>ViÊNÊ>ÊÀÞÊ}ÊNÊ>ÀiÞ
}Ê/iV}iÃ
Marley HP7000 Fan Clamped Blade Shank – 192" thru 240"
/
/
User Manual 01-1139A
Fan Components
300
101
120 ft·lbƒ (163 N·m)
SEE FIG 6 FOR DETAILS
15 ft·lbƒ (20 N·m)
OUTBOARD ROW NOT REQD
ON 30" DIA. HUB ASSEMBL
150 ft·lbƒ (204 N·m)
HUB ASSEMBLY
IDENTIFICATION NUMBER
102
131
121
122
123
133
140
132
111
200
132
100 Hub
101 Hub Center
102 Hub Plate
110 Kit–Blade Clamp
111 Blade Clamp
120 Kit–Center Hub Hardware
121 Cap Screw
122 Flat Washer
123 Pin
130 Kit–Blade Clamp Hardware
131 Machine Bolt
132 Flat Washer
133 Locking Hex Nut
Hex Nut
134 Thread Lubricant
140 Kit–Hub Cover Hardware
141 Machine Bolt C\,″
142 Flat Washer
143 Lock Washer
144 Hex Nut
145 Locking Hex Nut
146 Spacer
150 Kit–Balance Hardware
160 Manual
200 Blade
300 Hub Cover
2
Z\x″
B\,″
B\,″
C\v″
C\v″
C\v″ or
C\v″ and Lock Washer C\v″
C\,″
C\,″
C\,″
C\,″
Figure 1—Typical Fan Assembly
actual component appearance may vary
Order No. ___________________________________
Trial Pitch Angle ______________________________
Final Pitch Angle _____________________________
Speed-rpm __________________________________
Contract hp _________________________________
Fan Hub Installation
The following instructions detail the process for installing a Marley
HP7000 Fan on a Marley Geareducer® with a tapered fan (output)
shaft and bolted fan hub retention. Installation on other gear reduction units may be different. Contact your Marley sales representative
for supplemental instructions if required.
1–Remove the retention plate and hardware from the top of the
Geareducer shaft. Thoroughly clean the fan shaft, fan shaft key,
and the fan hub center bore to remove any debris and/or protective
coatings. After cleaning, apply a coat of anti-seize compound to the
top 5″ (130mm) of the fan shaft.
2–Prior to hub installation, fully seat the key in the fan shaft keyway.
The key is a tight t across the width and must never be altered.
3–Raise the fan hub above the fan shaft for installation. Slowly lower
the hub onto the shaft with the keyways properly aligned. Make certain the key does not slide down during installation. Stake the key
in the keyway with a center punch if necessary.
The fan shaft key should be approximately centered in the engaged
portion of the hub when engaged on the shaft. Verify the center hub
is fully seated by visual inspection.
4–The hub retention plate will sit on top of the spool. Discard the
retention bolts that come with the Geareducer. New retention bolts
are provided with the hub cover hardware kit. Torque bolts to 50 ft·lbƒ
(68 N·m).
Figure 2
3