Technibel KPA128R5TAA, GR79R5TBA, GR99R5TBA, MCAV127R5VAB, MCAV77R5TA Technical & Service Manual

...
0 (0)
MCAV77R5VAA - GR79R5TBA MCAV97R5VAA - GR99R5TBA MCAV127R5VAB - GR129R5TBA
7(&+1,&$/6(59,&(0$18$/
63/,76<67(0$,5&21',7,21(5
KPA128R5TAA - GR129R5TBA
Indoor Unit
MCAV77R5VAA MCAV97R5VAA MCAV127R5VAB
GR79R5TBA GR99R5TBA GR129R5TBA
Ceiling-Mounted
Floor-Mounted
KPA128R5TAA
0.8180.072.0 04/2001
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Table of Contents
Page
1.OPERATING RANGE..............................................................................................................................1
2.SPECIFICATIONS
2-1.Unit Specifications..........................................................................................................................2
2-2.Major Component Specifications....................................................................................................6
2-3.Other Component Specifications....................................................................................................13
3.DIMENSIONAL DATA..............................................................................................................................14
4.REFRIGERANT FLOW DIAGRAM .........................................................................................................17
5.PERFORMANCE DATA
5-1.Performance charts .......................................................................................................................19
5-2.Air Throw Distance Chart ..............................................................................................................22
5-3. Heating Capacity ...........................................................................................................................26
6.ELECTRICAL DATA
6-1.Electrical Characteristics................................................................................................................27
6-2.Electric Wiring Diagram..................................................................................................................31
7.FUNCTION
7-1.Room Temperature Control ...........................................................................................................34
7-2.Dry Operation ................................................................................................................................36
7-3.Automatic Switching between Cooling and Heating ......................................................................36
7-4.Freeze Prevention .........................................................................................................................37
7-5.Overload Prevention ......................................................................................................................38
7-6.Cold Draft Prevention ....................................................................................................................39
7-7.Defrosting Operation .....................................................................................................................40
8.TROUBLESHOOTING
8-1.Check before and after troubleshooting ........................................................................................42
8-2.Air conditioner does not operate ....................................................................................................43
8-3.Some part of air conditioner does not operate ..............................................................................47
8-4.Air conditioner operates, but abnormalities are observed .............................................................49
8-5.If a sensor is defective ...................................................................................................................51
9.CHECKING ELECTRICAL COMPONENTS
9-1.Measurement of Insulation Resistance..........................................................................................52
9-2.Checking Continuity of Fuse on PCB Ass'y....................................................................................53
9-3.Checking Motor Capacitor .............................................................................................................53
ii
10. DISASSEMBLY PROCEDURE FOR INDOOR UNIT
10-1.Removing Air Intake Grille ...........................................................................................................54
10-2. Removing Side Panels ................................................................................................................55
10-3. Access and Removal of Electrical Component Box ....................................................................55
10-4. Removing Flap Motor ..................................................................................................................56
10-5. Removing Evaporator ..................................................................................................................56
10-6. Removing Fan and Fan Motor .....................................................................................................58
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. – 7°C D.B. / – 8°C W.B.
2
2.SPECIFICATIONS
2-1.Unit Specifications
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 2.30 2.70
BTU/h 7,843 9200
Air circulation (High) m
3
/h 430
Moisture removal (High) Liters/h 0.6 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 3.7 3.5 Power input W 790 750 Power factor % 93 96 C.O.P. W/W 2.9 3.6 Compressor locked rotor amperes A 20 20
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /690 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31 37 / 32 / 31
Outdoor : Hi dB-A 42 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Accessories Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 35.0
Shipping kg 10.0 38.0 Shipping volume m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
3
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 2.60 3.45
BTU/h 8870 11760
Air circulation (High) m
3
/h 430
Moisture removal (High) Liters/h 0.8 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 4.4 4.2 Power input W 970 950 Power factor % 96 98 C.O.P. W/W 2.7 3.6 Compressor locked rotor amperes A 23 23
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /770 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31 37 / 32 / 31
Outdoor : Hi dB-A 42 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Accessories Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 36.0
Shipping kg 10.0 39.0 Shipping volume m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B.
Outdoorairtemperature7°CD.B./6°CW.B.
4
Indoor Unit MCAV127R5VAB Outdoor Unit GR129R5TBA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 3.40 4.10
BTU/h 11590 13980
Air circulation (High) m
3
/h 430
Moisture removal (High) Liters/h 1.3 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 5.8 6.4 Power input W 1270 1420 Power factor % 95 96 C.O.P. W/W 2.7 2.9 Compressor locked rotor amperes A 34 34
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /1135 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 39 / 35 / 33 39 / 35 / 33
Outdoor : Hi dB-A 44 45 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Accessories Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 38.0
Shipping kg 10.0 41.0 Shipping volume m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 3.35 3.90
BTU/h 11,424 13,299
Air circulation (High)
m3/h 700
Moisture removal (High) Liters/h 1.3
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 5.6 6.1 Power input W 1,220 1,320 Power factor % 95 94 C.O.P. W/W 2.7 3.0 Compressor locked rotor amperes A 34 34
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1260 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 44 / 40 / 35 44 / 40 / 35
Outdoor : Hi dB-A 45 47 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 540
Width mm 900 700
Depth mm 190 265 Package dimensions Height mm 813 568
Width mm 1,011 815
Depth mm 296 343 Weight Net kg 23.5 38.0
Shipping kg 30.0 41.0 Shipping volume
m
3
0.24 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
Indoor Unit KPA128R5TAA Outdoor Unit GR129R5TBA
5
6
2-2.Major Component Specifications
2-2-1.Indoor Unit
Indoor Unit MCAV77R5VAA
Controller PCB
Part No. POW-K78EH(A), POW-K8EH(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ...1,130 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT :561.8
VLT-WHT :197.4
VLT-ORG :63.4
YEL-ORG :155.7
YEL-PNK :115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close —
Run capacitor µF 0.6
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
7
Indoor Unit MCAV97R5VAA
Controller PCB
Part No. POW-K78EH(A), POW-K8EH(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ...1,190 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT :561.8
VLT-WHT :197.4
VLT-ORG :63.4
YEL-ORG :155.7
YEL-PNK :115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close —
Run capacitor µF 0.8
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
8
Indoor Unit MCAV127R5VAB
Controller PCB
Part No. POW-K128EH(A), POW-K8EH(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ...1,230 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT :561.8
VLT-WHT :197.4
VLT-ORG :63.4
YEL-ORG :155.7
YEL-PNK :115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close —
Run capacitor µF 1.0
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Indoor Unit KPA128R5TAA
Controller PCB
Part No. POW-K126GHS-(C) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-6HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 2 ... ø130 / L180 Fan motor model ... Q'ty K48407-M01596 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,160 Nominal output W 20 Coil resistance (Ambient temp. 20°C) GRY-WHT : 314±7%
WHT-PNK : 444±7%
WHT-VLT : 98.9±7%
VLT-ORG : 98.9±7% ORG-YEL : 223±7%
Safety devices Type Internal protector
Operating temp. Open °C 145±5
Close Automatic reclosing
Run capacitor µF 1.5
VAC 440
Flap Motor
Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k 16.45 ± 15%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area
m
2
0.192
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
10
2-2-2.Outdoor Unit
Outdoor Unit GR79R5TBA
Controller PCB POW-C96GH
Compressor
Type Rotary (Hermetic) Compressor model RH 145 VHAT Nominal output W 700 Compressor oil ... Amount cc DIAMOND MS56 ...300 Coil resistance (Ambient temp. 25°C) C–R :4.11±7%
C–S :6.04±7%
Safety devices Type Internal protector (K)
Operating temp. Open °C 150±5
Close °C 90±10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 22A
Run capacitor µF 25
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty K35610-M01723 ... 1 No. of poles ... rpm (230 V, High) 6 ...810 Nominal output W 22 Coil resistance (Ambient temp. 25°C) WHT-BRN :374±7%
BRN-PNK :484±7%
——
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 1.5
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m
2
0.353
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
11
Outdoor Unit GR99R5TBA
Controller PCB POW-C96GH
Compressor
Type Rotary (Hermetic) Compressor model RH 174 VHAT Nominal output W 800 Compressor oil ... Amount cc DIAMOND MS56 ...300 Coil resistance (Ambient temp. 25°C) C–R :3.4±7%
C–S :6.13±7%
Safety devices Type Internal protector (K)
Operating temp. Open °C 150±5
Close °C 90±10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 28A
Run capacitor µF 25
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty K35610-M01723 ... 1 No. of poles ... rpm (230 V, High) 6 ...810 Nominal output W 22 Coil resistance (Ambient temp. 25°C) WHT-BRN :374±7%
BRN-PNK :484±7%
——
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 1.5
VAC 400
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.2 Face area m
2
0.353
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
12
Outdoor Unit GR129R5TBA
Controller PCB POW-C96GH
Compressor
Type Rotary (Hermetic) Compressor model RH 231 VHFT Nominal output W 1,100 Compressor oil ... Amount cc DIAMOND MS56 ...520 Coil resistance (Ambient temp. 25°C) C–R :2.17±7%
C–S :3.99±7%
Safety devices Type Internal protector (K)
Operating temp. Open °C 150±5
Close °C 90±10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 36A
Run capacitor µF 30
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty K35610-M01722 ... 1 No. of poles ... rpm (230 V, High) 6 ...830 Nominal output W 21 Coil resistance (Ambient temp. 25°C) WHT-BRN :269±7%
BRN-PNK :362±7%
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 1.5
VAC 400
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.333
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-3.Other Component Specifications
13
<Only for 7000 BTU/h class models>
<Only for 12000BTU/h class models>
<Only for 12,000BTU/h class models>
PTC Thermistor (TH) TDK 101YV
Resistance (at 25°C)
100 ±20%
4-way Valve (SC)
CHV01A (Coil), CHV0202 (Valve)
Coil rating
AC 220/240V, 50Hz, 6W
Coil resistance (at 20°C)
1402 ±7%
4-way Valve (SC)
LB64012 (Coil), VH7100C (Valve)
Coil rating
AC 220/240V, 50Hz, 6W
Coil resistance (at 20°C)1740 ±7%
Thermostat (Defrost thermo. 23D) TRS02-12MSR
Operating temp. °C ON 12 ±2
Diff. 8 deg. below
Power Relay (PR)
DFU24D1F
Coil rating
DC 24V Coil resistance (at 20°C) 650 ±10% Contact rating AC 250V, 20A
Outdoor Unit GR79R5TBA
GR99R5TBA GR129R5TBA
Thermistor (Room sensor) DTN-TKS134B
Resistance k 25°C 5.0 ±3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ±2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ±10%
Secondary (BRN – BRN): 2.0 ±10%
Thermal cut-off temp. 150°C
Indoor Unit MCAV77R5VAA
MCAV97R5VAA MCAV127R5VAB
4-way Valve (SC)
Coil rating
Coil resistance (at 20°C)
CHV-01A (Coil), CHV-0101 (Valve)
AC 220/240V, 50Hz, 6W
1402 ±7%
<Only for 9000BTU/h class models>
KPA128R5TAA
14
3.DIMENSIONAL DATA
Indoor Unit MCAV77R5VAA
MCAV97R5VAA MCAV127R5VAB
58.599.5
805 177
41.0
41.0 270
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8") MCAV77/97 Wide tube ø12.7 (1/2") MCAV127
Center of tubing hole (2 places)
Drain hose ø18
Remote control unit
18.5
61
172.5
Unit : mm
Indoor Unit KPA128R5TAA
Remote control unit
86
74 74
Center of tubing hole ø75 (4 places)
Wide tube ø12.7 (1/2") Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
18.5
61
172.5
Unit : mm
15
16
Outdoor Unit GR79R5TBA
GR99R5TBA GR129R5TBA
700
540
15
255
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve ø9.52 (3/8") ø12.7 (1/2")
170
103 57
470
4 – ø12 holes
116
320
294
Air intake
Air discharge
GR79/99 GR129
Unit : mm