SMA Energy Meter User Manual

Flashing green: Energy Meter is sending or
EN
receiving data.
Information on Connection and Commis­sioning
The line conductor L1 supplies the Energy Meter with power. At least the line conductor L1 and the neutral conductor must be connected for the Energy Meter to switch on.
DANGER
Danger to life due to electric shock if external disconnect switch is missing
2
Lethal voltages are present in the live com­ponents of the Energy Meter.
• Install an external disconnect switch be­tween the Energy Meter and the grid­connection point. The external discon­nector must be close to the Energy Meter and easily accessible.
Complete Multicast support required
Incomplete Multicast support of individual network components can lead to malfunction of the Energy Meter.
Electrical Connection for Applications < 63 A
The following figure shows a connection exam­ple. For exact connection specifications, contact your electric utility company.
Designation Explanation
L1, L2, L3 Line conductor N Neutral conductor OUT Meter output, load side IN Meter input, grid side
Procedure:
DANGER
Danger to life due to electric shock
Lethal voltages are present in the switch cabinet.
• Disconnect the connection point from voltage sources and make sure it cannot be reconnected.
• Ensure that the conductors to be con­nected to the Energy Meter are free of voltage.
WARNING
Fire hazard
If a fuse is missing or incorrect and a fault oc curs, a fire ma y be caused. Thi s can result in death or serious injury.
•Protect the line conductors of the EnergyMeter with a fuse or a main/ selective circuit breaker, max. 63 A.
1. Mount the Energy Meter on the top-hat rail. Hook the Energy Meter into the top edge of the top-hat rail and press down until it snaps into place.
2. Connect the conductors to the Energy Meter. Observe the permitted connection cross-sec­tion and torque for screw terminals (see Sec­tion "Technical Data"):
• In a three-phase utility grid, connect the
line conductors L1, L2 and L3 and the neutral conductor to the Energy Meter in accordance with the wiring diagram.
• In a single-phase utility grid, connect the
line conductor L1 and the neutral conductor to the EnergyMeter in accordance with the wiring diagram.
Electrical Connection for Applications > 63 A
Additionally required material (not includ­ed in the scope of delivery):
☐ 3 x current transformer ☐ Connection cables for current transformers
Recommendations for the current trans­former
SMA Solar Technology AG recommends cur­rent transformers designed for a secondary current of 5 A. The current transformers should have at least accuracy class 1.
The following figure shows a connection exam­ple. For exact connection specifications, contact your electric utility company.
Designation Explanation
L1, L2, L3 Line conductor N Neutral conductor OUT Meter output, load side IN Meter input, grid side
SMA Energy Meter
Installation Manual
251851.0100
Validity
This document is valid for the SMA Energy Meter* (EMETER-10.GR1) from firmware version 1.02.04.R.
Target Group
Only qualified persons with the following skills are allowed to perform the tasks described in this document:
• Training in the installation and commissioning of electrical devices
• Training in electrical hazards and local safety regulations
• Knowledge of all applicable standards and directives
• Knowledge of and compliance with this doc­ument and all safety precautions
Symbols Used
Symbol Explanation
Indicates a hazardous situ­ation which, if not avoided, will result in death or seri­ous injury
Indicates a hazardous situ­ation which, if not avoided, can result in death or seri­ous injury Indicates a hazardous situ­ation which, if not avoided, can result in minor or mod­erate injury Indicates a situation which, if not avoided, c an r esult in property damage Information that is impor­tant for a specific topic or goal, but is not safety-rele­vant
Indicates a requirement for
meeting a specific goal ☑ Desired result ✖ A problem that might occur
Intended Use
The Energy Meter is a measuring device which detects electrical measured values at the connec­tion point and makes them available via Speed­wire.
The Energy Meter is for private use only. This product is NOT an energy meter for the con­sumption of active power as defined in the EU Di­rective 2004/22/EC (MID). The Energy Meter must not be used for billing purposes. The data collected by the Energy Meter relating to the power generated by your PV system may devi­ate from the data of the main Energy Meter. The Energy Meter must only be connected to the subdistribution of the household on the load side behind the Energy Meter of the electric utility company. For applications > 63 A, current trans­formers must be connected to the Energy Meter.
The Energy Meter is designed for indoor use on­ly.
The Energy Meter is approved for use in all EU member states. Only use the Energy Meter in ac­cordance with the information provided in the en­closed documentation. Any other use can result in personal injury or property damage.
For safety reasons, it is not permitted to modify the product or install components that are not ex­plicitly recommended or distributed by SMA So­lar Technology AG for this product. Any use of the product other than described in the Intended Use section does not qualify as appropriate us­age. It is prohibited to make any modifications that are not approved by SMA.
The enclosed documentation is an integral part of the product and must be read and observed. Keep in a convenient place for future reference.
Supported Products
For information on the supported products, see the product page of the Energy Meter at www.SMA-Solar.com.
Safety Precautions
DANGER
Danger to life due to electric shock
Lethal voltages are present in the live components.
• Only use the Energy Meter in a dry envi­ronment and keep it away from liquids.
• Install the Energy Meter in the switch cabinet only and ensure that the connec­tion areas for the line conductors and the neutral conductor are behind a cov­er or have contact protection.
• Disconnect the Energy Meter from voltage sources before cleaning. The Energy Meter must be cleaned with a dry cloth only.
• Observe the prescribed minimum clear­ance between the network cable and live installation components, or use suit­able insulation.
WARNING
Danger to life due to electric shock
If network cables are laid outdoors, they may be subject to overvoltages, e.g. due to flash of lightning. This can result in death or serious injury.
• Network cables laid outdoors must be suitably protected from overvoltage.
NOTICE
Damage to or destruction of the Energy Meter if connected to ISDN
• Do not connect an ISDN cable to the net­work terminal of the Energy Meter.
Damage to or destruction of the Energy Meter due to inappropriate use
• The Energy Meter must not be operated beyond the values specified in the technical data.
Technical Data
Communication Speedwire Nominal voltage 230 V/400 V AC Frequency 50 Hz/60 Hz ± 5% Self-consumption 2 W Limiting current/line con-
63 A
ductor Connection cross-section
with current transformers
See recommenda­tions of the current transformer manu­facturer
Connection cross-section
10 mm
2
to 25 mm
without current transform­ers
Torque for screw termi-
2 Nm nals Weight 0,30 kg Dimensions (W / H / D) 70 mm x 88 mm x
65 mm Ambient temperature in
− 25°C to +40°C
operation Ambient temperature dur-
− 25°C to +70°C
ing transport/storage Relative air humidity*
5% to 95% Protection class none Degree of protection**
* non-condensing
** in accordance with IEC 60529
IP2X
Scope of Delivery
• 1 x Energy Meter (EMETER-10.GR1)
• 1 x installation manual Contact your distributor if the scope of delivery is incomplete or damaged.
Product Description
A Connection area for line conductors
and neutral conductor B Network terminal (Speedwire) C Reset button D Speedwire LED E Status LED
LED States
Status LED ( ):
Glowing green: Energy Meter is switched on.
Flashing green slowly: Energy Meter starting up.
Flashing green fast: firmware update running.
Glowing or flashing red or orange: an error has occurred. Refer to Section "Trou­bleshooting".
Speedwire LED ( ):
Off: no Speedwire connection established
Glowing green: Speedwire connection es­tablished.
* referred to in this document as Energy Meter EnergyMeter-IA-en-16 | Version 1.6 SMA Solar Technology AG
Procedure:
DANGER
Danger to life due to electric shock
Lethal voltages are present in the subdistri­bution of the household.
• Disconnect the connection point from voltage sources and make sure it cannot be reconnected.
• Ensure that the conductors to be con­nected to the meter are free of voltage.
WARNING
Fire hazard
If a fuse is missing or incorrect and a fault occurs, a fire may be caused. This can result in death or serious injury.
•Protect the line conductors of the Energy Meter with a fuse or a main/se­lective circuit breaker switch, max. 63 A.
1. Connect one current transformer to each line conductor L1, L2 and L3.
2. On each current transformer, connect one connection cable for current measurement to each of the secondary current terminals (k/S1 and l/S2). Observe the permitted con­nection cross-section of the Energy Meter (see Section "Technical Data"):
4. Connect the connection cables for voltage measurement to the Energy Meter. Observe the prescribed torque for screw terminals (see Section "Technical Data"):
5. Connect the connection cables for voltage measurement to the corresponding line con­ductors.
Network Terminal
IGMP protocol from version 2 must be supported
The Energy Meter works with Multicasts. For the correct function of the Energy Meter, all network devices used must support the IGMP protocol, minimum required version 2 (IGMP V2).
Additionally required material (not includ­ed in the scope of delivery):
☐ 1 x network cable
Recommended cable types:
• SF/UTP, S-FTP, S/UTP, SF/FTP, S/FTP, S-STP For further information on cable types, refer to
the Technical Information "SMA Speedwire Fieldbus" at www.SMA-Solar.com.
Procedure:
1. Connect the network cable to the network ter­minal (Speedwire) of the Energy Meter.
2. Connect the other end of the network cable to a router/network switch. SMA products which are to receive measured values must be integrated in the same local network.
Commissioning
1. Cover the Energy Meter with the cover or the contact protection of the subdistribution.
2. Switch the power supply to the subdistribution back on.
☑The LEDs of the EnergyMeter glow during
start-up. If there is only one Energy Meter in the system, the Energy Meter connects automatically to SMA communication products in the same local network. For more information on commissioning, see the user manual of the supported devices.
✖ The LEDs are not glowing or the
Energy Meter is not displayed by the SMA communication products?
• Correct the error (see Section "Trouble-
shooting").
Resetting the Energy Meter to Default Settings
Procedure:
• Press the reset button with a sharp object and hold it for two to six seconds.
Restarting the Energy Meter
Procedure:
• Press the reset button with a sharp object and hold it for six seconds or longer.
Accessing the User Interface
Procedure:
1. Call up the Internet browser and in the ad­dress line enter
http://energymeter“Serial number“.local,
e.g.: http://energymeter7435667356.local Note: The serial number can be found on the
type label of the Energy Meter.
2. Press Enter.
☑ The user interface of the Energy Meter opens. ✖ The user interface does not open?
• Correct the error (see Section "Trouble-
shooting").
Configuring the Current Transformer
Procedure:
1. Open the user interface of the Energy Meter (see Section "Accessing the User Interface")
2. On the homepage, select Device settings > Current Transformer settings.
3. Activate the checkbox Use Current Transformers.
4. Enter the required transformation ratio in the field Current Transformer ratio.
5. Select [Apply].
.
Performing a Firmware Update
Procedure:
1. Download the update file from www.SMA-Solar.com and save it to your computer.
2. Open the user interface of the Energy Meter (see Section "Accessing the User Interface")
3. Follow the instructions in the menu
Firmware update.
Procedure after Replacing an Energy Meter
Procedure:
• If more than one Energy Meter is installed in your system and you have replaced one or more Energy Meters, you will need to adjust the serial number of the corresponding Energy Meter in the Sunny Island/Sunny Boy Smart Energy. This will avoid inaccurate me­ter reading data in the Speedwire data mod­ule Sunny Island/Sunny Boy Smart Energy: – In systems without Sunny Home Manager,
enter the serial number of the Energy Meter via Sunny Explorer in the Sunny Island/Sunny Boy Smart Energy (for information on changing device pa­rameters, see user manual of the Sunny Ex­plorer).
– In systems with Sunny Home Manager,
configure the Energy Meter in Sunny Portal (see user manual of the Sunny Home Manager).
Troubleshooting
The status LEDs are off.
The Energy Meter is not supplied with power.
• Make sure that at least the line conductor L1 and the neutral conductor are connected to the Energy Meter.
The status LEDs are glowing or flashing red or orange.
An error has occurred.
• Restart the Energy Meter (see Section "Re­starting the Energy Meter").
•Contact the SMAServiceLine.
The Speedwire LEDs are not glowing. or The Energy Meter is not displayed by the SMA communication product.
The network cable has not been correctly con­nected to the network terminal.
• Make sure that the network cable is correctly connected to the network terminal.
The Energy Meter is not integrated into the same local network as the SMA communication prod­uct.
• Connect the Energy Meter to the same rout­er/network switch as the SMA communica­tion product.
The Energy Meter provides unrealistic mea­sured values.
The Energy Meter has been installed the wrong way round.
• Connect and commission again.
The user interface cannot be called up via http://energymeter“Serial number“.local.
The name resolution via Avahi (Multicast DNS) is not working.
• Call up the user interface via the current IP ad­dress of the Energy Meter. Call up the user in­terface of the router and read off the IP address of the Energy Meter (see router man­ual).
•With Windows XP/7/8: Install Apple Bonjour www.apple.com. Note: Apple Bonjour also contained in Apple iTunes
®
(download links at
®.
).
®
is
• Contact your network administrator.
Disposal
Procedure:
• Dispose of the Energy Meter in accordance with the locally applicable disposal regula­tions for electronic waste.
Open Source Licenses
The license text and corresponding information is displayed in the user interface of the Energy Meter. You can request the source code with modifications from the SMA Service Line.
Contact
If you have technical problems concerning our products, contact the SMA Service Line. We re­quire the following information in order to pro­vide you with the necessary assistance:
• Type and serial number of the Energy Meter (see type label of the Energy Meter)
• Type and serial number of the SMA products (e.g. Sunny Home Manager, Sunny Explorer, Sunny Island)
•Error description
SMA Solar Technology AG
Niestetal International SMA Service Line
Toll free worldwide: 00800 SMA SERVICE (+800 762 7378423)
www.SMA-Solar.com