Toshiba HV6AS User Manual

Document: GF07Z301 Rev. 1
INSTRUCTION MANUAL
INSTALLATION - OPERATION - MAINTENANCE

HV6AS Vacuum Circuit Breakers – Fixed Type

4.8 & 7.2kV Voltage Classes
APPLICABLE MODEL NUMBERS:
(Manual Operation Types)
HV6AS-U HV6AS-L
(Motor Operation Types)
HV6AS-MU HV6AS-ML
Issued: 2/2000 Supercedes First Issue Dated 2/99.

INSTRUCTION MANUAL

For the Installation, Operation and Maintenance of

HV6AS Vacuum Circuit Breakers – Fixed Type

4.8 & 7.2kV Voltage Classes
Never attempt to install, operate, maintain or dispose of this equipment until
WARNING
To contact Toshiba, address all correspondence to:
Field Service Department Toshiba International Corporation 13131 West Little York Road Houston, Texas 77041 USA
you have first read and understood all of the relevent product warnings and user directions that are contained in this Instruction Manual.
or call:
(713) 466-0277 (800) 231-1412 (800) 527-1204 (Canada)
Fax: (713) 466-8773
Please complete the following information for your records and retain with this manual:
Model: ___________________________________
Serial Number:_____________________________
Date of Installation: _________________________
Inspected by: ______________________________
Reference Number: _________________________
© TOSHIBA INTERNATIONAL CORPORATION, 2000
SAFETY Page 1
IMPORTANT MESSAGES
Read this manual and follow its instructions. Signal words such as
DANGER, WARNING and CAUTION will be followed by important safety information that must be carefully reviewed.
DANGER
WARNING
CAUTION
NOTE Gives you helpful information

READ SAFETY SIGNS

To avoid injury, you must read and follow all safety signs.
Keep the safety signs visible and in good shape. Never remove or cover any safety signs.
Indicates a situation which will result in death, serious injury, and severe property damage if you do not follow instructions.
Means that you might be seriously injured or killed if you do not follow instructions. Severe property damage might also occur.
Means that you might be injured if you do not follow instructions. Equipment damage might also occur.
Page 2 SAFETY
QUALIFIED OPERATORS ONLY
Only qualified persons are to install, operate, or service this equipment according to all applicable codes and established safety practices.
A qualified person must:
1) Carefully read the entire instruction manual.
2) Be skilled in the installation, construction or operation of the equipment and aware of the hazards involved.
3) Be trained and authorized to safely energize, deenergize, clear, ground, lockout and tag circuits in accordance with established safety practices.
4) Be trained and authorized to perform the service, maintenance or repair of this equipment.
5) Be trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shield, flash clothing, etc. in accordance with established practices.
6) Be trained in rendering first aid.
SAFETY CODES
Toshiba HV6AS vacuum circuit breakers are designed and built in accordance with JIS C 4603-1990 and JEC-2300-1985. Installations must comply with all applicable state and local codes, adhere to all applicable National Electric Code (NFPA 70) standards and instructions provided in this manual.
SAFETY Page 3
DANGER
Turn off and lock out Primary and Control Circuit Power before servicing.
Keep all panels and covers securely in place.
Never Defeat, Modify, or Bypass any Safety Interlocks
Qualified Operators only
HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion and property damage.
SAFETY.................................................................................................................................................... 1
Page 4 TABLE OF CONTENTS
INTRODUCTION ......................................................................................................................................6
GENERAL DESCRIPTION.......................................................................................................................7
Components..................................................................................................................................7
Indicators and Controls ................................................................................................................. 8
RECEIVING, INSPECTION AND HANDLING..........................................................................................9
Receiving and Unpacking .............................................................................................................9
Acceptance Inspection..................................................................................................................9
Handling and Moving ..................................................................................................................10
INSTALLATION......................................................................................................................................11
Rating Verification.......................................................................................................................11
Mounting the Circuit Breaker to a Panel .....................................................................................12
Mounting Directly to a Shelf ........................................................................................................14
Main Circuit Cable Connections..................................................................................................15
Ground Connections ...................................................................................................................16
Control Circuit Connections ........................................................................................................17
Additional Auxiliary Switch ..........................................................................................................17
PRE-ENERGIZATION CHECK ..............................................................................................................18
General .......................................................................................................................................18
Electrical Checks ........................................................................................................................18
OPERATION...........................................................................................................................................19
Manual Operation........................................................................................................................19
Electrical Operation..................................................................................................................... 19
Undervoltage Trip........................................................................................................................24
MAINTENANCE .....................................................................................................................................25
Maintenance Program.................................................................................................................25
Maintenance Record...................................................................................................................25
Servicing Equipment ...................................................................................................................25
Inspection and Maintenance Types ............................................................................................26
Table 1. Tightening Torques ...................................................................................................... 26
Table 2. Check Points for Periodic Inspection ...........................................................................27
Vacuum Check............................................................................................................................29
DISPOSAL..............................................................................................................................................31
STORAGE ..............................................................................................................................................32
Storage........................................................................................................................................32
TABLE OF CONTENTS Page 5
Inspection During Storage...........................................................................................................32
SPECIFICATIONS..................................................................................................................................33
Table 3. Ratings – Manual Operation HV6AS-U and HV6AS-L Types ...................................... 33
Table 4. Ratings – Motor Operation HV6AS-MU and HV6AS-MU Types .................................. 33
WARRANTY AND LIMITATION OF LIABILITY.....................................................................................34
Page 6 INTRODUCTION
It is the intent of this manual to provide a guide for safely installing, operating and maintaining Toshiba vacuum circuit breakers. This manual consists of a section of general safety instructions and is marked throughout with warning symbols. Read this manual thoroughly before installation, operation and maintenance of this equipment.
This manual and all accompanying drawings should be considered a permanent part of the equipment. They should be readily available for review and reference at all times. This manual is not intended to cover all details, combinations, or variations of the equipment. Always refer to drawings accompanying the equipment for additional details.
All safety warnings must be followed to ensure personal safety. General safety instructions are found on pages 1 through 3. Read and save these instructions for future reference.
Follow all precautions to attain proper equipment performance and longevity.
Dimensions shown in the manual are in metric and/or their English equivalent.
This manual is divided into major sections of interest, as follows:
GENERAL DESCRIPTION – Provides a description of the equipment, information on major components and how they function, plus rating information.
RECEIVING, INSPECTION AND HANDLING – Describes procedures for receiving, unpacking, inspecting, handling, lifting and moving the circuit breaker.
INSTALLATION – Provides information on installing the circuit breaker in the switchgear cell along with breaker racking procedures.
PRE-ENERGIZATION CHECK – Provides a checklist for preparing the equipment for energization.
OPERATION – Provides information on manual and electrical operation of the circuit breaker, circuit
diagrams, operating sequence description and operation of circuit breaker optional accessories.
MAINTENANCE – Lists the basic maintenance procedures for this equipment necessary for safe and reliable operation.
DISPOSAL – Lists procedures for the safe disposal of the equipment when the service life has expired.
STORAGE – Provides guidelines for storing new equipment for an extended period of time.
SPECIFICATIONS – Covers ratings and other specifications of the circuit breaker.
WARRANTY AND LIMITATION OF LIABILITY – Details Toshiba International Corporation’s standard
warranty terms.
GENERAL DESCRIPTION Page 7
The Toshiba HV6AS vacuum circuit breakers described in this manual are suitable for use on systems of 4.8kV and 7.2kV voltage classes which require interrupting ratings of 16kA and 14kA respectively and a continuous current rating of 630A. The circuit breakers are intended for use in limited applications requiring small physical size and low maintenance.
These breakers are designed for fixed panel mounting and are available with upper main circuit terminals (U, MU types) or rear terminals (L, ML types).
The breakers are available as both manual and motor-operated types. Motor-operated breakers use a motor to charge the closing springs and to close the breaker upon command. Both types can be tripped electrically and also include undervoltage release.
Fig. 1 U and MU Type Circuit Breaker (Upper
Arc interruption is accomplished inside sealed vacuum interrupters mounted on track-resistant insulators. Vacuum interrupters use low-surge contact materials which exhibit low current chopping levels reducing switching overvoltages.
Main Circuit Terminals)
Fig. 1 and Fig. 2 illustrate and identify the major components of the circuit breakers.
COMPONENTS LEGEND:
1) Manual closing handle
2) Manual trip lever
3) On-Off indicator
4) Spring charge indicator (MU and ML only)
5) Operations counter
6) Secondary control circuit terminal block
7) Main circuit terminals
8) Auxiliary switch
9) Grounding terminal
Fig. 2 L and ML Type Circuit Breaker (Rear Main Circuit Terminals)
Page 8 GENERAL DESCRIPTION
5) Operations Counter - Indicates the total
SAFETY DEVICES
Safety interlocks and guards are provided as an integral part of the equipment design. These devices are provided for safety to the operator.
accumulated number of times the circuit breaker has been closed.
DANGER
WARNING
INDICATORS AND CONTROLS (Fig. 3)
The following front panel indicators and controls are provided:
1) On-Off Indicator - Indicates if the circuit breaker is OFF (Green) or ON (Red). When the indicator reads OFF, the main contacts of the circuit breaker are open. When the indication is ON, the main contacts are closed.
2) Closing Spring Status Indicator (MU, ML types only) - Indicates if the closing springs are CHARGED (Yellow) or DISCHARGED (White).
3) Manual Closing Handle – Rotating the handle clockwise approximately 75° closes the circuit breaker (On-Off indicator changes to ON). When the handle is released, it returns to its normal position.
4) Manual Trip Lever (Red) – Pushing the lever in the direction of the arrow trips the circuit breaker (On-Off indicator changes to OFF).
Never defeat, modify or bypass any safety devices, interlocks or operating mechanism. This would make the equipment unsafe. Fire, explosion, severe injury, death and property damage could occur.
Do not operate this equipment unless all covers and panels are in place.
Fig. 3 Indicators and Controls
RECEIVING, INSPECTION AND HANDLING Page 9
RECEIVING AND UNPACKING
The circuit breaker units are subjected to factory production testing prior to being packed and shipped.
ACCEPTANCE INSPECTION
Confirm that the circuit breaker unit is complete, correct as specified and undamaged from shipment and handling.
Upon receipt of the equipment, do the following:
1) Make an immediate inspection for damage which might have occurred during shipment. If damage is discovered, it should be noted with the carrier prior to accepting the shipment, if possible.
2) Carefully unpack the equipment sufficiently to check for missing parts or concealed damage.
3) Check for the presence of accessories that are shipped with the circuit breaker:
- Closing Handle (shipped loose with MU and ML type breakers) (Fig. 4)
- Insulating cylinders (qty-6) (Fig. 5)
Fig. 4 Closing Handle
Fig. 5 Insulating Cylinder
3) Keep the circuit breaker upright.
Never lay the circuit
CAUTION
4) File a claim with the carrier for any damaged or missing items and immediately notify the nearest Toshiba representative.
WARNING
breaker on its side or upside down. This may cause damage.
Do not install or energize equipment that has been damaged. Damaged equipment can fail during operation, resulting in fire and explosion.
Page 10 RECEIVING, INSPECTION AND HANDLING
HANDLING AND MOVING
When handling and moving the circuit breaker, the techniques shown in this section may be used.
Care and caution should be used when handling the circuit breaker units to avoid damage to the equipment and personal injury. Always keep the circuit breaker in a generally upright position.
Refer to Fig. 6 and Fig. 7 for the correct methods of lifting and moving the circuit breakers.
.
Fig. 6 Correct Method for Handling the U and
MU Type Circuit Breakers
Fig. 7 Correct Method for Handling the L and
ML Type Circuit Breakers
INSTALLATION Page 11
WARNING
Do not install this equipment in areas where unusual service conditions exist. Using this equipment in other than usual service conditions can result in equipment failure.
Toshiba HV6AS circuit breakers are intended for use in usual service conditions as defined in IEEE C37.20.2. The temperature of the cooling air (ambient air temperature) surrounding the breaker should be between the limits of -5°C (23°F) and +40°C (104°F). The altitude of the equipment installation should not exceed 3300 ft (1000 m).
In particular, avoid the following installation conditions:
- Excessive dust
- Corrosive gases
- Extreme variations in temperature
- Very high or low humidity
- Vibrations
- Inclined locations
If there is a chance that condensation can occur
at the installation location, a space heater should be installed inside the circuit breaker enclosure.
NOTE: Temperature, altitude or other
conditions outside of the usual limits may require derating or other special equipment. Contact your nearest Toshiba representative for additional information.
RATING VERIFICATION
Prior to Installation, the maximum fault current capacity of the power system at the point of installation should be verified. This value must not exceed the symmetrical interrupting capability of the circuit breaker. Fig. 8 illustrates a typical circuit breaker nameplate.
Do not exceed the ratings
DANGER
specified on the circuit breaker nameplate or system accessories. Underrated equipment can fail during operation causing fire, explosion, severe injury, death, and property damage.
Fig. 8 Typical Circuit Breaker Nameplate
VACUUM CIRCUIT BREAKER
TYPE
RATED VOLTAGE FREQUENCY CONTINUOUS AMPS IMPULSE LEVEL DIELECTRIC WEIGHT
PARTS & WIRING, SEE INSTRUCTIONS SER. No.
98700221 7/98
7.2/4.8 kV, RMS
24 53
HV6AS-
50/60 Hz
630A, RMS
60 kV, CREST
22 kV AC RMS
kg
TOSHIBA INTERNATIONAL CORPORATION
TOSHIBA
MU-VV
SHORT CKT. AMPS INTERRUPTING TIME CLOSE VOLTS SHUNT TRIP VOLTS UV TRIP VOLTS
MFG. STANDARD
lbs
GF07Z301
MFG. DATE
HOUSTON, TEXAS U.S.A.
14/16 kA, RMS
3 CYCLES
120 VAC / 125
JIS C 4603-1990
JEC-2300-1985
VDC
125
VDC
120 VAC
Page 12 INSTALLATION
MOUNTING THE CIRCUIT BREAKER TO A PANEL
The circuit breakers are designed to mount to a panel made from 11 ga. (.12 in.) thick steel. If the breaker must be mounted to a panel of different thickness, contact Toshiba.
Panel cutout dimensions for the circuit breakers are given in Fig. 12. One cutout size is used for all breaker types.
To mount the circuit breaker, follow the steps below:
1. Loosen the small screw (M5) on the closing handle and remove the handle.
2. Remove the four front plate mounting bolts (M8) from the circuit breaker (Fig. 9). Remove the spacer washers between the front plate and breaker and discard them (make sure none are left inside the breaker),
Fig. 10 Align Breaker With Panel Cutout
Fig. 11 Fasten Breaker and Front Plate to
3. Align the breaker with the cutout and mounting holes on the panel to which it is to be mounted (Fig. 10). Some breakers are furnished with two hooks which may be used to temporarily attach the breaker to the panel.
4. Using the four M8 bolts removed in step 2, fasten the breaker and its front plate to the mounting panel (Fig. 11). The tightening torque should be 120-150 kgf-cm (9-11 ft-lb).
5. Replace the closing handle removed in step 1 and the M5 screw. The screw should be tightened to a torque of 40-50 kgf-cm (35-43 in-lb).
Panel
Fig. 9 Remove Front Plate and Spacer Washers
INSTALLATION Page 13
0.343 DIA 4 PLACES
8.03
0.25
10.71
0.38 RADIUS
4 PLACES
0.25
0.25
0.25
Dimensions in Inches
Fig. 12 Panel Cutout Dimensions
Page 14 INSTALLATION
MOUNTING DIRECTLY TO A SHELF
The shelf should be flat and level within ± 0.5 mm (± 0.02 in.). If there are any noticeable gaps between the breaker and the shelf, fill them in using flat washers as spacers.
Check to make sure the breaker On-Off indicator shows OFF (green), then mount it by following the steps below:
1. Fasten the breaker onto steel angles or to a flat plate (Fig. 13). Use M8 hex head bolts (either 50 mm or 35 mm). The tightening torque should be 120-150 kgf-cm (9-11 ft-lb).
2. Either mounting method shown in (Fig. 14) may be used.
Fig. 13 Mounting Breaker to Flat Plate or Angles
PANEL
ANGLE
M8 x 35MM OR M8 x 50MM BOLT
Fig. 14 Optional Hardware Orientation
INSTALLATION Page 15
Fig. 15 Pass Cable Through Insulating
MAIN CIRCUIT CABLE CONNECTIONS
Cables which connect to the circuit breaker should be routed to avoid interference with sharp edges and moving parts. Minimum bending radius for the type of cable used should be observed.
Power cables should be braced and/or laced to withstand short-circuit forces wherever such cables are unsupported. Power cables should be adequately sized to carry the maximum continuous current in accordance with NEC requirements and should have an adequate voltage rating. Cables should be dressed and terminated as appropriate to the voltage class and cable manufacturer’s recommendations. When terminating shielded cables, use termination kits appropriate for the system voltage to taper the insulation and reduce electrical stress. Follow the manufacturer’s installation instructions provided with the termination kit.
Cylinder Fig. 16 Fasten Cable to Main Circuit
To connect cables, follow the steps below:
1. Pass the cable through the insulating cylinder (six cylinders are supplied with the circuit breaker) (Fig. 15).
2. Fasten the cable to the main circuit terminal (Fig. 16). Use 35 mm Class 8.8 M10 or M12 hex head bolts, 2 flat washers, a lock washer and a nut. While securely preventing the bolt from rotating with a wrench, torque the nut to 250-315 kgf-cm (18-23 ft-lb) for M10 bolts or 450-565 kgf-cm (32-41 ft-lb) for M12 bolts.
Use two wrenches to torque
CAUTION
3. Fasten the insulating cylinder in place, then check to make sure that the hook is engaged (Fig. 17).
the connection to prevent applying excessive force to the terminal which can damage the frame.
Terminal
Fig. 17 Fasten Insulating Cylinder
Page 16 INSTALLATION
GROUND CONNECTIONS
The circuit breaker must be grounded in accordance with the requirements of the National Electrical Code, Article 250 or applicable local standards.
WARNING
It is very important that the circuit breaker and its enclosure be adequately grounded to protect the operator from injury in the event of short circuits or other abnormal occurences and to ensure that the metal parts of the equipment, other than live parts, remain at ground potential.
For U and MU type circuit breakers, the ground terminal is on the left side of the operating mechanism as viewed from the rear of the breaker. To make the ground connection, first remove the fastening M6 hex head bolt and crimp-on terminal (provided with the breaker) and crimp the terminal to the end of the ground wire (Fig. 18). Then, reattach the terminal using the same bolt previously removed and torque to 50-65 kgf-cm (43-56 in-lb).
Proper grounding connections must be made to the circuit breaker before incoming power is applied.
Fig. 18 Ground Connection for U and MU Type Breakers
Fig. 19 Ground Connection for L and ML Type Breakers
For L and ML type circuit breakers, the ground terminal is on the left side of the terminal block as viewed from the rear of the breaker (Fig. 19). The same instructions as for the U and MU breaker above should be followed to attach the ground wire.
INSTALLATION Page 17
Fig. 20 Connection to Control Terminal
CONTROL CIRCUIT CONNECTIONS
Control circuit wiring is connected to the terminal block on the top of the operating mechanism (Fig. 20). Connect control wires in accordance with the appropriate wiring diagram shown in Fig. 28 through Fig. 31 in the OPERATION section of this manual.
On the U and MU type breakers, connections to auxiliary contacts are made directly to the auxiliary switch (Fig. 21).
On the L and ML type breakers, connections to auxiliary contacts are made to a terminal block on top of the operating mechanism (Fig. 22).
ADDITIONAL AUXILIARY SWITCH (Optional)
An optional second auxiliary switch may be furnished, located on the right side as viewed from the rear of the breaker.
Block Fig. 21 Auxiliary Contact Connections on U
When a second auxiliary switch is furnished, control wires are connected directly to the switch.
and MU Type Breakers Fig. 22 Auxiliary Contact Connections on L
and ML Type Breakers
Page 18 PRE-ENERGIZATION CHECK
ELECTRICAL CHECKS
GENERAL
Electrical shock hazard.
BEFORE ENERGIZING THE CIRCUIT BREAKER for the first time, follow the procedure
below to verify that the equipment is properly installed and functional.
DANGER
Hazardous Voltage. Turn off and lock out all primary and control circuit power sources prior to performing this pre-energization check.
WARNING
An electrical insulation resistance test should be performed to verify that the circuit breaker and associated field wiring are free from short circuits and grounds. Refer to the MAINTENANCE Section of this manual for additional information.
Do not touch energized components during a test using auxiliary power.
WARNING
WARNING
WARNING
WARNING
All blocks or other temporary braces used for shipment must be removed.
Before closing the enclosure, all metal chips, scrap wire and other debris left over from installation must be cleaned out.
Do not operate this equipment until a complete safety inspection has been made.
Do not energize damaged equipment that has not been repaired or verified.
Do not remove, cover or destroy any safety signs.
Do not operate this equipment until all panels and covers have been installed.
Hazardous voltages are
WARNING
The circuit breaker must be set to the OFF position before energizing incoming power.
present during dielectric testing which can result in serious injury or death. High potential tests should be performed only by qualified personnel.
Cover all unused openings. Install all panels, guards and covers.
A supply of spare parts should be established.
Instruction manuals and diagrams should be collected and filed.
OPERATION Page 19
MANUAL OPERATION
WARNING
CAUTION
MANUAL CLOSING (Motor-Operated MU and ML Types):
1. Check to make sure that the On-Off indicator shows OFF (green).
2. Attach the closing handle to the breaker if it is not already attached.
3. If the closing spring status indicator shows DISCHARGED (white):
Powerful springs. Do not place your hands or any part of your body inside the circuit breaker while the indicators show CHARGED (yellow) or ON (red).
To avoid damaging the mechanism, do not close the circuit breaker when the On-Off Indicator shows ON (red).
Fig. 23 Preparing to Manually Close Breaker
Fig. 24 Manually Closing Breaker
Turn the closing handle clockwise (Fig. 23). The breaker will close (On-Off indicator changes to ON) after the handle is turned approximately 75° (Fig. 24).
NOTE If the handle is turned in small
increments, the closing spring will store the energy from the handle action and the circuit breaker will close before 75° of rotation.
If the closing spring status indicator shows CHARGED (yellow):
Turn the closing handle clockwise. The breaker will close after the handle is turned approximately 10°.
4. Release the handle, and it will return to its initial position.
Page 20 OPERATION
Fig. 25 Manually Opening Breaker
MANUAL CLOSING (Manual Spring-Operated U and L Types):
1. Check to make sure that the On-Off indicator shows OFF (green).
2. Turn the closing handle clockwise. The breaker will close (On-Off indicator changes to ON) after the handle is turned approximately 75°.
NOTE If the handle is turned in small
increments, the closing spring will store the energy from the handle action and the circuit breaker will close before 75° of rotation.
3. Release the handle, and it will return to its initial position.
SYMBOL DESCRIPTION
MANUAL OPENING (All Types):
1. Push the trip lever in the direction of the arrow (Fig. 25).
2. The On-Off indicator changes to OFF (green).
ELECTRICAL OPERATION
The flow chart shown in Fig. 27 illustrates the sequence of electrical operation of the MU and ML type circuit breakers.
Refer to Fig. 26 and the circuit breaker schematics shown in Fig. 28 through Fig. 31 for determining external control circuit connections to the circuit breaker.
M Motor TC Voltage Trip Coil UV Undervoltage Trip Coil
a1 to a6 Auxiliary Contacts (N.O.) b1 to b6 Auxiliary Contacts (N.C.)
X Control Relay X-a Control Relay Contact (N.O.) X-b Control Relay Contact (N.C.)
Y Auxiliary Relay Y-a Auxiliary Relay Contact (N.O.) Y-b Auxiliary Relay Contact (N.C.)
LS1 to LS3 Limit Switches
R1 to R4 Resistors
REC Rectifier
D Diode
C Capacitor SP Surge Protector RL Red Lamp GL Green Lamp
Fig. 26 Legend for Schematics
OPERATION Page 21
Circuit Breaker Open
Control Power Applied
Motor Begins Operating
Closing Springs Begin Charging
Closing Springs Charged
Motor Stops
Closing Signal Given
Motor Begins Operating
Circuit Breaker Closes
Auxiliary Relay Closes
Anti-Pumping Circuit Completed
Opening Signal Given
- - - - Spring Status Indicator Changes to Yellow
- - - - Standby for Close Operation
- - - - Spring Status Indicator Changes to White and On-Off Status Changes to ON
- - - - Next Close Operation is Not Possible Unless Close Signal is Canceled
Trip Coil Energized
Circuit Breaker Opens
Fig. 27 Electrical Operation Flow Chart for MU and ML Type Breakers
- - - - On-Off Status Indicator Changes to OFF
Page 22 OPERATION
(
)
(
)
+
OFF
C4 K 1514 1312 11 16 15 14 13 12 11
Circuit Breaker Components Shown Inside Box
125 VDC SUPPLY
-
120 VAC SUPPLY
TCUV
C04 N2
C04C4N2K
Terminal Layout
As Viewed From Front of Circuit Breaker
a3 a2 a1 b3 b2 b1 a6 b5a4a5 b6 b4
25 24 23 22 21 26 2425 2223 21
RL GL
Fig. 28 125 VDC Control Circuit Schematic for U Type Circuit Breaker
Fig. 29 125 VDC Control Circuit Schematic for L Type Circuit Breaker
+
OFF
C4 K
A2 A1 B2 B1
Optional Auxiliary Contacts
Circuit Breaker Components Shown Inside Box
16 15 14 13 12 11
125 VDC SUPPLY
120 VAC
SUPPLY
-
Terminal La yout
As Viewed From Front of Circuit Breaker
TCUV
C04 N2
C04C4N2K
a3 a2 a1 b2 b1 b6 a5b4b5 a6 a4
A02 A01 B02 B01
RL GL
A01A1 A2 A02 B1 B01
26 2425 2223 21
Optional Auxiliary Contacts
B2 B02
OPERATION Page 23
Y
YR3Y-aY
Fig. 30 125 VDC Control Circuit Schematic for MU Type Circuit Breaker
+
Fig. 31 125 VDC Control Circuit Schematic for ML Type Circuit Breaker
ON
OFF
Circuit Breaker Components Shown Inside Box
125 VDC
SUPPLY
-
120 VAC
SUPPLY
C4 K 1514 131211 161514131211
C04 N2
PR3
SP
REC
X-a
LS2
M
LS3 LS3
NT3
Components Inside Dashed Box Located On Control Circuit Board
Terminal Layout (As Viewed From Front of Circuit Breaker)
X-a
X-b
R1 X-a
HPR3 NT3
H
D
-b
-bCR4
R2
X
C04C4N2K
a3 a2 a1 b3 b2 b1 a6 b5a4a5 b6 b4
LS1
TCUV
25 24 23 22 21 26 2425 2223 21
RL GL
Optional Auxiliary Contacts
(Connect Wires Directly To Auxiliary Switch Terminals)
+
125 VDC
SUPPLY
-
120 VAC
SUPPLY
ON
C4 K A2A1 B2B1 161514131211
NT3
C04 N2
PR3
SP
REC
X-a
LS2
M
LS3 LS3
Components Inside Dashed Box Located On Control Circuit Board
Terminal Layout (As Viewed From Front of Circuit Breaker)
X-a
X-b
X-a
R1
HPR3 NT3
H
D
Y-b
R2
X Y
Y-a
Y-bCR4
R3
OFF
a3 a2 a1 b2 b1 b6 a5b4b5 a6 a4
LS1
TCUV
A02 A01 B02 B01 26 2425 2223 21
RL GL
A1
C04C4N2K
A01
A2 B1
A02 B01
Circuit Breaker Components Shown Inside Box
Optional Auxiliary Contacts
(Connect Wires Directly To Auxiliary Switch Terminals)
B2
B02
Page 24 OPERATION
UNDERVOLTAGE TRIP
All HV6AS fixed mounted circuit breakers are furnished with an undervoltage trip device. The undervoltage trip device operates to trip the circuit breaker OFF unless 120VAC control power is present at the terminals of relay UV.
When the circuit breakers are shipped, the undervoltage trip device is defeated by a factory­installed plug (Fig. 32). If this plug is left in place, the circuit breaker will operate normally without power applied to relay UV. Removing this plug (Fig. 33) activates the undervoltage trip function.
Fig. 33 Removing Plug From UV Trip Device
Fig. 32 Plug Installed in UV Trip Device
MAINTENANCE Page 25
6) Comments
MAINTENANCE PROGRAM
The degree of detail of the record will depend In order to ensure continued reliable and safe operation of the equipment, a program of periodic maintenance must be established. Operating and environmental conditions will usually dictate the frequency of inspection required. NFPA Publication 70B "Electrical Equipment Maintenance" may be used as a guide for setting up the maintenance program.
somewhat on the operating conditions.
SERVICING EQUIPMENT
For your safety, turn off and lock out main and
control circuit power before servicing the circuit
breaker. Certain minimum safety procedures
must be followed:
DANGER
WARNING
WARNING
Contact with energized components can cause severe injury, death and property damage. Turn off and lock-out primary and control circuit power before servicing.
Improper maintenance can cause severe injury, death and property damage. Only qualified and authorized persons are to install, operate or service this equipment.
Grease is conductive. Do not allow grease or any other substances to contaminate insulating materials. Contaminated insulators can allow a short-circuit or ground fault to occur.
1) Only qualified personnel should attempt this service.
2) Never perform service on or next to exposed components energized with line voltage.
Failure to adhere to these safety procedures can
WARNING
result in severe injury, death and property damage.
NOTE: Refer to the SAFETY section of this
manual for important information.
MAINTENANCE RECORD
Keep a permanent record of all maintenance work. At a minimum, this record should include information on:
1) Items inspected
2) Reports of any testing
3) Equipment condition
4) Corrective actions or adjustments
5) Date of work
Page 26 MAINTENANCE
RECOMMENDED INSPECTION AND MAINTENANCE TYPES
NOTE: Refer to the SAFETY section of this
manual for important information.
A. Acceptance Inspection
This inspection confirms that the circuit breaker unit is complete, correct as specified, and undamaged from shipment. The procedure for this inspection is outlined in the RECEIVING, INSPECTION AND HANDLING section of this manual.
B. Patrol Inspection
Inspection is made of the condition of the circuit breaker while it is energized. Check that no unusual sounds or smells exist externally.
Inspection Frequency: Once every 6 months
C. Periodic Inspection
Screw
Nominal
Dia.
M4 15-20 kgf-cm
13-17 in-lb
M5 30-40 kgf-cm ()
26-34 in-lb
M6 50-65 kgf-cm ()
43-56 in-lb
M8 120-150 kgf-cm ()
9-11 ft-lb
M10 250-315 kgf-cm ()
18-23 ft-lb
M12 450-565 kgf-cm ()
32-41 ft-lb
Tightening Torque
Inspection is performed wth the circuit breaker de-energized. The lubrication of sliding and rotating parts is checked and the mechanism is lubricated if needed.
Inspection Frequency: Once every 1-3 years or every 3000 operations (normal). Once every 6 years (detailed).
Refer to Table 2 for the schedule of Periodic Inspections.
D. Unscheduled Inspection
Inspections are implemented as required.
Inspection Frequency: As needed
NOTE: The inspection frequency and points
to be inspected may vary from the above recommendations depending on the status of use, frequency of switching, amount of current interrupted and other factors.
Table 1 Tightening Torques
MAINTENANCE Page 27
Table 2 Check Points for Periodic Inspection
Check Point Check Item Check Method Criteria Disposition
Operating Mechanism
Loose bolts, nuts or screws
Dust or foreign matter inside
Indicator operation
Warpage Visual
Smooth operation
Tighten using screwdriver or wrench.
Visual inspection.
Visual inspection.
inspection.
Manual operation. Visual inspection or touch. Check lubrication.
Make sure all bolts, nuts and screws are tight.
The circuit breaker should be clean and contain no foreign matter.
Make sure the number of operations is correctly displayed.
There should be no warpage or missing parts.
Make sure moving parts operate smoothly.
Tighten if loose. See Table 1 for tightening torques.
Wipe with a clean dry cloth.
Check the cause and repair.
Check the cause and repair.
Apply a small amount of lubrication.
Main Circuit Discoloration
due to heat from conducting parts
Loose bolts, nuts or screws
Dust on surface of vacuum interrupter
Insulator Dust, foreign
matter or damage
Visual inspection.
Tighten using a wrench.
Visual inspection.
Visual inspection.
Make sure there is no discoloration.
Make sure all bolts, nuts and screws are tight.
Make sure there is no dust on the surface.
Make sure there is no dust, foreign matter or breakage.
Check the cause and repair. Tighten connections to circuit breaker. See Table 1 for tightening torques.
See Table 1 for tightening torques.
Wipe with a clean, dry cloth.
Wipe with a clean, dry cloth. If damaged, contact Toshiba.
Page 28 MAINTENANCE
Table 2. Check Points for Inspection (cont’d)
Check Point Check Item Check Method Criteria What to do
Auxiliary Switch
Control Circuits
Insulation Resistance Measure­ment
Terminals loose or disconnected
Case/contacts Visual
Smooth movement of motor charging mechanism
Terminals loose or disconnected
Meaure main circuit to ground
Meaure between main circuit terminals
Visual inspection. Tighten using a screwdriver.
inspection.
Energize the control circuit.
Visual inspection. Tighten using a screwdriver.
Megger test at 1000V.
Megger test at 1000V.
Make sure terminals are not loose or disconnected.
Make sure there is no damage or warping.
Breaker (motor-operated type) should charge quickly and smoothly.
Make sure terminals are not loose or disconnected.
Resistance should be 500M or greater.
Resistance should be 100M or greater.
Repair if disconnected. Tighten if loose. See Table 1 for tightening torques.
Replace if damaged or warped.
If the circuit fails to operate, check the cause and repair.
Repair if disconnected. Tighten if loose. See Table 1 for tightening torques.
If the insulation resistance is low, wipe off the vacuum interrupter and other insulation surfaces with a clean dry cloth and then repeat the test.
Meaure control circuits to ground
Megger test at 500V.
Resistance should be 2M or greater.
MAINTENANCE Page 29
Hazardous voltages are
VACUUM CHECK
A sufficient level of vacuum is necessary for proper performance of the vacuum interrupters. Although vacuum leaks are rare, the vacuum integrity should be checked periodically. The relationship between dielectric breakdown voltage of the contact gap and internal vacuum interrupter pressure has been found to be generally predictable. Therefore, vacuum interrupter integrity is checked by performing a high potential test across the open gap of the interrupter.
TEST EQUIPMENT:
Toshiba offers a compact vacuum checker (Type CI35-1D) which enables a quick and easy check on vacuum interrupter internal pressure. Alternatively, any commercially available AC high potential tester may be used which is capable of delivering at least 25 milliamperes at 22 kV for a period of one minute.
PRECAUTIONS:
Applying abnormally high voltage across a pair of contacts in vacuum may produce X-rays. The radiation may increase with the increase in voltage and/or decrease in contact spacing. X­radiation produced during this test with recommended voltage and normal contact spacing is extremely low and well below the maximum permitted by standards. As an additional safety measure, however, it is recommended that all personnel keep at least 1 meter (3.3 ft) away from the vacuum circuit breaker while this test is performed.
WARNING
TEST PROCEDURE:
1. The circuit breaker should be disconnected from the main circuit and be in the OFF position.
2. Connect all the line side primary terminals together and to the output of the vacuum checker or AC hi-pot machine. Connect all the load side primary terminals together and to the ground terminal of the vacuum checker or AC hi-pot machine.
3. Increase the voltage from zero to 22kV AC at a rate of approximately 2kV per second. Hold the voltage at this value for 1 minute and observe the current drawn by the interrupter.
4. Decrease the voltage back to zero.
Fig. 34 Toshiba Portable Vacuum Checker
present during dielectric testing which can result in severe injury or death. Only qualified personnel should conduct this testing.
WARNING
Radiation exposure hazard. X-rays may cause illness or injury. Stay at least 1 meter (3.3 ft) away from the circuit breaker during the vacuum check test .
Page 30 MAINTENANCE
CRITERIA:
Fig. 35 Application of Test Voltage for
1. If a current flow above 5 milliamperes is observed or if breakdown occurs, one or more of the interrupters has insufficient vacuum and must be replaced.
Exception: If the current exceeds 5 milliamperes the first time the voltage is brought up, reduce the voltage to zero and increase it again. It may be necessary to repeat this procedure a few times.
2. If the breaker fails to meet criteria 1, then repeat the test on each pole separately to identify the damaged interrupter or interrupters.
3. If the voltage can be held for 1 minute and the current flow does not exceed 5 milliamperes, the interrupter has a sufficient vacuum level.
Vacuum Check
1 minute 22kV AC (31kV DC)
Voltage
Zero
15 sec 15 sec
Time
After the test is complete, discharge any residual static charge from the primary terminals of the circuit breaker.
If a vacuum checker or AC hi-pot tester is not available, a DC hi potential test may be conducted. If a DC test is conducted, the test voltage must be increased to 31kV DC. The test duration for DC tests and the criteria for acceptance remain the same as for AC tests.
Do not use DC hi-pot
WARNING
testers which employ unfiltered half-wave rectifiers. The peak voltages produced by these testers may exceed the recommended value of 31kV. This can result in the production of harmful X­rays and may invalidate the test results.
DISPOSAL Page 31
DISPOSAL
Contact your state environmental agency for details on disposal of electrical components and packaging in your particular area.
STORAGE Page 32
STORAGE
If the circuit breaker is to be stored for any length of time prior to installation, the following precautions should be taken:
1) The original packing should be restored, if possible.
2) Do not subject the equipment to moisture or sun rays. Store in cool, clean, and dry location.
3) Place a dust cover over the circuit breaker packaging to protect against dirt and moisture.
4) Store in an upright position.
INSPECTION DURING STORAGE
Routine scheduled inspection is necessary if storage is for an extended period. The unit should be checked for condensation, moisture, corrosion, and vermin.
Prior to installation, the circuit breaker should be carefully examined for evidence of physical damage, corrosion, or other deterioration. Refer to the PRE-ENERGIZATION Section of this manual.
The MAINTENANCE section of this manual describes various types of inspections recommended for this circuit breaker during the operation period.
SPECIFICATIONS Page 33
Table 3 Circuit Breaker Ratings – Manual Operation HV6AS-U and HV6AS-L Types
Rated Voltage kV, rms 7.2 4.8
Rated Low Frequency Withstand Voltage kV, rms 22
Impulse Withstand Voltage kV, crest 60
Rated Continuous Current A, rms 630
Rated Frequency Hz 50/60
Rated Short-Circuit Breaking Current kA, rms 14 16
Rated Short-Circuit Making Current kA, crest 35 40
Rated Short-Time Withstand Current (2 sec) kA, rms 12.5
Rated Interrupting Time (60Hz Basis) cycles 3
Opening Time msec 8 - 25
Rated Control Voltage (Opening) V DC 30, 125
Rated Control Voltage (Undervoltage Trip) V AC 120
Operating Duty O - 1 min - CO - 3 min - CO
Auxiliary Contacts 2 N.O. - 2 N.C.
Weight kg 22 (U Type) 25 (L Type)
Table 4 Circuit Breaker Ratings – Motor Stored Energy Operation HV6AS-MU and HV6AS-ML Types
Rated Voltage kV, rms 7.2 4.8
Rated Low Frequency Withstand Voltage kV, rms 22
Impulse Withstand Voltage kV, crest 60
Rated Continuous Current A, rms 630
Rated Frequency Hz 50/60
Rated Short-Circuit Breaking Current kA, rms 14 16
Rated Short-Circuit Making Current kA, crest 35 40
Rated Short-Time Withstand Current (2 sec) kA, rms 12.5
Rated Interrupting Time (60Hz Basis) cycles 3
Opening Time msec 8 - 25
Closing Time msec 150 - 300
Charging Time sec 1.5 - 3
Rated Control Voltage (Closing/Charging) V AC 120, DC 125
Rated Control Voltage (Opening) V DC 30, 125
Rated Control Voltage (Undervoltage Trip) V AC 120
Operating Duty O - 1 min - CO - 3 min - CO
Auxiliary Contacts 2 N.O. - 2 N.C.
Weight kg 24 (MU Type) 27 (ML Type)
Page 34 WARRANTY AND LIMITATION OF LIABILITY
Toshiba International Corporation ("Company") warrants that all equipment and parts described herein will be free from defects in materials and workmanship. THIS WARRANTY WILL EXPIRE EIGHTEEN (18) MONTHS AFTER THE DATE ON WHICH SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED PURSUANT TO THIS WARRANTY) ARE SHIPPED BY THE COMPANY TO THE INITIAL PURCHASER OR TWELVE (12) MONTHS AFTER SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED PURSUANT TO THIS WARRANTY) ARE FIRST PLACED IN OPERATION, WHICHEVER PERIOD FIRST EXPIRES.
The Company will, at its option, repair or replace such equipment or part which is defective under the terms of the foregoing warranty, free of charge; provided the purchaser (1) promptly notifies the Company in writing of such defect, and (2) furnishes the Company satisfactory proof thereof, and (3) establishes that the equipment or part has been properly installed, maintained and operated within the limits of rated capacity and normal usage and in accordance with this manual, and (4) if requested by the Company, returns the defective equipment or part to the Company and pays all expenses incurred in connection with such return. The repaired or replacement equipment or part will be delivered, free of charge, to the purchaser F.O.B. the Company's warehouse or, at the Company's option, F.O.B. a Company authorized service shop, not loaded on truck or other carrier. The purchaser will pay the costs applicable to the equipment or part following such delivery, including, without limitation, all handling, transportation, assembly, insurance, testing and inspection charges.
THE FOREGOING OBLIGATION TO REPAIR OR REPLACE EQUIPMENT PARTS SHALL BE THE SOLE AND EXCLUSIVE REMEDY OF THE PURCHASER, ITS CUSTOMERS AND USERS OF THE EQUIPMENT AND PARTS FOR BREACH OF THE FOREGOING WARRANTY. THE COMPANY WILL HAVE NO OBLIGATIONS TO DISASSEMBLE ANY EQUIPMENT OR PART WHICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE WARRANTY OR TO INSTALL ANY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY COSTS INCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION. THE COMPANY, TOSHIBA CORPORATION AND THEIR SUPPLIERS AND SUBCONTRACTORS HEREBY DISCLAIM ALL OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, ALL EQUIPMENT AND PARTS FURNISHED PURSUANT TO THE FOREGOING WARRANTY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY.
The total liability of the Company, Toshiba Corporation and their suppliers and subcontractors for any loss, damage or claim, whether in contact, tort (including negligence and liability without fault), or otherwise, arising out of, connected with or resulting from the equipment and parts described in this manual or the performance or breach of any contract for the sale or supply of such equipment and parts, or from the design, manufacture, sale, delivery, resale, installation, technical direction or supervision of installation, inspection, testing, repair, replacement, operation, maintenance or use of any such equipment or part or any service relating thereto furnished by the Company shall not in any event exceed the price allocable to the equipment, part or service which gives claim, loss or damage. In no event, whether as a breach of contract or warranty, alleged negligence, liability without fault, or otherwise, shall the Company, Toshiba Corporation or their suppliers or subcontractors be liable for special or consequential damages, including, without limitation, loss or profits or revenue, loss of equipment described herein or any associated equipment, cost of capital, cost of substitute equipment or parts, facilities or services, down-time costs, labor costs or claims of customers of the purchaser for such damages.
TOSHIBA
TOSHIBA INTERNATIONAL CORPORATION
13131 W. Little York Road, Houston, TX 77041, U.S.A. Tel: (713) 466-0277Fax: (713) 466-8773
Loading...