AUTOMATIC TRAP PRIMER VALVE
695 SERIES |
PrimePerfect™ |
|
ITEM # SUBMITTED |
|
SPECIFICATION |
|
|
JOB NAME |
|
|
|
LOCATION |
||
Where replenishment of water in floor drain traps is required; trap primer valves |
||||
ENGINEER |
||||
shall be ½" FIP inlet × ½" MIP outlet, automatic trap primer valves which activate |
||||
with a 10 PSIG pressure drop between 30–150 PSIG. Water release shall be |
CONTRACTOR |
|||
factory set. Trap primer valve shall have large port openings and a non- |
PO#________________________ TAG |
|||
corrosive brass finish. Must be UPC/IAPMO listed, and ASSE certified to the |
||||
|
||||
ASSE 1018 standard. |
|
|
|
|
|
|
|
||
WORKING PRESSURE |
|
|
|
|
30–250 PSIG |
|
|
|
|
OPERATING PRESSURE |
|
|
|
|
Activates with a 10 PSIG pressure drop at 30–150 PSIG |
|
|
|
INSTALLATION
Install to a convenient ½"–1½" nominal water line, nearest the trap or traps to be served. Install in the upright, vertical position only. Install at least 5" (127 mm) above the grid of the floor drain or the flood rim of the sink or fixture which the trap serves. Install near plumbing fixtures to insure a full pressure drop of 10 PSI or more. If the trap primer is installed too far upstream in the system, the pressure drop may not be enough for activation. To help prevent sediment buildup, install a vertical loop that rises above the supply line tee. (see figure 1) Flush trap primer branch line prior to installing the trap primer. Install MIP adapter. Thread on trap primer. Install FIP union to bottom. Use PTFE tape sealant on both connections. Do not use pipe dope. Do not solder or braze directly to trap primer or fittings installed in trap primer. Water discharge is factory set—no adjustment is required on normal installations. However, for static pressures over 100 PSI, adjustments may be necessary. First loosen the nipple locknut (10, below), then turn the nipple (19, below) counter-clockwise until the trap primer starts dripping, turn the nipple clockwise ¼-turn, and re-tighten nipple locknut.
DIMENSIONS
Inlet |
½" FIP |
Outlet |
½" MIP |
Diameter |
2¾" |
Length |
5¼" |
COMPONENTS
1:Cap, brass-plated Zamac No. 3
2:Stainless steel screws
3:Diaphragm
4:Valve stem spring
5:Valve stem nut
6:rubber valve disc
7:Valve stem guide
8:Body, brass-plated Zamac No. 3
9:Nipple seat washer
10: Nipple locknut
11:Vacuum breaker
12:Sediment screen
13:Diaphragm stop washer
14:Diaphragm spring retainer
15:Valve stem
16:Diaphragm spring
17:Valve washer
18:Diaphragm adjustment nut
19:Brass nipple
695-01 |
cold water suppl y |
trap primer |
vacuum breaker |
gravity line |
floor drain |
trap |
figure 1 |
1 |
12 |
|
2 |
13 |
|
3 |
||
14 |
||
4 |
||
15 |
||
5 |
16 |
|
6 |
17 |
|
7 |
|
|
8 |
18 |
|
9 |
19 |
|
10 |
||
|
||
11 |
|
|
|
|
|
|
|
|
1018 |
|
|
|
|
|
|
|
|||
Create Item Number |
|
|
|
|
|
|
||
ACCESSORIES |
|
695-01 |
|
|
|
|||
|
|
|
|
|
||||
695 |
-Y52 = wye splitter |
695 |
-D40 = four ¼" male sweat branches |
695 |
-D432F = four ½" FIP branches with two plugs |
|||
695 |
-D20 |
= two ¼" male sweat branches |
695 |
-D432 = two ¼" male sweat branches, |
695 |
-D4325 = two ½" female sweat branches, |
||
695 |
-D30 |
= three ¼" male sweat branches |
|
two spin-closed branches |
|
two spin-closed branches |
||
|
|
|
|
|
|
|||
|
|
|
|
|
||||
|
|
|
Sioux Chief Manufacturing Company | P: 1.800.821.3944 |
| F: 1.800.758.5950 | www.siouxchief.com |
3-14 |