05/15/00 00136New Manual - CE Certified Console 2.03
Rev.- 1
Mid-T ech, Auto-Range, & T ASC ar e all registered trademarks of Midwest Technologies, Inc.
II
CE & STANDARDVERSION
ARC 6000
98-05017
Rev.- 1
TABLE OF CONTENTS
CHANGE LOG ..................................................................................................................................................................... II
TABLE OF CONTENTS ...................................................................................................................................................... III
1.0. SWITCHES AND CONTROLS ................................................................................................................................... 1-1
1.1. POWER SWITCH ................................................................................................................................................ 1-1
1.6. NOT USED ........................................................................................................................................................... 1-6
2.0. CALIBRATION AND SET UP .................................................................................................................................... 2-1
2.1. CHANGING THE APPLICATION PROGRAM ................................................................................................... 2-1
2.2. ENGLISH, METRIC OR METRISH UNITS ........................................................................................................ 2-1
2.2.1. UNITS FOR EACH POSITION (LIQUID APPLICATOR ONLY) .............................................................. 2-1
2.2.2. CHANGING UNITS (LIQUID APPLICATOR ONLY) .............................................................................. 2-2
2.8. SETTING THE "HOLD/CLOSE" RESPONSE OF THE FLOW CONTROL VALVE ......................................... 2-10
2.8.1. STATUS SWITCH ................................................................................................................................... 2-10
2.8.2. ALL BOOMS "OFF" ................................................................................................................................ 2-10
2.9. SETTING THE GROUND SPEED OVERRIDE (GSO) VALUE. ......................................................................... 2-11
2.10. SETTING THE FIELD AREA ALARM ........................................................................................................... 2-11
4.1. FLUSHING AND CLEANING ............................................................................................................................. 4-1
4.2. CONTROL CONSOLE ........................................................................................................................................ 4-1
A-0. APPENDIX A - DRAWINGS .......................................................................................................................................A-1
A-1 ARC FLOW/PRESSURE BASED - WIRING DIAGRAM ....................................................................................A-2
A-2 ARC FLOW/PRESSURE BASED - PLUMBING DIAGRAM ..............................................................................A-3
A-3 ARC SERVICE FORM ........................................................................................................... .............................A-4
C.5.2. BOOM CONTROL SWITCHES AND INTERFACE .................................................................................C-6
SHADED TOPICS RELATE TO GRANULAR APPLICATION ONLY!
CE & STANDARD VERSION
IV
ARC 6000
1.0. SWITCHES AND CONTROLS
98-05017
Rev.- 1
Flow
RATE
.
Gal./
MID-TECH
MIDWEST TECHNOLOGIES, INC.
4
ARC-6000
-Ac
¨
Automatic
Rate Controller
1
123456789
BOOMS
2
ONOPERATEINC.
OFFSET- UPDEC.
%Rate
Product Vol.
Total Area
Field AreaImpl.Width
Speed
Scan
Test
Speed
DISPLAY SELECTOR
3
Application Rate
Total Applied
Distance
Prime
5
1.1. POWER SWITCH
The power switch controls power to the console. The console has an "Auto Power Down" feature which powers the console
off after an operator selectable time (default is 30 min) has elapsed. The console has a nonvolatile memory so it "remembers"
the constants and data previously entered, even if the power is removed.
NOTE: The “Auto Power Down Feature is only available on the CE version of the console (CE designation label on back of
console).
1.2. MODE SELECTOR “OPERATE / SETUP” SWITCH
The Mode Selector switch (upper right center) is used to switch between the OPERATE and SETUP modes of the control
console. When applying materials, this switch must be in the “OPERATE” position. The “SET- UP” position is used for
entering information into the console. In the SETUP Mode an “Err” message will appear if a position which can not be
programmed has been selected.
1.3. INC / DEC SWITCH
The INC/DEC switch (upper right corner) is used to change the values appearing in the display. The INC/DEC switch is
usable in either the OPERATE or SETUP Mode.
This switch is also used to zero the accumulated areas, distance, and total applied by selecting the desired display and
holding this switch in the “DEC” position until the display resets to zero, (approximately 3 sec.).
Use this switch to reset the full load condition while displaying Product Vol. in the operate mode. Holding the switch in the
"INC" position until the display shows the programmed, full load value.
1-1
CE & S
TANDARD VERSION
98-05017
123456789
%Rate
DISPLAY SELECTOR
Speed
Field AreaImpl.Width
Distance
Test
Speed
Prime
Total Applied
Application Rate
Scan
Total Area
Product Vol.
BOOMS
OFFSET- UP
ONOPERATE
Rev.- 1
1.4. DISPLAY SELECTOR
The Display Selector (right center) is used to select and display the various console functions.
SPEED: The current vehicle speed in tenths of a Mile per Hour.
FIELD AREA: Accumulated Area, in hundredths of an Acre.*
TOTAL AREA: Accumulated Area, in Acres.*
PRODUCT V OL.: Amount of product aboard the vehicle. Resets to a pre-programmed, full load by holding the INC
switch up with ground speed zero. Ground speed zero also allows setting any value using the INC/DEC switch. Value
counts down as the product is applied, an alarm sounds with ten percent left aboard.**
% RATE: The percent of programmed application rate at which the product is being applied. This percentage can be
changed up or down a preset amount by operating the INC/DEC switch.***
APPLICATION RATE: The desired application rate can be set with the INC/DEC switch when the ground speed is zero
or all booms are OFF.** Once application has commenced, and metered discharge is established, the actual measured
application rate will be displayed here. Also used to set the controlvalve to manual operation.
TOTAL APPLIED: The actual volume applied, as measured by the flowmeter or pressure sensor.*
IMPL. WIDTH: The active boom width in tenths of Feet. Depends on the actual boom sections selected “ON”.
DISTANCE: The accumulated distance in Feet, Miles after 5,280 Ft.*
PRIME: This position is used to lock the control valve open during main pump priming on a liquid system. Initially the
display will show a series of five dashes. Hold INC switch up for three seconds to lock the control valve fully open. The
display will read OPEN. Switching away from PRIME will cause the control valve to drive CLOSED. When operating
in the pressure based (Psi) mode, the current boom pressure is displayed here.
TEST SPEED: The speed the console will use for stationary tests of the sprayer. Use the INC/DEC switch to change this
value.**
SCAN: The display will scan SPEED, FIELD AREA, PRODUCT VOLUME, APPLICATION RATE, TOTAL APPLIED,
and, if in pressure based mode, BOOM PRESSURE. The display will hold at each position for approximately two
seconds before automatically cycling to the next.
NOTES: * Totals can be zeroed in this mode.
** Values are programmable in this mode.
CE & STANDARD VERSION
***Values changeable by a % increase or decrease.
1-2
ARC 6000
12345678
%Rate
DISPLAY SELECTOR
Speed
Field AreaImpl.Width
Distance
Test
Speed
Prime
Total Applied
Application Rate
Scan
Total Area
Product Vol.
BOOMS
OFFSET- UP
ONOPERATE
98-05017
Rev.- 1
OPERATE
Flow
RATE
Gal./
Product Vol.
Total Area
MID-TECH
Field AreaImpl.Width
MIDWEST TECHNOLOGIES,INC.
Speed
ARC-6000
Automatic
-Ac
Rate Controller
.
%Rate
Test
Speed
Application Rate
Total Applied
Distance
Prime
¨
Scan
ONOPERATEINC.
SET- UP
OFFSET- UPDEC.
%Rate
Application Rate
Product Vol.
Total Area
Field AreaImpl.Width
Speed
Prime
Scan
Test Speed
DISPLAY SELECTOR
123456789
BOOMS
Total Applied
Distance
DISPLAY SELECTOR
1.4.2. DISPLAY SELECTOR FUNCTIONS -SET UP MODE (LIQUID APPLICATION)
SPEED: Ground Speed Override Value (GSO), in tenths of a MPH. Use the INC/DEC switch to change.**
FIELD AREA: Select area alarm. For example; if the alarm is set (using the INC/DEC switch) to 10.00, then
the display will flash and the console will beep when each increment of ten acres is reached. The display will
react for about three seconds and then stop until the next increment is reached.**
TOTAL AREA: Err, No function in the SETUP mode.
PRODUCT V OLUME: Use the INC/DEC switch to set the full tank capacity of the vehicle.**
% RATE: The percent of change in the application rate for each actuation of the INC/DEC switch, when
application operations are underway. Use the INC/DEC switch to change.**
APPLICATION RATE: A pressure sensor correction factor which is used when applying products with a specific
gravity different from that of water (see chart on page 2-7). The correction factor is only visible in Psi mode. Reads ERR
when in STnrd L or rEFLO L modes. Use the INC/DEC switch to change. Maximum is 1.50, minimum is 0.50**
TOTAL APPLIED: This is the pressure sensor or flowmeter calibration number. Use the INC/DEC switch to
change. Note: Must have all booms ON when in the REFLOW Mode.**
WIDTH: Individual boom section widths in inches. The display will cycle through the individual boom sections in
order, unless a particular boom switch is activated while the boom master switch is ON. Use the INC/DEC switch to
change.**
DISTANCE: The current Distance Calibration Number. Use the INC/DEC switch to change.**
PRIME: Holding the INC switch up for over ten seconds establishes LIQUID operation, either STnrd (standard), PSi
(Pressure) or rEFLO (reflow). Holding the DEC switch down for over ten seconds establishes GRANULAR operation,
either STnrd (standard) or SPLit (split drive). Current setting is shown in the display, Pump L is liquid, Pump C is
granular.
TEST SPEED: The current Test Speed in tenths of a Miles per Hour. Use the INC/DEC switch to change this value.**
SCAN: Err, No function in the SETUP mode.
NOTES: * Totals can be zeroed in this mode.
** Values are programmable in this mode.
***Values changeable by a % increase or decrease.
SPEED: The current vehicle speed in tenths of a Mile per Hour.
FIELD AREA: Accumulated Area, in hundredths of an Acre.*
TOTAL AREA: Accumulated Area, in tenths of an Acre.*
PRODUCT V OL.: Amount of product aboard the vehicle. Resets to a pre-programmed, full load by holding theINC
switch up with ground speed zero. Also allows setting any value using the INC/DEC switch. Value counts down as the
product is applied, an alarm sounds with ten percent left aboard.**
% RATE: The percent of programmed application rate at which the product is being applied. This percentage can be
changed up or down a preset amount by operating the INC/DEC switch.***
APPLICATION RATE: The desired application rate can be set with the INC/DEC switch when the ground speed is zero
or all booms are OFF.** Once application has commenced, and metered discharge is established, the actual measured
application rate will be displayed here. Also used to set the control valve to manual operation.
TOTAL APPLIED: The actual volume applied, as measured by the rate sensor. Rounds to tons after accumulating
19,999 pounds.*
IMPL. WIDTH: The active boom width in tenths of Feet. Depends on the actual boom sections selected “ON”.
DISTANCE: The accumulated distance in Feet, Miles after 5,280 Ft. (Accumulates only when selector switch is in this
position or when applying product)*
PRIME: This position is used to lock the control valve open. It can be used in a granular application to unload the
vehicle at its maximum discharge rate. Initially the display will show a series of five dashes. Hold INC switch up for
three seconds to lock the control valve fully open. The display will read OPEN. Switching away or toggling the DEC
switch will cause the valve to CLOSE.
TEST SPEED: The speed the console will use for stationary tests of the sprayer. Use the INC/DEC switch to change this
value.**
SCAN: The display will scan SPEED, FIELD AREA, PRODUCT VOLUME, APPLICATION RATE and TOTAL
APPLIED. The display will hold at each position for approximately two seconds before automatically cycling to the
next.
NOTES: * Totals can be zeroed in this mode.
CE & STANDARD VERSION
** Values are programmable in this mode.
***Values changeable by a % increase or decrease.
1-4
ARC 6000
12345678
%Rate
DISPLAY SELECTOR
Speed
Field AreaImpl.Width
Distance
Test
Speed
Prime
Total Applied
Application Rate
Scan
Total Area
Product Vol.
BOOMS
OFFSET- UP
ONOPERATE
98-05017
Rev.- 1
OPERATE
Flow
RATE
.
Gal./
Product Vol.
Total Area
MID-TECH
Field AreaImpl.Width
MIDWEST TECHNOLOGIES,INC.
Speed
¨
Scan
-Ac
%Rate
Test
Speed
ARC-6000
Automatic
Rate Controller
Application Rate
Total Applied
Distance
Prime
ONOPERATEINC.
SET- UP
OFFSET- UPDEC.
%Rate
Application Rate
Product Vol.
Speed
Scan
Test
Speed
DISPLAY SELECTOR
Total Applied
Prime
Total Area
Field AreaImpl.Width
123456789
BOOMS
Distance
DISPLAY SELECTOR
1.4.4. DISPLAY SELECTOR FUNCTIONS-SET UP MODE (GRANULAR APPLICATION)
SPEED: Ground Speed Override (GSO) Value, in tenths of a MPH, INC/DEC switch changes.**
FIELD AREA: Select area alarm. For example; if the alarm is set (using the INC/DEC switch) to 10.00, then the display
will flash "FIELD AREA" and the console will beep when each increment of ten acres is reached. The display will
react for about three seconds and then stop until the next increment is reached.**
TOTAL AREA: Err, No function in the SETUP mode.
PRODUCT V OLUME: Use the INC/DEC switch to set the full load capacity of the vehicle.**
% RATE: The percent of change in the application rate for each actuation of the INC/DEC switch, when application
operations are underway. Use the INC/DEC switch to change the value.**
APPLICATION RATE: Product density. The default value is 65.0. Use the INC/DEC switch to set the measured
product density.**
TOTAL APPLIED: This is the rate sensor calibration number. Calculate and use the number of sensor pulses per cubic
foot as the initial setting. Use the INC/DEC switch to change. Must have all booms ON when in the SPLIT Drive
Mode**
WIDTH: Individual boom section widths in inches. The display will cycle through the individual boom sections in
order, unless a particular boom solenoid switch is activated. Use the INC/DEC switch to change.**
DISTANCE: The current Distance Calibration Number. Use the INC/DEC switch to change.**
PRIME: Holding the DEC switch down for over ten seconds establishes GRANULAR operation, either STnrd (standard)
or SPLit (split drive). Holding the INC switch up for over ten seconds establishes LIQUID operation, either STnrd
(standard) or rEFLO (reflow). Current setting is shown in the display, Pump L is liquid, Pump C is granular.
TEST SPEED: The current Test Speed in tenths of a Mile per Hour. Use the INC/DEC switch to change this value.**
SCAN: Err, No function in the SETUP mode.
** Values are programmable in this mode.
***Values changeable by a % increase or decrease.
NOTES: * Totals can be zeroed in this mode.
1-5
CE & S
TANDARD VERSION
98-05017
ARC 6000
Rev.- 1
1.5. BOOM SECTION “ON/OFF” INDICATORS
The boom section on/off indicators (lower right, labeled “BOOMS”), indicate which boom sections have been selected by
the operator. When a boom has been selected, its indicator will light. Boom position number 1 is to the left. There is a
maximum of nine boom sections available.
1.6. NOT USED
1.7.--STATUS SWITCH
A status switch can be used to override the ARC control. The switch must present a positive voltage (+12.0 VDC) status on
the green (or white) wire of the Boom Interface Cable. So long as this condition is present, the control console will operate
normally. If the voltage is interrupted, the control console will automatically stop controlling. At the same time, the control
console will either "HOLD" or "CLOSE" the control valve, depending on the response selected by the operator. (See Section
2.9.1).
The intent of this feature is to allow the operator to control the operation of the control valve through the normal operation of
the vehicle. The Status switch input may be used to sense the "ON"/"OFF" condition of the main vehicle pump switch, a
separate Status switch, or, an external switch may sense an implement "UP"/"DOWN" condition. The Status switch can
often be used to lessen the operator's work load.
1.8. GROUND SPEED OVERRIDE (GSO) SWITCH
If the ARC system was purchased with an optional MID-TECH boom switch box, the Ground Speed Override switch is
already installed. If a MID-TECH switch box is not used to control the booms, an optional externally mounted Ground
Speed Override switch can be used to temporarily operate the sprayer (or spreader) using a pre-selected Minimum "(GSO)
Speed" rather than the actual speed registered by the Ground Speed Sensor. The override feature is used to bring the
applicator on line quickly when starting from a dead stop or to maintain an adequate application pattern when the vehicle is
maneuvering at very low ground speeds. It can also be used to allow the operator to flush or empty the vehicle from the cab,
while stopped.
The control console operates normally so long as the Ground Speed Override switch condition is open (OFF). Whenever the
Override switch is closed (ON) and the actual ground speed is less than "GSO Speed", the control console automatically
selects the "GSO Speed" value to control application rate. As soon as the switch reverts to its normally open (OFF) condition, or the actual ground speed increases above the preset "GSO Speed", the control console will adjust the rate on the basis
of the actual ground speed.
CAUTION: Controlling application rates based on "GSO Speed" is not as accurate as using the actual ground speed.
When Ground Speed Override is being used and the true ground speed is less than the "GSO Speed", the console will
sound a warning beep and the display will flash a "Too Slow" message to warn the operator of over application.
CE & STANDARD VERSION
1-6
ARC 6000
2.0. CALIBRATION AND SET UP
NOTE: PLEASE READ THROUGH THE FOLLOWING SECTIONS COMPLETELY BEFORE YOU BEGIN
CALIBRATION!
The control console needs to be calibrated and programmed with certain information before it is ready to be used. First, the console
needs to be programmed with the specific details of your applicator (i.e. Application Rates, Boom Widths, Test Speed, etc.). Next,
the rate sensor (flowmeter) and ground speed sensors both need to be calibrated. The calibration and set up processes are not
difficult, however; they must be followed precisely in order to get the maximum available accuracy out of the system.
First, BE SURE THE CONSOLE IS SELECTED TO THE APPLICATION PROGRAM YOU WANT. The Choices are;
Liquid Pressure, Liquid standard, Liquid reflow, Granular standard, and Granular split drive.
2.1. CHANGING THE APPLICATION PROGRAM
To view the program currently selected, set the Mode switch to "SETUP" and the Display Selector to "PRIME".
Pump L PSi is LIQUID PRESSURE application (normal pressure based spraying)
Pump L STnrd is STANDARD LIQUID application (normal flow based spraying)
Pump L rEFLO is LIQUID REFLOW application (for use on some European sprayers)
Pump C STnrd is standard GRANULAR application (single conveyor spreaders)
Pump C SPLit is GRANULAR SPLIT DRIVE application (dual conveyor spreaders, air delivery spreaders)
98-0501
Rev.- 1
To change programs, hold the INC switch up to set LIQUID and cycle between standard, reflow, and pressure. Hold the DEC
switch down to set GRANULAR and cycle between standard and split drive. The application remaining in the display when the
INC/DEC switch is released is the program selected. If you have a question about which application to use, check with your
supplier or call MID-TECH Customer Service.
2.2. ENGLISH, METRIC OR METRISH UNITS
When operating as a LIQUID applicator the control console is capable of displaying three separate units of measure, English,
Metric and Metrish. Metrish is the same as Metric, except area is measured in Acres, thus the term Metrish. Operating as a
granular applicator, the display is limited to English units of measurement.
2.2.1. UNITS FOR EACH POSITION (LIQUID APPLICATOR ONLY)
POSITIONENGLISH (US)METRICMETRISH
SpeedMiles/Hour (MPH)Kilometers/Hour (KPH)Kilometers/Hour(KPH)
Field AreaAcres ( Ac)Hectares ( Ha)Acres ( Ac)
Total AreaAcres ( AcHectares ( Ha)Acres ( Ac
Product Vol.Gallons (Gal.)LitersLiters
Appl. RateGallons/Acre(Gal.-Ac)Liters/Hectare (Liters-Ha)Liters/Acre (Liters-Ac)
Total AppliedGallons (Gal.)LitersLiters
Impl. WidthInches - Feet (In., Ft.)MetersMeters
DistanceFeet - Miles (Ft.)*Meters - Kilometers*Meters - Kilometers*
Test SpeedMiles/Hour (MPH)Kilometers/Hour (KPH)Kilometers/Hour(KPH)
* No units displayed after roll over of feet to miles or meters to kilometers
2-1
CE & STANDARD VERSION
98-05017
ARC 6000
Rev.- 1
2.2.2. CHANGING UNITS (LIQUID APPLICATOR ONLY)
To change units, set the Mode switch to “OPERATE” and the Display Selector to “SPEED”. The current speed units will be
displayed. Holding the INC/DEC switch up or down (see chart) until the display changes (approximately 5 sec.) will set the units
accordingly.
UNITS INC./DEC. Switch
English to MetricDOWN
Metric to EnglishDOWN
English to MetrishUP
Metrish to EnglishDOWN
NOTE: Metric to Metrish is not allowed. Convert to English first and then to Metrish.
2.3. SETTING APPLICATION RATE
The ARC system is designed to maintain a constant, pre-selected application rate. In order for the control console to do this, the
operator must enter the desired application rate.
A. Set the console switches to the following positions:
PowerON
Mode SelectorOPERATE (Application rate is set in the Operate Mode!!!)
Display SelectorAPPLICATION RATE
Ground SpeedZERO
All BoomsOFF
The display will show the current application rate.
B. Use the INC/DEC switch to set the value displayed to the desired rate.
C. Setting the APPLICATION RATE to 0.0 will shut off the flow control function.
2.4. SETTING THE % RATE CHANGE
This feature allows the operator to change the application rate “On The Go”. Application rate is changed with a simple
actuation of the INC/DEC switch. The amount of change each switch actuation makes is proportional to the value programmed into this position, (e.g. 20 =20% change in the target rate). For example, if the liquid application rate is set at 10.0
gallons per acre, a single actuation of the INC switch will cause the valve to control flow at the rate of 12.0 gallons per acre
(10.0 + 20% = 12.0).
A. Set the console switches to the following positions:
PowerON
Mode SelectorSETUP
Display Selector% RATE
The display will show the current % change value.
B. Use the INC/DEC switch to set this number to the desired % change value.
2.5. SETTING BOOM WIDTHS
The MIDWEST TECHNOLOGIES control console is designed to automatically compensate for changes in the swath width,
caused by turning on or off boom sections. For the console to automatically respond to changes in swath width, it needs to
know the size of each boom section. Use the following procedure to set boom section widths.
CE & STANDARD VERSION
2-2
ARC 6000
A. Set the console to the following positions;
PowerON
Mode SelectorSET- UP
Display SelectorIMPL. WIDTH
All Boom Solenoid Switches (external)OFF
The display will cycle through each boom position (1 through 9) and display its current width in inches.
B. As each boom position appears on the display, use the INC/DEC switch to set the display to the number of inches
covered by that boom. Repeat for each section.
NOTE: Individual boom widths are entered in inches. For example; for a liquid boom with 7 nozzles on
30" spacings, enter 180 for that boom. There is no need to convert to feet, the control console does that
automatically when it is switched back to the OPERATE MODE.
C. Set all unused boom sections to a width of zero “0” inches. This will insure that an accidental boom switch ON will not
affect the control console.
D. The boom width is now set. Turn all boom switches to the ON position and return to the OPERATE Mode, the new
total boom width will be displayed in feet. If this does not agree with your total applicator width, check the individual
boom widths, (steps B and C).
98-0501
Rev.- 1
2.6. APPLICATION RATE SENSOR CALIBRATION
The control console must be calibrated for the flowmeter, pressure sensor, or rate sensor being used. The calibration number
required by the control console is the actual number of electrical pulses per unit volume generated by the sensor, or, for the pressure
sensor, the gallons per acre rating of the nozzles being used. If you have any doubts as to the accuracy of the flow sensor
readings, a field calibration/catch test should be performed using the actual product solution. (see section 2.6.1.4)
2.6.1. CALIBRATING THE LIQUID APPLICATION
Verify that the correct application program has been selected (see section 2.1.)!
If in the Psi mode, check the correction factor. It should be set to 1.0 during the calibration routine. To check the correction
factor, set the Display Selector to APPLICATION RATE, set the Mode Selector switch to SETUP. Use the INC/DEC
switch to set the correction factor if necessary.
2.6.1.1. DETERMINING THE FLOWMETER INITIAL CALIBRATION NUMBER
FLOWMETERS are calibrated for water at the factory. This number is accurate enough for most applications. However, the
actual flow characteristics may differ due to plumbing or other factors.
* Raven flow meters, use the factory calibration number divided by 10. All other flowmeters use the manufacturers'
supplied information regarding the pulses per gallon (usually provided on a tag on the flowmeter).
2-3
CE & STANDARD VERSION
98-05017
ARC 6000
Rev.- 1
Once the initial calibration number has been entered into the console, proceed to section 2.6.1.4 to fine tune the flowmeter
for maximum accuracy.
2.6.1.2. DETERMINING THE PRESSURE SENSOR INITIAL CALIBRATION NUMBER
The Pressure Sensor Calibration Number can be found by determining the "Gallons per Acre" rating for the type of nozzles
being used. First find the chart that represents the nozzle series you will use and the nozzle spacing of your boom. Then find
the nozzle size needed for the range of speeds and the rate needed. When the nozzle has been selected find the column of
nozzle ratings in "Gallons per Acre" at 10 MPH. Then, on the left of the chart, find the horizontal line representing the
ratings at 30 PSI. Where the column and row intersect you will find the "Gallons per Acre" rating of your nozzles at 10
MPH and 30 PSI. This is the value to enter into the console as the pressure sensor Cal. #. For example, in the following chart,
for a floodjet K-SS10 nozzle, the row for 30 PSI and column for 10 MPH cross at 26.0 gallons per acre, the pressure sensor
cal. number for this particular nozzle.
NOTE: We recommend that these tests be done using water, and only after neutralizing the tank and system.
Gallons per AcreType
LiquidCapacity 40" Spacing
Floodjet
Tip No.
TK-SS10
4
TK-SS15
FloodjetPressure in 6 8 10 12
Nozzle in PSI GPMMPHMPHMPHMPH
101.025.016.614.912.4
K-SS10201.435.026.021.017.5
30
40
101.537.028.022.018.6
K-SS15202.153.039.032.026.0
302.664.048.039.032.0
403.074.056.045.037.0
1.7
2.0
43.032.026.021.0
50.037.030.025.0
Use this number as the cal. number in this example.
Use the following procedure to enter the flow sensor calibration number.
A. Set the console to the following positions;
PowerON
Mode SelectorSET- UP
Master SwitchOFF
Display SelectorTOTAL APPLIED
B. Use the INC/DEC switch to select the desired flow sensor calibration number.
2.6.1.3. PRESSURE SENSOR HIGH/LOW CALIBRATION
The pressure sensor's low and high values must be set to match the readings from your pressure gauge following the procedure below.
SETTING THE LOW SIDE:
A. Set the console to the following positions;
Power SwitchON
Setup/Operate SwitchOPERATE
Display Selector SwitchPRIME
Master SwitchON
At least one Boom SwitchON (to release any trapped pressure)
(May have to remove nozzle if it has a check valve)
Ground speed0 (zero)
GSO SwitchOFF
CE & STANDARD VERSION
2-4
ARC 6000
B. Hold INC/DEC switch to DEC until console reads PSi 0
Note: A display reading of "PSi - -" indicates that the pressure sensor is not connected. A reading of "PSi - 0" indicates a reading of less than 0 PSI. This suggests that the sensor may need to be recalibrated to 0 pressure.
B. Hold the INC/DEC switch to INC for about 3 seconds. The display will read "OPEN". Release the INC switch. Push
the INC switch again and hold it for about 3 seconds. The display will read "PSi xxx". The xxx is a pressure. The INC/
DEC switch can now be used to adjust the pressure reading on the console to match the reading on the pressure gauge. If
no switch changes are detected after 3 seconds, the console will read "OPEN" again. Actuating the DEC switch when the
console reads "OPEN" will cause the console to read "CLOSE" and the valve will close.
2.6.1.4. FINE TUNING THE FLOW SENSOR CALIBRATION NUMBER
98-0501
Rev.- 1
NOTE: We recommend that these tests be done using water, and only after neutralizing the tank and system.
Once the initial calibration number has been determined and entered into the console, a calibration run should be made to adjust
the number for maximum accuracy. The hardest part of the calibration procedure will be accurately measuring the actual discharge
of large volumes of liquid. The more accurately the discharge is measured, the more accurate the calibration will be. Since each
operator's facilities are different, it is not possible to prescribe a standard method of measuring discharge. Operators have
successfully performed the task using a second, calibrated flow meter, using a truck scale and calculating volumes based on weight
and density of the liquid discharged, and by discharging into a marked, calibrated tank.
It is necessary to pump and measure at least 100 gallons, and as much as 300 gallons, depending on the accuracy required. For
example: if the actual measurement is accurate to within 3 gallons, using 300 gallons will yield an accuracy of 1 %.
If only 100 gallons are pumped and measured, the calibration can be off as much as 3%. The better the measurement accuracy
of actual discharge and the more material pumped, the more accurate will be the resulting calibration.
A method similar to the following is recommended.
1. If using Psi mode, enter the appropriate Correction Factor for the material that you will be using for the test (Not
applicable for rEFLO or STnrd applications) (see section 2.4.1).
2. Turn the Mode Switch to "OPERATE", the Display Selector to "APPLICATION RATE". Enter the desired
application rate.
3. Verify that the boom switches are "OFF", select the "SETUP" mode; rotate the display selector switch to
"TOTAL APPLIED".
4. For Psi mode applications, the current pressure sensor calibration number will be displayed. Verify that it is the
recommended initial calibration number for the nozzles installed in the system. For rEFLO or STnrd applications,
the flowmeter calibration number will be displayed (rEFLO mode requires all booms be on to view cal. #.) Use the
INC/DEC switch to adjust as necessary.
5. Select "OPERATE" with the mode selector switch. Hold the DEC switch down for three to five seconds to zero
the accumulated gallons.
6. Make sure there is enough liquid in the main tank to do the test. Weigh the sprayer and load of water. Position
the sprayer in an appropriate area to do the calibration test.
2-5
CE & STANDARD VERSION
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.