Sioux Chief 672 User Manual

MANIFOLD – ASTM F2159 PEX CRIMP
672 SERIES PowerPEX™ AccuCrimp
SPECIFICATION
Sioux Chief AccuCrimp ASTM F2159 manifolds shall be used in plumbing systems for safe distribution of hot or cold water when used in standard plumbing practices. Manifolds shall be used in new construction or remodel applications, utilized in
AccuCrimp manifolds shall be listed to appropriate standards and include integrally
sealing barbs.
MATERIALS
APPLICATION
For use with hot and cold water distribution systems.
CERTIFICATIONS
cNSF us pw-G, U.P. Code, ASTM F2159, CSA B137.5
HANDLING AND USE (!)
Solvents, glues, lubricants, glycol, pipe dopes, thread oils and paste should not
and direct sunlight (UV exposure). Max Working Temperature: 210 ºF (99 ºC) @ 150 PSI. Constant Working Temperature: 140 ºF (60 ºC) @ 55 PSI. Manifold should not be used in any installation within mechanical systems that may have oil or solvent residue.
ITEM # SUBMITTED _________________________________________
JOB NAME _______________________________________________
LOCATION _______________________________________________
ENGINEER _______________________________________________
CONTR ACTOR ____________________________________________
PO# ________________________ TAG ________________________
INSTALLATION
Check with all local plumbing codes prior to installation.
1. Cut SDR-9 PEX tubing squarely and place ring or sleeve on tube end
2. proper placement over sealing barbs. For V-Sleeve installs, be sure the tubing end is witnessed through the sleeve's sight-slots.
3. Place properly calibrated crimp tool over the ring/sleeve at a 90-degree angle to tubing run and crimp fully. Only crimp once.
4. Use a 'Go/No Go' gauge to assure connection.
5.
Check with all local plumbing codes prior to installation.
Use bend supports and/or proper tube supports at PEX bends to manifold connections
Label the outlet ports with the supplied labels for hot and cold water
• See PEX installation manual online for complete installation instructions
Manifolds with valved branches require access panels and those without
valves do not require access panels