Schematic 6
Support 22
Outlet Connection 24
Hoisting Info 25
Freeze Prevention 26
Water Quality 27
Specifications / Base
Base 28
Thermal Performance 28
Performance Warranty 28
Design Loading 29
Construction 29
Mechanical Equipment 29
Fill, Louvers and Drift Eliminators 31
Hot Water Distribution System 31
Casing and Fan Guard 31
Access 31
Collection Basin 32
Warranty 32
Fan Motor Starter Control Panel 35
Vibration Limit Switch 36
Basin Heater 36
Fan Motor Variable Speed Drive 36
Miscellaneous Options
Equalizer Flume Weir Gates 38
Premium Efficiency Motor 38
Sound Control 39
Page 4
Marley / MD Cooling Tower
/
■ Air Movement Package
High efficiency fan—wide-chord design for maximum efficiency at low fan tip speeds
Eased inlet fan cylinder—ensures full area, low turbulent airflow through the cylinder
Spherical roller bearings are rated at an L10 life of 100,000 hours
TEFC Fan Motor—1.15 service factor, variable torque, and specially insulated for cooling tower duty
The MD Series air movement package including the structural support—guaranteed against failure for a
period of five full years. The motor is warranted separately by the motor manufacturer
4
■ Water Distribution System
Pressurized spray system distributes water evenly over the fill
Low-clog polypropylene nozzles—delivers precise distribution of water over the fill area
Marley MC thermoformed PVC film fill assembled into packs for ease of removal and cleaning
Marley XCEL drift eliminators—limit drift losses to no more than .001% of the design GPM flow rate
■ Structure
Induced-draft, counterflow design may require less plan area than crossflow towers typically use
Series 300 stainless steel, 316 stainless steel or heavy mill galvanized steel construction
Factory assembled—ensures final field installation will be hassle-free
Triple-pass PVC inlet louvers—limits splash-out and
eliminate sunlight from entering the collection basin
Page 5
Marley / MD Cooling Tower
/
5
towers are galvanized steel, factory
MD
designed to serve air conditioning and refrigeration
systems as well as light to medium industrial process
loads on clean water. The Marley MD evolved from a
factory-assembled concept of towers pioneered by
Marley some 75 years ago, and incorporate all of the
design advancements that our customers have found
valuable. MD towers represent the current state of the
art in this cooling tower category.
The specifications portion of this publication not
only relates the language to use in describing an
appropriate MD cooling tower—but also defines why
certain items and features are important enough to
specify with the intention of insisting upon compliance
by all bidders. The left hand column of pages 28
through 39 provides appropriate text for the various
specification paragraphs, whereas the right hand
assembled, counterflow cooling towers,
column comments on the meaning of the subject
matter and explains its value.
Pages 33 through 39 indicate those paragraphs
which will result in the purchase of a basic cooling
tower—one that accomplishes the specified thermal
performance, but which will lack many operation—and
maintenance-enhancing accessories and features
that are usually desired by those persons who are
responsible for the continuing operation of the
system of which the cooling tower is part. It will also
incorporate those standard materials which testing and
experience has proven to provide acceptable longevity
in normal operating conditions.
Pages 33 through 39 provide paragraphs intended to
add those features, components, and materials that
will customize the cooling tower to meet the user‘s
requirements.
Page 6
Marley / MDCooling Tower/Engineering Data : Schematic
H
A
569
140
2578
2731
35
8" INLET MOTOR
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
MD5008 SINGLE CELL
6
Page 7
Marley / MDCooling Tower/Engineering Data : Schematic
165
MD5008 SINGLE CELL
7
Model
note 2
MD5008MAC1L
MD5008MLC1L1635.579
MD5008NAC1L1797. 581
MD5008NLC1L1797. 579
MD5008PAC1L2021181
MD5008PLC1L2021180
MD5008QAC1L2161581
MD5008QLC1L2161580
MD5008MAD1L1805.580
MD5008MLD1L1775.579
MD5008NAD1L1977. 581
MD5008NLD1L1967. 579
MD5008PAD1L2231181
MD5008PLD1L2231180
MD5008QAD1L2391581
MD5008QLD1L2381580
MD5008MAF1L1895.580
MD5008MLF1L1855.579
MD5008NAF1L2077. 581
MD5008NLF1L2067. 579
MD5008PAF1L2341181
MD5008PLF1L2341180
MD5008QAF1L2551581
MD5008QLF1L2571580
Nominal Tons
note 3
Motor
kW
5.580
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
3294218130511702891
3599248631761828936
39042791330219531062
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain
current drawings from your Marley sales representative. All
table data is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 8
Marley / MDCooling Tower/Engineering Data : Schematic
H
INSTALLED
HEIGHT
A
35
MOTOR
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
8" INLET
C
L
569
2578
2371
2794
140
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
MD5008 MULTICELL
8
Page 9
Marley / MDCooling Tower/Engineering Data : Schematic
165
MD5008 MULTICELL
9
Model
note 2
MD5008MAC2L
MD5008MLC2L1655.579
MD5008NAC2L1797. 581
MD5008NLC2L1797. 579
MD5008PAC2L2021181
MD5008PLC2L2021180
MD5008QAC2L2171581
MD5008QLC2L2171580
MD5008MAD2L1805.580
MD5008MLD2L1805.579
MD5008NAD2L1967. 581
MD5008NLD2L1967. 579
MD5008PAD2L2221181
MD5008PLD2L2221180
MD5008QAD2L2391581
MD5008QLD2L2391580
MD5008MAF2L1885.580
MD5008MLF2L1885.579
MD5008NAF2L2057. 581
MD5008NLF2L2057. 579
MD5008PAF2L2341181
MD5008PLF2L2341180
MD5008QAF2L2511581
MD5008QLF2L2511580
Nominal Tons
note 3
Motor
kW
5.580
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
3526241330721723891
3831271831971848957
41363023332319741083
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain
current drawings from your Marley sales representative. All
table data is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia. M connection located on the side of the tower. A 3" M
drain connection is located on the side of the collection basin.
Page 10
Marley / MDCooling Tower/Engineering Data : Schematic
H
A
35
8" INLET
MOTOR
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
569
2578
3651
140
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
MD5010 SINGLE CELL
10
Page 11
Marley / MDCooling Tower/Engineering Data : Schematic
248
MD5010 SINGLE CELL
11
Model
note 2
MD5010PAC1L
MD5010PLC1L2491180
MD5010QAC1L2691581
MD5010QLC1L2701580
MD5010RAC1L28618.581
MD5010RLC1L28918.580
MD5010PAD1L2791181
MD5010PLD1L2801180
MD5010QAD1L3041581
MD5010QLD1L3051580
MD5010RAD1L32518.581
MD5010RLD1L32918.580
MD5010PAF1L2931181
MD5010PLF1L2941180
MD5010QAF1L3171581
MD5010QLF1L3181580
MD5010RAF1L34118.581
MD5010RLF1L34618.580
MD5010SAF1L3602281
MD5010SLF1L3622281
Nominal Tons
note 3
Motor
kW
1181
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
34122299388320791052
37172604404622421190
40212909423424301353
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 12
Marley / MDCooling Tower/Engineering Data : Schematic
H
A
35
8" INLET
MOTOR
C
L
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
569
2578
3651
3715
140
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
MD5010 MULTICELL
12
Page 13
Marley / MDCooling Tower/Engineering Data : Schematic
248
MD5010 MULTICELL
13
Model
note 2
MD5010PAC2L
MD5010PLC2L2491180
MD5010QAC2L2691581
MD5010QLC2L2701580
MD5010RAC2L28618.581
MD5010RLC2L28918.580
MD5010PAD2L2791181
MD5010PLD2L2801180
MD5010QAD2L3041581
MD5010QLD2L3051580
MD5010RAD2L32518.581
MD5010RLD2L32918.580
MD5010PAF2L2931181
MD5010PLF2L2941180
MD5010QAF2L3171581
MD5010QLF2L3181580
MD5010RAF2L34118.581
MD5010RLF2L34618.580
MD5010SAF2L3602281
MD5010SLF2L3622281
Nominal Tons
note 3
Motor
kW
1181
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
36282515390621021052
39322820406922651213
42373124425624531376
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 14
Marley / MDCooling Tower/Engineering Data : Schematic
H
A
3607
3651
35
8" INLET
ACCESS
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
153
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
MD5016 SINGLE CELL
14
Page 15
Marley / MDCooling Tower/Engineering Data : Schematic
317
MD5016 SINGLE CELL
15
Model
note 2
MD5016PAC1L
MD5016PLC1L3201178
MD5016QAC1L3451580
MD5016QLC1L3481579
MD5016RAC1L36918.580
MD5016RLC1L37218.579
MD5016SAC1L3902281
MD5016SLC1L3942280
MD5016PAD1L3501179
MD5016PLD1L3531178
MD5016QAD1L3831580
MD5016QLD1L3841579
MD5016RAD1L41018.580
MD5016RLD1L41218.579
MD5016SAD1L4362281
MD5016SLD1L4372280
MD5016TAD1L4753082
MD5016TLD1L4713080
MD5016PAF1L3681179
MD5016PLF1L3701178
MD5016QAF1L4031580
MD5016QLF1L4011579
MD5016RAF1L43118.580
MD5016RLF1L43118.579
MD5016SAF1L4602281
MD5016SLF1L4592280
MD5016TAF1L5003082
MD5016TLF1L4933080
Nominal Tons
note 3
Motor
kW
1179
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
42392529580532251710
45442834608935081763
48483139632037391977
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 16
Marley / MDCooling Tower/Engineering Data : Schematic
H
A
3607
3651
3715
35
8" INLET
ACCESS
C
L
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
153
MD5016 TWO OR THREE CELL
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
16
Page 17
Marley / MDCooling Tower/Engineering Data : Schematic
317
MD5016 TWO OR THREE CELL
17
Model
note 2
MD5016PAC2L
MD5016PLC2L3201178
MD5016QAC2L3451580
MD5016QLC2L3481579
MD5016RAC2L36918.580
MD5016RLC2L37218.579
MD5016SAC2L3902281
MD5016SLC2L3942280
MD5016PAD2L3501179
MD5016PLD2L3531178
MD5016QAD2L3831580
MD5016QLD2L3841579
MD5016RAD2L41018.580
MD5016RLD2L41218.579
MD5016SAD2L4362281
MD5016SLD2L4372280
MD5016TAD2L4753082
MD5016TLD2L4713080
MD5016PAF2L3681179
MD5016PLF2L3701178
MD5016QAF2L4031580
MD5016QLF2L4011579
MD5016RAF2L43118.580
MD5016RLF2L43118.579
MD5016SAF2L4602281
MD5016SLF2L4592280
MD5016TAF2L5003082
MD5016TLF2L4933080
Nominal Tons
note 3
Motor
kW
1179
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
45472837586032791710
48523142614335631800
51563447637537942032
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 18
Marley / MDCooling Tower/Engineering Data : Schematic
H
A
3607
3651
3715
35
8" INLET
ACCESS
C
L
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
153
MD5016 FOUR OR MORE CELLS
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
18
Page 19
Marley / MDCooling Tower/Engineering Data : Schematic
317
MD5016 FOUR OR MORE CELLS
19
Model
note 2
MD5016PAC4L
MD5016PLC4L3201178
MD5016QAC4L3451580
MD5016QLC4L3481579
MD5016RAC4L36918.580
MD5016RLC4L37218.579
MD5016SAC4L3902281
MD5016SLC4L3942280
MD5016PAD4L3501179
MD5016PLD4L3531178
MD5016QAD4L3831580
MD5016QLD4L3841579
MD5016RAD4L41018.580
MD5016RLD4L41218.579
MD5016SAD4L4362281
MD5016SLD4L4372280
MD5016TAD4L4753082
MD5016TLD4L4713080
MD5016PAF4L3681179
MD5016PLF4L3701178
MD5016QAF4L4031580
MD5016QLF4L4011579
MD5016RAF4L43118.580
MD5016RLF4L43118.579
MD5016SAF4L4602281
MD5016SLF4L4592280
MD5016TAF4L5003082
MD5016TLF4L4933080
Nominal Tons
note 3
Motor
kW
1179
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
48013091593333531710
51063396621736361874
54103701644838682105
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 20
Marley / MDCooling Tower/Engineering Data : Schematic
A
H
7366
7312
3715
35
8" INLET
ACCESS
C
L
C
L
PLAN
SIDE ELEVATIONEND ELEVATION
153
MD5016 FOUR CELL QUAD
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The UPDATE web-based selection software
—available at spxcooling.com—provides
MD model recommendations based on
customer's specific design requirements.
20
Page 21
Marley / MDCooling Tower/Engineering Data : Schematic
317
MD5016 FOUR CELL QUAD
21
Model
note 2
MD5016PAC4B
MD5016PLC4B3201178
MD5016QAC4B3451580
MD5016QLC4B3481579
MD5016RAC4B36918.580
MD5016RLC4B37218.579
MD5016SAC4B3902281
MD5016SLC4B3942280
MD5016PAD4B3501179
MD5016PLD4B3531178
MD5016QAD4B3831580
MD5016QLD4B3841579
MD5016RAD4B41018.580
MD5016RLD4B41218.579
MD5016SAD4B4362281
MD5016SLD4B4372280
MD5016TAD4B4753082
MD5016TLD4B4713080
MD5016PAF4B3681179
MD5016PLF4B3701178
MD5016QAF4B4031580
MD5016QLF4B4011579
MD5016RAF4B43118.580
MD5016RLF4B43118.579
MD5016SAF4B4602281
MD5016SLF4B4592280
MD5016TAF4B5003082
MD5016TLF4B4933080
Nominal Tons
note 3
Motor
kW
1179
dBA
1.5m from air
inlet face
Dimensions
HAWeight/Cell
48013091593333531710
51063396621736361874
54103701644838682105
Design
Operating
Weight
kg
Shipping Weight
kg
Heaviest
Section
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
selection software provides MD model recommendations
based on specific design requirements.
3
/hr per ton. The Marley UPDATE web-based
3 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
dia.
Page 22
Marley / MDCooling Tower/Engineering Data: Support
DEE
C
L
ANCHOR
BOLT
C
L
ANCHOR
BOLT
OVERALL OF BASIN
L
C
C
L
ANCHOR
BOLT
C
L
ANCHOR
BOLT
W OVERALL WIDTH OF BASIN
HOLES FOR
M16 ANCHOR
BOLTS 4 REQD
21
21
TOWER COLLECTION
BASIN
A
NORMAL
GAUGE
21
SUPPORT
BY OTHERS
TOWER
COLLECTION
BASIN
22
Model
MD5008__C
MD5008__D
MD5008__F
MD5010__C
MD5010__D
MD5010__F
MD5016__C
MD5016__D
MD5016__F
VIEW A
SUPPORTING STEEL
SINGLE CELL
WLCDEF
2578273125372629511653072563
2578273125372629511653197586
2578273125372629511653323609
2578365125373550511653906549
2578365125373550511654069568
2578365125373550511654256592
36073651356633971273185860908
36073651356633971273186143951
36073651356633971273186375982
DimensionsDesign
Operating
Weight
per cell
kg
Design
Operating Load
at support beam
kg/m
Page 23
Marley / MDCooling Tower/Engineering Data: Support
DFEE
C
L
ANCHOR
BOLT
C
L
ANCHOR
BOLT
21
21
OVERALL LENGTH OF BASIN
C
L
ANCHOR
BOLT
C
L
ANCHOR
BOLT
C
C
L
ANCHOR
BOLT
C
L
ANCHOR
BOLT
W OVERALL WIDTH OF BASIN
TOWER COLLECTION
BASIN
A
HOLES FOR
M16 ANCHOR
BOLTS 4/CELL
23
SUPPORTING STEEL
MULTICELL
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative for final design.
2 Purchaser to provide tower support complete with holes and
anchor bolts. Do not use studs! Anchor points must be framed
flush and level at top.
3 Design operating weight occurs with collection basin full to
overflow level. Actual operating weight varies with m3/hr and
piping scheme.
4 Tower may be placed on a flat concrete slab. Side outlet and
optional side drain and overflow must be specified.
Page 24
Marley / MD Cooling Tower/Engineering Data : Outlet Connection
the water in a cooling tower can freeze. Marley Technical
Report #H-003 “Operating Cooling Towers in Freezing
Weather” describes how to prevent freezing during
operation. Available at spxcooling.com or ask your Marley
sales representative for a copy.
During shutdown, water collects in the cold water
basin and may freeze solid. You can prevent freezing by
adding heat to the water left in the tower—or, you can
drain the tower and all exposed pipework at shutdown.
Electric Basin Heaters
An automatic basin water heater system is available
consisting of the following components:
With this type of system, water flows from an indoor
tank, through the load system, and back to the tower,
where it is cooled. The cooled water flows by gravity
from the tower to the tank located in a heated space. At
shutdown, all exposed water drains into the tank, where it
is safe from freezing.
The amount of water needed to successfully operate
the system depends on the tower size and GPM and
on the volume of water contained in the piping system
to and from the tower. You must select a tank large
enough to contain those combined volumes—plus a level
sufficient to maintain a flooded suction on your pump.
Control makeup water according to the level where the
tank stabilizes during operation.
Page 27
Marley / MDCooling Tower/Engineering Data: Water Quality
27
The MD cooling tower can be a very effective air
washer. Atmospheric dust able to pass through the
relatively small louver openings will enter the recirculating
water system. Increased concentrations can intensify
systems maintenance by clogging screens and strainers—
and smaller particulates can coat system heat transfer
surfaces. In areas of low flow velocity—such as the
collection basin—sedimentary deposits can provide a
breeding ground for bacteria.
In areas prone to dust and sedimentation, you should
consider installing some means for keeping the collection
basin clean. Typical devices include side stream filters and
a variety of filtration media.
Blowdown
Blowdown or Bleedoff is the continuous removal of
a small portion of the water from the open recirculating
system. Blowdown is used to prevent the dissolved solids
from concentrating to the point where they will form
scale. The amount of blowdown required depends on
the cooling range—the difference between the hot and
cold water temperatures of the closed circuit— and the
composition of the makeup water.
CAUTION
The MD cooling tower must be located at such
distance and direction to avoid the possibility
of contaminated discharge air being drawn into
building fresh air intake ducts. The purchaser should
obtain the services of a Licensed professional
Engineer or Registered Architect to certify that the
location of the cooling tower is in compliance with
applicable air pollution, fire and clean air codes.
Water Treatment
To control the buildup of dissolved solids resulting
from water evaporation, as well as airborne impurities and
biological contaminants including Legionella, an effective
consistent water treatment program is required. Simple
blowdown may be adequate to control corrosion and
scale, but biological contamination can only be controlled
with biocides.
An acceptable water treatment program must be
compatible with the variety of materials incorporated in
a cooling tower—ideally the pH of the recirculating water
should fall between 6.5 and 9.0. Batch feeding of the
chemicals directly into the cooling tower is not a good
practice since localized damage to the cooling tower
is possible. Specific startup instructions and additional
water quality recommendations can be found in the MD Cooling Tower User Manual which accompanies the
cooling tower and also is available at spxcooling.com.
Page 28
Specifications
Specification Value
Marley / MDCooling Tower/Specifications: Base
28
1.0 Base:
1.1 Furnish and install an induced-draft,
counterflow-type, factory assembled,
film fill, industrial duty, cooling tower.
Unitshallconsistof_____cell(s),as
shown on plans. The limiting overall
dimensions of the tower shall be _____
wide, _____ long, and _____ high. Total
operating power of all fans shall not
exceed _____ kW, consisting of_____
@_____kWmotor(s).Towershallbe
Marley Model _____________________.
2.0 Thermal Performance:
2.1 The tower shall be capable of cool-
ing _____ m
°C to _____ °C at a design entering
air wet-bulb temperature of _____ °C.
The thermal performance rating shall
be Certified by the Cooling Technology
Institute. Tower shall comply with all
ASHRAE90.1standards.
3
/hr of water from ____
■ Your specification base establishes the type, configuration, base materi-
al, and physical limitations of the cooling tower to be quoted. During the
planning and layout stages of your project, you will have focused your
attention on a cooling tower selection that fits your space allotment, and
whose power usage is acceptable. Limitations on physical size and total
operating horsepower avoid the introduction of unforeseen operational
and site-related influences. Specifying the number of cells, and the maximum fan hp/cell will work to your advantage.
You are specifying a counterflow tower, which is a type noted—and usually specified—for its economical use of plan area on projects where
the required thermal performance is very difficult. It effectively replaces
most makes of older towers—both forced-draft and induced-draft—without major redesign of the existing site.
■ CTI Certification means that the cooling
tower has been tested under operating conditions and found to perform as
rated by the manufacturer under those
circumstances. It assures the buyer that
the tower is not intentionally or inadvertently undersized by the manufacturer.
3.0 Performance Warranty:
3.1 CTI Certification notwithstanding, the
cooling tower manufacturer shall guarantee that the cooling tower supplied
will meet the specified performance
conditions when the tower is installed
as shown on the plans. If, because of
a suspected thermal performance deficiency, the owner chooses to conduct
an on-site thermal performance test
under the supervision of a qualified,
disinterested third party in accordance
with CTI, ASME or other applicable
standards during the first year of operation; and if the tower fails to perform
within the limits of test tolerance; then
the cooling tower manufacturer will
pay for the cost of the test and will
make such corrections as are appropriate and agreeable to the owner to
compensate for the performance deficiency.
■ However, CTI certification alone is not sufficient to assure you that the
cooling tower will perform satisfactorily in your situation. Certification
is established under relatively controlled conditions, and cooling towers
seldom operate under such ideal circumstances. They are affected by
nearby structures, machinery, enclosures, effluent from other sources,
etc. Responsible and knowledgeable bidders will take such site-specific
effects into consideration in selecting the cooling tower—but the specifier must insist by the written specification that the designer/manufacturer guarantee this “real world” performance. Any reluctance on the
part of the bidder should cause you some concern.
Page 29
Specifications
Specification Value
Marley / MDCooling Tower/Specifications: Base
29
4.0 Design Loading:
4.1 The tower and its components shall be
designed to withstand a wind load of
1.44kPa. The cooling tower shall be designed to withstand shipping and hoisting loads of 2g horizontal or 3g vertical.
Guardrails, where specified shall be
capable of withstanding a 890N concentrated live load in any direction and
shall be designed in accordance with
OSHA guidelines.
5.0 Construction:
5.1 Except where otherwise specified,
all components of the cooling tower
shall be fabricated of heavy-gauge
steel, protected against corrosion by
EN10142:2000 grade Z600 galvanizing. After passivation of the galvanized
steel(8weeksatpH7-8,andcalcium
hardness and alkalinity at 100-300
mg/Leach),thecoolingtowershallbe
capable of withstanding water having a
pH of 6.5 to 9.0; a chloride content up
150 mg/L; and design operating ranges
up to 10°C. The circulating water shall
contain no oil, grease, fatty acids, or
organic solvents.
■ The indicated design values are the minimum allowables under
accepted design standards. They give you assurance that the cooling tower can be shipped, handled, hoisted—and ultimately operated in a normal cooling tower environment. Most MD models will
withstand significantly higher wind and seismic loads. If your geographic location dictates higher wind load or seismic load values,
please make the appropriate changes, after discussion with your
Marley sales representative.
■ In the history of cooling towers, no other coating for carbon steel
has exhibited the success and longevity of galvanization in exposure to the normal cooling tower water quality defined at left. No
paints or electrostatically-applied coatings, however exotic they
may be, can approach galvanization's history of success.
If extended longevity of the cooling tower is required—or unusually
harsh operating conditions are expected—consider specifying stainless steel as either the base construction material, or the material
utilized for specific components of your choice. See Stainless Steel
Options on page 16.
5.2The specifications, as written, are
intended to indicate those materials
that will be capable of withstanding
the above water quality in continuing
service, as well as the loads described
in paragraph 4.1. They are to be regarded as minimum requirements. Where
component materials unique to individual tower designs are not specified,
the manufacturers shall take the above
water quality and load carrying capabilities into account in the selection of
their materials of manufacture.
6.0 Mechanical Equipment:
6.1Fan(s)shallbepropeller-type,incorpo-
rating heavy aluminum alloy blades and
electrogalvanized hubs. Blades shall be
individually adjustable and both stati-
callyanddynamicallybalanced.Fan(s)
➠
■ Propeller-type fans require only half the operating hp of blower-type
fans. However, they should be readily adjustable to permit compensation for jobsite conditions. The fans of one manufacturer require
the purchase of special positioners for each increment of fan blade
pitch. The Marley Power Belt drive system features all-aluminum
bearings. Bearings shall be rated at an
L10 life of 100,000 hours, or greater.
Bothmotorandfansheaves(pulleys)
shall be all cast aluminum to prevent
premature corrosion.
6.2Motor(s)shallbe____kWmaximum,
TEFC, variable torque, inverter duty
and specially insulated for cooling
tower duty. Speed and electrical char-
acteristicsshallbe______RPM,single-
winding, ___ phase, ____ hertz, ____
volts. Motor nameplate power shall
not be exceeded at design operation.
TEAO motors are not acceptable.
6.3The complete mechanical equipment
assembly for each cell shall be supported by a rigid, hot-dip galvanized steel
structural support that resists misalignment between the motor and sheaves
(pulleys).Forbelt-drivetowerswith
motors inside the airstream, motors
shall be mounted on an adjustable base
that swivels outside the access door
for maintenance. For belt-drive towers with motors mounted outside the
airstream, a protective cover shall be
mounted over the motor and sheave to
protect it from the weather and prevent
inadvertent contact. The mechanical
equipment assembly shall be warranted
against any failure caused by defects
in materials and workmanship for no
lessthanve(5)yearsfollowingthe
date of tower shipment. This warranty
shall cover the fan, speed reducer, drive
shaft and couplings, and the mechanical
equipment support. The electric motor
shall carry a manufacturer's warranty of
at least one year. The bearing assem-
bliesandV-beltsshallbewarrantedfor
18 months.
sheaves, power band belts and long-life bearings for dependable service.
TEFC motors offer additional benefits over TEAO motors whose only
source of cooling is the flow of air produced by the cooling tower fan.
This air rate is not always ideal due to motor position, blockage, etc.
TEFC ensures the motor will always be cooled properly.
Unless otherwise specified, motor speed will be 1500 RPM in on standard models. Low noise models will use motor speeds appropriate for
the specific model. If you prefer the operating flexibility of two-speed
operation, please specify two-speed, single-winding motors which
offer full and half speeds for maximum energy savings. Incidentally,
two speed motors are a far better choice than separate “pony” motors
which simply double the problems indicated above and induce parasitic
loads during operation for lower than nameplate efficiency.
The value of a 5 year mechanical equipment warranty speaks for
itself. Except for the motor, virtually all of the mechanical equipment
on a Marley tower is designed and manufactured by SPX Cooling
Technologies. Cooling tower vendors who purchase commercial fans,
gear reducers, driveshafts, etc. may require that you deal directly with
those commercial suppliers for warranty satisfaction.
Page 31
Specifications
Specification Value
Marley / MDCooling Tower/Specifications: Base
31
7.0 Fill, Louvers and Drift Eliminators:
7.1 Fill shall be cross-corrugated,
counterflow film type, thermoformed
from0.40mmthickPVC.Fillshall
be assembled into packs for ease of
removal and cleaning. Fill shall be supported on channel sections supported
from the tower structure and have a
flame spread rating less than 25. Drift
eliminatorsshallbePVCwithaminimum of three changes in air direction,
and shall limit drift losses to no more
than 0.001% of the design water flow
rate.
7.2Air inlet louvers shall be a minimum of
127mmairtravel,triplepassPVCto
prevent water splashout and eliminate
sunlight from entering the collection
basin. For ease of service and long
lifeoflouvers,PVClouversshallbe
enclosed in a removable frame that
attaches to the air inlet without tools.
Louvers with less than three changes
in air direction are unacceptable.
■ Fill modules can be removed for inspection and cleaning in accor-
dance with local anti legioinella guidelines.
Drift rate varies with design water loading and air rate, as well as
drift eliminator depth and number of directional changes. The indicated rate of 0.001% is easily achievable without premium cost. If a
lower rate is required, please discuss with your Marley sales representative.
8.0 Hot Water Distribution System:
8.1 A pressured spray system shall dis-
tribute water evenly over the fill. The
branch arms shall be corrosion resistantPVCwithpolypropylenespraynozzles attached to the branch arms with
a rubber socket connection for ease of
removal and cleaning. To ensure proper
spray system operation, nozzles shall
seat in branch arms without regard for
direction or alignment.
9.0 Casing and Fan Guard:
9.1 The casing shall be heavy gauge
EN10142:2000 grade Z600 galvanized
steel and shall be capable of withstanding the loads described in paragraph 4.1. Casing panels shall encase
the fill on all four sides of the tower.
The top of the fan cylinder shall be
equipped with a conical, non-sagging,
removable fan guard, fabricated of
welded 5/16" and 7 gauge rods, and
hot dip galvanized after fabrication.
■ The combination of PVC piping and polypropylene nozzles is very
resistant to the build-up of scale and slime.
Page 32
Marley / MDCooling Tower/Specifications: Base
32
Specifications
10.0 Access:
10.1 A large rectangular access door shall
be located in the plenum on the motor
side of the tower.
11.0 Cold Water Collection Basin:
11.1 The collection basin shall be heavy-
gauge galvanized steel and shall
include the number and type of suction
connections required to accommodate
the out-flow piping system shown on
the plans. Suction connections shall be
equipped with debris screens. A factory installed, float operated, mechanical make-up valve shall be included.
An overflow and drain connection shall
be provided in each cell of the tower.
The basin floor shall slope toward the
drain to allow complete flush out of
debris and silt which may accumulate. Towers of more than one cell
shall include steel flumes for flow and
equalization between cells.
13.0 Warranty:
Specification Value
■ The MD tower design offers side-suction as standard. Bottom outlets
may be supplied to accommodate a variety of piping schemes. Unless
so specified, the tower you may be asked to approve may only be available with one type of suction connection requiring you to redesign your
piping layout.
The sloping floor and low-level drain is valuable because it provides a
way to achieve flush-out cleanability.
13.1 The MD cooling tower shall be free
from defects in materials and work-
manshipforaperiodofeighteen(18)
months from the date of shipment.
Page 33
Marley / MDCooling Tower /Specifications: Options
33
Specifications
Stainless Steel Options
Stainless Steel Collection Basin:
11.1 Replace paragraph 11.1 with the
following: The collection basin shall
be heavy-gauge Series 300 stainless
steel. Only low-carbon stainless steel
alloys will be accepted in order to
minimize the risk of intergranular corrosion in the weld zones. Basin shall
include the number and type of suction
connections required to accommodate
the out-flow piping system shown on
the plans. Basin suction connections
shall be equipped with debris screens.
A factory installed, float operated,
mechanical make-up valve shall be
included. An overflow and drain connection shall be provided in each cell
of the tower. The basin floor shall slope
toward the drain to allow complete
flush out of debris and silt which may
accumulate.
All Stainless Cooling Tower
Specification Value
■ The cold water basin is the only part of the tower that is subject to
periods of stagnant water, concentrated with treatment chemicals
and customary contaminants. It is also the most expensive and difficult part of any tower to repair or replace. For these reasons, many
customers—particularly those who are replacing older towers—
choose to specify stainless steel cold water basins.
5.1Replace paragraph 5.1 with the
following: Except where other wise
specified, all components of the cooling tower shall be fabricated of heavygauge, series 300 stainless steel. Only
low-carbon stainless steel alloys will be
accepted in order to minimize the risk
of intergranular corrosion in the weld
zones. The tower shall be capable of
withstanding water having a chloride
design operating ranges up to 27.8°C.
The circulating water shall contain no
oil, grease, fatty acids, or organic solvents.
■ For pure resistance to corrosion—coupled with the capability to
meet stringent fire and building codes—there is no substitute for
stainless steel. No paints or electostatically-applied coatings, however exotic they may be, can match stainless steel's ability to withstand adverse operating conditions.
Page 34
Specifications
Marley / MDCooling Tower /Specifications: Options
34
Specification Value
Convenience and Safety Options
Mechanical Access Platform:
10.2 Add the following paragraph in
the Access section: There shall be
a mechanical access platform at the
mechanical access door allowing
access to the mechanical system, drift
eliminators, distribution system and fill.
The platform shall be galvanized steel
bar grating, supported by galvanized
steel framework attached to the tower.
The platform shall be surrounded by
a guardrail, kneerail, and toeboard
designed according to meet local
safety requirements. A ladder shall be
permanently attached to the platform
and to the casing of the tower, rising
from the base of the tower to the top
of the handrail.
Ladder Extension:
10.2 Add the following to the end of paragraph 10.2: Provide a ladder extension
for connection to the foot of the ladder.
This extension shall be long enough to
risefromtheroof(grade)leveltothe
base of the cooling tower. The installing contractor shall be responsible for
cutting the ladder to length; attaching it
to the foot of the cooling tower ladder;
and anchoring it at its base.
■ Periodic inspection and maintenance of a cooling tower distribution sys-
tem is fundamental to preserving maximum cooling system efficiency.
All cooling towers—crossflow or counterflow—are subject to clogging
to varying degrees by waterborne contaminants such as pipe scale and
sediment. Therefore, safe and easy access to these components is of
significant value to the operator.
Access can be provided in a number of ways, including portable ladders or scaffolding, but for maximum safety and convenience, a field
installed Marley access platform with guardrails is available to make
this task as safe and user-friendly as possible. Further, its location on
the side of the tower does not add to the height of the unit, preserving
architectural integrity. It also saves the owner time and money, in that
maintenance personnel may devote their time to inspection rather than
searching for ladders or erection of portable scaffolding.
■ Many cooling towers are installed such that the base of the unit is 60cm
or more above the roof or grade level. This makes it difficult to get up
to the foot of the attached ladder. The ladder extension alleviates this
problem. Marley ladder extensions are available in standard 1.5m and
3.5 lengths.
Ladder Safety Cage:
10.3 Add the following paragraph in the
Access section: A welded aluminum
safety cage shall surround the ladder,
extending from a point approximately
2m above the foot of the ladder to the
top of the handrail.
Page 35
Specifications
Marley / MDCooling Tower /Specifications: Options
35
Specification Value
Control Options
Fan Motor Starter Control Panel:
6.4 Add the following paragraph in
the Mechanical Equipment section: Each cell of the cooling tower
shall be equipped with a UL listed
control system in a IP52 or IP56 outdoor enclosure capable of controlling
single-speed or two-speed motors as
required, and designed specifically for
cooling tower applications. The panel
shall include a main fused disconnect or main circuit breaker with an
external operating handle, lockable in
the off position for safety. Across-theline magnetic starters or solid-state
soft-start starters as required shall
be controlled with a thermostatic or
solid-state temperature controller.
Door mounted selector switches shall
be provided to enable automatic or
manual control and wired to meet local
control voltage. If required, control circuit to be wired out to terminal blocks
for field connection to a remote vibration switch, overload trip alarms and
remote temperature control devices.
The temperature controller shall be
adjustable for the required cold-water
temperature. If a thermostatic controller is used it shall be mounted on the
side of the tower with the temperature
sensing bulb installed in the cold water
basin using a suspension mounting
bracket. If a solid-state temperature
controller is used the controller will be
door mounted on the control panel.
The temperature controller will display
two temperatures, one for outgoing
water and the other for set point.
Water temperature input shall be
obtainedusingathree-wireRTDwith
dry well in the outlet water piping and
wired back to the solid-state temperature controller in the control panel.
■ If it is your opinion that the control system for the cooling tower
be part of the cooling tower manufacturer’s responsibility, we are
in wholehearted agreement with you. Who better to determine the
most efficient mode and manner of a cooling tower’s operation—
and to apply a system most compatible with it—than the designer
and manufacturer of the cooling tower?
Marley variable speed drives are also available for the ultimate in
temperature control, energy management, and mechanical equipment longevity.
Page 36
Specifications
Marley / MDCooling Tower /Specifications: Options
36
Specification Value
Vibration Limit Switch:
6.5Add the following paragraph in the
Mechanical Equipment section: A
single-pole, double-throw vibration limit
switch in a NEMA 4 housing shall be
installed on the mechanical equipment
support for wiring into the fan motor
shutdown circuit. The purpose of this
switch will be to interrupt power to the
motor in the event of excessive vibration. It shall be adjustable for sensitivity, and shall require manual reset.
Basin Heater:
11.2 Add the following paragraph in the
Cold Water Provide an electric immer-
sion heater for each cell of the tower
to prevent freezing of water in the
collection basin during periods of shutdown. The rod type heater is installed
in the side of the cold water basin.
Each heater will include an integral
thermostat, set point nominally 4°C
but adjustable to suit local operating
requirements.
Fan Motor Variable Speed Drive:
■ Unless specified otherwise, a 3171 switch will
be provided. A double-pole, double-throw
model is also available. If purchased in conjunction with the Control System, it is also
factory-wired. The requirement for manual
reset assures that the tower will be visited to
determine the cause of excess vibration.
■ The Marley basin heater components described at left represent our rec-
ommendation for a reliable automatic system for the prevention of basin
freezing. They are normally shipped separately for installation at the jobsite by the installing contractor. When purchased in conjunction with the
enhanced Control System option, however, they are customarily factorymounted and tested.
Submerged in basin water, in which zinc ions are present, copper
immersion heaters must not be used. Insist upon stainless steel.
The ambient air temperature that you insert in the specifications should
be the lowest 1% level of winter temperature prevalent at site.
6.4 Add the following paragraph in
the Mechanical Equipment section
when VFD is used as a stand alone
system:
shall catch a fan spinning in the reverse
direction without tripping. The panel shall
include a main disconnect with short
circuit protection and external operating
handle, lockable in the off position for
safety. The system shall include a solid
state, PI temperature controller to adjust
frequency output of the drive in response
to the tower cold-water temperature.
The temperature of the cold water and
set point shall be displayed on the door
of the control panel. The bypass shall
include a complete magnetic bypass
circuitwithcapabilitytoisolatetheVFD
when in the bypass mode. Transfer to
the bypass mode shall be automatic in
theeventofVFDfailureorforspecic
trip conditions allowing safe transfer
AcompleteULlistedVariable
■ Marley VFD drive systems are designed to combine absolute tempera-
ture control with ideal energy management. The cooling tower user
selects a cold water temperature and the drive system will vary the
fan speed to maintain that temperature. Precise temperature control is
accomplished with far less stress to the mechanical equipment components. The improved energy management provides fast payback.
Page 37
Specifications
Marley / MDCooling Tower /Specifications: Options
37
Specification Value
of utility voltage to the motor. Automatic
bypass with an earth ground condition is
not allowed. The bypass contactor shall be
cycled on and off while operating in bypass,
to maintain the set-point temperature of the
cold water. The drive design shall be operated as a stand- alone system without the
need for a BMS system. Operator controls
shall be mounted on the front of the enclosure and shall consist of start and stop
control,bypass/VFDselectorswitch,Auto/
Manual selector switch, manual speed control, and solid-state temperature controller.
An emergency bypass selector switch internal to the panel allowing the cooling tower
fan motor to be run at full speed shall be
furnished. To prevent heating problems in
the cooling tower fan motor and to assure
propergearboxlubricationtheVFDsystem
shall de energize the motor once 25%
motor speed is reached and cooling is no
longerrequired.TheVFDshallincludede-
icing logic with auto canceling and adjustable time. Speed in De-Ice mode shall not
exceed 50 % motor speed. The cooling
towermanufacturershallsupplyVFDstart-
up assistance. Tower vibration testing
throughout the speed range is required to
identify and lockout any natural frequency
vibration levels which may exceed CTI
guidelines.
6
.4 Add the following paragraph in the
Mechanical Equipment section when
VFD is used with customers Building
Management System:
listedVariableSpeedDrivesystemina
IP10 indoor, IP52 indoor or IP14 outdoor
enclosureshallbeprovided.TheVFDshall
use PWM technology with IGBT switching
andintegratedbypassdesign.VFDoutput
switching shall not cause mechanical issues
withgearboxteethordriveshafts.TheVFD
shall catch a fan spinning in the reverse
direction without tripping. The panel shall
include a main disconnect with short circuit
protection and external operating handle,
lockable in the off position for safety. The
VFDsystemshallreceiveaspeedreference signal from the Building Management
System monitoring the tower cold-water
temperature. The bypass shall include a
complete magnetic bypass circuit and with
capabilitytoisolatetheVFDwheninthe
bypass mode. Transfer to the bypass mode
shallbemanualintheeventofVFDfailure.
Operator controls shall be mounted on the
front of the enclosure and shall consist of
A complete UL
Page 38
Specifications
Marley / MDCooling Tower /Specifications: Options
38
Specification Value
startandstopcontrol,bypass/VFDselection, Auto/Manual selections, manual
speed control. To prevent heating problems in the cooling tower fan motor and
to assure proper gear reducer lubrication
theVFDsystemshalldeenergizethe
motor once 25% motor speed is reached
and cooling is no longer required. The
cooling tower manufacturer shall supply
VFDstart-upassistance.Towervibration
testing throughout the speed range is
required to identify and lockout any natural frequency vibration levels which may
exceed CTI guidelines.
Miscellaneous Options
Equalizer Flume Weir Gates:
11.2 Add the following paragraph under
Cold Water Collection Basin: The
interconnecting flume between cells
shall be equipped with a removable
cover plate to permit the shutdown of
one cell for maintenance purposes, or
to permit independent cell operation.
■ Where it is your intention to be able to operate both cells of the tower
while the flume cover plate is installed, separate outlet connections,
float valves and overflows must be provided for each cell. Likewise, this
would require separate sensors and controls for basin heater systems, if
installed.
Premium Efficiency Motor
6.3Replace paragraph 6.3 with the following: The complete mechanical
equipment assembly for each cell
shall be supported by a rigid, hot-dip
galvanized steel structural support that
resists misalignment between the
motorandsheaves(pulleys).Forbelt-
drive towers with motors inside the
airstream, motors shall be mounted on
an adjustable base that swivels outside
the access door for maintenance. For
belt-drive towers with motors mounted
outside the airstream, a protective
cover shall be mounted over the motor
and sheave to protect it from the
weather and prevent inadvertent contact. The mechanical equipment assembly shall be warranted against any failure caused by defects in materials and
workmanshipfornolessthanve(5)
years following the date of tower shipment. This warranty shall cover the fan,
speed reducer, motor, drive shaft and
couplings, and the mechanical equipment support. The bearing assemblies
andV-beltsshallbewarrantedfor18
months.
■ IEC premium efficiency motor with a five year warranty enhances the
standard five year mechanical equipment warranty of the MD cooling
tower.
Page 39
Specifications
Marley / MDCooling Tower /Specifications: Options
39
Specification Value
Sound Control
1.2 Add the following paragraph under
Base: The cooling tower shall be quiet
operating, and shall produce an overall
level of sound no higher than ____
dBA, measured at the critical location
indicated on the plans.
■ Sound produced by a standard MD tower operating in an unob-
structed environment will meet all but the most restrictive noise
limitations—and will react favorably to natural attenuation. Where
the tower has been sized to operate within an enclosure, the
enclosure itself will have a damping effect on sound. Sound also
declines with distance—by about 5 or 6 dB(A) each time the distance doubles. Where noise at a critical point is likely to exceed an
acceptable limit, you have several options—listed below in ascending order of cost impact:
• In many cases, noise concerns are limited to night time, when
ambient noise levels are lower and neighbors are trying to sleep.
You can usually resolve these situations by using two speed
motors in either full / half speed or full / 2/3 speed configuration,
and operating the fans at reduced speed without cycling “after
hours”. (The natural night time reduction in wet-bulb temperature
makes this a very feasible solution in most areas of the world, but
the need to avoid cycling may cause the cold water temperature to
vary significantly.)
• Variable speed drives automatically minimize the tower's noise
level during periods of reduced load and/or reduced ambient
without sacrificing the system's ability to maintain a constant cold
water temperature. This is a relatively inexpensive solution, and can
pay for itself quickly in reduced energy costs.
• Where noise is a concern at all times (for example, near a hospital), the best solution is to oversize the tower so it can operate
continuously at reduced (2/3 or ½) motor speed even at the highest
design wet-bulb temperature. Typical sound reductions are 7 dB(A)
at 2/3 fan speed or 10 dB(A) at ½ fan speed, but larger reductions
are often possible.
• The most extreme cases may require discharge sound attenuator
sections—however, the static pressure loss imposed by discharge
attenuators may necessitate an increase in tower size. Your Marley
sales representative will be able to help you meet you sound
requirements.
Page 40
GREGORY'S BANK
WORCESTER WR3 8AB
UNITED KINGDOM
44 (0) 1905 720 200
info.uk@spx.com