IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY
INFORMATION!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS
THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR
MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PROPOSITION 65 WARNING: THIS PRODUCT CONTAINS CHEMICALS KNOWN TO THE STATE OF
CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
— Do not store or use gasoline or other flammable vapors and liquids, or other combustible materials
in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call the fire department.
• Do not return to your home until authorized by the gas supplier or fire department.
— DO NOT RELY ON SMELL ALONE TO DETECT LEAKS. DUE TO VARIOUS FACTORS, YOU MAY NOT
BE ABLE TO SMELL FUEL GASES.
• U.L. recognized fuel gas and CO detectors are recommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules
regulations, or customs.
— Improper installation, adjustment, alteration, service or maintenance can cause injury, property
damage or death. Refer to this manual. Installation and service must be performed by a qualified
installer, service agency or the gas supplier. In the commonwealth of Massachusetts, installation
must be performed by a licensed plumber or gas fitter for appropriate fuel.
ISO 9001:2008
FOR RGFG UPFLOW HIGH EFFICIENCY MODULATING
CONDENSING GAS FURNACES
RGFG
MMOODDUULLAATTIINNG
TTHHEERRMMOOSSTTAAT
IINNSSTTAALLLLAATTIIOON
SSEEEEPPAAGGEE9922
MMOODDUULLAATTIINNGG
CCOOMMMMUUNNIICCAATTIINNGG
TTHHEERRMMOOSSTTAATT
IINNSSTTAALLLLAATTIIOONN
SSEEEEPPAAGGEE110066
WARNING
!
DO NOT EXCHANGE MEMORY CARDS BETWEEN FURNACES. DOING SO COULD RESULT IN
UNEXPECTED OPERATION – INCLUDING INADEQUATE AIRFLOW DURING HEATING (AND
OTHER MODES) OR A LOSS OF HEAT.
G
T
N
SUPERSEDES 92-24161-104-02
92-24161-104-03
IMPORTANT: All Rheem products
meet current Federal OSHA Guidelines
for safety. California Proposition 65
warnings are required for certain products, which are not covered by the
OSHA standards.
California's Proposition 65 requires
warnings for products sold in California
that contain, or produce, any of over
600 listed chemicals known to the
State of California to cause cancer or
birth defects such as fiberglass insulation, lead in brass, and combustion
products from natural gas.
All “new equipment” shipped for sale in
California will have labels stating that
the product contains and/or produces
Proposition 65 chemicals. Although we
have not changed our processes, having the same label on all our products
facilitates manufacturing and shipping.
We cannot always know “when, or if”
products will be sold in the California
market.
You may receive inquiries from customers about chemicals found in, or
produced by, some of our heating and
air-conditioning equipment, or found in
natural gas used with some of our
products. Listed below are those chemicals and substances commonly associated with similar equipment in our
industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the
Websites for OSHA (Occupational
Safety and Health Administration), at
www.osha.gov
and the State of
California's OEHHA (Office of
Environmental Health Hazard
Assessment), at www.oehha.org.
Consumer education is important since
the chemicals and substances on the
list are found in our daily lives. Most
consumers are aware that products
present safety and health risks, when
improperly used, handled and maintained.
Installation Instructions are updated on
a regular basis. This is done as product
changes occur or if new information
becomes available. In this publication,
an arrow ➤ denotes changes from the
previous edition or additional new
material.
TABLE OF CONTENTS
SAFETY INFORMATION ..........................................................................................................................................3
GENERAL INFORMATION.......................................................................................................................................6
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY..............................................7
LOCATION REQUIREMENTS AND CONSIDERATIONS.......................................................................................8
SITE SELECTION...........................................................................................................................................9
DIMENSIONS AND CLEARANCE TO COMBUSTIBLES...........................................................................10
GAS SUPPLY AND PIPING....................................................................................................................................30
GAS VALVE...................................................................................................................................................31
LIFE HIST............................................................................................................................................63
(-)HC-TST550CMMS FULL COLOR, PROGRAMMABLE COMMUNICATING THERMOSTAT.............112
VIEWING FURNACE USER MENUS WITH THE (-)HC-TST550CMMS THERMOSTAT.......................113
CHANGING FURNACE SETUP ITEMS ON THE (-)HC-TST550CMMS THERMOSTAT.......................114
IMPORTANT: To insure proper installation and operation of this product, completely read all instructions prior to attempting to assemble, install, operate, maintain or repair this product. Upon unpacking of the furnace, inspect all parts for
damage prior to installation and start-up.
2
SAFETY INFORMATION
IMPORTANT!
THE COMMONWEALTH OF MASSACHUSETTS REQUIRES COMPLIANCE
WITH REGULATION 248 CMR 4.00
AND 5.00 FOR INSTALLATION OF
THROUGH-THE-WALL VENTED GAS
APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented
gas fueled equipment installed in every
dwelling, building or structure used in
whole or in part for residential purposes,
including those owned or operated by
the Commonwealth and where the side
wall exhaust vent termination is less than
seven (7) feet above finished grade in
the area of the venting, including but not
limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON
MONOXIDE DETECTORS. At the time of
installation of the side wall horizontal
vented gas fueled equipment, the
installing plumber or gasfitter shall
observe that a hard wired carbon
monoxide detector with an alarm and
battery back-up is installed on the floor
level where the gas equipment is to be
installed. In addition, the installing
plumber or gasfitter shall observe that a
battery operated or hard wired carbon
monoxide detector with an alarm is
installed on each additional level of the
dwelling, building or structure served by
the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the property owner to secure
the services of qualified licensed professionals for the installation of hard wired
carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is
installed in a crawl space or an attic, the
hard wired carbon monoxide detector
with alarm and battery back-up may be
installed on the next adjacent floor level.
b. In the event that the requirements of
this subdivision can not be met at the
time of completion of installation, the
owner shall have a period of thirty (30)
days to comply with the above requirements; provided, however, that during
said thirty (30) day period, a battery
operated carbon monoxide detector with
an alarm shall be installed.
2. APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide
detector as required in accordance with
the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed
and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above
grade directly in line with the exhaust
vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall read, in print size
no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
44..
INS
PECTION. T
inspector of the side wall horizontally
vented gas fueled equipment shall not
approve the installation unless, upon
inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through
4.
(b) EXEMPTIONS: The following equip-
ment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10
entitled “Equipment Not Required To Be
Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side
wall horizontally vented gas equipment
provides a venting system design or
venting system components with the
equipment, the instructions provided by
the manufacturer for installation of the
equipment and the venting system shall
include:
1. Detailed instructions for the installation of the venting system design or the
venting system components; and
2. A complete parts list for the venting
system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product
Approved side wall horizontally vented
gas fueled equipment does not provide
the parts for venting the flue gases, but
identifies “special venting systems”, the
following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with
the appliance or equipment installation
instructions; and
2. The “special venting systems” shall
be Product Approved by the Board, and
the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions
for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for
venting instructions, and/or all venting
design instructions shall remain with
the appliance or equipment at the completion of the installation.
he state or local gas
WARNING
!
INSTALL THIS FURNACE ONLY IN
A LOCATION AND POSITION AS
SPECIFIED IN THE LOCATION
REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE
INSTRUCTIONS. PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE FURNACE
SPACE AS SPECIFIED IN THE
VENTING SECTION OF THESE
INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO
THE FURNACE SPACE AS SPECIFIED IN THE COMBUSTION AND
VENTILATION AIR SECTION OF
THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST
BE DISCHARGED OUTDOORS.
CONNECT THIS FURNACE TO AN
APPROVED VENT SYSTEM ONLY,
AS SPECIFIED IN VENT PIPE
INSTALLATION SECTION OF
THESE INSTRUCTIONS.
WARNING
!
NEVER TEST FOR GAS LEAKS
WITH AN OPEN FLAME. USE A
COMMERCIALLY AVAILABLE
SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF
LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS
SUPPLY AND PIPING SECTION OF
THESE TION INSTRUCTIONS.
WARNING
!
THIS FURNACE IS NOT
APPROVED OR RECOMMENDED
FOR INSTALLATION ON ITS BACK,
WITH ACCESS DOORS FACING
UPWARDS, OR WITH SUPPLY AIR
DISCHARGING TO THE RIGHTHAND SIDE WHEN FACING THE
FRONT OF THE FURNACE. SEE
FIGURE 3 FOR PROPER INSTALLATION OF HORIZONTAL MODELS.
WARNING
!
DO NOT INSTALL THIS FURNACE
IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR
INSTALLATION IN A MOBILE
HOME. DOING SO COULD CAUSE
FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
USE ONLY WITH TYPE OF GAS
APPROVED FOR THIS FURNACE.
REFER TO THE FURNACE RATING
PLATE.
3
WARNING
!
WHEN THIS FURNACE IS INSTALLED
IN A RESIDENTIAL GARAGE, IT
MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE
LOCATED NO LESS THAN 18 INCHES ABOVE THE FLOOR. THIS IS TO
REDUCE THE RISK OF IGNITING
FLAMMABLE VAPORS WHICH MAY
BE PRESENT IN A GARAGE.
ALSO, THE FURNACE MUST BE
LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE
WARNINGS CAN CAUSE A FIRE OR
EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH.
WARNING
!
USE OF THIS FURNACE IS
ALLOWED DURING CONSTRUCTION
IF THE FOLLOWING TEMPORARY
INSTALLATION REQUIREMENTS
ARE MET. INSTALLATION MUST
COMPLY WITH ALL INSTALLATION
INSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDER
THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO
THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND
TEMPERATURE RISE PER RATING PLATE MARKING;
• MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION;
• RETURN AIR TEMPERATURE
MAINTAINED BETWEEN 55°F
(13°C) AND 80°F (27°C); AND;
• CLEAN FURNACE, DUCT WORK
AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE
CONSTRUCTION PROCESS, AND
VERIFY FURNACE OPERATING
CONDITIONS INCLUDING IGNITION, INPUT RATE, TEMPERATURE RISE AND VENTING,
ACCORDING TO THE INSTRUCTIONS.
WARNING
!
DO NOT JUMPER OR OTHERWISE
BYPASS OVERTEMPERATURE OR
ANY OTHER LIMITS OR SWITCHES
ON THE FURNACE. IF ONE OF
THESE LIMITS OR SWITCHES
SHOULD TRIP OR OPEN, THE USER
IS TO BE INSTRUCTED TO CALL A
QUALIFIED INSTALLER, SERVICE
AGENCY OR THE GAS SUPPLIER.
FOR MANUALLY RESETABLE
SWITCHES, THE USER IS FURTHER
INSTRUCTED TO NEVER RESET THE
SWITCH, BUT TO CALL A QUALIFIED
TECHNICIAN. MANUAL RESET
SWITCHES MAY REQUIRE FURTHER
CORRECTIVE ACTIONS. FAILURE TO
FOLLOW THIS WARNING COULD
RESULT IN CARBON MONOXIDE
POISONING, SERIOUS INJURY OR
DEATH. IF THE UNIT IS INSTALLED
IN A CLOSET, THE DOOR MUST BE
CLOSED WHEN MAKING THIS
CHECK. INSTALLERS AND TECHNICIANS ARE INSTRUCTED TO
REPLACE ANY LIMIT OR SAFETY
SWITCH/DEVICE ONLY WITH IDENTICAL REPLACEMENT PARTS.
WARNING
!
DUCT LEAKS CAN CREATE AN
UNBALANCED SYSTEM AND DRAW
POLLUTANTS SUCH AS DIRT, DUST,
FUMES AND ODORS INTO THE
HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM
TOXIC, VOLATILE OR FLAMMABLE
CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON
MONOXIDE (CO), CAN BE DRAWN
INTO THE LIVING SPACE THROUGH
LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING
PERSONAL INJURY OR DEATH.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
GARAGES OR OFF-GARAGE
STORAGE AREAS - ALL JOINTS,
SEAMS, AND OPENINGS IN THE
EQUIPMENT AND DUCT MUST BE
SEALED TO LIMIT THE MIGRATION
OF TOXIC FUMES AND ODORS
INCLUDING CARBON MONOXIDE
FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
SPACES CONTAINING FUEL
BURNING APPLIANCES SUCH AS
WATER HEATERS OR BOILERS ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND
DUCT MUST ALSO BE SEALED TO
PREVENT DEPRESSURIZATION
OF THE SPACE AND POSSIBLE
MIGRATION OF COMBUSTION
BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING
SPACE.
WARNING
!
ALWAYS INSTALL FURNACE TO
OPERATE WITHIN THE FURNACE'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT
SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN
THE ALLOWABLE RANGE, AS
SPECIFIED IN DUCTING SECTION
OF THESE INSTRUCTIONS. SEE
ALSO FURNACE RATING PLATE.
WARNING
!
WWHHEENNAAFFUURRNNAACCEEIISSIINNSSTTAALLLLEEDD
SO THAT SUPPLY DUCTS CARRY
CIRCULATED BY THE FUR-
AIR
NACE TO AREAS OUTSIDE THE
SPACE CONTAINING THE FURNACE, THE RETURN AIR SHALL
ALSO BE HANDLED BY DUCT(S)
SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE
THE SPACE CONTAINING THE
FURNACE.
NOTICE
IMPROPER INSTALLATION, OR
INSTALLATION NOT MADE IN
ACCORDANCE WITH THE CSA
INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR
DANGEROUS CONDI-TIONS AND
ARE NOT COVERED BY THE UNIT
WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY
DRAIN PAN BE INSTALLED
UNDER ALL EVAPORATOR COILS
OR UNITS CONTAINING EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE
BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT
OF AN OVERFLOW OF THE COIL
DRAIN PAN OR A STOPPAGE IN
THE PRIMARY CONDENSATE
DRAIN PIPING. SEE ACCESSORIES SECTION OF THESE
INSTRUCTIONS FOR AUXILIARY
HORIZONTAL OVERFLOW PAN
INFORMATION (MODEL RXBM).
WARNING
!
DO NOT EXCHANGE MEMORY
CARDS BETWEEN 2 OR MORE
DIFFERENT FURNACES. DOING
SO COULD RESULT IN UNEXPECTED OPERATION – INCLUDING INADEQUATE AIRFLOW DURING HEATING (AND OTHER
MODES OR A LOSS OF HEAT).
4
INSTALLATION CHECK LIST
REFER TO INSTALLATION INSTRUCTIONS
GAS SUPPLY
Adequate pipe size
Correct supply pressure (during furnace operation)
Manifold pressure
No gas leaks
Adequate clearance to combustibles
Adequate clearance for service (at front)
DUCT STATIC PRESSURE
in. w.c. on heating speed
in. w.c. on cooling speed
Air temperature rise
CONDENSATE LINE
Trap filled with water
Vented
Sloped toward drain
Condensate drain line hoses connected
and clamped
TERMINATIONS – DIRECT VENT
VERTICAL
Intake – 12" min. above roof/snow level
Correct relationship – exhaust to intake
VERTICAL – CONCENTRIC (RXGY-E03A)
Intake – 12" min. above roof/snow level
HORIZONTAL – STANDARD (RXGY-D02, -D02A, -D03,
-D03A)
Correct relationship – exhaust to intake
12" min. above grade/snow level
HORIZONTAL – ALTERNATE (RXGY-D02, -D02A, -D03,
-D03A, -D04 OR -D04A)
Correct relationship – exhaust to intake
Above anticipated snow level
HORIZONTAL – CONCENTRIC (RXGY-E03A)
12" min. above grade/snow level
Intake “Y” rotated above center
Exhaust sloped toward furnace
VENTING – NON-DIRECT VENT (VERTICAL ONLY)
in. diameter – exhaust pipe
ft. of pipe – exhaust
no. of elbows
TERMINATION – NON-DIRECT VENT (VERTICAL ONLY)
12" min. above roof/snow level
Freeze protection (if necessary)
Neutralizer (if needed)
VENTING – DIRECT VENT
in. diameter – intake pipe
in. diameter – exhaust pipe
ft. of pipe – intake air
no. of elbows – intake air
ft. of pipe – exhaust pipe
no. of elbows – exhaust pipe
Model #
Serial #
Date of installation
HORIZONTAL – STANDARD
12" min. above grade/snow level
HORIZONTAL – ALTERNATE
Above anticipated snow level
5
GENERAL INFORMATION
The RGFG series furnaces are
design-certified by CSA for use with
natural and L.P. gases as follows:
• As direct vent, central forced air
furnaces with all combustion air
supplied directly to the furnace
burners through a special air intake
system outlined in these instructions.
• As non-direct, central forced air furnace taking combustion air from
the installation area or using air
ducted from the outside.
• IMPORTANT: Proper application,
installation and maintenance of this
furnace are required if consumers
are to receive the full benefits for
which they have paid.
Install this furnace in accordance with
the American National Standard
Z223.1 – latest edition entitled
“National Fuel Gas Code” (NFPA54,
90A and 90B) and requirements or
codes of the local utilities or other
authorities having jurisdiction. This is
available from the following:
National Fire Protection
Association, Inc.
Batterymarch Park
Quincy, MA 02269
FIGURE 1
UPFLOW FURNACE RGFG
(GAS VALVE MAY BE DIFFERENT THAN SHOWN)
CSA International - U.S.
8501 East Pleasant Valley Road
Cleveland, Ohio, 44131
Canadian installations must be
installed in accordance with CSA,
local installation codes and
authorities having jurisdiction.
CSA is available from:
IMPORTANT INFORMATION ABOUT EFFICIENCY
AND INDOOR AIR
QUALITY
Central cooling and heating equipment is only as efficient as the duct
system that carries the cooled or
heated air. To maintain efficiency,
comfort and good indoor air quality, it
is important to have the proper balance between the air being supplied
to each room and the air returning to
the cooling and heating equipment.
Proper balance and sealing of the
duct system improves the efficiency
of the heating and air conditioning
system and improves the indoor air
quality of the home by reducing the
amount of airborne pollutants that
enter homes from spaces where the
ductwork and / or equipment is located. The manufacturer and the U.S.
Environmental Protection Agency’s
Energy Star Program recommend
that central duct systems be checked
by a qualified contractor for proper
balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN
UNBALANCED SYSTEM AND
DRAW POLLUTANTS SUCH AS
DIRT, DUST, FUMES AND ODORS
INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND
ODORS FROM TOXIC, VOLATILE
OR FLAMMABLE CHEMICALS, AS
WELL AS AUTOMOBILE EXHAUST
AND CARBON MONOXIDE (CO),
CAN BE DRAWN INTO THE LIVING
SPACE THROUGH LEAKING
DUCTS AND UNBALANCED DUCT
SYSTEMS CAUSING PERSONAL
INJURY OR DEATH (SEE FIGURE
2).
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
GARAGES OR OFF-GARAGE
STORAGE AREAS - ALL JOINTS,
SEAMS, AND OPENINGS IN THE
EQUIPMENT AND DUCT MUST
BE SEALED TO LIMIT THE
MIGRATION OF TOXIC FUMES
AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
SPACES CONTAINING FUEL
BURNING APPLIANCES SUCH
AS WATER HEATERS OR BOILERS - ALL JOINTS, SEAMS, AND
OPENINGS IN THE EQUIPMENT
AND DUCT MUST ALSO BE
SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE
AND POSSIBLE MIGRATION OF
COMBUSTION BYPRODUCTS
INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR
INSTALLATION NOT MADE IN
ACCORDANCE WITH THE CSA
INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS,
CAN RESULT IN UNSATISFACTORY
OPERATION AND/OR DANGEROUS
CONDI-TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN
BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPORATOR COILS THAT ARE
LOCATED IN ANY AREA OF A
STRUCTURE WHERE DAMAGE TO
THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT
OF AN OVERFLOW OF THE COIL
DRAIN PAN OR A STOPPAGE IN THE
PRIMARY CONDENSATE DRAIN PIPING. SEE ACCESSORIES SECTION
OF THESE INSTRUCTIONS FOR
AUXILIARY HORIZONTAL OVERFLOW PAN INFORMATION (MODEL
RXBM).
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
RECEIVING
Immediately upon receipt, all cartons
and contents should be inspected for
transit damage. Units with damaged
cartons should be opened immediately. If damage is found, it should
be noted on the delivery papers, and
a damage claim filed with the last
carrier.
• After unit has been delivered to
job site, remove carton taking care
not to damage unit.
• Check the unit rating plate for unit
size, electric heat, coil, voltage,
phase, etc. to be sure equipment
matches what is required for the
job specification.
• Read the entire instructions before
starting the installation.
• Some building codes require extra
cabinet insulation and gasketing
when unit is installed in attic applications.
• If installed in an unconditioned
space, apply caulking around the
power wires, control wires, refrigerant tubing and condensate line
where they enter the cabinet. Seal
the power wires on the inside
where they exit conduit opening.
Caulking is required to prevent air
leakage into and condensate from
forming inside the unit, control box,
and on electrical controls.
• Install the unit in such a way as to
allow necessary access to the
coil/filter rack and blower/control
compartment.
• Install the unit in a level position to
ensure proper condensate
drainage. Make sure unit is level in
both directions within 1/8”.
• Install the unit in accordance with
any local code which may apply
and the national codes. Latest edi-
tions are available from: “National
Fire Protection Association, Inc.,
Batterymarch Park, Quincy, MA
02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition)
National Electrical Code.
• NFPA90A Installation of Air
Conditioning and Ventilating
Systems.
• NFPA90B Installation of warm air
heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of
Federal Regulations, Chapter XX,
Part 3280.
7
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
!
CAUTION
DO NOT USE THIS FURNACE
DURING CONSTRUCTION IF
AIR LADEN CORROSIVE COMPOUNDS ARE PRESENT SUCH
AS CHLORINE AND FLUORINE.
OTHERWISE, PROVISIONS
MUST BE TAKEN TO PROVIDE
CLEAN, UNCONTAMINATED
COMBUSTION AND VENTILATION AIR TO THE FURNACE.
FURNACE COMBUSTION AND
VENTILATION AIR CONTAMINATED WITH THESE COMPOUNDS FORMS ACIDS DURING COMBUSTION WHICH CORRODES THE HEAT EXCHANGER
AND COMPONENT PARTS.
SOME OF THESE CONTAMINANTS ARE FOUND IN, BUT
NOT LIMITED TO, PANELING,
DRY WALL, ADHESIVES,
PAINTS, STAINS, VARNISHES,
SEALERS, AND MASONRY
CLEANING MATERIALS.
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!!
THIS FURNACE IS NOT
APPROVED FOR INSTALLATION
IN A MOBILE HOME. DOING SO
COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
!
WHEN THIS FURNACE IS
INSTALLED IN A RESIDENTIAL
GARAGE, IT MUST BE
INSTALLED SO THE BURNERS
AND IGNITION SOURCE ARE
LOCATED NO LESS THAN 18
INCHES ABOVE THE FLOOR.
THIS IS TO REDUCE THE RISK
OF IGNITING FLAMMABLE
VAPORS WHICH MAY
BE PRESENT IN A GARAGE.
ALSO, THE FURNACE MUST BE
LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY
VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN
CAUSE A FIRE OR EXPLOSION,
RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
1. IMPORTANT: If installing the unit
over a finished ceiling or living
area, be certain to install an auxiliary condensate drain pan under
the entire unit. Extend this auxiliary drain pan under any evaporator coil installed with the furnace
and the open portion of the con-
densate drain assembly. See
“Condensate Drain/Neutralizer”
section for more details.
2. IMPORTANT: If using a cooling
evaporator coil with this furnace.
Be sure the air passes over the
heat exchanger before passing
over the cooling coil. The cooled
air passing over the warm ambient
air inside the heat exchanger
tubes can cause condensation
inside the tubes resulting in corrosion and eventual failure.
3. IMPORTANT: Install the furnace
level. If it is not level, condensate
cannot drain properly, possibly
causing furnace shut down.
NOTE: These furnaces are approved
for installation in attics, as well as
alcoves, utility rooms, closets and
crawlspaces. Make provisions to prevent freezing of condensate.
4. IMPORTANT: If this furnace is
installed in a garage, attic or any
other unconditioned space, a selfregulating heat tape must be
installed around the condensate
trap and along the entire length of
the condensate drain in the unconditioned space.
The heat tape should meet the following requirements:
a. The heat tape must be UL listed.
b. Install the heat tape per the
manufacturer’s instructions for
the entire length of drain pipe in
the unconditioned space.
c. The heat tape should be rated
at 3 or 5 watts per foot at 120V.
5. IMPORTANT: If installing in a
utility room, be sure the door is
wide enough to:
a. allow the largest part of the
furnace to pass; or
b. allow any other appliance
(such as a water heater)
to pass.
6. Install the furnace level and
plumb. If it is not level, condensate cannot drain properly, possibly causing furnace to shut
down.
IMPORTANT: Do not attempt to twin
the modulating furnace. The characteristics of the ECM blower motor
preclude twinning applications.
8
FIGURE 3
REMOVING SHIPPING BRACKET
92-24379-01
CLEARANCE ACCESSIBILITY
The design of forced air furnaces with
models as listed in the tables under
Figure 4 are certified by CSA
Laboratories for the clearances to combustible materials shown in inches.
See name/rating plate and clearance
label for specific model number and
clearance information.
Service clearance of at least 24 inches
is recommended in front of
all furnaces.
FOR PURPOSES OF SERVICING
THIS APPLIANCE, ACCESSIBILITY
CLEARANCES, WHERE GREATER,
SHOULD TAKE PRECEDENCE OVER
FIRE PROTECTION CLEARANCES.
WARNING
!
FURNACES MUST NOT BE
INSTALLED DIRECTLY ON CARPET,
TILE OR OTHER COMBUSTIBLE
MATERIAL. INSTALLATION ON A
COMBUSTIBLE MATERIAL OTHER
THAN WOOD FLOORING MAY
RESULT IN FIRE CAUSING DAMAGE, PERSONAL INJURY OR
DEATH.
-GFG upflow furnaces and are
designed and certified for installation on combustible (wood only)
floors.
Upflow furnaces are shipped with
a bottom closure panel installed.
When bottom return air is used,
remove the panel by removing the
two screws attaching the panel to
the front base angle. See filter section for details (see Figure 5).
!
CAUTION
SOME MODELS HAVE A SHIPPING
BRACKET INSTALLED TO PROTECT THE BLOWER ASSEMBLY
DURING SHIPPING.
LOCATE AND REMOVE THE SHIPPING BRACKET FROM THE SIDE
OF THE BLOWER HOUSING
BEFORE OPERATING UNIT. SEE
FIGURE 3.
THE FOLLOWING MODELS
INCLUDE THE ADDITIONAL
BRACKET (WHICH MUST BE
REMOVED) ON THE BLOWER
ASSEMBLY:
RGFG-09EZCMS
RGFG-10EZCMS
RGFG-12ERCMS
SITE SELECTION
1. Select a site in the building near
the center of the proposed, or
existing, duct system.
2. Give consideration to the vent
system piping when selecting the
furnace location. Vent from the
furnace to the termination with
minimal length and elbows.
3. Locate the furnace near the
existing gas piping. If running a
new gas line, locate the furnace
to minimize the length and
elbows in the gas piping.
4. Locate the furnace to maintain
proper clearance to combustibles
as shown in Figure 4.
9
FIGURE 4
PHYSICAL DIMENSIONS AND CLEARANCE TO COMBUSTIBLES, UPFLOW MODELS
A039201
RGFG
UPFLOW MODELS
AIRFLOW
NOTE: For 1800 or more CFM, both side
returns must be used when not using a
bottom return configuration.
10
AO39201
DUCTING
NOTE: FILTER AND FILTER-ROD ARE SHIPPED
ON TOP OF SOLID BOTTOM. REMOVE FILTER
AND FILTER ROD TO ACCES SOLID BOTTOM
Proper airflow is required for the correct
operation of this furnace.
Too little airflow can cause erratic operation and can damage the heat
exchanger. The supply and return duct
must carry the correct amount of air for
heating and cooling if summer air conditioning is used.
Size the ducts according to acceptable
industry standards and methods. The
total static pressure drop of the supply
and return duct should not exceed 0.2"
w.c.
WARNING
!
NEVER ALLOW THE PRODUCTS
OF COMBUSTION FROM THE
FLUE TO ENTER THE RETURN
AIR DUCTWORK OR THE CIRCULATED AIR SUPPLY. ALL RETURN
DUCTWORK MUST BE ADEQUATELY SEALED AND
SECURED TO THE FURNACE
WITH SHEET METAL SCREWS;
AND JOINTS, TAPED. SECURE
ALL OTHER DUCT JOINTS WITH
APPROVED CONNECTIONS AND
SEAL AIRTIGHT. WHEN A FURNACE IS MOUNTED ON A PLATFORM WITH RETURN THROUGH
THE BOTTOM, IT MUST BE
SEALED AIRTIGHT BETWEEN
THE FURNACE AND THE RETURN
AIR PLENUM. THE FLOOR OR
PLATFORM MUST PROVIDE
PHYSICAL SUPPORT OF THE
FURNACE WITHOUT SAGGING,
CRACKS, OR GAPS AROUND THE
BASE, PROVIDING A SEAL
BETWEEN THE SUPPORT AND
THE BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM
BEING CIRCULATED INTO THE
LIVING SPACE CAN CREATE
POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON
MONOXIDE POISONING THAT
COULD RESULT IN PERSONAL
INJURY OR DEATH.
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN OR
SUPPLY DUCTWORK TO OR
FROM ANY OTHER HEAT PRODUCING DEVICE SUCH AS A
FIREPLACE INSERT, STOVE, ETC.
DOING SO MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING,
EXPLOSION, PERSONAL INJURY
OR PROPERTY DAMAGE.
IMPORTANT: Some high efficiency filters
have a greater than normal resistance to
airflow. This can adversely affect furnace
operation. Be sure to check airflow if
using any filter other than the factory-provided filter.
UPFLOW UNITS
1. Position the unit to minimize long
runs of duct or runs of duct with
many turns and elbows.
WARNING
!
UPFLOW FURNACE:
BASE PLATE MUST BE INSTALLED IN
THE FURNACE BOTTOM WHEN USING
SIDE AIR RETURN. FAILURE TO
INSTALL A BASE PLATE COULD
CAUSE THE PRODUCTS OF COMBUSTION TO CIRCULATE INTO THE LIVING
SPACE AND CREATE POTENTIALLY
HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING
OR DEATH.
A SOLID METAL
2. Open the return air compartment.
a. If using side return air, do not
remove the bottom base.
b. Cut an opening in the side .
The opening should be cut the
full width of the knockouts on
the unit.
NOTE: When using side
return, return air plenums,
RXGR-C17B, C21B and C24B
are available from the factory.
c. Remove the bottom base, if
using bottom return air.
Remove the panel by removing the two screws attaching
the base to the front base
angle. See Figure 5.
NOTE: Where the maximum
airflow is 1800 CFM or more,
both sides or the bottom must
be used for return air.
3. Connect the return duct or return
air cabinet to the unit. Make the
connection air tight to prevent
entraining combustion gases from
an adjacent fuel-burning appliance.
4. Be sure to have adequate
space for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace
rooms, garages, utility or laundry
rooms, or cold areas. DO NOT
use a rear air return.
5. If summer air conditioning is
desired, position the indoor coil on
the supply air side of the unit.
Insure that no air can bypass this
coil.
6. Connect the supply air plenum to
the furnace plenum opening.
IMPORTANT: If a flexible duct
connector must be used, it MUST
be rated for a minimum temperature of 250°F. continuous.
FIGURE 5
BOTTOM PANEL REMOVAL
ADS-5422-01
11
VENTING AND COMBUSTION AIR PIPING
GENERAL INFORMATION
WARNING
!
READ AND FOLLOW ALL
INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY
VENT THIS FURNACE OR PROTECT IT FROM INADEQUATE
COMBUSTION AIR CAN CAUSE
CARBON MONOXIDE POISONING, AN EXPLOSION OR FIRE,
RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
OVER TEMPERATURE
SAFETY SWITCHES
Furnaces are equipped with safety
switches in the burner compartment to
protect against over temperature conditions. If a switch is tripped, it must be
manually reset.
WARNING
!
DO NOT JUMPER OVERTEMPERATURE OR ANY OTHER
SAFETY SWITCHES! IF ONE OF
THESE OVER TEMPERATURE
SWITCHES SHOULD TRIP, CALL
A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS
SUPPLIER. DO NOT RESET THE
SWITCHES WITHOUT TAKING
CORRECTIVE ACTION. FAILURE
TO DO SO CAN RESULT IN CARBON MONOXIDE POISONING OR
DEATH. IF THIS UNIT IS
INSTALLED IN A CLOSET, THE
DOOR MUST BE CLOSED WHEN
MAKING THIS CHECK.
REPLACE THE OVER TEMPERATURE SAFETY SWITCHES ONLY
WITH THE IDENTICAL REPLACEMENT PART.
WARNING
!
IN CANADA, PRODUCTS CERTIFIED FOR INSTALLATION AND
INTENDED TO BE VENTED WITH
PLASTIC VENT SYSTEMS (PVC,
CPVC) MUST USE VENT SYSTEMS THAT ARE CERTIFIED TO
THE STANDARD FOR TYPE BH
GAS VENTING SYSTEMS, ULC
S636.
THE COMPONENTS OF THE
CERTIFIED MATERIAL MUST
NOT BE INTERCHANGED WITH
OTHER VENT SYSTEMS OR
UNLISTED PIPE/FITTINGS.
PLASTIC COMPONENTS AND
SPECIFIED PRIMERS AND
GLUES OF THE CERTIFIED SYSTEM MUST BE FROM A SINGLE
SYSTEM MANUFACTURER AND
NOT INTERMIXED WITH OTHER
SYSTEM MANUFACTURER’S
PARTS. EXCEPTIONS INCLUDE
THE RXGY-G02, RXGY-G02C
AND RXGY-E03A WHICH CAN BE
MIXED WITH OTHER MANUFACTURER’S COMPONENTS PROVIDED THEY ARE CONSTRUCTED FROM LIKE MATERIALS.
NOTE: INLET AIR PIPING IS NOT
CONSIDERED TO BE A PART OF
THE “VENTING SYSTEM”. THE
REQUIREMENT THAT VENT MATERIAL BE CERTIFIED TO ULC S636
DOES NOT APPLY TO INLET AIR
PIPING.
INSTALLATION WITH
PRE-EXISTING VENT
SYSTEMS
When the installation of this furnace
replaces an existing furnace that is
removed from a vent system serving
other appliances (such as a water
heater), the existing vent system is likely
to be too large to properly vent the
remaining attached appliances.
Follow the steps below with each appliance remaining connected to the original common vent system. Place the
appliance to be tested in operation,
while the other appliances remaining
connected to the common vent system
are not in operation. Test the operation
of each appliance individually by the following method.
1. Permanently seal any unused
openings in the common venting
system.
2. Visually inspect the venting system
for proper size and horizontal pitch
and determine that there is no
blockage, restriction, leakage, corrosion or other deficiencies which
could cause an unsafe condition.
3. If practical, close all building doors,
windows and all doors between the
space where the appliances
remaining connected to the common venting system are located.
Turn on clothes dryers and any
appliance not connected to the
common venting system. Turn on
any exhaust fans, such as range
hoods and bathroom exhausts, so
they will operate at maximum
speed. Do not operate a summer
exhaust fan. Close fireplace
dampers.
4. Follow the lighting instructions.
Place the appliance being inspected into operation. Adjust the thermostat so the appliance will operate
continuously.
5. Test for spillage at the draft hood
relief opening after 5 minutes of
main burner operation. Use the
flame of a match or candle, or
smoke from a cigarette, cigar
or pipe.
6. After it has been determined that
each appliance that remains connected to the common venting
system properly vents (when
tested as outlined above), return
doors, windows, exhaust fans,
fireplace dampers and any other
gas-burning appliance to their
previous conditions of use.
7. If improper venting is observed
during any of the above tests,
resize the common venting system. Refer to latest edition of the
National Fuel Gas Code ANSI
Z223.1, or the CSA-GAMA venting tables for Category I furnaces.
NOTE: For U.S. installations
only. Schedule 40 ABS-DWV
pipe and fittings may be used as
an alternate to PVC pipe for the
combustion air inlet and vent
pipes.
NOTE: For U.S. installations
only. Cellular core PVC is also
approved for use. It must be
schedule 40 PVC-DWV cellular
pipe manufactured under ASTM
F-891.
JOINING PIPE AND
FITTINGS
WARNING
!
PVC SOLVENT CEMENTS AND
PRIMERS ARE HIGHLY FLAMMABLE. PROVIDE ADEQUATE
VENTILATION AND DO NOT
ASSEMBLE COMPONENTS
NEAR HEAT SOURCE OR AN
OPEN FLAME. DO NOT
SMOKE. AVOID SKIN OR EYE
CONTACT. OBSERVE ALL
CAUTIONS AND WARNINGS
PRINTED ON MATERIAL CONTAINERS. FAILURE TO FOLLOW THESE GUIDELINES MAY
RESULT IN FIRE, EXPLOSION
OR ASPHYXIATION CAUSING
PERSONAL INJURY OR
DEATH.
In Canada, only approved vent materials, primers and solvents approved
to ULC S636 must be used for venting.
All pipe, fittings, solvent cement,
primers and procedures must conform to American National Standard
Institute and American Society for
Testing and Materials (ANSI/ASTM)
standards as shown below:
IMPORTANT: The plastic combustion
air and venting components are
MADE of PVC. If using ABS piping,
ensure that the solvent cement is
compatible for joining PVC to ABS
components or use a mechanical
connection that can withstand the
vent temperatures and is corrosion
resistant.
12
CEMENTING JOINTS
EQUIVALENTVENTING–ASSIGNINGVENTLENTGHTO
ELBOWS
ThissectionappliestoventingtablesinboththeNON-DIRECTandDIRECTVENTtablesinthisbook. Vent tables are provided only in equivalent length and do not reference elbows or a maximumnumber of elbows. Instead, elbows are assigned a length as described below. The length determined foreachelbowissubtractedfromthemaxventlengthinthetablestodeterminehowmuchstraightventpipe(inft)canstillbeused.
Thereareseveraldifferenttypesofelbowsthatcanbeusedforconstructingaventsystem.Thedrawings below show the dimensions of common ¼ bend and ¼ bend long sweep 90 degree elbows fromASTM3311,StandardSpecificationforDrain,WasteandVent(DWV)PlasticFittingsPatterns.
A
longsweep¼bend90degree(longradius)elbowhasanequivalentlengthof5feetofstraightpipe for either 2 or 3 inch plastic pipe. A standard 90° elbow has an equivalent length of 10 feet of pipe.Thisequivalentlengthcanbeusedincircumstanceswhereitmightbenecessarytolengthentheventattheoutsideofthestructure,suchasinareaswithlargeaccumulationsofsnowinwinter.Table 1 shows the equivalent lengths of different types of elbows:
Table 1
Fitting Type Equivalent Length
45° Standard Elbow 5 feet of pipe
90° Standard Elbow 10 feet of pipe
45° Long-Sweep Elbow 2-1/2 feet of pipe
90° Long-Sweep Elbow 5 feet of pipe
Properly seal all joints in the PVC vent
using the following materials and procedures:
PVC CLEANER-PRIMER AND
PVC MEDIUM-BODY SOLVENT
CEMENT
NOTE: Follow vent manufacturer
instructions for ULC S636 vent installations.
IMPORTANT: After cutting pipe,
remove all ragged edges and burrs.
This is important to prevent increase
in pressure drop throughout the system.
1. Cut pipe end square. Chamfer
edge of pipe. Clean fitting socket
and pipe joint area of all dirt,
grease and moisture.
2. After checking pipe and socket
for proper fit, wipe socket and
pipe with cleaner-primer. Apply
a liberal coat of primer to inside
surface of socket and outside of
pipe. READ INSTRUCTIONS
INCLUDED WITH THE PRIMER
FOR PROPER INSTALLATION.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a
heavy coat of cement to the pipe
end and insert pipe into fitting
with a slight twisting movement
until it bottoms out.
NOTE: Cement must be fluid; if
not, recoat with new cement.
4. Hold the pipe in the fitting for 30
seconds to prevent the tapered
socket from pushing the pipe out
of the fitting.
5. Wipe all excess cement from the
joint with a rag. Allow 15 minutes
before handling. Cure time varies
according to fit, temperature and
humidity.
NOTE: Stir the solvent cement frequently while using. Use a natural
bristle, one inch wide brush or the
applicator supplied with the can.
IMPORTANT: For Proper Installation DO
NOT use solvent cement that has
become curdled, lumpy or thickened.
DO NOT thin. Observe shelf precautions
printed on containers. For application
below 32°F, use only low-temperaturetype solvent cement.
For correct installation of the vent pipe,
follow the instructions provided by the
manufacturers of the pipe, primer and
solvent.
EQUIVALENT VENTING
––
ASSIGNING VENT
LENGTH TO ELBOWS
This section applies to venting tables in
both the NON-DIRECT and DIRECT
VENT tables in this book. Vent tables
are provided only in equivalent length
and do not reference elbows or a maximum number of elbows. Instead, elbows
are assigned a length as described
below. The length determined for each
elbow is subtracted from the max vent
length in the tables to determine how
much straight vent pipe (in ft) can still be
used.
ASTM
SPECIFICATION
D2661
D2665
There are several different types of
elbows that can be used for constructing a vent system. The drawings below show the dimensions of
common 1/4 bend and 1/4 bend long
sweep 90 degree elbows from ASTM
3311, Standard Specification for
Drain, Waste and Vent (DWV) Plastic
Fittings Patterns.
A long sweep 1/4 bend 90 degree
(long radius) elbow has an equivalent
length of 5 feet of straight pipe for
either 2 or 3 inch plastic pipe. A standard 90° elbow has an equivalent
length of 10 feet of pipe. This equivalent length can be used in circumstances where it might be necessary
to lengthen the vent at the outside of
the structure, such as in areas with
large accumulations of snow in winter. Table 1 shows the equivalent
lengths of different types of elbows:
With the equivalent length vent
concept a vent system can be
used any number of elbows and
length of straight pipe as long as
the maximum equivalent vent
length is not exceeded.
Example:
An RGFG-06 direct vent installation
needs a 31 foot long vent run with 5
elbows and 2 inch pipe.
31 feet of 2 inch pipe = 31
5 - 1/4 bend long sweep
elbows = 25
Since the maximum equivalent vent
length for an RGFG-06 is 60 feet, this
installation is acceptable.
If the same installation tried to use
standard elbows:
31 feet of 2 inch pipe = 31
5 - standard 90 degree
TABLE 1
And this installation is not acceptable
as it exceeds the 80 foot maximum
listed for the RGFG-06 model.
equivalent feet
equivalent feet
Total = 56
equivalent feet
equivalent feet
= 50
equivalent feet
Total = 81
equivalent feet
13
NON-DIRECT VENT PIPE INSTALLATION
(FOR VERTICAL TERMINATIONS ONLY)
COMBUSTION AIR
WARNING
!
ALWAYS PROVIDE THIS FURNACE AND ANY OTHER FUEL
BURNING APPLIANCE WITH
ENOUGH FRESH AIR FOR
PROPER COMBUSTION AND
VENTILATION OF THE FLUE
GASES. MOST BUILDING
CODES REQUIRE THAT OUTSIDE AIR BE SUPPLIED INTO
THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE
DEATH FROM CARBON
MONOXIDE POISONING.
Provide adequate facilities for combustion and ventilation air in accordance with section 5.3, Air for
Combustion and Ventilation of the
National Fuel Gas Code, ANSI
Z223.1 - latest edition; CAN/CGA
B149.1 and .2, or applicable provisions of the local building codes.
These combustion and ventilation
facilities must not be obstructed.
IMPORTANT: Air for combustion and
ventilation must not come from a
corrosive atmosphere. Any furnace
failure due to corrosive elements in
the atmosphere is excluded from
warranty coverage.
The following types of installation (but
not limited to the following) REQUIRE
OUTDOOR AIR for combustion, due
to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry
rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
Exposure to the following substances
in the combustion air supply (but not
limited to the following) also
REQUIRE OUTDOOR AIR for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool
chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon Tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers,
varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Anti-static fabric softeners for
clothes dryers
• Masonry acid washing materials
Combustion air must be free of acid
forming chemicals such as sulphur,
fluorine, and chlorine. These elements are found in aerosol sprays,
detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrigerants and many
other commercial and household
products. Vapors from these products
when burned in a gas flame form acid
compounds. The acid compounds
increase the dew point temperature
of the flue products and produce
highly corrosive condensate.
WARNING
!
ALL FURNACE INSTALLATIONS
MUST COMPLY WITH THE
NATIONAL FUEL GAS CODE,
CAN/CSA B149.1 (CANADA) AND
LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE.
FAILURE TO DO SO CAN RESULT
IN EXPLOSION, FIRE, PROPERTY
DAMAGE, CARBON MONOXIDE
POISONING, PERSONAL INJURY
OR DEATH.
Combustion air requirements are
determined by whether the furnace
is in an open (unconfined) area or in
a confined space such as a closet or
small room.
FURNACE LOCATED IN AN
UNCONFINED SPACE
Using indoor air for combustion.
An unconfined space must have at
least 50 cubic feet for each 1,000
BTUH of the total input for allappliances in the space. Here are a
few examples of the room sizes
required for different inputs. The
sizes are based on 8 foot ceilings.
See Table 2.
TABLE 2
UNCONFINED SPACE DIMENSIONS
BTUH Minimum Sq. Feet Typical Room Size
Input With 8 foot Ceiling
60,00037515' x 25' OR 19' x 20'
75,00046915' x 32' OR 20' x 24'
90,00056320' x 28' OR 24' x 24'
105,00065720' x 33' OR 26' x 25'
120,00075025' x 30' OR 24' x 32'
If the open space containing the furnace is in a building constructed to
severely limit outside air infiltration
(contemporary energy efficient construction methods), outside air may
still be required for the furnace to
operate and vent properly. Outside
air openings should be sized the
same as for a confined space.
14
FURNACE LOCATED IN A
CONFINED SPACE.
A confined space (any space smaller than shown before as “unconfined”) must have openings into
the space, which are located in
accordance with the requirements set forth in the following
subsections A and B. The open-
ings must be sized by how they
connect to the heated area or to the
outside, and by the input of all
appliances in the space.
If the confined space is within a
building with tight construction,
combustion air must be taken from
outdoors or areas freely communicating with the outdoors.
TABLE 3
INDOOR AIR OPENING DIMENSIONS
BTUHFree Area
InputEach Opening
60,000100 square inches
75,000100 square inches
90,000100 square inches
105,000105 square inches
120,000120 square inches
FIGURE 6
AIR FROM HEATED SPACE
A. USING INDOOR AIR FOR
COMBUSTION
IMPORTANT: DO NOT take air from
a heated space with a fireplace,
exhaust fan or other device that may
produce a negative pressure.
If combustion air is taken from the
heated area (see Figure 6), the
openings must each have at least
100 square inches of free area.
Each opening must have at least
one square inch of free area for
each 1,000 BTUH of total input in
the space. See Table 3.
B. USING OUTDOOR AIR FOR
COMBUSTION
IMPORTANT: Do not take air from
an attic space that is equipped with
power ventilation.
The confined space must communicate with the outdoors in accordance
with Methods 1 or 2. The minimum
dimension of air openings shall not
be less than 3 inches. Where ducts
are used, they shall be of the same
cross-sectional area as the free area
of the openings to which they connect.
Method 1
Two permanent openings, one located within 12 inches of the top and
one located within 12 inches of the
bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors.
a. Where directly communicating
with the outdoors or where communicating to the outdoors
through vertical ducts as shown in
Figure 7, each opening shall have
a minimum free area of 1 square
inch for each 4000 BTUH of total
appliance input rating in the
enclosure. See Table 4.
A077501
TABLE 4
VERTICAL OUTDOOR AIR OPENING
DIMENSIONS
BTUHFree AreaRound Pipe
InputEach OpeningSize
60,00015.00 square inches5"
75,00018.75 square inches5"
90,00022.50 square inches6"
105,00026.25 square inches6"
120,00030.00 square inches7"
15
b. Where communicating with out-
doors through horizontal ducts,
each opening shall have a minimum
free area of 1 square inch for each
2000 BTUH of total input rating of
all equipment in the enclosure. See
Table 5 and Figure 8.
TABLE 5
HORIZONTAL OUTDOOR AIR
OPENING DIMENSIONS
BTUHFree AreaRound Pipe
InputEach OpeningSize
60,00030.00 square inches7"
75,00037.50 square inches7"
90,00045.00 square inches8"
105,00052.50 square inches9"
120,00060.00 square inches9"
Method 2
One permanent opening, located
within 12 inches of the top of the
enclosure, shall be permitted where
the equipment has clearances of at
least 1 inch from the sides and back
and 6 inches from the front of the
appliance. The opening shall directly
communicate with the outdoors or
communicate through a vertical or
horizontal duct to the outdoors or
spaces (crawl or attic) that freely
communicate with the outdoors, and
shall have a minimum free area of:
a. One square inch for each 3000
BTUH of the total input rating of
all equipment located in the
enclosure (see Table 6), and
Combustion air openings must not be
restricted in any manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
FIGURE 7
AIR FROM ATTIC/CRAWL SPACE
A077601
FIGURE 8
OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET
b. Not less than the sum of the
areas of all vent connectors in the
confined space.
If the unit is installed where there is
an exhaust fan, sufficient ventilation
must be provided to prevent the
exhaust fan from creating a negative
pressure.
TABLE 6
VERTICAL OR HORIZONTAL
OUTDOOR AIR OPENING DIMENSIONS
direct furnace, only vertical terminations
are allowed. Do not use horizontal terminations when the furnace is installed with
a non-direct vent.
All exhaust vent piping must be installed
in compliance with Part 7, Venting of
Equipment, of the latest edition of the
National Fuel Gas Code NFPA 54/ANSI
A223.1, or CAN/CGA-B149.1 and .2,
local codes or ordinances and these
instructions.
7. The minimum vent length is 5 feet.
8. All piping through the roof is 2".
When using 3" pipe on 90, 105
and 120 kBtu furnaces, reduce
to 2" within 18" of the inside of
the roof.
9. Vertical through-the-roof installations do not require any special
vent termination. Use 2" PVC
pipe extending a minimum of 12
inches above the anticipated
maximum level of snow accumulation.
In Canada, the pipe must extend a
minimum of 18” above the roof or
maximum 24” above the roof without supports.
10. No screens may be used to
cover combustion air or
exhaust.
1. IMPORTANT: Do not common vent
with any other appliance. Do not
install in the same chase or chimney with a metal or high temperature plastic pipe from another gas or
fuel-burning appliance unless the
required minimum clearances to
combustibles are maintained
between the PVC pipe and other
pipes.
2. Use only medium or long radius
sweep elbows, such as PVC-DWV
elbows.
3. Vertical vent piping is preferred.
4. Install all horizontal piping as follows:
• Slope horizontal vent piping
upward a minimum of 1/4" per
foot of run so that condensate
drains toward the furnace.
• Support horizontal vent piping at
least every four feet. No sags or
dips are permitted.
5. Insulate all vent runs through
unconditioned spaces where belowfreezing temperatures are expected,
with 1" thick medium density, foil
faced fiber glass or equivalent
Rubatex/Armaflex insulation. For
horizontal runs where water may
collect and freeze, wrap the vent
pipe with self-regulating, 3 or 5 Watt
heat tape. The heat tape must be
U.L. listed and installed per the
manufacturer’s instructions.
6. All piping between the furnace and
the roof penetration is 2" or 3" as
specified in Table 7. Table 7 lists the
maximum allowable exhaust vent
pipe length for the number of
elbows used, based on the furnace
size.
IMPORTANT: Use Only standard
vertical terminations when installing
the modulating furnace as a nondirect vent appliance.
2. MAXIMUM OF 6 ELBOWS MAY BE USED. DO NOT COUNT ELBOWS IN ALTERNATE TERMINATION KIT.
MEDIUM OR LONG SWEEP ELBOWS MAY BE USED.
3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW.
4. CONCENTRIC TERMINATION NO. RXGY-E03A IS FOR THRU-THE-ROOF OR THRU-THE-WALL VENTING.
5. USE KITS RXGY-D02 OR D02A (2") OR RXGY-D03 OR D03A (3") FOR STANDARD OR ALTERNATE
THRU-THE-WALL VENTING.
6. USE KITS RXGY-D04 OR D04A FOR ALTERNATE VENTING OF 120,000 BTUH UNITS WITH LONG RUNS.
7. NO SCREENS MAY BE USED TO COVER COMBUSTION AIR AND EXHAUST.
1
⁄2” CABINET WIDTH
* A = 17
B = 21” CABINET WIDTH
8. ALL HORIZONTAL VENTING MUST BE DONE WITH DIRECT VENTING (2-PIPE). FURNACES INSTALLED
AS NON-DIRECT VENT MUST BE TERMINATED VERTICALLY.
17
DIRECT VENT PIPE INSTALLATION
WARNING
!
READ AND FOLLOW ALL
INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY
VENT THIS FURNACE CAN
CAUSE CARBON MONOXIDE
POISONING OR AN EXPLOSION
OR FIRE, RESULTING IN PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
Direct vent installations require a dedicated combustion air and venting system. All air for combustion is taken
from outside and all combustion products are discharged to the outdoors.
Therefore, no ventilation or combustion air openings are required.
INSTALLATION
GUIDELINES
All exhaust piping must be installed in
compliance with Part 7, “Venting of
Equipment,” of the latest edition of the
National Fuel Gas Code NPFA 54,
90A, 90B ANSI Z223.1-, CAN/CSA
B149.1 (Canada), local codes or ordinances and these instructions.
1. IMPORTANT: Do not common
vent with any other appliance. Do
not install in the same chase or
chimney with a metal or high temperature plastic pipe from another
gas or fuel-burning appliance
unless the required minimum
clearances to combustibles are
maintained between the approved
PVC pipe and other pipes.
2. Use only medium or long radius
sweep elbows.
NOTE: For all installations. Extend
the combustion air exhaust pipe a
minimum of 18" vertically above
the furnace cabinet before turning
the vent.
3. Vertical piping is preferred.
4. Install all horizontal piping as follows:
• Slope horizontal vent piping
upward a minimum of 1/4" per foot
of run so that condensate drains
toward the furnace.
• Support horizontal vent piping at
least every four feet. No sags or
dips are permitted.
In Canada, refer to manufacturer’s
instructions for supporting ULC S636
venting.
➤ TABLE 8
DIRECT VENT APPLICATIONS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE
5. Insulate all vent runs through
unconditioned spaces where
below-freezing temperatures are
expected with 1" thick medium
density, foil faced fiber glass or
equivalent Rubatex/Armaflex insulation. For horizontal runs where
water may collect, wrap the vent
pipe with self-regulating, 3 or 5
Watt heat tape. The heat tape
must be U.L. listed and installed
per the manufacturer’s instructions.
6. All piping between the furnace
and the roof or outside wall penetration is 2" or 3" as specified in
Table 8. Table 8 lists the maximum allowable length for the
exhaust vent pipe and intake air
pipe for the number of elbows
used, based on the type of termination and furnace size.
7. The minimum vent length is 5 feet for any termination.
8. All piping through the roof or outside wall is 2". When using 3"
pipe, reduce to 2" within 18" of
the inside of the roof or outside
wall (except 120,000 BTUH
model using the RXGY-D04 or
D04A Horizontal Vent Kit).
9. Terminate the vent using one of
the following termination options.
3
4
10. No screens may be used to cover
combustion air or exhaust.
VERTICAL TERMINATIONS
STANDARD VERTICAL TERMINATIONS
Combustion Air Piping
um-radius sweep elbows to keep the
inlet downward and prevent the entry of
rain. The inlet opening of the com-
bustion air termination must be a
minimum of 12" above the anticipated level of snow accumulation.
In Canada, the inlet pipe must extend a
minimum of 18” above the roof or a
maximum of 24” above the roof without
support.
Exhaust Vent Piping
must terminate at least 12 inches
above the combustion air termination
inlet. The maximum length of the
exposed vent pipe above the roof is
30".
(See Figure 9)
: Use two medi-
: The exhaust vent
PIPE REDUCTION
NOT REQUIRED ON
60 & 75K BTU MODELS
This kit is for vertical and horizontal
intake air/vent runs. One
5-in. diameter hole is required for
installation. See Figure 10 for the general layout. Complete installation
instructions are included with the kit.
" PVC PIPE SCHEDULE 40 -- 37.125" LONG
" PVC PIPE SCHEDULE 40 -- 24" LONG
" x 3" x 4" SPECIAL CONCENTRIC FITTING
" x 45° STREET ELBOW (FIELD SUPPLIED)
NNOOTTEE::
The following IPEX brand concentric terminations (System 636) may
be purchased in the field
and used in
place of factory supplied kits:
3” Concentric Kit – Item # 196006
VVEERRTTIICCAALLIINNSSTTAALLLLAATTIIOONN
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
In Canada, maintain a
minimum distance of 18”
above the roof or 24”
maximum without
additional support.
HHOORRIIZZOONNTTAALLIINNSSTTAALLLLAATTIIOONN
FFIIEELLDD--SSUUPPPPLLIIEEDD
SSTTRRAAPP
A
NOTE: AIR
ORIENTATION SENSITIVE.
INTAKE NOT
11""MMAAXXIIMMUUMM
A
A
NOTE: Drain tee is not needed for the inlet pipe.
20
INSTALLATION – RXGY-G02(U.S.) & RXGY-G02C (Canada certified to
ULC S636) Side Wall Vent
FIGURE 11
VENT KIT INSTALLATION OPTIONS
FIGURE 12
TYPICAL INSTALLATION
For all models installed with 3” pipereduce to a length between 12 inches
and 30 inches of 2 inch pipe.
Note: Vent should protrude a
maximum of 2-1/4” beyond vent plate.
Air intake should protrude a maximum
of 1 inch beyond vent plate.
Seal all wall cavities.
ST-A1075
21
HORIZONTAL TERMINATIONS
All horizontal venting must be done
with direct venting (2 pipe). Furnaces
installed as non-direct vent must be
terminated vertically.
STANDARD HORIZONTAL TERMINA
TIONS
NOTE: A
intakes (except those using horizontal
concentric vent kit RXGY-E03A) must
have a drain tee assembly and trap
installed in the combustion air pipe as
close to the furnace as possible. This is
to drain any water that may enter the
combustion air pipe to prevent it from
entering the furnace vestibule area.
These parts are included in horizontal
vent kits RXGY-D02A, RXGY-D03Aand
RXGY-D04A.
NNOOTTEE::
t
above grade or anticipated snow levels.
Use alternate horizontal terminations
when termination locations are limited
and higher snow levels are anticipated.
((SSEEEEFFIIGGUURREE1133))
ll furnaces with horizontal air
The combustion air and exhaust
erminations must be at least 12 inches
NNOOTTEE::
b
ustion air inlet with respect to the
sure the location of the com-
En
exhaust vent terminal complies with
Figure 13, detail C.
Combustion Air Piping
coupling with a wind deflector vane (pro-
vided) installed as follows:
: Use a 2" PVC
1. Install a 2" coupling to the combustion air pipe at the outside wall to
prevent the termination from being
pushed inward.
2. Cut a 2 1/4" length of 2" PVC pipe
and connect this to the coupling.
3. Connect another 2" coupling to the
end of the 2 1/4" length of pipe.
Terminate this outer coupling 4
inches from the wall.
4. Attach the vane in the final 2" coupling in the vertical position with
PVC cement.
IMPORTANT: To insure proper furnace operation, install the vane in
the vertical position as shown in
Figure 13, Detail B. Failure to install
the vane properly can result in nuisance tripping of the pressure
switch.
Exhaust Vent Piping
:
60,000 and 75,000 BTUH models:
Use 2" pipe only for the entire
length of the vent.
90,000 through 120,000 BTUH
models: Install a 2" coupling at the
outside wall to prevent the termination from being pushed inward. No
reduction of the 2" pipe used to
penetrate the wall is necessary.
Terminate the 2" PVC exhaust vent
at least 12 inches from the outside
wall.
FIGURE 13
STANDARD HORIZONTAL DIRECT VENTING
UPFLOW MODEL SHOWN
(TYPICAL FOR DOWNFLOW/HORIZONTAL MODELS)
NOTES:
SUPPORT HORIZONTAL
➀
PIPE EVERY FOUR FEET.
WHEN 3 IN. PIPE IS USED REDUCE TO
ABOVE GRADE TO KEEP TERMINAL
OPENINGS ABOVE ANTICIPATED
LEVEL OF SNOW ACCUMULATION
WHERE APPLICABLE.
DETAIL “B”, INSTALL WIND DEFLEC-
➅
TOR VANE IN 2 IN. PVC COUPLING IN
VERTICAL POSITION USING PVC
SOLVENT.
THE COMBUSTION AIR TERMINATION
MUST BE IN THE SAME PRESSURE
ZONE AS THE EXHAUST TERMINATION.
EEXXHHAAUUSSTTTTEERRMMIINNAATTIIOONN
EXHAUST/INTAKE RELATIONSHIP
DETAIL C
PIPE REDUCTION NOT REQUIRED
1
2
3
ON 60 & 75K MODELS W/2” PIPE.
REDUCTION IS STILL REQUIRED
WITH 3” PIPE.
NO SCREENS OR ELBOWS
AT THE END OF THE PIPES
DETAIL C
5
4
DETAIL A
EXHAUST
TERMINATION
(3” PIPE ONLY)
6
COMBUSTION AIR TERMINATION
DETAIL B
12”
ST-A0407-00
22
ALTERNATE HORIZONTAL TERMINATIONS (See Figure 14)
NNOOTTEE::
exhaust
The combustion air and
terminations must be at least
12 inches above grade or anticipated
snow levels. Alternate horizontal terminations allow the combustion air
and exhaust terminations to be raised
a maximum of 60 inches above the
wall penetrations to maintain the
required clearance.
NNOOTTEE::
extended
If combustion air vent pipe is
more than 24 inches, insulate the vent pipe between the two
outside 90° elbows with closed cell
insulation such as rubatex, armaflex
or equivalent.
NNOOTTEE::
combust
Ensure the location of the
ion air inlet with respect to
the exhaust vent terminal complies
with Figure 14.
Combustion Air Piping
: Use a 2" PVC
elbow with a wind deflector vane (provided) installed as follows:
1. Install a 2" elbow to the combustion
air pipe at the outside wall to prevent
the termination from being pushed
inward.
FIGURE 14
ALTERNATE HORIZONTAL DIRECT VENT TERMINATION
SEE DETAIL A
3" MAX.
NOTE: 3-1/2"
MAX. WHEN
D04 KIT IS
USED.
EXHAUST VENT
211/2" PVC FOR MODELS WITH 120,000 BTUH INPUT
(KIT NO. RXGY-D04A)
2" PVC FOR MODELS WITH INPUTS OF 90,000 THRU 120,000
BTUH. REDUCE TO 111/2" FOR MODELS WITH INPUTS OF 60,000
AND 75,000 BTUH. ELBOWS AND RISERS ARE 2" PVC.
12" FROM WALL
PIPE
SUPPORT
STRAP
DETAIL C
EXHAUST/INTAKE RELATIONSHIP
NOTE: If combustion air vent pipe is extended more
than 24 inches, insulate the vent pipes between the
two outside 90° elbows with closed cell insulation
such as rubatex, armaflex, or equivalent.
INTAKE VENT
211/2" PVC FOR MODELS WITH
120,000 BTUH INPUT.
2" PVC ELBOWS AND RISER
MODELS WITH INPUTS OF 75,000
THRU 120,000 BTUH.
USE KIT NO. RXGY-D02 OR D02A WHEN 2"
PIPE IS USED BETWEEN FURNACE AND
OUTSIDE WALL. USE KIT NO. RXGY-D03
OR D03A WHEN 3" PIPE IS USED.
DETAIL A
EXHAUST VENT FOR
MODELS WITH INPUT OF
60,000 AND 75,000 BTU
I339
2. Cut an adequate length of 2" PVC
pipe as needed to clear the anticipated snow level and connect this to
the elbow.
3. Connect another 2" elbow to the
end of the pipe such that the inlet is
facing away from the wall. This outer
coupling must terminate 4 inches
from the wall.
4. Attach the vane in the final 2" elbow
in the vertical position with PVC
solvent.
IMPORTANT: To insure proper furnace operation, the supplied vane
must be installed in the vertical position as shown in Figure 13, Detail B.
Exhaust Vent Piping
:
1. Install a 2" elbow to the exhaust vent
pipe at the outside wall to prevent the
termination from being pushed
inward.
2. Cut an adequate length of 2" PVC
pipe as needed to insure proper location of the exhaust vent termination
with respect to the combustion air
inlet and connect this to the elbow.
3. Connect another 2" elbow to the end
of the pipe such that the inlet is facing away from the wall.
Exhaust Vent Termination:
60,000 and 75,000 BTUH models:
Use 2" pipe only for the entire length
of the vent.
90,000 through 120,000 BTUH mod els: No reduction of the 2" pipe used
to penetrate the wall is necessary.
Terminate the 2" PVC exhaust vent
at least 12 inches from the outside
wall.
120,000 BTUH model with the
RXGY-D04A Horizontal Vent Kit:
Venting and terminations install the
same as above except the 2" pipe
and connectors are replaced with 2
1/2" pipe and connectors.
23
LOCATION REQUIREMENTS
HORIZONTAL DIRECT VENTS
CAUTION
!
THE COMBUSTION PRODUCTS
AND MOISTURE IN THE FLUE
GASES WILL CONDENSE AS
THEY LEAVE THE TERMINATION.
THE CONDENSATE CAN FREEZE
ON THE EXTERIOR WALL,
UNDER THE EAVES AND ON
SURROUNDING OBJECTS.
SOME DISCOLORATION TO THE
EXTERIOR OF THE BUILDING IS
TO BE EXPECTED. HOWEVER,
IMPROPER LOCATION OR
INSTALLATION CAN RESULT IN
STRUCTURAL OR EXTERIOR
FINISH DAMAGE TO THE BUILDING AND MAY RECIRCULATE
PRODUCTS OF COMBUSTION
INTO THE COMBUSTION AIR
TERMINAL AND FREEZE.
NOTE: In Canada vent terminations
must be in accordance with the current
CAN/CSA B149.1 Gas Installation
Code.
The vent must be installed with the following minimum clearances. See
Figures 15 and 16.
1. Locate the bottom of the vent terminal and the air inlet at least 12
inches above grade. Increase the
12-in. minimum to keep the terminal openings above the level of
snow accumulation, where applicable.
2. Do not terminate the vent over public walkways or over an area where
condensate or vapor could create a
nuisance or hazard.
3. Locate the vent terminal at least
one foot from any opening through
which flue gases could enter a
building.
4. Locate the vent terminal at least 3
feet above any forced air inlet
located within 10 feet, except the
combustion air inlet of a direct vent
appliance.
5. Allow the vent terminal minimum
horizontal clearance of 4 feet from
electric meters, gas meters, regulators and relief equipment.
6. Locate the furnace combustion air
inlet a sufficient distance from the
vent of any other gas or fuel burning appliance or electric clothes
dryer to prevent recirculation of the
flue gases into the furnace combustion air inlet. The only exception
to this requirement is the case of
multiventing two or more furnaces,
which is covered in the section on
multiventing in these instructions.
In addition to the minimum clearances
listed above, the vent location should
be governed by the following guidelines.
1. Do not terminate under any kind of
patio or deck (exceptions for
Canada are permitted under
CAN/CSA B149.1). If running the
vent under a deck, insulate it to
insure no condensate freezes and
blocks the pipe. The insulation
must be waterproof.
For vent considerations, the edge
of the deck must be considered
the outside wall.
2. Do not terminate behind any area
that may allow the flue products to
become stagnant and recirculate.
3. Do not locate on the side of a
building with prevailing winter
winds. This will help prevent moisture from freezing on walls and
overhangs (under eaves).
4. Do not extend vent directly
through brick or masonry surfaces. Use a rust-resistant sheet
metal or plastic backing plate
behind vent. See Figure 7.
5. Do not locate too close to shrubs
as condensate may stunt or
kill them.
FIGURE 15
MOISTURE ZONES
6. Minimum vertical clearances of 1
foot are recommended for overhangs up to 1 foot horizontal.
The vertical clearance should be
increased equally for each additional increase in horizontal overhang to a maximum vertical
clearance of 6 feet.
7. Caulk all cracks, seams and
joints within 6 feet horizontally
as well as 6 feet above and
below vent. See Figure 15.
8. Painted surfaces must be sound
and in good condition with no
cracking, peeling, etc. Painted
surfaces will require maintenance.
9. Do not expose 3" x 2" reducer/
bushing to outdoor ambient temperatures.
MULTIVENTING
IF VENTING TWO OR MORE FURNACES NEAR EACH OTHER IS
REQUIRED, EACH FURNACE
MUST BE INDIVIDUALLY VENTED –
NO COMMON VENTING IS PERMITTED. See Figures 17 and 18 for posi-
tioning of the terminations. When
2 FT. SQ. SHEET METAL PLATE ON BRICK OR
MASONRY SURFACE RECOMMENDED, BUT
NOT REQUIRED BY CODE.
24
FIGURE 16
Natural Gas and Propane Installation Code
National Fuel Gas Code
Canadian Installations
US Installations
Canadian Installations
US Installations
1 ft. (30.5 cm)
4 ft. (1.22 m)
3 ft. (91 cm)
1 ft. (30.5 cm)
3 ft. (91 cm)
12 inches (30 cm) for
appliances > 10,000 BTUH
(3 kW) and < 100,000
BTUH (30 kW), 36 inches
(91 cm) for appliances >
100,000 BTUH (30 kW)
For clearances not specified in ANSI Z223.1 / NFPA 54 or CAN/CSA-B149, one of the following shall
more than two furnaces are to be
vented, there must be at least 4 feet
between the first two furnaces and
the third, etc.
CONNECTING TO
FURNACE
IMPORTANT: Clean and deburr all
pipe cuts. The shavings must not be
allowed to block the exhaust, inlet or
condensate drain pipes.
IMPORTANT: When indoor combustion air is used, the inlet air opening
at the furnace must be protected from
accidental blockage. On downflow
models, install a double elbow in the
top inlet air opening.
SEE CONCENTRIC
VENT SECTION
ON PAGE 23
FOR MORE
INFORMATION.
UPFLOW MODELS
The exhaust air pipe connection is a
2-in. female PVC pipe fitting extending through the left
nace top plate. See Figure 19. This
opening has a protective cap which
should be removed just prior to
installing the exhaust pipe. When 2in. pipe is used, connect it directly to
this fitting. When 3-in. pipe is used,
connect a 2 to 3-in. coupling to this
fitting with a short piece of 2-in. PVC
pipe.
The inlet combustion air connection
is at the right
An alternate combustion inlet air connection may be made on the right
side of the jacket. The alternate con-
88””MMIINNIINNUUMM
2244””MMAAXXIIMMUUMM
side of the fur-
side of the top plate.
66‘‘MMIINNIIMMUUMM,,
1100‘‘RREECCOOMMMMEENNDDEEDD((UUSS))
33‘‘MMIINNIIMMUUMMCCAANNAADDAAOONNLLYY..
SEE CONCENTRIC VENT SECTION
ON PAGE 20 FOR MORE INFORMATION.
nection opening has a plastic cap. A
combustion inlet air connection fitting
is supplied with the furnace and it
must be installed in the furnace by
screwing it into the opening. Make
sure the rubber “O-ring” supplied with
the furnace is used with this fitting.
See Figure 19.
IMPORTANT: When using indoor
combustion air, the furnace air opening must be protected from accidental
blockage. Install a 2-inch 90° elbow
pointing downward on the side or a
double elbow pointing downward in
the top opening.
FIGURE 19
UPFLOW COMBUSTION AIR AND VENT PIPE CONNECTION
(GAS VALVE MAY BE DIFFERENT THAN SHOWN)
FIGURE 20
UPFLOW MODELS -- COMBUSTION AIR FITTING
ST-A1157-01
27
CONDENSATE DRAIN/OPTIONAL NEUTRALIZER
GENERAL INFORMATION
CAUTION
!
DO NOT RUN DRAIN OUTDOORS.
FREEZING OF CONDENSATE CAN
CAUSE PROPERTY DAMAGE.
IMPORTANT: Do not connect into a com-
mon drain line with an air conditioner
evaporator coil drain located below the
furnace. A blocked or restricted drain line
can result in overflow of the coil pan and
negate the furnace blocked-drain shutoff
control.
➤ IMPORTANT: If installing the unit over
a finished ceiling or living area, be certain
to install an auxiliary condensate drain
pan under the entire unit extending out
under the condensate tee. With the mini-
1
mum 5
or 13⁄4" for downflow models installed
above the tee, a blocked drain will result
in overflow from the riser. if the furnace is
installed in an attic, crawlspace or other
area where freezing temperatures may
occur, the furnace drain can freeze while
shut off for long periods of time.
If required by local codes, install a condensate neutralizer cartridge in the drain
line. Install cartridge in horizontal position
only. Also install an overflow line if routing
to a floor drain (see Figure 21). If available, install a condensate pump that is
resistant to acidic water. Pumps are available from your local distributor. If pump
used is not resistant to acidic water, a
condensate neutralizer must be used
ahead of the pump. The condensate
pump must have an auxiliary safety
switch to prevent operation of the furnace
and resulting overflow of condensate in
the event of pump failure. The safety
switch must be wired through the “R” circuit only (low voltage) to provide operation
in either heating or cooling modes.
When selecting neutralizer cartridges and
condensate pumps, use the following
data:
CONDENSATE PRODUCTION:
MAX (ALL MODELS) = 1-2 gallons per hr.
⁄2" riser for upflow models
FIGURE 21
UPFLOW CONDENSATE DRAIN
(GAS VALVE MAY BE DIFFERENT THAN SHOWN)
ST-A1158-01
pH LEVEL:
3.2 - 4.5 using OUTDOOR air
2.2 - 4.5 using INDOOR air
(neutral pH = 7.0)
UPFLOW MODELS
The condensate drain trap is located in
the blower compartment on the left- hand
side of the jacket. A short piece of 1⁄2-in.
PVC pipe and a 1⁄2-in. tee are provided.
Connect the 1⁄2-in. pipe to the elbow on
the trap and the tee to this pipe so that
the open end is upward. Run a drain tube
from the bottom of the tee to a floor drain
or condensate pump.
IMPORTANT: If installing the unit over a
finished ceiling or living area, be certain
to install an auxiliary condensate drain
pan under the entire unit extending out
under the condensate tee.
28
IMPORTANT: There are two options
when choosing a height for the condensate riser:
CONDENSATE OVERFLOW: With a
1
5
⁄2inch riser installed above the tee,
a blocked drain will result in overflow
from the riser.
FURNACE SHUTDOWN: To cause
the furnace to shut down when a
blocked drain is present, install a riser
which is a minimum of 10
13
⁄16”. If the
furnace is installed in an attic, crawlspace or other area where freezing
temperatures may occur, the furnace
drain can freeze while shut off for long
periods of time.
Use a solvent cement that is compatible with PVC material. Cut the drain
hoses to the appropriate length and
connect to the trap with hose clamps.
Tighten the clamps with pliers and
check for leaks after attaching.
FIGURE 22
UPFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
(NO KIT REQUIRED)
REVERSING THE TRAP
UPFLOW MODELS
The trap may be moved to the right
side for right-side drainage. Open the
knockout for the drain on the right side
of the cabinet. Remove the bracket
holding the trap from the left side.
Seal the left side drain hole with a
plug provided in the cloth bag with the
furnace. Position the mounting bracket
and trap so that the drain elbow is
centered in the hole on the right. See
Figure 22.
Drill two holes in the cabinet to mount
the bracket. Mount the trap and bracket to the right side with the drain
elbow pointing through the knockout.
Connect the
above. Route the drain hoses behind
the top of the electric box, cut to the
appropriate length, and connect to the
trap with hose clamps.
IMPORTANT: Do not connect into a
common drain line with an air conditioner evaporator coil drain located
above the furnace. A blocked or
restricted drain line can result in overflow of the coil pan and negate the
furnace blocked drain shutoff control.
1
⁄2" pipe and tee as noted
ST-A1159-01
29
GAS SUPPLY AND PIPING
GAS SUPPLY
WARNING
!
THIS FURNACE IS EQUIPPED
AT THE FACTORY FOR USE ON
NATURAL GAS ONLY. CONVERSION TO LP GAS REQUIRES A
SPECIAL KIT
TTHHEEDDIISSTTRRIIBBUUTTOORR
USE THE PROPER CONVERSION KIT CAN CAUSE FIRE,
CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY
DAMAGE, PERSONAL INJURY
OR DEATH.
See the conversion kit index supplied with the furnace. This index
identifies the proper LP Gas
Conversion Kit required for each
particular furnace.
IMPORTANT: Any additions, changes
or conversions required for the furnace
to satisfactorily meet the application
should be made by a qualified installer,
service agency or the gas supplier,
using factory-specified or approved
parts.
IMPORTANT: Connect this furnace
only to gas supplied by a commercial
utility.
IMPORTANT: A U.L. recognized
fuel gas and CO detector(s) are recommended in all applications, and their
installation should be in accordance
with the manufacturer’s recommendations and/or local laws, rules, regulations or customs.
AAVVAAIILLAABBLLEEFFRROOMM
. FAILURE TO
FIGURE 23
GAS PIPING -- UPFLOW INSTALLATION
(GAS VALVE MAY BE DIFFERENT
THAN SHOWN)
MANUAL
GAS VALVE
4 TO 5 FT.
ABOVE FLOOR
REQ’D BY
SOME
UTILITIES.
GROMMET
(IN NORMAL
POSITION)
DRIP LEG
UNION
(TYPICAL INSTALLATION)
TTOOPPVVIIEEWWOOFFGGAASSLLIINNEEAANNDD
VVAALLVVEE
IINNOOPPTT..PPOOSSIITTIIOONN
BURNERS
GROMMET
NOTE:
WHEN GAS LINE IS IN OPT.
POSITION, SWAP LOCATION
OF GROMMET AND PLUG.
OPTIONAL GAS LINE
POSITION
GAS VALVE
PLUG
(IN NORMAL
POSITION)
MANIFOLD
IMPORTANT: Do not run a flexible gas connector inside the unit.
MANIFOLD
PRESSURE TAP
A1122-01_1
GAS PIPING
Install the gas piping according to all
local codes and regulations of the utility company.
If possible, run a separate gas supply
line directly from the meter to the furnace. Consult the local gas company
for the location of the manual main
shut-off valve. The gas line and man-
ual gas valve must be adequate in
size to prevent undue pressure drop
and never smaller than the pipe size
30
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.