VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS
P/N 700,005M REV. X 11/2004
MODELS
This appliance may be installed in an aftermarket permanently located, manufactured home
(USA only) or mobile home, where not prohibited by local codes. This appliance is only for
use with the type of gas indicated on the rating
plate. This appliance is not convertible for use
with other gases, unless a certified kit is used.
WARNING: IF THE INFORMATION IN THIS MANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapors or liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• If your gas supplier cannot be reached, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE
LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE
BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser
d'essence ni d'autre vapeurs ou liquides inflammables
dans le voisinage de cet appareil ou de tout autre
appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une
odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où
vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service dos incendies.
OTL Report No. 116-F-13-4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
L'installation et service doit être exécuté par un qualifié
installeur, agence de service ou le fournisseur de gaz.
This installation manual will help you obtain a
safe, efficient, dependable installation for your
appliance and vent system.
Please read and understand these
instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace heater is
packaged with:
1 -one log set located in firebox area.
2 -one envelope containing the literature
package which consists of the homeowner's
manual, installation instructions, log set
supplement and warranty; envelope is located in the control area.
3 - one vent restrictor to be applied as shown on
page 9; restrictor is taped to the envelope.
4 -one hood located behind the top panel.
5 -one bag of decorative volcanic stone lo-
cated in the control area.
6 -one bag of glowing embers located in the
control area.
INTRODUCTION
These vented gas fireplace heaters are sealed
combustion, air circulating gas fireplaces designed for residential applications. These appliances must be installed with the SecureVent™ and /or Secure Flex™vent systems
routed to the outside atmosphere.
Millivolt appliances are designed to operate on
natural or propane gas. A millivolt gas control
valve with piezo ignition system provides safe,
efficient operation. External electrical power is
required to operate the optional blower if installed in these units.
Electronic appliances are designed to operate
on natural or propane gas. An electronic intermittent pilot ignition system provides safe,
efficient operation. External electrical power is
required to operate these units.
These appliances comply with National Safety
Standards and are tested and listed by OmniTest Laboratories (Report No. 116-F-13-4) to
ANSI Z21.88-2002 (in Canada, CSA-2.33-2002),
and CAN/CGA-2.17-M91 in both USA and
Canada, as vented gas fireplace heaters.
Both millivolt and electronic versions of
these appliances are listed by Omni-Test
Laboratories for installation in bedrooms
and mobile homes.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appliance should be inspected annually by a qualified professional service technician. More frequent inspections and cleanings may be required due to excessive lint from carpeting,
bedding material, etc. It is imperative that the
control compartment, burners and circulating
air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment
des commandes sont propres. Voir les instructions d'installation et d'utilisation qui
accompagnent l'appareil.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front openings of the appliance.
These appliances are designed to operate on
natural or propane gas only.
TYPICAL INSTALLATION
Installation must conform to local codes. In the
absence of local codes, installation must comply with the current National Fuel Gas Code,
ANSI Z223.1. (In Canada, the current CAN-1
B149 installation code.) Electrical wiring must
comply with the National Electrical Code ANSI/
NFPA 70 - (latest edition). (In Canada, the
current CSA C22-1 Canadian Electrical Code.)
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 1
Millivolt Models -
Millivolt models come standard with the
manually-modulated gas valve; flame appearance and heat output can be controlled at the gas valve.
Input of millivolt models is shown in the
following table:
htiwsledoMtlovilliM
saGlarutaNsaGenaporP
,TD,D
RD
seireS
005
006
008
etartupnI
RD
)H/UTB(
ot005,71
000,32
000,92
000,23
005
ot005,12
006
ot000,42
008
evlaVsaGdetaludoM-yllaunaM
,TD,D
seireS
etartupnI
)H/UTB(
ot005,71
000,32
ot005,22
000,92
ot005,52
000,23
Electronic Models -
Electronic models have a fixed rate gas valve.
Input of electronic models is shown in the
following table:
evlaVsaGetaR-dexiFhtiwsledoMcinortcelE
saGenaporPdnalarutaN
seireSRD,TD,D)H/UTB(etartupnI
005000,32
006000,92
008000,23
All Models -
Maximum manifold pressure is 3.5 in. w.c.
(0.87 kPa) for natural gas and 10 in. w.c.
(2.49 kPa) for LP/Propane gas.
Installations at Altitudes of 0 to 4500 ft.Units are tested and approved for elevations
of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.For elevations above 4500 feet (1372
meters), install the unit according to the
regulations of the local authorities having
jurisdiction and, in the USA, the latest edition
of the National Fuel Gas Code (ANSI Z223.1)
or, in Canada, the latest edition of the
CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
,TD,D
RD
seireS
005.ni090.045#
00663#25#
00833#.ni560.0
.taN.porP
ezisecifirO
noitavelE
teeF
)sretem(
0054-0
)0731-0(
Table 1
The millivolt appliances are manually controlled
and feature a spark ignitor (piezo) that allows the
appliance's pilot gas to be lit without the use of
matches or batteries. This system provides
continued service in the event of a power outage.
Do not use these appliances if any part has
been under water. Immediately call a qualified, professional service technician to inspect
the appliance and to replace any parts of the
control system and any gas control which
have been under water.
Ne pas se servir de cet appareil s'il a été plongé
dans l'eau, complètement ou en partie. Appeler
un technicien qualifié pour inspecter l'appareil et
remplacer toute partie du système de contrôle et
toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home,
where not prohibited by local codes. This
appliance is only for use with the type of
gas indicated on the rating plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison
préfabriquée (É.-U. seulement) ou mobile
déjà installée à demeure si les réglements
locaux le permettent.
Cet appareil doit être utilisé uniquement avec
les types de gaz indiqués sur la plaque
signalétique. Ne pas l'utiliser avec d'autres gaz
sauf si un kit de conversion certifié est installé.
Test gage connections are provided on the
front of the millivolt gas control valve (identified IN for the inlet and OUT for the manifold side). A ¹⁄₈" NPT test gage connection is
provided at the inlet and outlet side of
the electronic gas control valve.
Minimum inlet gas pressure to these appliances
is 5.0 inches water column (1.24 kPa) for natural
gas and 11 inches water column (2.74 kPa) for
propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to these
appliances is 10.5 inches water column (2.61
kPa) for natural gas and 13.0 inches water
column (3.23 kPa) for propane.
These appliances must be isolated from the gas
supply piping system (by closing their individual
manual shut-off valve) during any pressure testing of the gas supply piping system at test
pressures equal to or less than ¹⁄₂ psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure testing of that system at pressures in excess of ¹⁄₂
psig (3.5 kPa).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air
immediately. Turn off the gas supply to the
appliance and have it serviced by a qualified
professional, as it may not be operating
correctly.
WARNING: FAILURE TO COMPLY WITH
THE INSTALLATION AND OPERATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OPERATING APPLIANCE, VOIDING ITS WARRANTY. ANY
CHANGE TO THIS APPLIANCE AND/OR
ITS OPERATING CONTROLS IS DANGEROUS. IMPROPER INSTALLATION OR USE
OF THIS APPLIANCE CAN CAUSE SERIOUS INJURY OR DEATH FROM FIRE,
BURNS, EXPLOSION OR CARBON MONOXIDE POISONING.
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES. USE
CAUTION AROUND THE APPLIANCE TO
AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN
THE SAME ROOM AS THE APPLIANCE.
WARNING: DO NOT PLACE CLOTHING
OR OTHER FLAMMABLE MATERIALS
ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDES À VAPEUR INFLAMMABLES
À COTE DE L'APPAREIL.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns.
However, vent system routing to the exterior and
access to the fuel supply are also important.
Consideration should be given to traffic ways,
furniture, draperies, etc., due to elevated surface
temperatures (
see Figure 2
).
3
REAR VENT
APPLICATION
TOP VENT
APPLICATION
APPLICATION
TOP VENT
INSTALLATION
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
Figure 2
The location should also be free of electrical,
plumbing or other heating/air conditioning ducting. These direct vent appliances are uniquely
suited for installations requiring a utility shelf
positioned directly above the fireplace. Utility
shelves like these are commonly used for locating television sets and decorative plants.
To provide for the lowest possible shelf surface
use the alternate rear vent outlet with attached
venting routed in a way to minimize obstructions
to the use of the space above the appliance. Do
not insulate the space between the appliance
and the area above it. See
minimum height from the base of the appliance
to the underside of combustible materials used
to construct a utility shelf in this fashion is shown
in the table in
Figure 3
.
Figure 3
. The
VERTICAL VENT
(Rear Vent
Application)
Typical Locations
HORIZONTAL VENT
(Rear Vent Application
without a chase)
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a
metal or wood barrier covering the entire bottom surface must be used.
APPLIANCE AND VENT CLEARANCES
These appliances are approved with zero clearance from spacers to combustible materials on
all sides (as detailed in
following exception: When the unit is installed
with one side flush with a perpendictular side
wall, the wall perpendicular to the opposite side
of the appliance front face must not extend
more than five inches beyond the front edge of
the unit. In addition, when the unit is recessed,
the side walls surrounding the unit must not
extend more than five inches beyond the front
edge of the unit. Refer to
Table 2
Figure 2
), with the
.
Figure 3
Table 2
Shelf Height
(
see table)
Shelf Above Fireplace With Rear Venting
KCAB
SEDIS
)mm31(.ni2/1
**)mm31(.ni2/1
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
fomottoBmorF
gnilieCottinU
)mm6261(.ni46
TNEV*)mm4.52(.ni1
SECNARAELCECIVRES
TNORF)sretem9.0(.teeF3
Shelf Height
see table)
(
Shelf Above Fireplace With Top Venting
*Note: 3 in. (75 mm) above any horizontal/
srecaps)mm0(.ni0
inclined vent component.
srecaps)mm0(.ni0
**Note: The nailing flange and the cabinet
surfaces directly adjacent to the framing member attached to the nailing flange, are exempt
from the 1/2" clearance to combustibles defined for the rest of the cabinet sides and back.
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building
components according to
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
figure 4
2 FT
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum
Clearance to Combustibles
Terminate multiple vent terminations according to the installation codes listed at the top of
this page.
Horizontal Vent Termination Clearances
The horizontal vent termination must have a
minimum of 3" (76 mm) clearance to any
overhead combustible projection of 2 ¹⁄₂" (64
mm) or less. See
exceeding 2 ¹⁄₂" (64 mm), see
Figure 5.
For projections
Figure 5
. For
additional vent location restrictions refer to
Figure 8 on page 6
.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows,
however, each installation is unique resulting in
variations to those described.
See the page numbers references in the following steps for detailed procedures.
Step 1. (page 5) Construct the appliance framing. Position the appliance within the framing
and secure with nailing brackets.
Step 2. (page 5) Route gas supply line to
appliance location.
Horizontal Vent Termination Clearances
Combustible Projection
2¹⁄₂ inches or less in length
Combustible Projection
greater than 2¹⁄₂ inches in length
Ventilated
Soffit
Unventilated
Soffit
3"
18"
(457 mm)
Note - See
ances, into exterior walls, of the round, square and
small square horizontal terminations.
12"
(305 mm)
Figure 34 on page 16
Figure 5
(76 mm)
Termination Kit
for the recess allow-
Side Elevation View
Step 3. (page 9) Install the vent system and
exterior termination.
Step 4. (page 21) Field Wiring
a. Millivolt Appliances – Install the operating
control switch (not factory provided) and bring
in electrical service line for forced air circulating
blower (optional equipment).
b. Electronic Appliances – Field wire and install
operating control switch.
Step 5. (page 21) Install blower kit (optional
equipment).
Step 6. (page 22) Make connection to gas supply.
Step 7. (page 22) Install the logs, decorative
The appliance is shipped with all gas controls
and components installed and pre-wired. Remove the shipping carton, exposing the front
glass door. Remove the top panel. Remove the
cardboard from underneath the pressure relief plates. Gently depress the outer top cor-
ners of the access panel until the catches "pop"
the panel free, allowing it to swing out and down
to open. Open the two latches (located under
the firebox floor) securing the glass door. Remove the door by tilting it outward at the
bottom and lifting it up. Set the door aside
protecting it from inadvertent damage.
See
Figure 55 on page 23.
Step 1. FRAMING
Frame these appliances as illustrated in
Figure 9 on page 7,
to be installed in a corner
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
unless the appliance is
.
Figure 10 on page 7 or Figure 11 on page
See
8
for corner framing installations. All framing
details must allow for a minimum clearance to
combustible framing members as shown in
Table 2
.
If the appliance is to be elevated above floor level,
a solid continuous platform must be constructed.
Headers may be in direct contact with the appliance top spacers but must not be supported by
them or notched to fit around them. All construction above the appliance must be self supporting.
DO NOT use the appliance for structural support.
The fireplace should be secured to the side
framing members using the unit's nailing flanges
- one top and bottom on each side of the
fireplace front. See
Figure 6.
Use 8d nails or
their equivalent.
Side
Framing
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members
and screw heads located in areas directly adjacent
to the nailing flanges, are EXEMPT from the 1/2
clearance to combustible requirements for the
firebox outer wrapper. Combustible framing may be
direct contact with the nailing flanges and may
in
be located closer than 1/2
the firebox wrapper in areas adjacent to the nailing
flanges. Frame the opening to the exact dimensions
specified in the framing details of this manual.
To The Framing
Unit Nailing Flange
(No clearance to
combustible
framing is required)
” from screw heads and
”
Figure 6
Step 2. ROUTING GAS LINE
Route a ¹⁄₂" (13 mm) gas line along the inside of
the right side framing as shown in
Figure 7
Gas lines must be routed, constructed and
made of materials that are in strict accordance
with local codes and regulations.
All appliances are factory-equipped with a flexible gas line connector and ¹⁄₂ inch shutoff
valve. (See step 6 on page 22).
DR models have only a rear vent
DT models have only a top vent
NOTE - Hood shown as
positioned in louvered
front model.
GAS INLET
(Either Side
and bottom)
OPTIONAL ELECTRICAL
INLET KNOCKOUT
REQUIRING A FIELD
PROVIDED JUNCTION
BOX (Either Side)
3 (76)
1³⁄₈
(35)
16
(406)
5¹⁄₂
(140)
9³⁄₈
(238)
2
(53)
Right Side View
¹⁄₂ (13)
F**
ELECTRICAL INLET
2³⁄₄ x 2 (70 x 51) COVER
PLATE with KNOCKOUT)
**Rear vent models only
**Rear Vent Units Only.
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guideline and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and B149.2 in Canada.
These fireplaces are designed, tested and
listed for operation and installation with,
and only with, Secure Vent™ (SV 4.5) Direct
Vent System Components, Secure Flex™
Flexible Vent Components manufactured by
Security Chimneys International. These
approved vent system components are labeled for identification. DO NOT use any
other manufacturer's vent components with
these appliances. These fireplaces must be
vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue
serving a solid fuel burning appliance. The vent
pipe is tested to be run inside an enclosing wall
(such as a chase). There is no requirement for
inspection openings in the enclosing wall at any
of the joints in the vent pipe.
Preparing the Appliance Vent Collar on
D-500/600/800 Series (Combined Top
and Rear Vent) Models
Each of the unit's two vent collars are sealed
with a cover plate and a seal plate and gasket.
The cover, and seal plate and gasket must be
removed from the vent collar being used.
Refer to
Figure 14
Figure 13
for rear, and the following steps to
prepare the appropriate collar for use.
From the vent collar being used, remove the
four screws securing the vent seal plate and
gasket. Remove and discard the seal plate and
gasket.
When the top vent collar is being used, from
inside the firebox, loosen the two screws in the
keyhole slots of the cover plate and remove the
remaining two cover plate securing screws.
Remove and discard the cover plate. Reinstall
and securely tighten all four screws.
When the rear vent collar is being used, from
inside the firebox, remove the two screws
securing the lintel to the rear wall of the firebox, then remove the lintel. Remove the four
cover plate securing screws.
for top vent usage and
Remove and discard the cover plate. Reinstall
and securely tighten all four cover plate screws.
Re-secure the lintel to the rear wall of the
firebox.
WARNING: FAILURE TO REINSTALL AND
SECURELY TIGHTEN COVER PLATE
SCREWS COULD RESULT IN LEAKAGE OF
FLUE PRODUCTS INTO THE LIVING SPACE.
VENT COVER PLATE AND VENT SEAL PLATE
MUST REMAIN SECURELY INSTALLED ON
UNUSED VENT COLLAR. FAILURE TO DO
SO COULD RESULT IN LEAKAGE OF FLUE
PRODUCTS INTO LIVING SPACE.
ON D-500/600/800 SERIES MODELS
(COMBINED TOP AND REAR VENT UNITS)
TOP VENT SEAL & COVER PLATE
REMOVAL WHEN USING THE TOP VENT
(OUTSIDE UNIT)
CABINET TOP
FIREBOX TOP
VENT
COVER PLATE
(INSIDE UNIT)
CROSS SECTION
GASKET
TOP VENT
VENT SEAL PLATE
SECURING
SCREWS
COVER PLATE
SECURING SCREWS
Figure 13
ON D-500/600/800 SERIES MODELS
(COMBINED TOP AND REAR VENT UNITS)
REAR VENT SEAL & COVER PLATE REMOVAL
WHEN USING THE REAR VENT
COVER PLATE
SECURING SCREWS
LINTEL
SECURING
SCREWS
LINTEL
(INSIDE UNIT)
REAR VENT
CROSS SECTION
VENT SEAL PLATE
GASKET
SECURING
SCREWS
CABINET BACK
(OUTSIDE UNIT)
Figure 14
Installation of Vent Restrictor
A vent restrictor may be needed with this appliance, install the vent restrictor (provided) in the
appliance top flue outlet as shown in
or rear flue outlet as shown in
held in place by friction, only.
Figure 15
Figure 16
. It is
VENT RESTRICTOR INSTALLATION
(TOP VENT)
A vent restrictor may be needed when
vertically terminating the vent system above
the roof (when using the appliance top
vent), install vent restrictor in the top vent
of the fireplace outlet on D-500/600/800 and
DT-500/600/800 series models.
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
RESTRICTOR
INNER
FIREPLACE
COLLAR
APPLIANCE TOP
VENT OUTLET
Figure 15
VENT RESTRICTOR INSTALLATION
A vent restrictor may be needed when
horzontally terminating the vent system
from the rear of the appliance (when using
the applliance rear vent), install vent
restrictor in the rear vent of the fireplace
DR-500/600/800 series models, in any
installation that has a vertical vent run in
excess of three feet (0.914 meters).
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
INNER FIREPLACE
COLLAR
(REAR VENT)
outlet on D-500/600/800 and
in the inner fireplace collar.
APPLIANCE REAR
VENT OUTLET
RESTRICTOR
Figure 16
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, determine vent routing and identify the exterior
termination location. The following sections
describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of
approved venting components is shown in
the two tables on page 24 and the two tables
on page 25.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
VERTICAL TERMINATION SYSTEMS (ROOF)
Figure 17, and Figures 27 through 31 on
pages 13 and 14
and their associated
Vertical Vent Tables illustrate the various vertical venting configurations that are possible for
use with these appliances. Secure Vent pipe
applications are shown in these figures; SecureFlex pipe may also be used. A Vertical Vent
Table summarizes each system’s minimum
and maximum vertical and horizontal length
values that can be used to design and install the
vent components in a variety of applications.
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is specified in ANSI Z223.1-(latest edition) (In Canada,
the current CAN-1 B149 installation code) by
major building codes. Always consult your
local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer
to
Figure 4
on page 5).
Vertical (Straight) Installation
Determine the number of straight vent sections
required. 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22
¹⁄₂" (572 mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181
mm) net section lengths are available. Plan the
vent lengths so that a joint does not occur at the
intersection of ceiling or roof joists. Refer to
the Vent Section Length Chart.
SV4.5CGV-1
Termination
40' Max
(12.2 M)
SV4.5FA OR
SV4.5FB Flashing
AND SV4.5SC
STORM COLLAR
1" (25.4 mm)
Minimum
Clearance to
Combustibles
*SV4.5BF
Firestop/Spacer
SV4.5L6/12/24/36/48
Vent Sections
TRAHCHTGNELNOITCESTNEV
noitceSlanimoN
621426384
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.1210003
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202
27 6 103004
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022
69 8 101204
5.79521.8100023
2015.8200024
5.301526.8000303
801 9 100304
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
T
O
T
A
L
Q
T
Y
TRAHCHTGNELNOITCESTNEV
noitceSlanimoN
621426384
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
44121100034
0515.21010034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708
25212010708
46222001708
67232000808
97252.32000066
5.082573.32100809
5.382526.32100067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078
63382010078
54357.8200001001
5.943521.9210001011
27313000088
5.673573.13100089
5.973526.1300011011
5.814578.43000099
32452.531000901
56457.8300000101
T
O
T
A
L
Q
T
Y
10
Figure 17
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of elbows required. Refer to Vertical Vent Figuresand Tables on page 13 and 14 to select the type
of vertical installation desired. Vent sections
are available in net lengths of 4 ¹⁄₂" (114 mm),
10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876
mm) and 46 ¹⁄₂" (1181 mm). Refer to the VentSection Length Chart on page 10 for an aid in
selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to
Figure 22
for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Where required, a telescopic vent section(SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
has an effective length of from 1 ¹⁄₂" (38 mm) to
7 ¹⁄₂" (191 mm). The SV4.5LA is fitted with a
locking inclined channel end (identical to a
normal vent section component) and a plain
end with 3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Maintain a minimum 1" (25 mm) clearance to
combustible materials for all vertical elements.
Clearances for all horizontal elements are 3"
(76 mm) on top, 1" (25 mm) on sides and 1"
(25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line from
the ceiling above the appliance to locate center of
the vertical run. Cut and/or frame an opening,
10¹⁄₂" x 10¹⁄₂" (267mm x 267mm) inside dimensions, about this center mark (
Figure 18
10¹⁄₂” Min.
(267 mm)
10¹⁄₂” Min.
(267 mm)
).
Figure 18
B. Attach vent components to appliance Secure Vent SV4.5 direct vent system compo-
All of the appliances covered in this document are
fitted with collars having locking inclined channels. The dimpled end of the vent components fit
over the appliance collar to create the positive
twist lock connection.
First Vent
Component
Align the dimple (four places)
with the opening of the locking
incline channel on appliance
collar. Twist vent component
clockwise to engage and seal.
Dimple
Locking
Incline Channel
Appliance collar
Vent / Appliance Collar
Connection
Figure 19
Arrow
Arrow
Align the dimple (four places) of the
upper vent section with the opening of
the locking incline channel on the
lower vent section. Twist vent
component clockwise to engage and
seal until arrow and dimple align.
Dimple
Locking
Incline Channel
Connected
Vent Sections
Vent / Vent Section
Connection
Arrow
Figure 20
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlet of the
four inclined channels on the collar (
Figure 19
). Push the vent component against
the collar until it fully engages, then twist the
component clockwise, running the dimples
down and along the incline channels until they
seat at the end of the channels.
The unitized design of the Secure Vent components will engage and seal both the inner
and outer pipe without the need for sealant or
screws. If desired, a #6 x ¹⁄₂" screw may be
used at the joint, but is not required as the pipe
will securely lock when twisted.
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
C. Attach vent components to each other -
Other vent sections may be added to the previously installed section in accordance with
the requirements of the vertical vent figures
and tables.
refer to
To add another vent component to a length of
vent run, align the dimpled end over the inclined
channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the
four incline channels of the previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels. This seating
position is indicated by the alignment of the
arrow and dimple as shown in
Figure 20.
D. Install firestop/spacer at ceiling - When using
Secure Vent, use SV4.5BF firestop/spacer at ceiling joists; when using Secure Flex, use SF4.5BF
firestop/spacer. If there is living space above the
ceiling level, the firestop/spacer must be installed
on the bottom side of the ceiling. If attic space is
above the ceiling, the firestop/spacer must be
installed on the top side of the joist. Route the vent
sections through the framed opening and secure
the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members,
and attic or ceiling insulation when running
vertical chimney sections.
E. Support the vertical vent run sections -
Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent
outlet using field provided support straps (conventional plumber's tape).
Secure the plumber's
tape to the framing members with nails or
screws.
Blocking
Support Straps
(Plumber’s tape)
8 feet (2.4 m)
Maximum
1 inch
(25.4 mm)
minimum
clearance to
combustibles
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Loop the tape around the vent, securing the
ends of the tape to the framing. If desired,
sheet metal screws #6 x ¹⁄₂" length may be
used to secure the support straps to the vent
pipe . Refer to
Figure 21.
Storm
Collar
C
F. Change vent direction to horizontal/inclined run - At transition from or to a horizon-
tal/inclined run, install the SV4.5E45 and
SV4.5E90 elbows in the same manner as the
straight vent sections. The elbows feature a
twist section to allow them to be routed about
the center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the
possiblity of unlocking any of the previously
connected vent sections. See
4 ¹³⁄₁₆"
(122 mm)
Swivel Joint
(360
°
swivel)
SV4.5E45
(45° Elbow)
Figure 22
Swivel Joint
(360
°
swivel)
SV4.5E90
(90° Elbow)
.
8 ¹⁄₈"
(206 mm)
Figure 22
G. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps
every 5' (1.52 m) along horizontal/inclined vent
runs using conventional plumber’s tape. It is
very important that the horizontal/inclined
run be maintained in a straight (no dips) and
recommended to be in a slightly elevated
plane, in a direction away from the fireplace
of ¹⁄₄" rise per foot (20 mm per meter) which is
ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or
near level. Use a carpenter’s level to measure
from a constant surface and adjust the support
straps as necessary.
D
Framing Dimensions for Roof
PitchCD
0/1210¹⁄₂ in.10¹⁄₂ in.
(267 mm)(267 mm)
6/1210¹⁄₂ in.12 in.
(267 mm)(305 mm)
12/1210¹⁄₂ in.17 ³⁄₄ in.
(267 mm)(451 mm)
Figure 23
I. Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position
such that the vent column rises vertically (use
carpenters level) (
Figure 24
). Nail along perimeter to secure flashing or adjust roofing to
overlap the flashing edges at top and sides only
and trim where necessary. Seal the top and both
sides of the flashing with waterproof caulking.
Figure 24
Figure 25
K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections to
the height as shown in the "Vertical vent termination section" on page 5. The SV4.5CGV-1 Vertical Termination (
same fashion as any other Secure Vent section.
Align the termination over the end of the previously installed section, adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four
incline channels of the last vent section. Push
the termination down until it fully engages, then
twist the termination clockwise running the
dimples down and along the incline channels
until they seat at the end of the channels.
Figure 26
) installs in the exact
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and
Figure 23
12
J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the
vent/flashing joint. See
Figure 25.
Loosen the
storm collar screw. Slide collar down until it
meets the top of the flashing. Tighten the
adjusting screw. Apply non-combustible caulking or mastic around the circumference of the
joint to provide a water tight seal.
.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 26
If the vent system extends more than 5' (1.5 m)
above the roof flashing, stabilizers may be necessary. Additional screws may be used at section
joints for added stability. Guide wires may be
attached to the joint for additional support on
multiple joint configurations.
VERTICAL VENT FIGURES/TABLES
V
H
*Ceiling
Firestop/Spacer
(SV4.5BF)
**Wall
Firestop/Spacer
(SV4.5HF)
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
Note: Secure Vent (rigid vent pipe) is shown
in the figures; Secure Flex (flexible vent pipe)
may also be used.
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS
OF CONCENTRIC FLEXIBLE VENT PIPE
BE JOINED TOGETHER.
Note: It is very important that the horizontal/
inclined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from the
¹⁄₄
fireplace of
meter) which is ideal, though rise per foot run
ratios that are smaller are acceptable all the
way down to at or near level.
Note: SV4.5BF (Secure Vent), SF4.5BF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible
floor or ceiling. SV4.5HF (Secure Vent),
SF4.5HF (Secure Flex)firestop/spacer must be
used anytime vent pipe passes through a combustible wall.
" rise per foot (20 mm per
AELBAT
VM
1)503.0(2)16.0(
2)16.0(4 )222.1(
3)419.0(6)68.1(
4)22.1(8)4.2(
MUMINI
teef)m(teef)m(
mumixaMH
.xaM)m4.21(teef04=H+V
.xaM)m4.2(teef8=H
Note: Two 45 degree elbows may be used in
place of one 90 degree elbow. The same rise to
run ratios, as shown in the venting figures for
90 elbows, must be followed if 45 degree
Figure 28
-
Rear Vent - ONE 90 DEGREE ELBOW
elbows are used.
BELBAT
H
*Ceiling
Firestop/Spacer
(SV4.5BF)
*Ceiling
Firestop/Spacer
(SV4.5BF)
Figure 27
- Top Vent - STRAIGHT
40 feet (12.2 meters)
Maximum
*When using
Secure Flex, use
Firestop/Spacer
SF4.5BF
*When using Secure Flex,
V1
**Wall
Firestop/Spacer
(SV4.5HF)
Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
Figure 29
-
Top Vent - TWO 90 DEGREE ELBOWS
use Firestop/Spacer
SF4.5BF
*Ceiling
(SV4.5BF)
V
VM
MUMINI
HmumixaM
teef)sretem(teef)sretem(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6(
V+V
1
H.xaM)m2.6(teef02=
.xaM)m4.21(teef04=H+
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
VERTICAL VENT FIGURES/TABLES
(continued)
DELBAT
muminiMVmumixaMHH+H
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6(
H+H+
V+V
1
1
H+H
1
Figure 30
- Rear Vent - THREE ELBOWS
H1
1
.xaM)m84.2(teef8=H
mumixaM
*Ceiling
Firestop/Spacer
(SV4.5BF)
**Wall
Firestop/Spacer
.xaM)m4.21(teef04=
V1
(SV4.5HF)
.xaM)m2.6(teef02=
V
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
A Vent Restrictor, as
shown in Figure 18,
page 10, must be used
in this application
*Ceiling
Firestop/Spacer
(SV4.5BF)
H
VM
teef)m(teef)m(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6(
V+V
1
Figure 31 -
EELBAT
MUMINI
HH+
1
H+H
1
H+H+
1
Top Vent - THREE ELBOWS
mumixaM
.xaM)m2.6(teef02=
.xaM)m4.21(teef04=
*Ceiling
H
1
SF4.5BF
SF4.5HF
Firestop/Spacer
(SV4.5BF)
V
1
*When using Secure Flex,
use Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
**Wall
Firestop/Spacer
(SV4.5HF)
H
V
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
Figure 32, and Figures 36 to 43 on pages 17,
18 and 19
and their associated Horizontal Vent
Table illustrate the various horizontal venting
configurations that are possible for use with
these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex
pipe may also be used. A Horizontal Vent Table
summarizes each system’s minimum and maximum vertical and horizontal length values that
can be used to design and install the vent
components in a variety of applications.
Both of these horizontal vent systems terminate
through an outside wall. Building Codes limit or
prohibit terminating in specific areas. Refer to
covered in this document are fitted with collars
having locking inclined channels. The dimpled
end of the vent components fit over the appliance
collar to create the positive twist lock connection.
A.Plan the vent run -
Analyze the vent routing and determine the
types and quantities of sections required
4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572
mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm)
net section lengths are available. Make allowances for elbows as indicated in
Figure 19
.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clearances
for the horizontal runs are; 3" (76 mm) on top, 1"
(25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening -
Locate the center of the vent outlet on the
exterior wall according to the dimensions shown
Figure 9
in
on page 7. Cut and/or frame an
opening, 10¹⁄₂" x 12¹⁄₈" (267 mm x 308mm)
inside dimensions, about this center.
C.Frame ceiling opening - If the vertical
route is to penetrate a ceiling, use plumb line
to locate the center above the appliance. Cut
and/or frame an opening, 10¹⁄₂" x 10¹⁄₂" (267
mm x 267 mm) inside dimensions, about this
center (refer to
Figure 18
on page 11 ).
D. Attach vent components to appliance - To attach
a vent component to the appliance collar, align the
dimpled end over the collar, adjusting the radial
alignment until the four locking dimples are aligned
with the inlets of the four incline channels on the
collar (refer to
Figure 19
on page 11 ).
Push the vent component against the collar
until it fully engages, then twist the component clockwise, running the dimples down
and along the incline channels until they seat
at the end of the channels.
TYPICAL HORIZONTAL VENT INSTALLATION
Building
Support
Framing
SV4.5E90
Elbow
Vertical
Rise
Support
Brackets
Ceiling
Firestop/Spacer
Horizontal / Inclined Run
See Figure 21 on page 11 for
vertical vent section support.
Figure 32
The unitized design of the Secure Vent components will engage and seal both the inner and outer
pipe elements with the same procedure. Sealant
and securing screws are not required.
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
E. Attach vent components to each other -
Other vent sections may be added to the previously installed section in accordance with the
requirements of the vent tables. To add another
vent component to a length of vent run, align the
dimpled end of the component over the inclined
channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the
four incline channels of the previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.This seating position is
indicated by the alignment of the arrow and
dimple as shown in
F. Install firestop/spacer at ceiling -
When using Secure Vent, use SV4.5BF firestop/
spacer at ceiling joists; when using Secure Flex, use
SF4.5BF firestop/spacer. If there is living space
above the ceiling level, the firestop/ spacer must be
installed on the bottom side of the ceiling. If attic
space is above the ceiling, the firestop/ spacer must
be installed on the top side of the joist. Route the
vent sections through the framed opening and
secure the firestop/spacer with 8d nails or other
appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members,
and attic or ceiling insulation when running
vertical chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 20 on page 11.
SV4.5 HTS
Termination
Shown
SV4.5L6/12/24/36/48
Vent Sections
Support Bracket Spacing
Every 5 ft (1.52 m)
Fireplace
Exterior
Wall
SV4.5 HTS
Termination
Shown
Exterior
Wall
G. Support the vertical run sections See Section E on page 11.
H. Change vent direction - At transition from
or to a horizontal/inclined run, install the
SV4.5E45 and SV4.5E90 elbows in the same
manner as the straight vent sections. The
elbows feature a twist section to allow them
to be routed about the center axis of their
initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a clockwise
direction only so as to avoid the possiblity
of unlocking any of the previously connected vent sections. See
Figure 22
I. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber’s tape.
See
Figure 32.
It is very important that the
horizontal/inclined run be maintained in a
straight (no dips) and recommended to be in
a slightly elevated plane, in a direction away
from the fireplace of ¹⁄₄" rise per foot (20 mm
per meter) which is ideal, though rise per foot
run ratios that are smaller are acceptable all the
way down to at or near level.
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening as
described in Step B. Assemble the vent system
to point where the terminus of the last section is
within 5 in. (127 mm) to 9¹⁄₄ in. (235 mm)
inboard of the exterior surface to which the
termination is to be attached, see
.
Figure 34
.
15
If the terminus of the last section is not within
this distance, use the telescopic vent sectionSV4.5LA, as the last vent section. For wall
thicknesses greater than that shown in
34
, refer to
table 3 on page 17
. This table lists
the additional venting components needed (in
addition to the termination and adapter) for a
particular range of wall thicknesses.
K.Attach termination adapter - Attach the
adapter (adapter - SV4.5RCH - provided with
the termination) to the vent section or telescoping vent section), elbow or appliance collar as shown in
Figure 33
in the same manner
as any SV4.5 vent component (refer to Step E).
L.Install Firestop/Spacer at exterior wall -
When using the square termination, install
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)
Firestop/Spacer over the opening at the exterior
side of the framing, long side up, with the 3 inch
spacer clearance at the top as shown in
34
, and nail into place. (The Firestop/Spacer
may also be installed over the opening at the
interior side of the framing.) When using the
round termination, a separate firestop/spacer
is not required since this termination has integral spacers which provide the same function
as a separate firestop/spacer.
M. Install the desired termination -
See the horizontal venting figures for application restrictions on the round termination
(SV4.5HTR) and the small square horizontal
termination (SV4.5HTSS).
1. Install the square termination (SV4.5HTS)
or (SV4.5HTSS)- For the last step , from outside
the exterior wall, slide the collars of the termination onto the adapter (the outer over the outer
and the inner inside the inner) until the termination seats against the exterior wall surface to
which it will be attached. Orient the housing of
the termination with the arrow pointed upwards.
Secure the termination to the exterior wall. The
horizontal termination must not be recessed
into the exterior wall or siding by more than the
1 ¹⁄₄" (32 mm) as shown in
Figure 34
2. Install the round termination (SV4.5HTR)
– See
Figure 35
for an illustration of the round
termination. For the last step, from outside the
exterior wall, slide the collars of the termination
onto the adapter (the outer over the outer and
the inner inside the inner) until the termination
seats against the exterior wall surface to which
it will be attached. Orient the housing of the
termination with the arrow pointed upwards.
Secure the termination to the exterior wall.
SFHRK Snorkel Cap –The snorkel cap is de-
signed to be fitted into a basement window
box. The SFHRK cap is for use with flex vent
pipe. The vertical distance between the inlet
and outlet of the cap is 28 in. (711 mm).
16
.
Figure
Figure
See Venting Figures for Use Restrictions on the
Small Square Horizontal Termination
(SV4.5HTSS) and the Horizontal Round
Termination (SV4.5HTR).
7"
5¹⁄₈"
(130 mm)
(178)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
*Firestop/Spacer integral with
round termination (SV4.5HTR)
12¹⁄₈"
(308 mm)
Adapter
SV4.5RCH
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
*Firestop/Spacer (SV4.5HF)
shown on the exterior side of the
wall. It may also be installed on
the interior side.
10¹⁄₂"
(267mm)
the Framed Opening.
for Min. Distance to Base
Base of Appliance
(25.4 mm)
See Figure 9 on page 7
of Appliance.
1"
SV4.5 HTS
Termination
Shown.
3"
(76 mm)
Installing the Square Horizontal Termination (SV4.5HTS), Small Square
Horizontal Termination (SV4.5HTSS) or Round Horizontal Termination
Figure 33
(SV4.5HTR).
*Note - The SV4.5HTR Horizontal Round Termination may NOT be recessed at all.
Minimum wall thickness
5 in. (127 mm)
Maximum wall thickness
9¹₄ in.(235 mm)
Interior Surface of
Finished Wall
Siding
Stucco
See Venting Figures for Use Restrictions on the Small Square
Horizontal Termination (SV4.5HTSS) and the Horizontal Round
Termination (SV4.5HTR).
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Telescopic Vent
Section (SV4.5LA), If
Necessary
SV4.5HTS
Square Termination
shown
Adapter
SV4.5RCH
Exterior Surface of Siding
Exterior Surface of
Framing
5 in. to 9 ¹₄ in.
(127 to 235 mm)
SV4.5HTS
Square Termination
Shown
*1¹⁄₄" Maximum Recess of
Either Square Termination into
Exterior Finishing Material
Venting Connection and Exterior Wall Recessing of the Horizontal Square Termination
(SV4.5HTS),Small Square Termination (SV4.5HTSS) or Round Termination ((SV4.5HTR).
Figure 34
The SV4.5HTR Round Termination may not
be used when the appliance is vented directly out the wall from the rear (as shown in
Figures 36 or 37
on page 17). Do Not recess
the SV4.5HTR round termination at all.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 35
See Horizontal Venting Figures and Tables
for Use Restrictions
SV4.5HTR Horizontal
Round Termination
ELBATG
muminiMVmumixaMH
teef)m(teef)m(
1)503.0(5)25.1(
2)16.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6(
.xaM)m4.21(teef04=H+V
.xaM)m2.6(teef02=H
HORIZONTAL VENT FIGURES/TABLES
Note: Secure Vent components (rigid vent
pipe and terminal) are shown in the figures;
Secure Flex components (flexible vent pipe
and terminal) may also be used.
Note: Two 45 degree elbows may be used in place
of one 90 degree elbow. The same rise to run ratios,
as shown in the venting figures for 90 elbows, must
be followed if 45 degree elbows are used.
Note: SV4.5BF (Secure Vent), SF4.5BF (Secure
Flex) firestop/spacer must be used anytime vent
pipe passes through a combustible floor or
ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime
vent pipe passes through a combustible wall.
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS
OF CONCENTRIC FLEXIBLE VENT
PIPE BE JOINED TOGETHER.
Note: It is very important that the horizontal/
inclined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from the
fireplace of
¹⁄₄
" rise per foot (20 mm per
meter) which is ideal, though rise per foot run
ratios that are smaller are acceptable all the
way down to at or near level.
3ELBAT
stnenopmoCgnitneV
deriuqeR
ylnOtiKnoitanimreT4/19ot5)532ot721(
tnev.ni6dnatiKnoitanimreT
)6L5.4VS(noitces
4/19)943ot532(4/331ot
tnev.ni21dnatiKnoitanimreT
)21L5.4VS(noitces
cipocseleTdnatiKnoitanimreT
.ni6dna)AL5.4VS(noitces
)6L5.4VS(noitcestnev
Round Termination (SV4.5HTR) may not be used.
H = 28 in. (711 mm) Maximum.
*When using Secure Flex,
use Firestop/Spacer
SF4.5HF
7 in. (178 mm)
See
Table 3
as an aid in venting component selection for a particular
H
*Wall Firestop/Spacer
(SV4.5HF)
range of exterior wall thicknesses.
Figure 36
- Rear Vent - NO ELBOWS - Square Horizontal Termination
(SV4.5HTS)
Round Termination (SV4.5HTR) may not be used.
H = 28 in. (711 mm) Maximum.
llaWroiretxEsuoiraVrofderiuqeRstnenopmoCgnitneV
-stiKnoitanimreTesehTfoynAgnisUnehW,sessenkcihT
,)STH5.4VS(noitanimreTerauqS
)SSTH5.4VS(noitanimreTerauqSllamS
)RTH5.4VS(noitanimreTdnuoR
Square termination (SV4.5HTS)
shown; Round Termination
(SV4.5HTR) may also be used.
Small Square termination
(SV4.5HTSS) may only be used
on DT-500 and D-500 models.
ELBATF
wobleeerged09en0=V
.xaM)m419.0(teef3=H
ssenkcihTllaWroiretxE
)mm(sehcni
H
V
)205ot004(4/391ot4/351
)725ot372(4/302ot4/301
*When using Secure Flex,
use Firestop/Spacer
SF4.5HF
See
Table 3
as an aid in venting component selection for a particular
*Wall
Firestop/Spacer
(SV4.5HF)
range of exterior wall thicknesses.
Figure 38
-
Top Vent - ONE 90 DEGREE ELBOW -
ELBOW CONNECTION AT APPLIANCE
Square termination (SV4.5HTS)
shown; Round Termination
(SV4.5HTR) may also be used.
Small Square termination
(SV4.5HTSS) may only be used
on DT-500 and D-500 models.
H
**When using Secure
Flex, use Firestop/Spacer
8³⁄₁₆ in. (207 mm)
See
Table 3
range of exterior wall thicknesses.
Figure 37
only - Small Square Horizontal Termination (SV4.5HTSS)
H
SF4.5HF
**Wall Firestop/Spacer
(SV4.5HF)
as an aid in venting component selection for a particular
- Rear Vent - NO ELBOWS - for D-500 and DR-500 models
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
**When using Secure
Flex, use Firestop/Spacer
SF4.5BF
*When using Secure Flex,
use Firestop/Spacer
SF4.5HF
See
Table 3
as an aid in venting component selection
**Wall Firestop/Spacer
(SV4.5HF)
Firestop/Spacer
*Ceiling
(SV4.5BF)
for a particular range of exterior wall thicknesses.
Figure 39
-
Top Vent - ONE 90 DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
V
17
HORIZONTAL VENT FIGURES/TABLES
(continued)
H
1
H
muminiMVmumixaMHH+H
HELBAT
1
mumixaM
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6(
H+H+V
1
H+H
1
.xaM)m84.2(teef8=H
.xaM)m2.6(teef02=
.xaM)m4.21(teef04=
*When using
Secure Flex, use
Firestop/Spacer
SF4.5HF
*Wall
Firestop/Spacer
(SV4.5HF)
**Ceiling
Firestop/Spacer
(SV4.5BF)
*Wall
Firestop/Spacer
V
(SV4.5HF)
**When using
Secure Flex, use
Firestop/Spacer
SF4.5BF
Square termination (SV4.5HTS) shown. Round Termination (SV4.5HTR) may only be used on D-500, D-600 and DR-500, DR-600 series
models. The Small Square Termination (SV4.5HTSS) may only be used on D-500 and DR-500 series models.
See
Table 3 on page 17
Figure 40
-
Rear Vent - TWO 90 DEGREE ELBOWS
as an aid in venting component selection for a particular range of exterior wall thicknesses.
18
*Wall Firestop/Spacer
(SV4.5HF)
H
VM
teef)m(teef)m(
H
1
V
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
*When using Secure Flex,
use Firestop/Spacer
SF4.5HF
**Note - When using
Secure Flex, use
Firestop/Spacer SF4.5BF
*Wall Firestop/Spacer
(SV4.5HF)
**Ceiling
Firestop/Spacer
(SV4.5BF)
4)22.1(02)2.6(
Square termination (SV4.5HTS) shown. Round Termination (SV4.5HTR) may also be used.
The Small Square Termination (SV4.5HTSS) may only be used on D-500 and DT-500 series models.
See
Table 3 on page 17
Figure 41
-
Top Vent - TWO 90 DEGREE ELBOWS
as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
JELBAT
MUMINI
H+H
1
H+H+V
1
H+H
1
mumixaM
.xaM)m4.21(teef04=
.xaM)m2.6(teef02=
HORIZONTAL VENT FIGURES/TABLES
(continued)
**Wall Firestop/Spacer
(SV4.5HF)
muminiMVmumixaMH
H
1
H
2
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
KELBAT
H+H1H+
2
mumixaM
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6(
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
V
*Ceiling
Firestop/Spacer
(SV4.5BF)
H+H+V
1H+2
H+H1H+
2
H
.xaM)m4.21(teef04=
.xaM)m84.2(teef8=H
.xaM)m2.6(teef02=
Square termination (SV4.5HTS) shown. Round Termination (SV4.5HTR) may only be used on D-500, D-600 and DR-500, DR-600 series
models. The Small Square Termination (SV4.5HTSS) may only be used on D-500 and DR-500 series models.
See
Table 3 on page 17
Figure 42
- Rear Vent - THREE 90 DEGREE ELBOWS
as an aid in venting component selection for a particular range of exterior wall thicknesses.
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
H
1
**Wall Firestop/Spacer
(SV4.5HF)
V
1
**Wall Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
*Ceiling
Firestop/Spacer
(SV4.5BF)
H
(SV4.5HF)
V
Square termination (SV4.5HTS) shown. Round Termination (SV4.5HTR) may also be used.
The Small Square Termination (SV4.5HTSS) may only be used on D-500 and DT-500 series models.
See
Table 3 on page 17
Figure 43
-
Top Vent - THREE 90 DEGREE ELBOWS
as an aid in venting component selection for a particular range of exterior wall thicknesses.
LELBAT
VM
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6(
V+V
MUMINI
HmumixaM
teef)m(teef)m(
H+H
1
H+H+
1
1
.xaM)m2.6(teef02=
.xaM)m4.21(teef04=
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
19
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
KITS AND COMPONENTS
Secure Flex venting kits and components may
be used in any venting application where rigid
Secure Vent (SV4.5) direct vent components
can be used. All restrictions, clearances and
allowances that pertain to the rigid piping
apply to the flexible venting.
Secure Flex
kits
may not be modified; also, under no circumstances may separate sections of flex pipe
be joined together. Secure Flex kits may be
added to the end of a vent run made up of rigid
Secure Vent (SV4.5) vent sections provided
that doing so does not violate any of the
venting length, height, routing, horizontal to
vertical ratio requirements or clearance considerations detailed in this manual.
Secure Flex kits come with an included adapter
that can be fitted to the appliance collar or the
inclined channel end of the last Secure Vent
(SV4.5) vent section in a rigid system in the
exact same fashion as any other Secure Vent
section. Align the dimpled end of the adapter
over the previously installed section or appliance collar, adjusting the radial alignment until
the four locking dimples of the adapter are
aligned with the inlets of the four incline channels of the last vent section or collar. Push on
the adapter until it fully engages, then twist the
adapter clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.
Attach the flexible vent to the adapter as
follows (see also
Figure 44
):
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out of
the way.
2. Apply a bead of Mill-Pac Black (700
°F)
high temperature sealant - Catalog No.
10K81) to the inner adapter collar, approxi-
mately ¹⁄₂ inches from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adapter
collar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1³⁄₄
inch from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adapter
inner collar approximately ³⁄₄ inch from the
end of the flex.
6. Install three screws 120 degrees apart through
the flexible vent pipe and into the adapter collar
just below the gear clamp to provide additional
security to the connection.
NOTE: OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE
Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adapter (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inner and outer adapter collars.
1³⁄₄ in. (44 mm)
Flexible Pipe and
Adapter Outer
Collar Overlap
Adapter
(SV4.5RF)
Attach Adapter to Appliance
Collar, or Secure Vent Sections
Figure 44
B. Install the Outer Flex Pipe -
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of
the way.
2. Apply a bead of Mill-Pac Black (700
temperature sealant - Catalog No. 10K81) to
the outer adapter collar; to the grooves of the
collar which extend approximately 1 inch from
the end and to the flat surface, approximately
1³⁄₈ inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adapter
collar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1³⁄₄
inches from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adapter
outer collar approximately ³⁄₄ inch from the end
of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connection.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to
provide the required clearance. Do Not allow
the flexible vent to bend in a radius tighter than
5" (127 mm). Refer to
Figure 45
horizontal sections of flex with metal straps at
2 foot (0.61 m) intervals.
°F) high
. Support
FLEX VENT
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
GEAR
CLAMPS
1³⁄₄ in. (44 mm)
Flexible Pipe and
Adapter Inner
Collar Overlap
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
SF-12 or SF-18 Flexible Vent Section
5" (127 mm)
Radius Minimum
Figure 45
D. Attach Flex Vent to Termination Secure Flex components can be purchased
separately and attached to bulk lengths of
Secure Flex flexible tubing cut to size at the
job site. When using this method connect the
flex vent only to Flex Vent terminations, not
Secure Vent terminations. Secure the flexible
vent to the Secure Flex terminations in the
same manner (see
tached to the adapter.
Secure Flex
Note:
Secure Flex
substitute
Secure Vent
nents. The collars of
tions and adapters have a different circumference than that used with the
pipe. Additionally,
have an extended length center tube for use
in attaching the flexible vent.
Figure 44)
as it was at-
vent must be attached to
terminations only. DO NOT
Secure Vent
adapter for
terminations or the
Secure Flex
Secure Flex
compo-
termina-
Secure Vent
Secure Flex
components
20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 4. FIELD WIRING
1. If any of the original wire as supplied must be replaced,
1. it must be replaced withType AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
BK
Junction Box
Transf.
120 V.
24 V
Factory WiredField Wired
BL
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-100 and FBK-200 Kits
R
W
BL
OPT
BLOWER
G
W
*OPTIONAL
ACCESSORY
SWITCH
120
VAC.
BK
W
Gas Valve
B
R
IGNITER
PILOT
ASSEMBLY
Break Off
Tab
BK
G
*Blower speed control switch is provided in FBK200 blower kit.
Outlet Box
Green Ground
Screw
Hot side of Outlet
Schematic Representation Only
**ON/OFF Switch (Integral
with Gas Valve)
**Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH
OR OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
Red
pigtail
Black
pigtail
White Wire
to Opposite
Side
G
Refer to Section A for millivolt appliances and
Section B for electronic appliances. The gas
valve is set in place and pre-wired at the
factory on both models.
A. SIT and Honeywell Millivolt Wiring
(See Figure 46)
1. Select any of the following optional con-
trols: appliance-mounted (rocker switch) or
wall-mounted switch, thermostat, or one of
the optional remote control kits. If appliancemounted ON/OFF control is selected mount it
in the gas valve mounting bracket.
2. If wall-mounted ON/OFF control or thermostat is selected mount it in a convenient
location on a wall near the fireplace.
3. Wire the control switch within the millivolt
control circuit using the 15 feet of 2 conductor wire
supplied with the unit . Caution: do not connect the
optional wall switch to a 120V power supply.
4. Alternatively, the appliance may be operated
without the use of the controls indicated in step 1,
solely by manipulating the gas valve control knob. In
order to use this method, twist the free ends of the two
conductor wire (located inside the bottom compartment of the unit) together as shown in
Note: The supplied 15 feet of 2 conductor wire has one
end of each conductor connected to the gas valve
circuit and the other end of each conductor placed
loose inside the bottom compartment of the unit.
Honeywell Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced,
it must be replaced withType AWM105°C – 18 GA. wire.
TP
OR REMOTE CONTROL RECEIVER
*TWIST WIRES “A” AND “B” TOGETHER TO OPERATE UNIT
SOLELY BY MANIPULATING THE GAS VALVE CONTROL KNOB;
OR CONNECT WIRES TO OPTIONAL ON/OFF SWITCH OR WALL
B. Electronic Wiring
Note: The electronic appliance must be con-
nected to the main power supply.
A junction box is located at the rear of the control
compartment on either side of the cabinet. The
junction box on the right side contains a factory
installed and wired outlet box (duplex receptacle). Also, an optional field-provided junction
box with receptacle may be installed at the front
of the control compartment on either side of the
cabinet.
by a conduit fitting and locknut (field-provided).
Thermopile
AB
*OPTIONAL ON/OFF SWITCH,
WALL SWITCH, THERMOSTAT
SWITCH OR THERMOSTAT TO OPERATE UNIT.
See Figure 47.
(See figure 48 or 49)
It will be held in place
–
Figure 46
Figure 46
See Figure 12 on page 8
for Optional Electrical
Inlet Knockout Location
*Field-Provide
Junction Box
and Duplex
*Narrow (2 ¹⁄₈ inch Wide)
J-Box Required
Optional J-Box/Outlet Box
Figure 47
(Left Side Shown)
Receptacle
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. If the factory-provided outlet/junction box
at the right rear of the fireplace is being used,
remove the outlet box from the junction box by
removing two screws.
3. Connect the power supply wires (including the ground supply wire) as shown in
Figures 48or 49.
(If the field-provided J-box/
outlet box is being used, all of the outlet box
wiring must be field-provided.)
4. Locate and install a low voltage (24V) wallmounted switch or thermostat (both fieldprovided) in the desired location.
5. Connect the low voltage wire (located in-
.
side the bottom compartment of the unit) to
the wall-mounted switch or thermostat.
Note: The supplied 15 feet of 2 conductor wire has one
end of each conductor connected to the gas valve
circuit and the other end of each conductor placed
loose inside the bottom compartment of the unit.
Figure 48
6. Insert the control circuit plug into the
unswitched receptacle of the outlet box.
7. After wiring is complete, mount the outlet
box to the J-Box.
TH
TP
TH
Note: The gas valve-mounted ON/OFF switch is shown
in Figure 48 or 49. It is integral with the gas valve
and should be set to the ON position.
Step 5.WIRING - OPTIONAL FORCED AIR
BLOWER KIT
FBK-100, FBK-200 and FBK250 Kits
(See Figure 48 for FBK-100, FBK-200 and
Figure 49 for FBK-250 wiring)
An electrical outlet box (receptacle) is factory provided for the installation of the FBK-100, FBK-200 and FBK-250 forced air blower kits. (An
optional field-provided outletbox/J-Box may also
be used. Electrical power must be connected to
either of these receptacles in order to operate these
blowers. Install the blower kits according to the
–
installation instructions provided with the kits.
Note: The tab connecting the receptacles of the
outlet box must be broken in FBK-100 and FBK200 blower kit applications.
-
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-250 Kits
1. If any of the original wire as supplied must be replaced,
1. it must be replaced withType AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
*ON/OFF Switch (Integral
with Gas Valve)
Gas Valve
BK
R
BL
OPT
BLOWER
WH
*Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
PILOT
ASSEMBLY
IGNITER
Optional FBK-250
Module
W
B
Hot side of Outlet
Outlet Box Green
Ground Screw
G
G
BL
R
G
BK
W
White Wire
To Opposite
Side
Transf.
120 V.
24 V
120
VAC.
BK
IMPORTANT: Ground supply wire must be
connected to the green wire attached to the
outlet receptacle's green ground screw. See
Figure 48 or 49
. Failure to do so will result in
a potential safety hazard. The appliance
must be electrically grounded in accordance
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH
OR OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
Factory WiredField Wired
Schematic Representation Only
with local codes or, in the absence of local
codes, the National Electrical Code, ANSI/
Figure 49
NFPA 70-(latest edition). (In Canada, the
current CSA C22-1 Canadian Electrical Code.)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
21
Step 6. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-off valve mounted in the supply line.
ure 50
illustrates two methods for connecting
the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation
must be in compliance with local codes.
These appliances are equipped with a gas flex
line for use (where permitted) in connecting the
unit to the gas line. A gas flex line is provided
to aid in attaching the direct vent appliance to
the gas supply. The gas flex line can only be
used where local codes permit. See
for flex line description. The flex line is rated for
both natural and propane gas. A manual shut
off valve is also provided with the flex line.
The gas control valve is located in the lower
control compartment. To access the valve open
the lower control compartment door
51)
. The millivolt control valve has a ³⁄₈"
(10 mm) NPT thread inlet port. The electronic
control valve has a ¹⁄₂" (13 mm) NPT thread inlet
port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm x
10 mm) NPT fitting.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane resistant compounds are used in propane applications).
Gas Flex Line Connector
Gas
Valve
³₈" Nipple
³₈"
Union
³₈" Close Nipple
Figure 50-
Open the lower panel or louver assembly by
gently depressing the outer top corners of the
panel until the catches “pop” the panel free,
allowing it to swing out and down to open.
Control
Valve
³₈" NPT x ³₈
Flare Fitting
³₈" Flex Tubing
³₈" Shut-Off Valve
GAS CONNECTION
Lower Control
Compartment
Door
¹₂
Reducer
OPENING CONTROL
Figure 51
COMPARTMENT DOOR
Turn on gas supply and test for gas leaks using
a soapy water solution. Never use an open
flame to check for leaks.
Figure 50
(Figure
³₈" Flare
¹₂" x
Shut-Off Valve
Gas
Stub
x ³₈ "
Fig-
A. Mix a 50% dish soap, 50% water solution.
B. Light the appliance (refer to the lighting
instructions provided in the Homeowner's Care
and Operation Instructions).
C. Brush all joints and connections with the
soapy water solution to check for leaks. If
bubbles are formed, or gas odor is detected,
turn the gas control knob to the “OFF” position.
Either tighten or refasten the leaking connection and retest as described above.
D. When the gas lines are tested and leak free,
observe the individual tongues of flame on the
burner. Make sure all ports are open and producing flame evenly across the burner. If any
ports are blocked, or partially blocked, clean
out the ports.
Step 7. INSTALLING LOGS, DECORATIVE
VOLCANIC STONE AND GLOWING EMBERS
The packaged logs are located within the firebox. The decorative volcanic stone and glowing
embers are packaged separately in plastic bags
located in the control area of the fireplace.
Refer to the Homeowner's Care and OperationGuide for detailed placement instructions for
decorative volcanic stone, and to the Log Place-ment Guide for detailed placement instructions
for logs and glowing embers (rockwool).
Step 8. CHECKING APPLIANCE OPERATION
With gas line installed run initial system checkout
before closing up the front of the unit. Follow the
pilot lighting instructions provided in the
Homeowner's Care and Operation Instructions.
For piezo ignitor location see
Figure 52
(SIT and
Honeywell millivolt appliances only).
Note: Instructions are also found on the literature tag attached to the gas valve train.
When first lighting the appliance, it will take a few
minutes for the line to purge itself of air. Once
purging is complete, the pilot and burner will light
and operate as indicated in the instruction manual.
Subsequent lightings of the appliance will not require such purging. Inspect the pilot flame (remove
logs, if necessary, handling carefully).
SIT Gas Valve
Honeywell
Gas Valve
Piezo
Ignitor
Sit and Honeywell Millivolt Gas Valve
Showing Piezo Ignitor Location (Each Unit is
Equipped with Only One of these Gas Valves)
Figure 52
SIT and Honeywell Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or
floating. Flame should be blue in color with
traces of orange at the outer edge. The top ³⁄₈"
(10 mm) at the pilot generator (thermopile)
and the top ¹⁄₈" min (tip) of the quick drop out
thermocouple should be engulfed in the pilot
flame. The flame should project 1" (25 mm)
beyond the hood at all three ports (
- SIT, Figure 54 - Honeywell
Figure 53
)
Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall
switch and rotate the gas valve control knob
counterclockwise to the “ON” position.
MILLIVOLT
Thermocouple
Pilot
Nozzels
Hood Ignitor Rod
Thermopile
³⁄₈" Min
(9 mm)
Figure 53
MILLIVOLT HONEYWELL
¹⁄₈" Min
(3 mm)
Pilot
Nozzels
Thermopile
Thermocouple
Ignitor Rod
Hood
³⁄₈" Min
(9 mm)
Figure 54
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the optional
remote wall switch and turn the gas control
switch to the “ON” position. Ensure the ignitor
lights the pilot. The pilot flame should engulf
the flame rod as shown in
ELECTRONIC
Proper Flame
Adjustment
Pilot
Nozzle
Figure 55
(9 mm to 13 mm)
.
3/8 To 1/2 Inch
Ground
Electrode
Flame Rod
Hot Surface
Igniter
Figure 55
22
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 9. INSTALLING THE GLASS DOOR
Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket
surface must be clean, free of irregularities
and seated firmly.
Position the door in front of the firebox opening
with the bottom of the door held away from the
fireplace
(Figure 56
). Hook the top flange of the
door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently
in towards the fireplace ensuring that the gasket seats evenly as the door frame draws shut.
Fasten the two latches located underneath the
firebox floor to the door's vee-flange. Close
both the latches securely.
Top Flange
Door Frame
Glass Door
Latch
Bottom Vee-flange
Door Frame
INSTALLINGTHEGLASSDOOR
Latch
Firebox Floor
Figure 56
WARNING: HANDLE THIS GLASS WITH EXTREME CARE! THE GLASS PANEL IS SUSCEPTIBLE TO DAMAGE — DO NOT SCRATCH
WHILE HANDLING OR WHILE RE-INSTALLING THE GLASS DOOR FRAME.
WARNING: NEVER OPERATE THE APPLIANCE WITHOUT THE FRONT GLASS ENCLOSURE PANEL IN PLACE AND SECURE.
Step 10. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a matter of taste.
Generally, most people prefer the warm glow of
a yellow to orange flame.
Appliances operated with air shutter openings that
are too large will exhibit flames that are blue and
transparent. These weak, blue and transparent
flames are termed anemic. If the air shutter
opening is too small sooting may develop.
Sooting is indicated by black puffs developing
at the tips of very long orange flames. Sooting
results in black deposits forming on the logs,
appliance inside surfaces and on exterior surfaces adjacent to the vent termination. Sooting
is caused by incomplete combustion in the
flames and lack of combustion air entering the
air shutter opening. To achieve a warm yellow
to orange flame with an orange body that does
not soot, the shutter opening must be adjusted
between these two extremes.
No smoke or soot should be present. Reposition
the logs if flames impinge on any of them.
If the logs are properly positioned and sooting
conditions exist, the air shutter opening on the
main burner tube should be adjusted. Normally,
the more offsets in the vent system, the greater
the need for the air shutter to be opened further.
WARNING: AIR SHUTTER ADJUSTMENT
SHOULD ONLY BE PERFORMED BY A
QUALIFIED PROFESSIONAL SERVICE
TECHNICIAN.
IMPORTANT: ENSURE THAT THE FRONT
GLASS PANEL IS IN PLACE AND SEALED
DURING ADJUSTMENT.
Burner Adjustment
CAUTION: THE ADJUSTMENT ROD AND
NEARBY APPLIANCE SURFACES ARE HOT.
EXERCISE CAUTION TO AVOID INJURY
WHILE ADJUSTING FLAME APPEARANCE.
To adjust the flame, move the adjustment rod
(located in the lower control area) up or down
to increase or reduce the air shutter opening,
respectively. Initially, always position the air
shutter to the factory setting (the minimum air
opening position) as shown in
can be done by pulling the adjustment rod all
the way down. Allow the burner to operate for
at least 15 minutes. Observe the flame continuously. If it appears weak or sooty as previously
described, adjust the air shutter by pushing or
pulling on the adjustment rod until the flame
appearance is as desired.
The adjustment rod and associated adjustable air
shutter is patented technology. Flame adjustments can be made quickly and accurately to taste
without the need of disassembling the appliance
and waiting for 30 minutes after each adjustment.
Figure 57
. This
Adjusting Set Screw
Adjustment Rod Up
Burner Tube
Air Shutter
Adjustment Rod Down
(minimum air
opening position)
(Fully Open Position)
Figure 57
RIAYROTCAF
GNITTESRETTUHS
)mm(sehcni
sledoM
saG
TD,D
RD&
005
006
008
epyT
.taN23/3)83.2(23/3)83.2(
.porP)81.3(8/18/3)25.9(
.taN23/3)83.2()83.2(23/3
.porP8/3)25.9(8/3)25.9(
.taN61/3)67.4()67.4(61/3
.porP2/1)31()31(2/1
snoitacilppA
ehtgnisu
ecnailppA
tneVpoT
snoitacilppA
ehtgnisu
ecnailppA
tneVraeR
Note: If the flame still appears anemic with the
air shutter closed all the way against the stop
(usually a result of lengthy vertical runs), turn
the appliance off, turn the gas supply off, wait
for the parts to cool, remove the glass door and
logs to access the air shutter. The shutter is
prevented from actually closing all the way by
an adjustment set screw (see Figure 57 ). Remove this screw using a
¹⁄₄
inch nut driver.
Reinstall the logs and glass door, turn the gas
back on and then restart the appliance. After 30
minutes, reobserve the flame. Adjust the air
shutter as previously described.
When satisfied that the appliance operates
properly, proceed to finish the installation.
Leave the control knob in the ON position
and the remote switch OFF. Close the lower
control compartment door.
Step 11. HOOD INSTALLATION
All of these appliances must have hoods
installed prior to operating.
On all clean face units, slide the hood into the
slots on the lower edge of the radiant panel
(Figure 58 on page 24).
On louvered face
units, slide the hood into the slots on the lower
edge of the cabinet top (
Figure 59 on page 24
).
FINISHING REQUIREMENTS
Wall Details
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thickness of the finished wall (
Figure 59
on page 24
Figure 58, and
).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
23
Combustible
Finished Wall
Materials
Combustible
material
may touch the
appliance top.
Combustible
materials not
allowed below
this point on
the face of the
appliance.
Hood must be installed as shown.
Clean Face Models
This Area Must Remain
Clear of Combustible
Materials
1" Min
(25 mm)
Spacer
Top of Appliance
Radiant panel
Top of Door Frame
Figure 58
Combustible
Finished Wall
Materials
Combustible
material
may touch the
appliance top.
Combustible
materials not
allowed below
this point on the
face of the
appliance.
Hood must be installed as shown.
Louver Face Models
This Area Must Remain
Clear of Combustible
Materials
1" Min
(25 mm)
Spacer
Top of Appliance
Louvers
Top of Door Frame
Figure 59
Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 60
Combustible Materials
Allowed In Shaded
Area “Safe Zone”
.
Top View Of
Fireplace
12"
MANTEL CLEARANCES
Inches (mm)
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
14
(356)
12
(305)
10
(254)
8
6
(203)
(152)
NOTE - Hood shown as positioned
in louvered front model. The hood
position in the flush faced front model
is lower than shown.
6 (152) MANTEL
4 (102) MANTEL
2 (51) MANTEL
4
(102)
TOP OF
APPLIANCE
Figure 61
A hearth extension is not required with this
appliance. If a hearth extension is used, do not
block the lower control compartment door.
Any hearth extension used is for appearance
only and does not have to conform to standard
hearth extension installation requirements.
Note: Combustible wall finish materials and/or
surround materials must not be allowed to
encroach the area defined by the appliance
front face (black sheet metal). Never allow
combustible materials to be positioned in
front of or overlapping the appliance front
face. See Figure 58 and Figure 59.
Non-combustible materials, such as surrounds
and other appliance trim, may be installed on
the appliance front face with these exceptions:
they must not cover any portion of the glass or
louvers; they may cover any portion of the top
radiant panel or the air gaps surrounding the
top radiant panel up to the installed hood.
Vertical installation clearances to combustible
mantels vary according to the depth of the
mantel. See
Figure 61
. Mantels constructed
of non-combustible materials may be installed
at any height above the appliance opening;
however, do not allow anything to hang below
the hood.
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks around your appliance with noncombustible material
and wherever cold air could enter the room. It is especially important to insulate outside chase
cavity between studs and under floor on which appliance rests, if floor is above ground level.
*All compressed flex vents can be expanded up to two times.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
25
INSTALLATION ACCESSORIES CONTINUED
detsiLtneVeruceSstnenopmoC™
.oN.taC.oNledoMnoitpircseD
29K69PS5.4VSetalPtroppuS
00K79RGH5.4VSdnuoRdrauGtaeH
25M715.4VS
1-SGH
35M715.4VS
21-SGH
89K69RDH5.4VSdnuoRrofrotcelfeDtaeH
GAS CONVERSION KITS
)kcaP-1(
)kcaP-21(
noitanimreT
detsiLxelFeruceSstnenopmoC™
.taC
.oN
10L78KRHFSxelFhtiwtiKresiRlekronS
t
n
a
l
a
e
S
erauqSdrauGtaeH
erauqSdrauGtaeH
18K01PMFSerutarepmeT-iHkcalBcaPliM
66L196-4CG-FSrof)mm411(.ni5.4pmalCraeG
76L196-7CG-FS)mm5.091(.ni5.7pmalCraeG
04M91FH5.4FS-recapS/potseriF
14M91FB5.4FS-recapS/potseriF
ledoM
.oN
noitpircseD
dna,xelFfonoitcesa,retpadA
spmalCraeG
tnalaeS
)seceip6(xelF
)seceip6(xelFrof
)gnicaps1-1-3(latnoziroH
)gnicaps1-1-1(lacitreV
WARNING: THIS CONVERSION KIT SHALL BE
INSTALLED BY A QUALIFIED SERVICE AGENCY IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND ALL APPLICABLE CODES AND
REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. IF THE INFORMATION IN THESE
INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A
FIRE, EXPLOSION OR PRODUCTION OF CARBON
MONOXIDE MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED
APPLIANCE IS CHECKED AS SPECIFIED IN THE
OWNER INSTRUCTIONS SUPPLIED WITH THE KIT.
THE QUALIFIED SERVICE AGENCY PERFORMING
THIS INSTALLATION ASSUMES RESPONSIBILITY
FOR THIS CONVERSION.
In Canada:
THE CONVERSION SHALL BE CARRIED OUT
IN ACCORDANCE WITH THE REQUIREMENTS
OF THE PROVINCIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN1-B149.1
AND .2 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE
CONFORMÉMENT AUX RECOMMANDATIONS
DES AUTORITÉS PROVINCIALES AYANT
JURIDICTION ET CONFORMÉMENT AUX
EXIGENCES DU CODE D'INSTALLATION CAN1B149.1 ET.2.
Gas conversion kits are available to adapt your
appliance from the use of one type of gas to the
use of another. These kits contain all the necessary components needed to complete the task
including labeling that must be affixed to ensure
safe operation.
Kit part numbers are listed here and the following steps detail the conversion procedure.
26
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION
SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE
CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET
TOUTES EXIGENCES ET CODES APPLICABLES DE
L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION
DANS CETTE INSTRUCTION N'EST PAS SUIVIE
EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE
PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES
CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE
PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE
EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET
ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET
COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL
CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS
DANS LES INSTRUCTIONS DE PROPRIÉTAIRE
PROVISIONNÉES AVEC L'ÉQUIPEMENT.
Remove the front glass door/frame from the
appliance. Access the control compartment.
Step 2. Carefully remove the logs. Exercise
care so as not to break the logs.
b. Attach manometer to the manifold side
pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa)
for natural gas, and 10.0 inches water column
(2.49 kPa) for propane gas.
c. Refer to
Figure 63
and remove the pilot
hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the
one provided with the kit.
Step 3. Locate the screws securing the burner
(tray) to the appliance. Remove the burner and
retain the securing screws.
Step 4. Millivolt Appliances - SIT Systems
a. Refer to
Figure 62
and the instructions
provided with the kit. Using a Torx T20, remove
and discard the three pressure regulator mounting screws. Remove the pressure regulator,
spring, poppet, diaphragm and bushing. Dis-card all removed components. Ensure the
rubber gasket installed on the back of the
replacement pressure regulator is properly
positioned and install the new pressure regulator using the new screws supplied with the kit.
Tighten screws to 25 In. lb. torque.
SIT Millivolt Gas Valve
Pressure
Regulator
Remove
These
Components
Figure 64
Pilot for Honeywell Millivolt Gas Valve
(Loosening of Hex Fitting For Orifice Strip Tab Positioning)
Hood
7/16 in. Open End Wrench
Orifice Strip Tab
Take Care Not to Contact the Orifice Strip Tab
with the Hex Fitting Wrench - Distortion of the Tab
May Render the Pilot Inoperative.
Hood Alignment
Pilot for Honeywell Millivolt Gas Valve
Orifice Strip Tab Position Identification
For LP/Propane and Natural Gas
LP/Propane Gas Position -
1/16 in. Hole, LP and
Red Color shown on tab
L
P
Natural Gas Position -
NAT shown on tab
NAT
Figure 62
Pilot for SIT Millivolt Gas Valve
Pilot
Orifice
Figure 63
Figure 65
Top View of Hex Fitting and Orifice Strip Tab
Pilot for Honeywell Millivolt Gas Valve Orifice Strip Tab Positioning
Figure 66
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Pilot Hood Position After
Loosening Hex Fitting 1/4 Turn
Orifice Strip Tab
Push Tab to Set
Gas Type Usage
Note - Orifice Strip Tab May
Be Randomly Located On Any
Side Of The Hex Fitting
27
Step 5. Millivolt Appliances -
Honeywell Systems
a.
Convert the gas valve as follows (
see
Figure 67):
Remove the plastic protecting cap. Remove the
gas type setting screw by turning it counterclockwise. Obtain the replacement gas type
setting screw from the kit and screw it into
place (red for propane and blue for natural gas).
Tighten the gas type setting screw by turning it
clockwise. Replace the plastic protecting cap.
Honeywell Millivolt Gas Valve
Adjusting Knob
Regulator Cap
Conversion screw
(blue natural gas;
red LP/propane gas)
Figure 67
b. Attach manometer to the manifold side
pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa)
for natural gas, and 10.0 inches water column
(2.49 kPa) for propane gas.
c.
Convert the pilot orifice as follows (refer to
Figures 64, 65 and 66 ):
Note - Use extra care not to engage the orifice
strip with the 7/16" open end wrench (contacting the orifice strip could cause strip distortion
rendering the pilot inoperative). Also avoid
wrench contact to any of the other pilot parts.
Use a 7/16" open end wrench and turn the pilot
hex fitting counter-clockwise 1/4 turn. (
to Figure 64 ).
Note - The orifice strip tab may be randomly
located on any side of the hex fitting.
d. Push the orifice strip tab all the way against
the hex fitting to align the appropriate gas type
orifice
(refer to Figures 65 and 66)
of gas for which the pilot is set, is, the gas type
shown on the tab.
e. Retighten, clockwise, the pilot hex fitting
until the pilot hood aligns with the thermocouple and thermopile as indicated by the
arrows shown in
Figure 64
.
refer
. The type
Step 6. Electronic Appliances -
Honeywell Systems
See
Figure 68
and the instructions provided
with the kit. Remove the slotted cap screw, oring, pressure-regulating adjusting screw and
spring. Retain all parts for possible later use.
Install new components from the kit. Black cap
and red spring for propane gas units. Silver cap
and stainless steel spring for natural gas units.
Before installing the cap, attach manometer to
the manifold side pressure test fitting and adjust
screw until pressure reads 3.5 inches water
column (0.87 kPa) for natural gas, and 10.0
inches water column (2.49 kPa) for propane gas.
CONTROL
I
G
N
I
T
E
Manifold
Pressure
Test Port
Slotted
Cap
OFFION
Inlet Pressure Test Port
I
S
P
Adjusting
Screw
Spring
Figure 68
See
Figure 69
follows: Remove the ignitor assembly retainer
clip, and carefully remove the ignitor assembly. Exercise extreme care to prevent dam-age to or breakage of the ignitor assembly.
Remove the screw securing the pilot assembly
to its mounting bracket. Back off the flare nut
at the end of the pilot gas line to free the pilot
assembly from the gas line.
Remove the pilot orifice and replace it with the
one provided with the conversion kit. Reinstall
the pilot assembly by reversing the steps detailed here.
When reinstalling the ignitor assembly, use
extreme care to prevent damage and breakage. Do not apply any leverage to the ignitor
assembly while restoring the retainer clip to
its original position.
and replace the pilot orifice as
Pilot
Orifice
Retaining
Flare Nut
Pilot
Assembly
Ignitor
Assembly
Clip
Note: If the ignitor is damaged, a replacement
kit is available - order Catalog Number 87L54.
Figure 69
All Models
Step 7. Remove the orifice from the mani-
fold and replace it with the one provided with
the kit. See the following table for orifice sizes
for natural and propane models
. Figure 70
illustrates the orifice.
D, DT,
DR Series
Orifice Size
Natural
Propane
5000.090 in.#54
600#36#52
800#330.065 in.
Figure 70
Step 8. Reassemble all removed components
by reversing the procedures outlined in the
preceding steps. Use pipe joint compound or
Teflon tape on all pipe fittings before installing
(ensure propane resistant compounds are used
in propane applications, do not use pipe joint
compounds on flare fittings).
Step 9. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance.
Step 10. Turn on gas supply and test for gas
leaks.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.