Sioux Chief ProCheck Backwater Valves User Manual

Installation Guide
for ProCheck™ Backwater Valves
• Valves can be adapted for shallow­depth or deep-bury installations
• For gravity fl ow applications only
• Do not install vertically
• Made in the USA
Optional Access Sleeve Kit
Be sure valve lid is sealed tightly
Solvent weld pipe
into valve hub
Sch. 40 DWV Pipe
(not supplied)
Solvent weld pipe
into valve hub
Sch. 40 DWV Pipe
(not supplied)
• Valves are to be installed in a level position, and on nominally horizontal lines only.
• Access opening must be at top. Arrows on side must point in direction of fl ow. The slope of the drain line in which the valve is installed must not exceed ¼" per foot.
• When solvent welding joints, be sure that no solvent (glue) enters the valve body.
• If valve is to be installed in the ground or under a concrete oor, it is recommended that an access sleeve be installed to provide access to the valve for inspection/maintenance
• Before using the system, check that the fl apper is able to move freely and that the sealing surface makes clean contact all the way around the opening into the valve body.
• Be sure the fl apper is removed before using mechanical tools to service the drain line.
Install valve
in level position
The following should be used as a guide only. Always consult local plumbing codes for
specifi c requirements regarding backwater valves in your area before installation.
Building 1: A backwater valve would not be required for this building. During a sewer main backup, sewage would exit through the fi rst upstream manhole, since it is lower than the building’s drainage fi xtures.
Building 2: Drainage fi xtures located on the First Floor would not require backwater valves, since they are higher than the fi rst upstream manhole. However, drainage xtures in the basement of this building are below the level of the fi rst upstream manhole and would require a backwater valve on lines serving those fi xtures to prevent backup.
Building 3: Drainage fi xtures in this building are all located below the level of the fi rst upstream manhole. All xtures in this building would require the installation of a backwater valve to prevent backup.
Building
3
Basement
Building
2
Sewer Main
Basement
Building
1
Basement
Sewer Main
First
UPSTREAM
Manhole