Tekmar tekmarNet 4 Setpoint Control 161 Wiring Brochure

Page 1
- Wiring Brochure
W 161
tekmarNet®4 Setpoint Control 161
Overview
1
Information
Brochure
to match
application
2
Application
Brochure
Design your
mechanical
applications
3
Rough In
Wiring
Rough-in
wiring
instructions
The following brochure describes how to wire the tekmarNet®4 (tN4) Setpoint Control 161. The 161 has a single output for heat. The 161 has one sensor input.
tN4 Network
24 V (ac) Power
Sensor Input
Power: Relays:
DIP
Switches
Jumper
For product instructions see brochure
Use at least 194°F (90°C) conductors
tN4 Setpoint Control 161
One Stage Heat
24 V ±10% 50/60 Hz 1.7 VA 24 V (ac) 2 A
/
12/08
Relay
Contact
Cut jumper to isolate relay
Feb 2006 Lot 1948
Meets Class B: Canadian ICES FCC Part 15
161
4
Wiring
Brochure
Wiring and
installation of
Table of Contents
specific control
Definitions ....................................................................... 2
5
Data
Brochure
Control settings
and sequence of
operation
Rough-In Wiring .............................................................2
Remove the Wiring Cover ...............................................3
Mounting the Setpoint Control ........................................3
Wiring Symbols ...............................................................4
Electrical Drawings .........................................................4
6
Job
Record
Record settings &
wiring details for
future reference
1 of 12 © 2008 W 161 - 12/08
Wiring the Setpoint Control .............................................7
Troubleshooting the Wiring .............................................9
Testing the Wiring .........................................................10
Technical Data ..............................................................12
Page 2
Defi nitions
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product.
– Caution: Refer to accompanying documents.
– Caution: Refer to accompanying documents.
INSTALLATION
CATEGORY II
– Local level appliances.
Caution
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit. Do not attempt to service the control. Refer to qualified personnel for servicing. There are no user serviceable parts. Attempting to do so voids warranty and could result in damage to the equipment and possibly even personal injury or death.
Rough-In Wiring
Choose the placement of the setpoint control early in the construction process to enable proper wiring during rough-in.
Consider the following:
Interior Wall. Keep dry. Avoid potential leakage onto the control. RH 80% to 88°F (31°C),
down to 50% from 104 to 122°F (40 to 50°C). Non-condensing environment. No exposure to extreme temperatures beyond 32 - 122°F (0 - 50°C). No draft, direct sun, or other cause for inaccurate temperature readings. Away from equipment, appliances, or other sources of electrical interference. Easy access for wiring, viewing, and adjusting the display screen. Approximately 5 ft. (1.5 m) off the finished floor.
Use standard 18 AWG wire for the control power, relays, tN4 and sensor connections.
Refer to the diagram below to determine the number of conductors to run from each piece of equipment to the control location.
© 2008 W 161 - 12/08 2 of 12
Page 3
2 Cond. / 18 AWG
2 Cond. / 18 AWG
Sensor
Pump or Valve
Note: When multiple wires
run to the same equipment location, wiring conductors can share one wire jacket.
3 Cond. / 18 AWG
R C tN4
Zone Manager
Remove the Wiring Cover
To remove the wiring cover:
Place a small slot screwdriver or similar tool into the slot located on the top of the control.
While pushing against the plastic tab, pull the top of the front cover so that it pivots around the bottom edge of the control’s base.
1
2
Remove cover
Push tab
Item
u
en
M
Mounting the Setpoint Control
If a single gang switch box is used, an Adaptor Plate 007 is required to mount the control to the box.
Fasten the base of the control to the adaptor plate. Feed the wiring through the openings in the back of the adaptor plate and control. Use the upper and lower screw holes to fasten the adaptor plate to the box.
3 of 12 © 2008 W 161 - 12/08
Page 4
23/8”
(60 mm)
screwhole
If a switch box was not used, mount the control directly to the wall.
Feed the wiring through the openings in the back of the control. Use screws in the screw holes to fasten the control to the wall. At least one of the
screws should enter a wall stud or similar rigid material.
Mounted on switch box Mounted on wallboard
007 Adaptor
Plate
Control
Control
Base
Wiring Symbols
Dry contact switch. Operates a device.
tekmarNet®4
Do not apply power to these terminals. Serious control damage will result.
1
3
/4
(83 mm)
Stud
Switch Box
Control
Control
Base
23/8”
(60 mm)
screwhole
Stud
Wall
Electrical Drawings
The electrical drawing examples on the following pages show the 161 in common applications. Choose the drawing that most accurately depicts the components in your system and use that drawing as a guide to aid in wiring your system.
These are only concept drawings, not engineered drawings. They are not intended to describe a complete system nor any particular system. It is up to the system designer to determine the necessary components for and configuration of the particular system being designed including additional equipment isolation relays (for loads greater than the controls specified output ratings) and any safety devices which in the judgement of the designer are appropriate in order to properly size, configure and design that system and to ensure compliance with building and safety code requirements.
© 2008 W 161 - 12/08 4 of 12
Page 5
Electrical Application 161 E1
Description:
Setpoint Control used with tN4 System Zone Manager.
161
Meets Class B:
Canadian ICES
Feb 2006
Lot 1948
FCC Part 15
24 V ±10% 50/60 Hz 1.7 VA
24 V (ac) 2 A
Power:
Relays:
/
tN4 Setpoint Control 161
One Stage Heat
161
Cut jumper to
isolate relay
For product instructions see brochure Use at least 194°F (90°C) conductors
Sensor
Heat Zone
tN4 C R W
Zone Manager
Zone Pump
or
Valve
5 of 12 © 2008 W 161 - 12/08
Page 6
Electrical Application 161 E2
Description:
Setpoint Control used as a stand alone device. Relay 1 is used to cycle a pump to provide heat.
Legend:
P1 = Pump cycled for heating
161
Meets Class B:
Canadian ICES
Feb 2006
Lot 1948
FCC Part 15
24 V ±10% 50/60 Hz 1.7 VA
24 V (ac) 2 A
Power:
Relays:
/
tN4 Setpoint Control 161
One Stage Heat
161
Relay 003
3
4
5
6
Cut jumper to
isolate relay
2
1
8
7
For product instructions see brochure Use at least 194°F (90°C) conductors
P1
N L
External Class 2
Transformer
24 V (ac)
© 2008 W 161 - 12/08 6 of 12
RC
Sensor
Page 7
Wiring the Setpoint Control
Power 24 V (ac) Terminals 2, 3
Wire 24 V (ac) to terminals C and R.
If a Zone Manager is used:
Connect C on the setpoint control to C on the proper zone of the Zone Manager. Connect R on the setpoint control to R on the proper zone of the Zone Manager.
If a 24 V (ac) transformer is used:
Connect C on the setpoint control to C on the transformer. Connect R on the setpoint control to R on the transformer.
tN4 C R Com S1
12345
Setpoint Control
tN4 C R W
Zone Manager
tN4 Communication Terminals 1, 2
Wire the tN4 communication to terminals tN4 and C.
If a Zone Manager is used:
Connect tN4 on the setpoint control to the tN4 on the proper zone of the Zone Manager. The C terminal is already connected.
If a Zone Manager is not used:
Connect tN4 on the setpoint control to the tN4 terminal on another tN4 device on the same tN4 bus.
Connect C on the setpoint control to the C terminal on another tN4 device on the same tN4 bus.
tN4 C R Com S1
12345
Setpoint Control
tN4 C R W
Zone Manager
7 of 12 © 2008 W 161 - 12/08
Page 8
Relay 1 Terminals 6, 7
Relay 1 is used to switch the heat.
If a Zone Manager is used:
Connect Relay 1 to W on the proper zone on the Zone Manager.
If a Zone Manager is not used:
Determine if the jumper must be cut. When the jumper is not cut, Relay 1 is internally powered through terminal 3. When the jumper is cut, Rh and Relay 1 is an isolated switch.
RRhR1
367
Setpoint Control
tN4 C R W
Zone Manager
Sensor Input Terminals 4, 5
The sensor is connected to the setpoint control on terminals Com and S1.
Connect sensor to terminals S1 and Com.
Do not apply power
sensors and / or setpoint control will result!
tN4 C R Com S1
12345
Setpoint Control
to terminals S1 and Com, permanent damage to the
Universal
Sensor
Do Not Apply Power
© 2008 W 161 - 12/08 8 of 12
Page 9
Troubleshooting the Wiring
General
The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac), 0 - 2,000,000 Ohms, and testing for continuity is essential to properly test the wiring and sensors.
7
###
R1
6
Rh
tN4 C R Com S1
12345
9 of 12 © 2008 W 161 - 12/08
Page 10
Testing the Wiring
Testing 24 V (ac) Power Supply
1. Remove the front cover from the setpoint control.
2. Use an electrical test meter to measure (ac) voltage between the R and C
terminals. The reading should be 24 V (ac) +/– 10%.
3. Install the front cover.
Testing the Relay
1. Remove the front cover from the setpoint control.
2. Disconnect the wires from the relay.
3. Use an electrical test meter and check for continuity across the relay.
When the relay symbol is displayed in the LCD, there should be continuity.
When the relay symbol is not displayed in the LCD, there should be no continuity.
4. Reconnect the wires to the relay.
5. Install the front cover on the setpoint control.
161 LCD Display
Relay 1
© 2008 W 161 - 12/08 10 of 12
Page 11
Testing the Sensor
To test the sensor, the actual temperature at the sensor location must be measured.
Use a good quality digital thermometer with a surface temperature probe for ease of use and accuracy. Where a digital thermometer is not available, place a spare sensor alongside the one to be tested and compare the readings.
1. Remove the front cover from the setpoint control.
2. Disconnect the wires from the sensor.
3. Test the sensor’s resistance according to the instructions in the sensor Data
Brochure D 070, D 074 or D 079.
4. Reconnect the wires.
5. Install the front cover on the setpoint control.
Testing the tN4 Network
To test the tN4 Network, check the wires for continuity.
1. Remove the front cover from the setpoint control.
2. Disconnect the two wires (tN4 and C) at one end and connect them together.
3. Go to the other end of the wires and disconnect them.
4. Using an electrical test meter, check for continuity.
5. Reconnect the wires.
6. Install the front cover on the setpoint control.
11 of 12 © 2008 W 161 - 12/08
Page 12
Technical Data
tekmarNet®4 Setpoint Control 161 One Stage Heat
Control Microprocessor PID control;
This is not a safety (limit) control
Packaged Weight 0.46 lb. (210 g)
Enclosure White PVC plastic
Dimensions 2-7/8” H x 2-7/8” W x 13/16” D (73 x 73 x 21 mm)
Approvals
Ambient Conditions Indoor use only, 32 to 122°F (0 to 50°C)
Power Supply 24 V (ac) ± 10% 50/60 Hz, 1.7 VA, NEC / CEC Class 2
Relays 24 V (ac) 2 A
Sensors NTC thermistor, 10 k @ 77°F (25°C ± 0.2°C) ß = 3892
– Included Universal Sensor 071
– Optional tekmar type #070, 071, 072, 073, 076, 077, 078, 079, 082,
CSA C US, CSA/UL 61010-1, meets Class B: ICES and FCC Part 15
92% RH up to 104°F (40°C), 50% RH if > 104°F (40°C) Altitude <9840 feet (3000 m), Installation Category II, Pollution Degree 2
083, 084
The installer must ensure that this control and its wiring are isolated and / or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and / or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
tekmar Contro l System s Ltd., Cana da tekmar Contro l System s, Inc., U.S. A.
Head O ffic e: 5100 Silver Sta r Road Vernon, B.C. Can ada V1B 3K4 (250) 54 5-7749 Fax. (2 50) 545-0650 Web Site: w ww.te kmar contr ols.com
All specifications are subject to change without notice
12 of 12 W 161 - 12/08.
Product design, soft ware and literature are Copyright © 2008 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
Loading...