : Total below 6.4 Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 Indoor unit capacity code (*1) : Total 25.2 or more Indoor unit capacity code (*1) : Total below 6.4 Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 Indoor unit capacity code (*1) : Total 25.2 or more Indoor unit capacity code (*1) : Total below 14.2 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 Indoor unit capacity code (*1) : Total below 14.2 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 Indoor unit capacity code (*1) : Total below 14.2 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 Indoor unit capacity code (*1) : Total below 14.2 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
1 set 4 types T-shape joint pipes as described below: The required quantity is arranged and they are combined on site.
Connection piping Balance pipe Piping at liquid side Piping at discharge gas side Piping at suction gas side
Corresponded dia. (mm)
9.5
12.7 to 22.2
19.1 to 28.6
22.2 to 38.1
28HP
AP2802FT8
78.5 88
10HP 10HP
8HP
47
Q'ty
1 1 1 1
AP3002FT8
For 3
piping
For 2
piping (*6)
For 3 piping For 2
piping (*6)
For 3 piping
For 2
piping (*6)
30HP
84
95 10HP 10HP 10HP
48
Appearance
*1 ``Capacity code`` can be obtained from page 8. (Capacity code is not actual capacity) *2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit. *3 When using Y-shape branching joint for 1st branching, select according to the capacity code of outdoor unit. *4 Max. capacity code of 6.0 in total can be connected. *5 If capacity code of outdoor unit is 26 or more, it is not used for the 1st branching. *6 This is used for branching to ``cooling only`` indoor unit. *7 Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.
12
Super Heat Recovery Multi System Outdoor Unit
50Hz
HP (Capacity
code)
8HP ( 8)
10HP (10)
12HP (12)
16HP (16)
18HP (18)
20HP (20)
24HP (24)
26HP (26)
28HP (28)
30HP (30)
*
Model name
MMY-
MAP0802HT8
MAP1002HT8
MAP1202HT8
No. of
combined
units
1
1
1
2
2
2
12HP unit is for stand-alone use only.
Inverter
8 HP
MMY-
MAP0802FT8
MAP0802FT8
MAP0802FT8
MAP0802FT8
MAP0802FT8
MAP0802FT8
Outdoor unit combination with a 12HP unit is not available.
1. Allocation standard of model name
MMY- M AP T 8F
Used
Qty
1
2
1
3
2
1
Power supply specifications, 3 380-415 V, 50Hz ....... 8
T : Capacity variable unit
F : Heat recovery
Development series No.
Capacity rank HP x 10
New refrigerant R410A
M : Single module unit, No mark : Combined Model name
Modular Multi
Inverter
10 HP MMY-
MAP1002FT8
MAP1002FT8
MAP1002FT8
MAP1002FT8
MAP1002FT8
MAP1002FT8
Used
Qty
1
1
2
1
2
3
Inverter
12 HP MMY-
MAP1202FT8*
Used
Qty
1
4
2. Rated conditions (Rated mode : Condition)
Cooling : Indoor air temperature 27 DB/19 WB, Outdoor air temperature 35 DB Heating : Indoor air temperature 20
DB, Outdoor air temperature 7 DB/6 WB
3. Compatibility with 1 Series
Oudoor unit MMY-
1 Series
-MAP**1FT8
FS unit
1 Series
RBM-Y***1E
2 Series
RBM-Y***2E
OK
OK
* 2 series outdoor units cannot be used with 1 series outdoor units.
2 Series*
-MAP**2FT8
NG
OK
13
4
4. Indoor unit
*1) China market only *2) European market only *3) Korea market only
Type Appearance Model name Capacity rank Capacity code
009 type 012 type 015 type 018 type 024 type 027 type 030 type 036 type 048 type 056 type 007 type 009 type 012 type 015 type 018 type 024 type 027 type 030 type
1)
048 type 007 type 009 type 012 type 015 type 018 type 024 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type
1)
007 type
*
1)
009 type
*
1)
012 type
*
1)
015 type
*
1)
018 type
*
007 type 009 type 012 type 015 type 018 type 007 type 009 type 012 type 015 type 018 type 024 type 027 type 030 type 036 type 048 type 056 type 018 type 024 type 027 type 036 type 048 type 072 type 096 type 015 type 018 type 024 type 027 type 036 type 048 type
4-way Air Discharge Cassette Type
2-way Air Discharge Cassette Type
1-way Air Discharge Cassette Type
Slim Duct Type
Concealed Duct Standard Type
Concealed Duct High Static Pressure Type
Under Ceilling Type
MMU-AP0091H MMU-AP0121H MMU-AP0151H MMU-AP0181H MMU-AP0241H MMU-AP0271H MMU-AP0301H MMU-AP0361H MMU-AP0481H MMU-AP0561H MMU-AP0071WH MMU-AP0091WH MMU-AP0121WH MMU-AP0151WH MMU-AP0181WH MMU-AP0241WH MMU-AP0271WH MMU-AP0301WH MMU-AP0481WH* MMU-AP0071YH MMU-AP0091YH MMU-AP0121YH MMU-AP0151SH MMU-AP0181SH MMU-AP0241SH MMU-AP0152SH MMU-AP0182SH MMU-AP0242SH MMD-AP0071SPH MMD-AP0091SPH MMD-AP0121SPH MMD-AP0151SPH MMD-AP0181SPH MMD-AP0071SPH(SH)-C MMD-AP0091SPH(SH)-C MMD-AP0121SPH(SH)-C MMD-AP0151SPH(SH)-C MMD-AP0181SPH(SH)-C MMD-AP0071SPH-K MMD-AP0091SPH-K MMD-AP0121SPH-K MMD-AP0151SPH-K MMD-AP0181SPH-K
3)
*
3)
*
3)
*
3)
*
3)
* MMD-AP0071BH MMD-AP0091BH MMD-AP0121BH MMD-AP0151BH MMD-AP0181BH MMD-AP0241BH MMD-AP0271BH MMD-AP0301BH MMD-AP0361BH MMD-AP0481BH MMD-AP0561BH MMD-AP0181H MMD-AP0241H MMD-AP0271H MMD-AP0361H MMD-AP0481H MMD-AP0721H MMD-AP0961H MMC-AP0151H MMC-AP0181H MMC-AP0241H MMC-AP0271H MMC-AP0361H MMC-AP0481H
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00
0.8
1.00
1.25
1.70
2.00
2.50
3.00
3.20
5.00
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00
2.00
2.50
3.00
4.00
5.00
8.00
10.00
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
14.0
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
5.6
7.1
8.0
11.2
14.0
22.4
28.0
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
16.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
6.3
8.0
9.0
10.0
16.0
25.0
31.5
5.0
6.3
8.0
9.0
12.5
16.0
14
4. Indoor unit
*1) China market only *2) European market only
Type Appearance Model name Capacity rank Capacity code
007 type 009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 007 type 009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type 024 type 015 type 018 type 024 type 027 type 036 type 048 type 056 type
High Wall Type (1 series)
High Wall Type (2 series)
Floor Standing Cabinet Type
Floor Standind Concealed Type
Floor Standind Type
MMK-AP0071H MMK-AP0091H MMK-AP0121H MMK-AP0151H MMK-AP0181H MMK-AP0241H MMK-AP0072H* MMK-AP0092H* MMK-AP0122H* MML-AP0071H MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MML-AP0071H MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MMF-AP0151H MMF-AP0181H MMF-AP0241H MMF-AP0271H MMF-AP0361H MMF-AP0481H MMF-AP0561H
2)
2)
2)
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
3.00
4.00
5.00
6.00
*3) Korea market only
Cooling
capacity (kW)
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
16.0
Heating
capacity (kW)
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
10.0
16.0
18.0
4
15
5. Remote controller
4
Name
Model
name
Appearance Application Function
SET DATA
UNIT No.
SETTING
R.C. No.
TEST
CL
SET
Wired remote controllerSimple wired remote controllerWireless remote controller kit
TEST
SETTING
UNIT
ûC ûF
CODE No.
Connected to indoor unit
Wired remote
controller
Wired remote controller (In case of control by 2 remote controllers)
Connected to indoor unit
Start / Stop Mode Change Temperature setting Change of air flow Timer function
1
On or off timer operation, setting in 30 minute increments. Automatic Off function. Combined with the weekly timer, weekly
2
schedule operation can be operated.
Filter sign Displays automatically maintenance time of indoor filter. Filter sign flashes. Self-diagnosis function Pressing ``CHECK`` button displays cause of fault on the check code. Control by 2 remote controllers is available. Two remote controllers can be connected to one indoor unit. The indoor unit can be separately operated from a different location.
Start / Stop Temperature setting Change of air flow Check code display
RBC-AS21E/RBC-AS21E2 RBC-AMT21E/RBC-AMT31E
TCB-AX21U(W)-E
TCB-AX21U(W)-E2
RBC-AX22CE
RBC-AX22CE2
Simple remote controller
Connected to indoor unit
Start / Stop Mode change Temperature setting Change of air flow Timer function On or off timer operation, setting in 30 minute increments. Automatic Off function. Control by 2 remote controllers is available. Two wireless remote controllers can operate one indoor unit. The indoor unit can be separately operated from a different location. Check code display TCB-AX21U(W)-E2 (for 4-way airdischarge cassette) RBC-AX22CE2 (for under ceiling) TCB-AX21-E2 (for other units except for the concealed duct high static pressure)
16-1
16
TCB-AX21E
TCB-AX21E2
Name
Model
name
Appearance Application Performance
Weekly timer
RBC-EXW21E
RBC-EXW21E2
PROGRAM1
PROGRAM2
PROGRAM3
WEEKLY TIMER
SuMoTuWeTh FrSa
ERROR
Connected to central
remote controller or
wired remote controller
Wired
remote controller
Outdoor unit
Central
remote controller
Weekly
timer
Weekly
timer
Weekly schedule operation
1
Setting different start / stop time for each day of the week
2
ON / OFF can be set 3 times a day.
ON
8:00 12:00 13:00 18:00 19:00 21:00
3
``CHECK`` ``PROGRAM`` ``DAY``
OFF ON OFF ON OFF
button copying of settings easy.
4
Two different schedules for a week can be specified. (Summer schedule and winter schedule, etc.)
5
``CANCEL`` ``DAY`` button enables holiday setting.
6
If power supply fails, the setting contents are stored in the memory for 100 hours.
4
ZONE
ALL ZONE GROUP
1234
SET DATA
SETTING
SELECT ZONE
TCB-SC642TLE
TCB-SC642TLE2
TEST
UNIT No.
R.C.
No.
SET
CL
Central remote controller
GROUP
CODE
No.
Connected to outdoor unit,
indoor unit
Outdoor
unit
Central
remote controller
Central remote
controller
Indoor
remote controller
Individual control up to 64 indoor units.
Individual control for max. 64 indoor units divided into 4 zones.
Up to 16 indoor units for each zone
Up to 16 outdoor header units are connectable.
Four selectable central control settings to restrict individual remote controller operations.
Setting for one of 1 to 4 zones is available.
Can be used with other central control devices (Up to 10 central control devices with in one control circuit)
Two selectable control modes
Central controller mode Remote controller mode
Setting of simultaneous ON/OFF 3 times for each day of the week combined with a weekly timer.
16-2
17
Name
Model
name
Appearance Application Performance
TCB-CC163TLE2
ON-OFF controller
Connected to outdoor unit,
indoor unit
Header
ON-OFF controller
ON-OFF
controller
Outdoor unit
remote controller
Follower
Outdoor unit
Indoor
Individual control up to 16 indoor units.
Setting of simultaneous ON-OFF 3 times for each day of the week when combined with a weekly timer.
Connected to 2 remote controllers is possible.
16-3
18
5
Capacity compensation chart
17
18
5
Capacity compensation chart
Foreword
Cooling/heating capacity characteristics
1. Cooling capacity calculation method : Required cooling capacity = Cooling capacity x Factor ( ) kW
1
Indoor air wet bulb temperature vs. capacity correction value
1.2
1.1
1.0
0.9
5
0.8 15
Capacity correction value
20 24
Indoor air wet bulb temp. ( )
2
Outdoor air dry bulb temperature vs.capacity correction value
1.2
1.1
1.0
0.9
-
50 5 1015202530354043
Capacity correction value
Outdoor air dry bulb temp. ( )
3
Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)
1.1
1.0
0.9 80 90 100 110 120
Capacity correction value
1: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of
*
Air flow variation ratio (%)
the indoor units are not equal to the outdoor unit capacity.
19
5
4
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Outdoor unit (8 to 30HP)
50 40 30 20
%100
10
0
-
10
-
20
-
30
Height of outdoor unit H (m)
98
20 30 40 50 60 70 80 90
100
Pipe length (Equivalent length) L (m)
96
94
92
908488
ho l
86
Outdoor unit
,
L
is the longest one of
,
(l
,
o
H = ho + (Largest one of ha, hb, and hc)
82
80
78
100 110 120 130 140 150
o + l,a, l,o + l,b, l,o + l,c)
76
5
Correction of outdoor unit diversity
hb
hc
120
100
80
60
40
Correction (%)
20
20 40 60 80 100 120 135
0
ha
,
a
l
A
,
b
l
B
,
l
c
C
Standard capacity ratio
Indoor units total capacity ratio (%)
Indoor unit
1: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of
*
the indoor units are not equal to the outdoor unit capacity.
20
2. Heating capacity calculation method : Required heating capacity = Heating capacity x Factor ( ) kW
1
Indoor air dry bulb temperature vs. capacity correction value
1.2
1.1
1.0
0.9
0.8 15 20 24
Capacity correction value
Indoor air dry bulb temp. ( )
2
Outdoor air wet bulb temperature vs. capacity correction value
5
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
-
15
Capacity correction value
3
Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)
-
10
-
50 5 1015
Outdoor air wet bulb temp. (
)
1.1
1.0
0.9 80 90 100 110 120
Capacity correction value
1: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of
*
Air flow variation ratio (%)
the indoor units are not equal to the outdoor unit capacity.
2: Refer to item 3 on the next page.
*
21
0
80
60
40
20
20 40 60 80 100 120 135
120
100
Outdoor unit
Indoor unit
L, is the longest one of (l,o + l,a, l,o + l,b, l,o + l,c)
H = ho + (Largest one of ha, hb, and hc)
A
ha
hb
hc
ho l,o
l,a
l,b
l,c
B
C
100 2030405060708090
100 110 120 130 140 150
-
20
-
10
0
10
20
30
40
50
-
30
100%
92
93
94
96
97
98
99
91
95
5
4
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Outdoor unit (8 to 30HP)
Height of outdoor unit H (m)
Pipe length (Equivalent length) L (m)
5
Correction of outdoor unit diversity
*
the indoor units are not equal to the outdoor unit capacity.
1: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of
Correction (%)
Indoor units total capacity ratio (%)
Standard capacity ratio
3. Capacity correction in case of frost on the outdoor heat exchanger when in heating
Correct the heating capacity when frost can be found on the outdoor heat exchanger. Heating capacity =Capacity after correction of outdoor unit Correction value of capacity resulted from frost (Capacity after correction of outdoor unit : Heating capacity calculated in the above item 2.)
22
6
Capacity correction in case of frost on the outdoor heat exchanger
1.0
0.9
0.8
Capacity correction value
-
15
-
10
Outdoor air wet bulb temp. (
-
50 5 10
)
4. Capacity calculation for each indoor unit
Capacity for each indoor unit = Capacity after correction of outdoor unit x
Required standard capacity of indoor unit Total value of standard indoor unit capacity
5. Operating temperature range
In cooling time
45
40
35
30
25
20
15
10
5
0
Outdoor air dry bulb temp. ( )
-
5
-
10
Continuously
operable
range
Usable range
(in pull down)
3025 28201510
Indoor air wet bulb temp. ( )
)
-
Outdoor air wet bulb temp. (
-
-
In heating time
20
15
10
5
0
-
5
10
15
20
5 1015202530
Indoor air dry bulb temp. ( )
Continuously
operable
Usable range
(in warming-up)
range
* The unit can be operated even if the outdoor temperature goes below -20 , however you must note that the war­ ranty only covers down to -15 * When outdoor air temperature falls to below -15 * When outdoor temperature goes out of the specified range
this is because operation beyond this temperature is outside of specification.
, it may shorten the lifespan of the product.
`` or `` mark is indicated on the remote control-
ler display and the required operation will stop.
`` & `` : When heating operation `` `` : When cooling operation
5
[Notice]
This indication is not a failure. When outdoor temperature goes back to within the specified range,
`` or `` disappear and normal operation
will start. Operation stops because the concurrent operation can not be kept in the condition, as it is out of specification for Super HRM. (Outdoor temp.(DB) <-10 >21
: Cooling,
: Heating) * Do not use ``Super HRM`` other than for personal usage where the ambient temperature may go down below -10
. (For example, fresh air intake equipment/Electric device/Food/Animals and plants/Art object)
6. Rated conditions
Cooling : Indoor air temperature 27
Heating : Indoor air temperature 20
DB/19.0 WB, Outdoor air temperature 35 DB
DB, Outdoor air temperature 7 DB/6 WB
23
24
6
Piping requirements
25
26
6
Piping requirements
Foreword
1. Allowable length/height difference of refrigerant piping
Height difference between outdoor units
H3 5m
Height difference between outdoor and indoor units
H1 50m
Outdoor Unit
T-shape
branching
Main piping
L1
1st branching section
Follower Unit
C
Header Unit Follower Unit
A
Branching piping
Connecting piping of indoor unit
L3
a
ghi j
Indoor unit
Equivalent length corresponded to farthest piping
Equivalent length corresponded to farthest piping after 1st branching
L4 L5 L6 L7LhL8
def
FS unit
lmn
Indoor unit
B
La Lb Lc
LA
Main connecting piping between outdoor units Length corresponded to farthest piping between outdoor units
L2
bc
Branching
header
FS unit
LO 25m
L9
FS unit
< Cooling only > < Cooling only >
o
(Header)
k
Lj
Note: In case of connecting method Ex.2, a large amount of refrigerant and refrigerant oil may return to the head unit. Therefore, set the T-shape joint so that oil does not enter directly
<Ex.1> Header UnitFollower UnitFollower Unit.
<Ex.2> Header UnitFollower UnitFollower Unit
L 150m
pq
Li 50m
(q)
A B C
A B C
Height difference between indoor units
H2 35m
(Upper outdoor unit)
Height difference between indoor units in group control by one FS unit
H4 0.5 m
6
* Allowable length and height difference of refrigerant piping
Total extension of pipe (Liquid pipe, real length)
Farthest piping length L (*1)
Real length
Equivalent length
Max. equivalent length of main piping
Pipe
Length
Equivalent length of farthest piping from 1st branching Li (*1)
Max. real length of indoor unit connecting piping
Max. real length between FS unit and indoor unit (*2)
Max. Equivalent length of outdoor unit connecting piping LO (*1)
Max. real length of outdoor unit connecting piping
Max. equivalent length between FS unit and indoor unit Lj
Max. real length between FS unit and header indoor unit Lh (*2)
Upper outdoor unit
Lower outdoor unit
Upper outdoor unit
Lower outdoor unit
Height
Difference
Height between indoor and outdoor units H1
Height between indoor units H2
Height between outdoor units H3
Height difference between indoor units in group control by one FS unit H4
1 : The furthest outdoor unit from 1st branch is to be named C, and furthest indoor unit from 1st branch to be named (q).
*
2 : The supplied connection cable can be used up to 5 m in pipe length between the indoor and FS unit. When the pipe length
*
Allowable value
300 m
125 m
150 m
LA+La+Lb+Lc+L1+L2+L3+L4+L5+L6+L7+L8+9 +a+b+c+d+e+f+g+h+i+j+k+l+m+n+o+p+q
LA+Lc+L1+L3+L4+L5+L6+L7+L8+q
85 m L1
50 m L3+L4+L5+L6+L7+L8+q
30 m a+g, b+h, c+i, d+l, e+m, f+n, j, k
15 m g, h, i, l, m, n, L7+o, L7+L8+p, L7+L8+q
25 m LA+Lc (LA+Lb)
10 m La, Lb, Lc
30 m
15 m
50 m
30 m
35 m
15 m
5 m
0.5 m
L7+L8+q, L7+L8+p
L7+o
-
-
-
-
-
-
between the indoor and FS unit exceeds 5 m, you must use the connection cable kit (RBC-CBK15FE).
* System restrictions
Max. No. of combined outdoor units Max. capacity of combined outdoor units
Max. No. of connected indoor units
Max. capacity of combined indoor units
1 : MMY-MAP1201HT8 : UP to 120 %
*
84.0 kW 48 units
H2 15m H2
>
15m
3 units
135% (*1) 105%
Note 1) Combination of outdoor units : Header unit (1 unit) + Follower unit (0 to 2 units). Header unit is outdoor unit nearest to the connected indoor units Note 2) Install the outdoor units in order of capacity. (Header unit Follower unit 1 Follower unit 2) Note 3) Refer to outdoor unit combination table in page.6. Note 4) Piping to indoor units shall be perpendicular to piping to the head outdoor unit as Ex.1. Do not connect piping to indoor units in the same direction of head outdoor unit as Ex.2.
Piping section
27
Loading...
+ 236 hidden pages